Firmware v7.74, Software v8.15 Release Notes: Grid Solutions
Firmware v7.74, Software v8.15 Release Notes: Grid Solutions
Grid Solutions
Summary
GE Grid Solutions issues the Multilin 650 Family Firmware version 7.74 and EnerVista 650 Setup software
8.15. The firmware is specific to some 650 Family products and does not affect other devices.
The 7.74 firmware and 8.15 software version release for the 650 platform introduces software and
firmware improvements that only affect C650 and F650 devices. When using firmware version 7.74,
EnerVista 650 setup 8.15 or above must be used.
This document contains the release note for firmware version 7.74 for the Multilin 650 Family of products.
• Affected products: C650 & F650
• Firmware Release Date: June 3rd, 2021
• EnerVista Setup Release Date: June 3rd, 2021
For existing 650 devices installed with firmware version below 7.0x, you must obtain a new relay to
benefit from the enhancements described in this release note. If the new features and
enhancements are not needed, no upgrade of the relays is required.
Please contact your local Multilin sales representative or Multilin Customer Service Department
(CST) for any questions regarding this upgrade.
D Fixed issue when detecting the breaker status in C650 models without Enhanced Control functionality
option
Changes in dependency algorithm for C650 models that are not incorporating Magnetic Module
HW, that was causing breaker detection element not being executed.
Firmware Compatibility
The 7.74 firmware is not compatible with firmware versions below 7.0x, or with any previous F650 CPU
hardware, i.e. F650 whose order code contains Rear Ethernet Communication Board option B, C, D or E.
Existing B, C, D and E options still benefit from the previous CPU hardware. The released firmware version
runs only on the new models with Rear Ethernet Communication Board options: G, H, J, K, L & M. The 7.74
firmware requires EnerVista 650 Setup software version 8.15 or higher. GE suggests using the latest
version of the software.
Upgrading 650 devices installed with firmware versions below 7.0x requires replacement of the complete
relay. New relays require choosing from the new [G, H, J, K, L or M] characters in the order code under the
“Rear Ethernet Communication Board 2” option.
EnerVista 650 Setup software can convert settings files from an older version to the latest version. It also
provides a tool to compare settings files from different versions, generating a Difference Report. This
Difference Report identifies new settings and additional information to assist the user during the upgrade
process.
Software Compatibility
The minimum operative system requirements for the EnerVista 650 Setup software are as follows:
• Windows® XP with Service Pack 2 (Service Pack 3 recommended)
• Windows 7
• Windows 8
Change categories
This document uses the following categories to classify the changes.
R Changed, incomplete or false Changes to, or problems with relay records (oscillography,
relay records demand, fault reports, etc.)
P Protection out of specification Protection operates correctly but does not meet published
specifications (example: delayed trip)