CSC162 Manual
CSC162 Manual
CSC162 Manual
WARNING
1) During hot-line operation of equipment ,certain parts of this equipment are
under high voltage. Severe personal injury or significant equipment
damage could result from improper behavior.
2) Only qualified personnel should work on this equipment or in vicinity of the
equipment. These persons must be familiar with warning & service
procedure described in this manual, as well as with safety regulations.
3) Prerequisites to proper & safety operation of the equipment are proper
storage, setup, installation, operation & maintenance of the equipment.
4) In particularly cases, the general rules & safety regulations according to
relating standards(e.g. IEC, National standards or other International
standards) for work with high voltage equipment must be observed.
COPYRIGHT
All rights reserved.
Registered trademark
® are registered trademark of Beijing Sifang automation co., ltd.
CONTENTS
1. Introduction 1
1.1 Application 1
1.2 Features 1
1.3 Functions 2
2. Design 6
2.1 Mechanical structures 6
2.2 Dimensions 7
3. Technical data 8
3.1 General data 8
3.2 Function data 12
4. Hardware functions 14
4.1 Hardware arrangements 14
4.2 Operations of complete units 14
5 Protection functions 17
5.1 Whole structure of protection program 17
5.2 The protection basic elements 17
5.2 Monitoring functions 26
5.4 Other logic of pilot protection 30
5.5 Piolt protection 31
5.6 Four zones distance protection 36
5.7 Zero current protection 39
5.8 Direction over current protection 41
5.9 Over Voltage protection 42
5.10Under Voltage protection 42
5.11Breaker failure protection 43
5.12 Auto-reclose 44
5.13Broken conductor Function 46
5. Installation and commissioning 49
6.1 Unpacking & repacking 49
6.2 Mounting 49
6.3 Check before power on 49
7. Operation 50
7.1 Safety precautions 50
7.2 Dialog with the equipment 51
7.3 Setting the functional parameters 55
7.4 Annunciations 64
7.5 Testing and comissioning 68
7.6 Commissioning using primary tests 76
7.7 Putting the equipment into operation 78
8. Maintenance 80
8.1 Routine Checks 80
8.2 Relacing the back-up battery 80
8.3 Fault tracing 80
8.4 Repairs 80
8.5 The notice during operation 80
8.6 Manipulation after replacing software or CPU 81
8.7 Manipulation after replacing software or Master module 81
8.8 Manipulation after replacing input or output module 81
8.9 Manipulation after replacing AC module 81
8.10 Several illuminations 82
9. Storage 83
10. Ordering 84
10.1Selection and ordering data 84
10.2. Ordering data 84
11. Appendix 85
A Terminal diagram 85
B Communication protocol Tables 87
CSC-162 Numerical Transmission Line Protection Equipment Manual
1. Introduction
1.1 Application
CSC-162 numerical transmission lines protection equipment applicable to 132kV
and lower voltage transmission lines. The product consists of primary protection
namely 4 zones distance protection, 1 stage Definite time and Inverse time zero
current protection, 1 stage Definite time and Inverse time over-current protection, 2
stages over-voltage protection, 2 stages under-voltage protection, circuit breaker
failure protection and three phase auto-re-close etc, as shown in Table.1-1.
Table.1-1 Main function and arrangement
Main function and arrangement
Definite
Over Definite
4 zones phases- time and Three
voltage time and
Type Phase distance and Inverse Circuit phase
and inverse
ground distance time breaker Auto-
Under time over
protection zero Seq failure Re-close
voltage current
current
CSC-162 ● ● ● ● ● ● ●
1.2 Features
The equipment has characteristics as follows:
• The microprocessor combined 32 bits DSP with MCU, high performance
hardware system ensures the parallel real-time calculation in all components of the
equipment.
• Latest checking methods are used which can detect coil performance in
energized circuit. Therefore failure of the relay is identified easily The equipment
provides periodical automatic testing.
1
CSC-162 Numerical Transmission Line Protection Equipment Manual
extracted through serial port or Ethernet port and saved in COMTRADE format
• 1000 event records which are date and time tagged are stored in non volatile
memory to ensure that the data are not lost when DC supply fails.
• The relay can record protection operating process, logic flow and various
calculated values. Our CSPC software can be used for viewing the above and also
the recorded fault data and for analyzing disturbance records via RS-232 serial
port on the relay front fascia
• 2-channel high speed reliable electric Ethernet ports (optional optical fiber
Ethernet ports), 2-channel Lon-Works ports, RS-485 port and series printing port
are provided; the user can select any of these according to the requirements. The
protocol supports IEC60870-5-103, IEC61850 or CSC-2000 of Sifang Company,
for interface with substation automatization system and protection management
information system.
• Liquid crystal display with backlit is provided to display various messages such
as current, voltage, power, frequency, strip state, setting zones etc. The menu is
easy to operate. Four shortcut keys are set to finish operation with one key for
local operator.
1.3 Functions
Tele-Protection scheme (distance protection)
Distance protection is the primary protection for transmission line. Relay is suitable
for 2 types of channel aided schemes viz, permissive under reach mode and
permissive over reach mode. It consists of directional distance element, directional
zero-sequence and negative-sequence element. Directional distance element
consists of directional phase to earth distance element and phase to phase
distance element.
2
CSC-162 Numerical Transmission Line Protection Equipment Manual
For three-phase fault detection element, the method distinguishing fault from
power swing:
1. Within time τ , if ∆R < K· ∆RMin (1800, TZMAX, τ ) is satisfied, it is determined that
fault occurs in power system.
2. Within time τ , if ∆R ≥ K· ∆RMin (1800, TZMAX, τ ) is satisfied, it is determined that
swing occurs in power system.
T 0 _ factor
T= + T0_INV
Id
( ) −1
N0
3I 0 _ INV
Id - fault current.
T0_factor - Time factor of inverse time zero-current.
N0 - Index of inverse time zero-current.
3I0_INV - current setting of inverse time zero current.
T0_INV - delay time setting of inverse time zero current which can meet the
requirement that inverse time zero current co-operates with different protection.
Inverse curves can be obtained according to the following setting
N0=0.02 and T0_factor=0.14 ─ Standard inverse (IEC Standard)
N0=1 and T0_factor=13.5 ─ Very inverse
N0=2 and T0_factor=80 ─ Extremity inverse.
Toc _ factor
T= + Toc_INV
Id
( ) Noc − 1
Ioc _ INV
Id - fault current.
Toc_factor - Time factor of inverse time over current.
Noc - Index of inverse time over current.
3
CSC-162 Numerical Transmission Line Protection Equipment Manual
Auto-reclose (AR)
CSC-162 protection system has three-phase auto-reclose. For any fault on the
line, all the three poles will be tripped, and all the three poles will be re-closed.
This function can be enabled via binary settings.
Broken Conductor
CSC-162 relay has broken conductor function, if the necessary condition are
satisfied, relay can give alarm and trip output.
On-load measurement
The on-load measured values generated in the unit such as current, voltage,
phase angle, etc. can be displayed at the LCD or by means of a PC.
4
CSC-162 Numerical Transmission Line Protection Equipment Manual
2. Design
2.1 Mechanical structure
• The enclosure for equipment is 19 inches in width and 4U in height according
to IEC 60297-3.
• The equipment is flush mounting with panel cutout and cabinet.
• Connection terminals to other system on the rear.
• The front panel of equipment is aluminum alloy by founding in integer and
overturn downward. LCD, LED and setting keys are mounted on the panel.
There is a serial interface on the panel suitable for connecting a PC.
• Draw-out modules for serviceability are fixed by lock component.
• The modules can be combined through the bus on the rear board. Both the
equipment and the other system can be combined through the rear interfaces.
5
CSC-162 Numerical Transmission Line Protection Equipment Manual
2.2 Dimensions
Dimension drawings for CSC-162 are shown in Fig.2-2.
6
CSC-162 Numerical Transmission Line Protection Equipment Manual
3. Technical data
3.1 General data
3.1.1 Analog input and output
Nominal Frequency 50 Hz
Current Inputs
Rated current IN 1 A or 5 A
Current Overload Capability per Current Input
-thermal (rms.) 2 IN continuously
10 IN10s
70 IN1s
Voltage Inputs
Rated Voltage UN 110/√3
Voltage Overload Capability in Voltage Path per Input
-thermal (rms) 1.2 UN continuously
1.4 UN 10s
3.1.2 Power supply
Voltage Supply
Rated auxiliary voltage UDC 110V DC 220V DC
Permissible voltage ranges 88V~121V 176V~242V
Binary outputs
Variant Trip contacts Quantity Alarm contacts Quantity
CSC-162 48 NO contacts 16 NO contacts
Operator Interface
local Connection type RS-232 Ethernet RS-485
Medium of connection electric electric electric
Type of connector DB25 RJ45 twisted-pair
Type of data transfer serial serial serial
Speed of communication 9600bps 10/100Mbps 9600bps~38400bps
Dielectric level III III III
Maximum cable length 10m 110m 1.2km
7
CSC-162 Numerical Transmission Line Protection Equipment Manual
8
CSC-162 Numerical Transmission Line Protection Equipment Manual
• AC voltage circuit
≤0.5A Specific
•DC power supply rating
circuit: ≤50W defined by
4 Thermal property Manufacturer
4.1 Thermal of short and • AC current circuit DL/T 478-2001 in IEC
long time 2 In -continuously 60255-6
10 IN for10s 1988
70 IN for1s
• AC voltage circuit
1.2UN-continuously
1.4 UN for10s
5 Electrical insulation
5.1 Insulation resistance 100MΩ IEC 60255-5
2000
(GB/T 14598.3
-2006,IDT)
5.2 Insulation resistance in 1.5MΩ DL/T 478-2001 No defined
dry heat in IEC60255-
5
9
CSC-162 Numerical Transmission Line Protection Equipment Manual
10
CSC-162 Numerical Transmission Line Protection Equipment Manual
11
CSC-162 Numerical Transmission Line Protection Equipment Manual
12
CSC-162 Numerical Transmission Line Protection Equipment Manual
4. Hardware functions
4.1 Hardware arrangements
3 4 5 6 7 8 9 10 11
AC CPU MASTER DI DO1 DO2 DO3 DO4 POWER
Relay
Manage
Digital Input
Digital Output1
Digital Output2
Digital Output3
Digital Output4
Alternating
current
45 20 40 20 20 20 20 20 35
The AC module functions are to transform the secondary signals of voltage and
current transformers in power system into electric weak signals, and perform
isolation and anti-interference. The AC modules of CSC-162 are the same, the
wiring terminal at rear panel is X3. There are 9 analog signal transformers in CSC-
162, used respectively to transform UA, UB, UC, UX, IA, IB, IC 3I0 and IN. There are two
types of current transformer: Rated current 5A with linearity range 500mA - 150A
and rated current 1A with linearity range 100mA - 30A (please indicate clearly
when order the product). Please pay attention that IN’ is the polarity terminal while
IN is not. Rated phase value of voltage transformer is fixed to 110/ 3 V.
Combined DSP with MCU, the 32-bit microprocessor with 1M bytes flash memory
and 64 bytes RAM is employed to run programs in chip completely, and keep the
data bus in a chip. There is a CPU module in the CSC-162system. CPU1 performs
sampling, A/D transform, transmission analog data and input information,
judgment of the protection theory, fault recorder and software and hardware self-
testing etc.
In order to backup data and test A/D by the protection itself, every AC analog
13
CSC-162 Numerical Transmission Line Protection Equipment Manual
The input module 1 wring terminal at rear panel is X6. It is used to connect the
input signals and alarm signals such as the auxiliary contacts of the circuit
breaker (CB) etc.
Each of input modules has two groups input circuits and self-testing circuits, so all
input circuits can be performed real time self-testing. The power supply of 24V
energizing input module can be input directly, another group input need to be
connected, 220V or 110V power can be used.
14
CSC-162 Numerical Transmission Line Protection Equipment Manual
The power supply module with DC inverters module wiring terminal at rear panel
is X11. Its input power is DC 220V or 110V (indication when ordered), and its
outputs are five groups power supplies.
1. + 24V two groups provided: Power for inputs and outputs module
2. ± 12V: Power for A/D
3. + 5V: Power for all CPU
15
CSC-162 Numerical Transmission Line Protection Equipment Manual
5. Protection functions
5.1 Whole structure of protection program
Software of CPU protection includes main program, sampling interruption service
routine and fault detection routine.
Main program is running under normal operation to perform hardware self-testing,
setting solidified and transmission reports upward etc. Sampling interruption service
program is active in a sampling interval time to implement data sampled, wave
record and fault detected by abrupt current etc. Whenever the fault detector elements
operate, fault detection program is executed to run all protection logic and judge CT
circuit open or not etc. If any abnormal element is detected, a relevant alarm signal
and report will be given.
For the general alarm signals (ALARM II), only the signal is sent out to clue the
operator to examine and repair. For the serious alarm signal threatening the
protection security and reliability (ALARM I), once the signal is sent out, the
protection output circuit is blocked.
When fault occurs in power system, fault detection program does not return to the
main program until it has finished all relevant protection functions required to meet
the conditions of the whole reset.
5.2 The protection basic elements
Startup element main function is to detect faults, start the protection relay and
energize positive power supply for the output relay. Once startup element operates, it
does not reset until the all activated conditions return to normal reset mode.
Startup element includes current abrupt startup, zero-sequence current startup, the
loss of static stability startup, low-voltage startup element in weak-source and
autoreclose startup element. The fault detection program is picked up and the
positive power supply for the output relay is energized when any startup element
operates.
5.2.1.1 Abrupt current of phase-phase element — ∆Iφφ
Abrupt current phase-phase element is the main startup element that can sensitively
detect most of faults. Its criterion is as follows
∆iϕϕ> I_abrupt
Or ∆3i0> I_abrupt
where ∆iϕϕ= || iϕϕK- iϕϕK-T|-| iϕϕ K-T - iϕϕK-2T ||ϕϕ means AB,BC or CA, K is the
current sampling timingT=24 samples per cycle (K-T) is the sampling timing
before one cycle from timing K, (K-2T) the sampling timing before two cycles
from timing K,
∆3i0 is abrupt zero-current value,
I_abrupt is the setting value of abrupt current.
The abrupt current element operates when any phase-to-phase abrupt current
∆iϕϕ or zero-sequence abrupt current ∆3i0 continuously exceed the setting I_abrupt.
16
CSC-162 Numerical Transmission Line Protection Equipment Manual
Using integrated phase selector detect various fault types, phase selector can pick
out the faulted phase for selective-phase tripping.
Abrupt current phase selector is used at the beginning of fault after abrupt current
startup, later; sequence fault components phase selector is used. Both abrupt-
current phase selector and sequence fault components phase selectors are not
applicable to weak-source system and feeder terminal line where low voltage phase
selector is employed.
17
CSC-162 Numerical Transmission Line Protection Equipment Manual
ABN
BCN
0 0
+90 - 90
CN, ABN BN, CAN
0 0
+150 CAN - 150
18
CSC-162 Numerical Transmission Line Protection Equipment Manual
(4) and (6). On the other hand, in phasor areas of (1), (3) and (5), there are single-
phase and phase-to-phase both fault types which are always independent to each
other and can be differentiated by phase-to-phase impedance calculation. If phase-
to-phase impedance is bigger than its setting, then phase-to-phase fault is
impossible, single-phase-ground fault can be confirmed, otherwise phase-to-phase
fault will be done.
19
CSC-162 Numerical Transmission Line Protection Equipment Manual
Fig.5-2 Fig.5-3
The values in the small rectangle operation area are shown in Tab.5-2.
Tab.5-2
Setting X is set as XDZ/2, if XDZ≤ 1Ω
X is set to 0.5Ω(In=5A) or 2.5Ω (In=1A), if XDZ>1 Ω
20
CSC-162 Numerical Transmission Line Protection Equipment Manual
§l
¶m
forward
81¡ ã 81¡ ã
18¡ ã
3U0
reverse
21
CSC-162 Numerical Transmission Line Protection Equipment Manual
§l
¶m
forward
81¡ ã 81¡ ã
18¡ ã
3U2
reverse
Power system is impossible to begin swing within 150ms after sudden-charge current
startup element operating, therefore, during this time, all distance relays are settled
to take on action, and power swing block need not be enabled. After the setting of
“T_PS NO BLOCKING”, all distance relays are settled to take on action, and power
swing block need not be enabled. After 150ms or the protection startup by loss of
static stability or zero-sequence current, the distance relay must be enabled by fault
detector to prevent mistake trip during power swing.
Fault detectors for power swing blocking are different for asymmetric faults and
three-phase fault.
22
CSC-162 Numerical Transmission Line Protection Equipment Manual
1 2 jX
Rf
t Zm
0
R
0
Tz
a b
(a) Measuring resistance Rm. changing with time (b) the track of measuring
impedance on R-X plane
Fig.5-6 The trajectory of measuring impedance during power swing
Rm( t )
Rf
Rk
O t
t1 t2 t3
Fig.5-7 The trajectory of pre- and post-fault measuring resistance changing with
time
b) When fault occurs on the protected line, resistance component of measuring
impedance maybe changes due to electric arc elongated, but analysis and
calculation show that changing rate of arc resistance is far less than that of
resistance corresponding to the possibly biggest swing period noted up to the
present. After short circuit, measuring resistance is resistance RK of short
circuit, whose value hardly changes or almost keeps invariability, as shown in
23
CSC-162 Numerical Transmission Line Protection Equipment Manual
δ 180°
∆Rmin
t
τ /2
τ
It can be known from Fig.5-8 that a minimum changing resistance ∆RMin (1800, TZMAX, τ ) is
obtained corresponding to a time τ , in this way, for any swing period and any time period τ , all
exist: ∆R ≥ ∆RMin (1800, TZMAX, τ ). Therefore, consider error and protection margin, take the
following formula as criterion detecting swing.
∆R ≥ K·∆RMin (1800, TZMAX, τ ) (1)
Reliable coefficient K is a less than 1. Surely, also consider equivalent system impedance Z S ∑ for
(1). And, for a different regulated timeτ , the corresponding ∆RMin (1800, TZMAX, τ ) can be
calculated.
Concluding the above analysis, we can reason the method distinguishing fault from power swing:
1. Within time τ , if ∆R < K·∆RMin (1800, TZMAX, τ ) is satisfied, it is determined that fault occurs
in power system.
2. Within time τ , if ∆R ≥ K·∆RMin (1800, TZMAX, τ ) is satisfied, it is determined that swing occurs
in power system.
When fault occurs, it is possible that formula (1) is satisfied due to time τ too small, however, τ
can be increased to relax the restrained condition ∆R < K·∆RMin (1800, TZMAX, τ ), and to make
use of it to identify fault gradually.
c) When fault suddenly occurs on the protected line, if the angles between two
sources do not reach 180°, or three-phase fault occurs outside the swing center, the
magnitude and angle of pre- or post-fault impedance must have great sudden
change. Based on this characteristic, distance element can be enabled quickly when
three-phase fault occurs in power system without serious swing or under the
conditions that swing does not occur after protection pickup for 150ms.
24
CSC-162 Numerical Transmission Line Protection Equipment Manual
25
CSC-162 Numerical Transmission Line Protection Equipment Manual
Relay startup
NO DI“ CB
OPEN”
≥1
OR1
≥1
VT_bus OR2
&
Relay test AND3
&
AND5
Ia(b,c) >
0.04In
&
AND4
Ua(b,c) < 8V
To prevent the relay from wrong trip, interruptions in the secondary circuits of current
transformers is detected and reported by the device. When the zero-sequence
current is always larger than the setting value of 3I0 for 12s, “CT Fail” will be reported
and zero-sequence current protection will be blocked.
26
CSC-162 Numerical Transmission Line Protection Equipment Manual
By comparing value and phasor of calculation 3I0 (IA+ IB + IC) with that of 3I0 external
connected, whether the polarity of external 3I0 is connected in reverse or not can be
differentiated, if it is in reverse, “3I0 Reverse” will be reported.
If the third harmonic voltage exceeds 4V, “Harmonic Alarm” will be reported with 10s
delay time, but the protection is not blocked.
Under the auto-reclose condition of three-phase mode, if there is current through line
or not, input of auxiliary tripping contact of CB, which indicates CB is in the close
state. The following methods can check the line voltage in good condition.
When “AR_check Sync” or “AR_check low U” is set for automatic reclosure modes, if
the voltages between both sides of CB can not meet the setting synchronism
condition, which is confirmed with 14s delay time, “SYN Voltage Err” is reported. The
system supervises extractive voltage on real time.
If there is input signal of auxiliary contact of CB, and corresponding phase has
current, which is confirmed with 2s-delay time, “CB Open Err ” is reported.
a) In function of pilot protection such as< POR mode > and < PUR mode >, if both
modes are put into operation at the same time, “Pilot FUNC Alarm” is alarmed.
b) In function of automatic recolsure of equipment, if any two kinds of modes are put
into operation at the same time among < AR_No check >, < AR_check low U > and <
AR_check Sync >, “AR FUNC Alarm” is alarmed.
c) Choose VT mode, If two kinds of modes are put into operation at the same time <
VT_line >and < VT_bus>, “VT Choice Alarm” is alarmed. If for < VT_line >and <
VT_bus> is not put into operation, relay is put into operation for < VT_bus>.
d) In function of distance protection, Z4 put into operation, if two kinds of modes are
put into operation at the same time < Reverse_Z4 >and < Forward_Z4 >, “Z4 Choice
Alarm” is alarmed.
a) CPU module check. CPU module performs self-testing to its memories, analog
channels and program during power on, parts of the above are checked by itself in
real time during the system running. If any of them is confirmed to be incorrect, alarm
will be given, and the protection will be blocked.
27
CSC-162 Numerical Transmission Line Protection Equipment Manual
b) The sampled data can be checked with each other in real time due to the
redundancy of double A/D channel for one analog quality. If the difference between
two channels exceeds the setting limit, one of the double channels is regarded as
fault one.
c) Each I/O module performs self-testing during power-up and real-time self-tests.
Self-testing checks input channel, output channel, memories and code areas etc.
Self-testing of input channel is performed by bit changing simulation. Self-testing of
output channel includes coil tests and outer circuit tests. The tests are very thorough
with wide range, if any failure is confirmed, alarm is given.
d) Real-time self-testing of communication ports. CPU module and MASTER module
perform real-time self-tests of communication among all kinds of function modules.
When interrupt communication is detected, alarm is given.
e) MASTER module performs self-testing at power-up and real-time self-testing that
check memories, program areas and relevant communication with the outside. If any
abnormal event is detected, alarm will be given. The setting and strap messages
stored in this module are checked with each other.
f) Real-time supervision for DC power supply.
g) CRC checks for the setting etc.
The input of auxiliary tripping contact of CB lasts 10s, later ∆I operates, and then the
system regards this condition as manual closure of the CB. If no fault is detected, 1s
later, the whole system resets. If fault is detected, instantaneous trip function put into
operation.
Distance relay use impedance element to detect fault, zero-current relay operates
with 100ms delay, when fault occurs during switch-on-to-fault.
When switch-on-to-fault line occurs, if the binary setting of distance relay is enabled,
the distance relay will accelerate to operate. Six loops of impedance will be
calculated, if any of them is located in the area of operating characteristics with offset
region, the distance relay trips with no delay time.
If the fault still exists after automatic reclose, then the protective elements will re-trip
the circuit breaker.
The equipment requires three auxiliary tripping contacts of segregated phase
respectively as three binary inputs. For 3/2 bus connection scheme, each phase
tripping contacts of two breakers must be series at first, and then the series contacts
of each phase are connected to the corresponding binary input of the equipment.
When the equipment has detected CB opened, and any phase current is larger than
0.1In(three-phase reclose mode) or the input of auxiliary tripping contact disappears,
the equipment thinks that line has reclosed.
28
CSC-162 Numerical Transmission Line Protection Equipment Manual
When all the following conditions have been meet for 5s, the whole relay resets from
fault dealt program.
a) Six loops of impedance are outside the 4 zone of impedance.
b) Zero-current is less than the setting of zero-current startup value.
c) All three-phase currents are less than the setting “I_PS” of loss of static
stability.
5.4 Other logic of protection
After tripping commands sent out, the current of tripping phase is in the supervision.
When tripping phase has not current, the protection system considers that CB has
been opened. If tripping phase always has current, the system output three-phase
trip signal with 150ms delay. After this, if any phase current lasts 150ms, three-phase
final tripping command is issued. Later, if CB still in close state lasts 5s, three-phase
final tripping failure alarm will be sent out, and the whole relay will reset.
Trip command will be withdrawal as soon as fault is cleared. To ensure that CB trips
reliably, withdrawal command is impossible to be considered within 40ms after trip
command sent out.
When there is no current flowing through three phases for 12s after the output of
three-phase trip command, the program routine jumps to the whole relay reset. The
delay time of 12s is to believe that the most setting delay time for three-pole
autoclosure is impossible larger than 10s.
After tripping command output, the sending signal command (for permissive mode)
does not return until tripping command has been withdrawal for 120ms in order to
ensure the tele protection of both terminals to operate reliably.
29
CSC-162 Numerical Transmission Line Protection Equipment Manual
If one side of the line is feeder, when forward fault for the relay at feeder side occurs,
the fault characters are no longer same as that of two side source system. To
perform selective tripping function for a line with feeder, feeder tripping of pilot
protection must be put into operation.
If feeder function is enabled, CSC-162can fit the following conditions.
When internal faults occur, the local relay sends out permissive signal (permissive
mode) in order that the relay at power source side trips quickly. The relay at weak-
source side can correctly perform selective trip.
Phase selector of the relay at weak-source end can meet the phase-selection
requirements for line faults, and the relay can correctly perform selective trip. Even if
faults occur on load terminal line, the relay can either send out tripping command
quickly and exactly or select fault phase correctly.
When abrupt current startup element does not pick up, if feeder function is enabled,
relay starts up under the following conditions.
a) Voltage is lower than 30V.
b) Receiving signal.
After pickup, the feeder relay will send signal (for permissive mode) quickly, and
extend the signal 120ms to ensure the relay at power source side to trip quickly.
At feeder side, if the relay have picked up and the following conditions are satisfied,
the relay of permissive mode sends permissive signal. If the setting of the relay at
feeder is enabled, the relay can trip after confirming permissive signal.
a) At least one phase voltage or phase-phase voltage is less than 30V.
b) Both the forward and reverse directional elements do not operate.
c) Pickup time is less than 200ms.
d) Receiving permissive signal for 5ms.
30
CSC-162 Numerical Transmission Line Protection Equipment Manual
signal is sent out to the remote to permit the remote trip. If it is external fault that
occurs on line, the forward directional element of one end of the line operates and
does not receive permissive signal while that of another end of the line does not
operate and receive permissive signal, therefore, both ends can’t trip.
a) Internal fault
<Startup element>operates, relay trip for meeting following condition.
1) Instantaneous trip if Zone 1 Operation
2) Zone 2 + permission Signal from Remote end for 5ms.
Zone 2 operates that permissive signal is sent out to the remote.
b) External Fault
Because the directional element near fault detects reverse direction, it does not send
permissive signal to the remote. Although the remote relay can send signal, it cannot
receive the remote permissive signal, therefore, both of two sides do not trip.
c) Power flow reversing for external fault
The method to resolve this problem for the relay is that the relay sends signal with
40ms delay time when the directional element operates from the reverse to the
forward to avoid the period in which both sides are forward direction, and then both
sides trip after sending signal is confirmed with 15ms delay when internal fault occurs
again.
d) Protection schemes for feeder
The binary setting “Feeder_FUNC” is enabled.
1. For feeder end, abrupt current startup element cannot operates, the logic of the
low voltage is startup:
If the relay at feeder end receives the remote permissive signal and <low voltage
element> operates, relay startup.
2. For feeder end, abrupt current startup element operates, the operating logic of
the relay is as below.
Within 200ms after protection pickup, if <low voltage element> operates, both the
forward and reverse directional element at feeder end do not operate, and the
permissive signal has been received for 5ms, (sending signal) lasted for 120ms to
ensure the relay at power source end trips quickly, feeder end can also trip.
e) The protection is not picked up, receives the remote signal < CARR
RECEIVED > and there are < CB OPEN >, (send signal) can be done for 200ms to
ensure the remote pilot protection operates reliably.
31
CSC-162 Numerical Transmission Line Protection Equipment Manual
Relay
startup
&
AND-1
Zone 2
operation
&
Delay time AND-5
5ms &
& AND-2
CARR AND-3
Received & Trip three
AND-6 phase
Single fault
& Trip three
Multiphase AND-7 phase
fault
CB OPEN ≥
OR-1
&
AND- |0 200|
11
CSC-162pilot protection logic for under reach permissive mode is shown in Fig.5-11.
When internal fault occurs, the startup elements and zone 1 can operate, permissive
signal is sent out to the remote to permit the remote trip. If it is external fault that
occurs on line, the forward directional element of one end of the line operates and
does not receive permissive signal while that of another end of the line does not
operate and receive permissive signal, therefore, both ends can’t trip.
a) Internal fault
<Startup element>operates, relay trip for meeting following condition.
1)Instantaneous trip if Zone 1 Operation
2)Zone 2 + permission Signal from Remote end for 5ms.
Zone 1 operates that permissive signal is sent out to the remote.
b) External Fault
32
CSC-162 Numerical Transmission Line Protection Equipment Manual
Because the directional element near fault detects reverse direction, it does not send
permissive signal to the remote. Although the remote relay can send signal, it cannot
receive the remote permissive signal, therefore, both of two sides do not trip.
c) Power flow reversing for external fault
The method to resolve this problem for the relay is that the relay sends signal with
40ms delay time when the directional element operates from the reverse to the
forward to avoid the period in which both sides are forward direction, and then both
sides trip after sending signal is confirmed with 15ms delay when internal fault occurs
again.
d) Protection schemes for feeder
The binary setting “Feeder_FUNC” is enabled.
(1) For feeder end, abrupt current startup element cannot operates, the logic of
the low voltage is startup:
If the relay at feeder end receives the remote permissive signal and <low voltage
element> operates, relay startup.
(2) For feeder end, abrupt current startup element operates, the operating logic of
the relay is as below.
Within 200ms after protection pickup, if <low voltage element> operates, both the
forward and reverse directional element at feeder end do not operate, and the
permissive signal has been received for 5ms, (sending signal) lasted for 120ms to
ensure the relay at power source end trips quickly. Feeder end can also trip.
e) The protection is not picked up, receives the remote signal < CARR
RECIEVED > and there are < CB OPEN >, (send signal) can be done for 200ms to
ensure the remote pilot protection operates reliably.
33
CSC-162 Numerical Transmission Line Protection Equipment Manual
Relay
startup
&
AND-1
Single fault
& Trip three
Multiphase AND-7 phase
fault
CB OPEN ≥
OR-1
&
AND- |0 200|
11
The pilot protection has input of “B/LBB OPTD”, it will give output “Direct trip send”
for 200ms. If it has input of “Direct trip RECV”, it will give output “Direct trip RECV”.
Input Output
Direct trip
B/LBB OPTD 0 200
send
34
CSC-162 Numerical Transmission Line Protection Equipment Manual
After the abrupt current startup element operates, the protection switches the
executing program to the fault processed part, the distance measurement element is
instantaneously opened for 150ms. Within 150ms, zone 1, zone 2, zone 3 and zone
4 of distance relay are fixedly put into operation. The abrupt current startup element
operates after 150ms , or when the loss of static stability startup element or zero-
current startup element operates, before the setting of “T_PS NOBLOCKING”, the
executing program will directly go into the logic part of power swing blocking. In this
period, four zones of distance relay must be enabled by fault detector of power swing
blocking, that is, asymmetry faults are detected by asymmetry fault detector, three
phase fault is detected by the impedance change rate detector (dR/dt)
Four zones of distance relay are controlled by the setting to be selected whether they
are blocked during power swing. If the setting is set “off”, four zones of distance relay
are put into operation without blocking all the time during power swing.
During power swing, there is a special program module to detect whether power
swing quiets down or not, that is, if all zero-current elements, Power swing current
detection element and six impedances of four zones of distance relay don’t operate,
after 5s, the whole system resets.
The distance relay exits after loss of measure voltage, and at the same time, the
measure voltage of VT is monitored continually. Once the voltage comes to the
normal, the distance relay will be automatically put into operation again.
35
CSC-162 Numerical Transmission Line Protection Equipment Manual
Tab. 5-4
Item binary setting
“Z_PS Trip mode trip control
Zone blocking”
Blocked / the setting of“
Zone 1 Three phase trip
unblocked Z1_FUNC”
Blocked / the setting of“
Zone 2 Trip_no AR
unblocked Z2_FUNC”
Blocked / the setting of“
Zone 3 Trip_no AR
unblocked Z3_FUNC”
Blocked / the setting of“
Zone 4 Trip_no AR
unblocked Z4_FUNC”
36
CSC-162 Numerical Transmission Line Protection Equipment Manual
Four zones distance relay don’t consider power swing blocking after abrupt
current startup for the setting “T_PS NOBLOCKING”.
e) Permanent trip for three-phase fault:
Relay will permanent trip for three-phase fault.
f) Switch-on-to- fault: If any impedance lies in the area of zone 1, zone 2, zone
3, relay permanent trip immediately.
“ I_PS” start
up
Zero-
sequence ≥
current OR-1
startup &
Current AND-4
change |150 0|
startup
& ≥
Fault detect AND-1 OR-3
swing
unblocking
& ≥
Z1(2,3,4)_PS AND-2 OR-2
blocking &
AND-5
Forward
direction &
& Trip three
AND-3
AND-6 phase
VT fail
& &
SOTF AND-
AND-8
12
≥
OR-4
Zone 1 -pe
& Trip three
AND-9 phase
Zone
Single1 fault
-pp
Three &
AND-
phase fault 10
Zone 2 |T2 0|
≥ Permenent
OR-7 trip
≥ &
Zone 3 |T3 0| AND-
OR-6
11
Zone 4 |T4 0|
37
CSC-162 Numerical Transmission Line Protection Equipment Manual
One stage directional definite time and inverse time zero current protection are set
during three-phase operation. Directional element of zero current protection is fixed.
Zero current is controlled to be on or off by the setting of “3I0_FUNC”, and inverse
time zero current protection is controlled to be on or off by the setting of “3I0_INV
FUNC”, Directional element of inverse time zero current protection is controlled to be
on or off by the setting of “3I0_INV DIR”.
The directional element of inverse time zero current protection can be on or off via
the setting of “3I0_INV FUNC”. Its characteristic is written as below:
T0_factor
T= + T0_INV
Id
( ) −1
N0
3I0_INV
Where: Id ─ fault current.
T0_factor ─ time coefficient of inverse time zero current.
N0 ─ Index setting of inverse time zero current.
3I0_INV ─ current setting of inverse time zero current.
T0_INV ─ delay time setting of inverse time zero current which can meet the
requirement that inverse time zero current co-operates with different protection.
Inverse curves can be obtained according to the following setting:
N0 =0.02 and T0_factor =0.14 ─ Standard inverse (IEC Standard)
N0 =1 and T0_factor =13.5 ─ Very inverse
N0 =2 and T0_factor =80 ─ Extremity inverse.
38
CSC-162 Numerical Transmission Line Protection Equipment Manual
Tab.5-5
Directional
Item Tripping mode Output
element controlled
stage controlled by setting control
by setting
Definite time of the setting of
fixed with direction permanent trip
zero current “3I0_FUNC”
the the setting of
Inverse time of
setting“3I0_INV permanent trip “3I0_INV
zero current
DIR” is “on” or “off” FUNC”
SOTF
“ 3I0 FUNC”
3I 0> “ 3I 0”
& | T0 |
“ 3I0_INV FUNC”
≥ Permenent
OR-3 trip
3I0 ≥
|T_INV |
“ 3I0_INV DIR”
&
Forward
direction
& &
VT fail
39
CSC-162 Numerical Transmission Line Protection Equipment Manual
This protection function is a backup protection for the transmission line and the
power system. The protection comprises one stage definite time over current and
inverse time over current. The over current protection function can be applied to via
binary settings.
Each phase current is compared with the setting value “Ioc_pe” after numerical
filtering. Currents above the associated pickup value are detected and signaled. The
protection is blocked by directional element. Directional element is 90° connection
mode. Current of each phase is controlled by corresponding directional component.
Following figure (Fig.5-14) is over current directional element(current lags and angle
of voltage is positive).
directional element I U
A IA UBC
B IB UCA
C IC UAB
Forward -90° ≤ arg (U/I) ≤ 30°
forward
U
30°
After expiry of the associated time delays “Toc_pe”a trip command is issued. The
function can be operation via a binary setting “OC_FUNC” ,and inverse time over
current protection is controlled to be on or off by the setting of “OC_INV_FUNC”,
Directional element of inverse time over current protection is controlled to be on or
off by the setting of “OC_INV DIR”.. The over current function is permanent trip.
The directional element of inverse time over current protection can be on or off via
the setting of “OC_INV FUNC”. Its characteristic is written as below-
40
CSC-162 Numerical Transmission Line Protection Equipment Manual
Toc _ factor
T= + Toc_INV
Id
( ) −1
Noc
Ioc _ INV
The following figure (Fig.5-15) shows the logic diagram for over current.
“ OC FUNC”
I φ> “ I oc_pe”
& | “ Toc” |
≥ Permenent
“ OC_INV FUNC” trip
Iφ ≥ | T_INV |
“ OC_INV DIR”
&
Forward
direction
& &
VT fail
41
CSC-162 Numerical Transmission Line Protection Equipment Manual
permanent trip.
“ OV1_FUNC ”
& Tov1_pe
Uφ>OV1_pe
Permenent
≥
“ OV2_FUNC ” trip
& Tov2_pe
Uφ>OV2_pe
Uφ<UV1_pe &
“ UV1_FUNC ”
Initiate AR
≥ Permenent
“ UV2_FUNC ” trip
&
Uφ<UV2_pe &
Tuv2_pe
42
CSC-162 Numerical Transmission Line Protection Equipment Manual
the device. Fig.5-18 shows the operating principle. When the trip signal appears from
any internal or external protection and at least one current is larger than “I_CBF”, the
breaker failure protection is initiated and the corresponding delay time “T_CBF” is
“START 3-PH CBF”. When three-phase circuit breaker failure start up, single-phase
circuit breaker failure will be started up.
Relay trip
≥1
DI of “ Start CBF
3-PH”
“ CBF_ FUNC”
& T_CBF 3P_CBF startup
IA>I_CBF
≥1
IB>I_CBF
IC>I_CBF
5.12 Autoreclose
When all three phases of the circuit breaker are open, three kinds of check mode are
provided as below.
a. Synchronism check: If the line voltages and bus bar voltages are larger than
the value of have voltage setting, and meet the synchronous conditions,
synchronizing reclose can be performed.
b. Low voltage check: If the line voltages are checked to be less than the value of
no-voltage setting, reclose can be performed. If the line voltages and bus bar
voltages are all larger than the value of voltage setting, the check mode is
automatically turned to synchronism check to reclose.
43
CSC-162 Numerical Transmission Line Protection Equipment Manual
c. No check: Whatever the line voltage and bus bar voltage are, autoreclose is
performed.when relay only enable “AR_3p mode”,and don’t select any reclose
mode of “AR_No check”, “AR_check low U” and “AR_check Syn”,then relay think
it is in “AR_No check” mode .
Note : (1)The threshold of low voltage check is 17V of rated voltage and that of
voltage check is 40V of rated voltage, the angle of synchronism check
can be set.
(2)The voltage phases of synchronism check or low voltage check need
not be set, as the protection system can automatically identify, that is to
say, if autoreclose check mode is set to synchronism check or no-voltage
check, the voltage phases is identified according to the voltage from the
bus and line. When CB is closed, if the voltage phases whose voltage
can be satisfied with synchronism check can’t be found, “SYN Voltage
Err” is alarmed, and A-phase voltage is regarded as the synchronism
voltage.
The voltages provided for the relays are always from the bus VT, so the
reference voltage is referred to the voltage at terminal Ux for low voltage
check or synchronism check.
(3) When three check modes of autoreclose are all disenabled, the faceplate
of LCD displays: “check mode: No check”.
To avoid repetitious autoreclose, a special timer with charging interval for the setting
“T_Reclaim” is set to perform the function of charge and discharge. Only after charge
has been finished, autoreclose is enabled while charge is not finished, autoreclose is
disenabled.
a) The charge time counter starts when the following conditions are satisfied.
(1) There is no input of “CB OPEN”.
(2) The startup elements of autoreclose do not operate.
(3) No input of blocking autoreclose.
b) The charge time counter is reset when the following conditions are satisfied.
(1) External signals of blocking reclose are received.
(2) Discharge is performed when the reclose command is output.
(3) There is no input of “CB OPEN” or “INITIATE 3PH A/R” when charge is not
finished.
(4)During autoreclose startup, the opened phase has current.
Two kinds of pickup mode are set by relay internal trip, digital input of other relay trip
or the auxiliary contacts of CB.
a) Auto re-close startup caused by other relay trip
Input terminal “INITIATE 3PH A/R”. The relay must return immediately after a
successful tripping and reclosure is started after the contacts return from the close
position.
44
CSC-162 Numerical Transmission Line Protection Equipment Manual
b) Internal tripping signals have pick up autoreclose, therefore, the input terminal
for” INITIATE 3PH A/R” which need not be connected again from external contacts.
Only distance zone 1 and pilot relay operate to startup reclose. Other relays operate
to block AR.
c) Autoreclose shot caused by the auxiliary contacts of CB
Autoreclose shot caused by the auxiliary contacts of CB is mainly considered for CB
occasional mal-open. The CB occasional mal-open of three-phase can be set by the
control word to decide whether to pick up reclose or not.
In addition, no accelerated contacts are given after successful reclose caused by the
auxiliary contacts of CB.
5.12.5 Reclose
When autoreclose is picked up, the following functions are performed before reclose
signal output.
a) Continue to detect the digital input of “A/R BLOCK”. If it is received, time
counter of charging will be cleared, and the program of autoreclose will be reset.
b) Voltage check is performed according to the setting of voltage and
synchronism check, if voltage condition is not satisfied, the counter of time delay
of autoreclose is cleared.
c) If reclose command is sent out, autoreclose module is reset in 4s.
When autoreclose is picked up, the discharging conditions are satisfied,
autoreclose module is reset immediately and reclose is disabled.
If it is caused by unsatisfied synchronism conditions or the others that reclose can
not be performed successfully, autoreclose model will be reset with a certain time
delay. Under three-phase autoreclose mode, it is the setting delay of three-phase
autoreclose +12s.
The voltages provided for the CSC-162protection system are always from the bus
VT, so the reference voltage is referred to the voltage at terminal Ux for no-
voltage check or synchronism check. If the line voltages and bus voltages are all
larger than the value of voltage setting, the check mode is automatically turned to
synchronism check.
Relay will block reclose when any conditions occur, at the same time, it gives output
of “AR Lockout Alarm”.
a) Distance zone 1 operates when equipment has digital input of “CARRIER
FAIL”.
b) Distance zone 1 or pilot operates when the fault occur again after reclosing .
c) Distance zone 1 or pilot operates when equipment has digital input of “A/R
BLOCK ”.
45
CSC-162 Numerical Transmission Line Protection Equipment Manual
The CB closed state are detected according to trip and current, when two series of
autoreclose are set for one breaker and both of them are put into operation, it is
impossible for the second autoreclose to take place.
“ AR_CB3”
&
CB OPEN
“ INITIATE
3PH A/R” from
“ 1” to “ 0”
≥
≥
Distance trip
& T3p_AR Reclose
“ AR_3p mode”
“ AR_No check”
≥
“ AR_check Syn”
&
Syn condition meet
“ AR_check low U”
&
Low condition voltage
A/R BLOCK
46
CSC-162 Numerical Transmission Line Protection Equipment Manual
|Ia-Ib|or|Ib-Ic|
or|Ic-Ia|>0.15In
& “ T_BROKEN COND” Report&Alarm
CB OPEN
47
CSC-162 Numerical Transmission Line Protection Equipment Manual
48
CSC-162 Numerical Transmission Line Protection Equipment Manual
7. Operation
7.1 Safety precautions
During the equipment tests and start-up, the general safety regulations applicable to
electrical systems must be complied with. Failure to comply with these regulations
might cause harm to the working staff and damage to property. All the inspections
and tests must only be carried out by specially trained personnel.
• Check the enclosure shell has been grounded reliably and maintain electric
continuity to earth.
• The general safety regulations applicable to equipments must be strictly complied
with.
• Insert or pull out models must be strictly prohibited during the equipment tests
and operation.
• During operation, nobody is allowed to press the keyboard on the panel
optionally.
• During operation, nobody is allowed to operate the following commands:
▪ Test DO;
▪ Modification and write settings;
▪ Set up numbers of running CPU;
▪ Change setting zone;
▪ Change address used communication net.
49
CSC-162 Numerical Transmission Line Protection Equipment Manual
Front panel adopts little arc streamline and beelines sculpt, and function keys for
MMI are reasonably distributed in faceplate. Panel layout is shown in Figure 7-1.
CSC£ 1
- 62
Run
Oper at i on
Recl ose
Not Used
Not Used
Not Used
Not Used QUI T SET
Al ar m
SI O
F1 F2 F3 F4 + -
Press this key for loop display. Current screen can be fixed to be displayed
(there is a key mark on the right corner of screen, viz. orientating current screen),
press again to cancel orientating function. Press this key during menu operation to
cancel current operation to return the upper menu. Press this key to return normal
display state to operate other key.
50
CSC-162 Numerical Transmission Line Protection Equipment Manual
RESET : Used to reset LED of signal and output , return to loop display state.
Four shortcut keys and two function keys under LCD
<<F1>> Press one time, prompt Print the latest event report?
YES NO
If select YES, prompt Format of printed record wave Graph Data to select
graph format or data format to print.
Another function of key <<F1>> Press <F1> to turn screen page downward
to view set values.
<<F2>> Press one time, prompt Print set values of current setting zone?
Another function of key <<F2>> Press <F2> to turn screen page upward to
view set values.
<<F3>> Press one time, prompt Print sampled data?
<<F4>> Press one time, prompt Print device information and status?
<<+>> Function key —The number of setting group +1.
Press one time, prompt Select setting zone to switch:
Current setting zone:xx; Switch setting zone: xx.
<<—>> Function key, The number of setting group -1.
Press one time, prompt Select setting zone to switch:
Current setting zone:xx; Switch setting zone: xx.
SIO jack: 9-pin jack to connect external PC is dedicated interface of debugging
program “CSPC”.
51
CSC-162 Numerical Transmission Line Protection Equipment Manual
When alarm I (serious alarm) is issued, this light flash and all protections are
out of service, power supply for protection output is blocked.
52
CSC-162 Numerical Transmission Line Protection Equipment Manual
53
CSC-162 Numerical Transmission Line Protection Equipment Manual
Press QUIT+SET to enter into debugging menu for leaving factory. Input debugging
password, the menu is presented with 8 categories. Select one category to press
SET, more notation is given as shown in Tab.7.1-2.
Tab.7.1-2
Name Function Remarks
Setup CPU CPU1, CPU2…CPU8 Use UP or DOWN
View memory View CPU: MASETR Press SET
View type: EEPROM
Original address: 0000000
View length: 32
Clear Prompt Are you sure to clear Press SET to YES,
configuration configuration? QUIT to NO
Configure Prompt Are you sure to configure? Press SET to YES,
system QUIT to NO
System option Standard interface mode, display of Confirmed with √ and ×
channel info menu, clear configuration of
setting character, clear configuration of
main arrangements, big liquid crystal
mode, new protocol of CSC2000,
communication with CSN/2, print mode of
LON network, LON2 configured, LON1
configured, 485-1 configured, 485-2
configure, record of state quantity taking
byte as unit, transport event of 103
protocol with ASDV1, prohibit transporting
2000 report for Ethernet 1, prohibit
transporting 2000 report for Ethernet 2
Setup Panel LED 1 run, LED 2…LED 8 LED 2…LED 8, Set
LED holding or not holding
with key of UP or
DOWN
Setup Panel Back-light always on Confirmed with √ and ×
back-light Setup delay of back-light 00: 05 :00 Use UP and DOWN to
change time
54
CSC-162 Numerical Transmission Line Protection Equipment Manual
The setting procedure can be ended at any the time by the key “SET” or “QUIT”. If
you press the key “SET”, the display shows the question “choose setting zone”. The
range of setting zone is from 0 to 31. Confirm with the setting zone-key “SET” those
new settings shall be come valid now. If you press the key “QUIT” instead, all
alterations which have been changed since the last. Thus, erroneous alterations can
be made ineffective.
Tab.7-3
NO. Abbr. Unit Setting range
Meaning
(LCD Display)
1. I_abrupt Abrupt current A 0.01~20
2 Through current detect A 0.5~100
I_PS
power swing
3 Zero-sequence reactance No 0~8
Kx
compensation factor
4 Zero-sequence resistance No 0~8
Kr
compensation factor
5 Zero-sequence reactance No 0~8
Km compensation factor for
double line
6 Positive reactance of whole Ω 0.01~200
X_line
line
7 Positive resistance of Ω 0.01~200
R_line
whole line
8 Line length Line length km 0.1~999
9 U_PRIMARY Primary rated voltage kV 30~300
10 CT_PRIMARY Primary rated current kA 0.3~5
11 CT_SECOND A 1 or 5
Secondary rated current
ARY
12 Zone 1 Resistance of earth Ω 0.01~200
R1_pe
distance
13 Zone 1 Reactance of earth Ω 0.01~300
X1_pe
distance relay
14 Resistance of earth Ω 0.01~200
R2_pe
element
15 Reactance of earth Ω 0.01~300
X2_pe
distance relay for Z2
16 Resistance of earth Ω 0.01~200
R3_pe
element
17 Reactance of Z3 earth Ω 0.01~300
X3_pe
distance relay
18 Resistance of Ground Ω 0.01~200
R4_pe
element
55
CSC-162 Numerical Transmission Line Protection Equipment Manual
56
CSC-162 Numerical Transmission Line Protection Equipment Manual
b) Binary setting
57
CSC-162 Numerical Transmission Line Protection Equipment Manual
1) The setting values are all secondary values if there is no special note.
Impedance setting is set according to positive impedance of line. Zero-
sequence current is 3I0.
2) I_abrupt: 0.2In is commonly recommended.
3) In general, the primary value of settings “I_abrupt, I_PS” must be consistent
of both sides of one line. However, for some special instance, if the sensitivity
difference between protections of both sides is too large, the settings of both
sides may also be different.
4) “I_PS”: Set by avoiding the maximum load current.
5) Reactance compensation factor: Calculated based on the actual line
parameters, setting value ought to be less than or close to calculation value.
KX = (X0-X1 ) / 3X1
6) Resistance compensation factor: Calculated based on the actual line
parameters, setting value ought to be less than or close to calculation value.
58
CSC-162 Numerical Transmission Line Protection Equipment Manual
59
CSC-162 Numerical Transmission Line Protection Equipment Manual
with sensitivity and the matched requirements for terminal faults that protect
equipment locate line.
18) Reactance and delay time of 4th ground distance relay: Set to be satisfied
with sensitivity and the matched requirements for terminal faults that protect
equipment locate line.
19) Zone 1 Resistance of earth distance: Set to avoid load impedance. As the
setting range of ph-ph resistance component is usually set to be rather large
due to avoiding load impedance, resistance setting employed by 1st zone ph-
ph distance relay is lessened relatively on the basis of its set setting, whose
basic principle is that it is set according to ph-ph fault with 15Ω path
resistance near bus for short line and not being larger than half setting of 1st
zone ph-ph reactance for long line. The detail calculation is shown as below.
Rx = min{ R1_pp, max{ X1_pp/2, 15/LZ+ R_line }, 8 X1_pp }
Where, R1 ─actual used setting of 1st zone ph-ph resistance
R1_pp─set setting of ph-ph resistance
X1_pp─set setting of 1st zone ph-ph reactance
LZ: Convert coefficient of primary impedance and secondary impedance.
Compare between ratio of VT and that of CT. Resistance 25Ω is referred to
the primary value.
R_line ─resistance component of positive impedance of full line
8XX1─ the point of intersection created by down bias of impedance
characteristics at the first quadrant and axis R in complex plane.
Note: R1 is obtained by the relay itself calculation according to the above
formula.
20) Reactance of 1st ph-ph distance relay: according to 0.8~0.85 times of
positive reactance of full line, it must be lessened properly for lines with
mutual inductance.
21) Reactance and delay time of 2nd ph-ph distance relay: Set to be satisfied
with sensitivity and the matched requirement for terminal fault that protect
equipment locate line.
22) Reactance and delay time of 3rd ph-ph distance relay: Set to be satisfied
with sensitivity and the matched requirement for terminal fault that protect
equipment locate line.
23) Reactance and delay time of 4th ph-ph distance relay: Set to be satisfied with
sensitivity and the matched requirement for terminal fault that protect
equipment locate line.
24) T_PS NOBLOCKING: Time Power Swing no blocking. Distance trip that it
don’t need open condition after relay startup for “T_PS NOBLOCKING”.
60
CSC-162 Numerical Transmission Line Protection Equipment Manual
25) Current of the zero-current relay: Set to avoid the maximum zero-current at
ground fault of current line end.
26) Settings of inverse time zero-current relay: Standard inverse time curve is
recommended.
27) “ψ_AR”: The permissive biggest phase differences between bus voltage and
line voltage under synchronization check mode.
28) Current threshold of zero-current auxiliary pickup element need not be set
independently, which is created automatically considering sensitivity
coefficient according to the minimum of the settings of fourth stage of zero-
current and pilot zero-current.
29) “I_CBF”: Startup Current of Breaker FAIL, The setting is phase current.
61
CSC-162 Numerical Transmission Line Protection Equipment Manual
abrupt current startup element has been operating for 150ms or loss of
stability detector operates. If the bit is set to “off”, zone distance relay is
enabled from startup to whole system reset.
7) Zero protection function enabled: definite time and inverse time zero current
can separately enabled.
8) Inverse time zero-current direction enabled: If this bit is set to “on”, inverse
time zero-current trip when fault occur at forward direction. If this bit is set to
“off”, inverse time zero-current can trip whatever fault occurs at forward
direction or inverse direction.
9) Over current protection function enabled: definite time and inverse time over
current can separately enabled.
10) Inverse time over current direction enabled: If this bit is set to “on”, inverse
time over current trip when fault occur at forward direction. If this bit is set to
“off”, inverse time over current can trip whatever fault occurs at forward
direction or inverse direction.
11) Bits of no check enabled, lower voltage check enabled and synchronization
check enabled: All of these three modes are autoreclosure check modes, if
anyone of them is set to “on”, the others must be set to “off”.
62
CSC-162 Numerical Transmission Line Protection Equipment Manual
7.4.1Event reports
63
CSC-162 Numerical Transmission Line Protection Equipment Manual
64
CSC-162 Numerical Transmission Line Protection Equipment Manual
Tab. 7-8a
No. Report Detail Solutions
1 Communication Communication CPU working abnormlity or CAN
Fail failure network communication error.
Check CPU working status, or
check CAN network on backboard.
2 DevPara Discord Device Solidify parameter once more, and
parameter power on again, this alarm should
discordance disappear
3 SetGroup Setting group Switch setting zone once more,
Discord discordance and power on again, this alarm
should disappear
4 Setting Discord Setting Solidify setting once more, and
discordance power on again, this alarm should
disappear
5 Connector Connector On or off strap once more, and
Discord discordance power on again, this alarm should
disappear
LON1 Comm Fail LON1 If LON1 need not be configured,
6 Communication cancel configuration of LON1 from
failure system option menu of debugging
menu for leaving factory, and
power on again. This alarm should
65
CSC-162 Numerical Transmission Line Protection Equipment Manual
66
CSC-162 Numerical Transmission Line Protection Equipment Manual
Before the device leaves factory, zero drift and calibration have been regulated,
only examination needs in locale. To examine calibration, enter into measuring
quantities or analog quantities menu at first, then enter into analog quantities menu
to do it. If they don’t meet requirements, regulate them according to the following
methods. Notice to increase the setting value of startup elements.
To regulate zero drift, disconnect the device with testing instrument or standard
source to ensure not any input in AC terminal of the device. Enter into main menu—
testing—AdjDrift, select all, and confirm it, then zero drift regulation can be
performed. If regulation succeeds, report “AdjDrift OK”. After this, select main
menu—testing—ViewDrift, current channel must be less than 0.1A (rated value of CT
67
CSC-162 Numerical Transmission Line Protection Equipment Manual
5A) or 0.02A (rated value of CT 1A), voltage channel must be less than 0.1V.
Connect input terminals of voltage UA, UB, UC and UX together, and connect UN
and UX’ together, employ testing instrument with grade 0.5 and the above whose
outputs UA and UN are connected to protection terminals X3-a10 and b10. Current
outputs of testing instrument are connected to protection terminals X3-a1 and b4,
and current terminals of the protection are in series by polarity terminal. Enter into
main menu—testing—AdjScale, press keys <<up down left right>>and <<SET>> to
select all, set the regulation value to In and 50V, output AC quantities from testing
instrument to the protection system, then confirm these to execute. If fail to operate,
LCD displays analog channel error and the number of error channel. Check whether
connection, standard value and version are right or not.
After finishing calibration and zero drift regulation, measure linear error using
testing instrument with grade 0.5 and the abover, and write down testing result.
Requirements: For secondary rated current 5A of CT, input currents 25A, 10A (the
lasting time of the abover two is unallowed to exceed 10s), 2A, 1A and 0.4A
respectively. For secondary rated current 1A of CT, input currents 5A, 2A, 0.5A, 0.2A
and 0.08A. Supply voltage 60V, 30V, 5V, 1V and 0.4V respectively. Observe LCD
display or enter into main menu—testing—ViewScale, ask that the difference
between LCD display value and external meter is less than 0.1V for 0.4V and 1V of
voltage channel, the others are less than 2.5%, and current channel error is less than
0.02In for 0.08In and 0.2In, the others are less than 2.5%.
Switch on DC power supply, the setting steps are described as follows to initialize
CPU.
Press “QUIT” and “SET” at the same time, enter into debugging menu.
a) Enter into the menu of “CPU setup”, enable CPU1 press the key of SET to save.
And energize the device once again.
b) Enter main menu- Set Time, use square keyboard to set clock to current time.
Then return to the normal display LCD screen, observe whether the running clock is
normal or not. Cut off DC power supply for 5 min, then switch on, check the time and
date displayed in LCD screen to conform that the clock is running and nicety during
power turnoff.
68
CSC-162 Numerical Transmission Line Protection Equipment Manual
Tab. 7-9-a
Analog quality Type B Analog quality Type B Analog quality Type B
Ia √ Ua √ Ia R ×
Ib √ Ub √ Ib R ×
Ic √ Uc √ Ic R ×
3I 0 √ 3U0_COUNT √ 3 I0 R ×
IN √ Ux √
Tab. 7-9-b
Name description CSC-162
Relay Startup Relay startup √
Three Phase Trip A-phase trip √
69
CSC-162 Numerical Transmission Line Protection Equipment Manual
Note: where “√” means that the corresponding input is selected while “×” is not
selected, blank means none.
Enter into main menu-setup-SetPrint-Print Mode, press SET to display the
following:
Print Mode
AutoPrt RecValue √
PrintContWd √
RecPrintMode Grap
RelayTestOn,PrtRec X
If “Print record automatically” is set to “√”, record wave will be printed after fault. If it
is set to “×”, only fault reports will be printed while record wave will not, and record
wave need to be fetched. If Print control word is set to “√”, contents of control word
can be printed, if “×”, contents of control word cannot be printed. Print format of record
data can be set to format of “wave” or “data” with <<UP>> and <<DOWN>> keys.
The recommended setup is “Print record automatically”, “Print control word” and “Print
format of record data” set to wave. If the protection operating results have some
questions, suggest that set “Print format of record data” to “data” at first, then,
print a record wave again (or use shortcut key F1 to directly print the latest one
of record data), after that, device testing can be followed. This can avoid losing
data, and causing disadvantage for furthermore analysis.
J) Check version of software
Enter into main menu—OpStatus—EquipCod, write down the device type,
version of each software and code of CRC, check the version consistent with the
valid version.
k) Check print function
1) main menu—Print—ProtSet Enter into this menu, select setting zone to print
70
CSC-162 Numerical Transmission Line Protection Equipment Manual
The function of the binary inputs and outputs represented in the general diagrams
relate to the factory settings. The assignment of the inputs and outputs of the internal
functions can be rear ranged and thus adapted to the on-site conditions.
a) Enter into main menu—OpStatus—DI, check the current state of each digital
input.
Connect +110V or +220V for X6:c2~c26 terminals and Connect +24V for
X6:a2~a26 terminals shown in Tab.11 as bellow, the corresponding inputs displayed
on the faceplate are valid. If certain input is error, check the corresponding optical
isolator, resistance etc are false welded, welded in reverse, or damaged.
Tab. 11
Name of input description DC voltage Terminals
RESET Reset signal +24V X6:a26
CB OPEN Input of circuit breaker open DC + X6: c10
A/R BLOCK Blocking auto reclose DC + X6: c26
INITIATE 3-PH A/R Initiate three phase reclose DC + X6: c22
B/LBB OPTD Input of other relay action DC + X6: c20
CARR RECIEVED Input of signal DC + X6: c18
DIRECT TRIP RECV Input of direct trip DC + X6: c24
CARRIER FAIL Input of carrier fail DC + X6: c16
Input of initiate three phase DC + X6: c12
START CBF 3-PH
circuit breaker failure
Input of blocking remote +24V X6: a22
REM ACCESS BLK
control
RELAY TEST Test relay +24V X6: a24
71
CSC-162 Numerical Transmission Line Protection Equipment Manual
Enter into main menu—Test Do to performs digital output test. When digital
output test is made, the contacts of the corresponding relay ought to operate with
lighting signal while other contacts do not operate. Press button RESET on the
faceplate to reset the drived output. Test results should be consistent with the
following table.
The output test of CSC-162 is shown in Tab.13
Tab. 13
NO. Item Contacts for Panel Lights to be in To be displayed Conclusion
connection ON status on MMI
ALARM I X9:c22-a22 Flash of “Run” Test DO OK
ALARM I
1 X9:c24-a24 lamp
X6:c30-a30 Flash of “Alarm”
X6:c32-a32 lamp
Power ON of X6:c32-a32 Flash of “Alarm”
equipment after OFF
X9:c22-a22 lamp
2 ALARM II X9:c26-a26 Flash of “Run” Test DO OK
ALARM II
X9:c28-a28 lamp
Light-on of
“Alarm” lamp
Power ON of X9:c26-a26 Light-on of
equipment after OFF
“Alarm” lamp
3 3- Phase Trip X7:a4-a16 Flash of “Run” Test DO OK
3- Phase Trip
X7:c4-c16 lamp
X8:c22-a22 Light-on of
X8:c24-a24 “Operation” lamp
X9:c16-a16
Power ON of X8:c22-a22 Light-on of
equipment after OFF
“Operation” lamp
72
CSC-162 Numerical Transmission Line Protection Equipment Manual
73
CSC-162 Numerical Transmission Line Protection Equipment Manual
Power ON of X10:c26-a26
equipment after OFF
11 U/V_O/V-2 X10:c30-a30 Flash of “Run” Test DO OK
U/V_O/V-2
X10:c32-a32 lamp
Power ON of X10:c30-a30
equipment after OFF
12 Start 3-PH CBF X10:c14-a14 Flash of “Run” Test DO OK
Start 3-PH CBF
X10:c16-a16 lamp
X10:c22-a22
X10:c24-a24
Power ON of X10:c22-a22
equipment after OFF
13 AR Lockout Alarm X8:c10-a10 Flash of “Run” Test DO OK
AR Lockout
X8:c12-a12 lamp Alarm
Power ON of N/A
equipment after OFF
14 VT Fail X8:c14-a14 Flash of “Run” Test DO OK
VT Fail
lamp
Power ON of N/A
equipment after OFF
15 Broken Conductor X8:c18-a18 Flash of “Run” Test DO OK
Broken
lamp Conductor
Power ON of N/A
equipment after OFF
74
CSC-162 Numerical Transmission Line Protection Equipment Manual
Power ON of N/A
equipment after OFF
17 CARR Received X9:c10-a10 Flash of “Run” Test DO OK
CARR
X9:c12-a12 lamp Received
Power ON of N/A
equipment after OFF
18 Direct Trip RECV X9:c18-a18 Flash of “Run” Test DO OK
Direct Trip
X9:c20-a20 lamp RECV
Power ON of N/A
equipment after OFF
19 Weak End Infeed X9:c32-a32 Flash of “Run” Test DO OK
Weak End
lamp Infeed
Power ON of N/A
equipment after OFF
20 PSB Alarm X9:c18-a18 Flash of “Run” Test DO OK
PSB Alarm
lamp
Power ON of N/A
equipment after OFF
Note:
1. In the status of output drive, push RES button and relevant lights are off, relevant normally open contacts
switch off and normally close contacts switch on.
Short b1~b4 of AC module X3, IA, IB, IC and IN outputs of testing instrument are
75
CSC-162 Numerical Transmission Line Protection Equipment Manual
connected to terminals X3-a1, X3-a2, X3-a3 and X3-a4 of the device, input rated
current and three-phase symmetry voltage 50 via a11, a10, b10 and b11 of X3
respectively, short b9 with b11 and a9 with a11, each phase voltage leads each
phase current phase angle 60°respectively, check LCD loop display or enter into
main menu—OpStatus—Measure to view, phase difference of A-, B-, and C-phase
voltage must be 120°, and phase difference of A-, B-, and C-phase current must be
120°. One phase current must lag the corresponding phase voltage 60°(angle error ≤
3°). Otherwise, check the device of AC module connection.
Input three-phase symmetry voltage 50V, and rated current only to phase A which
lags phase A voltage 60°, observe the display of amplitude and angle of 3I0 which
must be the same as IA, otherwise, check the device of AC module connection.
The test is performed according to the method simulating sudden faults. Before
simulating faults near bus, the rated voltage must be given at first, and fault current is
I, fault lasts 100-150ms.
Input settings according to the setting advice note or typical settings and write
them to certain zone at first. Then make tests according to Tab.14.
Tab.14
Relay Fault type Fault analog Operation Remark
quantities
Distan Simulate A, B, C to U=m*I* Xn_pe Note: enable
ce ground (1+KX) Reliable operation zone 1, 2 or 3
relay instantaneous m=0.95 Reliable non- of distance
fault, check zone m=1.05 operation relay
1, 2, and 3 of m=0.7 For zone 1 respectively, in
ground distance (RD=0) tdz≤30ms. For zone the equation,
relay, mentioned in 2 and 3, error n=1, 2, 3, KX
note (d) (I=In) between tdz and the is residual
settings ≤20ms compensation
coefficient of
reactance
component.
Xn_pe and RD
are the
reactance and
resistance
settings of
ground
distance relay.
Xn_pp and RX
are the
reactance and
resistance
settings of
76 phase-to-
CSC-162 Numerical Transmission Line Protection Equipment Manual
The following items are only provided to be referred. Users should formulate the
corresponding rules for maintenance and operation according to the actual
situation in locale.
a) Check the setting lists inerrably, and then turn on DC power supply. Now the
green light - LED <Run> on panel is lit, other lights are extinguished. Under
normal conditions, LCD display on loop “year-month-day, hour: minute: second,
magnitude and phasor angle of analog quantities, channel state, current setting
zone: 00. autoreclose mode, synchronization check mode, charging finished.
Press <<SET>>to display main menu. Press one or several times <<QUIT>>
,exit current menu one times or step by step to return normal state of display.
Then re-check the clock by turning off DC power and then on.
77
CSC-162 Numerical Transmission Line Protection Equipment Manual
b) Connect currents (load current must be larger than 0.1In) and voltages to the
device, under normal state of loop display, press SET to enter into main menu,
then enter into every sub-menu to check whether the polarity and the phase
sequence of each analog input are correct or not. Verify the sampled data of the
protection in accordance with the actual ones.
c) Check the protection settings. Print each set of settings that are possibly
employed in the actual operating modes, in order to check them with informed
sheet of setting and backup debugging notes.
d) Note that carrier channel is perfect.
e) Check the digital inputs in accord with the practical state, and make note.
Especially notice that there is not display of “small hand” on the upper right of
LCD under normal conditions (that means test relay).
78
CSC-162 Numerical Transmission Line Protection Equipment Manual
8. Maintenance
8.1 Routine checks
• Measure resistance in turn between analog circuits and ground;
• Measure output voltage in every class;
• Check printer;
• Revise zero drift and scale;
• Verify alarm circuit;
• Verify binary input;
• Actual live tripping including circuit breaker;
• Check setting;
8.4 Repairs
• Users should not change modules circuit or backboard circuit in repair.
• It’s appropriate to change power board when power supply is fault.
• It’s suggested that power board should purchased per 4 or 6 years because it
can’t storage for a long time.
79
CSC-162 Numerical Transmission Line Protection Equipment Manual
corresponding LED of tripping signal is lit and MMI displays the newest operating
report. If auto re-closing operates to reclose, the “reclose” LED is lit. The operating
report, record report should be printed automatically and the detail notes must be
written down.
d) If the DC power supply disappears during operation quit the tripping strap at
first.
e) If alarm I occur during operation, the corresponding relay should be stop
employing, record the alarm message and inform the operator in charge of the
protection. Here, prohibit pressing the reset button. If alarm II occurs, record the
alarm message and inform the operator in charge of the protection to analyze and
handle it.
80
CSC-162 Numerical Transmission Line Protection Equipment Manual
b) There are three methods to input settings:(1) Use keyboard on panel, (2)
employ software tool of CSPC, (3) by automatically system.
c) Method to select running setting zone: Use the shortcut key on the bottom left
panel “+”, “—” to select or switch setting zone.
81
CSC-162 Numerical Transmission Line Protection Equipment Manual
9. Storage
• Although protection equipment’s are generally of robust construction, they
require a careful treatment prior to installation on site, since they must be
carefully packed and unpacked, without applying any force to the equipment
and using suitable tools. Once supplied, the equipment must be thoroughly
inspected to ensure that they have not undergone shipping damages. If the
equipment are not immediately installed upon reception, they must be stored in
places free from dust and moisture, causticity in their original packing.
• The equipment must only be stored and carried in the special antistatic bag.
82
CSC-162 Numerical Transmission line equipment Manual
10. Ordering
CSC-162 Numerical Transmission Line Protection Equipment Manual
10.Appendix
A Terminal diagram
85
CSC-162 Numerical Transmission Line Protection Equipment Manual
86