Part E - 2 - (HVAC) Engineering Design
Part E - 2 - (HVAC) Engineering Design
out the design requirements for all new construction and major renovation healthcare projects,
Compliance to this document, which stipulates minimum performance design standards for DHA,
Substantial variance from this Design Manual may be proposed by the design consultant to
promote new concepts and design enhancements. Variance shall not conflict with Federal
Regulations, Local Municipality Laws, Executive Orders, or the needs of the end users. Substantial
This document is intended for the Architect/Engineer and others engaged in the design and
renovation of healthcare facilities within the Emirate of Dubai. Where direction described in
applicable codes are in conflict, the AE shall comply with the more stringent requirement. The A/E
is required to make themselves aware of all applicable codes and ordinances and assure compliance
thereto.
The document should be read in conjunction with other parts of the Health Facility Guidelines (Part
A to Part F) & the typical room data sheets and typical room layout sheets.
The HVAC systems should be designed to achieve the following key objectives.
• Mechanical services that deliver the anticipated levels of comfort and functionality.
• Appropriate pressure differentials between adjacent spaces and departments in clinical facilities.
• Reducing operating and maintenance costs shall be a key component in all new constructions.
• An appropriate level of consistency across facilities, within the emirate of Dubai, recognizing the
Abbreviation Description
ΔT Delta T
C Celsius
CD Construction Documents
CFC Chlorofluorocarbon
CO2 Carbon-dioxide
Abbreviation Description
CT Computerized Tomography
CV Constant Volume
DB Dry Bulb
DD Design Development
DX Direct Expansion
EMG Electromyography
GE General Exhaust
HFC Hydrofluorocarbons
HFO Hydrofluoro-Olefins
Hp Horsepower
HX Heat Exchanger
Abbreviation Description
I/O Input/output
IR Infrared Radiation
IT Information Technology
kg Kilograms
kPa Kilopascal
NC Noise Criteria
OA Outdoor Air
OT Occupational Therapy
OR Operation Room
Pa Pascal
PE Protective Environment
Abbreviation Description
RA Return Air
RH Relative Humidity
SA Supply Air
SE Special Exhaust
TB Tuberculosis
while designing healthcare facilities in the Emirate of Dubai. The requirements given in these
regulations or standards are not repeated generally in this document; however specific additional
healthcare specific requirements emphasised in the following sections will take precedence over
referenced standards. Local standards will always take precedence over international standards. The
editions mentioned are current editions and latest editions of the documents, at the time of
Summary of Key Design Codes, Standards and Reference Documents for HVAC Design
Summary of Key Design Codes, Standards and Reference Documents for HVAC Design
Facilities
Ventilation for Catering NFPA 96- Ventilation control and fire 2014
Facilities protection of commercial cooking operation
Summary of Key Design Codes, Standards and Reference Documents for HVAC Design
It is important to note the below mentioned functions desired from the HVAC system serving a
healthcare facility, as compared to other building types for which the HVAC system is simply
Infectious diseases are spread by several different routes. Tuberculosis and in some cases influenza,
the common cold, and other diseases are spread by the airborne route. The spread can be
designer must keep these aspects in mind & consider it an ethical responsibility to comply with all
For healthcare facilities, HVAC systems play a very important role in reducing airborne infections by
Air Change Rates to reduce the residence time of particles in the air.
Ultra Violet Germicidal Irradiation (UVGI) to in-activate the viable agents and prevent
growth.
Pressurization of spaces to move air from clean to less clean and dirty area.
100% exhaust from designated high-risk spaces to remove the particles from the space.
Proper air distribution to reduce the deposition of particles and provide a designed path to
the exit.
The HVAC systems should follow design requirements stated within UAE Fire and Life Safety Code,
2017 & other relevant referenced NFPA standards. Points to note are listed below.
Fire Dampers, Smoke Dampers and Combination Fire and Smoke Dampers should be
provided in accordance with the local code and in line with the Fire and Life Safety Drawings.
Mechanical smoke management should be provided for atriums, corridor and open
circulation spaces.
Mechanical pressurization should be provided for egress stairs, lift hoist ways & lift lobbies
If the air handling units return ducting is utilized for smoke control, the system design zoning
should be carefully matched with the smoke zones, which in turn should line up with fire
alarm and fire sprinkler zones. All other requirements related to duct construction and fan
rating should be adhered to., as per UAE Fire Life Safety Code, 2017.
It is recommended to install dedicated extract air ducts for corridor and open circulation
spaces smoke management, where required by code, rather than utilizing AHU ducts which
would complicate AHU control and operation sequences, especially for typical in-patient
floors. Using AHU return duct would also warrant replacement of ducting, post fire incident.
Makeup air can however, be provided through the AHU supply fans.
The HVAC system designed for a healthcare facility is providing mission critical filtration, cooling,
humidification & dehumidification as well as pressure regime management to the various critical
Thus, the failure of an HVAC system component can lead towards a loss of pressurization which
could be life threating to an immune-compromised patient and can also result in a spread of viral
infections.
The following section will list out the key requirements for an HVAC system to meet these
challenges.
2.5.1 Reliability
Reliability of an HVAC system is the quality of the system components, installation, commissioning
To ensure reliable construction and operation, the DHA health facility guidelines aim to introduce a
prequalification system for the design consultants. Part A of these guidelines provide more
It is encouraged that owners and facility operators get involved early in the design process and
provide feedback on the system components and operational aspects of the design.
For future healthcare projects in Dubai, HVAC equipment manufacturers that have a strong local
presence and full-service support shall be selected. All applicable components should be tested at
the Dubai Central Laboratories or other equivalent facilities worldwide and test certificates
provided for record. Witness testing is encouraged for all major HVAC system components.
2.5.2 Redundancy
In simple terms, redundancy can be thought of the amount of standby equipment that is available to
Standby equipment requirement should always be aligned with the owner’s facility operation plan.
Key system components in healthcare facilities must be configured in N+1 configuration. A guidance
is provided below.
Operation Theatre Air Handling N+1 AHU’s with dual fans with each
Units sized at 100% of the airflow or fan
arrays with one additional fan are
allowed as an alternate to N+1
AHU’s.
Air-Side Equipment – Hygienic N+1 (Fans) Each sized Fan Coil Units can be used for
Air Handling Units (Critical Care, at 100% airflow & Emergency, Imaging, Oncology, in
LDR, Emergency, Diagnostic Critical Cooling. patient pharmacy, Radiotherapy
Imaging, Laboratory, Oncology, and renal departments but their
In-patient pharmacy, use is highly discouraged.
Radiotherapy, Renal Unit, CSSD,
Surgical Suite, Isolation Rooms)
Fire & Life Safety / Smoke N As per local Fire and Life Safety
Control System / Pressurization code requirements
System Fans
2.5.3 Resiliency
For the HVAC system, resiliency can best be thought of how much of the total system continues to
operate in the event of a failure of one part of the system. Resiliency is critical to business
continuity which is essential for public hospitals operating under disaster management and helps
mitigate revenue losses in case of system failures for private hospital operators.
Resiliency must be built into the design, during the concept design stage. The consultant must
evaluate the risks associated with the failure of a system component, engage in an effective
dialogue with client/owner/operator and determine ways and means to mitigate the risks.
External risks associated with climatic conditions such as Sand Storms & heavy rainfall
should also be evaluated and intake and exhaust louvers should be positioned & sized so that
Major equipment located below grade must be evaluated for flash flood risk.
weights of equipment’s such as absorption chillers should also be considered to ensure that
Redundant systems should be routinely operated through BMS and tested at design
conditions.
Some of the major equipment risks are mitigated by the table in the previous section on
redundancy, but distribution systems such as ductwork and pipework should be configured
Ring mains, multiple risers, dual connections to larger AHU coils, bypass over major control
valves with proper isolation, Individual VFD’s per fan, bypass for VFD’s, manifolded air
handling unit configuration are some of the measures that can be adopted for better system
resiliency.
HVAC systems for clinical buildings shall generally be zoned to match the smoke control
compartments for the building. The intention is to ensure that the impact of one zone being shut
down is minimized. If this approach results in an excessive quantity of air handling units, more than
one zone can be combined with fire and smoke dampers to separate them. In this case designers
shall consider arranging the distribution ductwork so that only part of the system has to be shut
By zoning the system using smoke control compartments it is unlikely that the capacity of a single
air handling unit would exceed 16,500 L/s (60,000 m3/hr). If it does the designer should consider
It is encouraged that consultants prepare zoning diagrams during the concept design stage to
Emergency generators are to be provided for the buildings to supply power to the HVAC system in
As described in the Electrical section, the capacity of the generators is determined using a risk
classification process. The HVAC designer shall work with the electrical designer for the building to
determine which HVAC systems are to be provided with emergency power through this process.
The result of this analysis should also be used to assess how systems are zoned.
As a minimum all critical areas identified within ASHRAE 170 (SSU(CSSD), Surgical Suite, Labour &
Delivery Suite/Birthing Unit, Recovery, Emergency, Intensive Care, Nursery & Inpatient Rooms)
should be provided with backup cooling fed from emergency power. The space ventilation and
pressure relationship requirements for Isolation rooms, Operating rooms including Caesarean
section, should be maintained, via backup power. Refer to the electrical section, detailing the
It is encouraged that mechanical consultant table the electrical power requirements (normal power
or emergency power) in the mechanical equipment schedules in order to obtain clarity for the
electrical engineer.
The HVAC system shall be designed to be compliant to HTM 08-01: Acoustics, as mandated by
Dubai Al Sa’fat Green Building rating system. Specific requirements for HVAC system components
should be obtained from ASHRAE HVAC Applications Handbook Chapter 48: Noise and Vibration
Control.
Lining of ductwork is not allowed in healthcare facilities after final filtration, as per ASHRAE
170 except in terminal units, sound attenuators and air distribution devices (plenum boxes
etc.). Such lining should be provided with an impervious cover, or carry certifications citing
no vapor absorption and be acceptable to local civil defence requirements. CAV/VAV boxes
which cannot meet acoustic requirements, should be provided with downstream attenuators
in critical areas.
Backup power generator’s if installed within hospital buildings should be provided with
Car park exhaust and make up air fans should be provided with sound attenuators to reduce
Acoustic Ratings for plant room doors should be carefully specified with detailed
Due to the nature of medical facilities, changes to internal layouts and upgradation of the medical
equipment is quite common, which results in HVAC cooling load variances. The designer should
engage in an effective dialogue with the owner/operator to determine the allowance to be kept for
As a strong recommendation this guide asks for 20% extra useable area allocated for mechanical
shafts for additional pipework and ductwork. It is also recommended that mechanical AHU rooms
for medium to large hospitals should allow for space for an additional air handling unit for every 10
air handling units. Mechanical Pump rooms should be provided with space for 1 additional pump for
The intent of this section is to provide a guidance for HVAC systems selection process for
healthcare facilities as well as list out acceptable and unacceptable HVAC systems. Specific Room
design guidance is provided at the end of this document in a separate section, which should be read
All-air systems shall be used for all new facilities and major renovations of existing facilities where
above ceiling clearance is available to accommodate HVAC air distribution systems. All-air systems
designs shall provide for the admittance of minimum required outdoor air in all operating
conditions. The use of constant volume (CV) systems shall be carefully considered and only utilized
if proven more cost effective through a Life Cycle Cost Analysis (LCCA), or if required due to the
area served.
The following list of systems is acceptable for air-distribution systems within healthcare facility.
This distribution system is acceptable in all facilities and is considered as the preferred solution for
• VAV terminal units shall be in a pressure independent configuration to maintain airflow under
• Supply air VAV terminals shall be provided with integral hot water reheat coil or electrical reheat
coil for areas with permanent occupancy as deemed necessary through heat load calculations.
• Supply air temperature differential to room temperature shall not exceed 10°C in heating mode
to prevent stratification.
• Terminal units shall be equipped with sound attenuators as necessary to meet acoustic
requirements.
• Supply air temperatures shall be reset based on demand to minimize cooling and reheat loads.
• VAV terminal units shall be provided for both supply and return/exhaust air systems for areas
• Minimum air volumes for VAV boxes shall be in accordance with the room air change rate specified
in ASHRAE 170. This will generally be higher than the typical 30% minimum for a conventional
commercial VAV system. The tender drawings & specs should indicate minimum value for each
VAV box.
Chilled water-based Fan Coil Units are an acceptable solution for administration and support areas
as well as clinical areas where ASHRAE 170 does not prohibit recirculation by room units.
For Larger facilities, use of FCU is discouraged due to higher energy consumption, maintenance
issues and the need to access clinical spaces to replace components such as filters, fan motors and
control valves.
In specific cases fan coil units may also be used in circulation spaces, if there are high sensible
cooling loads from heat gain through the building envelope or in spaces where there are localized
heat gain from electro-mechanical equipment’s; such as plant rooms, electrical and telecom rooms.
Care must be taken to place FCU’s outside of the electrical/telecom rooms to avoid chilled water
Fan coil units shall not be used to dehumidify the outdoor air as Dubai’s outdoor air has a high
moisture fraction. A dehumidified outdoor air supply should be ducted to the Fan coil units through
a dedicated 100% outdoor air handling unit, utilizing energy recovery as per DM regulation.
DX or VRF based Fan coil units are also acceptable where there is no centralized source of chilled
Displacement ventilation is an acceptable solution for non-clinical areas only. It is not recommended
in clinical areas due to the restrictions created by the fixed location of the supply diffusers. Where
displacement ventilation is used, the designer shall co-ordinate locations of terminals carefully with
the interior design proposals to ensure thermal comfort is achieved and future flexibility is not
compromised.
Displacement ventilation can be particularly effective in spaces with lofty ceilings such as entrance
areas atriums or spaces with high occupancy levels such as lecture halls.
If utilizing displacement ventilation, the designer shall refer to the ASHRAE standards and
The following systems are unacceptable and should not be used in future healthcare projects within
• Chilled beams or chilled ceilings due to concerns over potential condensation and associated
The following section aims to provide a general brief for the HVAC systems for new construction
and major renovation healthcare projects within the Emirate of Dubai, governed by the DHA.
The following minimum design conditions shall be used for all healthcare projects within the
Emirate of Dubai. These have been developed from the ASHRAE Fundamentals Handbook 2017 &
Outside design conditions for fresh air (as per 34°C DB, 32°C WB
DM)
Outside design conditions for selecting air 47.6°C DB (ASHRAE Projected Dry Bulb for
cooled HVAC equipment (Recommended) next 20 years)
Outside design conditions for selecting cooling 32°C WB (ASHRAE Projected Wet Bulb for
towers (Recommended) next 20 years)
The envelope design parameters, as a minimum should meet the prescriptive requirements listed
out in Dubai Al Sa’fat Code 501 Chapter 1- Conservation and Efficiency: Building Envelope & Dubai
As a best design practice, the following values are suggested to be used for future healthcare
It is encouraged to improve upon the recommended values for medium to large healthcare facilities
as they are operational round the clock and consume the most energy as compared to any other
building type.
The internal design criteria for DHA facilities is split up into two categories, clinical and non-clinical
spaces. All spaces identified within ASHRAE 170 shall be treated as clinical spaces.
The below tables would identify the performance level for internal spaces and the associated ceiling
with respect the heat gain from internal sources for both spaces.
Non-clinical ancillary support buildings that are part of the development shall follow the guidelines
Criteria Requirements
Temperature The internal temperature requirement for non-clinical spaces shall be set
at 24 °C DB.
Relative Humidity General non-clinical spaces would not be provided with active relative
humidity control, unless it is a requirement related to specialist
equipment within the space. The designer to ensure that maximum
relative humidity is kept within 60% by employing BMS control
Criteria Requirements
algorithms.
Electrical Lighting Lighting loads shall be based on an average watts/m2 figure for each
type of room based on a representative lighting layout. General guidance
can be obtained from ASHRAE 90.1.2016 Lighting Power Density. The
maximum overall limit set by Al Sa’fat 502.04 Lighting Power Density-
Interior should be adhered to.
Electrical Small Power Where there are specific equipment rooms, the heat loads shall be based
on the ‘worst case’ values from the potential range of suppliers.
Where are there no specific equipment layouts, allowances for small
power loads shall be made on an average watts/m2 basis as appropriate
for the space type. Refer to ASHRAE Handbook Fundamentals 2017
Chapter 18 Non-Residential Cooling and Heating Load Calculations.
Occupancy The design shall be based on the furniture layout or ASHRAE 62.1,
whichever is the more onerous.
Acoustic The design for HVAC system should follow the acoustic requirements
Requirements listed out in HTM 08-01 which is referenced in the Dubai Al Sa’fat Code.
Criteria Requirements
Relative Humidity Internal relative humidity shall generally be in accordance with ASHRAE
Standard 170. If there is an equipment specific temperature requirement
listed in the Room Data Sheets (RDS) it will supersede ASHRAE
Criteria Requirements
requirements.
Electrical Lighting Lighting loads shall be based on an average watts/m2 figure for each
type of room based on a representative lighting layout. General guidance
can be obtained from ASHRAE 90.1.2016 Lighting Power Density. The
maximum overall limit set by Al Sa’fat 502.04 Lighting Power Density-
Interior should be adhered to.
Electrical Load Due to Medical equipment heat dissipation loads shall be based on the Room
Medical Equipment Data Sheets (RDS) listed values. RDS values should represent actual
equipment heat dissipation values using ‘worst case’ manufacturer’s
published data from the range of potential suppliers.
Occupancy Design occupancy for each space shall be as specified on the room data
sheets. If no occupancy is provided, the design shall be based on the
furniture layout or ASHRAE 62.1, whichever is the more onerous.
Acoustic The design for HVAC system should follow the acoustic requirements
Requirements listed out in HTM 08-01 which is referenced in the Dubai Al Sa’fat Code.
The air intake and exhaust louvers/vents positions should be carefully planned for healthcare
facilities to ensure that there is no recirculation of air. Minimum separation distances mentioned in
ASHRAE 62.1 should be adhered too. ASHRAE 170 lists out the perspective requirements for
outdoor air intakes and exhaust discharges which will be enforced via this guideline.
Dubai’s harsh climatic conditions warrant special attention to the air intake air louvers. As a
minimum the intake outdoor air should be drawn into the system through sand trap louvers sized at
1m/s across the face area of the louver to provide an 80% or higher filtration efficiency at coarse
For bigger healthcare facilities providing a central air intake to the 100% outside air energy
recovery air handling unit it is recommended to utilize a self-cleaning inertial air cleaner. The air
cleaner provides 99% efficiency at a sand grain size of 10 to 100 microns. Due to the high velocity
intake it also overcomes the constraints regarding the large face area, which are a problem for the
Washable aluminium filters can be provided at the rear of the sand trap louver. If provided, designer
should ensure access for proper maintenance. If proper access cannot be guaranteed, enabling the
removal of the filters without shutting down the AHU, the filters should not be provided for the air
intake louvers as dirty filters would clog the air steam providing higher pressure drop and in turn
Based on the ambient acoustic levels, determined through a survey conducted at the site by a
professional acoustic consultant, if required the outdoor air intake & exhaust should be provided
Buildings shall maintain a positive pressurization (5-10% net positive). Tighter buildings are eligible
for less net pressurization. Designers should ensure enough outside air is provided for adequate
pressurization. It is encouraged to undertake blower door testing for facility integrity as part of the
2.10.5 Filtration
Mechanical filtration plays a very important role in ensuring that the hospital continues provide
best in class care & is fit for occupancy. Mechanical filtration is one of the key elements to
healthcare HVAC design and is of primary significance regarding air quality & infection control.
All air handling units directly serving the spaces & outside air handling units serving downstream
terminal units, should be provided with a 1st stage filtration of no less than MERV 8/ePM10 60%
rating and a final filter downstream of all wet-air cooling coils and supply fan according of no less
ASHRAE 170 Table 7.1 & 8.1 provide a list of healthcare spaces which do not allow recirculation
through room units. Majority of the spaces are highly critical departments [Critical Care, OT, NICU,
Procedure rooms, Recovery Rooms, Isolation Rooms, X-Ray Rooms (surgery/critical care &
catherization/angiography ), Endoscopy Rooms, Autopsy Room, etc.] where cleaning difficulty and
potential building of contamination has led to this requirement. DHA for all future projects would
therefore not allow terminal cooling or heating units for these spaces as identified by ASHRAE 170.
Ultraviolet (UV-C) disinfection (also called ultraviolet germicidal irradiation [UVGI]) is used to
inactivate microorganisms. The use of UV-C is encouraged for healthcare projects specially for
cooling coil surfaces to avoid fungal amplification. The peak effective wavelength range for
Alternative filtration techniques such as electronic filters and air cleaners using photocatalytic
oxidation (PCO) are not encouraged to be used because of negative health effects that arise from
exposure to ozone and its reaction products. Substantial technical evidence is required on the use of
these techniques, validated by international agencies, test standards and standard engineering
bodies such as ASHRAE, CIBSE etc. If utilized, they are not considered a replacement for mechanical
filtration but can be considered as aides to achieve better indoor air quality . Refer to ASHRAE
2.10.6 Materials
The table below provides basic information on reference design standards for core HVAC system
components. It is highly recommended that the materials and system components carry
certifications citing compliance to the following standards for all new construction and major
renovation healthcare projects within the Emirate of Dubai. Latest versions of the following will
HEPA Filter Standard EN 1822 High efficiency air filters (EPA, HEPA and 2009
ULPA). Aerosol production, measuring equipment,
particle counting statistics
ISO 29463 High efficiency filters and filter media for 2017
removing particles from air
Fan Coil Units & Eurovent RS 6/C/002-2017 Rating Standard for 2017
Package Units Certification of Non-Ducted Fan Coil Units
Hygienic Air Handling VDI 6022 - Ventilation and indoor-air quality - Hygiene 2011
Unit Construction requirements for ventilation and air-conditioning systems
and units
Ventilation Equipment AMCA 210 Laboratory Methods of Testing Fans for 2016
Certified Aerodynamic Performance Rating
Hydronics refers to the science of heating or cooling with water. Open systems are open to the
atmosphere at least one location, such as cooling towers. Closed systems on the other hand are not
Piping systems distribution scheme can be direct or reverse return. With the advent of Pressure
Independent control valves (PICV), direct return systems outweigh the advantages offered by
reverse return both in terms of cost and system simplification, so they are encouraged for new
healthcare facilities.
All new facilities using hydronic cooling or heating system, should utilize pressure independent two-
Hydronic piping distribution schemes should either be constant primary / variable secondary
pumping or variable primary pumping. For Variable Primary Flow the chillers must be provided with
automatic isolation valves and the decoupler line provided with a control bypass actuated by a flow
meter ensuring that the minimum flow through the chiller is guaranteed. Care must be taken in
correct sizing of expansion tanks and air separators especially for heating hydronic systems.
Variable Primary Flow pumping systems are the preferred choice for future medium to large scale
Constant primary / variable secondary systems are also acceptable. Pumps should be in headered
Refer to the Figure 2.1, 2.2. 2.3 for illustrative example of the various distribution schemes.
Pipe material should be Black Steel Schedule 40 with welded or grooved joints.
All insulation shall have a system fire and smoke hazard rating as tested by procedure ASTM-E-84,
NFPA 255, and UL 723 not exceeding: Flame Spread 25 and Smoke Developed 50. The system
rating shall be based on insulation, jacket, adhesives, coatings, fittings, and cements. Any treatment
Refer to Dubai Al Sa’fat Green Building Code for relevant insulation thickness. Refer to Dubai
Municipality Circulars for applicable materials. All insulation should be approved for use by the
The selection of insulation should look at not only thermal characteristic but also ensure no
Figure 2.1
Figure 2.2
Figure 2.3
2.11.1.1 Location
All significant HVAC equipment such as FAHU’s, AHU’s shall be located in enclosed mechanical
plant rooms. Mechanical rooms shall be provided with air-conditioning & ventilation. The only HVAC
• Exhaust Fans.
• Heat Rejection Equipment. (e.g. Air-cooled chillers, Air cooled condensers, Cooling Towers, etc)
Rooftop/Exposed air handling units are not recommended due to the high humidity conditions in
Dubai.
2.11.1.2 Access
Mechanical rooms and roofs with mechanical equipment shall be provided with staircase and
preferably lift access to facilitate maintenance and equipment replacement. Access to mechanical
rooms and roof mechanical areas shall be directly from cores or main corridors. It is not acceptable
for the access to mechanical rooms to be through treatment or patient care areas.
Clear access routes through mechanical rooms and roof areas shall be provided from the ls and
staircases. Routes shall be clearly and permanently marked on the mechanical room floor. The
minimum clear height for access routes shall be 2000mm or higher if dictated by the dimensions of
equipment.
Steps on access routes are not acceptable. If changes of level are needed, or if services must be run
2.11.2.1 Location
Service shafts shall be strategically located to provide rational and flexible services installations and
minimize the size of the distribution ductwork and pipework on each floor. It is recommended that
main ductwork shafts are located away from stair cores and elevator shafts to allow ducts to enter
In clinical facilities, shafts shall not be located inside surgery suites or critical care areas. If the
designer encounters a specific situation where a shaft is needed in one these spaces it should be
discussed and agreed with DHA during the schematic designs stage, through architectural design
submission.
2.11.2.2 Access
Pipework shafts shall be provided with access doors at each floor level to allow for inspection and
maintenance and installation of additional pipework in the future. Removable floor gratings are
Ductwork shafts shall be provided with access doors as needed to enable cleaning. It is anticipated
that installation of additional ductwork would require the removal and replacement of wall finishes.
Locating HVAC equipment in ceilings above patient, staff and public areas shall be avoided where
possible. Where it is necessary, its location shall be carefully selected to minimize the disturbance
during maintenance and limit the infection control measures which are required to access it.
In clinical facilities it is not acceptable under any circumstances to have HVAC equipment accessed
from the space in any of the areas listed below. Terminal units should be located outside the rooms
• Treatment Room
• Sterile Store
The only exception is room side accessible terminal HEPA filters and fan filter units (FFU), where
access is obtained through special housing’s allowing quick replacement. All HEPA filters should be
It is strongly suggested that the designer develops an access and maintenance strategy document.
This document shall clearly describe the access and maintenance strategy for all mechanical
systems, including HVAC, plumbing and medical gas. Document shall be made available during the
90% stage inspection by DHA. The document must identify the strategy for plant maintenance and
• Locations with Accessible ceilings for terminal units (VAV, FCU etc.)
The following section outlines the important design considerations that should be kept in mind
If the project is significantly large, it is beneficial to locate all major MEP equipment at a central
location. This will help optimize the cost and increase the overall efficiency of all the systems.
District cooling availability for the project should also be ascertained at an early stage and if
approved by the local district cooling provider the building should be designed to be hooked up to
district cooling system. The building still must provide critical cooling (SSU(CSSD), Surgical Suite,
Labour & Delivery Suite/Birthing Unit, Recovery, Emergency, Intensive Care, Nursery & optionally
Inpatient Rooms) in case of failure of the district cooling network, by means of local heat rejection
Remotely located central plant may use directly buried piping or use trenches/tunnels to connect to
hospital building. When utilizing service tunnels, a minimum of 2000mm clear depth should be
considered with a 900mm access passageway in between pipes to allow for sufficient space for
maintenance.
Select cost-effective and optimum central chilled water plants and/or small chilled water
systems to meet the project-specific requirements. Each installation shall consist of multiple
For central plants and small systems, it is recommended to conduct a comprehensive study
to evaluate and define the lowest life-cycle cost performance of the chilled water system.
Where a central plant serves more than one air handling system, the capacity of the central
plant shall be calculated based on the peak simultaneous load, not the sum of the individual
loads. In addition, the following diversity factors are reasonable when calculating central
cooling plant capacity. The actual calculated central plant capacity shall be specific to the
nature and size of the system(s) however and should be determined via computer simulation.
Lighting 0.9
Equipment 0.85
People 0.8
For air cooled chiller in noise-sensitive locations, include chiller manufacturer’s standard
Imaging systems such as MRIs, PET, CT Scanners, LINAC require chilled water for equipment
process cooling. Central plants should be sized to cover process loads, if use of plant central
chilled water use is approved by the imaging equipment manufacturer, otherwise a dedicated
chiller plant must be provided. Typically, the chiller, buffer tanks, and pumps for these
applications are provided by the manufacturer of the imaging equipment for installation by
others.
Potable water cooling should be provided as per the hydraulics engineering section of this
report.
Adequate space should be provided for equipment removal and maintenance. Replacement
routes should be marked on the design drawings. Design for non-disruptive access to all
chillers, pumps, cooling tower, and cooling tower components without the need to
Higher delta T should be utilized to obtain energy savings by lowering pumping costs.
Consider VFD driven equipment for further energy savings for any pump consuming over
7.5kW.
Arrange piping, especially piping in hydraulic decoupler to ensure that all water flow meters
have ideal flow conditions for accurate measurement. Follow worse case flow meter
recommendations.
Cooling Towers should be provided with an automatic basin cleaning system considering the
sand storms prevalent in Dubai & the risk of legionella associated with manual cleaning.
Cleaner environment friendly refrigerants should be utilized. ODP value should be 0 and
GWP value should be less than 2500. HFO’s are being developed which have much lower
Select cost-effective and optimum central hot water plants and/or small hot water systems
For central plants and small systems conduct a comprehensive study to evaluate and define
the lowest life-cycle cost performance of the hot water system. The study shall address both
Adequate space should be provided for equipment removal and maintenance. Replacement
All new projects within the emirate of Dubai must obtain full compliance with the Dubai Al Sa’fat
Green Building System Section Five: Resource Effectiveness: Energy 500. The values mentioned in
section 2.10.1 and 2.10.2 shall supersede the requirements from the Al Sa`fat code.
Medium to Large scale healthcare projects are encouraged to apply the principles mentioned in
Facilities.
In addition, LEED v4 for Healthcare guiding principles are also encouraged to be utilized for a
The following section lists out the specific requirements for major HVAC source equipment’s to be
utilized for healthcare projects. The aim is not to create an equipment specification list but to
highlight essential elements of design related to each equipment which must be considered due to
the critical nature of the healthcare facilities & the challenging climatic conditions of Dubai.
Water cooled chillers can be centrifugal/screw or absorption type. Most common water-
cooled chillers utilized in the UAE market are centrifugal chillers with single compressor or
maintenance.
Consultant is encouraged to undertake an LCC study for VFD chillers vs. standards chillers.
Refrigerants with 0 ODP and less than 2500 GWP should be utilized for future healthcare
Provide emergency chilled water flanged piping connections covered with blind flanges and
isolation valves for emergency chilled water service where redundant chillers are not
installed.
Chillers should adhere to the performance metrics listed in the Dubai Al’ Sa’fat Code as a
minimum.
Air cooled shall be screw type for tonnage over 100 tons. Scroll type chillers can be utilized
for smaller installations. Reciprocating chillers are not allowed to be installed in future
healthcare projects.
Consultant is encouraged to undertake an LCC study for VFD chillers vs. standards chillers.
Provide emergency chilled water flanged piping connections covered with blind flanges and
isolation valves for emergency chilled water service where redundant chillers are not
installed.
Chillers should adhere to the performance metrics listed in the Dubai Al’ Sa’fat Code as a
minimum.
preferred choice for new construction and major renovation projects for DHA. The cooling
towers shall be certified by the Cooling Tower Institute (CTI) and shall meet OSHA safety
requirements.
It is recommended that the Cooling Tower structure should be stainless steel, with FRP
Consultant is encouraged to undertake an LCC study for VFD cooling tower fan motors vs.
standard motors.
Legionnaires Disease: When a new hospital building is constructed, place cooling tower(s) in
such way that the tower drift is directed away from the hospital’s air-intake system and
design the cooling towers such that the volume of aerosol drift is minimized.
Heat exchangers used for HVAC applications for district cooling systems should comply with
the regulations from the relevant district cooling provider Empower, Palm District Cooling,
Emicool etc.
For potable water pre-conditioning and other applications plate and frame type heat
For low temperature hot water circuit for heating, heat exchangers can either be plate &
frame type or shell & Tube type. It is recommended that two heat exchangers as a minimum
The following section lists out the specific requirements for major HVAC air side equipment’s to be
utilized for healthcare projects. The aim is not to create an equipment specification list but to
highlight essential elements of design related to each equipment which must be considered due to
the critical nature of the healthcare facilities & the harsh climatic conditions of Dubai.
Outside air units should employ means of energy recovery. Approved methods include
Air to Air Plate Type Heat Exchangers. Preferred choice for areas where no cross
Heat Pipes. Allowed for all areas but offer lower energy savings.
Total Energy Recovery Wheels. Allowed & encouraged for all areas except OR’s. Must have
a cross contamination limit of less than 0.04% by particulate count and have a purging
section.
Run around Coils. Allowed for all areas but offer lower energy savings.
Outside air energy recovery should not be employed for the following air streams. These
Autopsy Exhaust.
Refer to the Figure 2.4,2.5,2.6 for outside air handling unit approved configurations.
Figure 2.4
Figure 2.5
Figure 2.6
The capacity of a single air-handling unit shall not exceed 50,000 m3/hr [16,500 L/s].
Air handling units shall be AHRI or Eurovent certified, factory-fabricated, and the standard
product of one manufacturer. All air-handling units shall be constructed in modular and
fully saturated air leaving the cooling coil causes damage to the downstream filters and
sound attenuators.
Air handling units serving clinical areas should be hygienic type units. Refer to the materials
To prevent cross contamination, separate AHU’s should be provided as a minimum for the
following spaces.
Operating Theatres
Mortuary
Main Kitchen
Each air-handling unit shall be installed as a standalone entity without any physical interface
with another air-handling unit. Selection of stacked (one on the top of another) air handling
units is not permitted. Use of a common return air fan for two or more air-handling units is
Use of a single or multiple plenum fans (fan array) is permitted & encouraged over housed,
Where room air can be returned to the system, provide a dedicated return or relief air fan
for each air-handling unit to facilitate room-by-room air balance, economizer cycle, and
intended volumetric air balance. Provide a direct digital control (DDC) interlock between the
Variable frequency drives (VFD) shall be utilized in all air handling units and rooftop units.
Building type (e.g., hospital, outpatient facility, etc.) will determine level of redundancy
required for VFDs. VFDs shall include either a bypass switch or be configured in a manner
that failure of one VFD does not disable the entire unit. Fan motor shall be high efficiency.
Each cooling coil shall not exceed six (6) rows and ten (10) fins per inch (FPI). Design two
(2) coils in a series arrangement if the cooling coil capacity requirement exceeds the
capability of an 6 row, 10 FPI coil. Chilled water shall be piped in series through both coils,
and a 42-inch access section shall be provided between the two equally sized coils
Maximum cooling coil discharge face velocity shall not exceed 450 fpm. Heating coil
Ultra violet (UV) lamps shall be located on the leaving air side of the cooling coil.
Access doors (or panels) on the air handling unit sections shall always open against the
positive side of the door and shall not be blocked by internal filter casings or internal
injuries.
Figure 2.7
All Fan Coil Units must be provided with a source of treated precooled dehumidified fresh
air through the DOAS systems. Direct injection of outside air dumped over the ceiling void
Fan coil unit systems served by chilled water with hot water or electric heating are an
attractive solution for areas requiring special control or out of hours operation. Such areas
and electrical rooms, PABX rooms and administration areas. Fan coil units are not allowed
Fan Coil unit’s usage is highly discouraged for new constructions for areas other than
mentioned above, where adequate space for distribution ductwork can be provided.
Select fan coil units that deliver the required capacity at medium speed.
For new construction and major renovation, PICV should be provided for each FCU.
FCU shall be located outside of patient occupied spaces/rooms for ease of maintenance.
All terminal units shall be pressure-independent type and equipped with DDC controls. All
air terminal units (constant volume or variable air volume) serving perimeter or interior
spaces with permeant occupancy & mandated ASHRAE 170 air change requirements, shall
The maximum and minimum air volume settings shall be factory set, but field adjustable. The
minimum setting for each space should be dictated by the air change requirement, the
ventilation requirement for multi zone VAV’s based on ASHRAE 62.1 and the makeup air
requirement for exhaust. The designer should list out minimum settings for each VAV box
All rooms requiring acoustic treatment according to HTM 08-01 should be provided with
Variable Air Volume (VAV) boxes shall be located outside of patient occupied spaces for
ease of maintenance.
If VAV systems are specified, Venturi Air Terminals or Air Valves with high speed actuators
are highly recommended to be utilized for all new construction and major renovation for the
following space types in lieu of VAV boxes due to their higher reliability and stable airflow
control.
Operation Theatre
Isolation Rooms
Laboratories with Fume Hoods ( Should be equipped with a 3 sec or faster response
actuator)
Additional rooms as identified by the building end user that have strict pressure control
Venturi air terminal should be programmed as using the variable air volume approach with
maximum energy savings. Usage based controls can also be employed at the facility owner’s
discretion. Each airflow control device shall be factory characterized on air stations NVLAP
Accredited.
Venturi Air Valves shall be located outside of patient occupied spaces for ease of
maintenance.
For an AHU provided with downstream venturi air terminals, it is preferable to utilize all
varying pressure drops. Low speed venturis and constant air venturis can be used for non-
2.12.2.6 Humidifiers
Considering the climatic conditions in Dubai, it is not anticipated that active humidification
Depending on the scale of the project humidification can be achieved by package electric
The humidifier should be located prior to the cooling coil and fed with clean steam (steam
If duct mounted humidifiers are used 304 stainless steel ducting should be provided for a
minimum of 1.5m downstream and 0.5m upstream of the humidifier. Designer Team to verify
the absorption distance for each application and adjust the length of stainless steel
accordingly. Duct sections downstream of steam humidifiers shall be sloped to a low point
Diffusers, Registers and grilles should be specified as per the project requirements and in alignment
with the clinical and interior design. Air Diffusion Performance Index (ADPI) shall conform to
selection criteria given in ADPI table of the “Room Air Distribution” chapter of the ASHRAE
Terminal HEPA filters for all spaces other than OT’s served by dedicated AHU’s should be Fan
powered type, catering for the entire pressure drop of the filter, allowing for the AHU supply fan to
2.12.2.8 Ductwork
Rectangular galvanised steel has consistently been shown to be more cost effective as
compared with rigid circular ductwork which is both less efficient in its space requirements
All clinical areas shall be provided with a fully ducted system. Use of the ceiling void, for air
delivery (supply or return) is not allowed, only back of house areas and admin areas can use
return air plenum but should be provided with appropriate sealing and smoke sensors.
Duct sizing is to be based on the recommended velocity and pressure drop ranges in the
Air handling duct systems shall be designed to be accessible for duct cleaning, generally by
the provision of access panels. Access panels shall be fitted at each reheat coil and fire and
Commercial dishwasher exhaust, steam sterilizer, and sterile washer exhaust shall be type
Laboratory hood exhaust ductwork shall be 304 stainless steel with welded joints.
Kitchen hood exhaust shall be 16-gauge black steel where concealed and 18-gauge, type 304
HVAC Instrumentation and Control systems which are commonly part of the BMS systems are
integral to the proper operation of a healthcare facility. BMS Control systems form the backbone of
the operation and maintenance system for HVAC and provide the facility management team with
The following points should be kept in mind while designing a BMS system for healthcare
applications.
The BMS system shall be suitable, compatible, scalable and flexible to meet the demands
imposed by healthcare facilities. The system shall have spare capacity at field level to allow
Specific requirements related to control actuators, control valves, control dampers, end
switches, safeties and safety alarms, control wiring, air flow measuring stations, room
temperature & humidity sensors, DDC control systems servers & tablet displays should be
A detailed Input/output point list should be prepared by the consultant in consultation with
specialist solution providers and included as part of the project tender documentation.
Control algorithms should be programmed to utilize the data collected and allow for effective
energy recovery, air-side filter diagnostics, critical alarms and sensor calibration checks.
Ensure system is capable of robust metering. Separate sub-meters should be allocated for
lighting, HVAC plant, HVAC distribution, general power, service water heating, renewables
and whole building power & water as a minimum. Energy use should be benchmarked every
The HVAC systems commissioning is an important phase in the project timeline and is critical in
confirming that the design parameters are met by the installed system and the system meets the
minimum code requirements related to air changes, filtration effectiveness and infection control.
For medium to large scale healthcare projects an independent commissioning agent (CxA) should be
The following points should be kept in mind while preparing for commissioning of HVAC systems
Method Statements should be provided by the contractor during the commissioning phase
Testing and Commissioning plan should be developed by the contractor in consultation with
the CxA to provide a clear and concise roadmap for the implementation of the commissioning
The design consultant should engage with the owner and the facility management team and
develop the Owner’s Project Requirements (OPR). Furthermore, these should be formulated
in a report along with the design narrative, submitted as part of the construction
Operating Rooms
Vivarium Areas
Operating Rooms and other clean rooms should be tested for particle counts as per
international standards.
The commissioning agent (CxA), Testing Adjusting and Balancing Contractor (TAB), MEP
commissioning of systems and provide all reports and test results as well as arrange for
witness testing for agreed systems for the owner’s representative and the supervision
consultant.
Functional Testing for all critical systems should be included in the scope of works.
O&M Manuals for all HVAC equipment should be provided by the contractor.
Training on the systems installed should be conducted by the contractor’s team for the
FM Team should keep a record of all O&M activities on site, preferably through an electronic
The intent of this section is to identify key design elements related to the various spaces found
within a healthcare environment and provide a checklist that must be adhered to for approval of
new construction and major renovation projects under the umbrella of DHA within the emirate of
Dubai.
Following requirements must be adhered too for Operating Room HVAC systems.
Proper temperature (18-22°C), humidity (20-60% RH) and ventilation control for the
comfort of surgical personnel and patients & to environmentally discourage the growth and
17 HEPA (99.995% MPPS as per EN 1822) filtered air for thermal control, 4 ACH (20%)
of which must be outside air. Air should be introduced at the ceiling and exhausted near the
floor.
Each operation theater should be provided with a dedicated air handling unit.
Air Handling units for operation theater should be provided with VFD’s to allow for variable
Air handling units should supply constant volume (20 ACH) airflow. Constant volume
systems are common and should be the basis of design as complicated systems lead to
Variable systems are permitted for use “only if” they continue to provide a positive room
pressure (normally +0.01-0.04 in. wg or +2.5-10 Pa differential) with respect to the corridors
and adjacent areas and the required ACHs are maintained when the room is occupied. This
required through a pressure display monitor, connected to the BMS system. Space
temperature , humidity and air change rate shall be displayed simultaneously. Pressure
monitor should have an IP-54 rated housing, resistant to spray washdown &
decontamination chemicals. Accuracy RSS of at least +/-0.25% full scale . This guide
HEPA-filtered airflow should be dissipated through laminar airflow diffusers. Laminar airflow
must be designed to move clean air over the aseptic operating field at a maximum face
velocity (0.15–0.3 m/s), sweeping away particles in its path. All laminar flow diffuser should
be room side accessible. Laminar flow array should entirely cover an area equivalent to the
Medical plume evacuation system should be provided for OR’s using lasers and other
instruments generating plumes. This equipment should be part of the medical equipment
Amount of reheat should be minimized, through supply air temperature reset, if humidity
conditions can be met, and through reduced airflow when the operating room is not occupied.
Special low temperature requirements, related to heart and orthopedic surgery should be
ascertained early in the design process and a corresponding low temperature chilled water
circuit be provided to meet the surgeon’s desired temperature (if required). It is to be noted
temperature requirements related to burn and pediatric units should also be ascertained,
Surgeons should only be allowed to set the dry bulb temperature. Humidity display should
be provided.
Humidity and temperature sensors should be provided in the return air duct for system
control.
In general, operating room air handling units should be designed at 2 m/s air velocity at the
In general, operating room chilled water pipes to the AHU should be designed at higher
velocities in the range of 1.8 m/s to 2 m/s to allow for better heat transfer.
Refer to Figure 2.8 for operating room airflow configuration and pressure relationship.
Figure 2.8
Following requirements must be adhered too for Imaging Room HVAC systems.
Imaging rooms can be grouped into 4 types as mentioned below, each having their respective
requirements.
Magnetic (MRI)
Nuclear (PET Scan, Linear Accelerator LINAC, Nuclear Camera, Gamma Knife)
In general Imaging rooms fall under diagnostics which according to ASHRAE require 6 ACH
of supply air with 2 ACH of outside air & a Temperature requirement (21-24°C), humidity
(<60% RH).
Imaging rooms do not require dedicated air handling units and can be served from the same
Imaging rooms designed for treatments such as fluoroscopy (e.g. vascular, cardiac
requirement for treatment rooms 15 ACH of supply air with 3 ACH of outside air but are
Data should be obtained from Room Data sheets for the control room, procedure room and
Wherever possible water cooled medical equipment should be preferred. Process water
cooling can be provided via dedicated medical grade chillers backed up by central chilled
water system or with the central chilled water system backed up by chilled potable water.
Discussion on the system and its criticality should be brought up by the designer to the
MRI rooms must be designed to cater for the heat load produced by the equipment. As a
minimum 6 ACH of supply air and 2 ACH of outside air should be provided. Following key
No rotating equipment (motors, fans) should be placed within the 1 gauss field.
Provide an insulated stainless-steel quench pipe with proper thrust restraints sized as per
manufacturer guidelines and vented to outside with the exclusion zone clearly marked.
Provide an emergency exhaust fan sized at 12ACH to exhaust helium. This can also be used
PET & SPECT Scan rooms are diagnostic rooms requiring 6 ACH SA/2 ACH OA. All air
should be exhausted via the general exhaust system from the scanning rooms. Chilled water
requirements as per point 6. Hot labs, Radio pharmacies provided with PET and SPECT scan
rooms normally house BSC II Hoods and should be provided with dedicated hood exhaust
with bag-in bag-out filtration for isotopes and general exhaust from the space.
LINAC rooms are also diagnostic rooms with no invasive procedures being carried out.
Regular requirements of 6AC SA/ 2 ACH OA will suffice. Humidity should be kept less than
50%. Chilled water requirements as per point 6. Modern day LINAC’s are often coupled with
MRI’s within the same suite. Care should be taken to accurately calculate the heat dissipation
2.15.3 Laboratories
Proper temperature control (21-24°C), maximum 60% RH with 6 ACH SA/ 2 ACH OA
All Laboratory work areas should be 100% exhausted to outside through general exhaust
Fume hoods and Bio Safety cabinets located within the labs should be exhausted to the
ambient through high plume dilution fans through proper filtration. Exhaust from BSC
cabinets can be combined into a single manifold, provided they carry the same class of air
and exhausted through N+1 exhaust fans. Similar approach can be adopted for Fume
cupboards. Engineer should minimize the number of fans for operational efficiency and
Labs containing Fume Hoods or BSC cabinets should be provided with laminar flow diffusers
Flammable cabinets should be provided with ventilation with dedicated exhaust fan and
discharge.
Variable systems are permitted for use “only if” they continue to provide a negative room
pressure (normally -0.01-0.04 in. wg or -2.5-10 Pa differential) with respect to the corridors
and adjacent areas and the required ACHs are maintained when the room is occupied. This
can be achieved by communicating fixed offset air-valves for the supply, general exhaust and
hood exhaust (one per BSC). Active Monitoring of pressure is required through a pressure
display monitor, connected to the BMS system. Space temperature , humidity and air change
rate shall be displayed simultaneously. Pressure monitor should have an IP-54 rated housing,
resistant to spray washdown & decontamination chemicals. Accuracy RSS of at least +/-
Laboratory sterilizing areas should be provided with 10 ACH SA/ 2 ACH OA.
2.15.4 Pharmacy
Pharmacy should be kept at positive pressure. VAV systems are permitted without
797.
Vault, if designed for controlled substances should be provided with cooling with supply and
return air.
Pharmacy clean rooms ( if required by clinical planning) should be designed to ISO Class 7
Standard according to ISO 14644, unless stated otherwise for the project by the operator ,
providing a minimum of 40 ACH of HEPA filtered air , with a ceiling coverage between 30%-
40%, keeping the maximum face velocity under 0.15 m/s and providing low level return.
These should be provided with an ISO Class 8 ante room , providing a minimum of 20 ACH
HEPA filters modules should be fan filter type to reduce central fan size.
Clean rooms should be kept at positive pressure except when used for hazardous drugs which
should be negative pressure with associated ante room at positive pressure. Clean rooms
Hazardous drugs compounding clean rooms are provided with BSC cabinets. The exhaust
from these cabinets should be filtered with a carbon filter and a hepa filter before being
Clean room personal are wearing heavy protective clothing so lower temperature should be
Following requirements must be adhered too for Patient Room HVAC systems.
Each patient room should be provided with a thermostat linked with the BMS system (if
available).
Following requirements must be adhered too for Intensive Care Room HVAC systems.
Intensive Care rooms include specialized rooms such as Surgical Intensive Care (SICU),
Medical Intensive Care (MICU), Cardiac Care Unit (CCU), Paediatric Intensive Care Unit
(PICU), Neonatal Intensive Care Unit (NICU), High Dependency Unit (HDU) etc. All these
rooms require a minimum of 6 ACH SA/2 ACH OA with temperature range of 21- 24°C, and
30-60% RH.
ICU areas should not be served with recirculating type units such as FCU’s.
Reheat should be provided to each ICU room/bay. Thermostat should be linked with the
Following requirements must be adhered too for Morgue & Autopsy HVAC systems.
As a minimum Morgue & Autopsy spaces should be provided with temperature control (20-
Exhaust grilles should be located at both high level and low level.
Direct exhaust connection to the autopsy table should be provided. Exhaust air should be
HEPA filtered, UV treated, and carbon filtered for odours and discharged at a high velocity,
preferably using a stack. Since autopsy is normally not carried out at private facilities, this
take the heat dissipated for the refrigerators into account while designing the HVAC system.
Negative room pressure (normally -0.01-0.04 in. wg or -2.5-10 Pa differential) with respect
to the corridors and adjacent areas is required. Active Monitoring of pressure is required
Class N- Airborne Infection Isolation Rooms (AIIR) – Negative Pressure Isolation Room
Class Q – Quarantine Isolation – Negative Pressure Isolation Room with Clean and Dirty
Utility.
Class P- Protective Environment Isolation Rooms (PE)- Positive Pressure Isolation Room.
Class S- Standard Isolation Room - Contact Isolation Room- Neutral Isolation Room.
Proper temperature (21-24°C), humidity (<60% RH) and ventilation control, minimum 12
Use of negative pressure rooms with close monitoring and control of airflow direction
pressure monitor with alarm points to building automation system. Space temperature ,
humidity and air change rate shall be displayed simultaneously. Pressure monitor should
have an IP-54 rated housing, resistant to spray washdown & decontamination chemicals.
Accuracy RSS of at least +/-0.25% full scale.This guide recommends a negative pressure of
Seal room below 0.5 ft2(465 cm2) of air leakage (called Effective Leakage Area under 4 Pa
Exhaust air grille should be placed over the patient head or at low level near the head. Air
from negative pressure rooms is to be HEPA-filtered with a bag in bag out filter and
exhausted directly to the outside with dedicated N+1 high plume dilution exhaust fans
discharged 10 feet above roof level. Recirculation is not allowed. Air from other AIIR rooms
can be mixed provided each room is provide with a VAV or Air Valves prior to connection.
UVGI fixtures may be placed in upper room, or inside the ducts as an additional measure ,
Pressure relationship should be negative with respect to the ante room with the ante room
Refer to Figure 2.9 for AIIR room airflow configuration. Room exhaust and supply air valves
should be VAV type while the remaining valves for ante room and toilet can be CAV types.
Figure 2.9
All the requirements for Class N rooms must be adhered too for Class Q rooms.
In addition, supply should be provided with HEPA filters similar to Class P rooms.
Class Q isolation suite will contain a dirty utility as well. That should also be exhausted to
These rooms are to be designed for high-risk, immuno-compromised patients (BMT, organ
transplant, leukemia, burn, late-stage HIV) and to minimize fungal spore counts in air.
Proper temperature (21-24°C), humidity (<60% RH) and ventilation control, minimum 12
Incoming air through HEPA filters or fan powered HEPA filters mounted in laminar flow
diffusers, supply air on top of the patient bed and exhaust out through the opposite side of
Pressure of +2.5 Pa (0.01" w.g.) relative to the corridor as a minimum. Provide differential
pressure monitor with alarm points to building automation system. Space temperature ,
humidity and air change rate shall be displayed simultaneously. Pressure monitor should
have an IP-54 rated housing, resistant to spray washdown & decontamination chemicals.
Accuracy RSS of at least +/-0.25% full scale. This guide recommends a positive pressure of
10 Pa for the isolation room. Refer to figure 2.10. Room return and supply air valves should
be VAV type while the remaining valves for ante room and toilet can be CAV types.
Seal room below 0.5 ft2(465 cm2) of air leakage (called Effective Leakage Area under 4 Pa
UVGI fixtures can be placed in upper room, or inside the ducts as an additional measure.
Pressure relationship should be positive with respect to the ante room with the ante room
These isolation rooms are used to provide physical isolation for patients having a
communicable disease which is not airborne as chicken pox, etc. Requirements for regular
Figure 2.10
2.15.9 SSU(CSSD)
Dirty Area – 6 ACH SA/2ACH OA with 100% dedicated exhaust and negative pressure.
Temperature 16-23°C
Clean Area- 4 ACH SA/2 ACH OA with positive pressure. Temperature 20-23°C
Sterile Store – 4 ACH HEPA filtered SA/ 2 ACH OA with positive pressure. Temperature
24°C
Means of recording daily temperature and humidity should be provided via the BMS system
Direct exhaust from washers, disinfectors and sterilisers should be provided as per the Room
Data Sheets.
Where ethylene oxide (ETO) sterilizers are used and ETO is stored system shall be designed
to provide 100% dedicated exhaust to outside. Upon loss of exhaust system airflow, an
audible and visual alarm shall activate in the steriliser work area, and at a location that is
continually staffed.
Following requirements must be adhered too for Renal Dialysis Patient Bays systems.
Room/Bay can be considered as having the same requirements as standard patient room.
Consider radiant heating panels directly over the patient chair/bed for radiant heating as
dialysis/chemo patients are frequently cold & anaemic & immobile for the duration of the
treatment.
Consider low design velocities of below 0.25 m/s at the treatment bed/chair, preferably
Following requirements must be adhered too for PACU Recovery area HVAC systems.
As a minimum PACU rooms should be provided with temperature control (21-24°C), 30-
Low level return should be provided with stainless steel grilles to capture the anaesthetic
gasses being exhaled by the patients and allow for better flushing of the space.
Each room/bay should be provided with a thermostat linked with the BMS system (if
available).
2.15.12 Emergency
Following requirements must be adhered too for Emergency area HVAC systems.
Decontamination Room: Temperature control (21-24°C), with a 12 ACH SA/ 2 ACH OA,
negative pressure. All air should be 100% exhaust with dedicated ducting.
Exam/Treatment Room: Temperature control (21-24°C), maximum 60% RH, with a 6 ACH
Resuscitation (Trauma) Room: Temperature control (21-24°C), 20-60% RH, with a 15 ACH
SA/ 3 ACH OA, positive pressure. If Trauma is to be utilized as emergency Operating room
under the hospitals disaster management scheme, operating room requirements should be
imposed.
Triage: Temperature control (21-24°C), maximum 60% RH, with a 12 ACH SA/ 2 ACH OA,
negative pressure. All air should be 100% exhaust with dedicated ducting.
60% RH, with a 6 ACH SA/ 2 ACH OA, negative pressure. All air should be 100% exhaust
Following requirements must be adhered too for Burn Unit Room HVAC systems.
As a minimum Burn Units rooms should be provided with temperature control (21-32°C),
40-60% RH, with a 6 ACH SA HEPA Filtered with laminar flow diffusers / 2 ACH OA. Room
Each patient room should be provided with a thermostat linked with the BMS system (if
available).
Each patient room should be provided with an individual humidifier and a humidistat to
Each patient room should be provided with reheat sized to raise the temperature to 32°C
Requirements for Protective Environment PE Isolation rooms should be applied for Bone Marrow
Transplant rooms.
Following requirements must be adhered too for Hydro-Therapy Pool HVAC systems.
Should be provided with temperature control (26-28°C), with the ability to reheat up to
32°C, with a minimum of 10 ACH SA / 100% exhaust from the space. Space should be at
negative pressure.
Provide a dedicated or common wet exhaust system with welded stainless-steel ductwork.
To allow for energy saving, VAV system can be employed via supply and exhaust terminal
The Spinal cord injury patient requires 33˚C (92˚F) water temperature, while the patient
with multiple sclerosis requires 28˚C(84˚F) water temperature. The pool equipment should
be designed to accommodate rapid water temperature change, where both patient types can
use the same pool on a given day based on schedule. Humidity control should be
appropriately designed to cater for the water evaporation from the pool surface.
Care must be taken that all grilles/diffusers and other HVAC devices must be suicide and
vandal resistant.
Use duct mounted sensors and allow for heavy-gage construction to resist damage and
Following requirements must be adhered too for Procedure Room HVAC systems.
20-60% RH, with a 15 ACH SA with laminar flow diffusers / 3 ACH OA. Room should be at
positive pressure.
If aesthetic gasses are administered all requirements related to operating rooms should be
applicable.
Following requirements must be adhered too for Endoscopy Procedure Room HVAC systems.
As a minimum should be provided with temperature control (21-23°C), 20-60% RH, with
a 6 ACH SA with laminar flow diffusers / 2 ACH OA. Room shall have no mandated
Endoscopy/Bronchoscopy:
As a minimum should be provided with temperature control (20-23°C), 20-60% RH, with
a 12 ACH SA with laminar flow diffusers / 2 ACH OA. Room shall be negative pressure
This is more common scenario and endoscopy rooms should be designed as a worse case to
As a minimum should be provided with temperature control (20-23°C), 20-60% RH, with
a 15 ACH SA with laminar flow diffusers / 3 ACH OA. Room shall have positive pressure
requirement.
As a minimum should be provided with temperature control (21-24°C), 20-60% RH, with
a 10 ACH SA / 2 ACH OA. Room shall have negative pressure requirement. All air should
The HVAC systems for outpatient clinics & support functions are often not designed to the same
level of redundancy as in-patient facilities. It is encouraged that the consultant engages with the
owner/facility manager early in the design process to figure out the requirements for the clinics and
Any particular low temperature requirements for day surgery units should be advised by the
owner’s representatives and the consultant should undergo an analysis of whether the requirements
Procedure Room & Embryo Transfer Room: The procedure room & embryo transfer room
should be treated as an OR and all requirements for operating room should be complied.
Recovery Room/Bays: Recovery bays should be treated as PACU rooms and all
Laboratories (Embryology, Andrology, Cryo etc.): Labs for IVF centre represent ultra clean
labs. In addition to the requirement for laboratory mentioned in the previous section all
air should be HEPA filtered with laminar flow diffusers. Pressure requirement should be
Infectious Labs: Infectious labs should be provided with the same systems as other IVF labs,
but the air pressure regime should be negative. (-0.01-0.02 in. wg or -2.5-5 Pa
differential)
Sample Collection Rooms: Sample collection rooms should be kept at negative pressure via
HVAC air handling units serving the laboratories, procedure and embryo transfer rooms
should be provided with carbon filters, with activated alumina impregnated with potassium
permanganate & HEPA filters in the air handling unit. HEPA filters can also be installed at
the terminal locations instead of the air handling units if dedicated air handling units are not
used.
Following requirements must be adhered too for Data Centre/Server Room HVAC systems.
As a minimum Server rooms should be provided with temperature control (19-22°C), 30-
60% RH, with supply air governed by the heat load for the servers but not less air required
to cool 0.5 kW/m2 of data hall of heat load, to cover for future expansion.
Server Room should be cooled by precision ac units or close control ac units, providing
cooling and humidity control, located within the server room with adequate clearance space
A minimum of two close control units should be provided for each server room in N+1
arrangement, one fed from the central chilled water circuit and one fed from a dedicated DX
machine for medium to large scale healthcare facilities. For smaller facilities and outpatient
facilities one close control unit can be provided with dual coil arrangement and dual fans.
Server Rooms rack should be arranged in hot aisle and hot cold arrangement, where
applicable.
Server Rooms should be conditioned through raised floor arrangement, with perforated floor
tiles provided for up to 6kW rack load and fan powered tiles or rack containment provided