#317 - Fire Bells: Which One Do I Need? and How Many?
#317 - Fire Bells: Which One Do I Need? and How Many?
One warning before we go any further: if your building has a fire alarm system—and
that system relies on fire bells to encourage evacuation—you probably can’t use fire
bells for security, time-keeping, or other reasons. Different types of signals
(evacuation, intrusion, and so on) need distinct sounds to help people hear the
difference between a life-saving signal and something less essential.
DIY-ers (and others using wall-mounted bells for reasons other than fire safety) can
take a page from the fire protection world. Bells need to be louder than ambient
sound levels to be heard.
We’ve looked at this topic in some depth before. Each ten-decibel
increase represents a ten-fold increase in the sound’s power. An 80dB bell is ten
times as loud as a 70db one, 90dB is ten times as loud as 80dB, and so on. A rule of
thumb in fire protection is that the bell’s sound should be 15dB over average
ambient noise levels.
Remember, though, that the volume heard will decrease as listeners get farther
and farther away. A 96-decibel bell is only that loud from a fixed distance—usually
ten feet. It’s roughly six decibels quieter each time that
distance doubles (although the exact amount varies with the carpets, ceilings, and
other materials featured in the room).
Notice how the decrease between 1 and 2 meters (90 – 84 = 6) is the same between
2 and 4 meters (84 – 78 = 6). Another six-decibel decline takes place at 8 meters, 16,
32, and so on. Source: Wikimedia Commons
The numbers confirm common sense: louder bells can be
heard over (much) longer distances
Let’s consider how loud a 96-decibel bell will be at various distances. If you take
these figures—and compare them with the ambient noise levels in a given building
—you’ll find that a high-decibel fire bell can be heard at great distances in all but
the loudest rooms:
90dB at 20 feet
85 dB at 35.5 ft
80 dB at 63 feet
75 dB at 112 feet
70 dB at 200 feet
Compare that with typical ambient noise levels that are offered in table A.18.4.3
of NFPA 72: National Fire Alarm and Signaling Code (a volume of rules governing the
installation of fire alarm systems). These averages are inexact—but they’re a good
starting point, especially for consumers who use bells for other reasons.
Note, however, that especially loud noises may cause permanent hearing damage.
The National Institute for Occupational Safety and Health warns that more than 90
seconds’ exposure to 110-decibel sounds can be unsafe.
You don’t need to do the math: a “fire bell alarm clock” will wake you up.
Source: Instructables
Fire bell design varies to account for different
uses in fire safety
In this section, we’ll show how fire safety professionals use bells in two distinct ways:
Nearly every commercial building—and all but the smallest residential ones—must
have a local waterflow alarm. The same is true for standpipe systems (excluding
manual-dry types). The fire bells used to sound these alarms connect to the fire
riser and may be electric (standard bells) or mechanical (water motor gongs).
Type and quantity: what you need to know about choosing a waterflow alarm
NFPA 13: Standard for the Installation of Sprinkler Systems requires that waterflow
alarm devices be:
One final note: signs are recommended (but not required) when there’s no fire
alarm system in the building. The 2019 edition of NFPA 13 recommends that signs
reading “SPRINKLER FIRE ALARM: WHEN BELL RINGS CALL FIRE DEPARTMENT or
POLICE” be installed next to the bell or gong in a highly visible location.
Put your knowledge to use: browse our 120-volt fire bells, water motor gongs, flow
and pressure switches, fire alarm bell accessories, and even our “CALL 911” signs.
Low-voltage DC bells are used with fire alarm systems, with
quantity varying with the size of the room
Devices connected to fire alarm control panels typically rely on DC, or direct current,
power. They’re also typically low-voltage, running at 24 or even 12 volts. While the
panels themselves connect to standard 120-volt AC sources, the energy delivered
from the panel to notification appliances downstream is of the low-voltage variety.
When coupled with a fire alarm system, fire alarm bells serve as occupant
notification devices—audible and/or visual signals that facilitate evacuation.
Under NFPA 72: National Fire Alarm and Signaling Code, all audible notification
devices must:
Be listed (18.3.1).
Have a nameplate with their electrical requirements and select installation rules
(18.3.2).
Protected against any damage they may face with listed guards or covers (18.3.4).
Never cause ambient sound levels to exceed 110 decibels, even when all bells,
horns, or other devices are active (18.4.1.2).
This nameplate features marks that indicate the fire bell’s listing, electrical
requirements, decibel rating, and more.
These devices sound one of three signal types: public mode audible, private mode
audible, and sleeping area. All must be louder than the average ambient sound
level or the maximum sound level having a duration of at least 60
seconds (whichever is greater). Sections 18.4.3, 18.4.4, and 18.5.5 prescribe these
sound levels depending on the device’s location and use:
Still, as noise levels increase, the fire bell is effective over a reduced range. The
simplest fix may be to select a louder device. A 105-decibel bell can provide 90 dB
of sound from more than 55 feet away—more than double the distance of a 96-
decibel appliance.
Alternatively, contractors can provide more fire bells, so long as they keep in mind
that each added bell will increase these levels only slightly. Imagine a 20-foot by 20-
foot room. To reach 105 decibels of sound at the center (10 feet away from the
walls), you’d need: