Ba 9043
Ba 9043
Ba 9043
According to IEC 255, EN 60 255, VDE 0435 part 303 3-phase For nominal voltage of 3 AC 100/57 to 500/290 V Measures arithmetic mean value Adjustable operate and release value For 3p3w or 3p4w systems BA 9043 optionally with adjustable time delay Closed circuit operation LED indicator for operation and state of contact Insensitive to harmonics Frequency up to 400 Hz Width 45 mm
0,4-0,6U N
Indicators upper LED: (only BA 9043) lower LED: Notes on, when voltage connected on, when output contact activated
tv
tv
In units with time delay the delay is only active at > 0,4 UN. At < 0,4 UN the relay switches without delay. Technical data
Circuit diagram
L1 L2 L3 11 21 L1 N L2 L3 L1 L2 L3 11 21
11 12 14
12 14 22 24 N
21 22 24
L1 L2 L3
11 12 14
12 14 22 24
3/N AC 100/57 V; 230/127 V; 400/230 V 415/240 V; 440/254 V; 500/290 V 50 ... 400 Hz 3 AC 100 V; 230 V; 400 V; 415 V, 440 V; 500 V; 50 ... 400 Hz 1,2 UN continuously 1,1 UN continuously AC 4 VA 50 ... 400 Hz 5% < 0,05 % / K
BA 9043/001, BA 9043/003 AA 9943/001: Max. overload BA 9043: AA 9943: Nominal consumption: Nominal frequency: Frequency range: Temperature influence: Setting ranges Response value: Hysteresis: Setting accuracy: Switching delay t M: Time delay tv:
M7520
M7521
0,85 ... 1,05 U N, infinite variable with upper potentiometer 0,75 ... 0,95 of operate value 10 % see diagram switching delay infinite variable from 0,5 ... 10 sec for BA 9043/002, BA 9043/003 Between 0,4 and 0,6 UN the contacts fall back according to the diagram without additional delay
All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time.
Technical data Output Contacts BA 9043: AA 9943.11: AA 9943.12: Thermal current I th: Switching capacity to AC 15 NO contact: NC contact: Electrical life to AC 15 at 3 A, AC 230 V: Short circuit strength max. fuse rating: Mechanical life: General data Operating mode: Temperature range: Clearance and creepage distances overvoltage category / contamination level: EMC Electrostatic discharge: HF irradiation: Fast transients: Surge voltages between wires for power supply: between wire and ground: HF wire guided: Interference suppression: Degree of protection: Housing: Vibration resistance: Climate resistance: Terminal designation: Wire connection: Continuous operation - 20 ... + 60C
Variants Ordering example for Variants BA 9043 2 changeover contacts 1 changeover contact 2 changeover contacts 6 A; see diagramm Continuous current limit curve /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz Nominal frequency Nominal voltage Variant, if required Type /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz Nominal frequency Nominal voltage Variant, if required Contact Type
AA 9943 .11 3 A / AC 230 V 1 A / AC 230 V 3 x 105 switching cycles 4 A gL EN 60 947-5-1 > 30 x 10 6 switching cycles Accessories AA 9943: K 70-34 EN 60 947-5-1 EN 60 947-5-1 EN 60 947-5-1
Cover
Characteristics
I (A)
contact current
6 5 4 3
4 kV / 2 8 kV (air) 10 V/m 2 kV
Wire fixing: Mounting: Weight BA 9043: AA 9943: Dimensions Width x height x depth BA 9043: AA 9943: Standard type BA 9043 3/N AC 400 / 230 V Article number: for 3p4w systems Nominal voltage U N: Output: Width: Variants AA 9943/001: AA 9943/175: BA 9043/001: BA 9043/002: BA 9043/003:
1 kV EN 61 000-4-5 2 kV EN 61 000-4-5 10 V EN 61 000-4-6 Limit value class B EN 55 011 Housing: IP 40 EN 60 529 Terminals: IP 20 EN 60 529 Thermoplastic with V0 behaviour according to UL subject 94 Amplitude 0,35 mm frequency 10 ... 55 Hz EN 60 068-2-6 20 / 060 / 04 EN 60 068-1 DIN EN 50 005 2 x 2,5 mm 2 solid or 2 x 1,5 mm2 stranded wire with sleeve DIN 46 228-1/-2/-3/-4 Flat terminals with self-lifting clamping piece EN 60 999 DIN rail EN 50 022 310 g 300 g
2 1
-20
M6865_a
20 40 60 ambient temperature
T (C)
Continuous current limit curve A = Devices mounted with 2 cm distance B = Devices mounted without distance
F 2,0 1,8 1,6 1,4 1,2 1,0 0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 t [s]
M6866_a
x off x on
Diagram switching delay 45 x 73 x 132 mm 45 x 77 x 127 mm Switching delay tM: When the voltage changes fast on the measuring input, the arithmetic mean value can only adjust after a short delay. stock item Example: F= U applied U setting F= 240 V 190 V = 1,26
U applied = 190 V U setting = 240 V according to diagram: tMon = approx. 800 ms tMoff = approx. 100 ms
without neutral earth quake proof without neutral with neutral, adjustable time delay tv = 0,5 ... 10 sec without neutral, adjustable time delay tv = 0,5 ... 10 sec
Specification for tender for BA 9043 Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for 3p4w systems Width 45 mm Type BA 9043 Manufactured by E. DOLD & SHNE KG Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for 3p4w systems, adjustable time delay up to 10 s. Width 45 mm Type BA 9043/002 Manufactured by E. DOLD & SHNE KG Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for 3p3w systems Width 45 mm Type BA 9043/001 Manufactured by E. DOLD & SHNE KG Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for 3p3w systems, adjustable time delay up to 10 s. Width 45 mm Type BA 9043/003 Manufactured by E. DOLD & SHNE KG