Operate SINAMICS G115D With S7-1500 R/H System - As Switched S1 Device
Operate SINAMICS G115D With S7-1500 R/H System - As Switched S1 Device
Operate SINAMICS G115D With S7-1500 R/H System - As Switched S1 Device
Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG ("Siemens"). They are
non-binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.
Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens AG 2021 All rights reserved
foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.
Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.
Security information
Siemens provides products and solutions with Industrial Security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.
Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 4
1.1 Overview............................................................................................... 4
1.2 Components used ................................................................................ 5
1.3 Restrictions ........................................................................................... 6
2 Engineering ........................................................................................................ 7
2.1 TIA Portal project .................................................................................. 7
2.1.1 SIMATIC S7-1500R/H-system ............................................................. 7
2.1.2 SINAMICS GSD file .............................................................................. 9
2.2 Startdrive project ................................................................................ 12
2.2.1 Commissioning the SINAMICS G115D .............................................. 12
2.2.2 Online connection via Ethernet (S7 routing) ...................................... 13
3 SINAMICS Parameterization ........................................................................... 15
3.1 Set point behavior .............................................................................. 15
4 Appendix .......................................................................................................... 16
4.1 Service and support ........................................................................... 16
4.2 Industry Mall ....................................................................................... 17
4.3 Application support ............................................................................. 17
4.4 Links and literature ............................................................................. 17
© Siemens AG 2021 All rights reserved
1 Introduction
1.1 Overview
As of firmware version V2.8, the S7-1500R/H redundant system supports the
“Switched S1 device” function. This function of the CPU enables operation of
standard IO devices on the S7-1500R/H redundant system.
Standard IO devices are always assigned to both CPUs of the S7-1500R/H
redundant system. In contrast to an IO device with S2 system redundancy, a
standard IO device supports only one application relation (AR). The AR for the IO-
device is only set up once by the primary CPU.
NOTE SINAMICS G115D does not support S2 system redundancy and is connected as
switched S1 device to the R/H redundant system.
This FAQ describes the connection of a SINAMICS G115D to the S7-1500R/H
system.
SINAMICS G120 and SINAMICS 210 can be connected equally.
© Siemens AG 2021 All rights reserved
1.3 Restrictions
Restrictions Engineering system / Startdrive / STARTER
As Startdrive currently does not support multi assignment to several CPUs the
configuration must be divided between two projects:
• 1st project: S7-1500R/H redundant system with SINAMICS GSD file.
• 2nd project: SINAMICS with Startdrive/STARTER.
Restrictions R/H-system
For restrictions of the R/H-system please refer to the system manual:
https://support.industry.siemens.com/cs/ww/en/view/109754833
2 Engineering
2.1 TIA Portal project
2.1.1 SIMATIC S7-1500R/H-system
No Action
3. Assign the IP addresses of the CPUs in the settings of the CPU respectively.
e.g., default setting:
CPU1: 192.168.0.1
CPU2: 192.168.0.2
© Siemens AG 2021 All rights reserved
4. Recommended: Enable and assign the system IP address for the interfaces X1 and X2.
NOTE A GSD file must be used. Startdrive currently does not support multi assignment.
SINAMICS G115D GSD file can be downloaded here:
https://support.industry.siemens.com/cs/ww/en/view/109784461
2. Configure the SINAMICS with the desired telegram in the device view.
No Action
3. Go into the network view and right click “Not assigned” and click on “Assign to new IO controller”
5. Navigate to the properties of the interface and assign the desired IP address and PROFINET
device name. e.g.: “192.168.0.115” and “sinamics-g115d”
No Action
6. Navigate to “Advanced Options” → “Media redundancy” and set the media redundancy role to
“Client”:
7. In „Advanced Options“ → „Real time settings“ set the accepted update cycles factor to the value
TIA Portal is requesting.
© Siemens AG 2021 All rights reserved
NOTE As the configuration is divided between two projects make sure that the IP
address, PROFINET device name and the configured telegram match in the S7-
1500R/H TIA portal project and in the Startdrive project!
Figure 2-1 IP address and PROFINET device name must match in both projects.
© Siemens AG 2021 All rights reserved
Figure 2-2 Configured telegram must match in both projects. e.g. Standard telegram 1
If you want to access the SINAMICS via Ethernet (Startdrive) when it is connected
to the R/H system and you are not using a switch, then you can use S7 routing via
the second interface of the R/H CPU (X2).
1. Connect your PG/PC to the second interface of the R/H CPU (X2).
2. Check the ‘S7 subnet ID’ in the S7-1500R/H system project:
© Siemens AG 2021 All rights reserved
3. Insert a ‘Dummy’-CPU with at least two interfaces (e.g. a S7-1515-2 PN) in the
Startdrive project, connect the SINAMICS with the CPU and set the ‘S7 subnet
ID’ to the same value. Additionally, add a subnet on the second interface (X2).
4. Check that the IP addresses of both, the R/H CPU and the ‘Dummy’-CPU,
match: e.g.
X1: 192.168.0.1
X2: 192.168.1.1
5. When choosing the interface to go online, choose the added second subnet of
the ‘Dummy’-CPU (PN/IE_2) and the CPU will automatically be set as ‘1st
gateway’.
© Siemens AG 2021 All rights reserved
6. Go online.
3 SINAMICS Parameterization
3.1 Set point behavior
If the primary CPU fails or is switched to STOP, the S7-1500R/H redundant system
disconnects the AR between the primary CPU and the standard IO device.
The redundant system has no access to the inputs and no control over the outputs
of the SINAMICS G115D until the new primary CPU has set up an AR to the
SINAMICS.
The status of the outputs of the SINAMICS in the meantime depend on the
configured message type of F08501: PROFINET: Setpoint timeout.
With changing the message type to an alarm, the last received set point freezes
until the new AR is set up.
Table 3-1 Parameterization of message type
Parameter Value
p2118[0] 8501
p2119[0] [2] Alarm (A)
© Siemens AG 2021 All rights reserved
Danger to life
When changing the message type to an alarm the axis keeps moving even with a
setpoint timeout. This can cause serious injury or death to persons in the danger
WARNING zone.
Take suitable measures, e.g., emergency stop or emergency off.
With the "Switched S1 device" function, the new primary CPU establishes the AR
to the SINAMICS again. “OB 86” is called for each return of an IO device. The
outputs of the SINAMICS are then controllable again.
For more information about “OB86” see S7-1500R/H manual:
https://support.industry.siemens.com/cs/ww/en/view/109754833
4 Appendix
4.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
support.industry.siemens.com
Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts.
Please send queries to Technical Support via Web form:
siemens.com/SupportRequest
© Siemens AG 2021 All rights reserved
Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc