Alarko Fcu İng
Alarko Fcu İng
Alarko Fcu İng
02
03
Alarko Fan Coil Unit is designed and manufactured on the base of advanced technology, and utilizes qualified galvanized iron as structure material. Due to its supper-thin design, it has such advantages: beautiful outlook, space saving, easy installation, etc.
Besides the Alarko Fan Coil Units product advantages, also Alarko has been offering its customers experience and knowledge to satisfy all their needs with trained team members for more than 50 years.
04
Modern and Genuine Lines
Its modern and pleasant styled design allows easy matching with any type of furnishing and many more diversified applications. 42 FA fan coils are available in 9 types and 78 sizes in total. The unit can handle air volumes changing between 300-3,800 m3/h, providing total cooling capacities differing between 1-20 kW and heating capacities between 2-22 kW (Eurovent conditions) at maximum fan speed.
05
FAN COIL
White
Grey (optional)
Black (optional)
Blue (optional)
The swing angle af the first louver are 40-42, degrees and the second louver are 37-38 degrees.
Adding digital tube displaying on the display board. LED can display the Error Code to make the malfunction checking easier. Built-in water pump with 750 mm pumping head.
750 mm
Specification
Model Nominal Air Flow (Low/Medium/High) Total Cooling Capacity1 Heating Capacity2 Water Flow Water Pressure Drop Inlet/Outlet Pipe Diameter Sound Pressure Level (Low/Medium/High)4 Weight3 Dimensions5 Unit Net Dimensions (L x H x W) Panel Dimensions (L x H x W) Unit Paking Dimensions (L x H x W) Panel Paking Dimensions (L x H x W)
Notes: 1 2 3 4 5
MKA-600R 600/772/1020 5,32 4,98 0,253 23,8 3/4 38,4/43,2/48 36 840x230x840 950x46x950 955x247x955 1035x90x1035
MKA-750R 717/922/1275 6,50 5,90 0,310 25,2 3/4 38,4/43,2/48 36 840x230x840 950x46x950 955x247x955 1035x90x1035
MKA-850R MKA-950R MKA-1200R MKA-1500R 1020/1218/1445 1153/1376/1615 1440/1720/2040 1800/2150/2550 6,76 7,65 9,63 11,94 7,15 7,79 10,09 11,89 0,322 0,364 0,459 0,569 27 30 44 46 3/4 3/4 3/4 3/4 39,2/44,1/49 41,6/46,8/52 43,2/48,6/54 44,8/50,4/56 42 42 42 42 840x300x840 950x46x950 955x317x955 1035x90x1035 840x300x840 950x46x950 955x317x955 1035x90x1035 840x300x840 950x46x950 955x317x955 1035x90x1035 840x300x840 950x46x950 955x317x955 1035x90x1035
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water delta temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 50C, according to water flow in cooling, high speed Net weight Sound Pressure Leveli measured 1 m. away from unit in a anechoic room Dimensions are for reference. Dimension details are in the Installation Manual
06
FAN COIL
Built-in water pump with 500 mm pumping head. With the function of auto-restart.
500 mm
Specification
Model Nominal Air Flow (Low/Medium/High) Total Cooling Capacity1 Heating Capacity2 Water Flow Water Pressure Drop Inlet/Outlet Pipe Diameter Sound Pressure Level (Low/Medium/High)4 Weight3 Dimensions5 Unit Net Dimensions (L x H x W) Panel Dimensions (L x H x W) Unit Paking Dimensions (L x H x W) Panel Paking Dimensions (L x H x W)
Notes: 1 2 3 4 5
MKD-300 380/490/510 3,00 5,90 0,143 14 3/4 33/36 20,5 575x260x575 647x50x647 705x340x705 715x123x715
MKD-400 440/540/680 3,70 7,48 0,176 15 3/4 39/42 20,5 575x260x575 647x50x647 705x340x705 715x123x715
MKD-500 597/657/710 4,41 5,37 0,210 18,3 3/4 39,4/44,4/49,3 29 575x260x575 647x50x647 705x340x705 715x123x715
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water delta temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 50C, according to water flow in cooling, high speed Net weight Sound Pressure Leveli measured 1 m. away from unit in a anechoic room Dimensions are for reference. Dimension details are in the Installation Manual
07
FAN COIL
Ultra thin body, space saving MKC-300R, MKC-400R: 235 mm., MKC600: 198 mm.
235 mm
Ultra slim
You can get detailed information for this model from our company.
08
FAN COIL
WALL TYPE
Left piping
Right piping
Air cleaning devices and high efficiency filter keep the air clean
You can get detailed information for this model from our company.
09
FAN COIL
DUCTED TYPE
Whole new structure makes the installation and the maintenance much easier New 4-speed motor expends the working range of single model Two external static pressure series (12Pa and 30Pa) give you more choices for variable applications 2-Row coil makes the units with lower weight and smaller installation space For the models with auxiliary electrical heater, the new electronic thermostat and air back plenum are standard
Models
12 Pa HSB 30 Pa HSB MKT3-200 MKT3H-200 MKT3-300 MKT3H-300 MKT3-400 MKT3H-400 MKT3-500 MKT3H-500 MKT3-600 MKT3H-600 MKT3-800 MKT3H-800 MKT3-1000 MKT3H-1000 MKT3-1200 MKT3H-12H00
Specification
Model Nominal Air Flow (Low/Medium/High) m3/h Total Cooling Capacity1 kW Heating Capacity2 kW Water Flow l/sn Water Pressure Drop kPa Inlet/Outlet Pipe Diameter inc. Sound Pressure Level (Low/Medium/High) dB(A) Weight3 kg Dimensions 4 Unit Net Dimensions (L) mm. (H) mm. (W) mm. Unit Paking Dimensions (L) mm. (H) mm. (W) mm. Model Nominal Air Flow (Low/Medium/High) m3/h Total Cooling Capacity1 kW Heating Capacity2 kW Water Flow l/sn Water Pressure Drop kPa Inlet/Outlet Pipe Diameter inc. Sound Pressure Level (Low/Medium/High) dB(A) Weight3 kg Dimensions 4 Unit Net Dimensions (L) mm. (H) mm. (W) mm. Unit Paking Dimensions (L) mm. (H) mm. (W) mm.
Notes: 1 2 3 4
MKT3-200 229/294/334 1,83 3,29 0,087 3,6 3/4 38/46/55 13 770 240 490 786 265 515 MKT3H-200 233/300/341 1,86 3,36 0,089 3,71 3/4 38/46/55 13 770 240 490 786 265 515
MKT3-300 256/349/582 2,93 5,30 0,140 8,3 3/4 41/48/57 15 827 240 490 841 265 515 MKT3H-300 261/356/594 2,99 5,40 0,142 8,55 3/4 41/48/57 15 827 240 490 841 265 515
MKT3-400 335/430/696 3,61 6,50 0,172 12,7 3/4 41/50/59 17 927 240 490 941 265 515 MKT3H-400 342/439/710 3,69 6,63 0,176 13,1 3/4 41/50/59 17 927 240 490 941 265 515
MKT3-500 365/643/921 4,40 7,93 0,210 16,7 3/4 44/53/60 17 927 240 490 941 265 515 MKT3H-500 372/656/939 4,49 8,09 0,214 17,2 3/4 44/53/60 17 927 240 490 941 265 515
MKT3-600 MKT3-800 MKT3-1000 MKT3-1200 422/731/1037 782/1083/1437 738/1226/1784 767/1315/2062 5,41 7,24 8,66 10,10 9,19 12,30 14,70 17,20 0,258 0,345 0,412 0,481 31,2 30,2 44,5 39,4 3/4 3/4 3/4 3/4 45/55/63 43/52/60 48/56/64 60/61/65 20 27 32 36 1140 240 490 1155 265 515 1440 240 490 1454 265 515 1546 240 490 1560 265 515 1835 240 490 1850 265 515
MKT3H-600 MKT3H-800 MKT3H-1000 MKT3H-1200 430/746/1058 798/1105/1466 753/1250/1820 782/1341/2103 5,52 7,38 8,83 10,30 9,38 12,60 15,00 17,60 0,263 0,351 0,420 0,490 32,1 31,1 45,8 40,6 3/4 3/4 3/4 3/4 45/55/63 43/52/60 48/56/64 60/61/65 20 27 32 36 1140 240 490 1155 265 515 1440 240 490 1454 265 515 1546 240 490 1560 265 515 1835 240 490 1850 265 515
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water delta temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 50C, according to water flow in cooling, high speed Net weight Dimensions are for reference. Dimension details are in the Installation Manual
10
FAN COIL
All metal parts are made of commercial grade galvanized steel, providing maximum protection against corrosion.
MKF1 / MKF4: Series, air intake from front MKF2 / MKF5: Series, air intake from bottom MKF3: Without cabinet
Designed and tested in accordance with ARI440 and B55141, ensured excellent performance and reliability. Soft, streamlined appearance. Electromagnetic 3-way valve can be built inside.
MKF 1 / 2 / 4 / 5 Model MKF-150 MKF-250 MKF-300 MKF-400 MKF-450 MKF-500 MKF-600 MKF-800 MKF-900 Nominal Air Flow (Low/Medium/High) m3/h 173/226/255 359/383/425 367/428/510 500/570/680 458/642/765 588/765/850 748/861/1020 963/1120/1360 1148/1364/1530 Total Cooling Capacity1 kW 1,15 1,77 2,37 3,05 3,77 4,56 4,91 6,09 7,25 Heating Capacity2 kW 3,16 3,31 3,48 4,31 6,26 6,81 6,99 8,68 9,33 Water Flow l/sn 0,055 0,084 0,113 0,145 0,180 0,217 0,234 0,290 0,345 Water Pressure Drop kPa 9,9 9,9 11 21 12,7 17,5 13,6 20 20 Inlet/Outlet Pipe Diameter inc. 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Sound Pressure Level (Low/Medium/High)4 dB(A) 25,6/28,8/32 28/31,5/35 29,6/33,3/37 31,2/35,1/39 32,8/36,9/41 34,4/38,7/43 35,2/39,6/44 36,8/41,4/46 38,4/43,2/48 Weight3 kg 22,5 22,5 26 26 32,5 32,5 39 39 39 Dimensions5 Unit Net Dimensions (L) mm. 800 800 1000 1000 1200 1200 1500 1500 1500 (H) mm. 626 626 626 626 626 626 626 626 626 (W) mm. 225 225 225 225 225 225 225 225 225 Unit Paking Dimensions (L) mm. 889 889 1089 1089 1289 1289 1589 1589 1589 (H) mm. 772 772 772 772 772 772 772 772 772 (W) mm. 312 312 312 312 312 312 312 312 312 Model MKF3-150 MKF3-250 MKF3-300 MKF3-400 MKF3-450 MKF3-500 MKF3-600 MKF3-800 MKF3-900 Nominal Air Flow (Low/Medium/High) m3/h 216/235/255 343/376/425 323/404/510 458/554/680 408/609/765 535/756/850 589/790/1020 880/1058/1360 1148/1364/1530 Total Cooling Capacity1 kW 1,15 1,88 2,53 3,26 4,00 4,84 5,24 6,51 7,71 Heating Capacity2 kW 2,20 3,34 3,52 4,36 6,30 6,86 7,06 8,77 9,43 Water Flow l/sn 0,055 0,090 0,120 0,155 0,190 0,230 0,250 0,310 0,367 Water Pressure Drop kPa 9,9 9,9 11 21 12,7 17,5 13,6 20 20 Inlet/Outlet Pipe Diameter inc. 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Sound Pressure Level (Low/Medium/High)4 dB(A) 25,6/28,8/32 28/31,5/35 29,6/33,3/37 31,2/35,1/39 32,8/36,9/41 34,4/38,7/43 35,2/39,6/44 36,8/41,4/46 38,4/43,2/48 Weight3 kg 17 17 20 20 25 25 32 32 32 Dimensions5 Unit Net Dimensions (L) mm. 550 550 750 750 950 950 1250 1250 1250 (H) mm. 545 545 545 545 545 545 545 545 545 (W) mm. 212 212 212 212 212 212 212 212 212 Unit Paking Dimensions (L) mm. 639 639 839 839 1039 1039 1339 1339 1339 (H) mm. 639 639 639 639 639 639 639 639 639 (W) mm. 305 305 305 305 305 305 305 305 305
Notes: 1 2 3 4 5 Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water delta temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 50C, according to water flow in cooling, high speed Net weight Sound Pressure Leveli measured 1 m. away from unit in a anechoic room Dimensions are for reference. Dimension details are in the Installation Manual
Specification
11
FAN COIL
Specification
Model MKT3H-800 G70 Nominal Air Flow (Low/Medium/High) m3/h 1089/1217/1377 Total Cooling Capacity1 kW 7,00 Heating Capacity2 kW 6,63 External Static Pressure Pa 70 Water Flow l/sn 0,316 Water Pressure Drop kPa 14 Inlet/Outlet Pipe Diameter inc. 3/4 Sound Pressure Level (Low/Medium/High4 dB(A) 49,6/55,8/62 Weight3 kg 50 Dimensions5 Unit Net Dimensions (L x H x W) mm. 946x400x816 Unit Paking Dimensions mm. 1015x480x857
Notes: 1 2 3 4 5
MKT3H-1000 G70 MKT3H-1200 G70 MKT3H-1400 G70 MKT3H-1600 G100 MKT3H-1800 G100 MKT3H-2200 G100 1355/1524/1703 1598/1865/2022 1897/2230/2359 2134/2434/2719 2427/2726/3026 3033/3382/3760 8,82 9,96 11,92 14,98 15,69 19,96 10,02 11,29 14,03 16,49 18,24 22,65 70 70 70 100 100 100 0,477 0,538 0,668 0,785 0,869 1,079 20 22 24 52 90 130 3/4 3/4 3/4 3/4 3/4 3/4 48,8/54,9/61 48,8/54,9/61 48/54/60 49,6/55,8/62 50,4/56,7/63 52,8/59,4/66 52 52 54 76 76 76 946x400x816 946x400x816 1015x480x857 1015x480x857 946x400x816 1015x480x857 1290x400x809 1368x460x877 1290x400x809 1368x460x877 1290x400x809 1368x460x877
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water delta temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 50C, according to water flow in cooling, high speed Net weight Sound Pressure Leveli measured 1 m. away from unit in a anechoic room Dimensions are for reference. Dimension details are in the Installation Manual
12
FAN COIL
High capacity of cooling and heating performance, high efficiency and energy-saving There are seperated chilled water and hot water coils available in the same body of the fancoil. With this way, different zones or units in the same building can work at the same time to cooling or heating. 360 air supply panel is standart for MKD, optional for MKA units. Aesthetic design of 4-way cassette units.
13
FAN COIL
m3/h kW kW l/sn kPa kPa inc. inc. dB(A) kg mm. mm. mm. mm.
MKA-600F 684/787/1159 2,64 3,22 0,126 15,8 33 3/4 1/2 39/45/56 35 840x300x840 950x55x950 955x317x955 1035x90x1035
MKA-750F 740/897/1270 3,13 3,79 0,149 20,4 42,6 3/4 1/2 43/49/63 35 840x300x840 950x55x950 955x317x955 1035x90x1035
MKA-850F MKA-950F MKA-1200F MKA-1500F 965/1163/1478 1100/1278/1558 1117/1448/1867 1117/1448/2100 3,55 3,95 4,35 4,75 4,35 4,82 4,65 5,05 0,169 0,188 0,207 0,226 21,3 31,6 39,6 45,2 41,2 54,3 60,5 68,8 3/4 3/4 3/4 3/4 1/2 1/2 1/2 1/2 48/52/61 52/56/65 52/59/67 52/59/69 35 35 38 38 840x300x840 950x55x950 955x317x955 1035x90x1035 840x300x840 950x55x950 955x317x955 1035x90x1035 840x300x840 950x55x950 955x317x955 1035x90x1035 840x300x840 950x55x950 955x317x955 1035x90x1035
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 70C, t= 10C, high speed Net weight Sound Pressure Leveli measured 1 m. away from unit in a anechoic room. Dimensions are for reference. Dimension details are in the Installation manual.
Specification
Model Nominal Air Flow (Low/Medium/High) Total Cooling Capacity1 Heating Capacity2 Water Flow Water Pressure Drop (Cooling) Water Pressure Drop (Heating) Inlet/Outlet Pipe Diameter (Cooling) Inlet/Outlet Pipe Diameter (Heating) Sound Pressure Level (Low/Medium/High)4 Weight3 Dimensions5 Unit Net Dimensions (L x H x W) Panel Dimensions (L x H x W) Unit Paking Dimensions (L x H x W) Panel Paking Dimensions (L x H x W)
Notes: 1 2 3 4 5
m3/h kW kW l/sn kPa kPa inc. inc. dB(A) kg mm. mm. mm. mm.
MKD-300S 380/490/510 2,50 3,70 0,119 22 17 3/4 1/2 41/47/54 17,5 575x260x575 647x50x647 705x340x705 715x123x715
MKD-400S 440/540/680 2,90 4,60 0,138 16 23 3/4 1/2 46/52/59 17,5 575x260x575 647x50x647 705x340x705 715x123x715
MKD-500S 470/570/850 3,50 5,10 0,167 24 27 3/4 1/2 48/56/63 17,5 575x260x575 647x50x647 705x340x705 715x123x715
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 70C, t= 10C, high speed Net weight Sound Pressure Leveli measured 1 m. away from unit in a anechoic room. Dimensions are for reference. Dimension details are in the Installation manual.
14
FAN COIL
m3/h 1,26 kW l/sn kPa kPa inc. inc. dB(A) kg mm. mm. mm. mm. mm. mm.
MKT5-200 229/294/334 1,98 1,67 0,060 2,3 8,8 3/4 1/2 38/46/55 14 770 242 490 786 265 515
MKT5-300 220/374/517 2,77 2,48 0,094 5,5 16,6 3/4 1/2 41/48/57 16,5 827 242 490 841 265 515
MKT5-400 411/540/671 3,25 3,34 0,132 13,9 34,4 3/4 1/2 41/50/59 18 927 242 490 941 265 515
MKT5-500 353/605/810 4,67 3,89 0,155 35,9 36,6 3/4 1/2 44/53/60 18 927 242 490 941 265 515
MKT5-600 MKT5-800 MKT5-1000 MKT5-1200 417/731/1051 676/1054/1436 843/1246/1615 821/1356/2048 6,23 7,43 9,65 5,29 7,05 8,25 10,39 0,222 0,297 0,354 0,460 21,8 25,3 33,1 51,8 60,9 63 65 67 3/4 3/4 3/4 3/4 1/2 1/2 1/2 1/2 45/55/63 43/52/60 48/56/64 60/61/65 21 28 32 37 1140 242 490 1155 265 515 1440 242 490 1454 265 515 1546 242 490 1560 265 515 1835 242 490 1850 265 515
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 70C, t= 10C, high speed Net weight Dimensions are for reference. Dimension details are in the Installation manual.
Specification
Model Nominal Air Flow (Low/Medium/High) Total Cooling Capacity1 kW Heating Capacity2 Water Flow Water Pressure Drop (Cooling) Water Pressure Drop (Heating) Inlet/Outlet Pipe Diameter (Cooling) Inlet/Outlet Pipe Diameter (Heating) Sound Pressure Level (Low/Medium/High) Weight3 Dimensions 4 Unit Net Dimensions (L) (H) (W) Unit Paking Dimensions (L) (H) (W)
Notes: 1 2 3 4
m3/h 1,29 kW l/sn kPa kPa inc. inc. dB(A) kg mm. mm. mm. mm. mm. mm.
MKT5H-200 229/294/334 2,03 1,71 0,061 2,3 8,8 3/4 1/2 38/46/55 14 770 242 490 786 265 515
MKT5H-300 148/220/517 2,84 2,55 0,097 5,5 16,6 3/4 1/2 41/48/57 16,5 827 242 490 841 265 515
MKT5H-400 325/411/671 3,25 3,42 0,135 11 34,4 3/4 1/2 41/50/59 18 927 242 490 941 265 515
MKT5H-500 267/353/810 4,67 3,89 0,155 35,9 36,6 3/4 1/2 44/53/60 18 927 242 490 941 265 515
MKT5H-600 MKT5H-800 MKT5H-1000 MKT5H-1200 323/417/1051 489/676/1436 843/1246/1615 643/821/2048 6,22 7,07 9,97 5,29 7,05 8,49 10,70 0,222 0,296 0,337 0,475 21,8 30,7 33,1 51,8 60,9 63 65 67 3/4 3/4 3/4 3/4 1/2 1/2 1/2 1/2 45/55/63 43/52/60 48/56/64 60/61/65 21 28 32 37 1140 242 490 1155 265 515 1440 242 490 1454 265 515 1546 242 490 1560 265 515 1835 242 490 1850 265 515
Eurovent conditions: Air Inlet Temp. = 27C/47 %RH - Water entering temp = 7C and water temp = 5 K, high speed Eurovent conditions: Air Inlet Temp. = 20C - Water entering temp = 70C, t= 10C, high speed Net weight Dimensions are for reference. Dimension details are in the Installation manual.
15
FAN COIL
CONTROLLERS
R05/BGE
Wireless Remote Controller High-grade remote controller, Light background, LCD display screen, Clock function, ON / OFF / Temp. setting / Mode setting / Fan speed setting / Horizontal swingNertical swing setting functions.
Standard remote for MKA, MKB, MKC, MKD series.
R51/E
Wireless Remote Controller On base of common remote controller. LCD display screen, Clock function, ON / OFF / Temp. setting / Mode setting / Fan speed setting, etc...
Standard remote for MKG serie.
KJR-10B/DP(T)-E
Wired Controller By wired method to control Fan coil unit as ON / OFF / Mode setting / Fan speed / Timer setting / Swing, etc...
Optional remote for MKA, MKB, MKC, MKD, MKG series.
KJR-15B/E(P)
Floor-standing Fan Coil Unit Thermostat Suitable for Floor-standing fan coil unit. Control function as ON / OFF / Mode setting / Temp. setting / Fan speed setting / Cold air preventing function.
Optional remote (assembly in case) for MKF1, MKF2, MKF4, MKF5 series.
KJR-18B
Wired Controller KJR-18B/E-A: Control3-speed fan, when the temperature reaches the setpoint, it will close the Fan. KJR-18B/E-B: Control Motorized Valve and 3-speed fan, when the temperature reaches the set-point, it will close the Motorized Valve and Fan both. KJR-18B/E-C: Control Motorized Valve and 3-speed fan, when the temperature reaches the set-point, it will close the Motorized Valve with the fan still running. KJR-18B/E-D: Control 4 pipe fan coil units, Control two Motorized Valves and 3-speed fan, when the temperature reaches the set-point, it will close the Motorized Valve with the fan still running.
KJR-21B/D
Wired Controller Suitable for fan coil unit. Control function as ON / OFF / Mode settingfTemp. setting / Fan speed setting / Aux. heating appliance setting.
16
FAN COIL
Fonction Code R Remote Control RA Electrical heater with remote control E Electrical heater F 4 pipe 4 way cassette S 4 pipe compact 4 way cassette Nominal air flow (cfm) - Nominal ESP H High ESP Type Code A 4 way casette B 4 way casette (Compact) C One way casette D 4 pipe 4 way cassette T2 Ducted Fan Coil T3 Ducted Fan Coil (high static) T5 4 pipe ducted fan coil F1 - F4 Floor standing, air intake from front F2 - F5 Floor standing, air intake from bottom F3 Floor standing, without cabinet G Wall type
Airconditioning Central
GOSB-Gebze Organize Sanayi Blgesi ahabettin Bilgisu Cad. 41480 Gebze/Kocaeli/TURKEY Phone : +90 262 648 60 00 PBX Telefax : +90 262 648 61 01 web
ALARKO CARRIER SANAY VE TCARET A..
: www.alarko-carrier.com.tr
e-mail : [email protected]