Polyethylene (PE) Plastic Pipe, Schedules 40 and 80, Based On Outside Diameter
Polyethylene (PE) Plastic Pipe, Schedules 40 and 80, Based On Outside Diameter
Polyethylene (PE) Plastic Pipe, Schedules 40 and 80, Based On Outside Diameter
This standard has been approved for use by agencies of the Department of Defense.
1
D 2447
2S/P 5 ~DO/t! 2 1 (1) sions, or other defects. The pipe shall be as uniform as
commercially practicable in color, opacity, density, and other
where: physical properties.
S 5 hydrostatic design stress, psi (or MPa),
6.2 Dimensions and Tolerances—All dimensions shall be
P 5 pressure rating, pse (or MPa),
DO 5 average outside diameter, in. (or mm), and measured in accordance with Test Method D 2122, using an
t 5 minimum wall thickness, in. (or mm). acceptable length of pipe.
3.2.4 standard thermoplastic pipe materials designation 6.2.1 Outside Diameters—In accordance with Test Method
code—the pipe materials designation code shall consist of the D 2122, classify the pipe as roundable or nonroundable and
abbreviation PE for the type of plastic, followed by the ASTM determine the average outside diameter accordingly. For non-
grade in Arabic numerals and the hydrostatic design stress in roundable pipe the tolerance for out-of-roundness shall apply
units of 100 psi with any decimal figures dropped. Where the only to pipe prior to shipment. The outside diameters and
hydrostatic design stress code contains less than two figures, a tolerances shall be as shown in Table 1.
cipher shall be used before the number. Thus a complete NOTE 2—Five-inch through twelve-inch pipe sizes in Schedule 40 meet
material code consists of two letters and four figures for PE the dimensional requirements of roundable pipe and most polyethylene
plastic pipe materials (see Section 5). pipe materials meet the tensile requirements for roundable pipe.
6.2.2 Wall Thickness—The wall thicknesses and tolerances
4. Pipe Classification
shall be as shown in Table 2.
4.1 General—This specification covers PE pipe made from 6.2.3 Wall Thickness Range—The wall thickness range shall
five PE plastic pipe materials in Schedule 40 and 80 sizes with be within 12 %.
outside diameter controlled. 6.2.4 Thickness of Outer Layer—For pipe produced by
5. Materials simultaneous multiple extrusion, that is, pipe containing two or
more concentric layers, the outer layer shall be at least 0.020
5.1 General—Polyethylene plastics used to make pipe in. (0.51 mm) thick.
meeting the requirements of this specification are categorized 6.3 Bond—For pipe produced by simultaneous multiple
by means of two criteria, namely, (1) short-term strength tests, extrusion, the bond between the layers shall be strong and
and (2) long-term strength tests. uniform. It shall not be possible to separate any two layers with
5.2 Basic Materials—This specification covers PE pipe a probe or point of a knife blade so that the layers separate
made from four PE plastics as defined in Specification D 1248, cleanly at any point.
in which the requirements are based on short-term tests. These 6.4 Carbon Black—The polyethylene pipe extrusion com-
are Grade P14, Grade P23, Grade P24, Grade P33, and Grade pound shall contain at least 2 % carbon black when tested in
P34. The PE plastics can also be described according to the accordance with Test Method D 1603. For pipe produced by
appropriate cell classification in accordance with Specification simultaneous multiple extrusion, this requirement shall apply
D 3350. The 80°C sustained pressure performance require- to the outer layer.
ments of 6.9 are not currently in PE material Specifications
D 1248 or D 3350. To identify the correct pipe test category NOTE 3—There is evidence that indicates that type, particle size, and
(C1 to C7), the PE material base resin density and melt index dispersion quality of the carbon black affects the weatherability of the
pipe. The problem is being investigated and when reliable test methods are
must be obtained from the PE material supplier.
developed, requirements for weatherability, or other suitable requirements
NOTE 1—Committee F-17 has requested that Committee D-20 add the to cover this property, will be included in a revision of this specification.
80°C sustained pressure performance requirements to Specifications
D 1248 and D 3350.
5.3 Hydrostatic Design Stresses—This specification covers
TABLE 1 Outside Diameters and Tolerances for PE Plastic Pipe,
PE pipe made from four PE plastics as defined by hydrostatic Schedules 40 and 80, in. (mm)
design stresses developed on the basis of long-term tests
Nominal Average Tolerance
(appendix). Pipe Outside
For Average For Maximum and
5.4 Compound—The PE plastic extrusion compound shall Size Diameter
Diameter Minimum Diameter
meet the requirements of either Grade P14, Class C; Grade (Out-of-Roundness)
P23, Class C; Grade P24, Class C; Grade P33, Class C; or ⁄
12 0.840(21.34) 60.004(60.10) 60.015(60.38)
Grade P34, Class C material as described in Specification ⁄
34 1.050(26.67) 60.004(60.10) 60.020(60.51)
D 1248 or the comparable cell classification in accordance with 1 1.315(33.40) 60.005(60.13) 60.025(60.64)
11⁄4 1.660(42.16) 60.005(60.13) 60.025(60.64)
Specification D 3350. 11⁄2 1.900(48.26) 60.006(60.15) 60.030(60.76)
5.5 Rework Material—Clean, rework material, generated 2 2.375(60.33) 60.006(60.15) 60.035(60.89)
from the manufacturer’s own pipe production, may be used by 21⁄2 2.875(70.03) 60.007(60.18) 60.035(60.89)
3 3.500(88.90) 60.008(60.20) 60.040(61.02)
the same manufacturer, as long as the pipe produced meets all 31⁄2 4.000(101.60) 60.008(60.20) 60.050(61.27)
the requirements of this specification. 4 4.500(114.30) 60.009(60.23) 60.050(61.27)
5 5.563(141.30) 60.010(60.25) 60.050(61.27)
6 6.625(168.28) 60.011(60.28) 60.050(61.27)
6. Requirements 8 8.625(219.08) 60.015(60.38) 60.075(61.91)
6.1 Workmanship—The pipe shall be homogeneous 10 10.750(273.05) 60.015(60.38) 60.075(61.91)
12 12.750(323.85) 60.015(60.38) 60.075(61.91)
throughout and free from visible cracks, holes, foreign inclu-
2
D 2447
TABLE 2 Wall Thicknesses and Tolerances for PE Plastic Pipe, Schedules 40 and 80, in.(mm)
Nominal Pipe Wall ThicknessA
Size
Schedule 40 Schedule 80
Minimum Tolerance Minimum Tolerance
⁄
12 0.109(2.77) +0.020(+0.51) 0.147(3.73) +0.020(+0.51)
3⁄4 0.113(2.87) +0.020(+0.51) 0.154(3.91) +0.020(+0.51)
1 0.133(3.38) +0.020(+0.51) 0.179(4.55) +0.021(+0.53)
11⁄4 0.140(3.56) +0.020(+0.51) 0.191(4.85) +0.023(+0.58)
11⁄2 0.145(3.68) +0.020(+0.51) 0.200(5.08) +0.024(+0.61)
2 0.154(3.91) +0.020(+0.51) 0.218(5.54) +0.026(+0.66)
21⁄2 0.203(5.16) +0.024(+0.61) 0.276(7.01) +0.033(+0.84)
3 0.216(5.49) +0.026(+0.66) 0.300(7.62) +0.036(+0.91)
31⁄2 0.226(5.74) +0.027(+0.69) 0.318(8.08) +0.038(+0.97)
4 0.237(6.02) +0.028(+0.71) 0.337(8.56) +0.040(+1.02)
5 0.258(6.55) +0.031(+0.79) 0.375(9.53) +0.045(+1.14)
6 0.280(7.11) +0.034(+0.86) 0.432(10.97) +0.052(+1.32)
8 0.322(8.18) +0.039(+0.99) ... ...
10 0.365(9.27) +0.044(+1.12) ... ...
12 0.406(10.31) +0.049(+1.24) ... ...
A
The minimum is the lowest wall thickness of the pipe at any cross section. The maximum permitted wall thickness, at any cross section, is the minimum wall thickness
plus the stated tolerance. All tolerances are on the plus side of the minimum requirement.
6.5 Density—The polyethylene base resin (uncolored PE) in 7.4 Density—Determine the density of the pipe compound
the pipe compound shall have a density in the range from 0.910 in accordance with Test Method D 1505 or D 792, using three
to 0.925 g/cm3 for pipe made from Grade P14 of Specification specimens. Determine the percentage of carbon black by
D 1248, 0.926 to 0.940 g/cm3 for pipe made from Grade P23 weight in accordance with 6.4. Calculate the density of the PE
and Grade P24 of Specification D 1248, 0.941 to 0.965 g/cm3 base resin (uncolored PE) in the pipe compound as follows:
for pipe made from Grade P33 of Specification D 1248, and D R 5 DP 2 0.0044 C (2)
0.941 to 0.965 g/cm3 for pipe made from Grade P34 of
Specification D 1248 when determined in accordance with 7.5. where:
6.6 Sustained Pressure—The pipe shall not fail, balloon, DR 5 density of resin, g/cm3,
burst, or weep as defined in Test Method D 1598, at the test DP 5 density of pipe compound, g/cm3, and
pressures given in Table 3 and Table 4 when tested in C 5 percentage by weight of carbon black.
accordance with 7.5. 7.5 Sustained Pressure Test—Select twelve pipe test speci-
6.7 Burst Pressure—The minimum burst pressure for PE mens at random. Test the specimens individually with water at
plastic pipe shall be as given in Table 5, when determined in two controlled temperatures under the pressures given in Table
accordance with 7.8. 3 and Table 4, each specimen at least ten times the nominal
6.8 Environmental Stress Cracking— There shall be no loss diameter in length, but not less than 10 in. (250 mm) or more
of pressure in the pipe when tested in accordance with 7.7. than 3 ft (1000 mm) between end closures and containing the
6.9 Elevated Temperature Sustained Pressure—The average permanent marking on the pipe. Test six specimens at each
failure time must meet or exceed the specified minimum temperature. Maintain the specimens at the pressures indicated
average failure time in Table 6 for both hoop stresses of a given in Table 3 and Table 4 for the appropriate pipe size and
pipe test category when tested in accordance with 7.7. temperature for a period of 1000 h or to failure, whichever
occurs first. Hold the pressure as closely as possible, but within
7. Test Methods 610 psi (669 kPa) (60.69 bar). Condition the specimens for
7.1 Conditioning—Condition the test specimens at 73.4 6 at least 2 h to within 62°C (63.6°F) of the specified test
3.6°F (23 6 2°C) and 50 6 5 % relative humidity for not less temperature. Except as noted, test in accordance with Test
than 40 h prior to test in accordance with Procedure A of Method D 1598. Failure of the pipe shall be as defined in Test
Practice D 618, for those tests where conditioning is required. Method D 1598.
7.2 Test Conditions—Conduct tests in the standard labora- 7.6 Environmental Stress Cracking Test— Use six randomly
tory atmosphere of 73.4 6 3.6°F (23 6 2°C) and 50 6 5 % selected 10-in. (250-mm) long specimens containing the per-
relative humidity, unless otherwise specified in the test meth- manent marking for this test. Connect one end of each
ods or in this specification. specimen to a 600-psi (4-MPa) (40-bar) pressure gage and the
7.3 Sampling—The selection of the sample or samples of other end to an air or nitrogen supply through a suitable valve.
pipe shall be as agreed upon by the purchaser and the seller. In Subject the specimens to the pressures listed in Table 3 for
case of no prior agreement, any sample selected by the testing 73.4°F (23°C), close the valve, and disconnect in such a
laboratory shall be deemed adequate. manner that the pressure is retained in the specimen. Apply
7.3.1 Test Specimens—Not less than 50 % of the test speci- enough pressure in excess of the listed value to compensate for
mens required for any pressure test shall have at least a part of the pressure lost during disconnection of the pressure source.
the marking in their central sections. The central section is that Test the assembly for leaks by immersion in water. Eliminate
portion of pipe which is at least one pipe diameter away from leaks or substitute nonleaking specimens for those that leak.
an end closure. Take care to dry the test specimen completely after immersion.
3
D 2447
TABLE 3 Sustained Pressure Test Conditions for Water at 23°C (73.4°F) for PE Plastic Pipe, Schedules 40 and 80
Nominal PressureA Required for Test
Pipe Size,
PE2306, PE2305 PE1404
in.
PE2406,
PE3306,
PE3406
Schedule 40 Schedule 80 Schedule 40 Schedule 80 Schedule 40 Schedule 80
MPa
⁄
12 2.69 3.86 2.14 3.03 1.65 2.41
3⁄4 2.21 3.10 1.72 2.48 1.38 1.93
1 2.07 2.90 1.65 2.28 1.24 1.79
11⁄4 1.65 2.34 1.31 1.86 1.03 1.52
11⁄2 1.52 2.14 1.17 1.72 0.97 1.31
2 1.24 1.86 0.97 1.45 0.76 1.10
21⁄2 1.38 1.93 1.10 1.52 0.83 1.24
3 1.17 1.72 0.97 1.38 0.76 1.10
31⁄2 1.10 1.59 0.90 1.24 0.69 0.97
4 1.03 1.45 0.83 1.17 0.62 0.90
5 0.90 1.31 0.69 1.03 0.55 0.83
6 0.83 1.24 0.62 0.97 0.48 0.83
8 0.69 ... 0.55 ... 0.45 ...
10 0.62 ... 0.48 ... 0.38 ...
12 0.59 ... 0.48 ... 0.38 ...
psi
⁄
12 390 560 310 440 240 350
3⁄4 320 450 250 360 200 280
1 300 420 240 330 180 260
11⁄4 240 340 190 270 150 220
11⁄2 220 310 170 250 140 190
2 180 270 140 210 110 160
21⁄2 200 280 160 220 120 180
3 170 250 140 200 110 160
31⁄2 160 230 130 180 100 140
4 150 210 120 170 90 130
5 130 190 100 150 80 120
6 120 180 90 140 70 120
8 100 ... 80 ... 65 ...
10 90 ... 70 ... 55 ...
12 85 ... 70 ... 55 ...
A
The fiber stresses used to derive these test pressures are as follows:
Apply a coating of “Igepal CO-630”8 to the pipe surface with 6 for the given pipe category in accordance with Test Method
a brush. Take care to keep the wetting agent at least 1⁄2 in. (12 D 1598. Use water as the internal test medium. Two of three
mm) away from the clamps used on each end of the pipe. Use specimens must meet or exceed the specified minimum average
fresh reagent for each test and take care to store the reagent in failure time.
closed containers because it is hygroscopic. Keep the coated 7.8 Burst Pressure—The test equipment, procedures and
pipe assembly at room temperature for 3 h and then examine. failure definitions shall be as specified in Test Method D 1599.
There shall be no loss of pressure in at least four of the six In addition, the failure must be ductile.
specimens. Discard specimens that leak at a connection and
retest. Loss of pressure caused by expansion of the pipe shall 8. Retest and Rejection
not be cause for rejection. 8.1 If the results of any test(s) do not meet the requirements
7.7 Elevated Temperature Test—Determine pipe test cat- of this specification, the test(s) may be conducted again in
egory in Table 6 for a given piping material. Base resin melt accordance with an agreement between the purchaser and the
index is determined in accordance with Test Method D 1238 seller. There shall be no agreement to lower the minimum
and base resin density is determined in accordance with Test requirement of the specification by such means as omitting
Method D 1505. Prepare at least three test specimens as in 7.5. tests that are a part of the specifications, substituting or
Test at 176°F (80°C) and the hoop stress (S) specified in Table modifying a test method, or by changing the specification
limits. In retesting the product requirements of this specifica-
8 tion shall be met and the test methods designated in the
This test method is based on the use of “Igepal CO-630,” a trademark for a
nonylphenoxy poly(ethyleneoxy)ethanol, which may be obtained from the GAF specification shall be followed. If, upon retest failure occurs,
Corp., Dyestuff and Chemical Div., 140 W. 51st St., New York, NY 10020. the quantity of product represented by the test(s) does not meet
4
D 2447
TABLE 4 Sustained Test Conditions for Water at 37.8°C (100°F) for PE Plastic Pipe, Schedules 40 and 80
Nominal PressureA Required for Test
Pipe Size,
PE2306, PE2305 PE1404
in.
PE2406,
PE3306,
PE3406
Schedule 40 Schedule 80 Schedule 40 Schedule 80 Schedule 40 Schedule 80
MPa
⁄
12 2.21 3.10 1.72 2.48 1.17 1.65
3⁄4 1.79 2.55 1.38 2.00 0.97 1.38
1 1.65 2.34 1.31 1.86 0.90 1.24
11⁄4 1.38 1.93 1.10 1.52 0.69 1.03
11⁄2 1.24 1.72 0.97 1.38 0.62 0.90
2 1.03 1.52 0.83 1.17 0.55 0.76
21⁄2 1.10 1.59 0.90 1.24 0.59 0.83
3 0.97 1.38 0.76 1.10 0.52 0.69
31⁄2 0.90 1.24 0.69 1.03 0.48 0.69
4 0.83 1.17 0.62 0.97 0.41 0.62
5 0.69 1.10 0.59 0.83 0.38 0.55
6 0.62 1.03 0.52 0.83 0.34 0.55
8 0.55 ... 0.45 ... 0.31 ...
10 0.52 ... 0.41 ... 0.28 ...
12 0.48 ... 0.38 ... 0.28 ...
psi
⁄
12 320 450 250 360 170 240
3⁄4 260 370 200 290 140 200
1 240 340 190 270 130 180
11⁄4 200 280 160 220 100 150
11⁄2 180 250 140 200 90 130
2 150 220 120 170 80 110
21⁄2 160 230 130 180 85 120
3 140 200 110 160 75 100
31⁄2 130 180 100 150 70 100
4 120 170 90 140 60 90
5 100 160 85 120 55 80
6 90 150 75 120 50 80
8 80 ... 65 ... 45 ...
10 75 ... 60 ... 40 ...
12 70 ... 55 ... 40 ...
A
The fiber stresses used to derive these test pressures are as follows:
the requirements of this specification. 9.1.6 Pipe intended for the transport of potable water shall
also include the seal or mark of the laboratory making the
9. Marking evaluation for this purpose, spaced at intervals specified by the
9.1 Marking on the pipe shall include the following, spaced laboratory.
at intervals of not more than 5 ft (1.5 m):
9.1.1 Nominal pipe size (for example, 2 in.). NOTE 4—Manufacturers using the seal or mark of a laboratory must
9.1.2 Type of plastic pipe material in accordance with the obtain prior authorization from the laboratory concerned.
designation code given in 3.5 (for example, PE2305). 9.1.7 Pipe test category in accordance with Table 6.
9.1.3 Schedule size (40 or 80, whichever is applicable) and
the pressure rating in pounds per square inch for water at 10. Quality Assurance
73.4°F (23°C) shown as the number followed by psi (for
example, 100 psi). When the indicated pressure rating is lower 10.1 When the product is marked with this designation,
than that calculated in accordance with 3.2.4(see appendix), D 2447, the manufacturer affirms that the product was manu-
this shall be indicated by placing a star after the pressure rating. factured, inspected, sampled, and tested in accordance with this
9.1.4 This designation “ASTM D 2447” with which the pipe specification and has been found to meet the requirements of
complies. this specification.
9.1.5 Manufacturer’s name (or trademark) and code (Note
1).
5
D 2447
TABLE 5 Burst Pressure Requirements for Water at 73.4°F (23°C) for PE Plastic Pipe, Schedules 40 and 80
Nominal Min Burst PressureA
Pipe Size,
PE2306, PE2305 PE1404
in.
PE2406,
PE3306,
PE3406
Schedule 40 Schedule 80 Schedule 40 Schedule 80 Schedule 40 Schedule 80
MPa
⁄
12 5.17 7.38 4.14 5.86 2.55 3.65
3⁄4 4.14 6.00 3.31 4.76 2.07 2.96
1 3.93 5.45 3.10 4.34 1.93 2.69
11⁄4 3.17 4.48 2.55 3.59 1.59 2.21
11⁄2 2.90 4.07 2.28 3.24 1.38 2.00
2 2.41 3.52 1.93 2.76 1.17 1.72
21⁄2 2.62 3.72 2.07 2.90 1.31 1.79
3 2.28 3.24 1.79 2.55 1.10 1.59
31⁄2 2.07 2.96 1.65 2.34 1.03 1.45
4 1.93 2.83 1.52 2.21 0.97 1.38
5 1.65 2.48 1.31 2.00 0.83 1.24
6 1.52 2.41 1.17 1.93 0.76 1.17
8 1.38 ... 1.03 ... 0.69 ...
10 1.24 ... 0.97 ... 0.62 ...
12 1.17 ... 0.90 ... 0.55 ...
psi
⁄
12 750 1070 600 850 370 530
3⁄4 600 870 480 690 300 430
1 570 790 450 630 280 390
11⁄4 460 650 370 520 230 320
11⁄2 420 590 330 470 200 290
2 350 510 280 400 170 250
21⁄2 380 540 300 420 190 260
3 330 470 260 370 160 230
31⁄2 300 430 240 340 150 210
4 280 410 220 320 140 200
5 240 360 190 290 120 180
6 220 350 170 280 110 170
8 200 ... 150 ... 100 ...
10 180 ... 140 ... 90 ...
12 170 ... 130 ... 80 ...
A
The fiber stresses used to derive these test pressures are as follows:
6
D 2447
TABLE 6 176°F (80°C) Sustained Pressure Requirements for Water PipeA,B
Pipe Test Base Resin Melt Index, Base Resin Density,D Minimum Average Hours to Failure
CategoryC D 1238 (g/10 min) D 1505 (g/cm3)
S 5 725 psi S 5 580 psi S 5 435 psi
(5 MPa) (4 MPa) (3 MPa)
C1 <0.05 0.941–0.948 100 200 —
C2 <0.05 0.935–0.940 100 200 —
C3 0.05–0.25 0.941–0.948 60 150 —
C4 0.05–0.25 0.935–0.940 60 150 —
C5 >0.25 0.941–0.948 45 100 —
C6 >0.25 0.935–0.940 45 100 —
C7 >0.50 0.926–0.940 — 80 150
A
For inside diameter controlled pipe, calculate internal pressure in accordance with the following formula:
2S
P5 D
i
t 11
B
For outside diameter controlled pipe, calculate internal pressure in accordance with the following formula:
2S
P5 D
o
t 21
where:
P 5 pressure, psig (MPa),
S 5 hoop stress, psi (MPa),
Di 5 average inside diameter, in. (mm),
Do 5 average outside diameter, in. (mm), and
t 5 minimum wall thickness, in. (mm).
C
Supplier to determine pipe test category appropriate for his product.
D
Pipe categories for water pipe with resin density below 0.926 g/cm3 or above 0.948 g/cm 3
will be added to this table when the data are available.
SUPPLEMENTARY REQUIREMENTS
This requirement applies whenever a Regulatory Authority or user calls for the product to be used
to convey or to be in contact with potable water.
S1. Potable Water Requirement NSF Standard 61 or the health effects portion of NSF Standard
S1.1 Products intended for contact with potable water shall 14 by an acceptable certifying organization when required by
be evaluated, tested, and certified for conformance with ANSI/ the regulatory authority having jurisdiction.
APPENDIX
(Nonmandatory Information)
X1.1 The hydrostatic design stresses recommended by the psi (3.45 MPa) (34.5 bar) for water at 73.4°F (23°C), desig-
Plastics Pipe Institute are used to pressure rate PE plastic pipe. nated as PE2305.
These hydrostatic design stresses are 400 psi (2.76 MPa) (27.6 X1.2.3 Grade P23, with a hydrostatic design stress of 630
bar), 500 psi (3.45 MPa) (34.5 bar), and 630 psi (4.34 MPa) psi (4.34 MPa) (43.4 bar) for water at 73.4°F (23°C), desig-
(43.4 bar) for water at 73.4°F (23°C). These hydrostatic design nated as PE2306.
stresses apply only to pipe meeting all the requirements of this X1.2.4 Grade P24, with a hydrostatic design stress of 630
specification. psi (4.34 MPa) (43.4 bar) for water at 73°F (23°C), designated
as PE2406.
X1.2 Six PE materials are included, based on the require- X1.2.5 Grade P33, with a hydrostatic sign stress of 630 psi
ments of Specification D 1248 and the PPI-recommended (4.34 MPa) (43.4 bar) for water at 73.4°F (23°C), designated as
hydrostatic design stresses as follows: PE3306.
X1.2.6 Grade P34, with a hydrostatic design stress of 630
X1.2.1 Grade P 14 with a hydrostatic design stress of 400 psi (4.34 MPa) (43.4 bar) for water at 73.4°F (23°C), desig-
psi (2.76 MPa) (27.6 bar) for water at 73.4°F (23°C), desig- nated as PE3406.
nated as PE1404.
X1.2.2 Grade P23, with a hydrostatic design stress of 500 X1.3 Information regarding the test method and other
7
D 2447
criteria used in developing these hydrostatic design stresses may be recommended, at the option of the pipe manufacturer,
may be obtained from the Plastics Pipe Institute, a division of in which case a star placed after the pressure rating shall be
The Society of the Plastics Industry, 355 Lexington Ave., New included in the marking. Experience of the industry indicates
York, NY 10017 (Note X1.1). These hydrostatic design stresses that PE plastic pipe meeting the requirements of this specifi-
may not be suitable for materials that show a wide departure cation gives satisfactory service under normal conditions for a
from a straight line plot of log stress versus log time to failure. long period at these pressure ratings. The sustained pressure
All the data available to date on PE pipe materials made in requirements (see 6.6) are related to these ratings through the
North America exhibit a straight-line plot under these plotting slopes of the strength-time plots of these materials in pipe
conditions. form.
NOTE X1.1—Refer also to Test Method D 2837.
X1.5 The hydrostatic design stresses recommended by the
X1.4 The pipe is rated for use with water at 73.4°F (23°C) Plastics Pipe Institute are based on tests made on pipe ranging
at the maximum internal pressures shown in Table X1.1. Lower in size from 1⁄2 to 2 in.
pressure ratings than those calculated in accordance with 3.2.3
TABLE X1.1 Water Pressure Ratings at 73.4°F (23°C) for PE Plastic Pipe, Schedules 40 and 80
Nominal Pipe Pressure RatingA
Size, in.
PE2306, PE2305B PE1404B
PE2406,
PE3306,
PE3406
Schedule 40 Schedule 80 Schedule 40 Schedule 80 Schedule 40 Schedule 80
MPa (bar)
⁄
12 1.30(13.0) 1.84(18.4) 1.03(10.3) 1.46(14.6) 0.82(8.2) 1.17(11.7)
⁄
34 1.05(10.5) 1.49(14.9) 0.83(8.3) 1.19(11.9) 0.66(6.6) 0.94(9.4)
1 0.98(9.8) 1.37(13.7) 0.78(7.8) 1.09(10.9) 0.62(6.2) 0.87(8.7)
11⁄4 0.80(8.0) 1.13(11.3) 0.63(6.3) 0.90(9.0) 0.51(5.1) 0.72(7.2)
11⁄2 0.72(7.2) 1.02(10.2) 0.57(5.7) 0.81(8.1) 0.45(4.5) 0.65(6.5)
2 0.60(6.0) 0.88(8.8) 0.48(4.8) 0.70(7.0) 0.38(3.8) 0.56(5.6)
21⁄2 0.66(6.6) 0.92(9.2) 0.52(5.2) 0.73(7.3) 0.42(4.2) 0.59(5.9)
3 0.57(5.7) 0.81(8.1) 0.45(4.5) 0.65(6.5) 0.37(3.7) 0.52(5.2)
31⁄2 0.52(5.2) 0.75(7.5) 0.41(4.1) 0.59(5.9) 0.34(3.4) 0.48(4.8)
4 0.48(4.8) 0.70(7.0) 0.38(3.8) 0.56(5.6) NPR 0.45(4.5)
5 0.42(4.2) 0.63(6.3) 0.34(3.4) 0.49(4.9) NPR 0.40(4.0)
6 0.38(3.8) 0.61(6.1) NPR 0.48(4.8) NPR 0.39(3.9)
8 0.34(3.4) ... NPR ... NPR ...
10 NPRC ... NPR ... NPR ...
12 NPR ... NPR ... NPR ...
psi
⁄
12 188 267 149 212 119 170
3⁄4 152 217 120 172 96 137
1 142 199 113 158 90 126
11⁄4 116 164 92 130 74 104
11⁄2 104 148 83 118 66 94
2 87 127 69 101 55 81
21⁄2 96 134 76 106 61 85
3 83 118 66 94 53 75
31⁄2 75 109 60 86 50 69
4 70 102 55 81 NPR 65
5 61 91 50 72 NPR 58
6 55 88 NPR 70 NPR 56
8 50 ... NPR ... NPR ...
10 NPRC ... NPR ... NPR ...
12 NPR ... NPR ... NPR ...
A
These pressure ratings apply only to unthreaded pipe. The industry does not recommend threading PE plastic pipe.
B
See 5.2 and appendix for code designation.
C
NPR 5 not pressure rated. The industry does not recommend pressure ratings less than 50 psi (0.34 MPa)(3.4 bar).
8
D 2447
The American Society for Testing and Materials takes no position respecting the validity of any patent rights asserted in connection
with any item mentioned in this standard. Users of this standard are expressly advised that determination of the validity of any such
patent rights, and the risk of infringement of such rights, are entirely their own responsibility.
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM Headquarters. Your comments will receive careful consideration at a meeting of the responsible
technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should make your
views known to the ASTM Committee on Standards, 100 Barr Harbor Drive, West Conshohocken, PA 19428.