Ac Boq
Ac Boq
Ac Boq
NAME OF PROJECT :- Animal House Facxility & other Miscellaneous work at VMMC, Safdarjung l lh NAME OF WORK :- S/I/T/C AIR-CONDITIONING SYSTEM FOR ANIMAL HOUSE (HVAC ) BILL OF QUANTITY UNIT QTY. Rate in figure (Rs) Rate in words (Rs) Amount (in Rs.)
ITEM NO.
Supplying, installation, testing and commissioning of 26TR, programmable microprocessor based, Air-cooled Package Type Splite AC units complete with condensing unit, scroll compressor, air-cooled condenser with fan and evaporator. Microprocessor Based Control Panel should be capable for Heating, Cooling & Humidification controls and interlocking with control wiring etc. as required. Nos. 2
Supplying, installation, testing and commissioning of 10TR, programmable microprocessor based, Air-cooled Package Type Splite AC units complete with condensing unit, scroll compressor, air-cooled condenser with fan and evaporator. Microprocessor Based Control Panel should be capable for Heating, Cooling & Humidification controls and interlocking with control wiring etc. as i d Mtrs. 150
Supplying, installation, testing and commissioning of hard drown copper refrigerant piping per circuit alongwith kinni foam insulation with necessory clamps, supports, fittings such as bends, tees, reducers, etc, as per site requirement. Nos.
Supplying, installation, testing and commissioning of 3KW-Pan Type Humidifier made from minimum 2mm thick stainless steel sheet top closed and insulated with 50mm thick expended polysterene (T.F. Quality).
Page 2 of 6
BILL OF QUANTITY UNIT Nos. 2 QTY. Rate in figure (Rs) Rate in words (Rs) Amount (in Rs.)
ITEM BRIEF DESCRIPTION OF ITEMS NO. 5 Supplying, installation, testing and commissioning of 1.5KW-Pan Type Humidifier made from minimum 2mm thick stainless steel sheet top closed and insulated with 50mm thick expended polysterene (T.F. Quality). Nos. 12
Supplying, installation, testing and commissioning of 1.5KW-Strip Type Electric Heater suitable to installed in Main Ducts/Duct Plenums/Blower Unit as required & specification.
Supplying, installation, testing & commissioning of GSS DUCTING of following thikness I/c necessory supports, hangers, nuts bolts, gaskets, splitters dampers, vanes canvass connections etc. comlete as per specification. a) 1.25 MM THICK Sq. Mtr. 30 50 200 300 3 Sq. Mtr. Sq. Mtr. Sq. Mtr.
b) 1.00MM THICK
c) 0.80 MM THICK
d) 0.63 MM THICK
Supply, installation, testing & commissioning of FIRE Sq. Mtr. DAMPERS with fusible links made out of 16 Gauge, GI sheets of at least 90 menutes fire rating complete with as per specification.
Supply, installation, testing & commissioning of Sq. Mtr. VOLUME CONTROL DAMPERS made out of 16 Gauge GI Sheet for main Ducting Braches & Headers.
Page 3 of 6
BILL OF QUANTITY QTY. 3 Rate in figure (Rs) Rate in words (Rs) Amount (in Rs.)
ITEM BRIEF DESCRIPTION OF ITEMS UNIT NO. 4 Supply, installation& balancing of square/circular Sq. Mtr. SUPPLY AIR DIFFUSERS of powder coated aluminium construction with attached volume control dampers as per specification and drawings 3
Supply, installation& balancing of square/circular Sq. Mtr. RETURN AIR DIFFUSERS of powder coated aluminium construction without attached volume control dampers as per specification and drawings.
Supply, installation & balancing of SUPPLY AIR Sq. Mtr. GRILLES of powder coated aluminium construction with attached volume control dampers as per specification and d 5
Supply, installation& balancing of RETURN AIR Sq. Mtr. GRILLES of powder coated aluminium construction without attached volume control dampers as per specification and drawings 200
Supplying, installation, testing & commissioning of 9mm Sq. Mtr. Nitrile Rubber insulation on supply / return air ducts. 40
Supplying, installation, testing & commissioning of 25 Sq. Mtr. mm thick & 24 Kg/cm resin bonded fibre glass Accoustic Insulation covered with tissue paper & 26 gauge aluminium perforated sheet as specification & drawings.
Page 4 of 6
BILL OF QUANTITY UNIT QTY. Rate in figure (Rs) Rate in words (Rs) Amount (in Rs.)
ITEM NO.
Febrication, Supply, Installation, Testing & Commissioning of Cubical Sectionalized floor standing Electrical Panel suitable for working 415, 50HZ, 3Phase A/C Supply make out of 2mm thick CPRA Sheet having suitable cable alley, 4Strip, 400A Bus Bar of Electolytic grade aluminium, duly powder coated with S/F for folloing accessories including making conection, interconnection with aluminium strip, Solid copper cunductor, glande plate, making etc. complete in all respect. INCOMER
400A FP ACB with (0-200A) ammeter with 3CT & selctor switch, (0-500 volts) Voltmeter with selector switch, phase indication ligth with protection fuse, On/Off/Trip indicating light with protection fuse.
OUTGOINGS
125A TP MCB with confirming to , ammeter (0-125A) with three CT, on-off/trip indication lights with protection fuse, etc. as required. ii) For 10TR A/C Unit x 02 Nos. 63A TP MCB with confirming to , ammeter (0-63A) with three CT, on-off/trip indication lights with protection fuse, etc. as required. iii) For 12KW Heaters Unit x 01 No. 63A TP MCB with confirming to , ammeter (0-63A) with three CT, on-off/trip indication lights with protection fuse, etc. as required. iv) For 3KW Heaters Unit x 02 Nos.
40A TP MCB with confirming to , ammeter (0-40A) with three CT, on-off/trip indication lights with protection fuse, etc. as required. v) For umidifier Unit x 03 Nos.
Page 5 of 6
BILL OF QUANTITY UNIT QTY. Rate in figure (Rs) Rate in words (Rs) Amount (in Rs.)
ITEM NO.
32A TP MCB with confirming to , ammeter (0-32A) with three CT, on-off/trip indication lights with protection fuse, etc. as required. Controls & Interlocking accessories as complete with connection/interconnection required for above switchgears. ( Lot ) No. 1
Supply, Laying, Testing & Commissioning of power and control cabling as per standard specification including end termination as required. Power & Control Cabling (PVC Insulated and PVC Sheathed, Armoured, Aluminium Conductor of 1.1KV grade on Surface/Existing cable trays). a) 3.5C X 16 Sq. mm Rmt Rmt Rmt 300 200 200
b) 3.5C X 6 Sq. mm
3 Rmt 400
EARTHING WIRE
a) Supply, Laying, of 4mm dia Copper Wire on surface of in recess for loop earthing as required.
Page 6 of 6
BILL OF QUANTITY UNIT QTY. Rate in figure (Rs) Rate in words (Rs) Amount (in Rs.)
ITEM NO.
SUMMARY SHEET
Quoted Price
NAME OF PROJECT :- Animal House Facxility & other Miscellaneous work at VMMC, Safdarjung Hospital, New Delhi.
CIVIL
ELECTRICAL
HVAC
GRAND TOTAL