Prometer: Precision Metering Series
Prometer: Precision Metering Series
Application Features
Energy transfer measurement and reconciliation 0.2S/0.5S accuracy for active and reactive measurement
Power plants, feeder monitoring, grid substations, Wide-range dual auxiliary supply with options for AC/DC
wind turbines, industrial and commercial premises and self-power (VT powered)
On-line monitoring of energy exchange at various Power quality features including THD, sag, swell, voltage
interface points unbalance and interruption recording
Energy accounting, automation and system integration Dynamic error compensation for CT/VT
Transformer/Line loss adjustment (Copper and Iron losses)
Intuitive graphical display including vector diagram, wave
Benefits
forms and bar chart for consumption
Minimal integration cost through multiple
Remote configuration of communication ports
communication interfaces
Simultaneous DLMS and MODBUS over Ethernet port
Suitable for diverse applications through wide-range
Support of meter reading / display over field replaceable
voltage, current and auxiliary supply inputs
battery
Support of industry standard DLMS and MODBUS meter
Dual loggers for energy and instantaneous parameters
reading protocols
Flexible time-of-day tariff, maximum demand support,
Meter reading and display viewing under power outage
DST (Daylight saving time) support with automatic billing
Field replaceable hot pluggable communication modules
dates
Multi-lingual support on display (Swedish,
Meter cover and terminal cover open detection
German and English)
RS232 port compatible with meter-powered modem
Prometer 100
The Prometer 100 offers various communication modules such as Rs232 with output to power up terminal modem, RS485 for multi-drop
connectivity and Ethernet for integrating into communication bus. The communication modules can be hot plugged in field and locally or
remotely configured for IDs, IP addresses. Multiple port opening on Ethernet allows for simultaneous communication over MODBUS and
DLMS through different clients. All communication ports can simultaneously transfer data at high speeds.
RS232/RS485
Converter
Server
Network switch
Ethernet Port LAN Switch
Telecom panel
WAN
Clients
Rs485 Network
Product options
Electrical
Connection type HV3/HV4/LV4
Measurement voltage range 57.7 V to 240 V (L-N), 100 V to 415 V (L-L) ±30%
Measurement current range 1-10 A (configurable)
Frequency 50/60 Hz ±5%
Burden with auxiliary / Self (VT) powered Current circuit:
< 0.1 VA/phase @ 1A
< 0.5 VA/phase @ 5A
Voltage circuit in case of Aux power:
< 0.1 VA/phase
Voltage circuit in case of internal / self power:
< 6 VA/phase
Accuracy Class 0.2S and class 0.5S
Maximum overload Voltage 1.5 times of nominal voltage continuously
2 times of nominal voltage for 0.5 second
Maximum overload current 1.5 times of Imax continuously
10 times Imax for 1 second
20 times Imax for 0.5 second
Compliance
Standards IEC 62052-11, IEC 62053-22, IEC 62053-23, IEC 62056-52, IEC 61010-1,
IEC 61010-2-030, CE, MID (EN 50470-1, EN 50470-3)
Environmental IP54
Operating temperature -10 °C to + 60 °C
Limit range of operation -25 °C to + 70 °C
Storage temperature -40 °C to + 80 °C
Temperature coefficient <0.3%/100C for class 0.5
Temperature coefficient <0.1%/100C for class 0.2
Indicator Six LEDs: 2 for metrology, 2 for pulse outputs, 2 for alarms/events
Connector type: standard RJ45 for all the ports except optical
Cewe Instrument AB
Box 1006 | SE-611 29 Nyköping | Sweden | Tel: +46 (0)155 775 00 | E: [email protected] | Fax: +46 (0)155 775 97 | www.ceweinstrument.se