Terasaki MV Breakers

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Medium voltage, arc-proof, air-insulated, metal-clad switchgear and controlgear up to 12kV

HS21

For marine and offshore use

catalog 07-02

Description
Characteristics
Medium voltage switchgear for marine and offshore use Full type approval Type tested in accordance with IEC 62271-200 Metal-clad construction Independently arc-fault tested Circuit breaker with safety metal shutter Option of air insulated bus bars Safety mechanical interlocks Front service operation Circuit breaker insertion and withdrawal with the front panel door closed Making current earthing switch Intelligent circuit monitoring devices

Application
All TERASAKI medium voltage switchboards are specifically designed and manufactured to meet the environmental and safety conditions of the marine and offshore industries. TERASAKIs reputation throughout the marine and offshore industry ensures that reliability and safety are of prime importance in the design and manufacture of the HS21 medium voltage switchboard.

Type testing
The HS21 switchboard is independently tested in accordance with IEC 62271-200 and marine classification society requirements. Temperature rise test This test is carried out at the rated current of the switchboard with the classification societies requirements of a 45-degree C ambient temperature being taken into consideration. Dielectric test Including impulse voltage and power frequency voltage test. Main circuit resistance measurement There shall be less than 20% difference in the DC measured resistance values of the main and control circuits. Short-time and peak withstand current test The panel is deemed to have passed the test if there is no deformation or damage to components and conductors following application of a short circuit current to the switchboard. Arcing due to internal fault test The switchboard is deemed to have passed the test if following the application of an internal arc fault, in accordance with IEC 62271-200 Annex A the original mechanical integrity and inflammability of the panel is maintained.

Design standards incorporated


The switchboard and the instrument have applied the following standards. IEC 62271-200 : switchboard IEC 62271-100 : circuit breaker IEC 62271-106 : contactor IEC 60044-1 : current transformer IEC 60044-2 : voltage transformer IEC 60255 : electrical measuring and protection relay IEC 60076-1 : power transformer JEC 1201 : zero phase transformer

Adapted various marine classification


American Bureau of Shipping (ABS) Det Norske Veritas(DNV) Bureau Veritas(BV) Germanischer Lloyds (GL) Lloyds Register of Shipping (LR) Nippon Kaiji Kyokai(NK)

Environmental specification vessel types


Ambient temperature 45 Relative humidity 95% Vibration (, in accordance with IEC 60092-504) all control devices 2 13.2Hz, interval of vibration1.0mm 13.2 100Hz, acceleration0.7g max. acceleration 0.7g

Vessel types
The HS21 switchboard is designed for use in: Offshore Plant Oil Rig supply vessels Floating Production Storage Offloading vessels (FPSO) Floating Storage Offloading vessels(FSO) LNG Carriers Large Passenger vessels Container ships Storage and Work Barges Floating Docks, Various Dredgers, etc

Arcing due to internal fault test

General specification
Basic specifications and panel size of 7.2 kV and 12 kV are the same (Refer to the following pages for panel size) Miniaturization rather than a conventional switchboard Abundant prepared optional equipment Type HS21-1 Application
Standard conformance Classification IEC 62271-200 (IEC 60092-508) 1) ABS, BV, DNV, LR, NK, GL and others

HS21-2

HS21-3

HS21-4

Rating
Rated voltage Rated frequency Rated power frequency withstand voltage Rated lightning impulse withstand voltage Rated short time withstand current Rated peak withstand current Internal arc withstand current Main bus bar current Load bus bar current 1250 A 600 A 20 kV/min 60 kV 25 kA 1sec (3sec) 2) 65 kA 25kA 0.2sec (20kA 1sec) 4) 2000 A 600/1000 A 1250 A 600 A 2000 A 600/1000 A AC 7.2 kV 50 / 60 Hz 28 kV/min 75kV AC 12 kV

Construction
Switchgear construction Degree of protection Metal-clad Low voltage compartment High voltage compartment IP32 IP42

Optional equipment 3)
- Inspection window - Arc gas exhaust duct - Earthing switch on main bus bar - Arc detecting system - Insulation tube cover on bus bar - Surge arrestor on main bus bar - IP33 of low voltage compartment protection - IP43 of high voltage compartment protection - Infrared rays window

Notes 1) ANSI C37.20.2 on request 2) 3 sec on request 3) Refer to the following pages about the details of optional equipment 4) With arc gas exhaust duct

Dimensions
Basic panel design (example)

600mm over

H1

H2

w
H2 : With open pressure relief flap

Panel type Generator panel Feeder panel Incoming panel GPT panel Motor panel Soft start motor panel Bus-tie panel 1 1) Bus riser & GPT panel Bus-tie panel 2 2) Sync panel ATr panel
Notes 1) LNG vessel only 2) Container vessel only

W (mm)

H1 (mm)

H2 (mm)

D (mm)

650 2300 800 900 1000 1000 2800 1680

Technical data
Typical unit
G F IC BT GPT

option

ATr

BRG

SM

G F IC BT GPT

Generator panel Feeder panel Incoming panel Bus-tie panel Grounded potential transformer panel

M ATr BRG SM

Motor panel Auto transformer panel Bus riser & GPT panel Soft start motor panel

An earthing switch can be provided in the GPT panel if required.

Vacuum circuit breaker and Vacuum contactor application


Panel types Generator panel Feeder panel Motor panel Incoming panel Soft start motor panel Bus-tie panel Applicable VCB 630A 1250A 2000A VCT 200/400A

Technical data
Cable entry plan
The HS21 switchboard standard cable entry is from the bottom. Power cables enter through the rear gland plate and control cables through the front gland plate. Top cable entry can be provided, but consultation with TERASAKI is recommended as panel dimensions will increase.
Bottom entry cable
Rear A

Power cable entry (example)

D E C 1680 mm B Bottom G F G C

J H Front

Panel type Standard panel 1) Bus riser & GPT panel Bus-tie panel Synch panel ATr panel

Width A(mm) 650 800 900 1000 1000 B(mm) 450 550 750

Power cable entry C(mm) D (mm) E (mm) F (mm) 450 550 125 140 150 650 750

Control cable entry G (mm) H (mm) J (mm)

125

140

200

Notes 1) Refer to 650mm panel width on Dimensionspage

Room planning
The room planning of installing HS21 in the switchgear room is shown below.
4 Rear 1 2 5 D

w
Front A

C
1...HS21 switchgear 2...Side aisle 3...Front operating space 4...Rear maintenance space 5...Switchgear room wall
C (mm) D (mm) 700 850 700 700

Panel width -W only 650 mm with 800 mm with 900 mm with 1000 mm

Room height (mm)

A (mm)

B (mm)

2900

1000

1600

1680

Metal-clad
Compartments
Each section of the HS21 metal-clad switchboard is separated into four compartments. Circuit breaker Main bus bar Cable terminations Low voltage equipment To withstand internal arc faults, segregation between compartments is achieved by the use of metal partitions. See picture below.

Low voltage compartment


The upper and lower low voltage compartments are located above and below the circuit breaker compartment. Cables routed through the circuit breaker compartment are protected by metal shielding.

Panel partitions
The compartment between each panel is divided by the metallic partition. Since each compartment have not penetrated between panels, other panels are not affected even when the accident happens by a certain panel. Moreover, when extending in the future, it can install easily.

Circuit breaker compartment


This compartment is equipped with a vacuum circuit breaker and contactor. The cradle is equipped with metal shutters. Draw-out and insertion of the circuit breaker can not be carried out without first satisfying the safety interlock procedure.

Main bus bar compartment


The main bus compartment is designed for 1250A and 2000A round-edged, tinned-copper bus bars. Insulation between panels is maintained by the use of track-resistant epoxy insulation materials. A fully insulated bus bar system can be provided if required.

Cable compartment
Standard cable entry is from the rear bottom. However, if required cable, entry can be from above, but the depth of the panel will increase. Access can not be gained to this compartment without first satisfying the safety interlock procedure of the switchboard. Also located within this compartment are: Earthing switch Zero-phase current transformer Surge arrestor Voltage and current transformers

Construction
Basic panel design (example)

16

1 2 3 4

D
17 18

26

27

19

5 20 14 6 7 8 9 11 12 13 10 21 28 22 15 23 29

A
24 25

Front view

Side view

Rear view

A 1 2 3 4 9

Low voltage compartment

Main bus bar compartment

: Upper door : Instrument : Protection and control unit : Switch : Lower door

16 : Pressure relief flap 17 : Insulation bushing 18 : Main bus bar

Circuit breaker compartment

Cable compartment

5 : Door of circuit breaker compartment 6 : VCB draw-in / out handle port 7 : Indicator of circuit breaker position 8 : VCB draw-in / out interlock key hole 10 : Emergency open mechanism 11 : Interlock key for de-excitation 12 : Earthing switch operating handle port 13 : Lower cable compartment door key 14 : Vacuum circuit breaker 15 : VCB cradle

19 : Surge arrestor 20 : Current transformer 21 : Load bus bar 22 : Power cable terminal 23 : Earthing switch 24 : Zero-phase current transformer 25 : Voltage transformer 26 : Upper door 27 : Upper cable compartment door key hole 28 : Lower door 29 : Lower cable compartment door key hole

Product description
Pressure relief flaps
To relieve pressure during an internal arc fault, pressure relief flaps are provided on the circuit breaker, bus bar and cable compartments at the positions shown.

Top panel
Pressure relief flaps

Insulation bushing
To maintain electrical characteristics and mechanical strength the three-phase single molding insulation bushings are manufactured using high-grade epoxy resin material. Specification
Rated voltage Rated power frequency withstand voltage Rated lightning impulse withstand voltage Over current strength 12 kV 28 kV / min 75 kV 25 kA 1sec (3sec) 1)

Insulation bushing

1) 3sec on request

VCB (VCT) cradle


The cradle is equipped with mechanical interlocking facilities on the basis of safety consideration. Metal shutters operate automatically on withdrawal or insertion of the VCB / VCT.

Metal shutters of VCB cradle

VCB cradle mechanism

Metal shutters on VCB cradle Circuit breaker grounding

Interlocks
Mechanical interlocking facilities satisfy demand of IEC62271-200. Descriptions of the HS21 switchboard interlocks are shown below. !. With metal-clad compartmented switchgear and controlgear, door should only be opened when the part of the main circuit contained in the compartment being made accessible is dead. @. They shall be provided with locking facilities, unless the safety of persons is assured by a suitable interlocking device. #. The withdrawal or engagement of a circuit breaker, switch or contactor shall be impossible unless it is in the open position. $. It shall be impossible to close the circuit breaker, switch or contactor in the service position unless it is connected to auxiliary circuit. %. When circuit breaker is a connect position, it isnt possible to do the ON position of earthing switch.

Interlock release procedure for maintenance (example)


step1 step2 step3

Circuit breaker open

Turn CB draw-in / out interlock key Circuit breaker draw-out

step4

step5

step6

Remove rear panel Open CB compt door ( in case of CB maintenance ) Turn and remove lower cable compt door key

Earthing switch ON

step7

step8

step9

Cable compt door open Open lower door Turn lower cable compt door key Turn and remove upper cable compt door key Remove upper door Turn upper cable compt door key

10

Components
Vacuum circuit breaker HVF
Applicable standards
The HVF vacuum circuit breakers meet all the requirements of IEC 62271-100 and the other applicable standards.
Manual spring charge port

Vacuum circuit breaker HVF


Control jack

Service life time


HVF vacuum circuit breaker operating mechanism features reduced maintenance requirements, providing a long-life expectancy of 30,000 operations. Because of the small amount of contact erosion, contact life is increased to 20,000 operations for the rated normal current.
Charge / discharge indicator Open / close indicator Operations counter Position handle Manual open button Manual close button

Maintenance free
The circuit breaker require little maintenance. In fact, only the parts subject to normal wear and aging must be serviced to ensure fully reliable operation. This involves simple jobs carried out by the customers personal with short servicing times and corresponding downtimes and also long operation periods between servicing. Maintenance is confined to lubricating the operating mechanism. The vacuum interrupters and their supports need not be serviced.

Upper contact

Vacuum interrupter

Rapid load transfer, synchronizing and operating duty


With its consistent short closing and opening times, the HVF is especially beneficial in load transfer from one circuit to another without interruption of service. This high speed operation synchronizes the systems so that they are parallel at the moment of contact closure. According to the relevant standards, tests were carried out for the following operation duty. O - 0.3s - CO - 3min - CO (for auto-reclosing)

Lower contact

HVF breaker on cradle

Switching upload transformers


By using special contact materials, the chopping current of the vacuum circuit breakers is only 4 to 5A. This means that no dangerous over voltages arise when unloaded transformers are disconnected. Specification
Type Rated voltage Rated current Rated frequency Rated short circuit breaking current Rated short circuit making current Rated short time withstand current Rated control circuit voltage 630 A HVF-104/ HVF-204 7.2 / 12 kV 1250 A 50 / 60 Hz 25 kA 65 kA 25 kA 3sec DC 110V
1)

2000 A

1) Type number in the square

z ...630A, x...1250A, c...2000A

11

Components
Vacuum contactor HCA
Applicable standard
The HCA vacuum contactor is manufactured in accordance with international standard IEC 62271-106.

Vacuum contactor HCA (with single fuse)


ON / OFF indicator

Service life time


HCA vacuum contactor operating mechanism features reduced maintenance requirements, providing a long-life expectancy of 1,000,000 operations.

Operations counter

Control jack Position handle

Contact inspection
Inspection of contacts for wear can be easily carried out by removal of the front plate and examination of the maximum contact wear point (2mm) marked in white on the contact. If the contacts are eroded below this mark, the vacuum interrupter should be immediately replaced. Specification
Type Rated voltage Rated frequency Rated current Rated short circuit breaking current (with power fuse) Rated short time current Rated control circuit voltage Max motor capacity HCA-6C1) 7.2 kV 50 / 60 Hz 200 A 400 A 40 kA 3.2 kA 1sec AC / DC 110V 1500kW 3000kW

Upper contact

Fuse

Lower contact

1) Type number in the square HCA-C 2...200A, 4...400A F...fixed type without fuse J...fixed type with fuse (double) A...fixed type with fuse (single) B...draw-out type without fuse D...draw-out type with fuse (single) H...draw-out type with fuse (double)

HCA contactor on cradle

Earthing switch
The earthing switch is located on the VCB/VCT cradle and has a making current capacity rating that ensures maximum possible protection for the operator in case of an error. Specification
Rated voltage Rated short time withstand current withstand voltage Rated short circuit making current withstand voltage 12 kV 25 kA 3sec 63 kA

Earthing switch

12

Components
Multi protection and control unit HIMAP-BCG
General characteristic
The multi protection and control unit HIMAP-BCG is a bay control unit supplying Power Management System. Nowadays our customers have required much more integrated multi protection relay, monitoring, control devices and power management for better and easier maintenance, performance, electrical system analysis and communication according to new trend of switchboard. HIMAP-BCG supplies those requirements of customers with easy handling and operation. HIMAP-BCG provides a graphic display with rear-lit LCD and push buttons as HMI (Human Machine Interface). HIMAP-BCG provides the parameter setting program, control setting program, various editors and fault recording and analysis program on Windows / 95 / 98 / NT / 2000 / XP for HMI. In addition, HIMAP-BC can be set manually and this manual setting function helps user to interface easily .

Multi protection and control unit HIMAP-BCG

Protections
This protection functions are based on the IEC60255. HIMAP-BCG has non-volatile Flash Memory that can store data safely. The Flash Memory reserves the data regardless of disturbance or electromagnetic wave. In addition to this Flash Memory can store a lot of backup data through a mirror effect.
- ANSI 25 ... Auto synchronizing - ANSI 27 ... Under voltage - ANSI 32 ... Reverse power - ANSI 50 ... Over current - ANSI 51 ... Time delay over current - ANSI 59 ... Over voltage relay - ANSI 64 ... Over voltage ground relay - ANSI 67 ... Directional over current relay - ANSI 87 ... Generator differential protective relay - ANSI 86 ... Lock out relay and more...

Power management system


The power management function in HIMAP-BCG controls and coordinates the load sharing on a busbar from several parallel generators. HIMAP-BCG can manage a maximum of 4 independent networks separated by tie-breakers. Each network works on its own power management control simultaneously with the other networks. The power management contains the load-dependant start and stop, as well as the symmetrical load sharing of generators. This means all generators will share their load in such a way as to have the same percentage of their own nominal rated power supplied to the same network. Each network can be assigned and prioritized by function input. HIMAP-BCG is equipped with a power management system that includes automatic connection to big consumers for controlling the entire mains system. Due to its modular structure, the system is not influenced by any central control unit. Since a HIMAP-BCG is assigned to each generator panel, all generator panels are identically constructed. A two-wire CAN bus communication connects the HIMAPBCG to each other. In case of the failure of one HIMAP-BCG, the others will continue operating.Each HIMAP-BCG incorporates all important functions necessary for the power management. Thus, the system of independent and autonomous electric engines has been consistently developed for switching gears, control and monitoring (modular independent systems). HIMAP-BCG has various pages for power management to access the power management system via HIMAP-BCG.The power management system with HIMAP-BCG doesnt mean the load depending start/stop only. It has the following functions for power management:
- Synchronizing - Load sharing - Frequency control - Load shedding (Preferential trip) - Load depending start / stop - Load calculation for big motor start - Protections - Power factor (cos) control - Asymmetrical power factor (cos)control - Voltage regulating - Engine control with alarm and priority

13

Components
Measuring function
HIMAP-BCG supplies each analogous data pages for measuring as follows.
- 3-phase current - 3-phase voltage - Measured and calculated grand voltage - Measured and calculated grand current - Two different 3-phase bus bar voltages - Frequency and power factor - Power meter page - Active power, reactive power - Working current - Harmonic wave - Operating value - Synchronizing

Control function
HIMAP-BCG provides breaker functions. These functions can be set manually also allowing customers to conveniently handle HIMAP-BCG without a PC and downloading program (Flash Loader). Of course, HIMAP-BCG requires a password or transponder card to access these functions. HIMAP-BCG is applied to various ship systems. Customers can select the graphic they want to apply. HIMAP-BCG has various graphic modes for each piece of electrical equipment or feeder. HIMAP-BCG also has an interlock between switching devices.

Alarm / Event control functions


HIMAP-BCG provides detailed information about events, alarms and interlocks. By use of this information, and a historical data system, trend can be analyzed.

Data recording functions


One of the most important function of HIMAP-BCG is extended fault recording function. HIMAP-BCG has additional CPU for this extended function as optional.

Diagnostics and Monitoring


Diagnostics and supervision are very important functions of the bay controller.

Panel automation
HIMAP-BCG provides convenient and perfect interlocking system for control logic of switchboard. In order to realize this function, HIMAP-BCG sensors position of each switching device and provides the position indication in feeder graphic. Every switching device can be controlled by HIMAP-BCG locally or remotely .

Parameter setting program


HIMAP-BCG supplies program for easy setting of parameters. Several categories simplify page setting.

Specification
Type Standard conformance Certifications Control power supply Communication HIMAP-BCG IEC 60255 ABS, BV, DNV, GL, LRS DC 24V / DC 110V / AC 110V AC 220V RS232C, CANbus, MODbus

Communication
HIMAP-BCG system treats very large data like as data recording or parameter data files via various communication systems in itself. The relevant signal is acknowledged in the related function.

Extension boards CMA


The extension board is used when additional input / output is required.

Extension boards CMA

14

Components
Generating plant management system GAC21
General characteristic
The GAC21 Generating Plant Management System is designed to be reliable and user friendly. The system design is based on TERASAKIs experience as a dedicated manufacturer of generator control technology and multiplex transmission systems that have successfully been supplied to a large number of marine projects for many years. The GAC21 System is a function-dispersed type system that is designed to operate using its PLC (programmable logic controller). It consists of two control units, the GAC21 Automatic Generator Controller and the Type EAS-101 Automatic Digital Synchroniserand can be utilized with up to a maximum of 5 generators.

PLC (programmable logic controller)


Power module CPU module other module

Specification
Type Standard conformance Control power supply CPU Processing speed Program memory Module function No. of controlled generators Communication Micrex-SX IEC 61131 DC 24V (+30% to -25%) 32 bit processor 20 to 520 ns 32 k step analog input / output, digital input / out put, communication Max. 5 RS232C, RS485, TM, SX-BUS, P-link

PLC (programmable logic controller)


The GAC21 automatically controls generators using its programmable logic controller. It covers the management of the entire generating plant, including the automatic load sharing function, automatic start, automatic switching and power management. Control parameters and settings can be easily modified using the device provided with every GAC21 system.

TM ... TERASAKI multiple transmission system SX-BUS, P-Link ... Fuji Electric original high speed data link system

Automatic digital synchronizer EAS-101


The EAS-101 digital synchronizer has the following features: 1. A single chip CPU enables this product to be very small and light in weight. Simple program control allows flexibility performing synchronous closing and detection control. 2. The system has a self-diagnostic capability. 3. For voltage detection, an effective value detection circuit is used to avoid the situation of disabled synchronous closing due to harmonic waveform distortion. 4. Automatic and check synchronizing functions are available.

Automatic digital synchronizer EAS-101

Specification
Type Control power supply Rated frequency Closing time of circuit breaker Limit of frequency difference for closing Limit of voltage difference for closing Maximum frequency difference for operation EAS-101 AC 110V (+10% to -15%) 50 / 60 Hz (+5% to -5%) 0 to 500 ms 0.1 to 0.5 Hz 2.0 to 10.0 % 8 Hz

15

Components
Feeder, incoming, transformer protection relay HIMAP-FI/T
General characteristic
HIMAP is a multifunctional digital protection relay to protect incoming, feeder and transformer lines. Communication facilities are provided to enable measuring functions to be monitored remotely and power management systems to operate automatically. HIMAP has a self-diagnosis function. Display of any internal malfunction can be shown on the integral display and also transmitted to a remote alarm system. HIMAP has a digital filter to prevent malfunctions caused by harmonic frequencies in supply lines. Specification
Type Control power supply Protect function Communication HIMAP-FI (feeder, incoming) ANSI 27, 50/51, 59, 64, 67 HIMAP-T (transformer) ANSI 50/51, 67, 87 AC 110V / AC 220V / DC 110V / DC 220V RS232C, RS485 HDLC

Protection relay HIMAP-FI/T

Motor protection relay MPR-6-DGF


General characteristic
The MPR-6-DGF motor protection relay is a new generation of microprocessor based relay designed to protect three phase induction motors. The MPR-6-DGF incorporates two main functions. a. Motor protection b. Supervision and communication

Motor protection

Motor protection relay MPR-6-DGF

AC motors are very rugged and reliable when operating within their limit. However, they are usually designed to operate close to their rated limits with minimal margins for operating under abnormal conditions. A comprehensive protection device is required to accurately create a thermal model for the motor to run safely up to its limits. This relay should protect the motor from abnormal conditions in the power supply, motor and cable faults as well as operator malfunctions. The MPR-6-DGF monitors three phase currents (true RMS line currents are measured at a sampling rate of 0.5m sec). The MPR-6DGF monitors ground fault current (true RMS) and zero sequence voltage (3Vo), for Directional Ground Fault protection. The MPR-6Specification DGF monitors three temperature (RTD or PTC/NTC thermistor) inputs. Type All together the MPR-6-DGF provides a comprehensive protection Control power supply package. Communication

MPR-6-DGF DC 110V RS485(MODbus)

Protections
- ANSI 47 ... Phase sequence - ANSI 48 ... Maximum start time - ANSI 51L ... Load increase - ANSI 49S/51 ... Thermal level (Overload) - ANSI 50/51R ... stall and short circuit /over current jam - ANSI 66 ... Start inhibit - ANSI 67 ... Directional over current - ANSI 46 ... Unbalanced current - Temperature (3 sensors) ... RTD Pt.100 or PTN / NTC thermistor - External fault 1 ... N.O / N.C contacts - External fault 2 ... N.O / N.C contacts

Actual data
Phase current, ground fault current and thermistor resistance, Motor load in % of FLC, Thermal capacity, Time to trip, Time to start, Unbalance current.

Communication
RS485 serial link with MODbus communication protocol, operating at a baud rate of 1200 to 9600 bits/sec enables monitoring of set-points and actual parameters. The serial link enables remote control of both the MPR-6-DGF and the motors.

16

Optional equipment
HS21 prepares the various option equipment to improve safety more. The list of the option equipment is shown below.

Inspection window

IR Window

Inspection window
Installed in the circuit breaker compartment door when visual confirmation is required by ships staff of the operating position of the circuit breaker.

IR Window
Using Thermography enables temperature measurement of busbar without opening the closed compartment.

Arc detecting system


Detection of an internal arc fault utilizing a light sensitive device (or current monitor) to detect arc flash. This enables the circuit breaker to open in the shortest possible time thereby minimizing damage to the switchboard.
CB compartment door Cable compartment door

Arc detecting system

Arc gas exhaust duct


Should be used to divert arc gases to a safe location in the event of an internal arc fault.

Fully insulated bus bars


This system affords additional insulated protection. Insulated tube on bus bar and boots are fitted to all bus bar connection points.
Option

Arc detecting device

Insulation boots

Arc gas exhaust duct Earthing switch on main bus bar


If the customer requires additional safety, an earthing switch can be provided for the main bus bar.

Fully insulated bus bars

Surge arrestor on main bus bar


Additional protection can be provided on the main bus bar by the fitting of surge arrestors.

17

Accessories
The accessories provided as standard are shown below.

Lifter

Circuit breaker lifter


Used to assist in the removal of the circuit breaker, contactor etc. Specification
Height Width Depth 1850 mm 770 mm 1241 mm

Vacuum checker

Circuit breaker draw-in/out handle


Used to assist in the withdrawal and insertion of the VCB and VCT.

Circuit breaker charge handle


Used to charge the closing spring of the circuit breaker.

Circuit breaker draw-in/out handle

Earthing switch operating handle


Used for earth switching operations.

Earthing switch operating handle

Vacuum checker
Used for check the vacuum degree. Specification
Input voltage Out-put voltage Weight AC 200 / 220 V AC 11 kV / 22 kV 22kg

Circuit breaker charge handle

Memo

18

TERASAKI Global Service Network


service & supply
TERASAKI ELECTRIC (EUROPE) LTD. TERASAKI ELECTRIC EUROPE GTI WEST INDUSTRIES BV MARINE & OFFSHORE KOREA ENGINEERING SYSTEM CO., LTD.

AMERICAN TERATEC INC. TERATEC LTD.

TERASAKI (MIDDLE EAST)

TERASAKI ELECTRIC (CHINA) LTD. TERASAKI ELECTRIC CO., (F.E.) PTE. LTD.

NOVAMARINE INSTRUMENTS PTY. LTD.

TERASAKI DO BRASIL LTDA.

TERATEC LTD.
7-9-10 Hannancho, Abeno-ku, Osaka, 545-0021, JAPAN Te l : +81 6 6693 6974 : +81 6 6693 6971 Fax: +81 6 6693 7116 : +81 6 6693 1716 E-Mail parts: [email protected] E-Mail maintenance: [email protected] Web site: http://www.teratec.co.jp Main Service & Spares Centre

I.S.E.S. members worldwide can also provide service required.

TERASAKI (MIDDLE EAST)


Lob 6, Office 13 Jebel Ali Free Zone P.O.Box 261080 Dubai, U.A.E. Te l : +971 4 881 2242 Fax: +971 4 881 2243 E-Mail: [email protected] Covering Middle East

TERASAKI ELECTRIC (EUROPE) LTD.


79 Beardmore Way, Clydebank, industrial Estate, Clydebank, Glasgow Scotland (UK) Te l : +44 141 941 1940 Fax: +44 141 952 9246 E-Mail: [email protected] Web site: www.terasaki.com Covering Europe, Africa

AMERICAN TERATEC INC.


PO Box 479, 92 North Main Street. Building 18-D Windsor, NJ. 08561-0479, USA Te l : +1 609 443 5551 Fax: +1 609 443 5590 E-Mail: [email protected] Web site: www.teratecusa.com Covering North & Central America

TERASAKI ELECTRIC CO., (F.E.) PTE. LTD.


23 Bukit Batok Street 22, Singapore 659590 Te l : +65 6561 1165 Fax: +65 6561 2166 E-Mail: [email protected] Web site: www.terasaki.com.sg Covering South East Asia

GTI WEST INDUSTRIES BV MARINE & OFFSHORE


Sluisjesdijk 37 3087 AD Rotterdam The Netherlands Te l : +31 10 28 31 844 Fax: +31 10 40 95 005 E-Mail: [email protected] Web site: www.gti-group.com Covering The Netherlands

TERASAKI ELECTRIC (CHINA) LTD.


72 Pacific Industrial Park, Xing Tang Zengcheng, Guangzhou 511340, China Te l : +86 20 8270 8556 Fax: +86 20 8270 8586 E-Mail: [email protected] Covering China

NOVAMARINE INSTRUMENTS PTY. LTD.


30 Downie Street, Newcastle 2293 Australia Te l : +61 2 4969 4477 Fax: +61 2 4962 1210 E-Mail: [email protected] Web site: www.novamarine.com.au Covering Oceania

TERASAKI DO BRASIL LTDA.


Rua Coldovil 259-Parada De Lucas, Rio De Janeiro-RJ Brasil Te l : +55 21 3301 9898 Fax: +55 21 3301 9861 E-Mail: [email protected] Web site: www.terasaki.com.br Covering South America

KOREA ENGlNEERlNG SYSTEMS CO., LTD.


327-4 Mugeo-Dong, Nam-ku Ulsan Korea Te l : +82 52 222 7773 Fax: +82 52 222 7774 E-mail: [email protected] Covering Korea

Head Office Osaka Sales Office Tokyo Sales Office

7-2-10 Hannancho, Abenoku, Osaka 545-0021, Japan Tel. International +81-6-6692-1131 Fax. +81-6-6692-2122 http://www.terasaki.co.jp/ 7-2-10 Hannancho, Abenoku, Osaka 545-0021, Japan Tel. International +81-6-6692-1241 Fax. +81-6-6694-5490 E-mail: [email protected] Nikko Kayabacho Building 5F, 1-6-10, Kayabacho, Nihonbashi, Chuo-ku, Tokyo 103-0025, Japan Tel. International +81-3-5644-0150 Fax. +81-3-5644-0155

Certified ISO9001

Kyusyu Sales Office 3798-4 Kubara, Yamashiro-Cho, Imari-City, Saga Pref 849-4256, Japan Tel. International +81-955-20-2175 Fax. +81-955-20-2177 Shanghai Office Hamburg Office Room No.1405-6, Tomson Commercial Building, 710 Dong Fang Road, Pudong Shanghai 200122, China Tel. International +86-21-58201611 Fax. +86-21-58201621 E-mail: [email protected] Anderheitsallee 4c, D-22175 Hamburg, Germany Tel. International +49-40-55-611-911 Fax. +49-40-55-611-912 E-mail: [email protected] Certified ISO14001

FEB.2007-1.0K
Ratings and specifications covered in this brochure may be subject to change without notice. Made from 100% recycled paper.

Printed in JAPAN

You might also like