ASHRAE Journal - VAV System Duct Main Design
ASHRAE Journal - VAV System Duct Main Design
ASHRAE Journal - VAV System Duct Main Design
This article was published in ASHRAE Journal, April 2019. Copyright 2019 ASHRAE. Posted at www.ashrae.org. This article may not be
copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit
www.ashrae.org.
Steven T. Taylor
* Theterm “medium pressure” is not strictly defined by ASHRAE or SMACNA but is commonly used to describe ductwork upstream
of VAV boxes. It is typically selected for SMACNA pressure class from 2 in. w.c. to 4 in. w.c. (500 to 1,000 Pa) inclusive with velocities
up to about 4,000 fpm (20 mps). Low pressure systems are typically selected for less than 2 in. pressure (500 Pa) class and less than
2,000 fpm (10 mps) velocity.
† Duct “mains” are defined here as ductwork upstream of the taps to VAV boxes. Toolbox column “VAV Box Duct Design” in the July 2015
ASHRAE Journal addresses sizing of the inlets and outlets to VAV boxes. Branch lines from VAV boxes to outlets are typically sized as
low-pressure ductwork using equal friction method at 0.08 in. w.c. to 0.10 in. w.c. per 100 ft [0.65 to 0.8 Pa/m].
54 A S H R A E J O U R N A L a s h r a e . o r g A P R I L 2 0 19
ThisfileislicensedtoStevenTaylor([email protected]).CopyrightASHRAE2019.
COLUMN ENGINEER’S NOTEBOOK
the static pressure loss due to friction in that section is to use any of these rates. The chapter includes an exam-
offset by the static pressure regain resulting from a re- ple where the friction rate (0.67 in. w.c. per 100 ft [5.5
duction in duct velocity at the beginning of that section. Pa/m]) is determined by the duct size that maximizes
Neither method has a strong rationale for why it the acoustically allowable velocity (3,000 fpm [15 mps]
should be used to size ducts! in the example); this friction rate is used to size all the
Clearly, there is no intrinsic value to having the same downstream ductwork. During my ~40 years designing
rate of pressure loss due to friction in each duct sec- and peer reviewing duct systems, I have never heard of
tion. In the author’s opinion, the EF method offers only anyone using this approach to size ductwork!
this benefit: it is readily understandable and repeat- The SMACNA HVAC Systems Duct Design manual suggests
able. Two engineers given the same desired friction rate starting with friction rates and velocities in the shaded
will design ducts roughly the same size. But there is no area of Figure 1. This is, of course, a huge range so not
way to relate friction rate to life-cycle costs other than very useful advice. The manual does suggest that a fric-
designing for lower friction rates will almost always tion rate of 0.1 in. w.c. per 100 ft (0.8 Pa/m) is a typical EF
result in higher first costs and lower energy costs. design value for low-pressure ducts.
The SR method results in the static pressure at each
tap to be roughly constant, arguably making the system Friction Rate Reduction Method
self-balancing. But true self-balancing is seldom pos- While ASHRAE and SMACNA Handbooks offer little
sible because of duct size limitations‡ and, moreover, concrete advice on sizing medium-pressure VAV duct
having the same static pressure at taps seldom provides mains, the EDR Advanced VAV System Design Guide7 out-
self-balancing in real systems§ since taps very seldom lines a relatively simple duct sizing technique called the
require the same pressure from that point to supply the Friction Rate Reduction Method. The procedure is as
desired airflow through the tap, through the branch follows:
ductwork, through terminal devices, then through the 1. Starting at the fan discharge, choose the larger duct
final air outlet. The SR method is also more difficult to size from among both of the following design limits:
use than EF because iteration is required; it cannot be a. Maximum velocity (to limit noise). Veloc-
readily done by hand. The SR method generally results ity limits are commonly used as a surrogate for
in larger downstream ducts (and lower energy costs) limiting duct noise generated by the airflow itself
than the EF method when starting with the same initial (as opposed to that generated by the fan). In fact,
duct size. research8 has demonstrated that noise created by
Because of the simplicity of the EF method, it is by far airflow in straight ducts is negligible compared to
the most popular method for sizing all types of HVAC other sources, such as noise generated by fans and
systems, including both constant volume and variable by turbulence at fittings. It is possible that a high
volume. But what is the “right” friction rate for each sys- velocity duct system with smooth fittings may make
tem? Chapter 21 states that friction rates typically range less noise than a low velocity system with abrupt fit-
from 0.05 to 0.20 in. w.c. per 100 ft (0.4 to 1.6 Pa/m) for tings. Nevertheless, limiting velocity to limit noise
low-pressure ductwork and has duct size tables for three is a common practice. Chapter 21 recommends the
rates: 0.08, 0.2, and 0.6 in. w.c. per 100 ft (0.65, 1.6, and velocity limits shown in Table 1.** Velocity limits for
5 Pa/m) friction rates. But it offers no advice about when flat-oval duct are not listed but can be estimated
‡ Round duct diameters are typically limited to multiples of 1 in. (25 mm), and to multiples of 2 in. (51 mm) in large diameter ducts (actual
break point varies by manufacturer). While rectangular duct making machines can readily make any duct dimension, standard practice is
to use multiples of 1 in. (25 mm).
§ One example where SR is useful is the design of stair pressurization fan ductwork. These systems are required by most codes for high
rise buildings to protect exit stairs during a fire. Duct sizing need not consider energy use or noise since these fans operate only for fire
emergencies. Hence, initial velocity can be high, e.g., 4,000 fpm (20 mps), which provides sufficient velocity pressure for substantial
regain to occur at taps for supply air grilles. The taps are also usually identical so the benefit of equal static pressure at each tap that
the SR method provides has the benefit of making the system relatively self-balancing. Using the SR method for this application typically
results in the duct remaining the same size down to the last one or two sections.
** Table 12 from Chapter 21 was extracted from A Practical Guide to Noise and Vibration Control for HVAC Systems, 2nd Edition, 2011,
which includes no references to research to support the velocity limits. They were likely created by the authors based on experience. For
this reason, and because turbulence is the driving factor, not speed, they should not be considered hard limits.
A P R I L 2 0 19 a s h r a e . o r g A S H R A E J O U R N A L 55
ThisfileislicensedtoStevenTaylor([email protected]).CopyrightASHRAE2019.
COLUMN ENGINEER’S NOTEBOOK
FIGURE 1 Duct Friction Loss Chart from SMACNA’s HVAC Systems Duct Design, Figure A-1.
USED WITH PERMISSION FROM SMACNA Air Quality cfm at 0.075 lb/ft3
to be between those for rectangular and round but TABLE 1 Recommended Maximum Airflow Velocities to Achieve Specified Acoustic
closer to rectangular due to the flat bottom surface Design Criteria (Table 12 from ASHRAE Handbook—Fundamentals, Chapter 21).
of the flat-oval duct. MAXIMUM AIRFLOW VELOC-
b. Maximum friction rate (to limit fan power). A ITY, FPM
reasonable starting friction rate for VAV systems is NC OR RC RATING IN RECTANGULAR ROUND
0.25 in. to 0.30 in. per 100 ft (2 to 2.5 Pa/m). The ra- DUCT LOCATION ADJOINING OCCUPANCY DUCT DUCT
tionale for this range is shown in the sidebar, Design 1 2 3 4
Friction Rates for VAV Systems, on page 58. In Shaft or Above Solid 45 3,500 5,000
2. At the end of the duct main, choose a minimum Drywall Ceiling
35 2,500 3,500
friction rate, typically 0.10 in. w.c. to 0.15 in. w.c. per 100
ft (0.8 to 1.2 Pa/m) 25 or less 1,500 2,500
3. Decide how many transitions will occur along the Above Suspended 45 2,500 4,500
hydraulically longest duct main (the so-called “index Acoustical Ceiling
35 1,750 3,000
run,” the run with the highest pressure drop that will
25 or less 1,000 2,000
determine the design pressure drop and fan power)
from the fan to the most remote VAV box. Typically, a Duct Within Occupied 45 2,000 3,900
Space
transition should not be made any more frequently than 35 1,450 2,600
every ~20 ft (6 m) since the cost of the transition will
25 or less 950 1,700
generally offset the cost of the sheet metal savings. The
56 A S H R A E J O U R N A L a s h r a e . o r g A P R I L 2 0 19
ThisfileislicensedtoStevenTaylor([email protected]).CopyrightASHRAE2019.
COLUMN ENGINEER’S NOTEBOOK
design is more flexible to accommodate future changes [2.5 less 1.25 = 1.25 Pa/m]) and divide it by the number of
and is more energy efficient with fewer transitions. It is transitions. The result is called the friction rate reduc-
not uncommon to have only three or four major transi- tion factor.
tions along the index run. 5. Size duct along the index run using calculated
4. Take the difference between the maximum friction airflow with diversity†† starting with the maximum
rate as determined in Step 1 (whether determined by the friction rate, then reduce the friction rate at each tran-
friction limit or velocity limit) and the minimum friction sition by the friction rate reduction factor. By design,
rate from Step 2 (e.g., 0.3 less 0.15 = 0.15 in. w.c. per 100 ft the last section will be sized for the minimum friction
†† VAV systems should be sized based on expected loads including diversity. Solar diversity (due to the fact that the sun can only be in
one position at a time) is easily determined with standard load calculation software. Diversity in other load components, such as people,
plug loads, and lighting loads, is a judgment call on the part of the designer, as are the peak design assumptions for these components.
58 A S H R A E J O U R N A L a s h r a e . o r g A P R I L 2 0 19
ThisfileislicensedtoStevenTaylor([email protected]).CopyrightASHRAE2019.
COLUMN ENGINEER’S NOTEBOOK
Conclusions
The ASHRAE Handbooks and SMACNA manuals
offer no specific advice for how to size VAV system duct
mains upstream of VAV box taps. Fortunately, the EDR’s
Advanced VAV System Design Guide describes a relatively
simple procedure, the Friction Rate Reduction Method,
Advertisement formerly in this space. that should provide a reasonable balance between first
costs and energy costs.
References
1. Taylor, S., McGuire M. 2008. “Sizing pipe using life-cycle
costs.” ASHRAE Journal 10.
2. ASHRAE/IES Standard 90.1-2016, Energy Standard for Buildings
Except Low-Rise Residential Buildings.
3. ASHRAE. 2017. Duct Fitting Database, version 6.00.05.
4. SMACNA. 2006. HVAC Systems Duct Design, 4th edition.
5. Rahmeyer, W.J. 2000. “Pressure loss coefficients for close-
coupled pipe ells.” ASHRAE Transactions 108(1):390-406 (ASHRAE
research project RP-1035).
6. Tsal, R.J., M.S. Adler. 1987. “Evaluation of numerical
methods for ductwork and pipeline optimization.” ASHRAE
Transactions 93(1):17-34.
7. EDR. 2009. Advanced Variable Air Volume (VAV) System Design Guide,
Energy Design Resources, California Public Utilities Commission
8. ASHRAE. 1965. ASHRAE Research Project 37, “Noise
Regeneration in Ducts,” Final Report.
60 A S H R A E J O U R N A L a s h r a e . o r g A P R I L 2 0 19
ThisfileislicensedtoStevenTaylor([email protected]).CopyrightASHRAE2019.