Ferraz Shawmut IEC Fuses

Download as pdf or txt
Download as pdf or txt
You are on page 1of 97

General Purpose Fuses IEC

General Purpose Fuses IEC


General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM & gG 400V to 690V
with/without Striker
aM & gG 8x32, 10x38, 14x51, 22x58

Residential and Industrial


Cylindrical Fuse-links
Ferraz Shawmut gF/gG-gG and aM fuse-links cover
a wide range of physical sizes and ampere ratings
for 250, 380*/ 400, 500, and 660* 690volts AC.
gF/gG fuse-links are for residential use. gG and aM
fuse-links are for industrial applications. Most
ratings are available with an optional indicator. All
industrial fuse-links have the option of a built-in
striker. All cylindrical fuse-links have ceramic bodies
and silver-plated ferrules.

* Fuse-links marked 380V (gF/gG) and 660V (gG-aM) will be


re-marked (and safely used at ) 400V AC and 690V AC in
compliance with changes in IEC Standard 269, but should
not be used above 418V AC or 726V AC.

gF/gG gG gG aM aM
Residential Full Range Full Range Short Circuit Short Circuit
Full Range Protection Protection Protection Protection
Protection
Fuse-links • 4 physical sizes Fuse-links
• 7 physical sizes • 4 physical sizes with striker from 8 x 31 mm with striker
from 6.3 x 23mm from 8 x 31mm to 22 x 58 mm
to 10.3 x 38 mm to 22 x 58 mm • 2 sizes- • 2 sizes -
14 x 51mm 14 x 51mm and
• 250 and 380 Volt • 400, 500 and 22 x 58mm
• 400, 500 and 690 and 22 x 58 mm
ratings - 0.5A 690 Volt ratings-
Volt ratings -0.5A 0.16A through
through 32A through 125A • 400, 500 and • 400, 500 and
690 Volt ratings 125A 690 Volt ratings
• Most ratings • Most ratings 4A through 125A - 2A through
available with • Most ratings 125A
available with available with
indicator indicator • All ratings
include striker indicator • All ratings
• Meet IEC, NFC, • Meet IEC, NFC include striker
UNE standards • Meet IEC, • Meet IEC, NFC
and UNE and UNE
standards NFC and UNE • Meet IEC, NFC
• See residential standards standards and UNE
fuse-links, Special • Approved by standards
Purpose section • Approved by • Approved by
Lloyds Register Lloyds Register
of Shipping and Lloyds Register of • Approved by
Shipping and of Shipping and Lloyds Register
Bureau Veritas Bureau Veritas
Bureau Veritas of Shipping and
Bureau Veritas

GPEU2
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58
Ratings - gG (Optional Blown-Fuse Indicator)
Size Rated In Rated Previous References Reference Number Breaking Catalog Number
Current (A) Voltage w/o w w/o w Capacity w/o w
Indicator Indicator Indicator Indicator Indicator Indicator
0.5 15009 - P218191 - FR8GG40V0.5
1 15011 - C218709 FR8GG40V1
2 15013 15213 Q219227 B222204 FR8GG40V2 FR8GG40V2I
4 15019 15219 W222958 X222959 FR8GG40V4 FR8GG40V4I
6 15023 15223 A211025 V201291 FR8GG40V6 FR8GG40V6I
8 x 31 8 400V 15027 15227 B213096 B211026 20kA - 400V FR8GG40V8 FR8GG40V8I
10 15031 15231 A214613 A212060 FR8GG40V10 FR8GG40V10I
12 15033 15233 R216146 C213097 FR8GG40V12 FR8GG40V12I
16 15035 15235 P216650 Y214105 FR8GG40V16 FR8GG40V16I
20 15037 15237 F217677 J215127 FR8GG40V20 FR8GG40V20I
25 15039 15239 D218710 S216147 FR8GG40V25 FR8GG40V25I
0.5 16009 - C211027 - FR10GG50V0.5 FR10GG50V2I
1 16011 - B212061 - FR10GG50V1 FR10GG50V4I
2 16013 16213 D213098 S216653 FR10GG50V2 FR10GG50V6I
4 16019 16219 X213598 E217170 FR10GG50V4 FR10GG50V10I
6 16023 16223 K215128 T218195 FR10GG50V6 FR10GG50V10I
10 X 38 8 500V 16027 16227 D217169 V219231 120kA - 500V FR10GG50V10 FR10GG50V12I
10 16031 16231 S218194 E222207 FR10GG50V10 FR10GG50V16I
12 16033 16233 W219761 H200751 FR10GG50V12 FR10GG50V20I
X211551 16 16035 16235 G200750 H201809 FR10GG50V16 FR10GG50V25I
20 16037 16237 D211028 X211551 FR10GG50V20 FR10GG50V32I
25 16039 16239 E213099 W212585 FR10GG50V25 FR10GG50V2I
32 400V 16043 16243 A214107 Z213600 120kA - 400V FR10GG50V32 FR10GG50V4I
1 17011 - K218716 - FR14GG69V1
2 17013 17213 Y219234 C201298 FR14GG69V2 FR14GG69V2I
4 17019 17219 A219765 H211032 FR14GG69V4 FR14GG69V4I
6 17023 17223 H222210 G212066 FR14GG69V6 FR14GG69V6I
8 17027 17227 D222965 K213104 FR14GG69V8 FR14GG69V8I
10 17031 17231 L200754 H214620 FR14GG69V10 FR14GG69V10I
14 X 51 12 690V 17033 17233 L201812 R215640 80kA - 690V FR14GG69V12 FR14GG69V12I
16 17035 17235 A211554 X216657 FR14GG69V16 FR14GG69V16I
20 17037 17237 Z212588 N217684 FR14GG69V20 FR14GG69V20I
25 17039 17239 C213603 M218718 FR14GG69V25 FR14GG69V25I
M218718
32 500V 17043 17243 W216656 C219767 FR14GG69V32 FR14GG69V32I
40 17047 17247 X218198 F222967 120kA - 500V FR14GG69V40 FR14GG69V40I
50 400V 17051 17251 Z219235 D201299 120kA - 400V FR14GG69V50 FR14GG69V50I
2 18013 - F219241 - FR22GG69V2
4 18019 18219 H219772 Q211039 FR22GG69V4 FR22GG69V4I
6 18023 18223 P222216 P212073 FR22GG69V6 FR22GG69V6I
8 18027 18227 L222972 R213110 FR22GG69V8 FR22GG69V8I
10 18031 18231 T200761 N214119 FR22GG69V10 FR22GG69V10I
12 18033 18233 J201304 Y215140 FR22GG69V12 FR22GG69V12I
16 18035 18235 S201818 D216157 FR22GG69V16 FR22GG69V16I
20 18037 18237 P211038 R217181 FR22GG69V20 FR22GG69V20I
22 x 58 25 690V 18039 18239 N212072 F218206 80kA - 690V FR22GG69V25 FR22GG69V25I
32 18043 18243 F212594 H219243 FR22GG69V32 FR22GG69V32I
40 18047 18247 J213609 R222218 FR22GG69V40 FR22GG69V40I
K211563 50 18051 18251 P214626 W200763 FR22GG69V50 FR22GG69V50I
63 18055 18255 Y215646 V201820 FR22GG69V63 FR22GG69V63I
80 18059 18259 Q217180 K211563 FR22GG69V80 FR22GG69V80I
100 500V 18063 18263 E218205 H212596 120kA -500V FR22GG69V100 FR22GG69V100I
125 400V 18065 18265 J219773 L213611 120kA -400V FR22GG69V125 FR22GG69V125I
Packaging 10

Blown-Fuse Indicator Dimensions


Fuse Size A B C
8 x 31 8.5 31.5 6.3
10 x 38 10.3 38 10.5
14 x 51 14.3 51 13.8
22 x 58 22.2 58 16.2
BEFORE AFTER

GPEU3
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58

Ratings – gI-gG with Striker


Size Rated Rated Previous Reference Breaking Catalog
(mm x mm) Current In Voltage Reference Number Capacity Number
(A)
2 17413 J211033 FR14GG69V2P
4 17419 H212067 FR14GG69V4P
P201815
6 17423 G214113 FR14GG69V6P
8 17427 R215134 FR14GG69V8P
10 17431 Z216153 FR14GG69V10P
12 17433 L217176 FR14GG69V12P
14 X 51 16 500V 17435 Z218200 120kA - 500V FR14GG69V16P
20 17437 B219237 FR14GG69V20P
25 17439 L222213 FR14GG69V25P
32 17443 P200757 FR14GG69V32P
40 17447 P201815 FR14GG69V40P
R212075 50 400V 17451 D211557 120kA - 400V FR14GG69V50P
4 18419 R214628 FR22GG69V4P
6 18423 A215648 FR22GG69V6P
8 18427 F216665 FR22GG69V8P
10 18431 W217691 FR22GG69V10P
12 18433 W218726 FR22GG69V12P
16 18435 L219775 FR22GG69V16P
22 X 58 20 690V 18437 P222975 80kA - 690V FR22GG69V20P
25 18439 M201307 FR22GG69V25P
32 18443 S211041 FR22GG69V32P
40 18447 R212075 FR22GG69V40P
50 18451 M213612 FR22GG69V50P
63 18455 S214629 FR22GG69V63P
80 18459 F216159 FR22GG69V80P
100 500V 18463 T217183 120kA - 500V FR22GG69V100P
125 400V 18465 H218208 120kA - 400V FR22GG69V125P
Packaging 10

Dimensions Striker
Fuse Size A B C D E
14 x 51 14.3 51 13.8 7.5 3.8
22 x 58 22.2 58 16.2 7.5 3.8 1 Ceramic body BEFORE AFTER
2 Sand
3 Indicator contact
4 Lower contact
5 Contact ring
6 Melting element
7 Indicator

Neutral
Size Previous Reference Standard Catalog
(mm x mm) Reference Number Pack/CTN Number

10 x 38 19100 R211569 FRN1038


14 x 51 19200 M212600 10 FRN1451
22 x 58 19300 R213616 FRN2258

GPEU4
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58

Characteristics t-l
PREARCING TIME T(S)

PROSPECTIVE CURRENT (A rms)

Cut-off characteristics
MAXIMUM VALUE OF CURRENT (KA PEAK)

PROSPECTIVE CURRENT (kA rms)

GPEU5
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58

Characteristics I2t

8
6
5
4 gG
3
2

8
6
5
4
3

}
2
690 V
8
6
500 V - OPERATING I2T
5
4
3 400 V

{
2

- PREARCING I2T
8
6
5
4
3
2

8
6
5
4
3
2

Table temperature increase (testing in superior contact)


ºC

100

90

80

70

60

50

40

30

20

10

2 4 6 8 10 12 16 20 25 32 2 4 6 8 10 12 16 20 25 32 40 50 16 20 25 32 40 50 63 80 100 125 In
10 x 38 14 x 51 22 x 58

GPEU6
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58

Power loss table


Size
In
10 x 38 14 x 51 22 x 58

0,5 A 2W
1A 2,5 W 3,4 W
2A 0,70 W 1W 1,20 W
4A 0,80 W 1,10 W 1,30 W
6A 0,90 W 1,20 W 1,40 W
8A 1,10 W 1,50 W 1,65 W
10 A 1,35 W 1,80 W 2W
12 A 1,55 W 2,10 W 2,40 W
16 A 1,90 W 2,55 W 3W
20 A 2,30 W 3W 3,40 W
25 A 2,80 W 3,50 W 3,80 W
32 A 3W 3,80 W 4,30 W
40 A 4,40 W 5,10 W
50 A 4,7 W 5,50 W
63 A 6,70 W
80 A 8W
100 A 9W
125 A 12,5 W

Maximum standardized 10 x 38 14 x 51 22 x 58
power low. IEC 269-2-1
NFC 63.213 25 A 40 A 100 A
UNE 21.103-2-1
3W 5W 9,5 W

Table of maximum length of network in function of In and conductor section.


Maximum standardized power low.

gG Class Fuses

Copper conductor Rated Current (In) OF gG Fuses (in A)


section (mm2)

16 20 25 32 40 50 63 80 100 125
1,5 99/113 86/87 40/59 21/29 13/16 7/9
2,5 134 110/122 67/84 41/51 25/33 13/20 8/11
4 183 139 108/119 67/84 46/58 24/32 14/17 7,3/10
6 214 165 139 94/113 55/70 33/41 20/27
10 275 226 172 130 90/108 57/70
16 283 217 168 128
25 336 257 197
35 367 283
50 379
* 99/118:
- 99; Cond. PVC / 118; Cond. PRC GPEU7
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58
Ratings – aM (Optional Blown-Fuse Indicator)
Size Rated In Rated Previous Reference Reference Number Breaking Catalog Number
(mm x mm) Current (A) Voltage w/o w w/o w Capacity w/o w
1 Indicator Indicator Indicator Indicator Indicator Indicator
15511 - C217168 - FR8AM40V1
2 15513 - R218193 - FR8AM40V2
S219229 4 15519 - S219229 - FR8AM40V4
8 x 31 6 400V 15523 - C222205 - 20kA - 400V FR8AM40V6
8 15527 - F200749 - FR8AM40V8
10 15531 - W201292 - FR8AM40V10
0.16 16503 - E214617 - FR10AM50V0.16
0.25 16507 - M215130 - FR10AM50V0.25
F214618 0.5 16509 - W216150 - FR10AM50V0.5
1 16511 16711 F217171 X219233 FR10AM50V1 FR10AM50V1I
2 16513 16713 H218714 G222209 FR10AM50V2 FR10AM50V2I
4 16519 16719 W219232 K200753 FR10AM50V4 FR10AM50V4I
6 16523 16723 F222208 K201811 FR10AM50V6 FR10AM50V6I
10 X 38 8 500V 16527 16727 Z201295 Z211553 120kA - 500V FR10AM50V10 FR10AM50V10I
10 16531 16731 Y211552 H213102 FR10AM50V10 FR10AM50V10I
12 16533 16733 A213601 D214110 FR10AM50V12 FR10AM50V12I
16 16535 16735 F214618 P215132 FR10AM50V16 FR10AM50V16I
20 16537 16737 X216151 V216655 FR10AM50V20 FR10AM50V20I
25 400V 16539 16739 G217172 L217682 120kA - 400V FR10AM50V25 FR10AM50V25I
32 400V 16543 - J218715 - 120kA - 400V FR10AM50V32
0.25 17507 - B212590 - FR14AM69V0.25
0.5 17509 - L213105 - FR14AM69V0.5
1 17511 17711 E213605 C212591 FR14AM69V1 FR14AM69V1I
2 17513 17713 H214114 M213106 FR14AM69V2 FR14AM69V2I
Q217686 4 17519 17719 K214622 J214115 FR14AM69V4 FR14AM69V4I
6 17523 17723 S215135 T215136 FR14AM69V6 FR14AM69V6I
8 17527 17727 T215642 A216660 FR14AM69V8 FR14AM69V8I
10 17531 17731 Z216659 R217687 FR14AM69V10 FR14AM69V10I
14 X 51 12 690V 17533 17733 M217177 Q218721 80kA - 690V FR14AM69V12 FR14AM69V12I
16 17535 17735 Q217686 F219770 FR14AM69V16 FR14AM69V16I
20 17537 17737 P218720 R200759 FR14AM69V20 FR14AM69V20I
25 17539 17739 E219769 Q201816 FR14AM69V25 FR14AM69V25I
32 17543 17743 M222214 F211559 120kA - 500V FR14AM69V32 FR14AM69V32I
40 500V 17547 17747 Q200758 D212592 FR14AM69V40 FR14AM69V40I
45 17549 17749 L211035 G213607 FR14AM69V45 FR14AM69V45I
50 400V 17551 17751 E211558 M214624 120kA - 400V FR14AM69V50 FR14AM69V50I
1 18511 - M219776 - FR22AM69V1
2 18513 - T222220 - FR22AM69V2
4 18519 18719 Q222976 L219246 FR22AM69V4 FR22AM69V4I
6 18523 18723 Y200765 V222221 FR22AM69V6 FR22AM69V6I
8 18527 18727 N201308 Y201823 FR22AM69V8 FR22AM69V8I
10 18531 18731 X201822 N211566 FR22AM69V10 FR22AM69V10I
12 18533 18731 T211042 K212598 FR22AM69V12 FR22AM69V12I
C215650 16 18535 18735 M211565 P213614 FR22AM69V16 FR22AM69V16I
22 x 58 20 690V 18537 18737 S212076 V214631 80kA - 690V FR22AM69V20 FR22AM69V20I
25 18539 18739 J212597 D215651 FR22AM69V25 FR22AM69V25I
32 18543 18743 V213113 J216668 FR22AM69V32 FR22AM69V32I
40 18547 18747 N213613 Z217694 FR22AM69V40 FR22AM69V40I
50 18551 18751 R214122 P219778 FR22AM69V50 FR22AM69V50I
63 18555 18755 C215650 Z200766 FR22AM69V63 FR22AM69V63I
80 18559 18759 H216667 P211567 FR22AM69V80 FR22AM69V80I
100 500V 18563 18763 Y217693 L212599 120kA - 500V FR22AM69V100 FR22AM69V100I
125 400V 18565 18765 J218209 W214632 120kA - 400V FR22AM69V125 FR22AM69V125I
Packaging 10

Blown-Fuse Indicator Dimensions


FUSE SIZE A B C
8 x 31 8.5 31.5 6.3
10 x 38 10.3 38 10.5
BEFORE AFTER 14 x 51 14.3 51 13.8
22 x 58 22.2 58 16.2

GPEC8
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58
Ratings – aM with Striker
Size Rated Rated Previous Reference Breaking Catalog
(mm x mm) Current In Voltage Reference Number Capacity Number.
(A)
1 17911 W215644 FR14AM69V1P
2 17913 B216661 FR14AM69V2P
4 17919 C218203 FR14AM69V4P
6 17923 E219240 FR14AM69V6P
8 17927 N222215 FR14AM69V8P
10 17931 S200760 FR14AM69V10P
X215645 14 X 51 12 500V 17933 R201817 120kA 500V FR14AM69V12P
16 17935 G211560 FR14AM69V16P
20 17937 E212593 FR14AM69V20P
25 17939 H213608 FR14AM69V25P
32 17943 N214625 FR14AM69V32P
40 17947 X215645 FR14AM69V40P
45 17949 C216662 FR14AM69V45P
50 400V 17951 D218204 120kA - 400V FR14AM69V50P
1 18911 E215652 FR22AM69V1P
2 18913 J216162 FR22AM69V2P
4 18919 A217695 FR22AM69V4P
6 18923 Y218728 FR22AM69V6P
8 18927 Q219779 FR22AM69V8P
10 18931 S222978 FR22AM69V10P
K216669
12 18933 R201311 FR22AM69V12P
16 18935 W211044 FR22AM69V16P
22 X 58 20 690V 18937 W212079 80kA - 690V FR22AM69V20P
25 18939 Q213615 FR22AM69V25P
32 18943 X214633 FR22AM69V32P
40 18947 F215653 FR22AM69V40P
50 18951 K216669 FR22AM69V50P
63 18955 B217696 FR22AM69V63P
80 500V 18959 Z218729 120kA - 500V FR22AM69V80P
100 18963 T222979 FR22AM69V100P
125 400V 18965 S201312 120kA - 400V FR22AM69V125P
Packaging 10

Dimensions Striker
Fuse Size A B C D E
14 x 51 14.3 51 13.8 7.5 3.8
22 x 58 22.2 58 16.2 7.5 3.8
BEFORE AFTER

Neutral
Size Previous Reference Standard Catalog
(mm x mm) Reference Number Pack/CTN Number

10 x 38 19100 R211569 FRN1038


14 x 51 19200 M212600 10 FRN1451
22 x 58 19300 R213616 FRN2258

GPEU9
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58

Characteristics t-l

aM
PREARCING TIME T(S)

PROSPECTIVE CURRENT (A rms)

Cut-off characteristics
MAXIMUM VALUE OF CURRENT (KA PEAK)

PROSPECTIVE CURRENT (kA rms)

GPEU10
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58

Characteristics I2t
I2T VALUE (A2S)

aM

690 V
500 V
400 V
} - OPERATING I2T

{ - PREARCING I2T

RATED CURRENT (A)

Temperature increase table (testing in superior contact)


ºC

80

70

60

50

40

30

20

10

1 2 4 6 8 10 12 16 20 25 32 1 2 4 6 8 10 12 16 20 25 32 40 50 1 2 4 6 8 10 12 16 20 25 32 40 50 63 80 100 125 In
10 x 38 14 x 51 22 x 58

GPEU11
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58

Power loss table


Size
In
10 x 38 14 x 51 22 x 58

0,16 A 0,35 W
0,25 A 0,50 W 0,70 W
0,5 A 0,50 W 0,75 W
1A 0,13 W 0,18 W 0,20 W
2A 0,20 W 0,25 W 0,30 W
4A 0,30 W 0,40 W 0,50 W
6A 0,45 W 0,55 W 0,65 W
8A 0,55 W 0,65 W 0,75 W
10 A 0,65 W 0,75 W 0,85 W
12 A 0,75 W 0,85 W 1W
16 A 0,90 W 1,20 W 1,40 W
20 A 1,10 W 1,50 W 1,70 W
25 A 1,40 W 1,80 W 2W
32 A 2W 2,10 W 2,60 W
40 A 2,60 W 3,20 W
45 A 2,80 W
50 A 2,90 W 3,90 W
63 A 4,60 W
80 A 5,60 W
100 A 6,50 W
125 A 9,50 W
Maximum standardized 10 x 38 14 x 51 22 x 58
power low. IEC 269-2-1
NFC 63.213 16 A 50 A 100 A
UNE 21.103-2-1
1,2 W 3W 7W

Table of maximum length of network in function of In and conductor section.


Maximum standardized power low.

aM Class Fuses

Copper
conductor Rated Current (In) OF aM Fuses (in A)
section (mm2)

16 20 25 32 40 50 63 80 100 125
1,5 55/64 37/45 25/30 15/20
2,5 116 84/94 58/68 40/49 26/32 17/20
4 181 147 118 84/95 58/68 42/48 28/33 18/23
6 273 223 178 139 105/117 79/89 55/64 37/42 26/31 14/20
10 227 181 147 113/125 80/94 57/69 40/47
16 236 189 151 120 83/97
25 231 185 147
35 262 210

GPEU12
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
aM 500V, 690V

NH Fuse System

DIN 57 636/VDE 0636 Parts 1, 10, 21, 22, 201


IEC 60269-2
DIN 43 620 Parts 1 to 4 (Standard dimensions)

The use category is identified by two letters, the first indicating the
operational class and the second the object to be protected.
The Ferraz shawmut range includes fuse-links to DIN VDE 0636
standard for the following uses categories:
gG: general purpose cable and line protection
aM: Partial purpose, motor circuit protection
gTr: general purpose, transformer protection
gR: general purpose, fast acting
aR: partial purpose, fast acting
Classification
The NH system is classed among plug-in fuse systems and is comprised of:
- fuse-base, (possibly including terminal covers and phase barriers)
- fuse-link with blade contact
- fuse-link replacement device (LV HRC fuse puller)
Since the design of this system cannot guarantee non-interchangeability of rated current, it must be
handled by a qualified professional.

Approval symbols

Germany

~0% lead
Austria
~0% cadmium

Switzerland

Netherlands
~it costs you
not a penny
more !
~it corresponds with the
2nd design of European
electronical scraps
guideline
~100% for a sure future

GPEU13
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 400V Size 000 to 3

NH-fuses, 400VAC gG
Pb-free with non-isolated gripping
lugs, double indicator,
contact blades, complying
with DIN VDE 0636Part 201
and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce

000 2 3,3 Z223674 1A613. Y 0,12 3 NH000GG40V2


000 4 1,35 A223675 1A619. Y 0,12 3 NH000GG40V4
000 6 1,7 B223676 1A623. Y 0,12 3 NH000GG40V6
000 10 1,0 C223677 1A631. Y 0,12 3 NH000GG40V10
000 16 1,8 D223678 1A635. Y 0,12 9 NH000GG40V16
000 20 2,0 E223679 1A637. Y 0,12 9 NH000GG40V20
000 25 2,4 F223680 1A639. Y 0,12 9 NH000GG40V25
000 32 2,6 G223681 1A643. Y 0,12 9 NH000GG40V32
000 35 3,2 H223682 1A645. Y 0,12 9 NH000GG40V35
000 40 3,1 J223683 1A647. Y 0,12 9 NH000GG40V45
000 50 3,5 K223684 1A651. Y 0,12 9 NH000GG40V50
000 63 4,6 L223685 1A655. Y 0,12 9 NH000GG40V63
000 80 5,0 M223686 1A659. Y 0,12 9 NH000GG40V80
000 100 5,5 N223687 1A663. Y 0,12 9 NH000GG40V100
00 125 8,6 E223702 1A765. Y 0,18 3 NH00GG40V125
00 160 9,6 F223703 1A769. Y 0,18 3 NH00GG40V160
1 35 3,9 J223706 1A145. N 0,28 3 NH1GG40V35
1 50 4,5 K223707 1A151. N 0,28 3 NH1GG40V50
1 63 5,7 L223708 1A155. N 0,28 3 NH1GG40V63
1 80 5,5 M223709 1A159. N 0,28 3 NH1GG40V80
1 100 7,0 N223710 1A163. N 0,28 3 NH1GG40V100
1 125 9,1 P223711 1A165. N 0,30 3 NH1GG40V125
1 160 13,0 Q223712 1A169. Y 0,30 3 NH1GG40V160
1 200 13,1 R223713 1A171. Y 0,30 3 NH1GG40V200
1 224 15,1 S223714 1A173. Y 0,30 3 NH1GG40V224
1 250 16,9 T223715 1A175. Y 0,30 3 NH1GG40V250
2 35 3,9 T227257 1A245. N 1,87 3 NH2GG40V35
2 50 4,5 V227258 1A251. N 1,87 3 NH2GG40V50
2 63 5,7 W227259 1A255. N 1,87 3 NH2GG40V63
2 80 6,1 F223726 1A259. N 0,32 3 NH2GG40V80
2 100 7,3 G223727 1A263. N 0,32 3 NH2GG40V100
2 125 9,1 H223728 1A265. N 0,32 3 NH2GG40V125
2 160 13,0 J223729 1A269. N 0,32 3 NH2GG40V160
2 200 13,5 K223730 1A271. N 0,32 3 NH2GG40V200
2 224 15,1 L223731 1A273. N 0,32 3 NH2GG40V224
2 250 18,0 M223732 1A275. N 0,32 3 NH2GG40V250
2 315 19,9 N223733 1A279. Y 0,40 3 NH2GG40V315
2 355 22,7 P223734 1A281. Y 0,40 3 NH2GG40V355
2 400 28,0 Q223735 1A283. Y 0,40 3 NH2GG40V400
3 250 19,9 R223736 1A375. N 0,45 1 NH3GG40V250
3 315 22,7 S223737 1A379. N 0,45 1 NH3GG40V315
3 400 28,0 T223738 1A383. Y 0,45 1 NH3GG40V400
3 500 30,8 V223739 1A387. Y 0,60 1 NH3GG40V500
3 630 43,0 W223740 1A389. Y 0,60 1 NH3GG40V630
(1) Suitable for Microswitch describes gG/aM Mechanics for Ceramic body Section page GPEU34

GPEU14
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 400V Size 000 to 3 - Isolated Lug

NH-fuses, 400VAC gG
with isolated metal gripping Pb-free
lugs (SGL),double indicator,
contact blades, complying
withDIN VDE 0636 Part 201
and IEC 60269-2-1

Rated current Power dissipation weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) kg/pce

000 2 3,3 P223688 1E613. 0,12 3 NH000GG40V2-1


000 4 1,35 Q223689 1E619. 0,12 3 NH000GG40V4-1
000 6 1,7 R223690 1E623. 0,12 3 NH000GG40V6-1
000 10 1,0 S223691 1E631. 0,12 3 NH000GG40V10-1
000 16 1,8 T223692 1E635. 0,12 9 NH000GG40V16-1
000 20 2,0 V223693 1E637. 0,12 9 NH000GG40V20-1
000 25 2,4 W223694 1E639. 0,12 9 NH000GG40V25-1
000 32 2,6 X223695 1E643. 0,12 9 NH000GG40V32-1
000 35 3,2 Y223696 1E645. 0,12 9 NH000GG40V35-1
000 40 3,1 Z223697 1E647. 0,12 9 NH000GG40V40-1
000 50 3,5 A223698 1E651. 0,12 9 NH000GG40V50-1
000 63 4,6 B223699 1E655. 0,12 9 NH000GG40V63-1
000 80 5,0 C223700 1E659. 0,12 9 NH000GG40V80-1
000 100 5,5 D223701 1E663. 0,12 9 NH000GG40V100-1
00 125 8,6 G223704 1E765. 0,18 3 NH00GG40V125-1
00 160 9,6 H223705 1E769. 0,18 3 NH00GG40V160-1
1 35 3,9 V223716 1E145. 0,28 3 NH1GG40V35-1
1 50 4,5 W223717 1E151. 0,28 3 NH1GG40V50-1
1 63 5,7 X223718 1E155. 0,28 3 NH1GG40V63-1
1 80 5,5 Y223719 1E159. 0,28 3 NH1GG40V80-1
1 100 7,0 Z223720 1E163. 0,28 3 NH1GG40V100-1
1 125 9,1 A223721 1E165. 0,30 3 NH1GG40V125-1
1 160 13,0 B223722 1E169. 0,30 3 NH1GG40V160-1
1 200 13,1 C223723 1E171. 0,30 3 NH1GG40V200-1
1 224 15,1 D223724 1E173. 0,30 3 NH1GG40V224-1
1 250 16,9 E223725 1E175. 0,30 3 NH1GG40V250-1
2 35 3,9 L227250 1E245. 2,65 3 NH2GG40V35-1
2 50 4,5 M227251 1E251. 2,65 3 NH2GG40V50-1
2 63 5,7 N227252 1E255. 2,65 3 NH2GG40V63-1
2 80 6,1 X223741 1E259. 0,32 3 NH2GG40V80-1
2 100 7,3 Y223742 1E263. 0,32 3 NH2GG40V100-1
2 125 9,1 Z223743 1E265. 0,32 3 NH2GG40V125-1
2 160 13,0 A223744 1E269. 0,32 3 NH2GG40V160-1
2 200 13,5 B223745 1E271. 0,32 3 NH2GG40V200-1
2 224 15,1 C223746 1E273. 0,32 3 NH2GG40V224-1
2 250 18,0 D223747 1E275. 0,32 3 NH2GG40V250-1
2 315 19,9 E223748 1E279. 0,40 3 NH2GG40V315-1
2 355 22,7 F223749 1E281. 0,40 3 NH2GG40V355-1
2 400 28,0 G223750 1E283. 0,40 3 NH2GG40V400-1
3 250 19,9 H223751 1E375. 0,45 1 NH3GG40V250-1
3 315 22,7 J223752 1E379. 0,45 1 NH3GG40V315-1
3 400 28,0 K223753 1E383. 0,45 1 NH3GG40V400-1
3 500 30,8 L223754 1E387. 0,60 1 NH3GG40V500-1
3 630 43,0 M223755 1E389. 0,60 1 NH3GG40V630-1
Non suitable for Microswitch.

GPEU15
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 4a

NH-fuses, 500VAC gG
Cd/Pb-free with non-isolated gripping lugs, double indicator, contact blades, complying
with DIN VDE 0636 Part 201 and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce

000 2 1,9 B211946 1B613. Y 0,13 3 NH000GG50V2


000 4 1,5 M212462 1B619. Y 0,13 3 NH000GG50V4
000 6 1,6 D213995 1B623. Y 0,13 3 NH000GG50V6
000 10 1,1 B219651 1B631. Y 0,13 3 NH000GG50V10
000 16 1,8 K222097 1B635. Y 0,13 9 NH000GG50V16
000 20 2,3 A222847 1B637. Y 0,13 9 NH000GG50V20
000 25 2,4 E201185 1B639. Y 0,13 9 NH000GG50V25
000 32 3,1 Z211438 1B643. Y 0,13 9 NH000GG50V32
000 35 3,0 C211947 1B645. Y 0,13 9 NH000GG50V35
000 40 3,7 N212463 1B647. Y 0,13 9 NH000GG50V40
000 50 4,1 T212974 1B651. Y 0,13 9 NH000GG50V50
000 63 5,4 E213996 1B655. Y 0,13 9 NH000GG50V63
000 80 6,5 Y216543 1B659. Y 0,13 9 NH000GG50V80
000 100 7,5 B219122 1B663. Y 0,13 9 NH000GG50V100
00 125 10,0 R201863 1B765. Y 0,20 3 NH00GG50V125
00 160 12,3 P211084 1B769. Y 0,20 3 NH00GG50V160
0 6 1,6 H213148 1B023. Y 0,27 3 NH0GG50V6
0 10 1,1 G214159 1B031. Y 0,27 3 NH0GG50V10
0 16 1,8 Q215179 1B035. Y 0,27 3 NH0GG50V16
0 20 2,3 R215686 1B037. Y 0,27 3 NH0GG50V20
0 25 2,4 Y216198 1B039. Y 0,27 3 NH0GG50V25
0 32 3,1 W216702 1B043. Y 0,27 3 NH0GG50V32
0 35 3,0 J217220 1B045. Y 0,27 3 NH0GG50V35
0 40 3,7 P217731 1B047. Y 0,27 3 NH0GG50V40
0 50 4,1 Z218246 1B051. Y 0,27 3 NH0GG50V50
0 63 6,6 N218765 1B055. Y 0,27 3 NH0GG50V63
0 80 8,0 C219284 1B059. Y 0,27 3 NH0GG50V80
0 100 9,4 D219814 1B063. Y 0,27 3 NH0GG50V100
0 125 11,8 P222492 1B065. Y 0,27 3 NH0GG50V125
0 160 14,6 F223013 1B069. Y 0,27 3 NH0GG50V160
0 200 18,1 C229611 1B071. Y 0,27 3 NH0GG50V200
0 224 19,2 D229612 1B073. Y 0,27 3 NH0GG50V224
0 250 20,3 E229613 1B075. Y 0,27 3 NH0GG50V250
1 16 1,8 M200801 1B135. N 0,28 3 NH1GG50V16
1 20 2,3 C201344 1B137. N 0,28 3 NH1GG50V20
1 25 2,4 N201860 1B139. N 0,28 3 NH1GG50V25
1 32 3,1 L211081 1B143. N 0,28 3 NH1GG50V32
1 35 3,0 A211600 1B145. N 0,28 3 NH1GG50V35
1 40 3,7 Y212633 1B147. N 0,28 3 NH1GG50V40
1 50 4,1 B213648 1B151. N 0,28 3 NH1GG50V50
1 63 6,6 L214669 1B155. N 0,28 3 NH1GG50V63
1 80 8,0 S215687 1B159. N 0,28 3 NH1GG50V80
1 100 9,4 X216703 1B163. N 0,28 3 NH1GG50V100
1 125 11,8 Q217732 1B165. Y 0,30 3 NH1GG50V125
1 160 14,6 A218247 1B169. Y 0,30 3 NH1GG50V160
1 200 18,0 P218766 1B171. Y 0,30 3 NH1GG50V200
1 224 19,0 D219285 1B173. Y 0,30 3 NH1GG50V224
1 250 20,0 E219815 1B175. Y 0,30 3 NH1GG50V250
1 315 20,5 Q228519 1B179. Y 0,42 3 NH1GG50V315
1 355 23,7 R228520 1B181. Y 0,42 3 NH1GG50V355
(1) Suitable for Microswitch describes page 106

GPEU16
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 4a

NH-fuses, 500VAC gG
with non-isolated gripping lugs, double indicator, contact blades, complying Cd/Pb-free
with DIN VDE 0636 Part 201 and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce

2 25 2,4 N200802 1B239. N 0,42 3 NH2GG50V25


2 32 3,1 D201345 1B243. N 0,42 3 NH2GG50V32
2 35 3,0 P201861 1B245. N 0,42 3 NH2GG50V35
2 40 3,7 M211082 1B247. N 0,42 3 NH2GG50V40
2 50 4,1 B211601 1B251. N 0,42 3 NH2GG50V50
2 63 6,8 Z212634 1B255. N 0,42 3 NH2GG50V63
2 80 8,3 C213649 1B259. N 0,42 3 NH2GG50V80
2 100 10,7 M214670 1B263. N 0,42 3 NH2GG50V100
2 125 12,2 T215688 1B265. N 0,42 3 NH2GG50V125
2 160 15,0 Y216704 1B269. N 0,42 3 NH2GG50V160
2 200 18,5 R217733 1B271. N 0,42 3 NH2GG50V200
2 224 19,2 Q218767 1B273. N 0,42 3 NH2GG50V224
2 250 20,6 R222494 1B275. N 0,42 3 NH2GG50V250
2 300 21,0 P200803 1B277. Y 0,64 3 NH2GG50V300
2 315 25,0 E201346 1B279. Y 0,64 3 NH2GG50V315
2 355 31,5 Q201862 1B281. Y 0,64 3 NH2GG50V355
2 400 28,5 N211083 1B283. Y 0,64 3 NH2GG50V400
2 425 29,2 S228521 1B285. Y 0,64 3 NH2GG50V425
2 500 35,6 T228522 1B287. Y 0,64 3 NH2GG50V500
3 250 21,1 C211602 1B375. N 0,65 1 NH3GG50V250
3 300 20,0 A212635 1B377. N 0,65 1 NH3GG50V300
3 315 25,0 L213151 1B379. N 0,65 1 NH3GG50V315
3 355 32,0 K214162 1B381. N 0,65 1 NH3GG50V355
3 400 34,0 T215182 1B383. N 1,05 1 NH3GG50V400
3 425 34,0 B216201 1B385. Y 1,05 1 NH3GG50V425
3 450 38,0 Z216705 1B386. Y 1,05 1 NH3GG50V450
3 500 43,0 M217223 1B387. Y 1,05 1 NH3GG50V500
3 630 43,1 S217734 1B389. Y 1,05 1 NH3GG50V630
3 800 53,2 V228523 1B391. Y 1,05 1 NH3GG50V800
with screw contact
4 400 31,0 *) A216039 8004.4007 N 2,00 1 NH4GG50V400-8
4 500 35,0 *) X216542 8004.5007 N 2,00 1 NH4GG50V500-8
4 630 46,6 *) W217576 8004.6307 N 2,00 1 NH4GG50V630-8
4 800 70,0 *) E218090 8004.8007 N 2,00 1 NH4GG50V800-8
4 1000 83,3 *) H201694 8004.1007 N 2,00 1 NH4GG50V1000-8
4 1250 110,0 *) C213994 8004.1257 N 2,00 1 NH4GG50V1250-8
contact blades for NH-bottom size 4a with swivel unit
4a 500 35,0 *) D201184 8014.5007 N 1,95 1 NH4AGG50V500-8
4a 630 46,6 *) T205752 8014.6307 N 1,95 1 NH4AGG50V630-8
4a 800 70,0 *) Y211437 8014.8007 N 1,95 1 NH4AGG50V800-8
4a 1000 83,3 *) A219650 8014.1007 N 1,95 1 NH4AGG50V1000-8
4a 1250 110,0 *) J200637 8014.1257 N 1,95 1 NH4AGG50V1250-8
*) with indicator on top
(1) Suitable for Microswitch describes page 106

GPEU17
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 3 - Isolated Lug

NH-fuses, 500VAC gG
Cd/Pb-free with isolated metal gripping
lugs (SGL), double indicator,
contact blades, complying
with DIN VDE 0636 Part 201
and IEC 60269-2-1

Rated current Power dissipation weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) kg/pce

000 2 1,9 C219652 1F613. 0,14 3 NH000GG50V2-1


000 4 1,5 N205770 1F619. 0,14 3 NH000GG50V4-1
000 6 1,6 P212464 1F623. 0,14 3 NH000GG50V6-1
000 10 1,1 V215528 1F631. 0,14 3 NH000GG50V10-1
000 16 1,8 F213997 1F635. 0,14 9 NH000GG50V16-1
000 20 2,3 F218091 1F637. 0,14 9 NH000GG50V20-1
000 25 2,4 K200638 1F639. 0,14 9 NH000GG50V25-1
000 32 3,1 D213489 1F643. 0,14 9 NH000GG50V32-1
000 35 3,0 G201187 1F645. 0,14 9 NH000GG50V35-1
000 40 3,7 D219653 1F647. 0,14 9 NH000GG50V40-1
000 50 4,1 C222849 1F651. 0,14 9 NH000GG50V50-1
000 63 5,4 R212466 1F655. 0,14 9 NH000GG50V63-1
000 80 6,5 N215016 1F659. 0,14 9 NH000GG50V80-1
000 100 7,5 J201189 1F663. 0,14 9 NH000GG50V100-1
00 125 10,0 V200808 1F765. 0,20 3 NH00GG50V125-1
00 160 12,3 W201867 1F769. 0,20 3 NH00GG50V160-1
0 6 1,6 B212636 1F023. 0,26 3 NH0GG50V6-1
0 10 1,1 M213152 1F031. 0,26 3 NH0GG50V10-1
0 16 1,8 E213651 1F035. 0,26 3 NH0GG50V16-1
0 20 2,3 L214163 1F037. 0,26 3 NH0GG50V20-1
0 25 2,4 P214672 1F039. 0,26 3 NH0GG50V25-1
0 32 3,1 V215183 1F043. 0,26 3 NH0GG50V32-1
0 35 3,0 W215690 1F045. 0,26 3 NH0GG50V35-1
0 40 3,7 C216202 1F047. 0,26 3 NH0GG50V40-1
0 50 4,1 A216706 1F051. 0,26 3 NH0GG50V50-1
0 63 6,6 N217224 1F055. 0,26 3 NH0GG50V63-1
0 80 8,0 T217735 1F059. 0,26 3 NH0GG50V80-1
0 100 9,4 D218250 1F063. 0,26 3 NH0GG50V100-1
0 125 11,8 S218769 1F065. 0,26 3 NH0GG50V125-1
0 160 14,6 F219287 1F069. 0,26 3 NH0GG50V160-1
1 16 1,8 H219818 1F135. 0,29 3 NH1GG50V16-1
1 20 2,3 T222496 1F137. 0,29 3 NH1GG50V20-1
1 25 2,4 K223017 1F139. 0,29 3 NH1GG50V25-1
1 32 3,1 R200805 1F143. 0,29 3 NH1GG50V32-1
1 35 3,0 G201348 1F145. 0,29 3 NH1GG50V35-1
1 40 3,7 Q211085 1F147. 0,29 3 NH1GG50V40-1
1 50 4,1 L212116 1F151. 0,29 3 NH1GG50V50-1
1 63 6,6 N213153 1F155. 0,29 3 NH1GG50V63-1
1 80 8,0 M214164 1F159. 0,29 3 NH1GG50V80-1
1 100 9,4 W215184 1F163. 0,29 3 NH1GG50V100-1
1 125 11,8 D216203 1F165. 0,42 3 NH1GG50V125-1
1 160 14,6 B216707 1F169. 0,42 3 NH1GG50V160-1
1 200 18,0 P217225 1F171. 0,42 3 NH1GG50V200-1
1 224 19,0 V217736 1F173. 0,42 3 NH1GG50V224-1
1 250 20,0 E218251 1F175. 0,42 3 NH1GG50V250-1
Non suitable for Microswitch.

GPEU18
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 3 - Isolated Lug

NH-fuses, 500VAC gG
with isolated metal gripping Cd/Pb-free
lugs (SGL), double indicator,
contact blades, complying
with DIN VDE 0636 Part 201
and IEC 60269-2-1

Rated current Power dissipation weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) kg/pce

2 25 2,4 J219819 1F239. 0,42 3 NH2GG50V25-1


2 32 3,1 V222497 1F243. 0,42 3 NH2GG50V32-1
2 35 3,0 L223018 1F245. 0,42 3 NH2GG50V35-1
2 40 3,7 S200806 1F247. 0,42 3 NH2GG50V40-1
2 50 4,1 H201349 1F251. 0,42 3 NH2GG50V50-1
2 63 6,8 T201865 1F255. 0,42 3 NH2GG50V63-1
2 80 8,3 F211605 1F259. 0,42 3 NH2GG50V80-1
2 100 10,7 P213154 1F263. 0,42 3 NH2GG50V100-1
2 125 12,2 N214165 1F265. 0,42 3 NH2GG50V125-1
2 160 15,0 X215185 1F269. 0,42 3 NH2GG50V160-1
2 200 18,5 E216204 1F271. 0,42 3 NH2GG50V200-1
2 224 19,2 Q217226 1F273. 0,42 3 NH2GG50V224-1
2 250 20,6 F218252 1F275. 0,42 3 NH2GG50V250-1
2 300 21,0 H219289 1F277. 0,64 3 NH2GG50V300-1
2 315 25,0 K219820 1F279. 0,64 3 NH2GG50V315-1
2 355 31,5 M223019 1F281. 0,64 3 NH2GG50V355-1
2 400 28,5 T200807 1F283. 0,64 3 NH2GG50V400-1
3 250 21,1 J201350 1F375. 0,65 1 NH3GG50V250-1
3 300 20,0 S211087 1F377. 0,65 1 NH3GG50V300-1
3 315 25,0 G211606 1F379. 0,65 1 NH3GG50V315-1
3 355 32,0 E212639 1F381. 0,65 1 NH3GG50V355-1
3 400 34,0 H213654 1F383. 1,05 1 NH3GG50V400-1
3 425 34,0 S214675 1F385. 1,05 1 NH3GG50V425-1
3 450 38,0 Z215693 1F386. 1,05 1 NH3GG50V450-1
3 500 43,0 F216205 1F387. 1,05 1 NH3GG50V500-1
3 630 43,1 D216709 1F389. 1,05 1 NH3GG50V630-1

Non suitable for Microswitch.

GPEU19
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 690V Size 000 to 4a

NH-fuses, 690VAC gG
Cd/Pb-free with non-isolated gripping lugs, doubleindicator, contact blades, complying
with DIN VDE 0636 Part 201 and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce

000 2 1,9 E228440 1C613. Y 0,13 3 NH000GG69V2


000 4 1,5 F228441 1C619. Y 0,13 3 NH000GG69V4
000 6 1,6 G228442 1C623. Y 0,13 3 NH000GG69V6
000 10 1,1 J228444 1C631. Y 0,13 3 NH000GG69V10
000 16 1,8 K228445 1C635. Y 0,13 3 NH000GG69V16
000 20 2,3 L228446 1C637. Y 0,13 3 NH000GG69V20
000 25 2,4 M228447 1C639. Y 0,13 3 NH000GG69V25
000 32 3,1 N228448 1C643. Y 0,13 3 NH000GG69V32
000 35 3,0 P228449 1C645. Y 0,13 3 NH000GG69V35
000 40 3,7 Q228450 1C647. Y 0,13 3 NH000GG69V40
000 50 4,1 R228451 1C651. Y 0,13 3 NH000GG69V50
000 63 5,4 S228452 1C655. Y 0,13 3 NH000GG69V63
000 80 6,5 T228453 1C659. Y 0,13 3 NH000GG69V80
00 32 3,1 V228454 1C743. Y 0,20 3 NH00GG69V32
00 35 3,0 W228455 1C745. Y 0,20 3 NH00GG69V35
00 40 3,7 X228456 1C747. Y 0,20 3 NH00GG69V40
00 50 4,1 Y228457 1C751. Y 0,20 3 NH00GG69V50
00 63 5,6 Z228458 1C755. Y 0,20 3 NH00GG69V63
00 80 6,8 A228459 1C759. Y 0,20 3 NH00GG69V80
00 100 7,5 B228460 1C763. Y 0,20 3 NH00GG69V100
00 125 10,0 C228461 1C765. Y 0,20 3 NH00GG69V125
0 6 1,6 D228462 1C023. Y 0,27 3 NH0GG69V6
0 10 1,1 E228463 1C031. Y 0,27 3 NH0GG69V10
0 16 1,8 F228464 1C035. Y 0,27 3 NH0GG69V16
0 20 2,3 G228465 1C037. Y 0,27 3 NH0GG69V20
0 25 2,4 H228466 1C039. Y 0,27 3 NH0GG69V25
0 32 3,1 J228467 1C043. Y 0,27 3 NH0GG69V32
0 35 3,0 K228468 1C045. Y 0,27 3 NH0GG69V35
0 40 3,7 L228469 1C047. Y 0,27 3 NH0GG69V40
0 50 4,1 M228470 1C051. Y 0,27 3 NH0GG69V50
0 63 6,6 N228471 1C055. Y 0,27 3 NH0GG69V63
0 80 8,0 P228472 1C059. Y 0,27 3 NH0GG69V80
0 100 9,4 Q228473 1C063. Y 0,27 3 NH0GG69V100
0 125 11,8 R228474 1C065. Y 0,27 3 NH0GG69V125
0 160 14,6 S228475 1C069. Y 0,27 3 NH0GG69V160
1 16 1,8 T228476 1C135. N 0,26 3 NH1GG69V16
1 20 2,3 V228477 1C137. N 0,26 3 NH1GG69V20
1 25 2,4 W228478 1C139. N 0,26 3 NH1GG69V25
1 32 3,1 X228479 1C143. N 0,26 3 NH1GG69V32
1 35 3,0 Y228480 1C145. N 0,26 3 NH1GG69V35
1 40 3,7 Z228481 1C147. N 0,26 3 NH1GG69V40
1 50 4,1 A228482 1C151. N 0,26 3 NH1GG69V50
1 63 6,6 B228483 1C155. N 0,26 3 NH1GG69V63
1 80 8,0 C228484 1C159. N 0,26 3 NH1GG69V80
1 100 9,4 D228485 1C163. N 0,26 3 NH1GG69V100
1 125 11,8 E228486 1C165. N 0,42 3 NH1GG69V125
1 160 14,6 F228487 1C169. N 0,42 3 NH1GG69V160
1 200 18,0 G228488 1C171. Y 0,42 3 NH1GG69V200
1 224 19,0 V233261 1C173. Y 0,42 3 NH1GG69V224
1 250 20,0 W233262 1C175. Y 0,42 3 NH1GG69V250
(1) Suitable for Microswitch describes page 106

GPEU20
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 690V Size 000 to 4a

NH-fuses, 690VAC gG
with non-isolated gripping lugs, doubleindicator, contact blades, complying Cd/Pb-free
with DIN VDE 0636 Part 201 and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce

2 32 3,1 H228489 1C243. N 0,42 3 NH2GG69V32


2 35 3,0 J228490 1C245. N 0,42 3 NH2GG69V35
2 40 3,7 K228491 1C247. N 0,42 3 NH2GG69V40
2 50 4,1 L228492 1C251. N 0,42 3 NH2GG69V50
2 63 6,8 M228493 1C255. N 0,42 3 NH2GG69V63
2 80 8,3 N228494 1C259. N 0,42 3 NH2GG69V80
2 100 10,7 P228495 1C263. N 0,42 3 NH2GG69V100
2 125 12,2 Q228496 1C265. Y 0,42 3 NH2GG69V125
2 160 15,0 R228497 1C269. Y 0,42 3 NH2GG69V160
2 200 18,5 S228498 1C271. Y 0,42 3 NH2GG69V200
2 224 19,2 T228499 1C273. Y 0,42 3 NH2GG69V224
2 250 20,6 V228500 1C275. Y 0,42 3 NH2GG69V250
2 300 21,0 W228501 1C277. Y 0,64 3 NH2GG69V300
2 315 25,0 X228502 1C279. Y 0,65 3 NH2GG69V315
2 355 31,5 Y228503 1C281. Y 0,65 3 NH2GG69V355
3 250 21,1 Z228504 1C375. N 0,65 1 NH3GG69V250
3 300 22,6 A228505 1C377. N 0,65 1 NH3GG69V300
3 315 25,0 B228506 1C379. Y 0,65 1 NH3GG69V315
3 355 32,0 C228507 1C381. Y 0,65 1 NH3GG69V355
3 400 34,0 D228508 1C383. Y 1,05 1 NH3GG69V400
3 425 34,0 E228509 1C385. Y 1,05 1 NH3GG69V425
3 500 43,0 F228510 1C387. Y 1,05 1 NH3GG69V500
with screw contact
4 400 31,0 *) N214004 8004.400765 N 2,00 1 NH4GG69V400-8
4 500 35,0 *) Y215025 8004.500765 N 2,00 1 NH4GG69V500-8
4 630 46,6 *) E215537 8004.630765 N 2,00 1 NH4GG69V630-8
4 800 70,0 *) K216554 8004.800765 N 2,00 1 NH4GG69V800-8
contact blades for NH-bottom size 4a with swivel unit
4a 400 31,0 *) W217070 8014.400765 N 1,95 1 NH4AGG69V400-8
4a 500 35,0 *) H217587 8014.500765 N 1,95 1 NH4AGG69V500-8
4a 630 46,6 *) W222107 8014.630765 N 1,95 1 NH4AGG69V630-8
4a 800 70,0 *) M222858 8014.800765 N 1,95 1 NH4AGG69V800-8
*) with indicator on top

(1) Suitable for Microswitch describes page 106

GPEU21
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 690V Size 000 to 3 - Isolated Lug

NH-fuses, 690VAC gG
Cd/Pb-free with isolated metal gripping lugs (SGL), double indicator, contact blades,
complying with DIN VDE 0636 Part 201 and IEC 60269-2-1
Rated current Power dissipation weight
Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) kg/pce
000 2 1,9 D229704 1G613. 0,14 3 NH000GG69V2-1
000 4 1,5 E229705 1G619. 0,14 3 NH000GG69V4-1
000 6 1,6 F229706 1G623. 0,14 3 NH000GG69V6-1
000 10 1,1 H229708 1G631. 0,14 3 NH000GG69V10-1
000 16 1,8 J229709 1G635. 0,14 3 NH000GG69V16-1
000 20 2,3 K229710 1G637. 0,14 3 NH000GG69V20-1
000 25 2,4 L229711 1G639. 0,14 3 NH000GG69V25-1
000 32 3,1 M229712 1G643. 0,14 3 NH000GG69V32-1
000 35 3,0 N229713 1G645. 0,14 3 NH000GG69V35-1
000 40 3,7 P229714 1G647. 0,14 3 NH000GG69V40-1
000 50 4,1 Q229715 1G651. 0,14 3 NH000GG69V50-1
000 63 5,4 R229716 1G655. 0,14 3 NH000GG69V63-1
000 80 6,5 S229717 1G659. 0,14 3 NH000GG69V80-1
00 32 3,1 T229718 1G743. 0,20 3 NH00GG69V32-1
00 35 3,0 V229719 1G745. 0,20 3 NH00GG69V35-1
00 40 3,7 W229720 1G747. 0,20 3 NH00GG69V40-1
00 50 4,1 X229721 1G751. 0,20 3 NH00GG69V50-1
00 63 5,6 Y229722 1G755. 0,20 3 NH00GG69V63-1
00 80 6,8 Z229723 1G759. 0,20 3 NH00GG69V80-1
00 100 7,5 A229724 1G763. 0,20 3 NH00GG69V100-1
00 125 10,0 B229725 1G765. 0,20 3 NH00GG69V125-1
0 6 1,6 C229726 1G023. 0,26 3 NH0GG69V6-1
0 10 1,1 D229727 1G031. 0,26 3 NH0GG69V10-1
0 16 1,8 E229728 1G035. 0,26 3 NH0GG69V16-1
0 20 2,3 F229729 1G037. 0,26 3 NH0GG69V20-1
0 25 2,4 G229730 1G039. 0,26 3 NH0GG69V25-1
0 32 3,1 H229731 1G043. 0,26 3 NH0GG69V32-1
0 35 3,0 J229732 1G045. 0,26 3 NH0GG69V35-1
0 40 3,7 K229733 1G047. 0,26 3 NH0GG69V40-1
0 50 4,1 L229734 1G051. 0,26 3 NH0GG69V50-1
0 63 6,6 M229735 1G055. 0,26 3 NH0GG69V63-1
0 80 8,0 N229736 1G059. 0,26 3 NH0GG69V80-1
0 100 9,4 P229737 1G063. 0,26 3 NH0GG69V100-1
0 125 11,8 Q229738 1G065. 0,26 3 NH0GG69V125-1
0 160 14,6 R229739 1G069. 0,26 3 NH0GG69V160-1
1 16 1,8 S229740 1G135. 0,29 1 NH1GG69V16-1
1 20 2,3 T229741 1G137. 0,29 1 NH1GG69V20-1
1 25 2,4 V229742 1G139. 0,29 1 NH1GG69V25-1
1 32 3,1 W229743 1G143. 0,29 1 NH1GG69V32-1
1 35 3,0 X229744 1G145. 0,29 1 NH1GG69V35-1
1 40 3,7 Y229745 1G147. 0,29 1 NH1GG69V40-1
1 50 4,1 Z229746 1G151. 0,29 1 NH1GG69V50-1
1 63 6,6 A229747 1G155. 0,29 1 NH1GG69V63-1
1 80 8,0 B229748 1G159. 0,29 1 NH1GG69V80-1
1 100 9,4 C229749 1G163. 0,29 1 NH1GG69V100-1
1 125 11,8 D229750 1G165. 0,42 1 NH1GG69V125-1
1 160 14,6 E229751 1G169. 0,42 1 NH1GG69V160-1
1 200 18,0 F229752 1G171. 0,42 1 NH1GG69V200-1
1 224 19,0 G229753 1G173. 0,42 1 NH1GG69V224-1
2 32 3,1 J229755 1G243. 0,43 1 NH2GG69V32-1
2 35 3,0 K229756 1G245. 0,43 1 NH2GG69V35-1
2 40 3,7 L229757 1G247. 0,43 1 NH2GG69V40-1
2 50 4,1 M229758 1G251. 0,43 1 NH2GG69V50-1
2 63 6,8 N229759 1G255. 0,43 1 NH2GG69V63-1
2 80 8,3 P229760 1G259. 0,43 1 NH2GG69V80-1
2 100 10,7 Q229761 1G263. 0,43 1 NH2GG69V100-1
2 125 12,2 R229762 1G265. 0,43 1 NH2GG69V125-1
2 160 15,0 S229763 1G269. 0,43 1 NH2GG69V160-1
2 200 18,5 T229764 1G271. 0,43 1 NH2GG69V200-1
2 224 19,2 V229765 1G273. 0,43 1 NH2GG69V224-1
2 250 20,6 D233729 1G275. 0,43 1 NH2GG69V250-1
2 300 21,0 X229767 1G277. 0,43 1 NH2GG69V300-1
2 315 25,0 Y229768 1G279. 0,65 1 NH2GG69V315-1
2 355 31,5 Z229769 1G281. 0,65 1 NH2GG69V355-1
3 250 21,1 A229770 1G375. 0,65 1 NH3GG69V250-1
3 300 22,6 B229771 1G377. 1,01 1 NH3GG69V300-1
3 315 25,0 C229772 1G379. 1,01 1 NH3GG69V315-1
3 355 32,0 D229773 1G381. 1,01 1 NH3GG69V355-1
3 400 34,0 E229774 1G383. 1,01 1 NH3GG69V400-1
3 425 34,0 F229775 1G385. 1,01 1 NH3GG69V425-1
Non suitable for Microswitch.

GPEU22 07/05
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG Curves Set

NH-fuses, 400VAC, 500VAC gG

Total Clearing I2t Current Limitation Curves


10 7
10 6
5000000 1250 A
3000000
1000 A
2000000
800 A
630 A
500 A
10 6 450 A
425 A
500000 400 A
300000 355 A
200000 315 A
10 5 300 A
10 5 250 A
224 A
50000 200 A
160 A

Rated current in A
30000
125 A
20000 100 A
80 A
10 4 63 A
50 A

Ip
5000 40 A

3
2.
3000 10 4 35 A

=
32 A

Im
2000
25 A
10 3
20 A
16 A
PEAK LET-THRU IN KA

500 10 A
300 6A
200 4A
10 2 2A
50
10 3
30
20

10

5
3
2
10 2
1
2 4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 300 355 400 425 500 630 800 1000 1250 10 2 10 3 10 4 10 5 10 6
315

SHORT CIRCUIT CURRENT Ip IN kA

Time VS. Current Characteristics


RATED CURRENT IN A
1000 A
450 A
630 A
400 A
100 A

200 A
250 A

315 A
20 A

32 A

40 A

63 A

1250 A
355 A
125 A
160 A

224 A
300 A

500 A
425 A

800 A
10 A
16 A

25 A

35 A

50 A

80 A
2A

4A

6A

10 4

10 3

10 2
MELTING TIME

10

10 -1

10 -2
1 2 4 6 8 10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A

GPEU23
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG Curves Set

NH-fuses, 690VAC gG
Total Clearing I2t Current Limitation Curves
10 7

5000000 10 6
3000000
2000000
1000 A
800 A
630 A
10 6 500 A
500000
450 A
425 A
300000 400 A
200000 355 A
10 5 315 A
10 5 300 A
250 A
50000 224 A
30000
200 A
160 A
20000 125 A
100 A
10 4 80 A
63 A
5000 50 A

Ip
40 A
3000 10 4 35 A

3
2.
2000 32 A

=
25 A

Im
10 3 PEAK LET-THRU IN KA 20 A
500 16 A
10 A
300
200 6A
4A
10 2
10 3 2A
50
30
20

10

5
3
2
10 2
1
2 4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 300 355 400 425 450 500 630 800 1000 10 2 10 3 10 4 10 5 10 6
315

SHORT CIRCUIT CURRENT Ip IN kA

Time VS. Current


RATED CURRENT IN A
1000 A
450 A
630 A
400 A
100 A

200 A
250 A

315 A
20 A

32 A

40 A

63 A

355 A
125 A
160 A

224 A
300 A

500 A
425 A

800 A
10 A
16 A

25 A

35 A

50 A

80 A
2A

4A

6A

10 4

10 3

10 2
MELTING TIME

10

10 -1

10 -2
1 2 4 6 8 10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A

GPEU24
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM 500V Size 000 to 4a

NH-fuses, 500VAC aM
with non-isolated gripping lugs, double indicator, contact blades, Cd/Pb-free
complying with DIN VDE 0636 Part 201and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce
000 2 0,1 K232493 2B613. Y 0,13 3 NH000AM50V2
000 4 0,2 L232494 2B619. Y 0,13 3 NH000AM50V4
000 6 0,3 M232495 2B623. Y 0,13 3 NH000AM50V6
000 10 0,5 N232496 2B631. Y 0,13 3 NH000AM50V10
000 16 0,7 P232497 2B635. Y 0,13 3 NH000AM50V16
000 20 0,9 Q232498 2B637. Y 0,13 3 NH000AM50V20
000 25 1,2 R232499 2B639. Y 0,13 3 NH000AM50V25
000 32 1,5 S232500 2B643. Y 0,13 3 NH000AM50V32
000 35 1,6 T232501 2B645. Y 0,13 3 NH000AM50V35
000 40 1,8 V232502 2B647. Y 0,13 3 NH000AM50V40
000 50 2,3 W232503 2B651. Y 0,13 3 NH000AM50V50
000 63 2,9 X232504 2B655. Y 0,13 3 NH000AM50V63
000 80 3,6 C227863 2B659. Y 0,13 3 NH000AM50V80
00 100 5,8 Y232505 2B763. Y 0,20 3 NH00AM50V100
00 125 6,4 Z232506 2B765. Y 0,20 3 NH00AM50V125
00 160 7,9 J227869 2B769. Y 0,20 3 NH00AM50V160
0 100 6,0 A232507 2B063. Y 0,26 3 NH0AM50V100
0 125 7,9 B232508 2B065. Y 0,26 3 NH0AM50V125
0 160 10,5 C232509 2B069. Y 0,26 3 NH0AM50V160
0 200 11,8 A227884 2B071. Y 0,26 3 NH0AM50V200
1 100 5,8 D232510 2B163. Y 0,42 3 NH1AM50V100
1 125 7,5 E232511 2B165. Y 0,42 3 NH1AM50V125
1 160 10,4 F232512 2B169. Y 0,42 3 NH1AM50V160
1 200 14,2 G232513 2B171. Y 0,42 3 NH1AM50V200
1 224 15,8 H232514 2B173. Y 0,42 3 NH1AM50V224
1 250 17,5 J232515 2B175. Y 0,42 3 NH1AM50V250
1 315 22,1 K227962 2B179. Y 0,42 3 NH1AM50V315
2 250 16,8 K232516 2B275. Y 0,64 3 NH2AM50V250
2 315 23,1 L232517 2B279. Y 0,64 3 NH2AM50V315
2 355 26,4 M232518 2B281. Y 0,64 3 NH2AM50V355
2 400 29,7 N232519 2B283. Y 0,64 3 NH2AM50V400
2 500 34,4 C227978 2B287. Y 0,64 3 NH2AM50V500
3 315 21,0 P232520 2B379. Y 1,05 1 NH3AM50V315
3 355 23,3 Q232521 2B381. Y 1,05 1 NH3AM50V355
3 400 29,1 R232522 2B383. Y 1,05 1 NH3AM50V400
3 425 29,1 S232523 2B385. Y 1,05 1 NH3AM50V425
3 450 34,0 T232524 2B386. Y 1,05 1 NH3AM50V450
3 500 42,0 V232525 2B387. Y 1,05 1 NH3AM50V500
3 630 42,0 M227987 2B389. Y 1,05 1 NH3AM50V630
with screw contact
4 400 26,0 *) P233555 8004.400505 N 2,18 1 NH4AM50V400-8
4 500 38,0 *) Q233556 8004.500505 N 2,18 1 NH4AM50V500-8
4 630 50,0 *) E222115 8004.630505 N 2,18 1 NH4AM50V630-8
4 800 65,0 *) V222865 8004.800505 N 2,18 1 NH4AM50V800-8
4 1000 80,0 *) S219137 8004.100505 N 2,18 1 NH4AM50V1000-8
4 1250 110,0 *) V219668 8004.125505 N 2,21 1 NH4AM50V1250-8
contact blades for NH-bottom size 4a with swivel unit
4a 500 38,0 *) R233557 8014.500505 N 2,00 1 NH4AAM50V500-8
4a 630 50,0 *) S233558 8014.630505 N 2,00 1 NH4AAM50V630-8
4a 800 65,0 *) T233559 8014.800505 N 2,00 1 NH4AAM50V800-8
4a 1000 80,0 *) V233560 8014.100505 N 2,00 1 NH4AAM50V1000-8
4a 1250 110,0 *) W233561 8014.125505 N 2,00 1 NH4AAM50V1250-8
*) with indicator on top

(1) Suitable for Microswitch describes page 106

GPEU25
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM 690V Size 000 to 4a

NH-fuses, 690VAC aM
Cd/Pb-free with non-isolated gripping lugs, double indicator, contact blades, complying
with DIN VDE 0636 Part 201 and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce

000 2 0,1 P227851 2C613. Y 0,13 3 NH000AM69V2


000 4 0,2 Q227852 2C619. Y 0,13 3 NH000AM69V4
000 6 0,3 R227853 2C623. Y 0,13 3 NH000AM69V6
000 10 0,5 S227854 2C631. Y 0,13 3 NH000AM69V10
000 16 0,7 T227855 2C635. Y 0,13 3 NH000AM69V16
000 20 0,9 V227856 2C637. Y 0,13 3 NH000AM69V20
000 25 1,2 W227857 2C639. Y 0,13 3 NH000AM69V25
000 32 1,5 X227858 2C643. Y 0,13 3 NH000AM69V32
000 35 1,6 Y227859 2C645. Y 0,13 3 NH000AM69V35
000 40 1,8 Z227860 2C647. Y 0,13 3 NH000AM69V40
000 50 2,3 A227861 2C651. Y 0,13 3 NH000AM69V50
000 63 2,9 B227862 2C655. Y 0,13 3 NH000AM69V63
00 50 2,3 D227864 2C751. Y 0,20 3 NH00AM69V50
00 63 2,9 E227865 2C755. Y 0,20 3 NH00AM69V63
00 80 3,6 F227866 2C759. Y 0,20 3 NH00AM69V80
00 100 5,2 G227867 2C763. Y 0,20 3 NH00AM69V100
00 125 6,4 H227868 2C765. Y 0,20 3 NH00AM69V125
0 6 0,3 K227870 2C023. Y 0,26 3 NH0AM69V6
0 10 0,5 L227871 2C031. Y 0,26 3 NH0AM69V10
0 16 0,8 M227872 2C035. Y 0,26 3 NH0AM69V16
0 20 1,0 N227873 2C037. Y 0,26 3 NH0AM69V20
0 25 1,3 P227874 2C039. Y 0,26 3 NH0AM69V25
0 32 1,6 Q227875 2C043. Y 0,26 3 NH0AM69V32
0 35 1,7 R227876 2C045. Y 0,26 3 NH0AM69V35
0 40 2,0 S227877 2C047. Y 0,26 3 NH0AM69V40
0 50 2,8 T227878 2C051. Y 0,26 3 NH0AM69V50
0 63 3,4 V227879 2C055. Y 0,26 3 NH0AM69V63
0 80 4,9 W227880 2C059. Y 0,26 3 NH0AM69V80
0 100 6,0 X227881 2C063. Y 0,26 3 NH0AM69V100
0 125 7,9 Y227882 2C065. Y 0,26 3 NH0AM69V125
0 160 10,5 Z227883 2C069. Y 0,26 3 NH0AM69V160
1 16 1,0 B227885 2C135. Y 0,43 3 NH1AM69V16
1 20 1,2 C227886 2C137. Y 0,43 3 NH1AM69V20
1 25 1,4 D227887 2C139. Y 0,43 3 NH1AM69V25
1 32 1,9 E227888 2C143. Y 0,43 3 NH1AM69V32
1 35 2,0 F227889 2C145. Y 0,43 3 NH1AM69V35
1 40 2,3 G227890 2C147. Y 0,43 3 NH1AM69V40
1 50 2,9 H227891 2C151. Y 0,43 3 NH1AM69V50
1 63 3,6 J227892 2C155. Y 0,43 3 NH1AM69V63
1 80 4,6 K227893 2C159. Y 0,43 3 NH1AM69V80
1 100 5,8 L227894 2C163. Y 0,43 3 NH1AM69V100
1 125 7,5 M227895 2C165. Y 0,43 3 NH1AM69V125
1 160 10,4 N227896 2C169. Y 0,43 3 NH1AM69V160
1 200 14,2 P227897 2C171. Y 0,43 3 NH1AM69V200
1 224 15,8 Q227898 2C173. Y 0,43 3 NH1AM69V224
1 250 17,5 R227899 2C175. Y 0,43 3 NH1AM69V250
(1) Suitable for Microswitch describes page 106

GPEU26
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM 690V Size 000 to 4a

NH-fuses, 690VAC aM
with non-isolated gripping lugs, double indicator, contact blades, Cd/Pb-free
complying with DIN VDE 0636 Part 201and IEC 60269-2-1

Rated current Power dissipation Micro- weight


Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) switch(1) kg/pce

2 35 1,8 L227963 2C245. Y 0,64 3 NH2AM69V35


2 40 2,1 M227964 2C247. Y 0,64 3 NH2AM69V40
2 50 2,7 N227965 2C251. Y 0,64 3 NH2AM69V50
2 63 3,4 P227966 2C255. Y 0,64 3 NH2AM69V63
2 80 4,4 Q227967 2C259. Y 0,64 3 NH2AM69V80
2 100 5,5 R227968 2C263. Y 0,64 3 NH2AM69V100
2 125 6,4 S227969 2C265. Y 0,64 3 NH2AM69V125
2 160 9,3 T227970 2C269. Y 0,64 3 NH2AM69V160
2 200 11,3 V227971 2C271. Y 0,64 3 NH2AM69V200
2 224 12,2 W227972 2C273. Y 0,64 3 NH2AM69V224
2 250 16,8 X227973 2C275. Y 0,64 3 NH2AM69V250
2 300 21,0 Y227974 2C277. Y 0,64 3 NH2AM69V300
2 315 23,1 Z227975 2C279. Y 0,64 3 NH2AM69V315
2 355 26,4 A227976 2C281. Y 0,64 3 NH2AM69V355
2 400 29,7 B227977 2C283. Y 0,64 3 NH2AM69V400
3 250 14,6 D227979 2C375. Y 1,05 1 NH3AM69V250
3 300 21,0 E227980 2C377. Y 1,05 1 NH3AM69V300
3 315 21,0 F227981 2C379. Y 1,05 1 NH3AM69V315
3 355 23,3 G227982 2C381. Y 1,05 1 NH3AM69V355
3 400 29,1 H227983 2C383. Y 1,05 1 NH3AM69V400
3 425 29,1 J227984 2C385. Y 1,05 1 NH3AM69V425
3 450 34,0 K227985 2C386. Y 1,05 1 NH3AM69V450
3 500 42,0 L227986 2C387. Y 1,05 1 NH3AM69V500
with screw contact
4 400 26,0 *) Q227990 8004.40056 N 2,00 1 NH4AM69V400-8
4 500 38,0 *) R227991 8004.50056 N 2,00 1 NH4AM69V500-8
4 630 50,0 *) S227992 8004.63056 N 1,75 1 NH4AM69V630-8
4 800 65,0 *) T227993 8004.80056 N 1,75 1 NH4AM69V800-8
4 1000 80,0 *) V227994 8004.10056 N 2,00 1 NH4AM69V1000-8
contact blades for NH-bottom size 4a with swivel unit
4a 500 38,0 *) X227996 8014.50056 N 1,95 1 NH4AAM69V500-8
4a 630 50,0 *) Y227997 8014.63056 N 1,95 1 NH4AAM69V630-8
4a 800 65,0 *) A227999 8014.80056 N 1,95 1 NH4AAM69V800-8
4a 1000 80,0 *) B228000 8014.10056 N 1,95 1 NH4AAM69V1000-8
*) with indicator on top

(1) Suitable for Microswitch describes page 106

GPEU27
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM Curves Set

NH-fuses, 500VAC aM
Total Clearing I2t Current Limitation Curves

10 7

5000000
3000000
2000000

10 6 10 6

500000
800 A (400 V)
300000
630 A
200000 500 A
450 A
10 5 400 A
355 A
315 A
50000 10 5 250 A
224 A
30000 200 A
20000 160 A
125 A
100 A
10 4
80 A
63 A
5000 PEAK LET-THRU IN KA 50 A
40 A

Ip
3000 10 4

3
2.
2000 35 A

=
32 A

Im
25 A
10 3 20 A
16 A
500 10 A
300 6A
200 4A
10 3
10 2

50
30
20

10
4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 315 355 400 450 500 630 800 10 2
(400V) 10 10 2 10 3 10 4 10 5 10 6

SHORT CIRCUIT CURRENT Ip IN kA

Time VS. Current Characteristics


RATED CURRENT IN A
630 A
450 A
100 A

200 A

250 A

355 A
20 A

32 A

40 A

63 A

400 A
125 A
160 A

224 A

315 A

500 A
10 A
16 A

25 A

35 A

50 A

80 A

(400 V)
800 A
4A

6A

10 2

10
MELTING TIME

10 -1

10 -2

10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A

GPEU28
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM Curves Set

NH-fuses, 690VAC aM
Total Clearing I2t Current Limitation Curves

10 7

5000000
3000000
10 6
2000000

10 6

500000 500 A
450 A
300000 400 A
355 A
200000 315 A
10 5 250 A
224 A
10 5 200 A
160 A
50000 125 A
100 A
30000 80 A
20000 63 A
50 A
40 A
10 4 10 4
PEAK LET-THRU IN KA

35 A
32 A
5000 25 A

Ip
20 A

3
3000

2.
16 A

=
2000 10 A

Im
6A
10 3 4A
10 3
500
300
200

10 2

50 10 2
30 10 10 2 10 3 10 4 10 5 10 6
20

10 SHORT CIRCUIT CURRENT Ip IN kA


4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 315 355 400 450 500

Time VS. Current Characteristics


RATED CURRENT IN A
450 A
100 A

200 A

250 A

355 A
20 A

32 A

40 A

63 A

400 A
125 A
160 A

224 A

315 A

500 A
10 A
16 A

25 A

35 A

50 A

80 A
4A

6A

10 2

10
MELTING TIME

10 -1

10 -2

10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A

GPEU29
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
400V gTr

NH-fuses, 400VAC gTr


with non-isolated gripping
lugs, double indicator,
contact blades, complying
with DIN VDE 0636 Part 22,
DIN VDE 0636 Part 201

Transformer Rated current Power dissipation weight


Size Voltage FS ref.-no. Previous ref. pack. Catalog Number
capacity (kVA) IN(A) (W) kg/pce
2 400 50,0 72 H232813(2) 5A251. 0,37 1 NH2GTR50KVA
2 400 75,0 108 G232812(2) 5A257. 0,37 1 NH2GTR75KVA
2 400 100,0 145 12,0 B232807(2) 5A263. 0,37 1 NH2GTR100KVA
2 400 125,0 181 15,0 C232808(2) 5A265. 0,37 1 NH2GTR125KVA
2 400 160,0 231 18,4 D232809(2) 5A269. 0,37 1 NH2GTR160KVA
2 400 200,0 289 22,0 E232810(2) 5A271. 0,37 1 NH2GTR200KVA
2 400 250,0 361 27,0 F232811(2) 5A275. 0,37 1 NH2GTR250KVA
3 400 250,0 361 26,0 J232814(2) 5A375. 0,61 1 NH3GTR250KVA
3 400 315,0 455 34,0 K232815(2) 5A379. 0,61 1 NH3GTR315KVA
3 400 400,0 578 39,0 L232816(2) 5A383. 0,61 1 NH3GTR400KVA
3 400 500,0 723 M232817 5A387. 0,81 1 NH3GTR500KVA
3 400 630,0 910 N232818 5A389. 0,81 1 NH3GTR630KVA
contact blades for NH-bottom size 4a with swivel unit
4a 400 100,0 145 11,4 *) T212997 8008.100005 2,09 1 NH4AGTR100KVA-8
4a 400 125,0 181 14,5 *) Y213507 8008.125005 2,17 1 NH4AGTR125KVA-8
4a 400 160,0 231 17,8 *) Z214014 8008.160005 1,95 1 NH4AGTR160KVA-8
4a 400 200,0 289 20,6 *) C214523 8008.200005 1,95 1 NH4AGTR200KVA-8
4a 400 250,0 361 25,7 *) F215032 8008.250005 2,13 1 NH4AGTR250KVA-8
4a 400 315,0 455 33,2 *) M215544 8008.315005 1,95 1 NH4AGTR315KVA-8
4a 400 400,0 578 38,1 *) S216055 8008.400005 1,95 1 NH4AGTR400KVA-8
4a 400 500,0 723 53,2 *) V216563 8008.500005 1,95 1 NH4AGTR500KVA-8
4a 400 630,0 910 68,7 *) E217078 8008.630005 1,95 1 NH4AGTR630KVA-8
4a 400 800,0 1155 90,4 *) R217595 8008.800005 2,10 1 NH4AGTR800KVA-8
*) with indicator on top
(2)
These fuses are able to operate it 500VAC (tested at 550V +0 +5%).

GPEU30
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
400V gTr
gTr Curves Set

NH-fuses, 400VAC gTr

Time VS. Current Characteristics

RATED CURRENT IN A
MELTING TIME

PROSPECTIVE CURRENT IP IN A
APPARENT POWER TRANSFORMER IN KVA
PEAK LET-THRU IN kA

SHORT CIRCUIT CURRENT IP IN KA

GPEU31
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG/aM Mechanics for ceramic Body

NH Fuses-links

Rated current
Size a1 a2 a3 a4 b c1 e1 e2 e4 h
IN(A)
Standard 400V and 500V gG with non-isolated gripping lugs
size 000 2 – 100A 79 52 45,5 49,5 15 35 40,5 20,8 6 52,5
size 00 125/160A 79 52,8 45 50 15 35 47,5 29,5 6 59,5
size 0 2 – 160A (500V) 125 66,8 61 66 15 35 47,5 29,5 6 59,5
size 116 – 100A (500V), 16 – 125A (400V) 135 70,8 63 68 15 40 47,5 29,5 6 64,5
size 1125 – 355A (500V),160 – 250A (400V) 135 70,8 63 68 20 40 52,5 39,5 6 64,5
size 2 16 – 250A 150 72,3 63 68 20 48 52,5 39,5 6 72,5
size 2 300 – 500A 150 72,3 63 68 26 48 60 51 6 72
size 3 250 – 400A 150 72,3 63 68 26 60 60 51 6 83,5
size 3 425 – 800A 150 72,3 63 68 33 60 74 70 6 86
size 4 400 – 1250A 200 85 62 68 49 86 108 90 8 117,5
size 4a 500 – 1250A 200 85 84 90 49 86 108 90 6 117,5
Standard 400V and 500V gG (SGL) with isolated gripping lugs
size 000 2 – 100A 78 53,4 45,7 49,7 15 35 40,5 20,8 6 52,5
size 00 125/160A 79 53,5 44,8 49 15 35 47,5 29,5 6 59,5
size 0 2 – 160A (500V) 125 67,5 62,5 66,7 15 35 47,5 29,5 6 59,5
size 116 – 100A (500V), 16 – 125A (400V) 135 71,5 62,8 67 15 40 47,5 29,5 6 64,5
size 1125 – 250A (500V), 160 – 250A (400V) 135 73,4 63 67,2 20 40 52,5 39,5 6 64,5
size 2 16 – 250A 150 73,4 63 67,2 20 48 52,5 39,5 6 72,5

GPEU32
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG/aM Mechanics for
ceramic Body

NH Fuses-links

Rated current
Size a1 a2 a3 a4 b c1 e1 e2 e4 h
IN(A)

size 2 300 – 400A 150 73,4 63 67,2 26 48 60 51 6 72


size 3 250 – 400A 150 73,4 63 68 26 60 60 51 6 83,5
size 3 425 – 630A 150 73,4 63 68 33 60 74 70 6 86
NH 690V gG with non-isolated gripping lugs
size 000 2 – 35A 79 53,8 45 49 15 35,8 40 20 6 47,8
size 00 40 – 100A 79 53,8 45 49 15 35,8 48 30 6 47,8
size 1 16 – 160A 135 75 64 68 20 40 44 30 6 52
size 1 200 – 250A 135 75 64 68 20 40 47 39 6 52
size 2 35 – 100A 150 75 64 68 626 48 44 30 6 60
size 2 125 – 315A 150 75 64 68 26 60 47 39 6 72
size 3 250 – 300A 150 75 64 68 26 60 47 39 6 72
size 3 315 – 425A 150 75 64 68 33 60 58 51 6 72
size 3 500A 150 75 64 68 33 70 64 64 6 72
size 4 400 – 800A 200 85 62 68 49 86 108 90 8 117,5
size 4a 400 – 800A 200 85 84 90 49 86 108 90 6 117,5
NH 690V gG (SGL) with isolated gripping lugs
size 000 2 – 35A 79 53,8 45 49 15 35,8 40,5 21 6 47,8
size 0 40 – 125A 79 53,8 45 49 15 35,8 40,5 30 6 47,8
size 1 35 – 200A 135 75 64 68 20 40 51 39 6 52
size 2 32 – 200A 150 75 64 68 26 48 51 39 6 60
size 2 250 – 315A 150 75 64 68 26 48 60 46 6 60
size 3 250 – 315A 150 73,4 63 68 26 60 60 51 6 83,5
size 3 350 – 425A 150 73,4 63 68 33 60 74 70 6 86
NH 500V aM with non-isolated gripping lugs
size 000 2 – 80A 79 53,8 45 49 15 35,8 40,5 21 6 47,8
size 00 100 – 160A 79 53,8 45 49 15 35,8 40,5 30 6 47,8
size 0 100 – 200A 125 68 64 68 15 35,8 44 30 6 47,8
size 1 160 – 250A 135 75 64 68 20 40 47 39 6 52
size 2 250 – 500A 150 75 64 68 26 48 47 39 6 60
size 3 315 – 630A 150 75 64 68 33 60 58 51 6 72
size 4 630 – 1250A 200 85 62 68 49 86 108 90 8 117,5
NH 690V aM with non-isolated gripping lugs
size 000 2 – 80A 79 52 45,5 49,5 15 35 40,5 20,8 6 52,5
size 00 50 – 160A 79 52,8 45 50 15 35 47,5 29,5 6 59,5
size 0 6 – 200A 125 66,8 61 66 15 35 47,5 29,5 6 59,5
size 1 16 – 315A 135 70,8 63 68 20 40 52,5 39,5 6 64,5
size 2 35 – 500A 150 72,3 63 68 26 48 60 51 6 72
size 3 250 – 630A 150 72,3 63 68 33 60 74 70 6 86
size 4 400 – 1250A 200 85 62 68 49 86 108 90 8 117,5
size 4a 500 – 1250A 200 85 84 90 49 86 108 90 6 117,5
NH 400/500V gTr with non-isolated gripping lugs
size 2 50 – 250kVA 150 72,3 63 68 26 48 60 51 6 72
size 3250 – 400kVA (500V), 500 - 630VA (400V) 150 72,3 63 68 33 60 74 70 6 86
size 4a 100 – 800kVA 200 85 84 90 49 86 108 90 6 117,5

GPEU33 07/05
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
Microswitch indication system for
NH-fuses size 000 to 3 with non-isolated gripping lugs

FS ref.-no. Designation weight g/piece pack. unit Catalog Number

2,8mm clips, automatically resettable


G210157 MS 4L 2-5 B2 + PRES 26 3 MS4L2-5B2PRES
6,3mm clips, automatically resettable
F210156 MS 4L 2-5 B6 + PRES 30 3 MS4L2-5B6PRES

25 61

7 3

33

45

60,5
15,5

Automatically resettable, these microswitch In case of improper mounting or fuse melting,


systems indicate fuse pressence (PRES) and proper this is indicated (terminal 1-4 closed).
mounting.

Fig.1 Fig.2

MS 4L 2-5 B6 + PRES MS 4L 2-5 B2 + PRES


F210156 G210157
6,3mm clips 2,8mm clips

GPEU34
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3

H216690 gG 500 - 690VAC


Rated current Rated voltage Breaking
Size Previous ref. Ref.-no. Catalog Number
IN(A) (V) capacity
0 32 690V 36443 P213637 80kA - 690V NH0GG69V32P-2
0 35 690V 36445 S214146 80kA - 690V NH0GG69V35P-2
0 40 690V 36447 W214655 80kA - 690V NH0GG69V40P-2
0 50 690V 36451 B215166 80kA - 690V NH0GG69V50P-2
0 63 690V 36455 D215674 80kA - 690V NH0GG69V63P-2
0 80 690V 36459 J216185 80kA - 690V NH0GG69V80P-2
0 100 690V 36463 H216690 80kA - 690V NH0GG69V100P-2
0 125 500V 36465 V217207 120kA - 500V NH0GG50V125P-2
R223000 0 160 500V 36469 A217718 120kA - 500V NH0GG50V160-2
0 200 500V 36471 K218233 120kA - 500V NH0GG50V200P-2
1 80 690V 36559 Y218751 80kA - 690V NH1GG69V80P-2
1 100 690V 36563 M219270 80kA - 690V NH1GG69V100P-2
1 125 690V 36565 P219801 80kA - 690V NH1GG69V125P-2
1 160 690V 36569 Z222478 80kA - 690V NH1GG69V160P-2
1 200 690V 36571 R223000 80kA - 690V NH1GG69V200P-2
1 224 500V 36573 Y200788 120kA - 500V NH1GG50V224P-2
1 250 500V 36575 Q201333 120kA - 500V NH1GG50V250P-2
1 315 500V 36579 Z201847 120kA - 500V NH1GG50V315P-2
1 355 500V 36581 W211067 120kA - 500V NH1GG50V355P-2
2 125 690V 36665 W212102 80kA - 690V NH2GG69V125P-2
2 160 690V 36669 L212622 80kA - 690V NH2GG69V160P-2
X214656 2 200 690V 36671 Y213139 80kA - 690V NH2GG69V200P-2
2 224 690V 36673 Q213638 80kA - 690V NH2GG69V224P-2
2 250 690V 36675 T214147 80kA - 690V NH2GG69V250P-2
2 315 690V 36679 X214656 80kA - 690V NH2GG69V315P-2
2 355 500V 36681 E215675 120kA - 500V NH2GG69V355P-2
2 400 500V 36683 K216186 120kA - 500V NH2GG50V400P-2
2 500 500V 36687 W217208 120kA - 500V NH2GG50V500P-2
3 315 690V 36779 B217719 80kA - 690V NH3GG69V315P-2
3 355 690V 36781 L218234 80kA - 690V NH3GG69V355P-2
3 400 690V 36783 Z218752 80kA - 690V NH3GG69V400P-2
3 500 690V 36787 N219271 80kA - 690V NH3GG69V500P-2
3 630 500V 36789 Q219802 120kA - 500V NH3GG50V630P-2
Pack. : 3 pieces
N219271
Dimensions
0 1 2 3
A 124.5 134.5 150 150
B 66 67 67 67
C 39 40 56 69
D 49 55 62.5 76
E 14.5 16 19 24
F 15.5 15.5 15.5 15.5
G 14 14.5 14.5 14.5
H 15 20 26 32
I 6 6 6 6
J 14 14 15 16
K 10 10 10 10
L 59 65 72.5 86
M 60 61 61 61
N 3 3 3 3
O 41.5 45 - -
P 47 52 60 60

GPEU36 07/05
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3

gG 500 - 690VAC
MELTING TIME - CURRENT DATA – 6-800 AMPERES
TIME IN SECONDS

CURRENT IN AMPERES

Striker
PEAK LET-THRU CURRENT DATA – 6-800 AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES

BEFORE AFTER

AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES

GPEU37
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3

gG 500 - 690VAC

Power Loss (Watts) at Rated Current


Rated current Size
IN(A) 0 1 2 3

32 3.7 W
35 4.0 W
40 4.5 W
50 5.2 W
63 6.2 W
80 7.5 W 6.9 W
100 8.5 W 8.1 W
125 10.7 W 9.6 W 9.5 W
160 13.5 W 11.9 W 11.5 W
200 15.0 W 14.9 W 14.5 W
224 16.7 W 16.0 W
250 18.7 W 17.5 W
315 25.0 W 23.0 W 23 W
355 28.0 W 25.0 W 25 W
400 29.0 W 29 W
425 34.0 W 34 W
500 39.0 W 39 W
630 47 W
800 67 W

Typical values allowed by the standards


Rated current 0 1 2 3
IN(A) 160A 250A 400A 630A

VDE 0660 (500V) 25 W 32 W 45 W 60 W


IEC 269-2-1 (660V) 25 W 32 W 45 W 60 W
UNE 21103 (500V) 25 W 32 W 45 W 60 W
NFC 63210 (500V) 25 W 32 W 45 W 60 W
VDE 0636 (660V) - 23 W 34 W 48 W
VDE 0636 (500V) 16 W 23 W 34 W 48 W
IEC 269 (500V) 16 W 23 W 34 W 48 W
UNESA (500V) 17 W 26 W 32 W 48 W
WDE W (500V) 16 W 21 W 32 W 42 W

GPEU38
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3

gG 500 - 690VAC

I2T CHARACTERISTICS – DISCRIMINATION


I2T (AMPERE2 SECONDS)

FUSE-LINK RATED CURRENT IN (A)

_ _ _ 660V
_ _ _ 500V Operating I2t
_ _ _ 380V

_ _ _ Pre-arcing I2t

GPEU39
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Ceramic body with French striker
aM 690V Size 0 to 3

L216187 aM 500 - 690VAC


Rated current Rated voltage Breaking
Size Previous ref. Ref.-no. Catalog Number
IN(A) (V) capacity
0 32 690V 37443 Z213140 80kA - 690V NH0AM69V32P-2
0 40 690V 37447 R213639 80kA - 690V NH0AM69V40P-2
0 50 690V 37451 V214148 80kA - 690V NH0AM69V50P-2
0 63 690V 37455 Y214657 80kA - 690V NH0AM69V63P-2
0 80 690V 37459 C215167 80kA - 690V NH0AM69V80P-2
0 100 690V 37463 F215676 80kA - 690V NH0AM69V100P-2
0 125 690V 37465 L216187 80kA - 690V NH0AM69V125P-2
0 160 690V 37469 J216691 80kA - 690V NH0AM69V160P-2
P219272
0 200 500V 37471 X217209 120kA - 500V NH0AM50V200P-2
1 80 690V 37559 C217720 80kA - 690V NH1AM69V80P-2
1 100 690V 37563 M218235 80kA - 690V NH1AM69V100P-2
1 125 690V 37565 A218753 80kA - 690V NH1AM69V125P-2
1 160 690V 37569 P219272 80kA - 690V NH1AM69V160P-2
1 200 690V 37571 B222480 80kA - 690V NH1AM69V200P-2
1 250 690V 37575 T223002 80kA - 690V NH1AM69V250P-2
1 315 500V 37579 A200790 120kA - 500V NH1AM50V315P-2
2 125 690V 37665 S201335 80kA - 690V NH2AM69V125-2
2 160 690V 37669 B201849 80kA - 690V NH2AM69V160-2
2 200 690V 37671 Y211069 80kA - 690V NH2AM69V200-2
2 224 690V 37673 P211590 80kA - 690V NH2AM69V224P-2
2 250 690V 37675 Y212104 80kA - 690V NH2AM69V250-2
Y212104 2 315 690V 37679 N212624 80kA - 690V NH2AM69V315P-2
2 355 690V 37681 A213141 80kA - 690V NH2AM69V355-2
2 400 690V 37683 S213640 80kA - 690V NH2AM69V400-2
2 500 500V 37687 W214149 120kA - 500V NH2AM50V500-2
3 315 690V 37779 Z214658 80kA - 690V NH3AM69V315P-2
3 355 690V 37781 D215168 80kA - 690V NH3AM69V355P-2
3 400 690V 37783 G215677 80kA - 690V NH3AM69V400P-2
3 500 690V 37787 M216188 80kA - 690V NH3AM69V500P-2
3 630 500V 37789 K216692 120kA - 500V NH3AM50V630P-2

Pack. : 3 pieces

M216188
Dimensions
0 1 2 3
A 124.5 134.5 150 150
B 66 67 67 67
C 39 40 56 69
D 49 55 62.5 76
E 14.5 16 19 24
F 15.5 15.5 15.5 15.5
G 14 14.5 14.5 14.5
H 15 20 26 32
I 6 6 6 6
J 14 14 15 16
K 10 10 10 10
L 59 65 72.5 86
M 60 61 61 61
N 3 3 3 3
O 41.5 45 - -
P 47 52 60 60

GPEU40
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Ceramic body with French striker
aM 690V Size 0 to 3

aM 500 - 690VAC
MELTING TIME - CURRENT DATA – 32-630 AMPERES
TIME IN SECONDS

CURRENT IN AMPERES

PEAK LET-THRU CURRENT DATA – 32-630 AMPERES


MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES

AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES

GPEU41
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Ceramic body with French striker
aM 690V Size 0 to 3

aM 500 - 690VAC

Power Loss (Watts) at Rated Current


Rated current Size
IN(A) 0 1 2 3

32 2.4 W
40 2.8 W
50 3.6 W
63 4.6 W
80 6.0 W 6.0 W
100 7.5 W 7.5 W
125 9.5 W 9.9 W
160 12.0 W 12.7 W 12.7 W
200 16.4 W 16.4 W
224 18.7 W 18.7 W
250 21.5 W 21.5 W
315 29.0 W 25.0 W
355 32.0 W 29.0 W
400 34.0 W 34.0 W
425 38.5 W
500 45.0 W
630 60.0 W

I2T CHARACTERISTICS – DISCRIMINATION

_ _ _ 660V
_ _ _ 500V Operating I2t
_ _ _ 380V

_ _ _ Pre-arcing I2t
I2T (AMPERE2 SECONDS)

FUSE-LINK RATED CURRENT IN (A)

GPEU42
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 00

from 10 to 160 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR


• COMPLYING WITH IEC 269.1 and 2.1 NF EN 60269.1 & 2 NF C 63210 AND DIN 43620 STANDARDS
• DIMENSIONS:

30
52
2.5 10
44

6
59
15 46
14.5
78 Weight: 150 g

Main Characteristics

Voltage Current Watts With BLOWN FUSE indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Reference Number Catalog Number
10 1 gG 00 L / 10 M098290 NH00GG50V10-3
16 1.4 gG 00 L / 16 N098291 NH00GG50V16-3
20 1.8 gG 00 L / 20 P098292 NH00GG50V20-3
25 2.1 gG 00 L / 25 Q098293 NH00GG50V25-3
32 3 gG 00 L / 32 R098294 NH00GG50V32-3
35 3 gG 00 L / 35 S098295 NH00GG50V35-3
00 500 40 3.3 gG 00 L / 40 T098296 NH00GG50V40-3
50 4.5 gG 00 L / 50 V098297 NH00GG50V50-3
63 6 gG 00 L / 63 X098299 NH00GG50V63-3
80 7 gG 00 L / 80 Z098301 NH00GG50V80-3
100 7.5 gG 00 L / 100 A098302 NH00GG50V100-3
125 13 gG 00 L / 125 B098303 NH00GG50V125-3
160 15 gG 00 L / 160 D098305 NH00GG50V160-3

Accessories: Neutral link Z218269


Pull-out handle - PMP - Part # P215592

GPEU44
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 00

from 10 to 160 A
Total Clearing I2t Current Limitation Curves
I2t (A2S)
106 Ic (kA)
100

105

104 160
125
100
10 80

63
103 50

40
32 35
25
20
102

16
10

101 1
10 16 20 25 32 35 40 50 63 80100125160 1 10 100
Rating (A)
Ip (kA)
b: total clearing I2t @ 500 V
Ic = Peak let-through current

Ip = Available fault current


a: pre-arcing I2t

Time VS. Current Characteristics


20 32 40 125

10 16 25 35 50 63 80 100 160
104
t (s) Breaking
t (s) = Pre-arcing duration
capacity
100 kA
103

102

10

10-1

Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT

GPEU45
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 0 and 1

from 40 to 250 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR or TRIP-INDICATOR


• COMPLYING WITH IEC 269.1 AND 2.1 NF EN 60269.1 & 2 NF C 63210 - 63211 AND DIN 43620
• DIMENSIONS:

D1 D1
D D
D2 G M
G M
B B
F
e e
A C A C
H K H

N N
L J L J

With trip-indicator With blown fuse indicator

Size A B C D D1 D2* F* G H J K L M N e Wgt.


0 46 62 59 67 36 39 14 2,5 15 14,5 14,5 125 10 14,5 6 230g
1 52 64 64 74 47 47 14 3 21 16 14,5 135 10 14,5 6 400g
* For fuses with trip-indicator

Voltage Current Watts With blown fuse indicator With trip-indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Ref. Number Catalog Number Designation Ref. Number Catalog Number
40 4.2 gG 0 / 40 A095013 NH0GG50V40-3 gG 0 / 40 P T095214 NH0GG50V40-4
50 5.5 gG 0 / 50 B095014 NH0GG50V50-3 gG 0 / 50 P V095215 NH0GG50V50-4
63 6.5 gG 0 / 63 C095015 NH0GG50V63-3 gG 0 / 63 P W095216 NH0GG50V63-4
80 8.5 gG 0 / 80 D095016 NH0GG50V80-3 gG 0 / 80 P Y095218 NH0GG50V80-4
0 500
100 9.5 gG 0 / 100 E095017 NH0GG50V100-3 gG 0 / 100 P A095220 NH0GG50V100-4
125 12 gG 0 / 125 F095018 NH0GG50V125-3 gG 0 / 125 P C095222 NH0GG50V125-4
160 15 gG 0 / 160 G095019 NH0GG50V160-3 gG 0 / 160 P G095226 NH0GG50V160-4
200 19 gG 0 / 200 H095020 NH0GG50V200-3
80 8.5 gG 1 / 80 K095022 NH1GG50V80-3 gG 1 / 80 P D095591 NH1GG50V80-4
100 9.6 gG 1 / 100 P095026 NH1GG50V100-3 gG 1 / 100 P E095592 NH1GG50V100-4
125 12.5 gG 1 / 125 T095030 NH1GG50V125-3 gG 1 / 125 P F095593 NH1GG50V125-4
1 500
160 15 gG 1 / 160 V095031 NH1GG50V160-3 gG 1 / 160 P G095594 NH1GG50V160-4
200 19 gG 1 / 200 W095032 NH1GG50V200-3 gG 1 / 200 P H095595 NH1GG50V200-4
250 23 gG 1 / 250 Z095035 NH1GG50V250-3 gG 1 / 250 P K095597 NH1GG50V250-4

Accessories: Neutral link Reference Number Z219304 - Reference Number A219834


Pull-out handle - PMP Reference Number P215592

GPEU46
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 0 and 1

from 40 to 250 A
Total Clearing I2t Current Limitation Curves
I2t (A2S) Ic (kA)
107
100

106

250
200
105 160
125
100
10
80
104 63
50
40

103

102
1
40 50 63 80 100 125 160 200 250
1 10 100
Rating (A)
b: total clearing I t @ 500 V
2 Ip (kA)
Ic = Peak let-through current

a: pre-arcing I2t Ip = Available fault current

Time VS. Current Characteristics


125 200

40 50 63 80 100 160 250


104 Breaking
t (s) capacity
t (s) = Pre-arcing duration
100 kA

103

102

10

10-1

Ip (A) = R.M.S.
AVAILABLE
10 -2
10 100 1 000 10 000 Ip (A) FAULT CURRENT

GPEU47
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 2 and 3

from 125 to 630 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR or TRIP-INDICATOR


• COMPLYING WITH IEC 269.1 and 2.1, NF EN 60269.1 & 2 NF C 63210 - 63211 AND DIN 43620
• DIMENSIONS:

D1 D1
D D2 D
G M G M
B B
F
e e
A C A C
H K H

N N
L J L J

With trip-indicator With blown fuse indicator

Size A B C D D1 D2* F* G H J K L M N e Wgt.


2 60 64 72 74 50 50 14 3 28 19 14,5 150 10 14,5 6 590g
3 75 61 88 75 70 64 14 2,5 36 23 14,5 150 10 18 6 850g
* For fuses with trip-indicator

Voltage Current Watts With blown fuse indicator With trip-indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Ref. Number Catalog Number Designation Ref. Number Catalog Number
125 12 gG 2 /125 H095066 NH2GG50V125-3 gG 2 /125 P X095033 NH2GG50V125-4
160 15 gG 2 /160 K095068 NH2GG50V160-3 gG 2 /160 P Y095034 NH2GG50V160-4
200 19 gG 2 /200 M095070 NH2GG50V200-3 gG 2 /200 P A095036 NH2GG50V200-4
2 500
250 23 gG 2 /250 G095042 NH2GG50V250-3 gG 2 /250 P F095041 NH2GG50V250-4
315 24 gG 2 /315 H095043 NH2GG50V315-3 gG 2 /315 P K095045 NH2GG50V315-4
400 33 gG 2 /400 J095044 NH2GG50V400-3 gG 2 /400 P M095047 NH2GG50V400-4
315 24 gG 3 /315 W095170 NH3GG50V315-3 gG 3 /315 P N095048 NH3GG50V315-4
400 33 gG 3 /400 V095054 NH3GG50V400-3 gG 3 /400 P P095049 NH3GG50V400-4
3 500
500 36 gG 3 /500 W095055 NH3GG50V500-3 gG 3 /500 P N095071 NH3GG50V500-4
630 45 gG 3 /630 X095056 NH3GG50V630-3 gG 3 /630 P P095072 NH3GG50V630-4

Accessories : Neutral link BS2 Reference Number J097712 - BS3 Reference Number K097713
Pull-out handle - PMP Reference Number P215592

GPEU48
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 2 and 3

from 125 to 630 A


Total Clearing I2t Current Limitation Curves
I t (A S)
2 2

108
Ic (kA)
100

107
630
500
400
315
250
10 6
200
160
125

10
105

104

103
125 160 200 250 315 400 500 630 1

b: total clearing I2t @ 500 V Rating (A) 1 10 100


Ic = Peak let-through current Ip (kA)
a: pre-arcing I2t Ip = Available fault current

Time VS. Current Characteristics


125 200 400 630

160 250 315 500


104
t (s) Breaking
t (s) = Pre-arcing duration capacity
100 kA
103

102

10

10-1

Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT

GPEU49
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 4

from 630 to 1250 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR or TRIP-INDICATOR


• COMPLYING WITH IEC 269.1 and 2.1, NF EN 60269.1 & 2 NF C 63210 - 63211 AND DIN 43620
• DIMENSIONS:

D1
D D2
G M
B
F
e With trip-indicator
A C
H K
N
150 J
L

D D1
G M
B

e
H
A C With blown fuse indicator
N
150 J
L

Size A B C D D1 D2* F* G H J K L M N e Wgt.


4 107 61 119 78 90 77 14 2,5 60 27 14,5 200 10 23 8 1900g
* For fuses with trip-indicator

Voltage Current Watts With blown fuse indicator With trip-indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Ref. Number Catalog Number Designation Ref. Number Catalog Number
630 45 gG 4 / 630 S098318 NH4GG50V630-3 gG 4 / 630 P G088510 NH4GG50V630-4
800 51 gG 4 / 800 T098319 NH4GG50V800-3 gG 4 / 800 P J088512 NH4GG50V800-4
4 500
1000 77 gG 4 / 1000 V098320 NH4GG50V1000-3 gG 4 / 1000 P K088513 NH4GG50V1000-4
1250 80 gG 4 / 1250 W098321 NH4GG50V1250-3 gG 4 / 1250 P L088514 NH4GG50V1250-4

Accessories: Neutral link - BS4 Reference Number M097715


Pull-out handle - PMP Reference Number P215592

GPEU50
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 4

from 630 to 1250 A


Total Clearing I2t Current Limitation Curves
I t (A S)
2 2
Ic (kA)
108 100 1250
1000
800
630
107

106

10

105

104

1
103
1 10 100
630 800 1000 1250 Rating (A)
Ip (kA)
2
b: total clearing I t @ 500 V Ic = Peak let-through current
Ip = Available fault current
a: pre-arcing I2t

Time VS. Current Characteristics


800 1250

630 1000
104
t (s) Breaking
t (s) = Pre-arcing duration capacity
100 kA
103

102

10

10-1

Ip (A) = R.M.S.
10-2 10 100 1 000 10 000 Ip (A)
AVAILABLE
FAULT CURRENT
GPEU51
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 00

from 16 to 125 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR


• COMPLYING WITH IEC 269.1 and 2.1 NF EN 60269.1 & 2 NF C 63210 AND DIN 43620 STANDARDS
• DIMENSIONS:

30
52
2.5 10
44

6
59
15 Weight: 150 g
46
14.5
78

Voltage Current Watts With blown fuse indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Ref. Number Catalog Number
16 0.8 aM 00 L /16 F098307 NH00AM50V16-3
20 1.1 aM 00 L /20 G098308 NH00AM50V20-3
25 1.3 aM 00 L /25 H098309 NH00AM50V25-3
32 1.8 aM 00 L /32 J098310 NH00AM50V32-3
35 2.0 aM 00 L /35 K098311 NH00AM50V35-3
500
00 40 2.5 aM 00 L /40 L098312 NH00AM50V40-3
50 3.0 aM 00 L /50 M098313 NH00AM50V50-3
63 3.6 aM 00 L /63 N098314 NH00AM50V63-3
80 5.2 aM 00 L /80 P098315 NH00AM50V80-3
100 6.0 aM 00 L /100 Q098316 NH00AM50V100-3
400 125 7.0 aM 00 L /125 R098317 NH00AM40V125-3

Accessories: Neutral link BS00 - Reference Number F097709


Pull-out handle - PMP - Reference Number P215592

GPEU52
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 00

from 16 to 125 A
Total Clearing I2t Current Limitation Curves
I2t (A2S)
107 Ic (kA)

106 100

105

125
100
104 80
10 63
50
40
32

103 25
20
16

35
102
16 20 25 32 35 40 50 63 80 100 125
Rating (A)

b: total clearing I t @ 500 V


2
1 10 100
Ic = Peak let-through current Ip (kA)
a: pre-arcing I t 2
Ip = Available fault current
Time VS. Current Characteristics

t (s) t (s) = Pre-arcing duration


Breaking
103 capacity
100 kA
35
20 50 100
102 16 25 32 40 63 80 125

10

10-1

10-2 Ip (A) = R.M.S.


10 100 1 000 10 000 Ip (A) AVAILABLE
FAULT CURRENT
GPEU53
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 0 and 1

from 40 to 315 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR


• COMPLYING WITH IEC 269.1 and 2.1 NF EN 60269.1 & 2 NF C 63210 AND DIN 43620 STANDARDS
• DIMENSIONS:
D1
D D1
D2 D
G M M
B G
B
F
e
e
A C
H K A C
H
N
N
L J L J
With trip-indicator With blown fuse indicator

Size A B C D D1 D2* F* G H J K L M N e Wgt.


0 46 62 59 67 36 39 14 2,5 15 14,5 14,5 125 10 14,5 6 230g
1 52 64 64 74 47 47 14 3 21 16 14,5 135 10 14,5 6 400g
* For fuses with trip-indicator

Voltage Current Watts With blown fuse indicator With trip-indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Ref. Number Catalog Number Designation Ref. Number Catalog Number
40 2,7 aM 0 / 40 K095114 NH0AM50V40-3 aM 0 / 40 P N095232 NH0AM50V40-4
50 3,2 aM 0 / 50 L095115 NH0AM50V50-3 aM 0 / 50 P R095235 NH0AM50V50-4
63 3,9 aM 0 / 63 M095116 NH0AM50V63-3 aM 0 / 63 P X095240 NH0AM50V63-4
80 5,5 aM 0 / 80 P095118 NH0AM50V80-3 aM 0 / 80 P Z095242 NH0AM50V80-4
0 500
100 6,5 aM 0 / 100 R095120 NH0AM50V100-3 aM 0 / 100 P A095243 NH0AM50V100-4
125 8,5 aM 0 / 125 T095122 NH0AM50V125-3 aM 0 / 125 P B095244 NH0AM50V125-4
160 11,5 aM 0 / 160 Y095126 NH0AM50V160-3 aM 0 / 160 P M095254 NH0AM50V160-4
200 13,5 aM 0 / 200 R088519 NH0AM50V200-3 aM 0 / 200 P F088509 NH0AM50V200-4
80 5,5 aM 1 / 80 R095166 NH1AM50V80-3 aM 1 / 80 P P095256 NH1AM50V80-4
100 6,5 aM 1 / 100 T095168 NH1AM50V100-3 aM 1 / 100 P E095270 NH1AM50V100-4
125 8,5 aM 1 / 125 C095130 NH1AM50V125-3 aM 1 / 125 P V095330 NH1AM50V125-4
1 500 160 11,5 aM 1 / 160 D095131 NH1AM50V160-3 aM 1 / 160 P W095331 NH1AM50V160-4
200 13,5 aM 1 / 200 E095132 NH1AM50V200-3 aM 1 / 200 P X095332 NH1AM50V200-4
250 17 aM 1 / 250 H095135 NH1AM50V250-3 aM 1 / 250 P A095335 NH1AM50V250-4
315 24 aM 1 / 315 T088521 NH1AM50V315-3 aM 1 / 315 P B095336 NH1AM50V315-4

Accessories: Neutral link BS0 Reference Number G097710 - BS1 Reference Number H097711
Pull-out handle - PMP Reference Number P215592

GPEU54
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 0 and 1

from 40 to 315 A
Total Clearing I2t Current Limitation Curves
I2t (A2S)
107 Ic (kA)

106 100

105 315
250
200
160
125
100
104 80
10 63
50
40

103

102
40 50 63 80 100 125 160 200 250 315
Rating (A)
2
b: total clearing I t @ 500 V 1 10 100
Ic = Peak let-through current Ip (kA)
a: pre-arcing I t 2
Ip = Available fault current

Time VS. Current Characteristics


t (s) t (s) =Pre-arcing duration
103 Breaking
capacity
100 kA
50 80 125 250
102 40 63 100 160 200 315

10

10-1

Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT

GPEU55
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 2 and 3

from 125 to 630 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR OR TRIP-INDICATOR


• COMPLYING WITH IEC 269.1 AND 2.1, NF EN 60269.1 & 2 NF C 63210 - 63211 AND DIN 43620
• DIMENSIONS:
D1 D1
D D
D2 G M
G M B
B
F
e e

A C A C
H H
K

N N
L L J
J

With trip-indicator With blown fuse indicator

Size A B C D D1 D2* F* G H J K L M N e Wgt.


2 60 64 72 74 50 50 14 3 28 19 14,5 150 10 14,5 6 590g
3 75 61 88 75 70 64 14 2,5 36 23 14,5 150 10 18 6 850g
* For fuses with trip-indicator

Voltage Current Watts With blown fuse indicator With trip-indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Ref. Number Catalog Number Designation Ref. Number Catalog Number
125 8,5 aM 2 /125 P095210 NH2AM50V125-3 aM 2 /125 P Z095196 NH2AM50V125-4
160 11,5 aM 2 /160 Q095211 NH2AM50V160-3 aM 2 /160 P S095213 NH2AM50V160-4
200 13,5 aM 2 /200 R095212 NH2AM50V200-3 aM 2 /200 P F095340 NH2AM50V200-4
2 500 250 17 aM 2 /250 Q095142 NH2AM50V250-3 aM 2 /250 P H095342 NH2AM50V250-4
315 24 aM 2 /315 R095143 NH2AM50V315-3 aM 2 /315 P J095343 NH2AM50V315-4
400 28 aM 2 /400 S095144 NH2AM50V400-3 aM 2 /400 P K095344 NH2AM50V400-4
500 34 aM 2 /500 W088523 NH2AM50V500-3 aM 2 /500 P L095345 NH2AM50V500-4
315 24 aM 3 /315 J095182 NH3AM50V315-3 aM 3 /315 P Q095073 NH3AM50V315-4
400 28 aM 3 /400 D095154 NH3AM50V400-3 aM 3 /400 P W095354 NH3AM50V400-4
3 500
500 34 aM 3 /500 E095155 NH3AM50V500-3 aM 3 /500 P X095355 NH3AM50V500-4
630 41 aM 3 /630 F095156 NH3AM50V630-3 aM 3 /630 P Y095356 NH3AM50V630-4

Accessories: Neutral link BS2 Reference Number J097712 - BS3 Reference Number K097713
Pull-out handle - PMP Reference Number P215592

GPEU56
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 2 and 3

from 125 to 630 A


Total Clearing I2t Current Limitation Curves
I2t (A2S)
108 Ic (kA)

107 100

630
500

106 400
315
250
200

160
125
105
10

104

103
125 160 200 250 315 400 500 630
Rating (A)
2
b: total clearing I t @ 500 V 1 10 100
Ic = Peak let-through current Ip (kA)
a: pre-arcing I2t Ip = Available fault current

Time VS. Current Characteristics


t (s) t (s) = Pre-arcing duration
103 Breaking
capacity
100 kA

125 200 400 630


102
160 250 315 500

10

10-1

Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT

GPEU57
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 4

from 630 to 1250 A

• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR OR TRIP-INDICATOR


• COMPLYING WITH IEC 269.1 AND 2.1, NF EN 60269.1 & 2 NF C 63210 - 63211 AND DIN 43620
• DIMENSIONS:

D D1
D1
D G M
D2 B
G M
B
F e
e A C
H
A C
H K
N
N 150 J
150 J L
L

With trip-indicator With blown fuse indicator

Size A B C D D1 D2* F* G H J K L M N e Wgt.


4 107 61 119 78 90 77 14 2,5 60 27 14,5 200 10 23 8 1900g

* For fuses with trip-indicator

Voltage Current Watts With blown fuse indicator With trip-indicator


Size rating rating loss
(VAC) IN(A) (W) Designation Ref. Number Catalog Number Designation Ref. Number Catalog Number
630 41 aM 4 /630 X098322 NH4AM50V630-3 aM 4 /630 P M088515 NH4AM50V630-4
500 800 49 aM 4 /800 A098325 NH4AM50V800-3 aM 4 /800 P N088516 NH4AM50V800-4
4
1000 70 aM 4 /1000 B098326 NH4AM50V1000-3 aM 4 /1000 P P088517 NH4AM50V1000-4
400 1250 75 aM 4 /1250 C098327 NH4AM40V1250-3 aM 4 /1250 P Q088518 NH4AM40V1250-4

Accessories: Neutral link - BS4 Reference Number M097715


Pull-out handle - PMP Reference Number P215592

GPEU58
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 4

from 630 to 1250 A


Total Clearing I2t Current Limitation Curves
I2t (A2S)
108 Ic (kA)

107 100 1250


1000
800
630

106

105
10

104

103
630 800 1000 1250
Rating (A)
2
b: total clearing I t @ 500 V 1 10 100
Ic = Peak let-through current Ip (kA)

a: pre-arcing I2t Ip = Available fault current

Time VS. Current Characteristics


t (s) t (s) = Pre-arcing duration

103 Breaking
capacity
100 kA
800 1250
102 630 1000

10

10-1

Ip (A) = R.M.S.
AVAILABLE
10-2
10 100 1 000 10 000 Ip (A) FAULT CURRENT

GPEU59
General Purpose Fuses IEC
General Purpose Fuses IEC
Masterfuse
gG 690V

Highlights
• High ratings 1250 to 2500 A
• gG operating fuse for 690V AC Nominal
• Conformity with IEC 60269 1 and 2
• Dimensional according section V on IEC 60269-2-1
• Breaking capacity 690V 160 KA – 50Hz
Applications
• General protection on Low Voltage Panel
• High power protection on 690V AC Voltage
• Back up for circuit breaker
• Blade fuses for power bus bar assembly
• Disconnector, Switch and/or Circuit Breaker isolation

Main characteristics
Rated Size Melting I2t Total I2t at 690V Power losses Breaking Ref.Number Catalog
current (ø in mm) (KA2s) (KA2s) at In (W) capacity number
1250 A 76 1590 8200 78 E 302753 MF76GG69V1250
1600 A 89 2500 13000 111 160 KA F 302754 MF89GG69V1600
2000 A 114 4800 25000 128 at 690V AC G 302755 MF114GG69V2000
2500 A 127 7000 36000 175 H 302756 MF127GG69V2500
Pack: 1piece
For ratings 3200A(Ø 146mm) – 4000A (Ø 160mm) – 4800 A (Ø 181mm) consults us

Electrical characteristics
I2t vs rated current and applied voltage characteristics
Prearcing and Peak let-thru current characteristics
clearing I2t(kA2s)
Maximum peak let-thru current Im (A)

2500 A

500000

Im=2.3Ip
2000 A
10000

5000
1600 A

1000
1250 A
2500
1250

2000
1600

Total I2T Rated current (A)


at 690V
50Hz RMS Symetrical prospective current Ip (A)
Melting
I2T

GPEU60
General Purpose Fuses IEC
General Purpose Fuses IEC
Masterfuse
gG 690V

Time current characteristics


Prearcing time (s)
10000
7000 1250 A
5000
3000
2000

1000
700
500
1600 A
300
200

100
70
50
30
2000 A
20

10
7
5
3
2
2500 A
1
0.7
0.5
0.3
0.2

0.1
0.07
0.05
0.03
0.02

0.01
0.007
0.005
0.003
0.002

0.001
0.0007
0.0005
0.0003
0.0002
100000

200000

300000

500000

700000
10000

20000

30000

50000

70000

1e+ 06
2000

3000

5000

7000

RMS value of prearcing current Ip (A)

GPEU61
General Purpose Fuses IEC
General Purpose Fuses IEC
Masterfuse
gG 690V

Dimensions
690 VgG 1250 A

690 VgG 1600 A

690 VgG 2000 A

690 VgG 2500 A

GPEU62
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System

2–100 A, 400 (440) VAC, 250 VDC

Line protection fuses - gG


Motor protection fuses - aM

IEC 269-3-1
DIN VDE 0636 Part 41
DIN VDE 0636 Part 301

Germany

Austria

D Denmark

Norway
N

Dimensions are stipulated in the following regulations:


DIN 49522 D0 Fuse-links
DIN 49523 D0 Gauge rings
DIN 49524 D0 Fuse bases

Structure of NEOZED fuse system


The NEOZED system, similar to the D-system, consists of a fuse base, gauge-ring, fuse link and screw
cap. It is dimensioned for nominal voltages of 440VAC 400 VAC and 250 VDC. The system guarantees
that from 6 A onwards rated current will not be confused from current stage to current stage. This is
ensured by staging the diameter of the fuse link’s base current in connection with gauge diameters
determined accordingly.

GPEU64
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System

NEOZED Fuse-links 2–100 A gG


400 VAC, 250 VDC

Rated in Gauge Previous Reference Catalog


Size Current (A) Color Reference Number Pack Number
D01 2 pink 01700.002000 T214676 50
4 brown 01700.004000 W200809 50
6 green 01700.006000 B215695 50
10 red 01700.010000 W211090 50
13 black 01700.013000* C201206* 50
16 grey 01700.016000 R223023 50
D02 20 blue 01701.020000 B217742 50
25 yellow 01701.025000 W213160 50
35 black 01701.035000 R219826 50
50 white 01701.050000 D215191 50
63 copper 01701.063000 C201873 50
D03 80 silver 01702.080000 L216716 10
100 red 01702.100000 N212647 10
*No VDE, ÖVE testing mark

Back-up fuse in operating class gG


Rated in
Current (A) 20 A 25 A 35 A 50 A 63 A 80 A
20 A aM 600 300 200 <100 <100 <100
25 A aM - 1500 700 100 <100 <100
35 A aM - - 1000 300 200 <100

NEOZED Fuse-links 20–35 A aM


400 VAC / 440 VAC

Rated in Gauge Previous Reference Catalog


Size Current (A) Color Reference Number Pack Number
D02 20 blue 01701.020500* H211607* 10
25 yellow 01701.025500* F212640* 10
35 black 01701.035500* J213655* 10
*No VDE, ÖVE testing mark
Dimensions see following pages

GPEU65
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
INNOZED Neozed-Sicherungssockel
für Schnappbefestigung mit Abdeckung, 400VAC

Bemessungs- Referenz Gewich Artikel


Größe strom in A Polzahl Nummer in g/Stück VE -Gruppe
D01 16 1 2724. 75 12 42
D01 16 3 2734. 223 4 42
D02 63 1 2725. 77 12 42
D02 63 3 2735. 229 4 42

INNOZED Neozed-Sicherungssockel
für Schnappbefestigung ohne Abdeckung, 400VAC
Bemessungs- Referenz Gewich Artikel
Größe strom in A Polzahl Nummer in g/Stück VE -Gruppe
D01 16 1 2724.1 70 12 42
D01 16 3 2734.1 210 4 42
D02 63 1 2725.1 72 12 42
D02 63 3 2735.1 217 4 42

Abdeckung für INNOZED


Bemessungs- Referenz Gewich Artikel
Größe strom in A Polzahl Nummer in g/Stück VE -Gruppe
D01/ D02 1 2718. 5 24 42
D01/ D02 3 2732. 12 12 42

GPEU66
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
NEOZED Screw cap - plastic
400 VAC / 440 VAC

Rated in Cap Previous Reference Catalog


Size Current (A) Thread Reference Number Pack Number
with testing hole
D01 16 E 14 01714.000200 E212501 20
D02 63 E 18 01715.000200 P211981 20
for D01 fuse links with adapter spring
D02 E 18 01715.890200 M214026 20
with sealable hole and testing hole
D01 16 E 14 11714.000220 R214536 20
D02 63 E 18 11715.000220 S214537 20
without testing hole
D02 63 E 18 01715.000000 L206435 20

NEOZED Screw cap - porcelain


400 VAC / 440 VAC

Rated in Cap Previous Reference Catalog


Size Current (A) Thread Reference Number Pack Number
with testing hole
D01 16 E 14 01710.000200 H201211 20
D02 63 E 18 01711.000200 T215044 20
without testing hole
D03 100 M30 x 2 01712.000200 V215045 20
Dimensions see following pages

NEOZED Gauge rings

Rated in Cap Previous Reference Catalog


Size Current (A) Thread Reference Number Pack Number
D01 2 pink 01705.002000 J216576 50
4 brown 01705.004000 J219681 50
6 green 01705.006000 P206438 50
10 red 01705.010000 M213014 50
D02 2 pink 01706.002000* K216577* 50
4 brown 01706.004000* S222127* 50
6 green 01706.006000* R211983* 50
10 red 01706.010000* H216069* 50
16 grey 01706.016000* Q218629* 50
20 blue 01706.020000 S200668 50
25 yellow 01706.025000 R213524 50
35 black 01706.035000 J216070 50
50 white 01706.050000 R218630 50
D03 80 silver 01707.080000 T200669 25
*For use of D01 fuse-links in D02 fuse-bases
Dimensions see following pages

GPEU67
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
NEOZED Insulating covers
single pole for ceramic fuse bases:

Previous Reference Catalog


Reference Number Pack Number
for type D01/D02
with 1-side marking area 01718.008000 M222881 50
with marking area 01718.700000 V200670 50
for type D03
without marking area 01728.000000 V211986 20
for type D01/D02
cover - cap 01721.030000 X201730 20
for type D01/D02
3 pole: with marking area 01732.700000 M216579 20
Dimensions see following pages

NEOZED Fuse bases


for screw mounting without shock-proof protection-cover, 400 VAC

Rated in Max. cross Previous Reference Catalog


Size Current (A) Pole sect. mm2 Reference Number Pack Number
D01 16 1 (1*) 4 01720.100000 Z216061 20
D02 63 1 (2*) 25 01721.200000 M214532 20
D02 63 1 (4*) 25 01721.400000 F213008 20
D03 100 1 (4*) 50 01722.400000 J213011 10
D01 16 3 (1*) 4 01730.100000 K200661 5
D02 63 3 (2*) 25 01731.200000 F216573 5
D02 63 3 (4*) 25 01731.400000 K206365 5
NEOZED Fuse bases
for snap-on fastening without shock-proof protection-cover, 400 VAC
D01 16 1 (1*) 4 01720.150000 J200660 20
D02 63 1 (2*) 25 01721.250000 J218623 20
D02 63 1 (4*) 25 01721.450000 W215552 20
D03 100 1 (4*) 50 01722.450000 Q214535 10
D01 16 3 (1*) 4 01730.152000 B216063 5
D02 63 3 (2*) 25 01731.252000 Y217601 5
D02 63 3 (4*) 25 01731.452000 M211979 5
*Terminal type and dimensions see following pages

NEOZED Fuse bases


For snap-on fastening with shock-proof protection-cover

Rated in Max. cross Previous Reference Catalog


Size Current (A) Pole sect. mm2 Reference Number Pack Number
D01 16 1 (1*) 4 01720.170000 B211463 20
D01 16 1 (3*) 4 01720.370000 T215550 20
D01 16 3 (1*) 4 01730.172000 A219144 5
D02 63 1 (2*) 25 01721.270000 M200663 20
D02 63 1 (4*) 25 01721.470000 K218624 20
D02 63 3 (2*) 25 01731.272000 E222874 5
D02 63 3 (4*) 25 01731.472000 K213518 5
D03 100 1 (4*) 50 01722.470000 F216067 10
Dimensions see following pages

GPEU68
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
LINOZED Fuse bases
For snap-on fastening, 400VAC

Rated in Max. cross Previous Reference Catalog


Size Current (A) Pole sect. mm2 Reference Number Pack Number
D01 16 1 35 01724.000000 M217085 6
D02 63 1 35 01725.000000 R215042 6
D01 16 3 35 01734.000000 E201208 2
D02 63 3 35 01735.000000 Y215554 2
Dual function terminals
Dimensions see following pages

NEOZED Universal fuse bases


for screw mounting, 400 VAC
Rated in Max. cross Previous Reference Catalog
Size Current (A) Pole sect. mm2 Reference Number Pack Number
D01 16 1 (1*) 4 01720.130000 B222871 20
D02 63 1 (2*) 25 01721.230000 D216571 20
63 1 (4*) 25 01721.430000 Q215041 20
D03 100 1 (4*) 50 01722.430000 K214024 10
D01 16 1 (1*) 4 01720.180000 G213515 20
D02 63 1 (2*) 25 01721.280000 L211978 20
D02 63 1 (4*) 25 01721.480000 G213009 20
D03 100 1 (4*) 50 01722.480000 H219680 10
* Terminal type and dimensions see following pages

NEOZED 3-pole fuse bases


without shock-proof protection, 400 VAC
Rated in Max. cross Previous Reference Catalog
Size Current (A) Pole sect. mm2 Reference Number Pack Number
Screw fixing
D01 16 3 (1*) 4 01737.100000 A212497 5
D02 63 3 (2*) 25 01738.200000 Z217602 5
Snap-on fastening
D01 16 3 (1*) 4 01737.150000 E213007 5
D02 63 3 (2*) 25 01738.250000 B218110 5
* Terminal type and dimensions see following pages

NEOZED 3-pole fuse bases


without shock-proof protection, 400 VAC Clamp fixing

Rated in Max. cross Previous Reference Catalog


Size Current (A) Pole sect. mm2 Reference Number Pack Number
Clamp fixing for busbar 12 x 4…5mm, 15 x4…5 mm
D02 63 1 (2*) 25 01746.200801 P222124 20
Clamp fixing for busbar 12 x 4 …10 mm, 15 x 4 …10 mm
D02 63 1 (2*) 25 01741.200001 L218625 20
Snap-on fastening for busbar 15 x 5 mm
D02 63 1 (2*) 25 01741.250000 G219679 20
* Terminal type and dimensions see following pages
Snap-on
fastening

GPEU69
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System

NEOZED Fuse-links 2–63 A gG


440 VAC, 250 VDC
Rated in Code Previous Reference Catalog
Size Current (A) Color Reference Number Pack Number
D01 2 rosa 01700.002400 E218780 50
4 braun 01700.004400 V219829 50
6 grün 01700.006400 X223028 50
10 rot 01700.010400 S201358 50
16 grau 01700.016400 C211096 50
D02 20 blau 01701.020400 X212126 50
25 gelb 01701.025400 S213663 50
35 schwarz 01701.035400 C214684 50
50 weiß 01701.050400 J215702 50
63 Kupfer 01701.063400 N216718 50
Dimensions see following pages

NEOZED Fuse bases


for snap-on fastening without shock-proof protection cover,440 VAC

Rated in Max. cross Previous Reference Catalog


Size Current (A) Pole sect. mm2 Reference Number Pack Number
D01 16 1 (1*) 4 01720.150040 D201207 20
D02 63 1 (2*) 25 01721.250040 M222122 20
D02 63 1 (4*) 25 01721.450040 C216064 20
D01 16 3 (1*) 4 01730.152040 C216570 5
D02 63 3 (2*) 25 01731.252040 A218109 5
D02 63 3 (4*) 25 01731.452040 C212499 5
* Terminal type see following pages

LINOZED Fuse bases, Dual function clamps


for snap-on fastening,440 VAC

Rated in Max. cross Previous Reference Catalog


Size Current (A) Pole sect. mm2 Reference Number Pack Number
D01 16 1 35 01724.000040 X217600 6
D02 63 1 35 01725.000040 X215553 6
Dimensions see following pages

LINOZED Fuse bases, Dual function terminal


for snap-on fastening,440 VAC

Rated in Max. cross Previous Reference Catalog


Size Current (A) Pole sect. mm2 Reference Number Pack Number
D01 16 3 35 01734.000040 P201723 2
D02 63 3 35 01735.000040 E216066 2
Dimensions see following pages

GPEU70
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System

NEOZED - Special holding spring

Previous Reference Catalog


Size Reference Number Pack Number
D01 Fuse-links in D02-socket 01713.000000 Z215049 50
D02 Fuse-links in D03-socket 01709.000000 P214028 10
D01 Fuse-links in DL-socket 01733.000000 J218117 100

NEOZED - Spacer

Previous Reference Catalog


Size Reference Number Pack Number
D02 Fuse-links in D03-socket 01707.000000 T211985 10

NEOZED - Gauge ring key

Previous Reference Catalog


Size Reference Number Pack Number
gauge-rings D01, D02, D03 01708.000000 J212505 10

NEOZED - Screw-cap remover

Previous Reference Catalog


Size Reference Number Pack Number
plastic screw-caps D01, D02 01716.000000 X222936 1
01716.333000 F200726 1

NEOZED - Locking caps

Previous Reference Catalog


Size Reference Number Pack Number
D01 supply boards (1) 01714.800000* D212546* 25
D01 Industry (2) 01714.810000 P213062 25
D02 supply boards (1) 01715.800000* R214582* 25
D02 Industry (2) 01715.810000 Y215094 25
* only for authorized energy supplier personnel
1) black top, red screw pitch
2) red top, black screw pitch

NEOZED - Locking keys

Previous Reference Catalog


Size Reference Number Pack Number
D02 Supply boards 01714.820000* K213564 10
D02 Industry 01714.830000 J214069 10
* for authorized energy supplier personnel only

GPEU71
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
INNOZED
Der Neozed-Sicherungssockel mit innovativer Anschlusstechnik

Kunststoffe
mit höchsten Ansprüchen
• Sockelabdeckung aus flammwidrigem Polyamid
• Gehäuse aus glasfasergefülltem, duroplastis-
chem Polyester
• Hohe mechanische und thermische
Belastbarkeit

Innovative Anschlusstechnik
durch zweigeteilte Rahmenklemme.
• Kontaktierung der Einspeiseleitungen
• Anschluss der Verdrahtungsschienen
• Leitungen leichter einführbar Klemmstellen
der Leitungen visuell kontrollierbar
• Einsparung von Montagezeit
• Zusätzliche Betriebssicherheit und Flexibilität

Verdrahtungsschienen
Folgende Schienen sind einsetzbar:
- 3-phasig 16 mm2 – Ref.Nr. 2963.003
- 1-phasig 16 mm2 – Ref.Nr. 2963.

Flexible Klemmentechnik
Unterschiedliche Leiterquerschnitte und Leiterarten sind problemlos klemmbar, sowohl eingangs- als
auch abgangsseitig
• Flexibilität bei der Verdrahtung
• Erhöhung der Betriebssicherheit bei der Klemmung unterschiedlicher Leiter

35mm2 und 4mm2 2 x 16mm2 Zwillingsaderendhülse 35mm2 und 4mm2


abgangseitig auf der auf der auf der
Einspeiseseite Einspeiseseite Einspeiseseite

GPEU72
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
Variabler Berührungsschutz

MIT SOCKELABDECKUNG FÜR VERTEILERBAU OHNE SOCKELABDECKUNG FELDABDECKUNG AUS


IM INDUSTRIELLEN KUNSTSTOFF
Berührungsschutz durch einfaches Aufrasten der
ANLAGENBAU
Sockelabdeckung. individuell zugeschnitten
Berührungsschutz nach BGVA
• einfach und kostengünstig
2 auch ohne ockelabdec-
kung bis 25mm2
Anschlussquerschnitt
• Einsparung der
Montagezeit und der Kosten
der Sockelabdeckung

Geteilte Anschlussklemme zur Klemmung zweier Leitungen

Einspeisung Abgang

1. flexible Leitungen mit Aderendhülse


zwei Leitungen gleichen Querschnitts: bis max. 10mm2 bis max. 16mm2
zwei unterschiedliche Leitungen: 16mm2 u. max. 10mm2
25mm2 u. max. 6mm2 25mm2 u. max. 6mm2
35mm2 u. max. 4mm2 35mm2 u. max. 4mm2
mit Zwillingsaderendhülse: bis max. 16mm2 bis max. 16mm2
2. flexible, feindrähtige Leitungen ohne Aderendhülse
zwei Leitungen gleichen Querschnitts: bis max. 10mm2 bis max. 16mm2
zwei unterschiedliche Leitungen: 16mm2 u. max. 10mm2
25mm2 u. max. 10mm2 25mm2 u. max. 16mm2
35mm2 u. max. 10mm2 5mm2 u. max. 10mm2
3. kurzschlussfeste Leitungen:
zwei Leitungen gleichen Querschnitts: bis max. 6mm2 bis max. 6mm2
Maximaler Anschlussquerschnitt der Zu- und Abgangsklemme: 35mm2

V O R T E I L E des INNOZED
• Schnellere Montage
• Höhere Betriebssicherheit
• Klemmstelle sichtbar vor Verdrahtungsschiene

GPEU73
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
Vorschriften
IEC 60269-3-1
DIN VDE 0636 Teil 301

Prüfzeichen Germany D Denmark N Norway

Baugrößen
Drei Baugrößen stehen zur Verfügung:
• Sicherungssockel D01
- Gewinde E 14
- Nennstrom 16A
- für Sicherungseinsätze 2 ... 16A
• Sicherungssockel D02
- Gewinde E 18
- Nennstrom 63A
- für Sicherungseinsätze 20 ... 63A
- mit Spezialpasshülsen auch verwendbar für Sicherungseinsätze 2 ... 16A
• Sicherungssockel D03
- Gewinde M 30 x 2
- Nennstrom 100A
- für Sicherungseinsätze 80 und 100A
Betriebsklassen
Die Betriebsklasse ist durch zwei Buchstaben gekennzeichnet.
Der erste Buchstabe gibt die Funktionsklasse, der zweite das zu
schützende Objekt an. Unser Lieferprogramm umfasst NEOZEDSicherungseinsätze
nach DIN VDE 0636 für folgende Betriebsklassen:
• gG: Ganzbereichskabel- und Leitungsschutz
• gR: Ganzbereichs-Halbleiterschutz
• aM: Teilbereichs-Schaltgeräteschutz (Motorschutz)
Schaltvermögen
NEOZED-Sicherungseinsätze schalten im gesamten Bereich der
Zeit-Stromkennlinie auch im Bereich der kritischen Ströme zuverlässig
ab.
Das Schaltvermögen ist 50kA.
Klemmrausführunger der keramiksockel

Fig.1 Fig.2 Fig.3 Fig.4

GPEU74
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
Ausschreibungstexte

Neozed-Sicherungssockel INNOZED Neozed-Sicherungseinsatz


400VAC / 250VDC, 400VAC / 400VAC
D01 (D02), 16A (63A), D02, 20A (25A,35A)
Berührungsschutz nach BGVA 2 (auch ohne Betriebsklasse aM für Schaltgeräteschutz in
Abdeckung) Motorenstromkreisen
Abdeckung abnehmbar bei eingeschraubter
Sicherung Neozed-Sicherungseinsatz
Material Kunststoff zweigeteilte Rahmenklemmen 440VAC
D01 (D02, D03)
Neozed-Sicherungssockel LINOZED 2 ... 16A (20 ... 63A, 80 ... 100A)
400VAC / 250VDC Betriebsklasse gR für Halbleiterschutz
D01 (D02), 16A (63A)
Berührungsschutz nach BGVA 2 Neozed-Schraubkappen
Material Kunststoff 400VAC / 250VDC
Doppelfunktionsklemmen gefederter Fußkontakt D01 (D02, D03)
16A (63A, 100A)
Neozed-Sicherungssockel Material Kunststoff (Keramik),
400VAC / 250VDC mit Prüfloch (und Plombierloch)
D01 (D02, D03)
16A (63A, 100A) Neozed-Hülsenpasseinsatz
Material Keramik D01 (D02, D03)
Anschlussart Klemmbügel (Schelle – Schelle, 2 ... 10A (20 ... 50A, 80A)
Schraube – Schelle) Neozed-Spezialhülsenpasseinsatz für D01-
Sicherungseinsätze in D02-Sicherungssockeln
Neozed-Sicherungseinsatz D02, 2 ... 16A
400VAC / 250VDC
D01 (D02, D03)
2 ... 16A (20 ... 63A, 80 ... 100A)
Betriebsklasse gG

GPEU75
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
2 – 100A, 400 (440)VAC,250VDC Leitungsschutzsicherungen gG
Eigenverbrauch in W
Nennstrom in A Größtwerte * Messwerte

2 2,5/2,5 1,5
4 1,8 1,5
6 1,8 1,3
10 2,0 1,8
16 2,5/2,2 2,1
20 3,0/2,5 2,3
25 3,5/3,0 2,6
35 4,0 2,9
50 5,0 3,5
63 5,5 4,2
80 6,5 4,9
100 7,0 5,8

Selektivität
NEOZED-Sicherungseinsätze sind im Verhältnis 1:1,6 der Nennströme
mit allen Sicherungseinsätzen selektiv, die folgenden
Anforderungen entsprechen:
Betriebsklasse gG entspr. lEC 60269-2-1, 60269-3-1
Betriebsklasse gG entspr. DIN VDE 0636 Teil 201, 301
NEOZED-Sicherungseinsätze sind untereinander und bei gemischtem
Einsatz mit Sicherungseinsätzen anderer Lindner-Systeme im
Verhältnis 1:1,25 selektiv, d.h. von Nennstromstufe zu Nennstromstufe.
Beide Sicherungen sollten jedoch bei so enger Staffelung
gleichen Umgebungseinflüssen ausgesetzt sein.

NEOZED-Sicherungseinsätze 32A
Zur Absicherung von 32A CEE Steckdosen sind entsprechend der
neuen DIN VDE 0623 Teil 1/06.93 (DIN EN 60309-1) Sicherungseinsätze
mit maximal 32A Bemessungsstrom vorgeschrieben.
Bisher durften 32A CEE Steckdosen ausnahmsweise mit 35A abgesichert
werden.
Diese Ausnahmeregelung darf zukünftig für Neuanlagen nicht
mehr angewendet werden, da die entsprechende Vorschrift DIN
VDE 0623/03.77 nicht mehr gültig ist. Es gilt jedoch eine Übergangsfrist
bis 2003-02-01.
Passorgane: Es sind die Hülsenpasseinsätze 35A zu verwenden.

GPEU76
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
Direkte Zuordnung bei Schutz von Kabel und Leitungen bei Überlast
Bei der Zuordnung von Überstrom-Schutzorganen zum Kabel- und Leitungsschutz sind nach DIN VDE
0100 Teil 430 folgende Bedingungen zu erfüllen:
lB ≤ IN ≤ lZ (Nennstromregel) (1)
I2 ≤ 1,45 x lN (Auslöseregel) (2)
IB - Betriebsstrom des Stromkreises
IN - Nennstrom der ausgewählten Überstromeinrichtung
IZ - zulässige Strombelastbarkeit des Kabels
I2 - Auslösestrom der Schutzeinrichtung

DIN VDE 0636 Teil 301 wurde durch eine Zusatzprüfung "Abschalten mit l2 = 1,45 x IN in der konven-
tionellen Prüfdauer" ergänzt.
NEOZED-Sicherungseinsätze gG erfüllen die Bedingungen dieser Zusatzprüfung. Damit ist eine direkte
Zuordnung des Nennstromes des Sicherungseinsatzes zur Belastbarkeit der Leitung oder des Kabels
möglich.

GPEU77
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
Vorschriften
IEC 60269-3-1
DIN VDE 0636 Teil 301
20/25/35A 400 (440)VAC, 250VDC
Schaltgeräteschutz-Sicherungen aM

Anwendung
NEOZED-Sicherungseinsätze der Betriebsklasse aM gewähren
Motoren und Schaltgeräten den besten Schutz im Fall eines Kurzschlusses.
Im Vergleich zu alternativen Schutzorganen haben Sicherungseinsätze der Betriebsklasse aM entschei-
dende Vorteile:
Besonders träges Abschaltverhalten im Überlastbereich verhindert
unerwünschtes, vorzeitiges Auslösen des Schutzorganes; sehr flinkes Abschalten im Kurzschlussfall
sorgt für höchste Kurzschlussstrombegrenzung und verhindert damit das Abbrennen und
Verschweißen der Kontakte des Schaltgerätes.
Eine um bis zu 50% geringere Verlustleistung bietet entscheidende Vorteile bei häufigem Lastwechsel
und Reversierbetrieb und spart außerdem noch Energiekosten.

Nennströme und Zeit-Strombereiche


NEOZED-Sicherungseinsätze aM gibt es nur in der Baugröße D02
20A 25A 35A
Zeit-Strombereiche nach IEC 60269

Selektivität Eigenverbrauch und Erwärmung


SeIektivität erreicht man, wenn die vorgeschaltete Die Verlustleistung der NEOZED-
Sicherung der Betriebsklasse gG mindestens drei Sicherungseinsätze aM sind technisch bedingt
Nennstromstufen größer als die geringer als bei den vergleichbaren der
Motorschutzsicherung aM ist. Dies verhindert Betriebsklasse gG. Auch bei diesen
unerwünschtes Abschmelzen der Vorsicherung Sicherungseinsätzen unterschreitet die LINDNER-
bei kleinen Kurzschlussströmen. Konstruktion die Größenwerte entsprechender
• Beispiel: Nennstrom der Motorschutzsicherung Norm erheblich.
25A aM
Nennstrom der Vorsicherung 35A gG Eigenverbrauch in W
Kurzschlussstrom im Motorstromkreis
500A Nennstrom in A Größtwerte * Messwerte
Selektivitätsgrenze It. Tabelle 700A 20A 3,0/2,5 1,10
• Ergebnis: keine Selektivität 25A 3,5/3,0 1,05
35A 4 1,95
Selektivitätsgrenzen in A *) nach IEC 269-3-1, DIN VDE 0636 Teil 301/DIN VDE 0636 Teil 41

Nennstrom 20A 25A 35A 50A 63A 80A


20A aM 600 300 200 <100 <100 <100
25A aM – 1500 700 100 <100 <100
35A aM – – 1000 300 200 <100
Vorsicherung der Betriebsklasse gG

GPEU78
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
Aufbau
Die NEOZED Sicherunsein stätze der Betnebklasse aM bestehen
aus den gleichen Bauteilen wie die Standard-Typen der Betriebsklasse gG:
Keramikhülse, Kontaktkappen, Kennmelder mit Kennmelderdraht,
Löschsand. Nur der Schmelzleiter, der die Kennlinie und das Abschmelzverhalten einer Sicherung aus-
macht, ist ein anderer. Zur Unterscheidung zu anderen Betriebsklassen sind die aM-Sicherungseinsätze
in grüner Farbe beschriftet.
ZEIT-STROM-KENNLINIEN

DURCHLASSSTROM-KENNLINIEN

GPEU79
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
INNOZED-Sicherungssockel

NEOZED-Sicherungssockel

Referenz. Catalog a b c c1 d d1 eØ f g h k
Nummer Number
1720.1 26 36 – 39,5 20 22 25,5 64 34Ø – 50,5
1721.2/.4 26 36 – 39,5 20 22 25,5 64 34Ø – 57,5
1722.4 44 50 – 44 32 32 40 74 52Ø – 86
1730.1 81 36 – 39,5 74 22 25,5 64 – – 50,5
1731.2/.4 81 36 – 39,5 74 22 25,5 64 – – 57,5
1730.12 81 36 55 39,5 74 22 25,5 64 45 71 50,5
1731.22/.42 81 36 55 39,5 74 22 25,5 64 45 71 57,5
1720.15 26 36 – 41,5 20 22 25,5 66 34Ø – 50,5
1721.25/.45 26 36 – 41,5 20 22 25,5 66 34Ø – 57,5
1722.45 44 50 – 46 32 32 40 76 52Ø – 86
1720.17 27 36 57 41,5 20 22 25,5 66 45 71 50,5
1721.27/.47 27 36 57 41,5 20 22 25,5 66 45 71 57,5
1722.47 44 50 54,5 46 32 32 40 76 45 71 86
1730.15 81 36 – 41,5 74 22 25,5 66 – – 50,5
1731.25/.45 81 36 – 41,5 74 22 25,5 66 – – 57,5
1730.17 81 36 57 41,5 74 22 25,5 66 45 71 50,5
1731.27/.47 81 36 57 41,5 74 22 25,5 66 45 71 57,5

Referenz. Catalog a b c d d1 eØ f
Nummer Number
1720.13 31 70 44,5 20 22 25,5 64
1721.23/1721.43 31 70 44,5 20 22 25,5 64
1722.43 50 105 48 32 32 40 74
1720.18 31 70 46,5 20 22 25,5 66
1721.28/1721.48 31 70 46,5 20 22 25,5 66
1722.48 50 105 50 32 32 40 76

GPEU80
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
NEOZED NEOZED
Schraubkappen Hülsenpasseinsätze

Referenz. Catalog a b
Nummer Number
1714. 29,5 23 Referenz. Catalog a b
1715. 29,5 23 Nummer Number
1710. 31 25 1705. 10 12
1711. 31 25 1706. 10 16
1712. 37 40 1707. 10 27

NEOZED NEOZED
Abdeckungen Sicherungseinsätze

Referenz. Catalog a b c Referenz. Catalog a b


Nummer Number Nummer Number
1718.008 60 26,8 23 D01 36 11
1728.7 71 26,8 23 D02 36 15
1728. 60 44 18 D03 43 22
1732.7 71 81 23

LINOZED-Sicherungssockel

GPEU81
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED

D0 Fuse System
NEOZED-Reiter-Sicherungssockel
mit Schellenbefestigung, 400VAC

NEOZED-Reiter-Sicherungssockel
mit Schnappbefestigung, 400VAC

NEOZED-Reihen-Sicherungssockel

Referenz. Catalog a b c c1 d d1 eØ f g h i k
Nummer Number
1737.12 80,5 30 55 39,5 22 20 25,5 64 45 71 88,5 36,5
1738.22 80,5 30 55 39,5 22 20 25,5 64 45 71 91,5 44,5
1737.17 80,5 30 57 41,5 22 20 25,5 66 45 71 88,5 36,5
1737.27 80,5 30 57 41,5 22 20 25,5 66 45 71 91,5 44,5

GPEU82
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED

D Fuse System

2 – 200 A, 500 V, 690 V


Line protection fuses gL-gG
IEC 60269 parts1, 3 and 3-1
DIN VDE 0636 Parts 10, 30 and 31

Dimensions are stipulated in the following regulations:


DIN 49360 D Fuse-links
DIN 49515 D Fuse-links
DIN 49367 D Fuse-links, long design
DIN 49514 D Screw caps
DIN 49510 D Fuse bases
DIN 49362 D Gauge rings
DIN 49516 D Screw gauge pieces

Structure of the D fuse system


Like the modern NEOZED system, the D-Fuse system consists of fuse base, gauge piece, fuse link and
screw cap. It is designed for a rated voltage of 500V. Noninterchangeability of rated current is guaran-
teed from one current level to the other above 6 Amps. This is ensured by graduating the diameter of
the bottom contact of the fuse-link along with corresponding fixed diameters for the gauge piece.

GPEU84
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED

D Fuse System
D Fuse bases
for snap-on fastening 500 VAC / 690 VAC
Rated in Max. cross Previous Reference Catalog
Size Current (A) Pole sect. mm2 Reference Number Pack Number
without shock-proof protection cover
DII 25 1* 6 00685.100000 K207055 15
DIII 63 4* 16 00686.400000 V215597 15
with shock-proof protection cover
DII 25 1 6 00685.110000 D211511 10
DIII 63 4 16 00686.410000 C216110 10
* Terminal type see following pages

D Fuse bases
for screw fixing 500 VAC / 690 VAC
Rated in Max. cross Previous Reference Catalog
Size Current (A) Pole sect. mm2 Reference Number Pack Number
without shock-proof protection cover
DII 25 1* 6 00081.100000 K218670 15
DIII 63 4* 16 00072.400000 H212021 15
with shock-proof protection cover
DII 25 1* 6 00081.110000 Z219189 10
DIII 63 4* 16 00072.410000 A212543 10
* Terminal type see following pages

D Fuse-links
2 - 200A fast acting (CEE-16 standard), 500 VAC

Rated in Gauge Previous Reference Catalog


Size Current (A) Color Reference Number Pack Number
NDZ 2 pink 00594.002000 C222918 25
NDZ 4 brown 00594.004000 L200708 25
NDZ 6 green 00594.006000 A201250 25
NDZ 10 red 00594.010000 L201766 25
NDZ 16 gray 00594.016000 D207049 25
NDZ 20 blue 00594.020000 B211509 25
NDZ 25 yellow 00594.025000 Y212541 25
DII 2 pink 00597.002000 E213559 25
DII 4 brown 00597.004000 D214064 25
DII 6 green 00597.006000 L214577 25
DII 10/6 (1) red 00597.610000 X218152 25
DII 10 red 00597.010000 S215089 25
DII 16 gray 00597.016000 A216108 25
DII 20 blue 00597.020000 J217128 25
DII 25 yellow 00597.025000 P217639 25
DIII 35 Black 00598.035000 J218669 25
DIII 50 white 00598.050000 J222165 25
DIII 63 copper 00598.063000 M200709 25
(1) with base contact stud for 6 A

GPEU85
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED

D Fuse System
D Fuse-links
2 -200 A gG, 500 VAC
Rated in Gauge Previous Reference Catalog
Size Current (A) Color Reference Number Pack Number
NDZ 2 pink 00594.002700 W212539 25
NDZ 4 brown 00594.004700 G213055 25
NDZ 6 green 00594.006700 C213557 25
NDZ 10 red 00594.010700 B214062 25
NDZ 16 grey 00594.016700 J214575 25
NDZ 20 blue 00594.020700 Q215087 25
NDZ 25 yellow 00594.025700 Q215593 25
D II 2 pink 00597.002700 Z219718 25
D II 4 brown 00597.004700 G222163 25
D II 6 green 00597.006700 B222917 25
D II 10/6 f1 red 00597.610700 D213558 25
D II 10 red 00597.010700 K200707 25
D II 16 grey 00597.016700 K201765 25
D II 20 blue 00597.020700 A211508 25
D II 25 yellow 00597.025700 X212540 25
1 with base contact stud for 6 A (without VDE test mark)
D III 35 black 00598.035700 C214063 25
D III 50 white 00598.050700 K214576 25
D III 63 copper 00598.063700 R215088 25
D IV 80 silver 00595.080700 V216609 10
D IV 100 red 00595.100700 M217637 10
DV 125 yellow 00596.125700 V218150 10
DV 160 copper 00596.160700 G218667 10
DV 200 blue 00596.200700 W219186 10
Characteristics see following pages
D Fuse system 690 VAC
In this design, the fuse base and gauge piece correspond to the 500 V standard for D III (E33). The
extended fuse links D III and a special extended screw cap serve to complement the present system.
D-type 690 V fuses are only available in size III.

D Fuse-links Rated in Gauge Previous Reference Catalog


2 - 63 A gG 690 VAC Size Current (A) Color Reference Number Pack Number
D III 2 pink 00603.002700 R215594 25
D III 4 brown 00603.004700 Z216107 25
D III 6 green 00603.006700 W216610 25
D III 10 red 00603.010700 H217127 25
D III 16 grey 00603.016700 N217638 25
D III 20 blue 00603.020700 W218151 25
D III 25 yellow 00603.025700 H218668 25
D III 35 black 00603.035700 X219187 25
D III 50 white 00603.050700 A219719 25
D III 63 copper 00603.063700 H222164 25

D Screw-cap long design 690 VAC

D III 63 00605.000000 L218671 25


Dimensions see following pages

GPEU86
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED

D Fuse System
D Screw caps
Porcelain and Plastic, 500 VAC
Rated in Gauge Previous Reference Catalog
Size Current (A) Color Reference Number Pack Number
Porcelain with testing hole
DII 25 E 27 00690.000200 E218619 20
DIII 63 E 33 00691.000200 B213004 20
Porcelain without testing hole
NDZ 25 E 16 00589.000000 Z216613 50
DII 25 E 27 00690.000000 Z218108 20
DIII 63 E 33 00691.000000 F211973 20
DIV 100 R11/4 00592.000000 Y216060 10
Plastic with testing hole
DII 25 E 27 02071.000000 L201720 20
DII 63 E 33 02072.000000 E214019 20

D Gauge piece
Rated in Gauge Previous Reference Catalog
Size Current (A) Color Reference Number Pack Number
NDZ 2 pink 01655.002000 B212544 50
NDZ 4 brown 01655.004000 M213060 50
NDZ 6 green 01655.006000 H213562 50
NDZ 10 red 01655.010000 G214067 50
NDZ 16 grey 01655.016000 P214580 50

D Screw gauge pieces for DII / DIII


D II 2 pink 01657.002000 A219190 25
D II 4 brown 01657.004000 D219722 25
D II 6 green 01657.006000 L222167 25
D II 10 red 01657.010000 F222921 25
D II 16 grey 01657.016000 P200711 25
D II 20 blue 01657.020000 D201253 25
D II 25 yellow 01657.025000 P201769 25
D III 35 black 01658.035000 C207071 25
D III 50 white 01658.050000 E211512 25
D III 63 copper 01658.063000 J212022 25

D Gauge rings for DII / DIII, TRI60 System


D II 2 pink 01652.002000 W215092 50
D II 4 brown 01652.004000 W215598 50
D II 6 green 01652.006000 D216111 50
D II 10 red 01652.010000 A216614 50
D II 16 grey 01652.016000 M217131 50
D II 20 blue 01652.020000 S217642 50
D II 25 yellow 01652.025000 A218155 50
D III 2 pink 01653.002000 M218672 50
D III 4 brown 01653.004000 E219723 50
D III 6 green 01653.006000 M222168 50
D III 10 red 01653.010000 G222922 50
D III 16 grey 01653.016000 Q200712 50
D III 20 blue 01653.020000 E201254 50
D III 25 yellow 01653.025000 Q201770 50
D III 35 black 01653.035000 L207079 50
D III 50 white 01653.050000 F211513 50
Dimensions see following pages

GPEU87
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED

Key for D gauge pieces D Fuse System


Previous Reference Catalog
Size Pack
Reference Number Number
DII, DIII 01657.993000 E216112 10

D Cover insulating material


Single pole
D II (40 mm width) 00685.700000* H214068 30
D III (50 mm width) 00686.700000* X215093 30
D II (45 mm width) 00685.709000 Q214581 30
D III (54 mm width) 00686.709000 X215599 30
* Standart version

Tiple pole
D II 00625.700000 N213061 8
D II 00626.700000 J213563 8

D Touch Protection rings


Plastic
D II 00181.900000 K222120 50
D III 00182.900000 A222870 50
Porcelain
D II 00081.900000 C219675 30
D III 00072.900000 K212023 20

D Adapter fittings
for DII-fuses links in D III-bases
D II/ D III 00581.000000 C212545 50

DII Supply boards1) 02071.800000* B216615* 10


DII Industry2) 02071.810000 N217132 10
D Locking caps DIII Supply boards1) 02072.800000* T217643* 10
DIII Industry2) 02072.810000 B218156 10
* For authorized energy supplier personnel only
1)
black top, red screw pitch
2)
red top, black screw pitch

Locking keys Supply boards 01714.820000* K213564* 10


Industry 01714.830000 J214069 10
*For authorized energy supplier personnel only

GPEU88
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED

D Fuse System
RATED CURRENT In IN A
2 Ip 2 Ip 2
103 20
VIRTUAL PRE-ARCING TIME T IN S

ID IN KA
100
80

RATED CURRENT IN IN A
65
10 50
102 35

FORWARD CURRENT
25
20
4 16
101
10
6
2
0
10 4
1
2

10-1
0,4

10-2 0,2

0,1
10-3
2 4 101 2 4 102 2 4 103 2 4 104 0,1 0,2 0,4 1 2 4 10 20 100
PROSPECTIVE CURRENT Ip IN A SHORT CIRCUIT CURRENT I IN KA
P

Time-current characteristics of D Fuses 2…100 A gL-gG Forward current characteristics of DIAZED fuses 2…100 A gL-gG

Terminal types
0 1 2 4 6

Clamp terminal Twin Screw terminal Twin Screw terminal Twin Screw terminal

Screw terminal Clamp terminal Twin Screw terminal Screw terminal Clamp terminal

Dimensions

D Fuse-links D Screw caps D Covers D touch protection rings


Cat Cat Cat Cat
a bX a b a b C a b C
Number 1 Number Number Number
NDZ 50 12 690.0002 42 34 685.7 40 90 22 181.9 17,5 44,5 40,5
DII 50 22 691.0002 43 42 686.7 50 90 22 182.9 19 54 50,5
DIII 50 27 589.0002 34 27 685.709 45 90 22 81.9 18,5 43,5 39,8
DIV 63 37 690 42 34 686.709 54 90 22 72.9 18 53,5 50,5
DV 65 45 691 43 42 625.7 107 107 51
592 52 60 626.7 127 130 51
2071 42 33
2072 43 40

GPEU89
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED

Dimensions D Fuse System

Catalog Sizes in mm
number a b c d d1 eX f
99 40 70 53 32 – 38 82
199 40 70 54 20 – 38 83
200 50 90 54 20 – 48 83

Catalog Sizes in mm
number a b c c1 d d1 eX f
625 90 81 54.5 46 80 35 37 81
626 109 100 54.5 46 95 49.5 46.5 81
625* 107 107 51 – – – – –
626* 127 130 51 – – – – –
* with cover cap

Catalog Sizes in mm
number a b c c1 d d1 eX f X h i k
685/81 38 40 60 46 29 27 38 82 43 – – 60
686/72 46 44 57 48 35 33,5 48 84 52 – – 73

Catalog Sizes in mm
number a b c d e f g g1
120 42 52 60 44 38 85 12 37
121 52 62 63 54 48 88 13 38

GPEU90
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C

• The fuse complies with standard EN 60269-2 section II


and standard BS 88 part 2.

• These fuses are designed for :


- “General purpose use” protection (gG type)
- motor protection (gM type)

• This fuse range insures an excellent current limitation for


all overloads on a large range of applications.
Their size cannot allow exchange by other fuses of higher
rating in their range.
They are screwed into fuseholders or bolted directly onto
busbars, or in fuse interruptors disconnectors.

A, B and C types - gG curve Applications


• Power cable protection
Features /Benefits • Distribution panel protection
• Fast gG curve • Control Panel
• Very current limiting • Main circuit
• Tested in DC • Distribution panel
• Voltage 415VAC and 250VDC • Lighting, heating and electrical equipments
• High breaking capacity : 80kA @ 415VAC • Capacitor, Circuit breakers, batteries
and 40kA @ 250VDC tested DC circuit protection.
• A type: bracket connection,
• B type: blade with single central fixing hole connection Approvals
• C type: blade with two central fixing hole connection. • Asta 20 Certified

Ratings
• A type • B type • C type
A1 : from 2A to 32A B1 : from 32A to 100A C1 : from 355A to 400A
A2 : from 2A to 32A B2 : from 125A to 200A C2 : from 450A to 630A
A3 : from 40A to 100A B3 : from 250A to 315A C3 : from 670A to 800A
A4 : from 32A to 100A B4 : from 355A to 400A
Overrating till 200A
A and B types - gM curve Applications
• Motor protection
Features /Benefits
• Inductive load protections
• Fast curve gM • Transient overloads
• Very current limiting • Electrical equipment using motors protection
• Voltage 415VAC Capacitor
• High breaking capacity : 80kA @ 415VAC tested
• A type : bracket connection, Approvals
• B type : blade with single central fixing hole • Asta 20 Certified
connection
Ratings
• A type • B type
A1: 20A B1: 100A
A2: 30A B2: 200A
A3: 63A B3: 315A
A4: 100A and 200A

GPEU92
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C

Standard fuse ampere rating

A, B and C types - gG curve

A type
Type Rating Ref. no Designation Pack. Catalog
Number
A1 2 N226263 2A1 10
A1 4 P226264 4A1 10
A1 6 Q226265 6A1 10
A1 10 R226266 10A1 10
A1 16 S226267 16A1 10
A1 20 T226268 20A1 10
A1 25 V226269 25A1 10
A1 32 W226270 32A1 10
A2 2 Z226273 2A2 10
A2 4 A226274 4A2 10
A2 6 B226275 6A2 10
A2 10 C226276 10A2 10
A2 16 D226277 16A2 10
A2 20 V227833 20A2 10
A2 25 E226278 25A2 10
A2 32 F226279 32A2 10
A3 40 L226284 40A3 10
A3 50 M226285 50A3 10 C type
A3 63 N226286 63A3 10 Catalog
Type Rating Ref. no Designation Pack. Number
A3 80 P226287 80A3 10
A3 100 Q226288 100A3 10 C1 355 G226326 355C1 1
A4 32 T226291 32A4 5 C1 400 H226327 400C1 1
A4 40 V226292 40A4 5 C2 450 J226328 450C2 1
A4 50 W226293 50A4 5 C2 500 K226329 500C2 1
A4 63 X226294 63A4 5 C2 560 L226330 560C2 1
A4 80 Y226295 80A4 5 C2 630 M226331 630C2 1
A4 100 Z226296 100A4 5 C3 670 N226332 670C3 1
A4X* 125 D226300 125A4X 5 C3 710 P226333 710C3 1
A4X* 160 E226301 160A4X 5 C3 750 Q226334 750C3 1
A4X* 200 F226302 200A4X 5 C3 800 R226335 800C3 1

* Current ratings additional to BS88.

B type
Type Rating Ref. no Designation Pack. Catalog
Number
B1X* 32 J226305 32B1X 10
B1X* 40 K226306 40B1X 10
B1X* 50 L226307 50B1X 10
B1X* 63 M226308 63B1X 10
B1 80 N226309 80B1 5
B1 100 P226310 100B1 5
B2 125 T226314 125B2 5
B2 160 V226315 160B2 5
B2 200 W226316 200B2 5
B3 250 Z226319 250B3 1
B3 315 A226320 315B3 1
B3X* 250 C226322 250B3X 1
B3X* 315 D226323 315B3X 1
B4 355 E226324 355B4 1
B4 400 F226325 400B4 1

GPEU93
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C

A and B types - gM curve


A type
Type Rating Ref. no Designation Pack. Catalog
Number
A1 20M25 X226271 20M25A1 10
A1 20M32 Y226272 20M32A1 10
A2 32M40 G226280 32M40A2 10
A2 32M50 H226281 32M50A2 10
A2 32M63 K226283 32M63A2 10
A3 63M80 R226289 63M80A3 10
A3 63M100 S226290 63M100A3 10
A4 100M125 A226297 100M125A4 5
A4 100M160 B226298 100M160A4 5
A4 100M200 C226299 100M200A4 5
A4X 200M250 G226303 200M250A4X 1
A4X 200M315 H226304 200M315A4X 1

B type
Type Rating Ref. no Designation Pack. Catalog
Number
B1 100M125 Q226311 100M125B1 5
B1 100M160 R226312 100M160B1 5
B1 100M200 S226313 100M200B1 5
B2 200M250 X226317 200M250B2 1
B2 200M315 Y226318 200M315B2 1
B3 315M400 B226321 315M400B3 1

Dimensions
A type
Ref. Dimensions (mm & In)
Current ratings (A)
BS 88 A max B max D max E max F nom G nom H nom J nom K max
mm 33 12,7 56 9,5 0,8 44,25 4,8 open 14,3
A1 2, 4, 6, 10, 16, 20, 25*, 32*, 20M25, 20M32 In 1-1/4 1/2 2-3/16 3/8 1/32 1-3/4 3/16 hole 9/16
mm 49 22 86 9 1,2 73 5,5 8 24
A2 2, 4, 6, 10, 16, 20, 25, 32, 32M40, 32M50, 32M63 In 1-15/16 7/8 3-3/8 11/32 3/64 2-7/8 7/32 5/16 15/16
mm 49 22 89 13 1,2 73 5,5 open 24
A3 40, 50, 63 In 1-15/16 7/8 3-1/2 1/2 3/64 2-7/8 7/32 hole 15/16
mm 49 26 89 13 1,2 73 5,5 open 28
A3 80*, 100*, 63M80, 63M100 In 1-15/16 1-1/32 3-1/2 1/2 3/64 2-7/8 7/32 hole 1-3/32
mm 51 22 110 20 2,4 94 8,7 11 25,4
A4 32, 40, 50, 63 In 2 7/8 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1
mm 51 26 110 20 2,4 94 8,7 11 29
A4 80, 100 In 2 1-1/32 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1-1/8
mm 51 35 110 20 2,4 94 8,7 11 38
A4X 125, 160, 200, 100M125, 100M160, 100M200 In 2 1-3/8 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1-1/2
mm 51 41 110 20 2,4 94 8,7 11 45
A4X 200M250*, 200M315* In 2 1-5/8 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1-3/4
* Current ratings additional to BS88.

GPEU94
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C

Dimensions
B type
Ref. Current ratings (A) Dimensions (mm & In)
BS 88 A max B max D max E max F nom G nom H nom I nom
mm 45 22 137 15 1,4 111 8,7 14
B1X 32, 40, 50, 63 in 1-3/4 7/8 5-3/8 9/16 3/64 4-3/8 11/32 9/16
mm 45 26 137 20 3,2 111 8,7 14
B1 80, 100 in 1-3/4 1/32 5-3/8 3/4 1/8 4-3/8 11/32 9/16
mm 45 35 137 20 3,2 111 8,7 14
B1 100M125, 100M160, 100M200 in 1-3/4 1-3/8 5-3/8 3/4 1/8 4-3/8 11/32 9/16
mm 45 35 137 20 3,2 111 8,7 14
B2 125, 160, 200 in 1-3/4 1-3/8 5-3/8 3/4 1/8 4-3/8 11/32 9/16
mm 45 41 137 26 3,2 111 8,7 14
B2 200M250, 200M315 in 1-3/4 1-5/8 5-3/8 1-1/32 1/8 4-3/8 11/32 9/16
mm 45 41 137 26 3,2 111 8,7 14
B3 250, 315 in 1-3/4 1-5/8 5-3/8 1-1/32 1/8 4-3/8 11/32 9/16
mm 45 51 137 26 6,4 111 8,7 14
B3 315M400 in 1-3/4 2 5-3/8 1-1/32 1/4 4-3/8 11/32 9/16
mm 45 41 159 26 3,2 133 10,3 14
B3X 250, 315 in 1-3/4 1-5/8 6-1/4 1-1/32 1/8 5-1/4 13/32 9/16
mm 52 51 137 26 6,4 111 8,7 16
B4 355, 400 in 2-1/16 2 5-3/8 1-1/32 1/4 4-3/8 11/32 5/8

C type
Ref. Current ratings (A) Dimensions (mm & In)
BS 88 A max B max D max E max F nom G nom H nom J nom L nom
C1 355*, 400 mm 52 51 210 26 6,3 133 10,3 16 25,4
In 2-1/16 2 8-1/4 1-1/32 1/4 5-1/4 13/32 5/8 1
C2 450*, 500, 560*, 630 mm 54 61 210 26 7,8 133 10,3 16 25,4
In 2-1/8 2-3/8 8-1/4 1-1/32 5/16 5-1/4 13/32 5/8 1
C3 670*, 710, 750*, 800 mm 56 73 210 26 9,5 133 10,3 16 25,4
In 2-1/16 2 8-1/4 1-1/32 3/8 5-1/4 13/32 5/8 1

* Current ratings additional to BS88.

GPEU95
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
gG and gM fuse-link selection
Fuse-link selection for 3 phase 415 V AC induction motor circuit
Motor rating Direct-on-line start (7 x FLC for 10 sec) Assisted start (3,5 x FLC for 20 sec)
kW In Fuse-link rating (amperes) Fuse-link rating (amperes)
HP gG gM gG gM
0,75 1 2 6 - 4 -
1,1 1,5 2,5 10 - 6 -
1,5 2 3,5 10 - 6 -
2,2 3 5 16 - 10 -
3 4 6,5 20 - 16 -
4 5 8 25 20M25 16 -
5,5 7,5 11 32 20M32 20 -
7,5 10 14 40 32M40 25 20M25
10 13,5 19 50 32M50 32 20M32
11 15 21 50 32M50 32 -
15 20 28 63 32M63 40 32M40
18,5 25 35 80 63M80 50 -
22 30 41 100 63M100 50 -
26 35 48 100 63M100 63 -
30 40 55 125 100M125 80 63M80
33 45 62 160 100M160 80 63M80
37 50 69 160 100M160 100 -
45 60 83 200 100M200 100 -
53 70 97 200 100M200 125 100M125
55 75 100 200 100M200 125 100M125
60 80 110 250 200M250 160 -
67 90 120 250 200M250 160 -
75 100 135 250 200M250 160 -
90 120 160 315 200M315 200 -
93 125 170 355* 315M400* 200 -
110 150 200 400 315M400* 250 200M250
130 175 230 400 315M400* 315 -
150 200 260 450* 400M500* 315 -
160 215 280 500 400M500* 355* 315M400*
170 225 290 500 400M500* 355* 315M400*
180 250 320 560* - 400 -
200 270 350 630 - 400 -
220 300 380 670* - 450 400M500*
250 335 420 710* - 500 -
260 350 450 750* - 560* -
300 400 500 800 - 630 -
* Current ratings additional to BS88.
Maximum full load current starting capability
Direct-on-line start (7 x FLC for 10 sec) Assisted start (3,5 x FLC for 20 sec)
Fuse-link Maximum Fuse-link Maximum
rating (amperes) motor rating (amperes) motor
gG gM In gG gM In
2 - 0,6 2 - 1,3
4 - 1,3 4 - 2,4
6 - 2,3 6 - 4,3
10 - 4,1 10 - 6,4
16 - 6,0 16 - 11 This data is based upon normal starting
20 - 7,9 20 - 14 conditions and usual efficiency and
25 20M25 10 25 20M25 19
32 20M32 13 32 - 24
power factor.
40 32M40 18 40 32M40 31 Conditions such as long run-up times,
50 32M50 26 50 - 46 large numbers of start in succession,
63 32M63 30 63 - 51
80 63M80 40 80 - 69
high ambient temperature or abnormal
100 63M100 54 100 - 94 transients during start/delta switching
125 100M125 61 125 - 110 may necessitate adjustments to fuse-link
160 100M160 82 160 - 150
200 - 110 200 - 180
selection.
250 200M250 150 250 - 220
315 200M315 170 315 - 250
355* 315M400* 200 355* - 310
400 315M400* 240 400 - 340
450* 400M500* 280 450* 400M500* 380
500 400M500* 310 500 - 430
560* - 350 560* - 460
630 - 380 630 - 500
670* - 420 670* - 530
710* - 450 710* - 550
750* - 480 750* - 570
800 - 510 800 - 600
* Current ratings additional to BS88.

GPEU96
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C

Time/current data
20000
4 hours
10000

gG
1000

rating (A)
Fuse-link
100
PRE-ARCING TIME (S)

10

0.1

0.005
1 10 100 1000 10000 100000

PROSPECTIVE CURRENT (R.M.S. SYMMETRICAL A)

20000
4 hours
10000

gM
1000
rating (A)
Fuse-link

100
PRE-ARCING TIME (S)

10

0.1

0.005
1 10 100 1000 10000 100000
Curves from BS88 standard part 1 and 2 PROSPECTIVE CURRENT (R.M.S. SYMMETRICAL A)
(sections 2.1 and 2.2) of 1988.
Voltage rating : 415 V. Interrupting rating : 80 kA under 415 V.
* Current ratings additional to BS88.
GPEU97
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C

I2t characteristics
107

106

105

Operating I2t at 415 V.


104 Pre-arcing I2t

103

102

10

* Current ratings additional to BS88

Dissipated power

BS 88 part 2 (Section 2.2) standardized limit

* Current ratings additional to BS88

GPEU98
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C

100
Peak let-through
current

10

0.1
0.1 1 10 100
* Current ratings additional to BS88
Nominal current derating by temperature
Fuse-link Current carrying capability (in amperes) at elevated temperatures - When the fuse-link is mounted in the open, the elevated
rating (A) 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C temperature is the ambient air temperature (Ta).
2, 4, 6, 10 - When the fuse-link is mounted in an enclosure, the elevated
16 15 temperature is the internal “fluid environment temperature”
20 18 16 (Te) within the enclosure.
25 23 21 19
32 31 30 29 - When it is not known, it should be assumed to be 15°C higher
40 39 38 37 than the ambient air temperature external to the enclosure, i.e.
50 49 48 47 Te = Ta + 15°C.
63 61 59 57
80 79 78 76
Examples:
100 98 96 94 - 100A fuse-link mounted in the open at an ambient air
125 122 119 116 temperature of 65°C.
FUSE-LINKS
160 155 150 145 140 Current carrying capability = 100A.
FULLY RATED
200 195 190 185 180 175 - 200A fuse-link mounted in the open at an ambient air
250 240 230 220 210 200 temperature of 60°C.
315 310 300 290 270 250
Current carrying capability = 195A.
355* 345 335 320 300 280
400 390 380 370 350 330 310 - 400A fuse-link mounted in an enclosure having an internal
450* 445 430 410 390 370 350 temperature of 65°C.
500 490 480 460 440 420 400 Current carrying capability = 370A.
560* 550 530 510 490 470 450 - 800A fuse-link mounted in an enclosure with an unknown
630 620 610 590 570 550 530 510 490
internal temperature and an external ambient air temperature
670* 660 640 620 600 580 560 540 520
710* 700 680 660 640 620 600 580 560
of 40°C. Assume the internal temperature is 55°C (40°C +
750* 740 730 710 690 670 650 630 600 15°C). Current carrying temperature = 740A.
800 780 760 740 720 700 680 660 640

Curves and derating comply with BS88 standard part 1 and 2 sections 2.1 and 2.2 of 1988.
* Derating also applies, to additional current ratings.

GPEU99
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes F1,F2

•The fuse comply with standard EN 60269-2 section II


and standard BS88 part 2.
•This fuses are designed for :
- “general purpose use” protection, (gG type)
- motor protection (gM type)
•This fuse range insures an excellent current limitation
for all overloads on a large range of applications.
Their size cannot allow exchange by other fuses of
higher rating in the F type range.
They are compact and can be connected with clips.

F1,F2 types - gG curve Applications


• Power cable protection
Features /Benefits • Distribution panel protection
• Compact design • Control panel
• Curve gG and gM • Main circuit
• Very current limiting • Lighting, heating and electrical equipments
• Tested in DC • Capacitor, batteries
• Voltage 415VAC • Can be used with circuit breakers.
• High breaking capacity : 80kA @ 415VAC
• Connection by clips or appropriate fuse holders. Approvals
• Asta 20 Certified

Ratings
• F1 type
from 2A to 32A

• F2type
from 10A to 63A

Fuses designations and ratings

F1 type F2 type
Rating Ref. no Designation Pack. Catalog Type Rating Ref. no Designation Pack. Catalog
Type Number Number
F1 2 S226336 2F1 10 F2 10 D226346 10F2 10
F1 4 T226337 4F1 10 F2 16 E226347 16F2 10
F1 6 V226338 6F1 10 F2 20 F226348 20F2 10
F1 10 W226339 10F1 10 F2 25 G226349 25F2 10
F1 16 X226340 16F1 10 F2 32 H226350 32F2 10
F1 20 Y226341 20F1 10 F2 40 J226351 40F2 10
F1 25 Z226342 25F1 10 F2 50 K226352 50F2 10
F1 32 A226343 32F1 10 F2 63 L226353 63F2 10
F1* 20M25 B226344 20M25F1 10
F1* 20M32 C226345 20M32F1 10

* Selection table for gM fuses : refer to A, B and C types

GPEU100
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes F1,F2

Dimensions

Ref. Voltage (Vac) Current ratings (A) Dimensions (mm)


BS 88 A max B max D max E max F nom N nom
mm 35,5 14,3 62 11,5 0,8 3,5
F1 415V 2, 4, 6, 10, 16, 20, 25, 32, 20M25*, 20M32*
in 1-2/5 9/16 2-7/16 9/20 1/32 1/8
mm 39 17,5 69 15 1,4 3,5
F2 415V 10, 16, 20, 25, 32, 40, 50, 63
In 1-7/13 11/16 2-13/8 9/16 1/18 1/8
* Current ratings additional to BS88 also comply to the BS 88 standard part 6 of 1988.

Time/current data
20000
4 hours
10000

1000
Fuse-link ampere
rating

100

10

0.1

0.005
1 10 100 1000 10000 100000

GPEU101
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes F1,F2
I2t characteristics
107

106
Curves from BS88 standard part 6 of
1988.
Voltage rating : 415 VAC.
105
Interrupting rating : 40 kA
under 415 VAC.
104

ASTA 20 certified
103
Operating I2t at 415 V. * Current ratings additional to BS88 also comply to
pre-arcing I2t
102 the BS 88 standard part 6 of 1988.

10

0
Dissipated power
5

Curves from BS88 standard part 6


of 1988. 4
Voltage rating : 415 VAC.
Interrupting rating : 40 kA
under 415 VAC.
3

* Current ratings additional to BS88 also


comply to the BS 88 standard part 6 of
1988. 2

Peak let-through current


1
100

0
BS 88-part 6 standardized limit

10
Curves from BS88 standard part 6 of 1988.
Voltage rating : 415 VAC.
Interrupting rating : 40 kA
under 415 VAC.
1 * Current ratings additional to BS88 also comply to the BS 88
standard part 6 of 1988.

0.1
0.1 1 10 100

GPEU102