DES-092B: Multiple of Long-Time Pickup

This document contains information about time-current curves for circuit breakers, including: - The short time pickup is a multiple of the nominal long-time pickup value. - The curve represents a tolerance range of -9% to 11% around actual current values and operating times. - The bottom left of each curve band indicates the "commit" time while the top right indicates the "maximum clear" time including all variances.

Uploaded by

Ben Clark
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views1 page

DES-092B: Multiple of Long-Time Pickup

This document contains information about time-current curves for circuit breakers, including: - The short time pickup is a multiple of the nominal long-time pickup value. - The curve represents a tolerance range of -9% to 11% around actual current values and operating times. - The bottom left of each curve band indicates the "commit" time while the top right indicates the "maximum clear" time including all variances.

Uploaded by

Ben Clark
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

MULTIPLE OF LONG-TIME PICKUP

100

100
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
1000 1000
900 900
800 800
700 700
600 600
500 500

400 Short Time Time (Sec.) 400


Band (60Hz) Commit Clear
300 1 0.025 0.080 300
2 0.033 0.088
200 3 0.042 0.097
200
Sensors Max ST Pickup 4 0.058 0.113
Envelope 1 400-2000A 12X 5 0.092 0.147
6 0.117 0.172
Envelope 2 400-3200A 12X
7 0.158 0.213
100 Envelope 3 3000-6000A 10X 100
90 8 0.183 0.238 90
80 80
9 0.217 0.272
70 70
10 0.350 0.405
60 60
11 0.417 0.472
TIME IN SECONDS

TIME IN SECONDS
50 50
ST Pickup is a multiple of the nominal
40 (RPXPU) LT PI 40

30
Curve represents a tolerance of -9% 30
and 11% around the actual value of
current, + operating time.
20 FE time current curves include all 20
required trip unit tolerance and CB
operational variance
Bottom/left of curve band is the
“commit” time. The top/right is
10 the “maximum” clear time. 10
9 9
8 8
7 7
6 6
5 5

4 4

3 3

2 2

Max.
1 1
.9 .9
.8 .8
Int.
.7 .7
DES-092B

DES-092B
.6 .6
.5 .5
11
.4 .4
Min. 10
.3 .3

9
.2 8 .2
7
6
5
.1 .1
.09 .09
.08 4 .08
.07 .07
3
.06 10X STPU Maximum .06
.05 Slope Calculation 2 .05

.04 1 .04

.03 .03

.02 .02
Transition to Instantaneous, Transition to Instantaneous,
Override or Application Override or Application
Determines End of Curve Determines End of Curve
.01 .01
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100

100

MULTIPLE OF LONG-TIME PICKUP

Low-Voltage Circuit Breakers DES-092B


Frames 800-5000A UL1066
Frames 800-6000A UL489
EntelliGUard TU Trip Unit Pickup Range

Sensors 400-6000A for EntelliGuard G and R (Retrofill) 1.5X-12X Long-Time Pickup


Circuit Breakers
UL489 and UL1066 Stored Energy
Mechanism Circuit Breakers
All Voltages: 600 Vac and below
Short-Time Pickup and Delay Bands
Curves apply at 60 Hertz
and from -20°C to 55°C circuit breaker ambient temperature.

12.14