Model: Avr - 102: Micro Controller Based Automatic Voltage Regulating Relay

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 2

NEW GENERATION

MICRO CONTROLLER BASED BANGALORE

AUTOMATIC VOLTAGE REGULATING RELAY


MODEL : AVR - 102

The make Automatic Voltage Regulating Relay Model AVR - 102 serves for the
Automatic Regulating Transformers equipped with on-load-Tap changer. The user
friendly Soft Key Programming enables precise setting of NVA, Band width, Initial time
delay, control pulse ON / OFF duration, under / over voltage Trip & Restoration levels
and control failure time delay settings. As a safety precaution, the upper and lower end of
aforesaid parameters are freezed, so that even by oversight an abnormal / unrealistic
value cannot be programmed into the Regulating system.

The AVR - 102 has been designed around a powerful single chip micro controller thereby
reducing the component count and enhancing the reliability factor. Since the voltage
levels and time delay settings are digitally computed, the regulating relay operates to the
set parameter precisely without any hysteresis.

Provision of surge protecting devices and RF / EMI filters ensures trouble free operation
even in highly electrified terrains. AVR - 102 comes with a powder coated metal enclosure
and elegantly printed anodized aluminium facia with acrylic cover.
TECHNICAL DATA
SETTING RANGES
Voltage level (NVA) : 99.0V ..... 121.0 Volts insteps of 0.1V.
Lower Relay setting (LRS) : 100.5% ..... 105.0% of a NVA insteps of 0.1%.
Raise Relay setting (RRS) : 99.5% ..... 95.0% of NVA insteps of 0.1%.
Initial time delay (td) : 0.3 ..... 120.0 secs insteps of 0.1 secs.
Control pulse ‘ON’ time duration (tON) : 0.2 ..... 0.8 secs insteps of 0.1 secs.
Control pulse ‘OFF’ time duration (tOFF) : 3.0 ..... 10.0 secs insteps of 0.1 secs.
Under voltage and
(UVT/UVR) : 69% ..... 89% of NVA insteps of 0.1%.
Restoring level
Over voltage & Restoration Level : 110% ..... 120% of NVA insteps of 0.1%.
(OVT / OVR)
Control failure delay (CFD) : 0 ..... 900 secs insteps of 1 sec.

IMPORTANT NOTES :
1. The lower and upper limit settings are freezed. In the event of operator trying to
programme the setting either below or above the limits, the value that gets registered will
be ONLY lower or upper limit respectively as specified above for each parameter.
2. Automatic restoration of AVR Functions from control failure status after the PT Voltage
crosses any one of the dead Band setting.
FUNCTION KEYS : Five function keys viz.,
SET INC ENT VIEW RESET to set the above parameters as
well as to VIEW the parameters and to RESET under CFD failure
conditions.
OUTPUT RELAYS : Total number of relays : 3 Nos. One relay each for Lower and
Raise control pulse, 1 Trip relay for under / over voltage and
control failure status.
PT INPUT : 110VAC from Secondary of suitable PT < 1 VA at 50 Hz.
AUX POWER SUPPLY : 110V (+ 15%, - 30%) 50 Hz 12 VA.
PROTECTION : RF / EMI filters and fast acting fuses (200 mA) at PT input and
AUX input lines.
ENCLOSURE : 1.5 mm thick powder coated steel plate housing with screen printed
anodized aluminium front and acrylic cover.
DIMENSIONS : Overall : 202 mm (H) x 156 mm (W) x 250 mm (D).
Cutout : 188 mm (-0.00, +2.00) (H) x 138 mm (-0.00, +2.00) (W).
TEMPERATURE : - 5 0 C ..... + 55 0 C.
Manufactured by :
P.E. SYSTEMS PVT. LTD.
Regd. Office & Works. # 13 / 14,
Begur Road 1st Cross, Bommanahalli,
Bangalore - 560 068 INDIA