Ferraz Shawmut IEC Fuses
Ferraz Shawmut IEC Fuses
Ferraz Shawmut IEC Fuses
gF/gG gG gG aM aM
Residential Full Range Full Range Short Circuit Short Circuit
Full Range Protection Protection Protection Protection
Protection
Fuse-links • 4 physical sizes Fuse-links
• 7 physical sizes • 4 physical sizes with striker from 8 x 31 mm with striker
from 6.3 x 23mm from 8 x 31mm to 22 x 58 mm
to 10.3 x 38 mm to 22 x 58 mm • 2 sizes- • 2 sizes -
14 x 51mm 14 x 51mm and
• 250 and 380 Volt • 400, 500 and 22 x 58mm
• 400, 500 and 690 and 22 x 58 mm
ratings - 0.5A 690 Volt ratings-
Volt ratings -0.5A 0.16A through
through 32A through 125A • 400, 500 and • 400, 500 and
690 Volt ratings 125A 690 Volt ratings
• Most ratings • Most ratings 4A through 125A - 2A through
available with • Most ratings 125A
available with available with
indicator indicator • All ratings
include striker indicator • All ratings
• Meet IEC, NFC, • Meet IEC, NFC include striker
UNE standards • Meet IEC, • Meet IEC, NFC
and UNE and UNE
standards NFC and UNE • Meet IEC, NFC
• See residential standards standards and UNE
fuse-links, Special • Approved by standards
Purpose section • Approved by • Approved by
Lloyds Register Lloyds Register
of Shipping and Lloyds Register of • Approved by
Shipping and of Shipping and Lloyds Register
Bureau Veritas Bureau Veritas
Bureau Veritas of Shipping and
Bureau Veritas
GPEU2
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58
Ratings - gG (Optional Blown-Fuse Indicator)
Size Rated In Rated Previous References Reference Number Breaking Catalog Number
Current (A) Voltage w/o w w/o w Capacity w/o w
Indicator Indicator Indicator Indicator Indicator Indicator
0.5 15009 - P218191 - FR8GG40V0.5
1 15011 - C218709 FR8GG40V1
2 15013 15213 Q219227 B222204 FR8GG40V2 FR8GG40V2I
4 15019 15219 W222958 X222959 FR8GG40V4 FR8GG40V4I
6 15023 15223 A211025 V201291 FR8GG40V6 FR8GG40V6I
8 x 31 8 400V 15027 15227 B213096 B211026 20kA - 400V FR8GG40V8 FR8GG40V8I
10 15031 15231 A214613 A212060 FR8GG40V10 FR8GG40V10I
12 15033 15233 R216146 C213097 FR8GG40V12 FR8GG40V12I
16 15035 15235 P216650 Y214105 FR8GG40V16 FR8GG40V16I
20 15037 15237 F217677 J215127 FR8GG40V20 FR8GG40V20I
25 15039 15239 D218710 S216147 FR8GG40V25 FR8GG40V25I
0.5 16009 - C211027 - FR10GG50V0.5 FR10GG50V2I
1 16011 - B212061 - FR10GG50V1 FR10GG50V4I
2 16013 16213 D213098 S216653 FR10GG50V2 FR10GG50V6I
4 16019 16219 X213598 E217170 FR10GG50V4 FR10GG50V10I
6 16023 16223 K215128 T218195 FR10GG50V6 FR10GG50V10I
10 X 38 8 500V 16027 16227 D217169 V219231 120kA - 500V FR10GG50V10 FR10GG50V12I
10 16031 16231 S218194 E222207 FR10GG50V10 FR10GG50V16I
12 16033 16233 W219761 H200751 FR10GG50V12 FR10GG50V20I
X211551 16 16035 16235 G200750 H201809 FR10GG50V16 FR10GG50V25I
20 16037 16237 D211028 X211551 FR10GG50V20 FR10GG50V32I
25 16039 16239 E213099 W212585 FR10GG50V25 FR10GG50V2I
32 400V 16043 16243 A214107 Z213600 120kA - 400V FR10GG50V32 FR10GG50V4I
1 17011 - K218716 - FR14GG69V1
2 17013 17213 Y219234 C201298 FR14GG69V2 FR14GG69V2I
4 17019 17219 A219765 H211032 FR14GG69V4 FR14GG69V4I
6 17023 17223 H222210 G212066 FR14GG69V6 FR14GG69V6I
8 17027 17227 D222965 K213104 FR14GG69V8 FR14GG69V8I
10 17031 17231 L200754 H214620 FR14GG69V10 FR14GG69V10I
14 X 51 12 690V 17033 17233 L201812 R215640 80kA - 690V FR14GG69V12 FR14GG69V12I
16 17035 17235 A211554 X216657 FR14GG69V16 FR14GG69V16I
20 17037 17237 Z212588 N217684 FR14GG69V20 FR14GG69V20I
25 17039 17239 C213603 M218718 FR14GG69V25 FR14GG69V25I
M218718
32 500V 17043 17243 W216656 C219767 FR14GG69V32 FR14GG69V32I
40 17047 17247 X218198 F222967 120kA - 500V FR14GG69V40 FR14GG69V40I
50 400V 17051 17251 Z219235 D201299 120kA - 400V FR14GG69V50 FR14GG69V50I
2 18013 - F219241 - FR22GG69V2
4 18019 18219 H219772 Q211039 FR22GG69V4 FR22GG69V4I
6 18023 18223 P222216 P212073 FR22GG69V6 FR22GG69V6I
8 18027 18227 L222972 R213110 FR22GG69V8 FR22GG69V8I
10 18031 18231 T200761 N214119 FR22GG69V10 FR22GG69V10I
12 18033 18233 J201304 Y215140 FR22GG69V12 FR22GG69V12I
16 18035 18235 S201818 D216157 FR22GG69V16 FR22GG69V16I
20 18037 18237 P211038 R217181 FR22GG69V20 FR22GG69V20I
22 x 58 25 690V 18039 18239 N212072 F218206 80kA - 690V FR22GG69V25 FR22GG69V25I
32 18043 18243 F212594 H219243 FR22GG69V32 FR22GG69V32I
40 18047 18247 J213609 R222218 FR22GG69V40 FR22GG69V40I
K211563 50 18051 18251 P214626 W200763 FR22GG69V50 FR22GG69V50I
63 18055 18255 Y215646 V201820 FR22GG69V63 FR22GG69V63I
80 18059 18259 Q217180 K211563 FR22GG69V80 FR22GG69V80I
100 500V 18063 18263 E218205 H212596 120kA -500V FR22GG69V100 FR22GG69V100I
125 400V 18065 18265 J219773 L213611 120kA -400V FR22GG69V125 FR22GG69V125I
Packaging 10
GPEU3
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58
Dimensions Striker
Fuse Size A B C D E
14 x 51 14.3 51 13.8 7.5 3.8
22 x 58 22.2 58 16.2 7.5 3.8 1 Ceramic body BEFORE AFTER
2 Sand
3 Indicator contact
4 Lower contact
5 Contact ring
6 Melting element
7 Indicator
Neutral
Size Previous Reference Standard Catalog
(mm x mm) Reference Number Pack/CTN Number
GPEU4
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58
Characteristics t-l
PREARCING TIME T(S)
Cut-off characteristics
MAXIMUM VALUE OF CURRENT (KA PEAK)
GPEU5
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58
Characteristics I2t
8
6
5
4 gG
3
2
8
6
5
4
3
}
2
690 V
8
6
500 V - OPERATING I2T
5
4
3 400 V
{
2
- PREARCING I2T
8
6
5
4
3
2
8
6
5
4
3
2
100
90
80
70
60
50
40
30
20
10
2 4 6 8 10 12 16 20 25 32 2 4 6 8 10 12 16 20 25 32 40 50 16 20 25 32 40 50 63 80 100 125 In
10 x 38 14 x 51 22 x 58
GPEU6
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
gG 8x32, 10x38, 14x51, 22x58
0,5 A 2W
1A 2,5 W 3,4 W
2A 0,70 W 1W 1,20 W
4A 0,80 W 1,10 W 1,30 W
6A 0,90 W 1,20 W 1,40 W
8A 1,10 W 1,50 W 1,65 W
10 A 1,35 W 1,80 W 2W
12 A 1,55 W 2,10 W 2,40 W
16 A 1,90 W 2,55 W 3W
20 A 2,30 W 3W 3,40 W
25 A 2,80 W 3,50 W 3,80 W
32 A 3W 3,80 W 4,30 W
40 A 4,40 W 5,10 W
50 A 4,7 W 5,50 W
63 A 6,70 W
80 A 8W
100 A 9W
125 A 12,5 W
Maximum standardized 10 x 38 14 x 51 22 x 58
power low. IEC 269-2-1
NFC 63.213 25 A 40 A 100 A
UNE 21.103-2-1
3W 5W 9,5 W
gG Class Fuses
16 20 25 32 40 50 63 80 100 125
1,5 99/113 86/87 40/59 21/29 13/16 7/9
2,5 134 110/122 67/84 41/51 25/33 13/20 8/11
4 183 139 108/119 67/84 46/58 24/32 14/17 7,3/10
6 214 165 139 94/113 55/70 33/41 20/27
10 275 226 172 130 90/108 57/70
16 283 217 168 128
25 336 257 197
35 367 283
50 379
* 99/118:
- 99; Cond. PVC / 118; Cond. PRC GPEU7
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58
Ratings – aM (Optional Blown-Fuse Indicator)
Size Rated In Rated Previous Reference Reference Number Breaking Catalog Number
(mm x mm) Current (A) Voltage w/o w w/o w Capacity w/o w
1 Indicator Indicator Indicator Indicator Indicator Indicator
15511 - C217168 - FR8AM40V1
2 15513 - R218193 - FR8AM40V2
S219229 4 15519 - S219229 - FR8AM40V4
8 x 31 6 400V 15523 - C222205 - 20kA - 400V FR8AM40V6
8 15527 - F200749 - FR8AM40V8
10 15531 - W201292 - FR8AM40V10
0.16 16503 - E214617 - FR10AM50V0.16
0.25 16507 - M215130 - FR10AM50V0.25
F214618 0.5 16509 - W216150 - FR10AM50V0.5
1 16511 16711 F217171 X219233 FR10AM50V1 FR10AM50V1I
2 16513 16713 H218714 G222209 FR10AM50V2 FR10AM50V2I
4 16519 16719 W219232 K200753 FR10AM50V4 FR10AM50V4I
6 16523 16723 F222208 K201811 FR10AM50V6 FR10AM50V6I
10 X 38 8 500V 16527 16727 Z201295 Z211553 120kA - 500V FR10AM50V10 FR10AM50V10I
10 16531 16731 Y211552 H213102 FR10AM50V10 FR10AM50V10I
12 16533 16733 A213601 D214110 FR10AM50V12 FR10AM50V12I
16 16535 16735 F214618 P215132 FR10AM50V16 FR10AM50V16I
20 16537 16737 X216151 V216655 FR10AM50V20 FR10AM50V20I
25 400V 16539 16739 G217172 L217682 120kA - 400V FR10AM50V25 FR10AM50V25I
32 400V 16543 - J218715 - 120kA - 400V FR10AM50V32
0.25 17507 - B212590 - FR14AM69V0.25
0.5 17509 - L213105 - FR14AM69V0.5
1 17511 17711 E213605 C212591 FR14AM69V1 FR14AM69V1I
2 17513 17713 H214114 M213106 FR14AM69V2 FR14AM69V2I
Q217686 4 17519 17719 K214622 J214115 FR14AM69V4 FR14AM69V4I
6 17523 17723 S215135 T215136 FR14AM69V6 FR14AM69V6I
8 17527 17727 T215642 A216660 FR14AM69V8 FR14AM69V8I
10 17531 17731 Z216659 R217687 FR14AM69V10 FR14AM69V10I
14 X 51 12 690V 17533 17733 M217177 Q218721 80kA - 690V FR14AM69V12 FR14AM69V12I
16 17535 17735 Q217686 F219770 FR14AM69V16 FR14AM69V16I
20 17537 17737 P218720 R200759 FR14AM69V20 FR14AM69V20I
25 17539 17739 E219769 Q201816 FR14AM69V25 FR14AM69V25I
32 17543 17743 M222214 F211559 120kA - 500V FR14AM69V32 FR14AM69V32I
40 500V 17547 17747 Q200758 D212592 FR14AM69V40 FR14AM69V40I
45 17549 17749 L211035 G213607 FR14AM69V45 FR14AM69V45I
50 400V 17551 17751 E211558 M214624 120kA - 400V FR14AM69V50 FR14AM69V50I
1 18511 - M219776 - FR22AM69V1
2 18513 - T222220 - FR22AM69V2
4 18519 18719 Q222976 L219246 FR22AM69V4 FR22AM69V4I
6 18523 18723 Y200765 V222221 FR22AM69V6 FR22AM69V6I
8 18527 18727 N201308 Y201823 FR22AM69V8 FR22AM69V8I
10 18531 18731 X201822 N211566 FR22AM69V10 FR22AM69V10I
12 18533 18731 T211042 K212598 FR22AM69V12 FR22AM69V12I
C215650 16 18535 18735 M211565 P213614 FR22AM69V16 FR22AM69V16I
22 x 58 20 690V 18537 18737 S212076 V214631 80kA - 690V FR22AM69V20 FR22AM69V20I
25 18539 18739 J212597 D215651 FR22AM69V25 FR22AM69V25I
32 18543 18743 V213113 J216668 FR22AM69V32 FR22AM69V32I
40 18547 18747 N213613 Z217694 FR22AM69V40 FR22AM69V40I
50 18551 18751 R214122 P219778 FR22AM69V50 FR22AM69V50I
63 18555 18755 C215650 Z200766 FR22AM69V63 FR22AM69V63I
80 18559 18759 H216667 P211567 FR22AM69V80 FR22AM69V80I
100 500V 18563 18763 Y217693 L212599 120kA - 500V FR22AM69V100 FR22AM69V100I
125 400V 18565 18765 J218209 W214632 120kA - 400V FR22AM69V125 FR22AM69V125I
Packaging 10
GPEC8
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58
Ratings – aM with Striker
Size Rated Rated Previous Reference Breaking Catalog
(mm x mm) Current In Voltage Reference Number Capacity Number.
(A)
1 17911 W215644 FR14AM69V1P
2 17913 B216661 FR14AM69V2P
4 17919 C218203 FR14AM69V4P
6 17923 E219240 FR14AM69V6P
8 17927 N222215 FR14AM69V8P
10 17931 S200760 FR14AM69V10P
X215645 14 X 51 12 500V 17933 R201817 120kA 500V FR14AM69V12P
16 17935 G211560 FR14AM69V16P
20 17937 E212593 FR14AM69V20P
25 17939 H213608 FR14AM69V25P
32 17943 N214625 FR14AM69V32P
40 17947 X215645 FR14AM69V40P
45 17949 C216662 FR14AM69V45P
50 400V 17951 D218204 120kA - 400V FR14AM69V50P
1 18911 E215652 FR22AM69V1P
2 18913 J216162 FR22AM69V2P
4 18919 A217695 FR22AM69V4P
6 18923 Y218728 FR22AM69V6P
8 18927 Q219779 FR22AM69V8P
10 18931 S222978 FR22AM69V10P
K216669
12 18933 R201311 FR22AM69V12P
16 18935 W211044 FR22AM69V16P
22 X 58 20 690V 18937 W212079 80kA - 690V FR22AM69V20P
25 18939 Q213615 FR22AM69V25P
32 18943 X214633 FR22AM69V32P
40 18947 F215653 FR22AM69V40P
50 18951 K216669 FR22AM69V50P
63 18955 B217696 FR22AM69V63P
80 500V 18959 Z218729 120kA - 500V FR22AM69V80P
100 18963 T222979 FR22AM69V100P
125 400V 18965 S201312 120kA - 400V FR22AM69V125P
Packaging 10
Dimensions Striker
Fuse Size A B C D E
14 x 51 14.3 51 13.8 7.5 3.8
22 x 58 22.2 58 16.2 7.5 3.8
BEFORE AFTER
Neutral
Size Previous Reference Standard Catalog
(mm x mm) Reference Number Pack/CTN Number
GPEU9
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58
Characteristics t-l
aM
PREARCING TIME T(S)
Cut-off characteristics
MAXIMUM VALUE OF CURRENT (KA PEAK)
GPEU10
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
gG 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58
Characteristics I2t
I2T VALUE (A2S)
aM
690 V
500 V
400 V
} - OPERATING I2T
{ - PREARCING I2T
80
70
60
50
40
30
20
10
1 2 4 6 8 10 12 16 20 25 32 1 2 4 6 8 10 12 16 20 25 32 40 50 1 2 4 6 8 10 12 16 20 25 32 40 50 63 80 100 125 In
10 x 38 14 x 51 22 x 58
GPEU11
General Purpose Fuses IEC
General Purpose Fuses IEC
Ferrule Fuses
aM 400V to 690V
with/without Striker
aM 8x32, 10x38, 14x51, 22x58
0,16 A 0,35 W
0,25 A 0,50 W 0,70 W
0,5 A 0,50 W 0,75 W
1A 0,13 W 0,18 W 0,20 W
2A 0,20 W 0,25 W 0,30 W
4A 0,30 W 0,40 W 0,50 W
6A 0,45 W 0,55 W 0,65 W
8A 0,55 W 0,65 W 0,75 W
10 A 0,65 W 0,75 W 0,85 W
12 A 0,75 W 0,85 W 1W
16 A 0,90 W 1,20 W 1,40 W
20 A 1,10 W 1,50 W 1,70 W
25 A 1,40 W 1,80 W 2W
32 A 2W 2,10 W 2,60 W
40 A 2,60 W 3,20 W
45 A 2,80 W
50 A 2,90 W 3,90 W
63 A 4,60 W
80 A 5,60 W
100 A 6,50 W
125 A 9,50 W
Maximum standardized 10 x 38 14 x 51 22 x 58
power low. IEC 269-2-1
NFC 63.213 16 A 50 A 100 A
UNE 21.103-2-1
1,2 W 3W 7W
aM Class Fuses
Copper
conductor Rated Current (In) OF aM Fuses (in A)
section (mm2)
16 20 25 32 40 50 63 80 100 125
1,5 55/64 37/45 25/30 15/20
2,5 116 84/94 58/68 40/49 26/32 17/20
4 181 147 118 84/95 58/68 42/48 28/33 18/23
6 273 223 178 139 105/117 79/89 55/64 37/42 26/31 14/20
10 227 181 147 113/125 80/94 57/69 40/47
16 236 189 151 120 83/97
25 231 185 147
35 262 210
GPEU12
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
aM 500V, 690V
NH Fuse System
The use category is identified by two letters, the first indicating the
operational class and the second the object to be protected.
The Ferraz shawmut range includes fuse-links to DIN VDE 0636
standard for the following uses categories:
gG: general purpose cable and line protection
aM: Partial purpose, motor circuit protection
gTr: general purpose, transformer protection
gR: general purpose, fast acting
aR: partial purpose, fast acting
Classification
The NH system is classed among plug-in fuse systems and is comprised of:
- fuse-base, (possibly including terminal covers and phase barriers)
- fuse-link with blade contact
- fuse-link replacement device (LV HRC fuse puller)
Since the design of this system cannot guarantee non-interchangeability of rated current, it must be
handled by a qualified professional.
Approval symbols
Germany
~0% lead
Austria
~0% cadmium
Switzerland
Netherlands
~it costs you
not a penny
more !
~it corresponds with the
2nd design of European
electronical scraps
guideline
~100% for a sure future
GPEU13
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 400V Size 000 to 3
NH-fuses, 400VAC gG
Pb-free with non-isolated gripping
lugs, double indicator,
contact blades, complying
with DIN VDE 0636Part 201
and IEC 60269-2-1
GPEU14
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 400V Size 000 to 3 - Isolated Lug
NH-fuses, 400VAC gG
with isolated metal gripping Pb-free
lugs (SGL),double indicator,
contact blades, complying
withDIN VDE 0636 Part 201
and IEC 60269-2-1
GPEU15
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 4a
NH-fuses, 500VAC gG
Cd/Pb-free with non-isolated gripping lugs, double indicator, contact blades, complying
with DIN VDE 0636 Part 201 and IEC 60269-2-1
GPEU16
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 4a
NH-fuses, 500VAC gG
with non-isolated gripping lugs, double indicator, contact blades, complying Cd/Pb-free
with DIN VDE 0636 Part 201 and IEC 60269-2-1
GPEU17
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 3 - Isolated Lug
NH-fuses, 500VAC gG
Cd/Pb-free with isolated metal gripping
lugs (SGL), double indicator,
contact blades, complying
with DIN VDE 0636 Part 201
and IEC 60269-2-1
GPEU18
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 500V Size 000 to 3 - Isolated Lug
NH-fuses, 500VAC gG
with isolated metal gripping Cd/Pb-free
lugs (SGL), double indicator,
contact blades, complying
with DIN VDE 0636 Part 201
and IEC 60269-2-1
GPEU19
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 690V Size 000 to 4a
NH-fuses, 690VAC gG
Cd/Pb-free with non-isolated gripping lugs, doubleindicator, contact blades, complying
with DIN VDE 0636 Part 201 and IEC 60269-2-1
GPEU20
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 690V Size 000 to 4a
NH-fuses, 690VAC gG
with non-isolated gripping lugs, doubleindicator, contact blades, complying Cd/Pb-free
with DIN VDE 0636 Part 201 and IEC 60269-2-1
GPEU21
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG 690V Size 000 to 3 - Isolated Lug
NH-fuses, 690VAC gG
Cd/Pb-free with isolated metal gripping lugs (SGL), double indicator, contact blades,
complying with DIN VDE 0636 Part 201 and IEC 60269-2-1
Rated current Power dissipation weight
Size FS ref.-no. Previous ref. pack. Catalog Number
IN(A) (W) kg/pce
000 2 1,9 D229704 1G613. 0,14 3 NH000GG69V2-1
000 4 1,5 E229705 1G619. 0,14 3 NH000GG69V4-1
000 6 1,6 F229706 1G623. 0,14 3 NH000GG69V6-1
000 10 1,1 H229708 1G631. 0,14 3 NH000GG69V10-1
000 16 1,8 J229709 1G635. 0,14 3 NH000GG69V16-1
000 20 2,3 K229710 1G637. 0,14 3 NH000GG69V20-1
000 25 2,4 L229711 1G639. 0,14 3 NH000GG69V25-1
000 32 3,1 M229712 1G643. 0,14 3 NH000GG69V32-1
000 35 3,0 N229713 1G645. 0,14 3 NH000GG69V35-1
000 40 3,7 P229714 1G647. 0,14 3 NH000GG69V40-1
000 50 4,1 Q229715 1G651. 0,14 3 NH000GG69V50-1
000 63 5,4 R229716 1G655. 0,14 3 NH000GG69V63-1
000 80 6,5 S229717 1G659. 0,14 3 NH000GG69V80-1
00 32 3,1 T229718 1G743. 0,20 3 NH00GG69V32-1
00 35 3,0 V229719 1G745. 0,20 3 NH00GG69V35-1
00 40 3,7 W229720 1G747. 0,20 3 NH00GG69V40-1
00 50 4,1 X229721 1G751. 0,20 3 NH00GG69V50-1
00 63 5,6 Y229722 1G755. 0,20 3 NH00GG69V63-1
00 80 6,8 Z229723 1G759. 0,20 3 NH00GG69V80-1
00 100 7,5 A229724 1G763. 0,20 3 NH00GG69V100-1
00 125 10,0 B229725 1G765. 0,20 3 NH00GG69V125-1
0 6 1,6 C229726 1G023. 0,26 3 NH0GG69V6-1
0 10 1,1 D229727 1G031. 0,26 3 NH0GG69V10-1
0 16 1,8 E229728 1G035. 0,26 3 NH0GG69V16-1
0 20 2,3 F229729 1G037. 0,26 3 NH0GG69V20-1
0 25 2,4 G229730 1G039. 0,26 3 NH0GG69V25-1
0 32 3,1 H229731 1G043. 0,26 3 NH0GG69V32-1
0 35 3,0 J229732 1G045. 0,26 3 NH0GG69V35-1
0 40 3,7 K229733 1G047. 0,26 3 NH0GG69V40-1
0 50 4,1 L229734 1G051. 0,26 3 NH0GG69V50-1
0 63 6,6 M229735 1G055. 0,26 3 NH0GG69V63-1
0 80 8,0 N229736 1G059. 0,26 3 NH0GG69V80-1
0 100 9,4 P229737 1G063. 0,26 3 NH0GG69V100-1
0 125 11,8 Q229738 1G065. 0,26 3 NH0GG69V125-1
0 160 14,6 R229739 1G069. 0,26 3 NH0GG69V160-1
1 16 1,8 S229740 1G135. 0,29 1 NH1GG69V16-1
1 20 2,3 T229741 1G137. 0,29 1 NH1GG69V20-1
1 25 2,4 V229742 1G139. 0,29 1 NH1GG69V25-1
1 32 3,1 W229743 1G143. 0,29 1 NH1GG69V32-1
1 35 3,0 X229744 1G145. 0,29 1 NH1GG69V35-1
1 40 3,7 Y229745 1G147. 0,29 1 NH1GG69V40-1
1 50 4,1 Z229746 1G151. 0,29 1 NH1GG69V50-1
1 63 6,6 A229747 1G155. 0,29 1 NH1GG69V63-1
1 80 8,0 B229748 1G159. 0,29 1 NH1GG69V80-1
1 100 9,4 C229749 1G163. 0,29 1 NH1GG69V100-1
1 125 11,8 D229750 1G165. 0,42 1 NH1GG69V125-1
1 160 14,6 E229751 1G169. 0,42 1 NH1GG69V160-1
1 200 18,0 F229752 1G171. 0,42 1 NH1GG69V200-1
1 224 19,0 G229753 1G173. 0,42 1 NH1GG69V224-1
2 32 3,1 J229755 1G243. 0,43 1 NH2GG69V32-1
2 35 3,0 K229756 1G245. 0,43 1 NH2GG69V35-1
2 40 3,7 L229757 1G247. 0,43 1 NH2GG69V40-1
2 50 4,1 M229758 1G251. 0,43 1 NH2GG69V50-1
2 63 6,8 N229759 1G255. 0,43 1 NH2GG69V63-1
2 80 8,3 P229760 1G259. 0,43 1 NH2GG69V80-1
2 100 10,7 Q229761 1G263. 0,43 1 NH2GG69V100-1
2 125 12,2 R229762 1G265. 0,43 1 NH2GG69V125-1
2 160 15,0 S229763 1G269. 0,43 1 NH2GG69V160-1
2 200 18,5 T229764 1G271. 0,43 1 NH2GG69V200-1
2 224 19,2 V229765 1G273. 0,43 1 NH2GG69V224-1
2 250 20,6 D233729 1G275. 0,43 1 NH2GG69V250-1
2 300 21,0 X229767 1G277. 0,43 1 NH2GG69V300-1
2 315 25,0 Y229768 1G279. 0,65 1 NH2GG69V315-1
2 355 31,5 Z229769 1G281. 0,65 1 NH2GG69V355-1
3 250 21,1 A229770 1G375. 0,65 1 NH3GG69V250-1
3 300 22,6 B229771 1G377. 1,01 1 NH3GG69V300-1
3 315 25,0 C229772 1G379. 1,01 1 NH3GG69V315-1
3 355 32,0 D229773 1G381. 1,01 1 NH3GG69V355-1
3 400 34,0 E229774 1G383. 1,01 1 NH3GG69V400-1
3 425 34,0 F229775 1G385. 1,01 1 NH3GG69V425-1
Non suitable for Microswitch.
GPEU22 07/05
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG Curves Set
Rated current in A
30000
125 A
20000 100 A
80 A
10 4 63 A
50 A
Ip
5000 40 A
3
2.
3000 10 4 35 A
=
32 A
Im
2000
25 A
10 3
20 A
16 A
PEAK LET-THRU IN KA
500 10 A
300 6A
200 4A
10 2 2A
50
10 3
30
20
10
5
3
2
10 2
1
2 4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 300 355 400 425 500 630 800 1000 1250 10 2 10 3 10 4 10 5 10 6
315
200 A
250 A
315 A
20 A
32 A
40 A
63 A
1250 A
355 A
125 A
160 A
224 A
300 A
500 A
425 A
800 A
10 A
16 A
25 A
35 A
50 A
80 A
2A
4A
6A
10 4
10 3
10 2
MELTING TIME
10
10 -1
10 -2
1 2 4 6 8 10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A
GPEU23
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG 400V, 500V, 690V
gG Curves Set
NH-fuses, 690VAC gG
Total Clearing I2t Current Limitation Curves
10 7
5000000 10 6
3000000
2000000
1000 A
800 A
630 A
10 6 500 A
500000
450 A
425 A
300000 400 A
200000 355 A
10 5 315 A
10 5 300 A
250 A
50000 224 A
30000
200 A
160 A
20000 125 A
100 A
10 4 80 A
63 A
5000 50 A
Ip
40 A
3000 10 4 35 A
3
2.
2000 32 A
=
25 A
Im
10 3 PEAK LET-THRU IN KA 20 A
500 16 A
10 A
300
200 6A
4A
10 2
10 3 2A
50
30
20
10
5
3
2
10 2
1
2 4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 300 355 400 425 450 500 630 800 1000 10 2 10 3 10 4 10 5 10 6
315
200 A
250 A
315 A
20 A
32 A
40 A
63 A
355 A
125 A
160 A
224 A
300 A
500 A
425 A
800 A
10 A
16 A
25 A
35 A
50 A
80 A
2A
4A
6A
10 4
10 3
10 2
MELTING TIME
10
10 -1
10 -2
1 2 4 6 8 10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A
GPEU24
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM 500V Size 000 to 4a
NH-fuses, 500VAC aM
with non-isolated gripping lugs, double indicator, contact blades, Cd/Pb-free
complying with DIN VDE 0636 Part 201and IEC 60269-2-1
GPEU25
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM 690V Size 000 to 4a
NH-fuses, 690VAC aM
Cd/Pb-free with non-isolated gripping lugs, double indicator, contact blades, complying
with DIN VDE 0636 Part 201 and IEC 60269-2-1
GPEU26
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM 690V Size 000 to 4a
NH-fuses, 690VAC aM
with non-isolated gripping lugs, double indicator, contact blades, Cd/Pb-free
complying with DIN VDE 0636 Part 201and IEC 60269-2-1
GPEU27
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM Curves Set
NH-fuses, 500VAC aM
Total Clearing I2t Current Limitation Curves
10 7
5000000
3000000
2000000
10 6 10 6
500000
800 A (400 V)
300000
630 A
200000 500 A
450 A
10 5 400 A
355 A
315 A
50000 10 5 250 A
224 A
30000 200 A
20000 160 A
125 A
100 A
10 4
80 A
63 A
5000 PEAK LET-THRU IN KA 50 A
40 A
Ip
3000 10 4
3
2.
2000 35 A
=
32 A
Im
25 A
10 3 20 A
16 A
500 10 A
300 6A
200 4A
10 3
10 2
50
30
20
10
4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 315 355 400 450 500 630 800 10 2
(400V) 10 10 2 10 3 10 4 10 5 10 6
200 A
250 A
355 A
20 A
32 A
40 A
63 A
400 A
125 A
160 A
224 A
315 A
500 A
10 A
16 A
25 A
35 A
50 A
80 A
(400 V)
800 A
4A
6A
10 2
10
MELTING TIME
10 -1
10 -2
10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A
GPEU28
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM 500V, 690V
aM Curves Set
NH-fuses, 690VAC aM
Total Clearing I2t Current Limitation Curves
10 7
5000000
3000000
10 6
2000000
10 6
500000 500 A
450 A
300000 400 A
355 A
200000 315 A
10 5 250 A
224 A
10 5 200 A
160 A
50000 125 A
100 A
30000 80 A
20000 63 A
50 A
40 A
10 4 10 4
PEAK LET-THRU IN KA
35 A
32 A
5000 25 A
Ip
20 A
3
3000
2.
16 A
=
2000 10 A
Im
6A
10 3 4A
10 3
500
300
200
10 2
50 10 2
30 10 10 2 10 3 10 4 10 5 10 6
20
200 A
250 A
355 A
20 A
32 A
40 A
63 A
400 A
125 A
160 A
224 A
315 A
500 A
10 A
16 A
25 A
35 A
50 A
80 A
4A
6A
10 2
10
MELTING TIME
10 -1
10 -2
10 10 2 10 3 10 4 10 5
PROSPECTIVE CURRENT IP IN A
GPEU29
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
400V gTr
GPEU30
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
400V gTr
gTr Curves Set
RATED CURRENT IN A
MELTING TIME
PROSPECTIVE CURRENT IP IN A
APPARENT POWER TRANSFORMER IN KVA
PEAK LET-THRU IN kA
GPEU31
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG/aM Mechanics for ceramic Body
NH Fuses-links
Rated current
Size a1 a2 a3 a4 b c1 e1 e2 e4 h
IN(A)
Standard 400V and 500V gG with non-isolated gripping lugs
size 000 2 – 100A 79 52 45,5 49,5 15 35 40,5 20,8 6 52,5
size 00 125/160A 79 52,8 45 50 15 35 47,5 29,5 6 59,5
size 0 2 – 160A (500V) 125 66,8 61 66 15 35 47,5 29,5 6 59,5
size 116 – 100A (500V), 16 – 125A (400V) 135 70,8 63 68 15 40 47,5 29,5 6 64,5
size 1125 – 355A (500V),160 – 250A (400V) 135 70,8 63 68 20 40 52,5 39,5 6 64,5
size 2 16 – 250A 150 72,3 63 68 20 48 52,5 39,5 6 72,5
size 2 300 – 500A 150 72,3 63 68 26 48 60 51 6 72
size 3 250 – 400A 150 72,3 63 68 26 60 60 51 6 83,5
size 3 425 – 800A 150 72,3 63 68 33 60 74 70 6 86
size 4 400 – 1250A 200 85 62 68 49 86 108 90 8 117,5
size 4a 500 – 1250A 200 85 84 90 49 86 108 90 6 117,5
Standard 400V and 500V gG (SGL) with isolated gripping lugs
size 000 2 – 100A 78 53,4 45,7 49,7 15 35 40,5 20,8 6 52,5
size 00 125/160A 79 53,5 44,8 49 15 35 47,5 29,5 6 59,5
size 0 2 – 160A (500V) 125 67,5 62,5 66,7 15 35 47,5 29,5 6 59,5
size 116 – 100A (500V), 16 – 125A (400V) 135 71,5 62,8 67 15 40 47,5 29,5 6 64,5
size 1125 – 250A (500V), 160 – 250A (400V) 135 73,4 63 67,2 20 40 52,5 39,5 6 64,5
size 2 16 – 250A 150 73,4 63 67,2 20 48 52,5 39,5 6 72,5
GPEU32
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG/aM Mechanics for
ceramic Body
NH Fuses-links
Rated current
Size a1 a2 a3 a4 b c1 e1 e2 e4 h
IN(A)
GPEU33 07/05
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
Microswitch indication system for
NH-fuses size 000 to 3 with non-isolated gripping lugs
25 61
7 3
33
45
60,5
15,5
Fig.1 Fig.2
GPEU34
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3
GPEU36 07/05
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3
gG 500 - 690VAC
MELTING TIME - CURRENT DATA – 6-800 AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
Striker
PEAK LET-THRU CURRENT DATA – 6-800 AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
BEFORE AFTER
GPEU37
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3
gG 500 - 690VAC
32 3.7 W
35 4.0 W
40 4.5 W
50 5.2 W
63 6.2 W
80 7.5 W 6.9 W
100 8.5 W 8.1 W
125 10.7 W 9.6 W 9.5 W
160 13.5 W 11.9 W 11.5 W
200 15.0 W 14.9 W 14.5 W
224 16.7 W 16.0 W
250 18.7 W 17.5 W
315 25.0 W 23.0 W 23 W
355 28.0 W 25.0 W 25 W
400 29.0 W 29 W
425 34.0 W 34 W
500 39.0 W 39 W
630 47 W
800 67 W
GPEU38
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Ceramic body with French striker
gG 690V Size 0 to 3
gG 500 - 690VAC
_ _ _ 660V
_ _ _ 500V Operating I2t
_ _ _ 380V
_ _ _ Pre-arcing I2t
GPEU39
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Ceramic body with French striker
aM 690V Size 0 to 3
Pack. : 3 pieces
M216188
Dimensions
0 1 2 3
A 124.5 134.5 150 150
B 66 67 67 67
C 39 40 56 69
D 49 55 62.5 76
E 14.5 16 19 24
F 15.5 15.5 15.5 15.5
G 14 14.5 14.5 14.5
H 15 20 26 32
I 6 6 6 6
J 14 14 15 16
K 10 10 10 10
L 59 65 72.5 86
M 60 61 61 61
N 3 3 3 3
O 41.5 45 - -
P 47 52 60 60
GPEU40
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Ceramic body with French striker
aM 690V Size 0 to 3
aM 500 - 690VAC
MELTING TIME - CURRENT DATA – 32-630 AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
GPEU41
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Ceramic body with French striker
aM 690V Size 0 to 3
aM 500 - 690VAC
32 2.4 W
40 2.8 W
50 3.6 W
63 4.6 W
80 6.0 W 6.0 W
100 7.5 W 7.5 W
125 9.5 W 9.9 W
160 12.0 W 12.7 W 12.7 W
200 16.4 W 16.4 W
224 18.7 W 18.7 W
250 21.5 W 21.5 W
315 29.0 W 25.0 W
355 32.0 W 29.0 W
400 34.0 W 34.0 W
425 38.5 W
500 45.0 W
630 60.0 W
_ _ _ 660V
_ _ _ 500V Operating I2t
_ _ _ 380V
_ _ _ Pre-arcing I2t
I2T (AMPERE2 SECONDS)
GPEU42
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 00
from 10 to 160 A
30
52
2.5 10
44
6
59
15 46
14.5
78 Weight: 150 g
Main Characteristics
GPEU44
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 00
from 10 to 160 A
Total Clearing I2t Current Limitation Curves
I2t (A2S)
106 Ic (kA)
100
105
104 160
125
100
10 80
63
103 50
40
32 35
25
20
102
16
10
101 1
10 16 20 25 32 35 40 50 63 80100125160 1 10 100
Rating (A)
Ip (kA)
b: total clearing I2t @ 500 V
Ic = Peak let-through current
10 16 25 35 50 63 80 100 160
104
t (s) Breaking
t (s) = Pre-arcing duration
capacity
100 kA
103
102
10
10-1
Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT
GPEU45
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 0 and 1
from 40 to 250 A
D1 D1
D D
D2 G M
G M
B B
F
e e
A C A C
H K H
N N
L J L J
GPEU46
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 0 and 1
from 40 to 250 A
Total Clearing I2t Current Limitation Curves
I2t (A2S) Ic (kA)
107
100
106
250
200
105 160
125
100
10
80
104 63
50
40
103
102
1
40 50 63 80 100 125 160 200 250
1 10 100
Rating (A)
b: total clearing I t @ 500 V
2 Ip (kA)
Ic = Peak let-through current
103
102
10
10-1
Ip (A) = R.M.S.
AVAILABLE
10 -2
10 100 1 000 10 000 Ip (A) FAULT CURRENT
GPEU47
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 2 and 3
D1 D1
D D2 D
G M G M
B B
F
e e
A C A C
H K H
N N
L J L J
Accessories : Neutral link BS2 Reference Number J097712 - BS3 Reference Number K097713
Pull-out handle - PMP Reference Number P215592
GPEU48
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 2 and 3
108
Ic (kA)
100
107
630
500
400
315
250
10 6
200
160
125
10
105
104
103
125 160 200 250 315 400 500 630 1
102
10
10-1
Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT
GPEU49
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 4
D1
D D2
G M
B
F
e With trip-indicator
A C
H K
N
150 J
L
D D1
G M
B
e
H
A C With blown fuse indicator
N
150 J
L
GPEU50
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 4
106
10
105
104
1
103
1 10 100
630 800 1000 1250 Rating (A)
Ip (kA)
2
b: total clearing I t @ 500 V Ic = Peak let-through current
Ip = Available fault current
a: pre-arcing I2t
630 1000
104
t (s) Breaking
t (s) = Pre-arcing duration capacity
100 kA
103
102
10
10-1
Ip (A) = R.M.S.
10-2 10 100 1 000 10 000 Ip (A)
AVAILABLE
FAULT CURRENT
GPEU51
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 00
from 16 to 125 A
30
52
2.5 10
44
6
59
15 Weight: 150 g
46
14.5
78
GPEU52
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 00
from 16 to 125 A
Total Clearing I2t Current Limitation Curves
I2t (A2S)
107 Ic (kA)
106 100
105
125
100
104 80
10 63
50
40
32
103 25
20
16
35
102
16 20 25 32 35 40 50 63 80 100 125
Rating (A)
10
10-1
from 40 to 315 A
Accessories: Neutral link BS0 Reference Number G097710 - BS1 Reference Number H097711
Pull-out handle - PMP Reference Number P215592
GPEU54
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 0 and 1
from 40 to 315 A
Total Clearing I2t Current Limitation Curves
I2t (A2S)
107 Ic (kA)
106 100
105 315
250
200
160
125
100
104 80
10 63
50
40
103
102
40 50 63 80 100 125 160 200 250 315
Rating (A)
2
b: total clearing I t @ 500 V 1 10 100
Ic = Peak let-through current Ip (kA)
a: pre-arcing I t 2
Ip = Available fault current
10
10-1
Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT
GPEU55
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 2 and 3
A C A C
H H
K
N N
L L J
J
Accessories: Neutral link BS2 Reference Number J097712 - BS3 Reference Number K097713
Pull-out handle - PMP Reference Number P215592
GPEU56
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 2 and 3
107 100
630
500
106 400
315
250
200
160
125
105
10
104
103
125 160 200 250 315 400 500 630
Rating (A)
2
b: total clearing I t @ 500 V 1 10 100
Ic = Peak let-through current Ip (kA)
a: pre-arcing I2t Ip = Available fault current
10
10-1
Ip (A) = R.M.S.
10-2 AVAILABLE
10 100 1 000 10 000 Ip (A) FAULT CURRENT
GPEU57
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 4
D D1
D1
D G M
D2 B
G M
B
F e
e A C
H
A C
H K
N
N 150 J
150 J L
L
GPEU58
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 4
106
105
10
104
103
630 800 1000 1250
Rating (A)
2
b: total clearing I t @ 500 V 1 10 100
Ic = Peak let-through current Ip (kA)
103 Breaking
capacity
100 kA
800 1250
102 630 1000
10
10-1
Ip (A) = R.M.S.
AVAILABLE
10-2
10 100 1 000 10 000 Ip (A) FAULT CURRENT
GPEU59
General Purpose Fuses IEC
General Purpose Fuses IEC
Masterfuse
gG 690V
Highlights
• High ratings 1250 to 2500 A
• gG operating fuse for 690V AC Nominal
• Conformity with IEC 60269 1 and 2
• Dimensional according section V on IEC 60269-2-1
• Breaking capacity 690V 160 KA – 50Hz
Applications
• General protection on Low Voltage Panel
• High power protection on 690V AC Voltage
• Back up for circuit breaker
• Blade fuses for power bus bar assembly
• Disconnector, Switch and/or Circuit Breaker isolation
Main characteristics
Rated Size Melting I2t Total I2t at 690V Power losses Breaking Ref.Number Catalog
current (ø in mm) (KA2s) (KA2s) at In (W) capacity number
1250 A 76 1590 8200 78 E 302753 MF76GG69V1250
1600 A 89 2500 13000 111 160 KA F 302754 MF89GG69V1600
2000 A 114 4800 25000 128 at 690V AC G 302755 MF114GG69V2000
2500 A 127 7000 36000 175 H 302756 MF127GG69V2500
Pack: 1piece
For ratings 3200A(Ø 146mm) – 4000A (Ø 160mm) – 4800 A (Ø 181mm) consults us
Electrical characteristics
I2t vs rated current and applied voltage characteristics
Prearcing and Peak let-thru current characteristics
clearing I2t(kA2s)
Maximum peak let-thru current Im (A)
2500 A
500000
Im=2.3Ip
2000 A
10000
5000
1600 A
1000
1250 A
2500
1250
2000
1600
GPEU60
General Purpose Fuses IEC
General Purpose Fuses IEC
Masterfuse
gG 690V
1000
700
500
1600 A
300
200
100
70
50
30
2000 A
20
10
7
5
3
2
2500 A
1
0.7
0.5
0.3
0.2
0.1
0.07
0.05
0.03
0.02
0.01
0.007
0.005
0.003
0.002
0.001
0.0007
0.0005
0.0003
0.0002
100000
200000
300000
500000
700000
10000
20000
30000
50000
70000
1e+ 06
2000
3000
5000
7000
GPEU61
General Purpose Fuses IEC
General Purpose Fuses IEC
Masterfuse
gG 690V
Dimensions
690 VgG 1250 A
GPEU62
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
IEC 269-3-1
DIN VDE 0636 Part 41
DIN VDE 0636 Part 301
Germany
Austria
D Denmark
Norway
N
GPEU64
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
GPEU65
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
INNOZED Neozed-Sicherungssockel
für Schnappbefestigung mit Abdeckung, 400VAC
INNOZED Neozed-Sicherungssockel
für Schnappbefestigung ohne Abdeckung, 400VAC
Bemessungs- Referenz Gewich Artikel
Größe strom in A Polzahl Nummer in g/Stück VE -Gruppe
D01 16 1 2724.1 70 12 42
D01 16 3 2734.1 210 4 42
D02 63 1 2725.1 72 12 42
D02 63 3 2735.1 217 4 42
GPEU66
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
NEOZED Screw cap - plastic
400 VAC / 440 VAC
GPEU67
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
NEOZED Insulating covers
single pole for ceramic fuse bases:
GPEU68
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
LINOZED Fuse bases
For snap-on fastening, 400VAC
GPEU69
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
GPEU70
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
NEOZED - Spacer
GPEU71
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
INNOZED
Der Neozed-Sicherungssockel mit innovativer Anschlusstechnik
Kunststoffe
mit höchsten Ansprüchen
• Sockelabdeckung aus flammwidrigem Polyamid
• Gehäuse aus glasfasergefülltem, duroplastis-
chem Polyester
• Hohe mechanische und thermische
Belastbarkeit
Innovative Anschlusstechnik
durch zweigeteilte Rahmenklemme.
• Kontaktierung der Einspeiseleitungen
• Anschluss der Verdrahtungsschienen
• Leitungen leichter einführbar Klemmstellen
der Leitungen visuell kontrollierbar
• Einsparung von Montagezeit
• Zusätzliche Betriebssicherheit und Flexibilität
Verdrahtungsschienen
Folgende Schienen sind einsetzbar:
- 3-phasig 16 mm2 – Ref.Nr. 2963.003
- 1-phasig 16 mm2 – Ref.Nr. 2963.
Flexible Klemmentechnik
Unterschiedliche Leiterquerschnitte und Leiterarten sind problemlos klemmbar, sowohl eingangs- als
auch abgangsseitig
• Flexibilität bei der Verdrahtung
• Erhöhung der Betriebssicherheit bei der Klemmung unterschiedlicher Leiter
GPEU72
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
Variabler Berührungsschutz
Einspeisung Abgang
V O R T E I L E des INNOZED
• Schnellere Montage
• Höhere Betriebssicherheit
• Klemmstelle sichtbar vor Verdrahtungsschiene
GPEU73
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
Vorschriften
IEC 60269-3-1
DIN VDE 0636 Teil 301
Baugrößen
Drei Baugrößen stehen zur Verfügung:
• Sicherungssockel D01
- Gewinde E 14
- Nennstrom 16A
- für Sicherungseinsätze 2 ... 16A
• Sicherungssockel D02
- Gewinde E 18
- Nennstrom 63A
- für Sicherungseinsätze 20 ... 63A
- mit Spezialpasshülsen auch verwendbar für Sicherungseinsätze 2 ... 16A
• Sicherungssockel D03
- Gewinde M 30 x 2
- Nennstrom 100A
- für Sicherungseinsätze 80 und 100A
Betriebsklassen
Die Betriebsklasse ist durch zwei Buchstaben gekennzeichnet.
Der erste Buchstabe gibt die Funktionsklasse, der zweite das zu
schützende Objekt an. Unser Lieferprogramm umfasst NEOZEDSicherungseinsätze
nach DIN VDE 0636 für folgende Betriebsklassen:
• gG: Ganzbereichskabel- und Leitungsschutz
• gR: Ganzbereichs-Halbleiterschutz
• aM: Teilbereichs-Schaltgeräteschutz (Motorschutz)
Schaltvermögen
NEOZED-Sicherungseinsätze schalten im gesamten Bereich der
Zeit-Stromkennlinie auch im Bereich der kritischen Ströme zuverlässig
ab.
Das Schaltvermögen ist 50kA.
Klemmrausführunger der keramiksockel
GPEU74
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
Ausschreibungstexte
GPEU75
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
2 – 100A, 400 (440)VAC,250VDC Leitungsschutzsicherungen gG
Eigenverbrauch in W
Nennstrom in A Größtwerte * Messwerte
2 2,5/2,5 1,5
4 1,8 1,5
6 1,8 1,3
10 2,0 1,8
16 2,5/2,2 2,1
20 3,0/2,5 2,3
25 3,5/3,0 2,6
35 4,0 2,9
50 5,0 3,5
63 5,5 4,2
80 6,5 4,9
100 7,0 5,8
Selektivität
NEOZED-Sicherungseinsätze sind im Verhältnis 1:1,6 der Nennströme
mit allen Sicherungseinsätzen selektiv, die folgenden
Anforderungen entsprechen:
Betriebsklasse gG entspr. lEC 60269-2-1, 60269-3-1
Betriebsklasse gG entspr. DIN VDE 0636 Teil 201, 301
NEOZED-Sicherungseinsätze sind untereinander und bei gemischtem
Einsatz mit Sicherungseinsätzen anderer Lindner-Systeme im
Verhältnis 1:1,25 selektiv, d.h. von Nennstromstufe zu Nennstromstufe.
Beide Sicherungen sollten jedoch bei so enger Staffelung
gleichen Umgebungseinflüssen ausgesetzt sein.
NEOZED-Sicherungseinsätze 32A
Zur Absicherung von 32A CEE Steckdosen sind entsprechend der
neuen DIN VDE 0623 Teil 1/06.93 (DIN EN 60309-1) Sicherungseinsätze
mit maximal 32A Bemessungsstrom vorgeschrieben.
Bisher durften 32A CEE Steckdosen ausnahmsweise mit 35A abgesichert
werden.
Diese Ausnahmeregelung darf zukünftig für Neuanlagen nicht
mehr angewendet werden, da die entsprechende Vorschrift DIN
VDE 0623/03.77 nicht mehr gültig ist. Es gilt jedoch eine Übergangsfrist
bis 2003-02-01.
Passorgane: Es sind die Hülsenpasseinsätze 35A zu verwenden.
GPEU76
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
Direkte Zuordnung bei Schutz von Kabel und Leitungen bei Überlast
Bei der Zuordnung von Überstrom-Schutzorganen zum Kabel- und Leitungsschutz sind nach DIN VDE
0100 Teil 430 folgende Bedingungen zu erfüllen:
lB ≤ IN ≤ lZ (Nennstromregel) (1)
I2 ≤ 1,45 x lN (Auslöseregel) (2)
IB - Betriebsstrom des Stromkreises
IN - Nennstrom der ausgewählten Überstromeinrichtung
IZ - zulässige Strombelastbarkeit des Kabels
I2 - Auslösestrom der Schutzeinrichtung
DIN VDE 0636 Teil 301 wurde durch eine Zusatzprüfung "Abschalten mit l2 = 1,45 x IN in der konven-
tionellen Prüfdauer" ergänzt.
NEOZED-Sicherungseinsätze gG erfüllen die Bedingungen dieser Zusatzprüfung. Damit ist eine direkte
Zuordnung des Nennstromes des Sicherungseinsatzes zur Belastbarkeit der Leitung oder des Kabels
möglich.
GPEU77
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
Vorschriften
IEC 60269-3-1
DIN VDE 0636 Teil 301
20/25/35A 400 (440)VAC, 250VDC
Schaltgeräteschutz-Sicherungen aM
Anwendung
NEOZED-Sicherungseinsätze der Betriebsklasse aM gewähren
Motoren und Schaltgeräten den besten Schutz im Fall eines Kurzschlusses.
Im Vergleich zu alternativen Schutzorganen haben Sicherungseinsätze der Betriebsklasse aM entschei-
dende Vorteile:
Besonders träges Abschaltverhalten im Überlastbereich verhindert
unerwünschtes, vorzeitiges Auslösen des Schutzorganes; sehr flinkes Abschalten im Kurzschlussfall
sorgt für höchste Kurzschlussstrombegrenzung und verhindert damit das Abbrennen und
Verschweißen der Kontakte des Schaltgerätes.
Eine um bis zu 50% geringere Verlustleistung bietet entscheidende Vorteile bei häufigem Lastwechsel
und Reversierbetrieb und spart außerdem noch Energiekosten.
GPEU78
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
Aufbau
Die NEOZED Sicherunsein stätze der Betnebklasse aM bestehen
aus den gleichen Bauteilen wie die Standard-Typen der Betriebsklasse gG:
Keramikhülse, Kontaktkappen, Kennmelder mit Kennmelderdraht,
Löschsand. Nur der Schmelzleiter, der die Kennlinie und das Abschmelzverhalten einer Sicherung aus-
macht, ist ein anderer. Zur Unterscheidung zu anderen Betriebsklassen sind die aM-Sicherungseinsätze
in grüner Farbe beschriftet.
ZEIT-STROM-KENNLINIEN
DURCHLASSSTROM-KENNLINIEN
GPEU79
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
INNOZED-Sicherungssockel
NEOZED-Sicherungssockel
Referenz. Catalog a b c c1 d d1 eØ f g h k
Nummer Number
1720.1 26 36 – 39,5 20 22 25,5 64 34Ø – 50,5
1721.2/.4 26 36 – 39,5 20 22 25,5 64 34Ø – 57,5
1722.4 44 50 – 44 32 32 40 74 52Ø – 86
1730.1 81 36 – 39,5 74 22 25,5 64 – – 50,5
1731.2/.4 81 36 – 39,5 74 22 25,5 64 – – 57,5
1730.12 81 36 55 39,5 74 22 25,5 64 45 71 50,5
1731.22/.42 81 36 55 39,5 74 22 25,5 64 45 71 57,5
1720.15 26 36 – 41,5 20 22 25,5 66 34Ø – 50,5
1721.25/.45 26 36 – 41,5 20 22 25,5 66 34Ø – 57,5
1722.45 44 50 – 46 32 32 40 76 52Ø – 86
1720.17 27 36 57 41,5 20 22 25,5 66 45 71 50,5
1721.27/.47 27 36 57 41,5 20 22 25,5 66 45 71 57,5
1722.47 44 50 54,5 46 32 32 40 76 45 71 86
1730.15 81 36 – 41,5 74 22 25,5 66 – – 50,5
1731.25/.45 81 36 – 41,5 74 22 25,5 66 – – 57,5
1730.17 81 36 57 41,5 74 22 25,5 66 45 71 50,5
1731.27/.47 81 36 57 41,5 74 22 25,5 66 45 71 57,5
Referenz. Catalog a b c d d1 eØ f
Nummer Number
1720.13 31 70 44,5 20 22 25,5 64
1721.23/1721.43 31 70 44,5 20 22 25,5 64
1722.43 50 105 48 32 32 40 74
1720.18 31 70 46,5 20 22 25,5 66
1721.28/1721.48 31 70 46,5 20 22 25,5 66
1722.48 50 105 50 32 32 40 76
GPEU80
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
NEOZED NEOZED
Schraubkappen Hülsenpasseinsätze
Referenz. Catalog a b
Nummer Number
1714. 29,5 23 Referenz. Catalog a b
1715. 29,5 23 Nummer Number
1710. 31 25 1705. 10 12
1711. 31 25 1706. 10 16
1712. 37 40 1707. 10 27
NEOZED NEOZED
Abdeckungen Sicherungseinsätze
LINOZED-Sicherungssockel
GPEU81
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D0-type
NEOZED
D0 Fuse System
NEOZED-Reiter-Sicherungssockel
mit Schellenbefestigung, 400VAC
NEOZED-Reiter-Sicherungssockel
mit Schnappbefestigung, 400VAC
NEOZED-Reihen-Sicherungssockel
Referenz. Catalog a b c c1 d d1 eØ f g h i k
Nummer Number
1737.12 80,5 30 55 39,5 22 20 25,5 64 45 71 88,5 36,5
1738.22 80,5 30 55 39,5 22 20 25,5 64 45 71 91,5 44,5
1737.17 80,5 30 57 41,5 22 20 25,5 66 45 71 88,5 36,5
1737.27 80,5 30 57 41,5 22 20 25,5 66 45 71 91,5 44,5
GPEU82
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED
D Fuse System
GPEU84
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED
D Fuse System
D Fuse bases
for snap-on fastening 500 VAC / 690 VAC
Rated in Max. cross Previous Reference Catalog
Size Current (A) Pole sect. mm2 Reference Number Pack Number
without shock-proof protection cover
DII 25 1* 6 00685.100000 K207055 15
DIII 63 4* 16 00686.400000 V215597 15
with shock-proof protection cover
DII 25 1 6 00685.110000 D211511 10
DIII 63 4 16 00686.410000 C216110 10
* Terminal type see following pages
D Fuse bases
for screw fixing 500 VAC / 690 VAC
Rated in Max. cross Previous Reference Catalog
Size Current (A) Pole sect. mm2 Reference Number Pack Number
without shock-proof protection cover
DII 25 1* 6 00081.100000 K218670 15
DIII 63 4* 16 00072.400000 H212021 15
with shock-proof protection cover
DII 25 1* 6 00081.110000 Z219189 10
DIII 63 4* 16 00072.410000 A212543 10
* Terminal type see following pages
D Fuse-links
2 - 200A fast acting (CEE-16 standard), 500 VAC
GPEU85
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED
D Fuse System
D Fuse-links
2 -200 A gG, 500 VAC
Rated in Gauge Previous Reference Catalog
Size Current (A) Color Reference Number Pack Number
NDZ 2 pink 00594.002700 W212539 25
NDZ 4 brown 00594.004700 G213055 25
NDZ 6 green 00594.006700 C213557 25
NDZ 10 red 00594.010700 B214062 25
NDZ 16 grey 00594.016700 J214575 25
NDZ 20 blue 00594.020700 Q215087 25
NDZ 25 yellow 00594.025700 Q215593 25
D II 2 pink 00597.002700 Z219718 25
D II 4 brown 00597.004700 G222163 25
D II 6 green 00597.006700 B222917 25
D II 10/6 f1 red 00597.610700 D213558 25
D II 10 red 00597.010700 K200707 25
D II 16 grey 00597.016700 K201765 25
D II 20 blue 00597.020700 A211508 25
D II 25 yellow 00597.025700 X212540 25
1 with base contact stud for 6 A (without VDE test mark)
D III 35 black 00598.035700 C214063 25
D III 50 white 00598.050700 K214576 25
D III 63 copper 00598.063700 R215088 25
D IV 80 silver 00595.080700 V216609 10
D IV 100 red 00595.100700 M217637 10
DV 125 yellow 00596.125700 V218150 10
DV 160 copper 00596.160700 G218667 10
DV 200 blue 00596.200700 W219186 10
Characteristics see following pages
D Fuse system 690 VAC
In this design, the fuse base and gauge piece correspond to the 500 V standard for D III (E33). The
extended fuse links D III and a special extended screw cap serve to complement the present system.
D-type 690 V fuses are only available in size III.
GPEU86
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED
D Fuse System
D Screw caps
Porcelain and Plastic, 500 VAC
Rated in Gauge Previous Reference Catalog
Size Current (A) Color Reference Number Pack Number
Porcelain with testing hole
DII 25 E 27 00690.000200 E218619 20
DIII 63 E 33 00691.000200 B213004 20
Porcelain without testing hole
NDZ 25 E 16 00589.000000 Z216613 50
DII 25 E 27 00690.000000 Z218108 20
DIII 63 E 33 00691.000000 F211973 20
DIV 100 R11/4 00592.000000 Y216060 10
Plastic with testing hole
DII 25 E 27 02071.000000 L201720 20
DII 63 E 33 02072.000000 E214019 20
D Gauge piece
Rated in Gauge Previous Reference Catalog
Size Current (A) Color Reference Number Pack Number
NDZ 2 pink 01655.002000 B212544 50
NDZ 4 brown 01655.004000 M213060 50
NDZ 6 green 01655.006000 H213562 50
NDZ 10 red 01655.010000 G214067 50
NDZ 16 grey 01655.016000 P214580 50
GPEU87
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED
Tiple pole
D II 00625.700000 N213061 8
D II 00626.700000 J213563 8
D Adapter fittings
for DII-fuses links in D III-bases
D II/ D III 00581.000000 C212545 50
GPEU88
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED
D Fuse System
RATED CURRENT In IN A
2 Ip 2 Ip 2
103 20
VIRTUAL PRE-ARCING TIME T IN S
ID IN KA
100
80
RATED CURRENT IN IN A
65
10 50
102 35
FORWARD CURRENT
25
20
4 16
101
10
6
2
0
10 4
1
2
10-1
0,4
10-2 0,2
0,1
10-3
2 4 101 2 4 102 2 4 103 2 4 104 0,1 0,2 0,4 1 2 4 10 20 100
PROSPECTIVE CURRENT Ip IN A SHORT CIRCUIT CURRENT I IN KA
P
Time-current characteristics of D Fuses 2…100 A gL-gG Forward current characteristics of DIAZED fuses 2…100 A gL-gG
Terminal types
0 1 2 4 6
Clamp terminal Twin Screw terminal Twin Screw terminal Twin Screw terminal
Screw terminal Clamp terminal Twin Screw terminal Screw terminal Clamp terminal
Dimensions
GPEU89
General Purpose IEC Fuses
General Purpose IEC Fuses
DIN Fuses
D-type
DIAZED
Catalog Sizes in mm
number a b c d d1 eX f
99 40 70 53 32 – 38 82
199 40 70 54 20 – 38 83
200 50 90 54 20 – 48 83
Catalog Sizes in mm
number a b c c1 d d1 eX f
625 90 81 54.5 46 80 35 37 81
626 109 100 54.5 46 95 49.5 46.5 81
625* 107 107 51 – – – – –
626* 127 130 51 – – – – –
* with cover cap
Catalog Sizes in mm
number a b c c1 d d1 eX f X h i k
685/81 38 40 60 46 29 27 38 82 43 – – 60
686/72 46 44 57 48 35 33,5 48 84 52 – – 73
Catalog Sizes in mm
number a b c d e f g g1
120 42 52 60 44 38 85 12 37
121 52 62 63 54 48 88 13 38
GPEU90
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
Ratings
• A type • B type • C type
A1 : from 2A to 32A B1 : from 32A to 100A C1 : from 355A to 400A
A2 : from 2A to 32A B2 : from 125A to 200A C2 : from 450A to 630A
A3 : from 40A to 100A B3 : from 250A to 315A C3 : from 670A to 800A
A4 : from 32A to 100A B4 : from 355A to 400A
Overrating till 200A
A and B types - gM curve Applications
• Motor protection
Features /Benefits
• Inductive load protections
• Fast curve gM • Transient overloads
• Very current limiting • Electrical equipment using motors protection
• Voltage 415VAC Capacitor
• High breaking capacity : 80kA @ 415VAC tested
• A type : bracket connection, Approvals
• B type : blade with single central fixing hole • Asta 20 Certified
connection
Ratings
• A type • B type
A1: 20A B1: 100A
A2: 30A B2: 200A
A3: 63A B3: 315A
A4: 100A and 200A
GPEU92
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
A type
Type Rating Ref. no Designation Pack. Catalog
Number
A1 2 N226263 2A1 10
A1 4 P226264 4A1 10
A1 6 Q226265 6A1 10
A1 10 R226266 10A1 10
A1 16 S226267 16A1 10
A1 20 T226268 20A1 10
A1 25 V226269 25A1 10
A1 32 W226270 32A1 10
A2 2 Z226273 2A2 10
A2 4 A226274 4A2 10
A2 6 B226275 6A2 10
A2 10 C226276 10A2 10
A2 16 D226277 16A2 10
A2 20 V227833 20A2 10
A2 25 E226278 25A2 10
A2 32 F226279 32A2 10
A3 40 L226284 40A3 10
A3 50 M226285 50A3 10 C type
A3 63 N226286 63A3 10 Catalog
Type Rating Ref. no Designation Pack. Number
A3 80 P226287 80A3 10
A3 100 Q226288 100A3 10 C1 355 G226326 355C1 1
A4 32 T226291 32A4 5 C1 400 H226327 400C1 1
A4 40 V226292 40A4 5 C2 450 J226328 450C2 1
A4 50 W226293 50A4 5 C2 500 K226329 500C2 1
A4 63 X226294 63A4 5 C2 560 L226330 560C2 1
A4 80 Y226295 80A4 5 C2 630 M226331 630C2 1
A4 100 Z226296 100A4 5 C3 670 N226332 670C3 1
A4X* 125 D226300 125A4X 5 C3 710 P226333 710C3 1
A4X* 160 E226301 160A4X 5 C3 750 Q226334 750C3 1
A4X* 200 F226302 200A4X 5 C3 800 R226335 800C3 1
B type
Type Rating Ref. no Designation Pack. Catalog
Number
B1X* 32 J226305 32B1X 10
B1X* 40 K226306 40B1X 10
B1X* 50 L226307 50B1X 10
B1X* 63 M226308 63B1X 10
B1 80 N226309 80B1 5
B1 100 P226310 100B1 5
B2 125 T226314 125B2 5
B2 160 V226315 160B2 5
B2 200 W226316 200B2 5
B3 250 Z226319 250B3 1
B3 315 A226320 315B3 1
B3X* 250 C226322 250B3X 1
B3X* 315 D226323 315B3X 1
B4 355 E226324 355B4 1
B4 400 F226325 400B4 1
GPEU93
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
B type
Type Rating Ref. no Designation Pack. Catalog
Number
B1 100M125 Q226311 100M125B1 5
B1 100M160 R226312 100M160B1 5
B1 100M200 S226313 100M200B1 5
B2 200M250 X226317 200M250B2 1
B2 200M315 Y226318 200M315B2 1
B3 315M400 B226321 315M400B3 1
Dimensions
A type
Ref. Dimensions (mm & In)
Current ratings (A)
BS 88 A max B max D max E max F nom G nom H nom J nom K max
mm 33 12,7 56 9,5 0,8 44,25 4,8 open 14,3
A1 2, 4, 6, 10, 16, 20, 25*, 32*, 20M25, 20M32 In 1-1/4 1/2 2-3/16 3/8 1/32 1-3/4 3/16 hole 9/16
mm 49 22 86 9 1,2 73 5,5 8 24
A2 2, 4, 6, 10, 16, 20, 25, 32, 32M40, 32M50, 32M63 In 1-15/16 7/8 3-3/8 11/32 3/64 2-7/8 7/32 5/16 15/16
mm 49 22 89 13 1,2 73 5,5 open 24
A3 40, 50, 63 In 1-15/16 7/8 3-1/2 1/2 3/64 2-7/8 7/32 hole 15/16
mm 49 26 89 13 1,2 73 5,5 open 28
A3 80*, 100*, 63M80, 63M100 In 1-15/16 1-1/32 3-1/2 1/2 3/64 2-7/8 7/32 hole 1-3/32
mm 51 22 110 20 2,4 94 8,7 11 25,4
A4 32, 40, 50, 63 In 2 7/8 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1
mm 51 26 110 20 2,4 94 8,7 11 29
A4 80, 100 In 2 1-1/32 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1-1/8
mm 51 35 110 20 2,4 94 8,7 11 38
A4X 125, 160, 200, 100M125, 100M160, 100M200 In 2 1-3/8 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1-1/2
mm 51 41 110 20 2,4 94 8,7 11 45
A4X 200M250*, 200M315* In 2 1-5/8 4-5/16 3/4 3/32 3-11/16 11/32 7/16 1-3/4
* Current ratings additional to BS88.
GPEU94
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
Dimensions
B type
Ref. Current ratings (A) Dimensions (mm & In)
BS 88 A max B max D max E max F nom G nom H nom I nom
mm 45 22 137 15 1,4 111 8,7 14
B1X 32, 40, 50, 63 in 1-3/4 7/8 5-3/8 9/16 3/64 4-3/8 11/32 9/16
mm 45 26 137 20 3,2 111 8,7 14
B1 80, 100 in 1-3/4 1/32 5-3/8 3/4 1/8 4-3/8 11/32 9/16
mm 45 35 137 20 3,2 111 8,7 14
B1 100M125, 100M160, 100M200 in 1-3/4 1-3/8 5-3/8 3/4 1/8 4-3/8 11/32 9/16
mm 45 35 137 20 3,2 111 8,7 14
B2 125, 160, 200 in 1-3/4 1-3/8 5-3/8 3/4 1/8 4-3/8 11/32 9/16
mm 45 41 137 26 3,2 111 8,7 14
B2 200M250, 200M315 in 1-3/4 1-5/8 5-3/8 1-1/32 1/8 4-3/8 11/32 9/16
mm 45 41 137 26 3,2 111 8,7 14
B3 250, 315 in 1-3/4 1-5/8 5-3/8 1-1/32 1/8 4-3/8 11/32 9/16
mm 45 51 137 26 6,4 111 8,7 14
B3 315M400 in 1-3/4 2 5-3/8 1-1/32 1/4 4-3/8 11/32 9/16
mm 45 41 159 26 3,2 133 10,3 14
B3X 250, 315 in 1-3/4 1-5/8 6-1/4 1-1/32 1/8 5-1/4 13/32 9/16
mm 52 51 137 26 6,4 111 8,7 16
B4 355, 400 in 2-1/16 2 5-3/8 1-1/32 1/4 4-3/8 11/32 5/8
C type
Ref. Current ratings (A) Dimensions (mm & In)
BS 88 A max B max D max E max F nom G nom H nom J nom L nom
C1 355*, 400 mm 52 51 210 26 6,3 133 10,3 16 25,4
In 2-1/16 2 8-1/4 1-1/32 1/4 5-1/4 13/32 5/8 1
C2 450*, 500, 560*, 630 mm 54 61 210 26 7,8 133 10,3 16 25,4
In 2-1/8 2-3/8 8-1/4 1-1/32 5/16 5-1/4 13/32 5/8 1
C3 670*, 710, 750*, 800 mm 56 73 210 26 9,5 133 10,3 16 25,4
In 2-1/16 2 8-1/4 1-1/32 3/8 5-1/4 13/32 5/8 1
GPEU95
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
gG and gM fuse-link selection
Fuse-link selection for 3 phase 415 V AC induction motor circuit
Motor rating Direct-on-line start (7 x FLC for 10 sec) Assisted start (3,5 x FLC for 20 sec)
kW In Fuse-link rating (amperes) Fuse-link rating (amperes)
HP gG gM gG gM
0,75 1 2 6 - 4 -
1,1 1,5 2,5 10 - 6 -
1,5 2 3,5 10 - 6 -
2,2 3 5 16 - 10 -
3 4 6,5 20 - 16 -
4 5 8 25 20M25 16 -
5,5 7,5 11 32 20M32 20 -
7,5 10 14 40 32M40 25 20M25
10 13,5 19 50 32M50 32 20M32
11 15 21 50 32M50 32 -
15 20 28 63 32M63 40 32M40
18,5 25 35 80 63M80 50 -
22 30 41 100 63M100 50 -
26 35 48 100 63M100 63 -
30 40 55 125 100M125 80 63M80
33 45 62 160 100M160 80 63M80
37 50 69 160 100M160 100 -
45 60 83 200 100M200 100 -
53 70 97 200 100M200 125 100M125
55 75 100 200 100M200 125 100M125
60 80 110 250 200M250 160 -
67 90 120 250 200M250 160 -
75 100 135 250 200M250 160 -
90 120 160 315 200M315 200 -
93 125 170 355* 315M400* 200 -
110 150 200 400 315M400* 250 200M250
130 175 230 400 315M400* 315 -
150 200 260 450* 400M500* 315 -
160 215 280 500 400M500* 355* 315M400*
170 225 290 500 400M500* 355* 315M400*
180 250 320 560* - 400 -
200 270 350 630 - 400 -
220 300 380 670* - 450 400M500*
250 335 420 710* - 500 -
260 350 450 750* - 560* -
300 400 500 800 - 630 -
* Current ratings additional to BS88.
Maximum full load current starting capability
Direct-on-line start (7 x FLC for 10 sec) Assisted start (3,5 x FLC for 20 sec)
Fuse-link Maximum Fuse-link Maximum
rating (amperes) motor rating (amperes) motor
gG gM In gG gM In
2 - 0,6 2 - 1,3
4 - 1,3 4 - 2,4
6 - 2,3 6 - 4,3
10 - 4,1 10 - 6,4
16 - 6,0 16 - 11 This data is based upon normal starting
20 - 7,9 20 - 14 conditions and usual efficiency and
25 20M25 10 25 20M25 19
32 20M32 13 32 - 24
power factor.
40 32M40 18 40 32M40 31 Conditions such as long run-up times,
50 32M50 26 50 - 46 large numbers of start in succession,
63 32M63 30 63 - 51
80 63M80 40 80 - 69
high ambient temperature or abnormal
100 63M100 54 100 - 94 transients during start/delta switching
125 100M125 61 125 - 110 may necessitate adjustments to fuse-link
160 100M160 82 160 - 150
200 - 110 200 - 180
selection.
250 200M250 150 250 - 220
315 200M315 170 315 - 250
355* 315M400* 200 355* - 310
400 315M400* 240 400 - 340
450* 400M500* 280 450* 400M500* 380
500 400M500* 310 500 - 430
560* - 350 560* - 460
630 - 380 630 - 500
670* - 420 670* - 530
710* - 450 710* - 550
750* - 480 750* - 570
800 - 510 800 - 600
* Current ratings additional to BS88.
GPEU96
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
Time/current data
20000
4 hours
10000
gG
1000
rating (A)
Fuse-link
100
PRE-ARCING TIME (S)
10
0.1
0.005
1 10 100 1000 10000 100000
20000
4 hours
10000
gM
1000
rating (A)
Fuse-link
100
PRE-ARCING TIME (S)
10
0.1
0.005
1 10 100 1000 10000 100000
Curves from BS88 standard part 1 and 2 PROSPECTIVE CURRENT (R.M.S. SYMMETRICAL A)
(sections 2.1 and 2.2) of 1988.
Voltage rating : 415 V. Interrupting rating : 80 kA under 415 V.
* Current ratings additional to BS88.
GPEU97
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
I2t characteristics
107
106
105
103
102
10
Dissipated power
GPEU98
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes A,B,C
100
Peak let-through
current
10
0.1
0.1 1 10 100
* Current ratings additional to BS88
Nominal current derating by temperature
Fuse-link Current carrying capability (in amperes) at elevated temperatures - When the fuse-link is mounted in the open, the elevated
rating (A) 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C temperature is the ambient air temperature (Ta).
2, 4, 6, 10 - When the fuse-link is mounted in an enclosure, the elevated
16 15 temperature is the internal “fluid environment temperature”
20 18 16 (Te) within the enclosure.
25 23 21 19
32 31 30 29 - When it is not known, it should be assumed to be 15°C higher
40 39 38 37 than the ambient air temperature external to the enclosure, i.e.
50 49 48 47 Te = Ta + 15°C.
63 61 59 57
80 79 78 76
Examples:
100 98 96 94 - 100A fuse-link mounted in the open at an ambient air
125 122 119 116 temperature of 65°C.
FUSE-LINKS
160 155 150 145 140 Current carrying capability = 100A.
FULLY RATED
200 195 190 185 180 175 - 200A fuse-link mounted in the open at an ambient air
250 240 230 220 210 200 temperature of 60°C.
315 310 300 290 270 250
Current carrying capability = 195A.
355* 345 335 320 300 280
400 390 380 370 350 330 310 - 400A fuse-link mounted in an enclosure having an internal
450* 445 430 410 390 370 350 temperature of 65°C.
500 490 480 460 440 420 400 Current carrying capability = 370A.
560* 550 530 510 490 470 450 - 800A fuse-link mounted in an enclosure with an unknown
630 620 610 590 570 550 530 510 490
internal temperature and an external ambient air temperature
670* 660 640 620 600 580 560 540 520
710* 700 680 660 640 620 600 580 560
of 40°C. Assume the internal temperature is 55°C (40°C +
750* 740 730 710 690 670 650 630 600 15°C). Current carrying temperature = 740A.
800 780 760 740 720 700 680 660 640
Curves and derating comply with BS88 standard part 1 and 2 sections 2.1 and 2.2 of 1988.
* Derating also applies, to additional current ratings.
GPEU99
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes F1,F2
Ratings
• F1 type
from 2A to 32A
• F2type
from 10A to 63A
F1 type F2 type
Rating Ref. no Designation Pack. Catalog Type Rating Ref. no Designation Pack. Catalog
Type Number Number
F1 2 S226336 2F1 10 F2 10 D226346 10F2 10
F1 4 T226337 4F1 10 F2 16 E226347 16F2 10
F1 6 V226338 6F1 10 F2 20 F226348 20F2 10
F1 10 W226339 10F1 10 F2 25 G226349 25F2 10
F1 16 X226340 16F1 10 F2 32 H226350 32F2 10
F1 20 Y226341 20F1 10 F2 40 J226351 40F2 10
F1 25 Z226342 25F1 10 F2 50 K226352 50F2 10
F1 32 A226343 32F1 10 F2 63 L226353 63F2 10
F1* 20M25 B226344 20M25F1 10
F1* 20M32 C226345 20M32F1 10
GPEU100
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes F1,F2
Dimensions
Time/current data
20000
4 hours
10000
1000
Fuse-link ampere
rating
100
10
0.1
0.005
1 10 100 1000 10000 100000
GPEU101
General Purpose Fuses IEC
General Purpose Fuses IEC
BS88-2 Fuses
gG/gM Sizes F1,F2
I2t characteristics
107
106
Curves from BS88 standard part 6 of
1988.
Voltage rating : 415 VAC.
105
Interrupting rating : 40 kA
under 415 VAC.
104
ASTA 20 certified
103
Operating I2t at 415 V. * Current ratings additional to BS88 also comply to
pre-arcing I2t
102 the BS 88 standard part 6 of 1988.
10
0
Dissipated power
5
0
BS 88-part 6 standardized limit
10
Curves from BS88 standard part 6 of 1988.
Voltage rating : 415 VAC.
Interrupting rating : 40 kA
under 415 VAC.
1 * Current ratings additional to BS88 also comply to the BS 88
standard part 6 of 1988.
0.1
0.1 1 10 100
GPEU102