Indent No. Annexure - 1 Technical Specification of Alstom / Areva/ Make Protection Relay With Case. 1. CDG31 As Below Specs 4 Nos
Indent No. Annexure - 1 Technical Specification of Alstom / Areva/ Make Protection Relay With Case. 1. CDG31 As Below Specs 4 Nos
Annexure -1
Contact
CDG61EG101ZMCH Configuration
1 – 2, 3 – 4 NO- S/R
IDMT 3 O/C RELAY WITH HI (CDG)
5 – 6 , 3 – 7 NO- S/R
Model No : CDG61EG101ZM(M) (CAG)
CDG61/CAG17(MRK-III)
APPLICATION - 3 O/C
BURDEN / D.M.T - 3 VA / 3 SEC.
9-10 CT
C.T. SECONDARY - 5 AMP C.T. CONNECTION
CASE SIZE - 3D HORZ.
CONTACTS (S/R OR H/R) - 2 N/O S/R
FLAG - YES
FREQUENCY - 50 HZ
HIGH SET TYPE - CAG17
HIGHSET CONTACTS - 2M S/R
HIGHSET O/C SETTING - 12.5 - 100 Amps.
MOUNTING - FLUSH
O/C SETTING - 2.5 - 10 Amps.
NAME PLATE - AS PER STANDARD
Outline Diagram AS PER STANDARD
Wiring Diagram AS PER CONTACT CONFIGURATION
3) CDG21 as below specs………………………………2 Nos
Contact
CDG21AF104ZMCH Configuration
1 – 2, 3 – 4 NO- S/R
1 POLE INV.TIME E/F RELAY WITH IN (CDG)
5 – 6 , 3 – 7 NO- S/R
Model No : CDG21AF104ZM(M) (CAG)
CDG21/CAG17(MRK-III)
APPLICATION - E/F
BURDEN / D.M.T - 3 VA / 3 SEC.
9-10 CT
C.T. SECONDARY - 5 AMP C.T. CONNECTION
CASE SIZE - 1D V 10T
CONTACTS (S/R OR H/R) - 2 N/O S/R
E/F SETTING - 0.5 - 2 Amps.
FLAG - YES
FREQUENCY - 50 HZ
HIGH SET TYPE - CAG17
HIGHSET CONTACTS - 2M S/R
HIGHSET E/F SETTING - 5 - 40 Amps.
MOUNTING - FLUSH
NAME PLATE - AS PER STANDARD
Outline Diagram AS PER STANDARD
Wiring Diagram AS PER CONTACT CONFIGURATION
Contact
CDG31FF001SACH Configration
NON DIRECTIONAL INV TIME 3O/C 1 – 2, 3 – 4 NO- S/R
Model No : CDG31FF001SA(M)
CDG31
APPLICATION - 3 O/C
BURDEN / D.M.T - 3 VA / 3 SEC.
5-6, 7-8, 9-10 CT
C.T. SECONDARY - 5 AMP C.T. TERMINAL
CASE SIZE - 3D VERT.
CONTACTS (S/R OR H/R) - 2 N/O S/R
FLAG - YES
FREQUENCY - 50 HZ
MOUNTING - FLUSH
O/C SETTING - 2.5 - 10 AMPS.
NAME PLATE - AS PER STANDARD
Outline Diagram AS PER STANDARD
Wiring Diagram AS PER CONTACT CONFIGURATION
5) CDG11 as below specs………………………………2 Nos
Technical Specifications
Model No CDG11AF004SACH
CDG11
APPLICATION - E/F
BURDEN - 3VA / 3 SECS.
C.T. SECONDARY - 5 AMP C.T. 9-10 CT TERMINAL
CASE SIZE - 1D V 10T
CONTACTS (S/R OR H/R) - 2 N/O S/R
E/F OR U/V SETTING - 0.5 - 2 Amps.
FLAG - YES
MOUNTING - FLUSH
O/C OR O/V SETTING - NOT APPLICABLE
NAME PLATE - AS PER STANDARD
Outline Diagram AS PER STANDARD
Wiring Diagram AS PER CONTACT CONFIGURATION
Contact
VAGM22AF77G / VAGM22AF72G Configration
INST. VOLTAGE RELAY WITH ADJ. SETTING 1-2, 3-4 N/C
Technical Specifications 5-6 N/O
Model No VAGM22AF77G
VAGM22
APPLICATION - U/V
CASE SIZE - 1D V 10T
CONTACTS (S/R OR H/R) - 1 N/O 2 N/C S/R
U/V SETTING - 40 - 80% U/V
EXTERNAL TRANSFORMER - NOT REQUIRED
FLAG - REVERSE FOR U/V
FREQUENCY - 50 HZ
MOUNTING - FLUSH
O/C OR O/V SETTING - NOT APPLICABLE
V.T/P.T SECONDARY - 110V AC 9-10
NAME PLATE-1 AS PER STANDARD
OUTLINE DRAWING AS PER STANDARD
WIRING DIAGRAM AS PER STANDARD
Contact
VAPM31AF21A Configration
FUSE FAILURE RELAY 1 – 2, NC, 3 – 4 NO
Technical Specifications
Relay Model No VAPM31AF22A
Relay type VAPM 31 Special
Case size 1D V 10T
Application Fuse Failure relay
PT VOLT : 5 - 6, 7 - 8,
Nominal voltage 110V ac 9 - 10
Frequency 50 Hz
Contacts 1 N/O 1 N/C S/R
Flag Yes
Mounting Flush
External Resistor (3-OFF) 1 K Ohms 35 W
NAME PLATE-1 AS PER STANDARD
OUTLINE DRAWING AS PER STANDARD
WIRING DIAGRAM AS PER STANDARD
Contact
VAA21ZG8323BCH Configration
TWO POLE VOLTAGE OPERATED AUXILIARY RELAY
Technical specification
Relay model no VAA21ZG8323BCH
Relay type VAA 21
Case size 1D H 20T
Nominal voltage 48V dc
1-2, 5-6, 17-18 N/O. 13-
Contacts - Unit A L.H 3 N/O 1 N/C S/R 14N/C
3-4, 7-8, 19-20 N/O. 15-
Contacts - Unit B R.H 3 N/O 1 N/C S/R 16N/C
Flag Yes
Mounting Flush
NAME PLATE-1 AS PER STANDARD
OUTLINE DRAWING AS PER STANDARD
WIRING DIAGRAM AS PER CONTACT
CONFIGERATION
VAA11YF0750BA
MULTIPLICATION AUXILIARY RELA
Technical specification
Relay model no VAA11YF0750BA
Relay type VAA 11
Case size 1/4 N,15T
Nominal voltage 250 V dc
Contacts - 6 N/O S/R
Flag NO
Mounting Flush
NAME PLATE-1 AS PER STANDARD
OUTLINE DRAWING AS PER STANDARD
WIRING DIAGRAM AS PER STANDARD
Information to bidders:
1. Any deviation in technical specifications shall not be acceptable and such
offers will be rejected.
2. Only those venders/ Manufactures quote those have complete Testing
facility at manufacture ‘s premises.
3. Technical catalogue should be submitted with their quotation.
4. Details of similar supplies shall be submitted with their quotation.