User Manual: Hybrid 5.5KW PV Inverter
User Manual: Hybrid 5.5KW PV Inverter
User Manual: Hybrid 5.5KW PV Inverter
Version: 1.0
Table of Contents
1. Introduction ........................................................................ 1
2. Important Safety Warning .................................................... 2
3. Unpacking & Overview......................................................... 4
4. Installation ......................................................................... 5
5. Surge Protection Device Installation ..................................... 6
6. Grid (Utility) Connection ...................................................... 7
7. PV Module (DC) Connection ................................................. 8
8. Battery Connection ............................................................ 11
9. Load (AC Output) Connection ............................................ 12
10. Communication ................................................................. 14
11. Application with Energy Meter ............................................ 15
12. Commissioning .................................................................. 16
13. Initial Setup ...................................................................... 17
14. Operation ......................................................................... 27
15. Charging Management....................................................... 38
16. Maintenance & Cleaning .................................................... 40
17. Trouble Shooting ............................................................... 41
18. Specifications .................................................................... 44
1. Introduction
This hybrid PV inverter can provide power to connected loads by utilizing PV power, utility
power and battery power.
Hybrid inverter
PV module
Distribution Electric grids
Box
Load
Battery
Note: To conform to the EEG standard, every inverter sold to German area is not allowed
to charge battery from Utility. The relevant function is automatically disabled via the software.
1
2. Important Safety Warning
Before using the inverter, please read all instructions and cautionary markings
on the unit and this manual. Store the manual where it can be accessed easily.
This manual is for qualified personnel. The tasks described in this manual may be performed
by qualified personnel only.
General Precaution-
Conventions used:
WARNING! Warnings identify conditions or practices that could result in personal injury;
CAUTION! Caution identify conditions or practices that could result in damage to the unit
or other equipment connected.
WARNING! Before installing and using this inverter, read all instructions and cautionary
markings on the inverter and all appropriate sections of this guide.
WARNING! This inverter is so heavy that it should be lifted by at least two persons.
CAUTION! To avoid fire and electric shock, make sure that existing wiring is in good
condition and that the wire is not undersized. Do not operate the damaged Inverter or
substandard wiring.
2
CAUTION! In high temperature environment, the surface of this inverter could be hot
enough to cause skin burns if accidentally touched. Ensure that this inverter is away from
normal traffic areas.
CAUTION! Use only recommended accessories from installer. Otherwise, disqualified tools
may cause fire, electric shock, or injury to persons.
CAUTION! To reduce risk of fire hazard, do not cover or obstruct the cooling fan.
CAUTION! Do not operate the Inverter if it has undergone a sharp blow, been dropped, or
damaged in any way. If the Inverter is damaged, please call for an RMA (Return Material
Authorization) request.
CAUTION! AC breaker, DC switch and Battery circuit breaker are used as disconnect devices
and these disconnect devices shall be easily accessible.
3
3. Unpacking & Overview
3-1. Packing List
Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. You should receive the following items inside of package:
Mounting
Surge protection device L-type plate Screws Magnets Cables screws
4
4. Installation
4-1. Selecting Mounting Location
Consider the following points to install the inverter:
Do not mount the inverter on flammable construction materials.
Mount on a solid surface
This inverter might make noises during operation which may be perceived as a
nuisance in a living area.
Install this inverter at eye level in order to allow the readability of LCD display at
all times.
For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to
the side and approx. 50 cm above and below the unit.
Dusty conditions on the unit may impair the performance of this inverter.
The ambient temperature should be between 0°C and 40°C and relative humidity
should be between 5% and 85% to ensure optimal operation.
The recommended installation is vertical adherence.
For proper operation of this inverter, please use appropriate cables for grid
connection.
The pollution degree of the inverter is PD2. Select an appropriate mounting
location. Install the solar inverter in a protected area that is dry, free of excessive
dust and with adequate air flow. Do NOT operate it in the place where the
temperature and humidity is beyond the specific limits. (Please check the specs for
the limitations.)
The inverter should be installed in the position where the disconnection means is
easily accessible.
This inverter is designed with IP20 protection for indoor applications only.
Regularly clean the fan filter.
Installation to the wall should be fixed with proper screws. After that, the device should
be bolted on securely.
The inverter can only operate in a CLOSED ELECTRICAL OPERATING AREA. Only service
personnel can enter this area.
5
Fix the unit with four screws.
Magnet x 6 pieces
Step 2: To prevent surge protection device falling apart, use supplied L-type plate and
fix it to attach surge protection device tightly to the inverter.
6
Step 3: Connect the OUTPUT of SPD to AC grid connectors of Hybrid Inverter. The
INPUT of SPD is connected to AC utility.
AC Grid Input
Output of
SPD
Hybrid Inverter
7
WARNING! For safety and efficiency, it's very important to use appropriate cables for
grid (utility) connection. To reduce risk of injury, please use the proper cable size
recommended below.
Suggested cable requirement for AC wire
Model 5.5KW
Nominal Grid Voltage 230VAC
Conductor cross-section (mm2) 6
AWG no. 10
6-2. Connecting to the AC Utility
Step 1: Check the grid voltage and frequency with an AC voltmeter to see if it’s same as
the “VAC” value on the product label.
L
Step 2: Turn off the circuit breaker.
N
Step 3: Remove insulation sleeve 10 mm from three
conductors and shorten phase L and neutral
conductor N for 3 mm. Refer to chart 1. Chart 1
Step 4: Connect wires according to the polarities indicating on terminal block. Be sure
to connect PE protective conductor (G) first.
L→LINE (brown or black)
N→Neutral (blue or white)
G→Ground (yellow-green)
8
WARNING: Because this inverter is non-isolated, only three types of PV modules are
acceptable: single crystalline and poly crystalline with class A-rated and CIGS
modules.
To avoid any malfunction, do not connect any PV modules with possible current
leakage to the inverter. For example, grounded PV modules will cause current leakage
to the inverter. When using CIGS modules, please be sure NO grounding.
CAUTION: It’s requested to use PV junction box with surge protection. Otherwise, it
will cause damage on inverter when lightning occurs on PV modules.
Step 1: Check the input voltage of PV array modules. The acceptable input voltage of
the inverter is 250VDC-450VDC (with rated load). This system is applied with two strings
of PV array. Please make sure that the maximum current load of each PV input
connector is 13A.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the
system before wire connection.
Step 2: Disconnect the circuit breaker and switch off the DC switch.
Step 3: Assemble provided PV connectors with PV modules by the following steps.
Components for PV connectors and Tools:
Female connector housing
Female terminal
Male connector housing
Male terminal
Crimping tool and spanner
Insert striped cable into female terminal and crimp female terminal as shown below.
9
Insert striped cable into male terminal and crimp male terminal as shown below.
Then, use spanner to screw pressure dome tightly to female connector and male
connector as shown below.
Step 4: Check the correctness of the polarity of connection cable on PV modules and PV
input connectors. Then, connect positive pole (+) of connection cable to positive pole (+)
of PV input connector. Connect negative pole (-) of connection cable to negative pole (-)
of PV input connector.
WARNING! For safety and efficiency, it's very important to use appropriate cables for
PV module connection. To reduce risk of injury, please use the proper cable size as
recommended below.
Conductor cross-section (mm2) AWG no.
4~6 10~12
CAUTION: Never directly touch the terminals of inverter. It might cause lethal electric
shock.
10
Recommended Panel Configuration
CAUTION: Do NOT touch the inverter to avoid electric shock. When PV modules are
exposed to sunlight, it may generate DC voltage in the inverter.
8. Battery Connection
CAUTION: Before connecting to batteries, please separately install a DC circuit
breaker between inverter and batteries.
NOTE1: Please only use sealed lead acid battery, vented and Gel battery. Please check
its maximum charging voltage and current when first using this inverter. If using Lithium
iron or Nicd battery, please consult with installer for the details.
NOTE2: Please use 80VDC/200A circuit breaker.
NOTE3: The overvoltage category of the battery input is II.
Please follow the steps below to implement battery connection:
Step 1: Check the nominal voltage of batteries. The nominal
input voltage for inverter is 48VDC.
Step 2: Use two battery cables. Remove insulation sleeve 12
mm and insert conductor into cable ring terminal. Refer to the
right diagram.
Step 3: Remove the cover of battery and follow the polarity of battery printed near the
battery terminal! Place the external battery cable ring terminal over the battery terminal.
RED cable to the positive terminal (+);
BLACK cable to the negative terminal (-).
11
WARNING! Wrong connections may damage the unit permanently.
Step 4: Make sure the wires are securely connected. The reference tightening torque is
2.04 N.m.
WARNING! For safety and efficiency, it's very important to use appropriate cables for
battery connection. To reduce risk of injury, please use the proper cable size
recommended as below.
Conductor cross-section (mm2) 38
AWG no. 2
Step 1: Remove insulation sleeve 8 mm for three conductors. And shorten phase L and
neutral conductor N 3 mm. Refer to Diagram 3.
Step 2: Connect wires according to the polarities L
indicated on terminal block. Be sure to connect PE
N
protective conductor ( ) first. Refer to Diagram 4.
Diagram 3
12
L→LINE (brown or black)
→Ground (yellow-green)
N→Neutral (blue or white)
CAUTION: It’s only allowed to connect load to “AC Output Connector”. Do NOT connect
the utility to “AC Output Connector”.
CAUTION: Be sure to connect L terminal of load to L terminal of “AC Output Connector”
and N terminal of load to N terminal of “AC Output Connector”. The G terminal of “AC
Output Connector” is connected to grounding of the load. Do NOT mis-connect.
CAUTION: This inverter is not allowed to operate in parallel. Please do NOT connect
more than one unit in parallel in AC output connector. Otherwise, it will damage this
inverter.
13
10. Communication
The inverter is equipped with RS232 port, USB port and a slot for alternative
communication interfaces in order to communicate with a PC via corresponding
software. This intelligent slot is suitable to install with SNMP card and Modbus card.
Follow the procedure below to connect communication wiring and install the
software.
For RS232 port, you should use a DB9 cable as below:
For SNMP or MODBUS card, you should use RJ45 cables as below:
14
11. Application with Energy Meter
With Modbus card II and energy meter, hybrid inverter can be easily integrated into the
existing household system. For details please refer to Modbus card II manual.
Note: This application is only valid for Grid-Tie with Backup II mode.
Equipped with Modbus card II, hybrid inverter is connected to energy meter with RS485
communication port. It’s used to set up self-consumption function via Modbus card to
control power generation and battery charging of the inverter.
Grid
L1 L2 L3
N
PV Arry
Modbus card
L
Grid
N
G
Hybrid Inverter
AC Output
G N L
To Main
Family Load
Battery
To Urgent
Load
15
12. Commissioning
Step 1: Check the following requirements before commissioning:
Ensure the inverter is firmly secured
Check if the open circuit DC voltage of PV module meets the requirement (Refer to
Section 6)
Check if the voltage of the open circuit utility is approximately as same as the
expected nominal value from local utility company.
Check if connection of AC cable to grid (utility) is correct if the utility is required.
Fully connect to PV modules.
Check if AC circuit breaker (only applied when the utility is required), batter circuit
breaker, and DC circuit breaker are installed correctly.
Step 2: Switch on the circuit breaker of battery and then switch on PV DC breaker. After
that, if there is any connection with utility, please switch on the AC circuit breaker. At this
moment, the inverter is already turned on. However, there is no output generation from
loads. Then:
If LCD lights up to display the status of current inverter, commissioning has been
completed successfully. After pressing “ON” button for 1 second when the utility is
detected, this inverter will start to supply power to the loads. If no utility exists,
simply press “ON” button for 3 seconds. Then, this inverter will start to supply power
to the loads.
If an error occurs to this inverter, a warning/fault indicator will appear on LCD display.
Please inform your installer.
Step 3: Please insert CD into your computer and install monitoring software on your PC.
Follow the steps below to install the software.
1. Follow the on-screen instructions to install the software.
2. When your computer restarts, the monitoring software will appear as shortcut icon
located in the system tray, near the clock.
NOTE: If using modbus card as communication interface, please install bundled software.
Check local dealer for the details.
16
13. Initial Setup
Before inverter starts to operate, it’s required to set up “Operation Mode” via software.
Please strictly follow the steps below to set up. For more details, please refer to software
manual.
Step 1: After turning on the inverter and installing the software, please click “Open
Monitor” to enter main screen of this software.
Step 2: Log in the software first by entering the default password “administrator.”
Step 3: Select Device Control>>MyPower Management to set up inverter operation mode
and personalized interface. Refer to diagram below.
Mode
There are three operation modes: Grid-tie with backup, Grid-Tie and Off-Grid.
Grid-tie with backup: PV power can feed back to grid, provide power to the load and
charge battery. There are four options available in this mode: Grid-tie with backup I,
II, III and IV. In this mode, users can configure PV power supply priority, charging
source priority and load supply source priority. However, when Grid-tie with backup
IV option is selected in PV energy supply priority, the inverter is only operating
between two working logics based on defined peak time and off-peak time of
electricity. Only peak time and off-peak time of electricity are able to set up to
optimize electricity usage.
Grid-Tie: PV power can only feed back to grid.
Off-Grid: PV power can only provide power to the load and charge battery but can’t
feed back to grid.
SECTION A:
Standard: It will list local grid standard. To make any modification, you’re requested to
have factory password. Please check local dealer only when this standard change is
17
requested.
CAUTION: Wrong setting could cause damage to the unit or not working.
Allow AC charging duration: It’s a period of time to allow AC (grid) to charge battery. When
the duration is set as 0:00-00:00, it means no time limitation for AC to charge battery.
AC output ON/Off Timer: Set up on/off time for AC output of inverter. If setting it as
00:00/00:00, this function is disabled.
Allow to feed-in to the Grid: This option is only valid under Grid-tie and Grid-tie with backup
modes. Users can decide if this inverter can feed-in to the grid.
Allow battery to feed-in to the Grid when PV is available: This option is only valid in Grid-
tie with backup II or Grid-tie with backup III modes.
Allow battery to feed-in to the Grid when PV is unavailable: This option is only valid in all
options of Grid-tie with backup mode.
PV energy supply priority setting: 1st Battery, 2nd Load and 3rd Grid.
PV power will charge battery first, then provide power to the load. If there is any
remaining power left, it will feed-in to the grid.
Battery charging source:
1. PV and Grid (Default)
It’s allowed to charge battery from PV power first. If it’s not sufficient, grid will charge
battery.
2. PV only
It is only allow PV power to charge battery.
3. None
It is not allowed to charge battery no matter it’s from PV power or grid.
Load supply source:
When PV power is available: 1st PV, 2nd Grid, 3rd Battery
If battery is not fully charged, PV power will charge battery first. And remaining PV
19
power will provide power to the load. If it’s not sufficient, grid will provide power to the
load. If grid is not available at the same time, battery power will back up.
PV energy supply priority setting: 1st Load, 2nd Battery and 3rd Grid.
PV power will provide power to the load first. Then, it will charge battery. If there is any
remaining power left, it will feed-in to the grid.
Battery charging source:
1. PV and Grid
It’s allowed to charge battery from PV power first. If it’s not sufficient, grid will charge
battery.
2. PV only
Only PV power is allowed to charge battery.
3. None
It is not allowed to charge battery no matter it’s PV power or grid.
20
Load supply source:
When PV power is available:
1. 1st PV, 2nd Battery, 3rd Grid
PV power will provide power to the load first. If it’s not sufficient, battery will provide
power to the load. When battery is running out power or not available, grid will back up
the load.
2. 1st PV, 2nd Grid, 3rd Battery
PV power will provide power to the load first. If it’s not sufficient, grid will provide power
to the load. If grid is not available at the same time, battery power will back up the load.
PV energy supply priority setting: 1st Load, 2nd Grid and 3rd Battery
PV power will provide power to the load first. If there is more PV power available, it will
feed-in to the grid. If feed-in power reaches the max. feed-in power setting, the
remaining power will charge battery.
NOTE: The max. feed-in grid power setting is available in parameter setting. Please
refer to software manual.
Battery charging source:
1. PV and Grid: It’s allowed to charge battery from PV power first. If it’s not sufficient,
grid will charge battery.
21
2. PV only: PV power is only allowed to charge battery.
3. None: It is not allowed to charge battery no matter it’s PV power or grid.
Load supply source:
When PV power is available:
1. 1st PV, 2nd Battery, 3rd Grid
PV power will provide power to the load first. If it’s not sufficient, battery power will
provide power to the load. When battery power is running out or not available, grid will
back up the load.
2. 1st PV, 2nd Grid, 3rd Battery
PV power will provide power to the load first. If it’s not sufficient, grid will provide power
to the load. If grid is not available at the same time, battery power will back up the load.
Grid-Tie
In this operation mode, PV power only feeds in to the grid. No priority setting is
available.
23
Off-Grid
Off-Grid (I): Default setting for off-grid mode.
24
Battery power will provide power to the load first. If battery power is running out, grid will
back up the load.
NOTE: This option will become ineffective during AC charging time and the priority will
automatically become 1st Grid and 2nd Battery order. Otherwise, it will cause battery
damage.
Off-Grid (II)
Off-Grid (III)
14. Operation
Operation and Display Panel
The operation and display panel, shown in the diagram below, is on the front panel of
the inverter. It includes three indicators, four function keys and a LCD display, indicating
the operating status and input/output power information.
LCD display
LED indicators
Function keys
LED Indicator
LED Indicator Messages
Solid On Output is powered by utility in Line mode.
Green
Flashing Output is powered by battery or PV in battery mode.
Solid On Battery is fully charged.
Yellow Flashing Battery is charging.
Solid On Fault occurs in the inverter.
Red
Flashing Warning condition occurs in the inverter.
Function Keys
Function Key Description
/OFF To exit setting mode
To go to previous selection or decrease value in setting mode
Enter setting mode
To go to next selection or increase value in setting mode
Enter setting mode
/ON To confirm the selection in setting mode or turn on AC output
27
LCD Display Icons
Icon Function
Input source information
Indicates the AC input
Indicates the 1st PV panel input
Indicates the 2nd PV panel input
Left digital display information
Indicate input voltage, input frequency, battery voltage, PV1 voltage,
PV2 voltage, charger current
Middle digital display information
28
Indicates unit connects to the 1st PV panel
Mute operation
Indicates unit alarm is disabled.
LCD Setting
After pressing and holding “ ” or “ ” button for one second, the unit will enter
setting mode. Press “ ” or “ ” button to select setting programs. And then, press
“ ” button to confirm the selection or “ ” button to exit.
*IMPORTANT: It’s requested to enter password in the setting program with *. It will
29
Only Solar
Only charge by Solar energy
None
Charger disabled
30
(*It’s required to enter
password)
230V 240V
(default)
Nominal output freq. *
13 (*It’s required to enter
password) (default)
Backlight on
2C LCD backlight sleep timer Default 60s, Range 0~100s
31
Operating Mode Description
Operating Behaviors LCD display
No output power,
Standby mode
solar or utility charger
(*Charge mode) Only PV available, charged by PV power. *
available
32
Utility power and PV available, feed to grid is
enabled and PV energy is larger and it charges
battery,
1. PV charge battery.
2. Remain energy feed to grid.
No charging.
33
PV and utility power available, PV doesn’t
charge battery.
1. No charging.
2. PV provides power to the load.
3. PV feeds energy to the grid.
34
When utility power is available, the utility icon
will show.
No PV or AC, no charging
Select Displays
The LCD display will be switched in turns by pressing “UP” or “DOWN” key. The selectable
information is switched in order as: input voltage, input frequency, PV voltage, battery
voltage, charging current, output voltage, output frequency, load percentage, load in VA,
load in Watt, and load in Watt. If no button be pressed in 1 min, it will return to default
display.
Selection LCD display
Input voltage and output voltage
35
Battery voltage and output voltage
36
PV2 voltage and PV2 input power
Charging current
Real Date
Real time
37
DSP firmware version
(FW issued date)
Floating charging voltage (default) 54.0 Vdc It is adjustable via software from
50Vac to 62Vdc.
Max. absorption charging voltage It is adjustable via software
56.0 Vdc
(default) from 50Vac to 62Vdc.
Battery overcharge protection 64.0 Vdc
U
setting.
Float Voltage
3 stages:
1st – max. charging voltage Bulk Absorption Floating
increases to 56V;
time
This inverter can connect to following battery types: sealed lead acid battery, vented
battery, gel battery and lithium battery. The detailed installation and maintenance
explanations of the external battery pack are provided in the manual of the manufacturer’s
external battery pack.
38
If using sealed lead acid battery, please set up the max. charging current according to
the formula below:
The maximum charging current = Battery capacity (Ah) x 0.2
For example, if you are using 300 Ah battery, then, maximum charging current is 300 x
0.2=60 (A). Please use at least 50Ah battery because the settable minimum value of
charging current is 10A. If using AGM/Gel or other types of battery, please consult with
installer for the details.
39
16. Maintenance & Cleaning
Check the following points to ensure proper operation of the whole solar system at
regular intervals.
Ensure all connectors of this inverter are cleaned all the time.
Before cleaning the solar panels, be sure to turn off PV DC breakers.
Clean the solar panels during the cool time of the day, whenever it is visibly dirty.
Periodically inspect the system to make sure that all wires and supports are
securely fastened in place.
WARNING: There are no user-replaceable parts inside the inverter. Do not attempt to
service the unit by yourself.
Battery Maintenance
Servicing of batteries should be performed or supervised by personnel with
knowledge about batteries and the required precautions.
Replace the batteries with the same type and number of batteries or battery packs.
The following precautions should be observed when working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source prior to connecting or disconnecting battery
terminals.
f) Determine if battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can result
in electric shock. The likelihood of such shock can be reduced if such grounds are
removed during installation and maintenance (applicable to equipment and remote
battery supplies without a grounded supply circuit).
CAUTION: A battery can present a risk of electric shock and high short-circuit current.
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
40
17. Trouble Shooting
When there is no information displaying in the LCD, please check if PV
module/battery/grid connection is correctly connected.
NOTE: The warning and fault information can be recorded by remote monitoring
software.
17-1. Fault code reference
When a fault occurs, the icon will flash as a reminder. See below for fault codes
for reference.
Situation
Solution
Fault Event
01 DC bus voltage exceeds the upper Disconnect AC circuit breaker first.
threshold Then, disconnect DC circuit breaker.
02 DC bus voltage falls below the lower Until LCD screen completely shuts down,
threshold turn on DC breaker first. It will show “No
03 DC bus voltage soft-start is time-out Utility” in LCD screen. Then, turn on AC
04 Inverter soft-start is time-out breaker. After 300 seconds, the system
05 An Inverter overcurrent event is will automatically connect to the grid.
detected If the error message still remains, please
07 An relay failure event is detected contact your installer.
08 DC component in the output current
exceeds the upper threshold
11 Over-current on PV input is detected
14 Inverter DC component exceeds the
allowable range
16 Leakage current CT failed
06 Over temperature fault The internal temperature is higher than
specified temperature.
Leave inverter to cool down to room
temperature. If the error message still
remains, please contact your installer.
09 PV input voltage exceeds the upper Check if the open circuit voltage of PV
threshold modules is higher than 500VDC.
If PV open circuit voltage is less than
500VDC and the error message remains,
pelase contact your installer.
10 Auxiliary power* failed Turn off the inverter. Then, restart the
*Auxiliary power means switch inverter. If the error message still
power supply. remains, please contact your installer.
12 Leakage current exceeds the The ground voltage is too high.
allowable range Please disconnect AC breaker first and
then DC breaker. Check if grounding is
connected properly after LCD screen
41
completely shuts down.
If grounding is correctly connected, turn
on DC brearker. After it displays “No
Utility” in LCD screen, turn on AC
breaker. After 300 seconds, the system
will automatically connect to the grid.
If the error message still remains, please
contact your installer.
13 PV insulation resistance is too low Check if the impedance between
positive and negative poles to the
ground is greater than 1MΩ.
If the impedance is lower than 1MΩ,
please contact your installer.
15 A difference occurred in the Please disconnect AC breaker first and
readings from the main and then disconnect DC breaker.
secondary controllers After LCD screen is completely off, turn
17 Communication with the main and on DC breaker. Until it shows “No Utility”
secondary controllers is interrupted in LCD display, turn on AC breaker. After
20 Discharge circuit fault 300 seconds, the system will
21 Soft start in battery discharge fails automatically connect to the grid.
If error message remains, please
contact your installer.
22 Charging voltage is too high Check if the connection between battery
and inverter is good. Make sure battery
condition is ok. Then, restart the
inverter. If error message remains,
please contact your installer.
23 Overload fault Remove exessive loads. Be sure the total
power consumption of the connected
loads are less than that of the maximum
which this inverter can support. Then,
restart the inverter.
24 Battery disconnected Check if battery cable is connected
firmly. If error message remains, please
contact your installer.
25 Inverter current is too high for a Remove exessive loads.
long time Then, restart the inverter.
26 Short circuited on inverter output Turn off the inverter.
Disconnect AC circuit breaker first.
Then, disconnect DC circuit breaker and
then disconnect the loads.
Please check if load circuit is ok. After
removing the error, turn on the PV DC
42
breaker and battery breaker.
Turn on the inverter. If error message
remains, please contact your installer.
27 Fan fault Please check if fans are running ok.
If fans are running ok, please shut
down inverter first and then restart it.
If fans stop running or error message
remains after restart the inverter,
please contact your installer.
28 OP Current Sensor fault Shut down the inverter completely.
Restart the inverter to see if it’s ok.
If error message still remains, please
contact your installer.
29 Charger failure Shut down the inverter completely.
Restart the inverter to see if it’s ok.
If error message still remains, please
contact your installer.
30 Version mismatch between Shut down the inverter completely.
controller board and power board Restart the inverter to see if it’s ok.
If error message still remains, please
contact your installer.
31 Reverse connection of input and Shut down the inverter completely.
output wires Check if grid wires are connected to AC
output terminals. If mis-connected, re-
connect it correctly. And turn on the
inverter again. If error message still
remains, please contact your installer.
17-2. Warning Reference Codes
When a warning event occurs, the icon will flash as a reminder. See warning codes
below for reference.
Situation
Solution
Warning Event
02 Restart the unit again.
Internal EEPROM failed If problem still exists, please contact
your installer.
04 Battery low Recharge or replace the battery
07 Overload Try to reduce the applied load
17 Battery open Re-connect the battery
20 Check the ventilation around the unit
Over temperature Try to reduce the load
Check if fans run normally
43
18. Specifications
MODEL 5.5KW
RATED POWER 5500 W
PV INPUT (DC)
Maximum DC Power 6500 W
Nominal DC Voltage 360 VDC
Maximum DC Voltage 500 VDC
Working DC Voltage Range 120 VDC ~ 500 VDC
Start-up Voltage / Initial Feeding Voltage 116 VDC / 150 VDC
MPP Voltage Range 120 VDC ~ 450 VDC
Full Load MPP Voltage Range 250 VDC ~ 450 VDC
Maximum Input Current 2*13 A
GRID OUTPUT (AC)
Nominal Output Voltage 230 VAC
Output Voltage Range 184 - 265 VAC
Output Frequency Range 47.5 ~ 51.5 Hz or 59.3~ 60.5Hz
Max. Output Current 23.9 A
AC INPUT
AC Start-up Voltage 120-140 VAC
Auto Restart Voltage 180 VAC
Acceptable Input Voltage Range 170 - 280 VAC
Nominal Frequency 50 Hz / 60 Hz
AC Input Power 5500VA/5500W
Maximum AC Input Current 40 A
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage 230 VAC Pure sine wave
Output Frequency 50 Hz / 60 Hz (auto sensing)
Output Power 5500VA/5500W
Efficiency (DC to AC) 93%
BATTERY & CHARGER (Lead-acid/Li-ion)
DC Voltage Range 40 – 63 VDC
Nominal DC Voltage 48 VDC
Maximum Battery Discharging Current 150 A
Maximum Charging Current 60 A
GENERAL
PHYSICAL
Dimension, D X W X H (mm) 110 X 450 X 445
Net Weight (kgs) 16
INTERACE
Communication Port RS-232/USB
Intelligent Slot Optional SNMP, Modbus, AS-400
ENVIRONMENT
Humidity 0 ~ 90% RH (No condensing)
Operating Temperature -10 to 40°C
44