Boiler Modulation Controls Datasheet
Boiler Modulation Controls Datasheet
Technical Datasheet
Other products
Other products we can offer :
How can we help you?
• Boiler feed water modulation level controls and valves Delta Mobrey offers fast, efficient and
• Sequencing blowdown valves knowledgeable support when and where
you need it. Please visit our web site at
www.delta-mobrey.com to find your
local support centre or call us on:
+44 (0)1252 729140
www.delta-mobrey.com Page 1 of 8
TDS-BMC-A: SEPT 2020
How to order
The instrument can be selected from the table below, which details the specification of each model. For
assistance in selecting the model that best suits your needs, please contact your local sales office.
* denotes the size of the valve lid & seat (A-I). Valves can be supplied without the lid and seat fitted.
Boiler Water Level Controls
Vertical Air Break Controls
www.delta-mobrey.com Page 2 of 8
TDS-BMC-A: SEPT 2020
Operation
A positive change of water level in the boiler alters the inductance value of Coil “A” causing an imbalance in
the system. This signal is transmitted through the electronic control box to the appropriate solenoid valve on
the modulating valve thus producing a change of hydraulic pressure on the piston assembly, the movement
of which modulates the flow of water to the boiler.
Simultaneously this same vertical travel creates a change in the inductance value of Coil “B” until the bal-
ance is restored, thus closing the solenoid valve and hydraulically locking the modulating valve spindle.
This sequence is repeated in very small steps until the feed water input equals the required evaporation rate
of the boiler.
To prevent the modulating valve responding to random water movement against the general direction of
level change, a 13 mm reversal or (dead) band is incorporated in the electronic circuitry.
Low water alarm and burner cut out contacts are also provided within the control box to operate when the
water level falls to a predetermined position.
Installation notes
For the further safety of boilers, it is recommended that the Mobrey Control Unit is mounted on a Mobrey
Sequencing Valve.
The water connection from the boiler to the float chamber should be as short as possible and the control
head float chamber should be mounted close to the gauge glasses.
The chamber band mark indicates the lowest adjustment position of the low level alarm and it is our recom-
mendation that the positioning of the boiler control chambers relative to the water level gauge glasses and
the N.W.L. is such that there is always water visible in the gauge glass even at the lowest operating band
level. If required our technical staff will advise on individual installations.
Application notes
Throttle control
Modulating Valve in feed line
Suitable for automatic cold start conditions
Used for all pumps capable of operating against a closed discharge.
With a rising water level in the boiler, the modulating valve closes progressively to reduce the rate of feed
into the boiler. The size of valve lid is determined by the actual capacity of the boiler plus an allowance. See
below for the sizing of the valve lids.
Power failure and high water shutdown – with a third solenoid valve
Where one pump is feeding more than one boiler it is imperative that a boiler cannot be overfilled. Therefore
a third solenoid valve can be installed on the modulating valve which is operated by either a loss of power
on the boiler control circuit or the high water alarm. In either case the valve will be closed and prevent fur-
ther water entering the boiler. The third solenoid valve can be retrofitted to existing valves.
www.delta-mobrey.com Page 3 of 8
TDS-BMC-A: SEPT 2020
The formula for determining the Cv value and correct size of valve lid are given below. The pressure drop across the
valve should be 1.4 kg/cm² or greater – normally, the higher the pressure drop the better the degree of control. The lid
size is that with the nearest Cv value above the calculated value.
Where:
Q = Actual Evaporation of Boiler plus 15 per cent margin kg/hr.
P = Pump discharge pressure in kg/ cm² when passing Q quantity of water minus (boiler max working pressure + 0.4
kg/cm²).
In the following example, an allowance of 0.4 kg/cm² has been made for all feed line losses. In practice, the allowance
should be that of the installation under consideration and may well be in excess of 0.4 kg/cm², particularly where the
feed pump is remote from the boiler and/or where an anti-siphon valve adjacent to the boiler feed check valve has been
fitted.
Example
Boiler Water Level Controls
www.delta-mobrey.com Page 4 of 8
TDS-BMC-A: SEPT 2020
Technical Specifications
www.delta-mobrey.com Page 5 of 8
TDS-BMC-A: SEPT 2020
www.delta-mobrey.com Page 6 of 8
TDS-BMC-A: SEPT 2020
Approvals
EUROPEAN DIRECTIVES
The level controls, cast chambers and modulation valves are categorised as Sound Engineering Practice
(SEP) under Article 4.3.
The fabricated chambers are category 1 under Article 4.1(c)(i) for Group 2 fluids and CE marked under
Module H
www.delta-mobrey.com Page 7 of 8
TDS-BMC-A: SEPT 2020
In the interest of development and improvement Delta Mobrey Ltd, reserves the right to amend, without notice, details
contained in this publication. No legal liability will be accepted by Delta Mobrey Ltd for any errors, omissions or amendments.