SFW, SFA

Satchwell TM

WATER AND AIR FLOW SWITCHES

The Satchwell water flow switch is designed to monitor water flow in


pipe diameters from 1" up to a maximum of 6" and is factory set at a
minimum value (see table). The switching value can be increased as
required.
The water flow switch can be mounted in a short necked welding
socket or in a tee with a short branch. It is not possible to use a swept
tee as this will interfere with paddle movement.
The air flow switch has a paddle that can be trimmed if the air flow is
above 5m/s.
Both the water and air flow switches are SPDT types.

Satchwell
SPECIFICATION
Types: SFW1251 – Water flow switch 1" to 6" pipe diameter
SFA1451 – Air flow switch
Factory Flow Setting: SFW: Set at minimum (see table), depends on the pipe diameter.
SFA : Set at minimum 1m/s, 2.5m/s if the paddle is trimmed
Differential: See table below:

SFW SWITCHING VALUES


Minimum Cut-in Value Minimum Cut-out Value Maximum Cut-in Value Maximum Cut-out Value
Pipe Diameter in Inches
m3/Hour m3/Hour m3/Hour m3/Hour
1 1.0 0.6 2.1 2.0
1.25 1.3 0.8 3.0 2.8
1.5 1.7 1.1 4.0 3.7
2 3.1 2.2 6.1 5.7
2.5 4.0 2.7 7.0 6.5
3 6.2 4.3 11.4 10.7
4 14.7 11.4 29.0 27.7
5 28.4 22.9 55.6 53.3
6 43.1 35.9 85.1 81.7

SFW SWITCHING VALUES


Minimum Cut-in Value Minimum Cut-out Value Maximum Cut-in Value Maximum Cut-out Value
Paddle
m/s m/s m/s m/s
Untrimmed <5 m/s 2.0 1.0 9.2 8.0
Trimmed >5 m/s 3.5 2.5 10.7 9.5

Maximum Differential Pressure: SFW :11 mbar


Contact: Single Pole Double Throw (SPDT)
Contact Rating: 15A resistive, 8A inductive @ 24 to 250Vac
Ambient Temperature Limits: –20 to +85°C
Maximum fluid or air temperature +85°C

CONSTRUCTION
Cable Entry: PG 11 cable gland
Head Protection Class: IP 65
Cover: Impact resistant plastic
Casing: Galvanised steel
Lever: Brass
Paddle: Stainless Steel

2
WARNING -
ISOLATE ALL WIRING BEFORE REMOVING THE COVER AS MAINS VOLTAGES ARE PRESENT AT THE TERMINALS.
INSTALLATION
SFW - WATER FLOW SWITCH
1. Select a point in the pipe that has no elbows, bends or other obstructions that may cause turbulence. The pipe must be straight for at least
5 pipe diameters up and downstream of the flow switch.
2. The flow switch should be mounted in a horizontal pipe. Do not mount the flow switch directly under the pipe. If the flow switch is mounted
in a vertical section of pipe the set value will differ from the settings as the water will have to move the weight of the paddle as well as the
switch tension.
3. If the pipe diameter is 1, 2 or 3" then remove any unwanted paddles. If the pipe is 1.25", 1.5", 2.5", 4", 5" or 6" in diameter then use the
template below to trim the 6 paddle supplied and fit it to the SFW, keep the existing paddles on the SFW as this will help to stiffen the new
longer paddle.

4. Fit the flow switch in to the pipe using a short neck welding socket or a tee with a short branch. It is not possible to use a swept tee or a long
branch tee.
5. Check that the paddle does not touch the pipe or any other obstruction.
6. Ensure the flow direction arrow is correct for the water flow.
7. Flush out the system thoroughly.
8. Use the minimum quantity of jointing materials.
9. Remove the cover and wire the switch according to Fig.1. THE EARTH TERMINAL MUST BE CONNECTED.
10. Do not adjust the set value below the minimum setting as shipped from the factory.
11. Replace the cover.
SFA - AIR FLOW SWITCH
1. Select a point in the duct that has no bends or other obstructions that may cause turbulence. The duct must be straight for at least 5 duct
diameters up and downstream of the flow switch.
2. The flow switch should be mounted in a horizontal duct. Do not mount the flow switch directly under the duct. If the flow switch is mounted
in a vertical section of duct the set value will differ from the settings as the air will have to move the weight of the paddle as well as the switch
tension.
3. If the flow rate is to be above 5m/s then the paddle should be trimmed as marked. This will increase the effective switching values by 1.5m/s.
4. Cut a slot in the duct to accept the paddle. Use the gasket supplied to seal the duct.
5. Check that the paddle does not touch the duct or any other obstruction.
6. Ensure the flow direction arrow is correct for the air flow.
7. Remove the cover and wire the switch according to Fig.1. THE EARTH TERMINAL MUST BE CONNECTED.
8. Do not adjust the set value below the minimum setting as shipped from the factory.
9. Replace the cover.

BASIC CONNECTIONS

4
Red Blue
2 Set value adjustment.
White
Factory set at
minimum do not adjust
below this value.

Fig.1

3
DIMENSION DRAWINGS

SFW SFA

Dimensions in mm Weights:
SFW 760g
SFA 410g

PADDLES

Fitted

Supplied

WARNINGS -
THESE FLOW SWITCHES ARE MAINS OPERATED DEVICES. LOCAL
WIRING REGULATIONS AND USUAL SAFETY PRECAUTIONS MUST
BE OBSERVED. NOTE EARTHING REQUIREMENTS.
ISOLATE ALL WIRING BEFORE REMOVING THE COVER AS MAINS
VOLTAGES ARE PRESENT AT THE TERMINALS.
Cautions
• Do not apply any voltages until a qualified technician has checked
the system and the commissioning procedures have been
completed.
• If any equipment covers have to be removed during the installation
of this equipment, ensure that they are refitted after installation to
comply with UL and CE safety requirements.
• Do not exceed the maximum ambient temperature.
• Interference with parts under sealed covers invalidates the
guarantee.
• Design and performance of TAC Satchwell equipment is subject to
improvement and therefore liable to alteration without notice.
• Information is given for guidance only and TAC Satchwell does not
accept responsibility for the selection and installation of its
products unless information has been given by the Company in
writing relating to a specific application.
• A periodic system and tuning check of the control system is
recommended. Please contact your local sales office for details.

Copyright © 2005, TAC AB TAC Headquarters


All brand names, trademarks and registered trademarks are Malmö, Sweden
the property of their respective owners. Information contained +46 40 38 68 50
within this document is subject to change without notice. All
rights reserved.
Satchwell Helpline
DS 21.670 12/05 +44 (0) 1753 611000