Ieee-Std C57.13-2016
Ieee-Std C57.13-2016
Ieee-Std C57.13-2016
Instrument Transformers
Sponsored by the
Transformers Committee
IEEE
3 Park Avenue IEEE Std C57.13™-2016
New York, NY 10016-5997 (Revision of
USA IEEE Std C57.13-2008)
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13™-2016
(Revision of
IEEE Std C57.13-2008)
Sponsor
Transformers Committee
of the
IEEE Power and Energy Society
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Abstract: Electrical, dimensional, and mechanical characteristics are covered, taking into consideration
certain safety features, for current and inductively coupled voltage transformers of types generally used in
the measurement of electricity and the control of equipment associated with the generation, transmission,
and distribution of alternating current. The aim is to provide a basis for performance and interchangeability
of equipment covered and to assist in the proper selection of such equipment. Safety precautions are also
addressed. Accuracy classes for metering service are provided. The test code covers measurement and
calculation of ratio and phase angle, demagnetization, impedance and excitation measurements, polarity
determination, resistance measurements, short-time characteristics, temperature rise tests, dielectric tests,
and measurement of open-circuit voltage of current transformers.
Keywords: accuracy, current transformer, IEEE C57.13™, instrument transformer, primary winding,
rated secondary voltage, routine tests, secondary winding, type tests, voltage transformer
IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics Engineers,
Incorporated.
2
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Important Notices and Disclaimers Concerning IEEE Standards Documents
IEEE documents are made available for use subject to important notices and legal disclaimers. These
notices and disclaimers, or a reference to this page, appear in all standards and may be found under the
heading “Important Notice” or “Important Notices and Disclaimers Concerning IEEE Standards
Documents.”
Translations
The IEEE consensus development process involves the review of documents in English only. In the event
that an IEEE standard is translated, only the English version published by IEEE should be considered the
approved IEEE standard.
3
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Official statements
A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board
Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its
committees and shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures,
symposia, seminars, or educational courses, an individual presenting information on IEEE standards shall
make it clear that his or her views should be considered the personal views of that individual rather than the
formal position of IEEE.
Comments on standards
Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of
membership affiliation with IEEE. However, IEEE does not provide consulting information or advice
pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a
proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a
consensus of concerned interests, it is important that any responses to comments and questions also receive
the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and
Standards Coordinating Committees are not able to provide an instant response to comments or questions
except in those cases where the matter has previously been addressed. For the same reason, IEEE does not
respond to interpretation requests. Any person who would like to participate in revisions to an IEEE
standard is welcome to join the relevant IEEE working group.
Comments on standards should be submitted to the following address:
Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with
the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory
requirements. Implementers of the standard are responsible for observing or referring to the applicable
regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not
in compliance with applicable laws, and these documents may not be construed as doing so
Copyrights
IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws.
They are made available by IEEE and are adopted for a wide variety of both public and private uses. These
include both use, by reference, in laws and regulations, and use in private self-regulation, standardization,
and the promotion of engineering practices and methods. By making these documents available for use and
adoption by public authorities and private users, IEEE does not waive any rights in copyright to the
documents.
Photocopies
Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to
photocopy portions of any individual standard for company or organizational internal use or individual,
non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance
Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission
to photocopy portions of any individual standard for educational classroom use can also be obtained
through the Copyright Clearance Center.
4
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Updating of IEEE Standards documents
Users of IEEE Standards documents should be aware that these documents may be superseded at any time
by the issuance of new editions or may be amended from time to time through the issuance of amendments,
corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
document together with any amendments, corrigenda, or errata then in effect.
Every IEEE standard is subjected to review at least every ten years. When a document is more than ten
years old and has not undergone a revision process, it is reasonable to conclude that its contents, although
still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to
determine that they have the latest edition of any IEEE standard.
In order to determine whether a given document is the current edition and whether it has been amended
through the issuance of amendments, corrigenda, or errata, visit the IEEE-SA Website at
http://ieeexplore.ieee.org/Xplore/home.jsp or contact IEEE at the address listed previously. For more
information about the IEEE SA or IEEE’s standards development process, visit the IEEE-SA Website at
http://standards.ieee.org.
Errata
Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL:
http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata
periodically.
Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter
covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to
the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant
has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the
IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may
indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without
compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of
any unfair discrimination to applicants desiring to obtain such licenses.
Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting
inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or
conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing
agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that
determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely
their own responsibility. Further information may be obtained from the IEEE Standards Association.
5
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Participants
At the time this IEEE standard was completed, the Requirements for Instrument Transformers Working
Group had the following membership:
The following members of the individual balloting committee voted on this standard. Balloters may have
voted for approval, disapproval, or abstention.
6
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Steven Snyder Jane Verner Barrett Wimberly
David Stankes David Wallace Jian Yu
David Tepen David Wallach Peter Zhao
Roger Verdolin D. Weers Xi Zhu
John Vergis Kenneth White
When the IEEE-SA Standards Board approved this standard on 29 January 2016, it had the following
membership:
Chuck Adams
Ronald W. Hotchkiss Mehmet Ulema
Masayuki Ariyoshi
Michael Janezik Yingli Wen
Ted Burse
Joseph L. Koepfinger* Howard Wolfman
Stephen Dukes
Hung Ling Don Wright
Jianbin Fan
Kevin Lu Yu Yuan
J. Travis Griffith
Annette D. Reilly Daidi Zhong
Gary Hoffman
Gary Robinson
*Member Emeritus
7
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Introducti
This introduction is not part of IEEE Std C57.13™-2016, IEEE Standard Requirements for Instrument Transformers.
This standard was prepared by the Instrument Transformer Subcommittee of the Transformers Committee
of the IEEE Power and Energy Society. The purpose of this standard is to cover the electrical, dimensional,
and mechanical characteristics and to take into consideration certain safety features, for current and
inductively coupled voltage transformers.
The changes in this revision of IEEE Std C57.13 include revised partial discharge requirements, the
addition of Annex B, covering bushing current transformers and two classes of instrument transformer
requirements have been introduced. In addition, this standard has been reorganized to make it more
understandable. The accuracy requirements from IEEE Std C57.13.6™ have also been incorporated into the
standard.1
1
Information on references can be found in Clause 2.
8
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Conten
1. Overview....................................................................................................................................................11
1.1 Scope...................................................................................................................................................11
1.2 Purpose................................................................................................................................................11
2. Normative references..................................................................................................................................12
3. Definitions..................................................................................................................................................12
4. General requirements..................................................................................................................................13
4.1 Service conditions................................................................................................................................13
4.2 Effect of air density on flashover voltage............................................................................................14
4.3 Frequency............................................................................................................................................15
4.4 Effect of altitude on temperature rise and effect of ambient temperature on permissible loading......15
4.5 Basic impulse insulation levels, dielectric tests, and outdoor instrument transformer creepage
distance and wet test..................................................................................................................................16
4.6 Temperature rise..................................................................................................................................19
4.7 Capacitance and dissipation factor requirements................................................................................20
4.8 Classification of tests...........................................................................................................................20
4.9 Construction.........................................................................................................................................22
6. Current transformers...................................................................................................................................30
6.1 Terms in which ratings shall be expressed..........................................................................................30
6.2 Standard burdens.................................................................................................................................30
6.3 Accuracy ratings for metering.............................................................................................................30
6.4 Accuracy ratings for relaying..............................................................................................................32
6.5 Continuous thermal current rating factors based on 30 °C average ambient air temperature.............34
6.6 Short-time current ratings....................................................................................................................34
6.7 Secondary winding-induced voltages..................................................................................................35
6.8 Nameplates..........................................................................................................................................36
6.9 Terminals.............................................................................................................................................36
6.10 Application data.................................................................................................................................36
6.11 Routine accuracy tests.......................................................................................................................39
7. Voltage transformers..................................................................................................................................40
7.1 Terms in which ratings shall be expressed..........................................................................................40
7.2 Standard burdens.................................................................................................................................44
7.3 Accuracy ratings..................................................................................................................................45
7.4 Thermal burden ratings........................................................................................................................45
7.5 Nameplates..........................................................................................................................................46
7.6 Terminals.............................................................................................................................................46
7.7 Short-circuit capability........................................................................................................................46
7.8 Application data...................................................................................................................................47
7.9 Induced voltage test.............................................................................................................................47
7.10 Routine accuracy tests.......................................................................................................................47
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
Conten
8. Test procedures applicable to instrument transformers..............................................................................47
8.1 Ratio and phase angle measurement and calculations.........................................................................48
8.2 Impedance, excitation, and composite error measurements................................................................49
8.3 Polarity.................................................................................................................................................52
8.4 Resistance measurements....................................................................................................................53
8.5 Dielectric tests.....................................................................................................................................55
8.6 Partial discharge measurement............................................................................................................57
Annex B (normative) Bushing-type current transformer (BCT) and special purpose window type current
transformers....................................................................................................................................................86
B.1 Introduction.........................................................................................................................................86
B.2 Scope...................................................................................................................................................86
B.3 General requirements..........................................................................................................................86
B.4 Continuous thermal ratings.................................................................................................................88
B.5 Short-time ratings................................................................................................................................90
B.6 Dielectric consideration......................................................................................................................90
B.7 Construction........................................................................................................................................90
B.8 Routine tests........................................................................................................................................92
B.9 Type tests............................................................................................................................................93
B.10 Installation.........................................................................................................................................93
B.11 Field tests..........................................................................................................................................94
B.12 Bushing linear coupler (BLC)...........................................................................................................94
10
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Standard Requirements for
Instrument Transformers
IMPORTANT NOTICE: IEEE Standards documents are not intended to ensure safety, security, health,
or environmental protection, or ensure against interference with or from other devices or networks.
Implementers of IEEE Standards documents are responsible for determining and complying with all
appropriate safety, security, environmental, health, and interference protection practices and all
applicable laws and regulations.
This IEEE document is made available for use subject to important notices and legal disclaimers.
These notices and disclaimers appear in all publications containing this document and may
be found under the heading “Important Notice” or “Important Notices and Disclaimers
Concerning IEEE Documents.” They can also be obtained on request from IEEE or viewed at
http://standards.ieee.org/IPR/disclaimers.html.
1. Overview
1.1 Scope
This standard is intended for use as a basis for performance and interchangeability of equipment covered,
and to assist in the proper selection of such equipment. Safety precautions are also addressed.
This standard covers certain electrical, dimensional, and mechanical characteristics, and takes into
consideration certain safety features of current and inductively coupled voltage transformers of types
generally used in the measurement of electricity and the control.
1.2 Purpose
The purpose of this standard is to provide the performance requirements for electrical system and test
interchangeability of current and inductively coupled voltage transformers. These transformers are for both
indoor and outdoor application.
This standard covers the requirements for Class 1 instrument transformers. For instrument transformers of a
nominal system voltage of 115 kV and above if Class 2 is required refer to IEEE Std C57.13.5™.1
1
Information on references can be found in Clause 2.
11
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
2. Normative references
The following referenced documents are indispensable for the application of this document (i.e., they must
be understood and used, so each referenced document is cited in text and its relationship to this document is
explained). For dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments or corrigenda) applies.
IEEE Std 693™, IEEE Recommended Practice for Seismic Design of Substations.
IEEE Std C37.04™, IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers.
IEEE Std C37.09™, IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a
Symmetrical Basis.
IEEE Std C57.12.00™, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power,
and Regulating Transformers.
IEEE Std C57.12.90™, IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and
Regulating Transformers.
IEEE Std C57.13.5™, IEEE Standard of Performance and Test Requirements for Instrument Transformers
of a Nominal System Voltage of 115 kV and Above.
IEEE Std C57.19.00™, IEEE Standard General Requirements and Test Procedure for Power Apparatus
Bushings.
3. Definitions
For the purposes of this document, the following terms and definitions apply. The IEEE Standards
Dictionary Online should be consulted for terms not defined in this clause.5
class 1 instrument transformer: An instrument transformer that is constructed and tested in accordance
with this standard.
class 2 instrument transformer: An instrument transformer that is constructed and tested in accordance
with IEEE Std C57.13.5™.
gapped core: A core where the magnetic core has an intentional gap filled with non-magnetic material.
2
IEC publications are available from the International Electrotechnical Commission (http://www.iec.ch/). IEC publications are also
available in the United States from the American National Standards Institute (http://www.ansi.org/).
3
IEEE publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854,
USA (http://standards/ieee.org/).
4
The IEEE standards or products referred to in this clause are trademarks of the Institute of Electrical and Electronics Engineers, Inc.
5
IEEE Standards Dictionary Online subscription is available at: http://ieeexplore.ieee.org/xpls/dictionary.jsp.
12
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
indoor voltage transformer: One that, because of its construction, shall be protected from the weather.
prescribed extinction voltage: The minimum voltage at which the reference partial discharge intensity
shall be met when the voltage applied to the transformer is gradually decreased without interruption from
the power frequency withstand voltage or pre-stress voltage value during the partial discharge test.
partial discharge inception voltage: The lowest voltage at which partial discharges exceeding a specified
level are observed under specified conditions when the voltage applied to the test object is gradually
increased from a lower value.
4. General requirements
Instrument transformers conforming to this standard shall be suitable for operation at their thermal ratings,
provided that the altitude does not exceed 1000 m.
The minimum ambient air temperature is –30 °C for outdoor applications and –5 °C for indoor
applications.
If the transformers are air cooled, the ambient temperature of the cooling air does not exceed 40 °C and the
average ambient temperature of the cooling air for any 24-hour period does not exceed 30 °C.6
Instrument transformers may also be given ratings for operation in 55 °C average ambient temperature,
with maximum ambient air temperature not exceeding 65 °C.
Instrument transformers may be applied at higher altitudes or higher ambient temperatures than specified in
4.1.1, but the performance may be affected and special consideration should be given to these applications
(see 4.2 and 4.4).
6
It is recommended that the average temperature of the cooling air be calculated by averaging 24 consecutive hourly readings. When
the outdoor air is the cooling medium, the average of the maximum and minimum daily temperature may be used. The value that is
obtained in this manner is usually higher than the true daily average by not more than 1/2 °C.
7
Notes in text, tables, and figures of a standard are given for information only and do not contain requirements needed to implement
this standard.
13
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Where conditions other than those discussed in 4.1.1 or 4.1.2 exist, they should be brought to the attention
of those responsible for the design and application of instrument transformers. Examples of these
conditions are as follows:
a) Damaging fumes or vapors, excessive or abrasive dust, explosive mixtures of dust or gases, steam,
salt spray, excessive moisture or dripping water, etc.
b) Abnormal vibrations, shocks, or tilting.
c) Ambient temperatures above 55 °C or below –30 °C.
d) Unusual transportation or storage conditions.
e) Unusual space limitations or restricted ventilation.
f) Unusual duty, frequency of operation, difficulty of maintenance, poor wave form, unbalanced
voltage, special insulation requirements, etc.
g) Applications in switchgear assemblies, including metal enclosed bus.*
h) Applications with high-voltage power circuit breakers.*
i) Applications with power transformers.*
j) Applications with outdoor bushings.*
k) For altitudes below sea level or buried underground.*
l) Seismic conditions: For seismic qualification methods refer to IEEE Std 693.
The effect of decreased air density is to decrease the flashover voltage for a given flashover distance. See
IEEE Std 4 for use of a correction factor.
The dielectric strength of air decreases as altitude increases. Dielectric strength that depends on air should
be multiplied by the proper altitude correction factor to obtain the dielectric strength at the required altitude
(see Table 1). For an altitude exceeding 3000 m, caution should be exercised.
14
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Table 1 —Dielectric strength correction factors for altitudes greater than 1000 m
a
An altitude of 4500 m is considered a maximum for instrument
transformers conforming to this standard.
4.3 Frequency
Instrument transformers shall be designed and rated for operation at a frequency of 60 Hz.
4.4.1 Loading of current transformers at less than rated current at high altitudes
Current transformers may be operated at altitudes greater than 1000 m without exceeding established
temperature limits provided the current is reduced below rated (or below rated times continuous thermal
current rating factor) by 0.3% for each 100 m that the altitude exceeds 1000 m.
Current transformers designed for 55 °C temperature rise above 30 °C average ambient air temperature
may be loaded in accordance with the curves shown in Figure 1 for any given average cooling air
temperature and continuous thermal current rating factor. The percent of rated primary current that can be
carried continuously without causing established temperature limits to be exceeded is given by the curves.
For example, a transformer with a continuous thermal current rating factor (RF) of 2.0 at 30 °C ambient
temperature can be used at approximately 150% of rated current at an ambient temperature of 55 °C.
Refer to Annex B for use of bushing-type current transformers in ambient temperatures of 90 °C in hot oil.
15
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
For safety reasons, voltage transformers can be operated at higher altitudes or higher ambient temperatures
only after consultation with the manufacturer, because a large percentage of the temperature rise may be
due to iron loss, which varies widely with design.
4.5 Basic impulse insulation levels, dielectric tests, and outdoor instrument
transformer creepage distance and wet test
An instrument transformer shall be assigned a basic impulse insulation level (BIL) to indicate the factory
dielectric tests that the transformer is capable of withstanding.
With the following exceptions, basic impulse insulation voltages, applied voltage test voltages for primary
winding insulation, and creepage distances and wet tests for outdoor instrument transformers are listed in
Table 2 and Table 3:
a) Applied voltage tests for primary winding insulation are not required on grounded-neutral-terminal-
type voltage transformers.
b) For insulated-neutral-terminal-type voltage transformers, the applied voltage test for primary
winding insulation shall be 19 kV on outdoor types with BILs greater than 110 kV. On indoor
types, and on outdoor types with BILs of 110 kV or less, the test voltage shall be 10 kV.
c) There is no BIL requirement on the neutral terminal of grounded-neutral- or insulated-neutral-
terminal-type voltage transformers.
d) The applied voltage test for secondary winding insulation and between multiple secondary
windings shall be 2.5 kV.
e) The applied voltage test for autotransformers for use in the secondary circuits of instrument
transformers shall be 2.5 kV.
f) The applied voltage test for the primary insulation of auxiliary instrument transformers (for use in
the secondary circuits of instrument transformers) shall be 2.5 kV.
16
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
NOTE 1—Average ambient cooling air temperature for 24-hour period degrees Celsius (maximum ambient air
temperature does not exceed average by more than 10 ºC).
NOTE 2—These curves are based on the assumption that average winding temperature rise is proportional to current
squared.
Figure 1 —55 ºC rise current transformer basic loading characteristics (in air)
17
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
18
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
NOTE 1—The definitions of light and heavy pollution levels are provided in IEEE
Std C57.19.100-2012.
NOTE 2—The creepage distance for composite insulator with silicone rubber
sheds has not been established. This standard recommends the use of the same
creepage distance as that for the porcelain insulator.
The limits of observable temperature rise in instrument transformers when tested in accordance with their
ratings shall be as given in Table 4, and the transformers shall be designed so that the hottest-spot winding
temperature rise above ambient will not exceed the values given in Table 4.
30 C ambient 55 C ambient
Terminals for use in air shall be designed so that their maximum operating temperature when tested with
their ratings do not exceed the values provided in Table 5.
19
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The capacitance and dissipation factor of the transformer shall be measured at power frequency at the
following test voltages:
10 kV
Maximum rated voltage
The test shall be performed before and after the dielectric tests. The increase of capacitance measured after
compared with that measured before the dielectric tests shall be less than the value produced by the
breakdown of one capacitive element.
These are the routine, type, and other tests that are necessary to assure that the design and construction of
the transformer are adequate to meet the specified requirements. The method of making tests shall be as
described in Clause 8 through Clause 13, or by equivalent alternative methods. Many references are
available as sources for the material in the preceding clauses. Those references referred to specifically are
listed by number in Annex A. Other references, which may be of general utility to the user of these clauses,
or of the complete standard, are also included in Annex A. Routine and type tests are in Table 6.
20
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Test requirements for current transformers and voltage transformers are summarized in Table 6.
Measurement or
Current transformers Voltage transformers
test
Test Test
Reference subclause Reference subclause
classification classification
Capacitance and
4.7 Rd 4.7 Rd
dissipation factor
4.5d), 4.5e), 4.5f), and 4.5a), 4.5b), 4.5c), 4.5d),
Applied voltage R R
8.5.3 4.5e), 4.5f), and 8.5.3
Partial discharge 8.6 R and 11.4 T R/T 8.6 R and 11.4 T R/T
Inter-turn
12.3 Ta —
overvoltage
Short-time thermal
11.1 and 12.1 T 11.1 and 13.1 T
rating
Wet voltage
withstand tests – for
11.5 T 11.5 T
outdoor instrument
transformers
21
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
These tests are to be performed subject to agreement between the producer and the user. Procedures for the
following tests can be found in IEEE Std C57.13.5:
Other tests are additional tests made for application information, for provision of specific data requested by
users, for verification of type capability, and so on. Examples of other tests are, but not limited to the
following:
4.9 Construction
The relative instantaneous polarity of terminals or leads shall be clearly indicated by permanent markings
that cannot easily be obliterated.
When the polarity is indicated by letters, the letter “H” shall be used to distinguish the leads or terminals
connected to the primary winding and the letter “X” (also “Y” and “Z,” etc., if multiple secondary windings
are provided) shall be used to distinguish the leads or terminals connected to the secondary winding. In
addition, each lead shall be numbered, for example, H1, H2, X1, and X2. If more than three secondary
windings are provided, they shall be identified as X, Y, Z, and W for four secondary windings; X, Y, Z, W,
and V for five secondary windings; X, Y, Z, W, V, and U for six secondary windings, and so on. H1 and
X1 (also Y1 and Z1, etc., if provided) shall be of the same polarity.
When multiple primary windings are provided, the leads or terminals shall be designated by the letter “H”
together with consecutive pairs of numbers (H1, H2, H3, H4, etc.). The odd-numbered leads or terminals
shall be of the same polarity.
When taps or leads are provided on the secondary winding(s), the leads or terminals shall be lettered as
required above and numbered X1, X2, X3, etc., or Y1, Y2, Y3, etc., with the lowest and highest numbers
indicating the full winding and the intermediate numbers indicating the taps in their relative order. When
X1 is not in use, the lower number of the two leads in use shall be the polarity lead. In the case of dual
primary ratios that are obtained by secondary taps, the X3 or Y3 terminal shall be common to both taps.
22
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
For 72 kV class instrument transformers and above a ground shield shall be provided between the primary
and secondary windings.
4.9.3 Symbols
23
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
24
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Accuracy classes for revenue metering are based on the requirement that the transformer correction factor
(TCF) of the voltage transformer or of the current transformer shall be within the specified limits when the
power factor (lagging) of the metered load has any value from 0.6 to 1.0, under specified conditions as
follows:
a) For current transformers, at the specified standard burden (see 6.2 for standard burdens) at 10% or
5% (see Table 10), and at 100% of rated primary current [also at the current corresponding to the
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
25
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
rating factor (RF) if it is greater than 1.0]. The accuracy class at a lower standard burden is not
necessarily the same as at the specified standard burden.
b) For voltage transformers, for any burden in voltamperes from zero to the specified standard burden,
at the specified standard burden power factor (see 7.2 for standard burdens), and at any voltage
from 90% to 110% of the rated voltage. The accuracy class at a lower standard burden of a
different power factor is not necessarily the same as at the specified standard burden.
It can be shown that a TCF at 0.6 power factor (lagging) of the metered load is as follows8:
TCF RCF (1)
2600
TCF = RCF (2)
2600
where
RCF is the ratio correction factor derived from 1 – (±Ratio Error/100). Note that for transformers
having negative ratio error the RCF will be greater than unity.
, ß is the phase angle, in minutes, for voltage transformers and current transformers, respectively.
The limits of transformer correction factor in standard accuracy classes shall be as shown in Table 8.
8 This is true of errors within the range of the standard metering accuracy
26
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Table 8 —Standard accuracy class for metering service and corresponding limits of
transformer correction factor and ratio correction factor [0.6 to 1.0 power factor (lagging)
of metered load]c
Voltage transformers
(at 90% to 110% Current transformers
Metering
rated voltage)
accuracy
class At 100% rated currenta At 10% rated current At 5% rated current
Minimum Maximum
Minimum Maximum Minimum Maximum Minimum Maximum
0.15S b
— — 0.9985 1.0015 — — 0.9985 1.0015
0.15b 0.9985 1.0015 0.9985 1.0015 — — 0.9970 1.0030
0.15N — — 0.9985 1.0015 0.9970 1.0030 — —
0.3S — — 0.9970 1.0030 — — 0.9970 1.0030
0.3 0.9970 1.0030 0.9970 1.0030 0.9940 1.0060 — —
0.6 0.9940 1.0060 0.9940 1.0060 0.9880 1.0120 — —
1.2 0.9880 1.0120 0.9880 1.0120 0.9760 1.0240 — —
a
For current transformers, the 100% rated current limit also applies to the current corresponding to the continuous thermal current rating
factor.
b
Previously defined in IEEE Std C57.13.6.
c
Other accuracy requirements may be specified and should be included on the nameplate.
5.4 Limiting values of ratio correction factor and phase angle for standard
accuracy classes
The limiting values of RCF are the same as those for TCF (see 5.2). For any known value of RCF for a
given transformer the limiting values of the angles derived from the expression in 5.2 are given as shown in
Equation (3) and Equation (4).9
in which TCF is taken as the maximum and minimum values, given in Table 8, for the specified accuracy
class.
These relations are shown graphically in Figure 2, Figure 3, and Figure 4 for current transformers, and
Figure 5 for voltage transformers.
9
This is true of errors within the range of the standard metering accuracy classes.
27
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Figure 2 —Limits for accuracy classes for current transformers for metering
In Figure 2, the accuracy requirements for 100% rated current also apply at the continuous thermal current
rating of the transformer.
Figure 3 —Limits for 0.15 accuracy class for current transformers for metering
In Figure 3, the transformer characteristics shall lie within the stated limits of the parallelogram at 5% and
100% of rated current. For current transformers, the 100% rated current limits also applies to the current
corresponding to the continuous thermal current rating factor, if it is greater than 1.0.
28
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Figure 4 —Limits for 0.3S and 0.15S accuracy classes for current transformers for
metering
In Figure 4, the transformer characteristics shall lie within the stated limits of the parallelogram from 5%
through 100% of rated current. For current transformers, the limit also applies to the current corresponding
to the continuous thermal current rating factor, if it is greater than 1.0.
29
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
6. Current transformers
a) Basic impulse insulation level in terms of full-wave test voltage (see Table 2).
b) Nominal system voltage or maximum system voltage (see Table 2).
c) Frequency (in Hz).
d) Rated primary and secondary currents (see 6.3, as well as Table 9 and Table 2).
e) Accuracy classes at standard burdens (see 6.3, 6.4, as well as, Table 8, Table 10, and Table 13).
f) Continuous thermal current rating factor based on 30 °C average ambient air temperature, unless
otherwise stated (see 6.5).
g) Short-time mechanical current rating and short-time thermal current rating (see 6.6).
Table 9 —Example of ratings for current transformers with one or two ratios
Standard burdens for current transformers with 5 A rated secondary current shall have resistance and
inductance according to Table 10 for metering and Table 13 for relaying.
A current transformer for metering shall be given an accuracy rating for each standard burden for which it
is rated (see Clause 5). The accuracy class may be stated for the maximum burden for which it is rated and
30
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
will imply that all other lower burdens shall also be in that class; e.g., 0.3 B-1.8 would imply 0.3 B-0.1, B-
0.2, B-0.5, B-0.9, and B-1.8. If the accuracy class given is specific only to that burden it is assigned, e.g.,
0.3 @ B-0.5, or a range of burdens, e.g., 0.3 @ B0.5-B0.9, then the accuracy class is not guaranteed for
other burdens unless specifically stated.
Electronic meters and connecting circuits may present a lower burden, thus affecting a current transformers
ratio and phase angle. A current transformer that meets a given accuracy class at B-0.1 and less may not
meet the same accuracy class when the application calls for burden power factor between 0.9 and unity.
“E” burdens shall be stated separately.
The metering accuracy rating applies only to the full secondary winding, unless otherwise specified (see
Table 11).
31
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
A current transformer designed for relaying purposes shall be given an accuracy rating according to Table
12.
32
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
6.4.1.1 C classification
Covers current transformers in which the leakage flux in the core of the transformer does not have an
appreciable effect on the ratio(s) within the limits defined in 6.4 with standard burdens outlined in Table
13, so that the ratio can be calculated in accordance with 9.1.1, 9.1.2, and 9.1.3.
6.4.1.2 T classification
Covers current transformers in which the leakage flux does have an appreciable effect on the ratio(s) within
the limits defined in Table 13 with standard burdens outlined in Table 13, such that it is not practical to
calculate the ratio.
The relay classification for C and T class is given in terms of the secondary terminal voltage, which the
current transformer will deliver to a standard burden at 20 times rated current without exceeding the limits
outlined in 6.4. The secondary terminal voltage ratings are based on 5 A nominal secondary current (100 A
at 20 times) and standard burdens as per Table 13.
33
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
6.4.1.4 X classification
User defined for a specific condition in which the minimum secondary excitation requirements are given as
follows:
The ratio error at rated current shall be as defined in 6.4. If only Ek is given, then the manufacturer will
establish Ik and Rct based on the necessary design required to meet Ek.
For requirements for Class TPX, TPY, and TPZ current transformers, refer to IEC 61869-2.
The relay accuracy class applies only to the full winding, unless otherwise specified. If transformers have C
classification on the full winding, all tapped sections shall be arranged so that the ratio can be calculated in
accordance with 9.1.1, 9.1.2, and 9.1.3.
6.5 Continuous thermal current rating factors based on 30 °C average ambient air
temperature
The preferred continuous thermal current rating factors are 1.0, 1.33, 1.5, 2.0, 3.0, or 4.0.
The short-time thermal current and short-time mechanical capabilities are not independent.
The short-time mechanical current rating is the maximum peak value of a fully displaced (asymmetrical)
primary current wave whose magnitude shall be 2.7 times the short-time thermal rating, that the
transformer is capable of withstanding with the secondary winding short-circuited. “Capable of
withstanding” shall be interpreted to mean that if subjected to this duty, the current transformer shall show
no damage and shall be capable of meeting the other applicable requirements of this standard.
The short-time thermal current rating of a current transformer is the rms symmetrical primary current that
can be carried for 1 s with the secondary winding short-circuited without exceeding in any winding the
limiting temperature. The temperature of a conductor in the windings of a current transformer shall be
determined from calculation using methods specified in 11.1.2.
34
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The limiting temperature shall be 250 C for copper conductor or 200 C for electrical conductor (EC)
aluminum. A maximum temperature of 250 C shall be allowed for aluminum alloys that have resistance to
annealing properties at 250 C equivalent to EC aluminum at 200 C, or for applications of EC aluminum
where the characteristics of the fully annealed material satisfy the mechanical requirements.
If the 1 second rating is not dependent on core saturation (see 12.1), the short-time thermal current rating
for any time up to 5 s may be determined from the 1 s rating by dividing the current for 1 s by the square
root of the specified number of seconds. For example, the 3 second thermal current rating is equal to the 1
second current rating divided by the square root of 3, or 58% of the one-second rating. This calculation
includes the assumption that the primary current is symmetrical during the time interval.
Such current transformers, in which the primary conductor is not an integral part of the current
transformers, shall be rated in terms of primary current, even though the short-time mechanical and thermal
limitations and the continuous thermal limitations are those of the secondary winding only. Such ratings
specified for current transformers of this construction should not be considered to be applicable to the
conductor used for the primary winding of these transformers; as such, the conductor may be a component
of other apparatus or bus work having different limitations. For bushing-type current transformers, see
Annex B.
Current transformers should never be operated with the secondary circuit open because hazardous peak
voltages may result. Transformers conforming to this standard shall be capable of operating under
emergency conditions for 1 minute with rated primary current times the rating factor with the secondary
circuit open if the open-circuit voltage does not exceed 3500 V peak.
When the open circuit voltage exceeds 3500 V peak, the user should consider applying a voltage limiting
device (varistors or spark gaps) across the secondary terminals. The voltage limiting device should be able
to withstand an open-circuit situation for a period of 1 minute without damage to the secondary circuit. The
voltage limiting device may need to be replaced after such an abnormal condition.
For test frequencies of 120 Hz and below the 1 minute test voltage applied to the secondary terminals with
the primary winding open shall be twice the relay rated secondary terminal voltage given in 6.4.1.3 but not
less than 200 V. For test frequencies above 120 Hz, see 8.5.4 for test duration. Transformers with no relay
voltage classification shall be tested at 200 V.
For X classification the induced level shall be 2 × Ek or 2500 V rms (3.5 kV peak), whichever is less.
If a frequency higher than 60 Hz is necessary to avoid excessive exciting current, see 8.5.4 for reduced time
of application. If the voltage cannot be induced sinusoidally even at 400 Hz without core saturation, no test
is required.
35
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
This test is not required for window-type or bar-type 10 kV BIL current transformers that are rated below
600 A and that have no relay accuracy rating.
6.8 Nameplates
Current transformers shall be provided with nameplates that shall include, as a minimum, the following
information (see Table 7):
NOTE 1—See IEEE Std C37.04 and NEMA SG 4 for nameplate requirements in high-voltage circuit breakers.
6.9 Terminals
The primary terminals of wound-type and bar-type current transformers shall be suitable for use with either
aluminum or copper conductors. The secondary terminals and voltage terminals, where provided, shall be
suitable for use with copper conductors.
The characteristic data in 6.10.1 and 6.10.2 suitable for portraying or calculating performance shall be
made available upon request.
36
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
a) Typical ratio correction factor and phase angle curves, for the standard burdens for which metering
accuracy ratings are assigned, plotted over the range of current per Table 8 from 0.1 or 0.05 times
rated current to the maximum continuous thermal current rating. These curves shall be plotted on
rectangular coordinate paper and need not be drawn where the errors exceed the limits of the 1.2
accuracy class.
b) Short-time mechanical and short-time thermal current ratings, as defined in 6.6.1 and 6.6.2,
respectively.
NOTE—The 45° tangent was established from experience using conventional magnetic materials. The
significance of these tangent points will be dependent on the magnetic material in use.
e) For T class transformers, typical overcurrent ratio curves on rectangular coordinate paper plotted
between primary and secondary current over the range from 1 to 22 times rated primary current for
all the standard burdens10 up to the standard burden, which causes a ratio correction of 50% (see
Figure 7).
10
Except B-0.9 and B-1.8.
37
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Ek
38
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Tests for current transformers with metering accuracy ratings shall be made on each transformer, and they
shall consist of the measurement of ratio error (ratio correction factor) and phase angle at rating factor,
100% and at 10% or 5% of rated current as per Table 8, when energized at rated frequency and rated
burden. Unless otherwise requested by the customer, non-compensated current transformers shall be tested
at only the maximum rated burden.
Routine accuracy tests for current transformers with a relay accuracy rating shall be made on each
transformer and shall consist of a turns ratio check, secondary excitation, and RCF measurements at 100%
rated current with standard rated burden. For ring-type cores of low reactance, the RCF measurement may
be the composite error performed by secondary excitation at the voltage equivalent to standard rated burden
at 100% as calculated in 9.1.1, 9.1.2, and 9.1.3.
The routine secondary excitation test shall consist of a knee point determination for C class transformers to
prove compliance with the published characteristic curve.
For X classification transformers, the routine secondary excitation test shall consist of measurements of
exciting voltage versus exciting current at Ek, and at two additional points (one point above Ek and one
point below Ek). The test points are arbitrary and selected for convenience to verify conformance, and shall
be at least 50% of Ek. If Rct was a given parameter, it shall be measured and corrected to 75 °C.
39
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
All excitation measurements shall be compared with the published curve, and shall comply with the limits
indicated in Figure 6 (except for X class where Ek and Ik are maximum limits). Additional points may be
required as deemed necessary to prove compliance.
7. Voltage transformers
a) Basic impulse insulation level in terms of full-wave test voltage (see Table 14 through Table 18, as
well as Figure 8 through Figure 15).
b) Rated primary voltage and ratio (see Table 14 through Table 18, as well as Figure 8 through Figure
15). Secondary voltage is 120 V up to 25 kV class inclusive and 115 volts above 25 kV.
c) Frequency (in Hz)
d) Accuracy ratings (see 5.3)
e) Thermal burden rating (see 7.4)
In Table 14 through Table 17, voltage transformers connected line-to-ground on an ungrounded system
cannot be considered grounding transformers and shall not be operated with the secondary windings in
closed delta because excessive currents may flow in the delta.
40
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
OR
4 160 V WYE
SYSTEM-NEUTRAL
4 160 V 4 160 V
EFFECTIVELY GROUNDED
LINE-TO-NEUTRAL ON A
4 160 V 2 400 V 2 400 V 4 160 V WYE SYSTEM
2 400 V
41
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
OR
14 400 V WYE SYSTEM
NEUTRAL GROUNDED OR
UNGROUNDED 14 400 V 14 400 V 8 314 V
LINE-TO-NEUTRAL CONNECTION
ON THE SAME SYSTEM
14 400 V 8 314 V
8 314 V
42
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
39 837 V
4 160 V WYE
SYSTEM-NEUTRAL
VOLTAGE
EFFECTIVELY 4 160 4 160 TRANSFORMERS
GROUNDED V V GROUP 4A-RATED
VOLTAGE
2 400 2 400/4 160 GRD Y
2 400
4 160 V V V
LINE-TO-GROUND
ON A 4 160V WYE
2 400 V SYSTEM
43
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
14 440 V WYE
SYSTEM VOLTAGE
14 400 V 14 400 V
TRANSFORMERS
GROUP 4A-RATED
VOLTAGE
14 400 V 8 314 V 8 314 V 14 400/14 400 GRD Y
LINE-TO-GROUND
ON A 14 440 V
8 314 V WYE SYSTEM
20 125 V
Standard burdens for voltage transformers for rating purposes are shown in Table 19.
44
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Characteristics on standard
Characteristics on 120 V basisc Characteristics on 69.3 V basisc
burdensa
A voltage transformer shall be assigned an accuracy rating for each of the standard burdens for which it is
rated (see Clause 5). The accuracy class may be stated for the maximum burden for which it is rated and
will imply that all other lower burdens shall be in that class; e.g., 0.3Z would imply 0.3 class at 0, W, X, M,
Y, and Z. If the class is different at other burdens, it shall be stated as follows: 0.3Y, 0.6Z, and 1.2ZZ, or it
may be stated at a specific burden, such as 0.3 @ Y, where the accuracy class is not guaranteed for other
burdens unless specifically stated.
7.3.2 Accuracy classification for voltage transformers with two secondary windings
or tapped secondary windings
The burden on any two secondary terminals affects the accuracy on all other terminals. The burden stated
in the accuracy ratings is the total burden on the transformer. The accuracy class shall apply with the
burden divided between the secondary outputs in any manner.
The thermal burden rating of a voltage transformer shall be specified in terms of the maximum burden in
volt-amperes that the transformer can carry at rated secondary voltage without exceeding the temperature
rise given in Table 4.
If no thermal burden in volt-amperes rating is given, the thermal burden rating in volt-amperes shall be the
same as the maximum standard burden for which an accuracy rating is given.
45
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Each winding, including the primary winding, of a multiple-secondary transformer shall be given a thermal
burden rating. If only one thermal burden rating is specified, it shall be equally divided among the
secondary windings unless otherwise specified.
7.5 Nameplates
Voltage transformers shall be provided with nameplates that shall include, as a minimum, the following
information (see Table 7):
7.6 Terminals
Primary terminals shall be electrically and mechanically suitable for use with either copper or aluminum
conductors. Secondary terminals shall be electrically and mechanically suitable for use with copper
conductors.
Voltage transformers shall be capable of withstanding for 1 second the mechanical and thermal stresses
resulting from a short circuit on the secondary terminals with full voltage maintained on the primary
terminals. “Capable of withstanding” shall be interpreted to mean that, if subjected to this duty, the voltage
transformer shall show no damage and it shall be capable of meeting the other applicable requirements of
this standard. The temperature of the conductors in the windings of voltage transformers under short-circuit
conditions shall be determined from calculations using the methods specified in 13.1. The limiting
temperature shall be 250 C for copper conductors or 200 C for EC aluminum conductors. A maximum
temperature of 250 C shall be allowed for aluminum alloys that have resistance to annealing properties at
250 C equivalent to EC aluminum at 200 C, or for applications of EC aluminum where the characteristics
of the fully annealed material satisfy the mechanical requirements.
46
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
a) Typical ratio correction factor and phase angle curves for rated primary voltage (and, when
specified, for rated primary voltage divided by the square root of 3), plotted for the standard
burdens from 0 VA to the volt-amperes of the burden, and also plotted for unity power factor
burden from 0 VA to the volt-amperes of the largest standard burden plotted. Ratio correction
factor and phase angle data for other burdens may be calculated by methods outlined in 8.1 and
10.1.
b) Accuracy ratings for all standard burdens up to and including the maximum standard burden rating
of the transformer.
See 8.5.4 for test frequency and duration. The test voltage shall be as follows:
CAUTION
Many
a) Forof the tests calledwith
transformers for in
twothis subclause
fully involve
insulated high
primary voltage. the
terminals, Therefore, they shall
test voltage should
be be performed
twice the rated
only by experienced personnel
voltage of the windings. familiar with any dangers that may exist in the test setups and test
procedures. Although some dangers are specifically pointed out herein, it is impractical to list all
possible dangers
b) For insulated-neutral or grounded-neutral and precautions.
terminal-type transformers, the test voltage shall be equal
to the power frequency withstand voltage specified in Table 2 for the BIL.
These tests shall be made on each transformer and shall consist of ratio and phase angle tests at 100% of
rated primary voltage at rated frequency with zero burden, and with the maximum standard burden for
which the transformer is rated at its best accuracy class.
CAUTION
Many of the tests called for in this clause involve high voltage. Therefore, they should be performed
only by experienced personnel familiar with any dangers that may exist in the test setups and test
procedures. Although some dangers are specifically pointed out herein, it is impractical to list all
possible dangers and precautions.
47
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
a) Revenue metering applications: to have proper traceability the uncertainty ratio of the accuracy
measuring systems shall be no less than 4:1, as specified in ANSI/NCSL Z540-3. For example: for
the 0.3 class transformers, the system’s errors shall not exceed ±0.075% for ratio and ±0.75 mrad
(2.6 min) for phase angle.
b) Other applications: ±1.2% for ratio and ±17.5 mrad (1°) for phase angle.
In selecting the measurement method to use from those listed in this subclause, the maximum uncertainty
should be considered. For example, item b) includes relaying, load control, and similar applications. For
these applications, acceptable uncertainty is usually obtainable with nonprecise methods not discussed
herein.
The equipment used for accuracy tests shall be traceable to a national or international standards bureau or
agency. Records of accuracy verification for the calibration systems by an independent laboratory shall be
regularly maintained.
The maximum interval shall be five years for non-electronic equipment and one year for electronic devices,
unless specified otherwise by the measuring equipment manufacturer.
8.1.2 General
Instrument transformers considered herein are designed either for metering or for relaying applications. The
ratio of a transformer can be described by Equation (5):
Q1
Q2 NO (1 a) e
(5)
jb
where
The expression in Cartesian form is close enough, and is as shown in Equation (6) as
follows:
Q1 (6)
N O (1 a jb)
Q2
where
48
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
If the transformer is to be used for revenue metering, the method of calibration shall permit the
determination of both the ratio and the phase angle to the uncertainties prescribed in 8.1.1. If the
transformer is to be used only for relaying, only the ratio needs to be determined. This may be achieved
either experimentally or by computation.
The circuit shall be arranged to avoid or minimize spurious magnetic coupling and the consequent
generation of unknown electromotive forces. Thus, the measuring network should be as far removed as is
practical from conductors carrying large currents, and twisted bifilar or coaxial leads shall be used to
minimize effects from loops.
The proper location of grounds and the proper use of electrostatic shielding and guarding networks are
critical. These locations are governed by the type of circuit and cannot be uniquely prescribed. The
controlling criterion is arranged so that spurious capacitance current cannot enter or leave the measuring
circuit. The arrangement shall eliminate these leakage paths or otherwise control them so that the
capacitance effects are negligible or adequately calculable.
The error of an instrument transformer is a function of current (or voltage), burden, and frequency. For the
minimum uncertainty, the calibration shall be made under the conditions the transformer will encounter in
service. This requirement is appreciably more stringent for current transformers (CTs) than for voltage
transformers (VTs), since the excitation of the CT core varies over wide limits. The voltage normally
applied to the VT is nearly constant so that its excitation varies over a limited range. Also, the error of a
voltage transformer at a given voltage can be computed for any burden at any power factor if the errors are
known for zero burden and for another burden at known power factor.
The errors of a current transformer may be influenced by its location and orientation relative to nearby
high-current conductors. To achieve reproducible results, such conductors should be arranged to minimize
current transformer errors.
To ensure meaningful results, the current transformer shall be demagnetized prior to calibration. Even after
demagnetization, stray direct currents present in the test circuit, e.g., from a dc resistance measurement,
may remagnetize the transformer and introduce errors that will not permit reproducible results.
The errors of a voltage transformer that is not completely enclosed within a shielded structure, such as a
metal tank, can be influenced by the proximity of nearby objects. However, except for high-precision
laboratory measurements, this effect is usually negligible.
Heating effects are also of particular importance in accuracy testing of current transformers. Where
relatively high magnitudes of primary or secondary current, or both, are involved, the test equipment
should have sufficient thermal capacity to permit making the necessary measurements without significant
heating. In making overcurrent accuracy tests, such as for relaying application, care should be exercised to
ensure that (1) the short-time thermal current rating of the transformer under test is not exceeded and (2)
self-heating during the measurements does not materially alter the characteristics being measured.
Impedance measurements discussed in 8.2.2 uses terminology typically used for power and distribution
transformers. Impedance measurements discussed in 9.3.1 and 10.2.1 use terminology typically used for
instrument transformers.
49
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The voltage required to circulate the rated current of the transformer under short-circuit conditions is the
impedance voltage of the transformer as viewed from the terminals of the excited winding.
The impedance voltage is comprised of an equivalent resistance component and a reactive component. It is
not practical to measure these components separately, but after the loss and the impedance voltage are
measured, the components may be separated by calculation.
It is sufficient to measure and adjust the current in the excited winding only, because the current in the
short-circuited winding will be the correct value (except for a negligible excitation current) when the
current in the excited winding is correct. The introduction of current-measuring equipment in series with
the short-circuited winding may introduce large errors in the impedance measurements.
For two-winding transformers, one of the windings (either the high-turn or the low-turn) is short-circuited,
and voltage at rated frequency is applied to the other winding and adjusted to circulate rated current in the
winding.
For transformers having more than two windings, the impedance voltage is a function of the test
connections used. When making tests on multiple-winding transformers, the windings should be connected
in such a manner as to provide the correct impedance data for the purpose intended.
Resistive and reactive components of the impedance voltage are determined by the use of Equation (7) and
Equation (8).
Pz
V
(7)
r
I
Vx V 2 V 2 (8)
zr
where
The I2R losses of the two windings are calculated from the ohmic resistance measurements (corrected to the
temperature at which the impedance test is made) and the currents that are used in the impedance
measurement. These I2R losses subtracted from the impedance loss give the stray losses of the transformer.
The temperature of the windings shall be taken immediately before and after the impedance measurements
in a manner similar to that described in 8.4. The average shall be taken as the true temperature.
Loss measurements are not mandatory and only need to be performed if requested. The circuit connection
for the measurement of exciting current and loss is shown in Figure 16. A series of simultaneous readings
are taken on the ammeter, rms reading voltmeter, average reading voltmeter, calibrated in rms, and
wattmeter.
50
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The following two excitation current curves can be drawn from the data obtained:
If these curves differ, the supply voltage is not a sine wave. In this case, curve 1 will be lower and curve 2
will be higher than the corresponding curve for sine wave voltage. If the two curves are within 2% of each
other, either curve can be used without correction. If they differ by 2% to 10%, the value of the average
reading voltmeter is used to determine the excitation current on a sine-wave basis. If they differ by more
than 10%, very serious waveform distortion is indicated and appropriate circuit changes shall be made.11
The excitation loss of a transformer includes the dielectric loss and core loss. It is measured by the
wattmeter in Figure 16.
The excitation loss determination is based on a sine wave voltage applied to the terminals of the
transformer. Peaked voltage waves (form factor greater than 1.11) resulting generally from the nonlinear
character of the excitation load of the transformer on the test source, give smaller excitation losses than a
sine wave voltage. Flat-topped voltage waves, rarely encountered in such tests, give larger losses.
Current transformer cores should be demagnetized just prior to excitation loss measurements, and all
measurements should be made on the low-current winding with other windings open-circuited
WARNING
8.2.3.1 Composite error measurements
This circuit may result in abnormally high voltages at the high-voltage terminals and abnormally low
Thiscurrents
method in
maythebeexcitation
performedcircuit of certain
as shown voltage
in Figure 16 transformers.
except withoutSafety precautions
the wattmeter. Theshould be taken
exciting current is
measured at an induction level equivalent to rated current with standard rated burden. The exciting current
may be considered the total error as defined in 9.1.2.3.
11
Very large waveform distortion can be detected more conveniently by oscilloscope or wave analyzer.
51
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Measurements on voltage transformers and current transformers under overcurrent conditions are made
using the average-reading voltmeter. The average value of the test voltage applied shall be the same as the
average value of the desired sine wave of voltage at the proper frequency. Under this condition, the
hysteresis component of the loss will be correct.
It is recommended that the test be made on the low-voltage winding with all other windings open circuited.
When the low-voltage winding is excited, full voltage will appear across the high-voltage winding and
safety precautions shall be taken.
After the voltage is adjusted to the desired value as indicated by the average-reading voltmeter, the
simultaneous values of rms voltage, power, and current are recorded. Then the tare on the wattmeter,
representing the losses of the connected instruments, is read and subtracted from the earlier wattmeter
reading to obtain the excitation loss of the transformer.
Exciting current measurements are obtained at the same time that loss measurements are made. In order to
obtain the correct exciting current measurement, the tare on the ammeter, which represents the current
taken by the voltage elements of the wattmeter and voltmeters, shall be measured and subtracted vectorially
from the previous current measurements. If the readings of voltage as indicated on the rms voltmeter and
the average-reading voltmeter differ by more than 2%, the measurements shall also be corrected for
waveform (see IEEE Std 4).
8.3 Polarity
The lead polarity of a transformer is a designation of the relative instantaneous directions of currents in its
leads. Primary and secondary leads are said to have the same polarity when at a given instant the current
enters the primary lead in question and leaves the secondary lead in question in the same direction as
though the two leads formed a continuous circuit.
Two methods are in common use for determining the polarity of instrument transformers. They are as
follows:
To determine the polarity of instrument transformers using this method, do the following:
a) Connect the high-turn and low-turn windings as shown in Figure 17. In most cases, the high-turn
winding of a current transformer is X1X2 and that of a voltage transformer is H1H2.
b) Energize the circuit from a controlled voltage source at the terminals AB of the high-turn winding.
c) Read the value of the voltages across AB and BD.
d) If the voltage across BD is less than the voltage across AB, the polarity is as marked. If the voltage
across BD is greater than the voltage across AB, the polarity is reversed.
52
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
WARNING
The source voltage should always be impressed across the high turn winding; otherwise, dangerously
high voltages might be encountered.
NOTE—The suitability of this method for high-ratio transformers is limited by the sensitivity of the voltmeter used.
These measurements are made on instrument transformers for the following reasons:
53
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The resistance is defined as the open-circuit voltage across the potential terminals divided by the current
entering and leaving the current terminals. Thus, for example, if the resistance of a winding between two
points ‘a’ and ‘b’ is needed, the potential leads are connected to terminals P1 and P2, and the current leads
are connected to terminals C1 and C2.
There is no precise rule that governs the selection of a four-terminal measurement over a two-terminal one.
The choice depends primarily on the magnitude of the resistance and on the accuracy to which it is to be
measured. However, either contact resistance or uncertainties in lead resistance may be as much as 0.01 Ω.
Both two-terminal and four-terminal resistance measurements may be made using voltmeter-ammeter
methods or bridge methods. The four-terminal measurement should be used for resistances of 1 Ω and
below. Resistance bridges suitable to measure the resistance down to the µohm range are commercially
available.
When a two-terminal measurement is adequate, the Wheatstone bridge is recommended. When four-
terminal measurements are necessary, the double-ratio arm (Kelvin) bridge is required. Both types are
commercially available and require minimum external equipment.
The Wheatstone bridge consists of a pair of ratio arms, an adjustable resistance arm for achieving balance,
and an arm containing the resistance to be measured. In the commercial versions, the ratio arms are
equipped so that any one of several ratios can be readily selected. Thus, resistances can be measured over a
wide range with maximum resolution available from the adjustable arm.
The double-ratio arm bridge is more complex in both its design and its operation. Textbooks in electrical
measurements contain excellent discussions of the bridge and should be consulted. Generally speaking, the
bridge measures a four-terminal resistance in such a way that its points of attachment to the measuring
circuit and its lead resistances do not enter into the measurement.
The lowest measurement uncertainty available from either type of bridge can be obtained if a substitution
technique is employed. The technique, however, requires a known standard whose nominal value is the
same as the resistance being measured. The bridge is first balanced with the standard in the unknown arm
and is then rebalanced with the standard replaced by the unknown resistor. In this way, only the small
difference between the two is measured, and since the other arms of the bridge remain unchanged, their
values need not be known.
54
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The reference temperature of the winding shall be determined accurately when measuring the winding
resistance of the relaying accuracy current transformers and for use in temperature rise tests. The
temperature of the winding shall not be assumed to be the same as the surrounding air.
The resistance measurements shall be made on a transformer only when the winding temperature is stable.
The temperature is considered stable if the external surface temperature of dry-type transformers or top
liquid temperature of oil-filled transformers does not vary more than 1 ºC in a 1-hour period.
Dielectric tests should be made with the transformer at room temperature, and unless otherwise specified,
the voltage should be measured in accordance with IEEE Std 4.
When tests are required on bushings or insulators separately from the transformers, the tests shall be made
in accordance with IEEE Std C57.19.00.
The purpose of dielectric tests in the factory is to check the insulation and workmanship and to demonstrate
that the transformer has been designed to withstand the specified insulation tests.
It is recognized that the dielectric tests impose a severe stress on the insulation and, if applied frequently,
will hasten breakdown or may cause breakdown. The stress imposed, of course, is more severe the higher
the value of the applied voltage. Hence, periodic testing may not be advisable.
It is recommended that initial user tests of insulation should not be in excess of 75% of the factory test
voltage; that for old apparatus rebuilt in the field, tests should not be in excess of 75% of the factory test
voltage; and the periodic insulation tests by the user should not be in excess of 65% of the factory test
voltage. Tests made by the user for design approval may be made at 100% of the factory test voltage.
The terminal ends and taps brought out of the case from the winding under test shall all be joined together
and connected to the line terminal of the testing transformer. All other terminals and parts (including tank
and core, if accessible) should be connected to ground and to the other terminal of the testing transformer.
The ground connection between the apparatus being tested and the testing transformer shall be a substantial
metallic circuit.
Wire of sufficient size and suitable arrangement to prevent excessive partial discharge (corona) at the test
voltage should be used in connecting the respective taps, line terminals, and the test transformer together.
Care shall be taken to keep the wire on the high-voltage side well away from the ground. No appreciable
impedance should be placed between the testing transformer and the one under test.
55
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
It is recommended that a suitable current-sensitive failure detection device be provided. The reason for this
is that the voltage change across the test transformer at failure may not easily be detected by observation of
the input voltmeter.
As a safety precaution, a relief gap set at a voltage 10% to 20% in excess of the specified test voltage
should be connected during the applied voltage test. For instrument transformers to be tested at 50 kV or
less, it is permissible to omit the relief gap (see 8.5).
The applied test voltage should be started at one third or less of full value and increased gradually to full
value in not more than 15 s. After being held for 1 minute, it should be reduced gradually in not more than
15 s to one third of the maximum value or less and the circuit opened.
The applied voltage test requirements for insulated-neutral-terminal types of voltage transformers are
specified in 4.5.
These tests are made by applying voltage to one winding with all the other windings open. One end of each
winding shall be grounded during this test. Usually the voltage is applied to the low-voltage winding. When
the voltage across any winding will exceed 50 kV during this test, some means should be provided to verify
the voltage.
As this test (if made at rated frequency) overexcites the transformer under test, the frequency of the applied
voltage should be such as to prevent saturation of the core. Ordinarily this requirement necessitates the use
of a frequency of 120 Hz or more when exciting 60 Hz units. For those types that have large distributed
capacitance, the excitation current increases with the frequency of the applied voltage, making it necessary
to guard against an exciting current that will exceed 200% normal load current based on the thermal rating.
When frequencies higher than 120 Hz are used, the severity of the test is abnormally increased, and for this
reason, the duration of the test should be reduced in accordance with Table 20.
The voltage should be started at one-third or less of the full value and be increased gradually to full value in
not more than 15 s. After being held for the duration of time specified in Table 20, it should be reduced
gradually in not more than 15 s to one-third the maximum value, or less, and the circuit opened.
Voltage transformers in polyphase metering equipment may be tested with single-phase voltage. Usually
the specified test voltage is applied to one of the windings on each core with the neutral ends of the open
windings grounded.
Frequency Duration
(Hz) (s)
120 or less 60
180 40
240 30
360 20
400 18
56
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Partial discharge (PD) tests are intended to determine the freedom of internal insulation from damaging
internal discharges.
The preferred arrangement for making the partial discharge test is to have the instrument transformer under
test to be fully assembled prior to conducting the test; however, during the partial discharge test, if external
fittings or hardware on the assembled transformer being tested results in interfering with the test, they may
be removed or provided with supplementary shielding.
Oil-filled, gas-filled, and dry-type instrument transformers 5 kV nominal system voltage and above shall be
given a partial discharge test as a routine test. No test shall be made on terminals that are intended to be
grounded.
At the discretion of the manufacturer, the induced or applied voltage and partial discharge tests may be
performed together.
If necessary, external electrodes may be used for the primary terminal and the ground of the transformer.
The test method shall be in accordance with IEC 60270. For typical test circuits see IEC 60270.
When using a 60 Hz pre-stress voltage it shall be maintained for a minimum of 60 s; where a higher
frequency is used the duration may be reduced as per Table 20. Subsequently the test voltage shall be
reduced to the level of the prescribed extinction voltage, which shall then be maintained for a minimum of
30 s. The partial discharge intensity shall be measured during this time. It is recommended that the
reduction from the pre-stress to test voltage be done over approximately 10 s.
The transformer shall be considered as having met the requirements if the partial discharge intensity
measured at the prescribed extinction voltage level is equal to or less than 10 pC for oil-filled or gas-filled
transformers, and 50 pC for dry-type insulation systems.12
For current transformers the test voltage shall be applied to H1 and H2. All secondary terminals and the
base shall be grounded.
For line-to-line voltage transformers, the partial discharge shall be measured for each of the following
connections:
a) The test voltage shall be applied to H1. H2, one end of each secondary winding, and the base shall
be grounded.
b) The test voltage shall be applied to H2. H1, one end of each secondary winding, and the base shall
be grounded.
For line-to-ground voltage transformers the test voltage shall be applied to H1. H2, one end of each
secondary winding and the base shall be grounded.
For combination units containing both a voltage and current transformer the pre-stress and prescribed
extinction test voltages shall be based upon the guidelines established below for voltage transformers. The
connections for the combination units are to be made with the voltage applied to H1 and H2 with the
current transformer secondary terminals grounded one secondary of the voltage transformer grounded and
the base grounded.
12
It is recommended that the actual measured partial discharge extinction voltage be recorded.
57
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
A partial discharge test shall be made after all dielectric tests are completed; however, the partial discharge
test may be performed while decreasing the voltage after the induced or applied voltage test. If the
measured PD level exceeds the permitted limits, a separate test shall be performed and shall govern.
58
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
8.6.2 Partial discharge measurement for current transformers for a nominal system
voltage of 72 kV and below
For current transformers having substantially continuous ring cores, uniformly distributed secondary
windings, and having either a centrally located primary conductor or a uniformly distributed primary
winding, the values of ratio, ratio error, and phase angle may be obtained by calculation (computation)
from the obtained secondary excitation characteristics at the rated frequency.
Although the following indirect test will lead to results which are close to the results obtained in the direct
test, the routine accuracy tests for the metering current transformers shall always be performed as a direct
test. On the other hand, the alternative method is suitable for on-site measurements, and for monitoring
purposes.
59
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
For current transformers with negligible leakage fluxes, the equivalent circuit shown in Figure 19 and the
vector diagram shown in Figure 20 are suitable for calculations. It shall be noted that the alternative
(indirect) method never considers the influence of stray fluxes entering the core from the adjacent
conductors.
impedance
60
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Assuming that electric and magnetic components of transformer and burden are linear, and primary current
is sinusoidal, then performance of this transformer can be illustrated by the following vector diagram.
For a current transformer with the turns ratio equal to the rated transformation ratio, the difference in the
lengths of the vectors IS and I’P, related to the length of I’ P, is the current ratio error (RE), and the angular
difference β is a phase angle (PA).
61
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
A substantially sinusoidal voltage ES is injected between secondary terminals X1 and X2 of the CT. The
voltage EP across the terminals H1and H2, and exciting current Ie are measured. The value of ES should be
selected to obtain measureable voltages on both windings but shall not exceed the knee point voltage EK.
Turns ratio may be determined from the relationship:
NS EO
NP EP (9)
where
In the case of window-type CTs an artificial primary winding has to be established. If they are installed on
equipment, consideration shall be taken as to what the artificial primary winding used in this test is
comprised of.
Determine the equivalent operational secondary voltage ET at the desired secondary current IS (i.e., 5 A, 0.5
A, or some other point of interest) and burden
ET IS Z (10)
where
Z R SB RX
2
B
2
(11)
Inject the substantially sinusoidal voltage ET between secondary terminals X1 and X2 of the CT. The
secondary exciting current Ie is measured.
Employing fundamental formulas for current transformer (see Harris [B9]), the accuracy performance
yields:
Ie
Ratio Error (RE) = sin( ) (12)
I
S
13
Refer to 8.2.3 for additional information.
62
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Ie
Phase Angle (PA) = cos( ) (13)
I
S
where
From Equation (10) determine the equivalent operational secondary voltage E T at some desired secondary
current IS (rated current, 20 times rated current, or some other point of interest) and burden. Inject the
substantially sinusoidal voltage ET between secondary terminals X1 and X2 of the CT. The secondary
exciting current Ie is measured.
Ie
The percent composite error = 100 % (14)
I
S
Since T-type current transformers have appreciable leakage flux entering the core, they cannot be
represented adequately by an equivalent circuit. This type of current transformer does not lend itself to
simple, accurate calculations. Therefore, these calculations are primarily applicable to types C, i.e.,
bushing-type current transformers for relaying service.
Since these transformers are generally multiratio, the most useful form in which the transformer secondary
excitation characteristics may be given is a family of curves similar to Figure 1 showing the excitation
voltage and currents on the secondary winding turns base for each ratio. These curves are usually
determined from test data taken on a typical unit of a given design by the method covered in 8.2.3.
9.2 Demagnetization
a) Method 1. Connect the current transformer in the test circuit as shown in Table 21. Apply enough
current to the high-turn winding (usually X1X2) to saturate the core of the transformer as
determined by the ammeter and voltmeter readings; then slowly reduce the current to zero. The
rated secondary current of the transformer shall not be exceeded.
63
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
WARNING
9.3AImpedance measurements
continuously variable resistance shall be used to avoid opening the high turn winding circuit when
resistance values are changed, since, as the resistance is increased, the voltage across the resistance
will approach the dangerous open-circuit value.
9.3.1 Current transformer short-circuit impedance measurements
The measured short-circuit impedance of a current transformer is the sum of the primary and secondary
impedance. Since the secondary impedance cannot be determined from this information alone, the data
64
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
obtained is of little value in the calculation of ratio and phase angle characteristics. However, it is of value
in determining the burden imposed on main transformers by auxiliary transformers.
Except for current, the quantities measured in making impedance measurements on current transformers are
extremely small and great care shall be exercised in order to obtain accurate results.
For the purpose of impedance measurements, current transformers can be divided into the following three
types, according to their physical details:
a) Type 1: Bushing-type, window-type, or bar-type, with turns well distributed about the core. In
current transformers of this type, the leakage reactance is extremely small and the impedance may
be considered to be the resistance of the whole winding or that part to be used if it is well
distributed. The manufacturer should be consulted if the winding distribution is not known.
b) Type 2: Wound type in which the high-current (primary) terminals are at opposite ends of the
transformer. Transformers of this type should be excited from the high-current winding with the
low-current winding short circuited, because a short circuit on the high-current winding will
introduce appreciable error in the measurement due to the added impedance of the short-circuiting
connections.
It is recommended that the three-voltmeter method, as described in 10.2.1, be used for impedance
measurement on this type of transformer.
c) Type 3: Wound type in which the high-current (primary) leads are brought out parallel to each
other through a single bushing. Current transformers of this type may be excited from either the
high-current or the low-current winding with the other winding short circuited.
Either the three-voltmeter method or the wattmeter, voltmeter, ammeter method can be used for
impedance measurements on transformers of this type, depending on which winding is excited.
9.4 Polarity
To determine the polarity of current transformers using this method, do the following:
b) Energize the circuit from a controlled current source so that the test current flows in the H1 H2
windings as shown in Figure 23.
c) If the ammeter reads the sum of the currents in the high-turn windings, the polarity of the unknown
transformer is reversed. If the ammeter reads the difference of currents in the high-turn windings,
the polarity of the unknown transformer is as marked.
65
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Several methods are available for calculating the accuracy of voltage transformers at different burdens.
These methods, utilizing winding impedances and core excitation characteristics, are subject to some
limitations and give results having less precision than those methods that employ a combination of test and
calculation.
The latter methods, using measured values of true ratio and phase angle at zero burden and one other
burden within the maximum standard burden rating of the transformer, yield results having a high degree of
precision. This is possible because both the ratio and the phase angle of a voltage transformer give
practically straight lines when plotted against secondary current at a given voltage, power factor, and
frequency.
10.1.2 Calculation of voltage transformer ratio and phase angle from known zero and
rated burden data
In this method, the true ratio and phase angle of a voltage transformer are known at both zero burden and
one other burden, either a rated standard burden or, more conveniently, a pure resistive or capacitive
burden, for a given voltage and frequency. At the same voltage and frequency, the accuracy for any other
burden and power factor may be calculated from the following equations:14
14
These equations are approximations. Although they yield accurate results for many cases, the user should be aware that for large
burdens (e.g., Z or ZZ), intolerable errors may be introduced unless the volt-amperes of the known burden are equal to or greater than
those of the unknown burden, and the values for the known and the zero burdens are measured accurately. This problem is minimized
for all cases if the magnitude of the known burden is made nominally equal to the magnitude of the rated burden of the transformer
under test.
66
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
NOTE 1—t and c are positive angles for lagging power factors.
NOTE 2— is considered positive when the secondary voltage leads the primary
voltage.
(15)
RCFd RCFt RCFo
which equals difference between the transformer ratio correction factors for burdens Bt and Bo
d t o (16)
which equals the difference between the transformer phase angles burdens Bt and Bo, in radians
Bc
RCF RCF RCF cos( ) sin( )
c o d t c d t c
(17)
Bt
B
c cos( ) RCF sin( ) [in radians] (18)
c o d t c d t c
Bt
NOTE 3—Multiply radians by 1000 to obtain milliradians (mrad). If minutes are desired, multiply by 3438.
NOTE 4—These equations provide an analytical determination of voltage transformer accuracy. Although they are
long, a simple computer or programmable calculator program can be written to perform the necessary calculations
quickly and accurately. Also, it has been shown that graphical solutions of these equations by means of special scaled
polar coordinate paper and a protractor are sufficiently accurate for most revenue-metering applications.
The equations for RCFc and c above reduce to the following simpler form in the case where the burden for
RCF and are known to be at unity power factor.
B
RCF RCF c RCF cos( ) sin( )
c o d c d c
(19)
B
t
Bc
c o d cos(c ) RCFd sin(c ) [in radians] (20)
Bt
where
67
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
For burdens not exceeding the burden for which RCF and are known, the foregoing calculations will
produce the same accuracy as would be obtained from the actual tests at the unknown burden. When the
calculations are used for determining performance at greater burdens, a lower accuracy will be obtained.
Consideration should be given to the effects of the increased heating due to the heavier burdens.
Voltage transformers operate at high magnetic flux densities in normal service. Although short-circuit
impedance measurements are necessarily made at low magnetic flux densities, the components of
impedance thus obtained are of value for the computation of transformer ratio and phase angle. The short-
circuit characteristics are also of value in selection of fuses.
The short-circuit impedance can be measured by the wattmeter, voltmeter, ammeter method.
The wattmeter, voltmeter, ammeter method is shown in Figure 24. The measured values shall be corrected
for instrument burden, if the analog wattmeter and voltmeter with low input impedance are used.
NOTE—It is recommended that the low-voltage winding be excited and the high-voltage winding be short-circuited
68
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
10.3 Polarity
To determine the polarity of voltage transformers using this method, do the following:
a) Connect the high-turn windings of the two transformers in parallel, as shown in Figure 25, by
connecting H1 of the known transformer to H1 of the unknown transformer and H2 of the known
transformer to H2 of the unknown transformer.
b) Connect the low-turn windings through a voltmeter, as shown in Figure 25 by connecting X1 of the
known transformer to X1 of the unknown transformer and X2 of the known transformer to one
voltmeter terminal and X2 of the unknown transformer to the other voltmeter terminal.
WARNING
High voltages will be present on the high-voltage terminals of both transformers. Safety precautions
should be taken.
69
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The test to demonstrate the short-time mechanical current rating of a current transformer shall be made by
subjecting the current transformer, with the secondary winding short-circuited; to a fully asymmetrical
short-circuit current of the duration of at least six cycles. The magnitude of the first asymmetrical peak
current shall be 2.7 times the thermal short-time current rating with the other peaks decreasing in
magnitude. This test may be combined with the thermal short-time test as long as the first peak satisfies the
mechanical rating and the remaining peak values are not less than the thermal rating for the duration of the
test.
The test to demonstrate the mechanical short-circuit capability of a voltage transformer shall be made with
rated voltage maintained on the primary for 1 s with the secondary terminals short-circuited. The test shall
be performed with the secondary windings paralleled if multiple secondary windings are present and by
short-circuiting the taps that result in the highest current. As an alternative, the test could be performed by
short-circuiting the primary winding and applying the rated secondary voltage for 1 s. The test shall be
performed with the secondary windings paralleled and by applying the voltage between the taps that result
in the highest current.
The calculation of temperature rise of a winding under short-time conditions is based on the assumption
that heating is adiabatic, i.e., that all of the energy developed in the winding during the period of the short
circuit (5 s or less) is stored as heat in the winding.
It is also assumed that the starting temperature of the winding when the short circuit occurs is the maximum
hottest-spot temperature of the winding at 30 °C ambient temperature under continuous loading at (1) the
continuous thermal current rating for a current transformer or (2) the maximum rated standard burden and
110% of rated voltage for a voltage transformer. Where this hottest-spot winding temperature is not
established by test, the limits of hottest-spot temperature rise (specified in Table 4) for 30 °C ambient shall
be used.
The calculated maximum temperature attained by the winding during the short circuit shall not exceed the
limits specified in 6.6.2 for a current transformer or in Clause 7 for a voltage transformer.
The general equation of winding temperature under short-circuit conditions is most conveniently expressed
and used as the current density that will produce the maximum permissible temperature in the winding
under the conditions specified above. Thus,
T 2
m K
I C(T 20) T s
(21)
ln
A 2 20 t 1 K
where
70
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
This general equation may be simplified for most practical applications, since short-time thermal ratings are
based on a short-circuit duration of 1 s, and except for large current transformer primary bars, K is usually
negligible.
I
16 240 234.5 2 A (22)
ln m 2
A 234.5 s cm
I
10 760 225 2 A (23)
ln m 2
A 225 s cm
If m is taken as 250 °C for copper and as 200 °C for EC aluminum (see 6.6.2), and if s is taken as 95 °C
for 55 °C rise types, 110 °C for 65 °C rise types, and 140 °C for 80 °C rise types (see Table 4), then:
For copper:
71
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
For aluminum:
11.2.1 General
All temperature rise tests shall be made under the normal conditions of the means, or method, of cooling.
All temperature rise tests shall be made with the transformer under test in the orientation and under the
conditions for which it is designed to operate. If the transformer is designed for use in any one of several
orientations, or under several possible conditions, the test shall be made in the orientation and condition
that is expected to result in the greatest temperature rise.
The transformer shall be mounted in a normal manner. Mounted in a normal manner shall be interpreted to
mean that the heat dissipation due to conduction and radiation shall not be substantially influenced by
abnormal heat transfer to, or from, surrounding objects. Transformers shall be completely assembled with
normal finish, and if oil-filled, they shall be filled to the recommended level.
Temperature rise tests shall be made in an area as with a wind speed of 0.5 m/s or less.
The design shall be considered as having met the requirements of 4.6 if the temperature rise is in
accordance with Table 4 and terminal temperature rise is in accordance with Table 5.
The ambient temperature shall be the temperature of the air surrounding the transformer under test.
The ambient temperature shall be not less than 10 °C nor more than 40 °C during a temperature rise test.
The preferred method of measuring the ambient temperature is by using an ideal identical transformer, or
one having similar thermal-time characteristics, and measuring the temperature by the resistance method.
The idle transformer shall be located so as to respond to ambient temperature changes in the same manner
as the transformer under test (see 8.4.3).
When an identical transformer is not available, the temperature of the cooling air shall be determined from
the average of the readings of several thermometers or thermocouples (one may be used for small
transformers) placed around and approximately at the same level as the center of the maximum vertical
heat-dissipating surface of the transformer, at a horizontal distance adequate to prevent the transformer
under test from influencing the readings (1 m to 2 m is usually sufficient).
To reduce to a minimum the errors due to time lag between the temperature of the transformers and the
variations in the ambient temperature, the thermocouples, or thermometers, shall be placed in suitable
containers and shall have such proportions as will require not less than 2 h for the indicated temperature
within the container to change 6.3 °C if suddenly placed in air that has a temperature 10 °C higher, or
lower, than the previous steady-state indicated temperature within the container.
72
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
When the ambient temperature, based on the average readings of the thermometers or thermocouples
during one observation period, is not 30 °C, the winding losses will not be the same as the values that
would have been obtained at 30 °C ambient conditions. If the temperature rise values obtained are close to
the limiting values for the insulation used in the transformer, a correction shall be applied to that part of the
temperature rise due to the winding losses.
The corrected temperature rise for current transformers shall be obtained by multiplying the total measured
temperature rise by the applicable factor [as shown in Equation (24) and Equation (25)].
264.5
Factor for copper windings (24)
equals 234.5 a
255
Factor for EC aluminum windings equals (25)
225 a
where
The temperature rise of voltage transformers depends on both the winding losses and the core losses. Only
that part of the temperature rise due to the winding losses is affected by the ambient temperature, as the
core losses are not appreciably changed over the temperature range in which instrument transformers
normally operate.
The part of the temperature rise due to the winding losses shall be corrected by using the applicable factor
covered above. To obtain the part of the temperature rise due to winding losses, a temperature rise test shall
be made with the voltage transformer secondary winding open-circuited and the values obtained subtracted
from the temperature rise values that were obtained under the corresponding condition specified by 13.2.
Provision shall be made to measure the surface temperature of all metal parts surrounding, or adjacent to,
the outlet leads or terminals carrying large currents.
When possible, the top liquid temperature of oil-filled transformers shall be measured by a thermocouple or
spirit thermometer immersed to approximately 5 cm below the top liquid surface.
The bulbs of the spirit thermometer or other temperature-reading means used for taking temperatures of the
transformer surfaces in air shall be covered by small felt pads, or the equivalent, cemented to the
transformer. If thermocouples are used, the leads shall be so arranged that excessive heat is not conducted
to or from the junction.
The ultimate average temperature rise of the windings shall be determined by the resistance method
whenever practical.
To avoid errors due to the time required for the bridge current to become constant, the time required shall
be determined during the measurement of the winding resistance reference temperature. An equal or
slightly longer time shall be allowed when making ultimate and cooling rate temperature measurements.
Measurements of temperature rise by the resistance method shall not include contact resistances. This may
be accomplished by using a four wire method.
73
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The temperature rise shall be considered constant when all temperatures that can be measured without
shutdown at intervals of not less than 30 min show three consecutive readings within 1 °C. Temperature
rise tests shall not be made by any method that requires shutting off the power for more than 2 min in any 2
hours to establish that a constant temperature has been reached.
A correction shall be made for the cooling that occurs from the time that the power is shut off to the time
that the hot resistance is measured.
The recommended method of determining the temperature of the winding at the time of shutdown shall be
by measuring the resistance of the windings, as the transformer cools, immediately after shutdown and
extrapolating to the time of shutdown. At least four measurements shall be made at intervals of not more
than 3 min but no less than the time required for the measuring current to stabilize. If the current does not
exceed 15% of the rated current of the winding, it may be maintained during the entire period.
The average temperature of a winding shall be determined by Equation (26) or Equation (27)
R t
t
T T o (26)
R o
R t R o
t (27)
R (T o )
o
o
where
The dc resistance measuring equipment shall have a minimum resolution of three significant digits
following the first significant digit.
The temperature rise is the corrected total temperature minus the ambient temperature at the time the
observations were made.
When tests are made at an altitude not exceeding 1000 m above sea level, no altitude correction shall be
applied to the temperature rise.
74
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
When tests are made at an altitude that is more than 1000 m above sea level, the temperature rise shall be
corrected to 30 °C conditions by the following method:
h 1000
r m 1 0.005 100 (28)
where
These tests consist of applying in the following order one reduced full wave, one full wave, two chopped
waves, and two full waves.
The wave to be used shall consist of a nominal 1.2 × 50 µs wave. Either, but not both, positive or negative
waves may be used. Waves of negative polarity for oil-filled apparatus, and of positive polarity for dry-type
or compound-filled apparatus, are recommended and shall be used unless otherwise specified.
The voltage shall be measured and the waveform traces scaled as specified in IEEE Std 4.
For this test, the voltage wave shall have a peak value of between 50% and 70% of the full-wave peak
given in Table 2.
For this test, the applied voltage wave shall be chopped by a suitable air gap. It shall have a peak value and
time to flashover in accordance with Table 2.
To avoid recovery of insulation strength if failure has occurred during a previous impulse, the time interval
between the application of the last chopped wave and the final full wave should be minimized and
preferably should not exceed 10 min.
For this test, the voltage wave shall have a peak value in accordance with Table 2, and no flashover of the
transformer under test or test gap shall occur.
75
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The time interval between application of the last chopped wave and the final full wave shall be minimized
to avoid recovery of insulation strength if a failure has occurred prior to the final full wave.
All impulses applied to a transformer shall be recorded if their peak values exceed 40% of the peak of the
full-wave value given in Table 2.
When reports require waveform traces, those of the first reduced full wave, the first full wave, the last two
chopped waves, and the last full wave of voltage shall represent a record of the successful applications of
the impulse test to the transformer.
The impulse voltage shall be applied to all primary leads simultaneously with the secondary windings
short-circuited and grounded.
The specified test voltage shall be applied to each primary terminal. In testing transformers equipped with
fuses, the fuses should be short-circuited. Test voltages shall be applied to the polarity terminal of the high-
voltage winding with the opposite lead grounded and to the nonpolarity terminal with the polarity lead
grounded.
One terminal of the winding under test shall be grounded directly or through a small resistance if current
measurements are to be made. One terminal of each of the other windings may be grounded directly or
through a resistor. It is desirable that the voltage on ungrounded terminals of a winding not under test
should not exceed 80% of the full-wave voltage for its BIL rating.
In some cases the inductance of the winding is so low that the desired voltage magnitude and duration of
the 50% point on the tail of the wave cannot be obtained with available equipment. Low-inductance
windings may be tested by inserting a resistor of not more than 500 in the grounded end of the winding.
In all such cases, shorter waves may be used (for additional information, see 10.3.1.1 of IEEE
Std C57.12.90).
Any unexplained differences between the first 100% full wave and the final full wave detected by
superimposing the two voltage waveform traces, or any such differences observed by comparing the
chopped waves to each other and to the full wave up to the time of flashover, are indications of failure.
Deviations may be caused by conditions in the test circuit external to the transformer or by protective
devices and should be fully investigated.
Smoke bubbles rising through the liquid in the transformer are definite evidence of failure. Clear bubbles
may or may not be evidence of trouble; they may be due to entrapped air. They should be investigated by
repeating the test, or by reprocessing the transformer and repeating the test to determine whether a failure
has occurred.
In making the chopped-wave test, failure of the chopping gap, or any external part, to flashover, although
the voltage waveform traces show a chopped wave, is a definite indication of a flashover either within the
transformer or in the test circuit.
Unusual noise within the transformer at the instant of applying the impulse is an indication of trouble.
76
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
For instrument transformers with capacitive graded insulation, current waveform traces comparison is
mandatory. When the ground current method of detection is used, impulse current in the grounded end of
the winding tested is measured. Any unexplained differences detected by superimposing the two current
waveform traces of the first 100% full wave and last full wave tests may be an indication of failure.
Deviations in the current wave shapes may also be caused by conditions in the test circuit external to the
transformers, or by built-in protective devices, and should be investigated fully. It is difficult to shield the
measuring circuit completely from the influence of the high voltage of the impulse generator, and some
stray voltages are frequently picked up that may produce an erratic record for the first 1 µs or 2 µs. Such
influences, if they occur at the start of the current wave, should be disregarded. The ground current method
of detection is not applicable for use with chopped-wave tests.
The pre-stress and prescribed extinction voltages shall be in accordance with Table 21 or 8.6.2 depending
on voltage rating.
Before the test, the setup shall be calibrated for the partial discharge measurement of 10 pC for oil-filled or
gas-filled, and 50 pC for dry-type instrument transformers. The measuring method shall be in accordance
with IEC 60270.
If necessary, external electrodes may be used for the primary terminals and the ground of the transformer.
As the test voltage is increased, the voltage at which the partial discharge intensity of 10 pC for oil-filled or
gas-filled, and 50 pC for dry-type instrument transformers is detected shall be recorded (i.e., the partial
discharge inception voltage). The test voltage shall then be increased until it reaches the prestress voltage
level which shall be maintained for the duration in accordance with Table 20. Subsequently the test voltage
shall be reduced to the prescribed extinction voltage level 15 and then maintained for a duration of 30 s
within which the partial discharge intensity shall be measured. The actual partial discharge extinction
voltage shall be recorded during the reduction from prestress voltage to the prescribed extinction voltage.
If the partial discharge intensity exceeds the limit of 10 pC for oil-filled or gas-filled, and 50 pC for dry-
type instrument transformers, the test may be extended, at the manufacturer’s discretion, by up to 10 min at
the prescribed extinction voltage level. The test shall be terminated if the measured partial discharge
intensity has decreased to less than or equal to 10 pC for oil-filled or gas-filled, and 50 pC for dry-type
instrument transformers.
The design shall be considered as having met the requirements if the following are true:
a) No external disruptive discharge or collapse of voltage is observed during the test, and
b) The partial discharge intensity measured at the prescribed extinction voltage level is equal to or less
than 10 pC for oil-filled or gas-filled, and 50 pC for dry-type instrument transformers,16 and
c) No internal insulation failure is found by the capacitance and dissipation factor measurement.
d) For transformers with a rated voltage less than 10 kV, for dry type molded transformers without
capacitive graded insulation or for bushing current transformers these capacitance and dissipation
factor requirements do not apply.
15
The partial discharge intensity may be measured as the test voltage is reduced from the power frequency withstand voltage level.
16
It is recommended that the actual measured partial discharge extinction voltage be recorded.
77
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The test shall be performed only on transformer designs of a nominal system voltage of 345 kV and above.
The voltage shall be applied between the primary terminal and the ground terminal of the transformer. All
secondary winding terminals and the base frame shall be grounded.
The preparation of the transformer and wetting procedure shall be in accordance with ‘Wet Tests’ of IEEE
Std 4. The precipitation conditions shall be as described under the “Standard test procedure” as outlined in
Table 3 of the same standard. Air density correction shall be done in accordance with 13.2 of IEEE Std 4-
2013.
The voltage waveshape shall be 250 µs ± 20% × 2500 µs ± 60% (or [200 – 300] µs × [1000 – 4000] µs)
standard wave-shape. The test voltage shall be in accordance with Table 2. The applied wave shall be at
positive polarity only.
a) One reduced wave with 50% to 70% of rated value provided in Table 2, and
b) Fifteen full waves
The test shall be performed only on transformers of a nominal system voltage of 230 kV and below.
The preparation of the transformer and wetting procedure shall be in accordance with IEEE Std 4. The
precipitation conditions shall be as described under the “Standard test procedure” for wet tests. Air density
correction shall be done in accordance with 13.2 of IEEE Std 4-2013.
78
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
A three–terminal capacitance and dissipation factor measurement in the grounded specimen mode and at a
voltage of 1.0 kV (rms) or lower shall be performed to determine the following:
For gas-filled transformer the test may be performed at any setting of the gas pressure.
The presence of the ground shield shall be indicated if the measured capacitances are in accordance with
Equation (29).
1/ C ps 1/ Cp 1/ Cs
(29)
The transformer shall be considered as having met the requirements if the measured parameters are within
±10% of the value determined with the above expression.
The short-time thermal rating assigned to a current transformer shall be such that the permissible current
density, as determined by Equation (21), Equation (22), or Equation (23) as applicable, will not be
exceeded in any winding.
For current transformers, the major portion of the stray conductor loss, if any, is normally in the primary
winding, and K, the ratio of stray conductor loss to I2R loss, should be applied to the calculations of the
temperature rise in the primary winding only. The value may be determined from the equation:
P (I2 R) A
z (30)
K
I R
2
cm2
p
where
The value of K at the prescribed starting temperature may be determined from the stray loss ratio Ka at
some other temperature a by the following equations:
For copper:
79
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
234.5 2
A
K Ka 234.5 a cm2 (31)
s
For EC aluminum:
2
225 A
K Ka 225 a cm2 (32)
s
For the calculation of permissible current density in the secondary winding, K may be considered
negligible and the simplified equations at the end of 11.1.2 may be used.
In a current transformer, under the conditions prescribed for the calculation of temperature rise, saturation
of the core may cause the actual secondary current to be less than that indicated by the marked ratio of the
transformer.
Where actual secondary current under the overload condition has been established by test or calculation,
the actual secondary current density may be used rather than that indicated by the marked ratio.
Tests on current transformers shall be made at maximum-rated continuous current and at rated frequency.
All terminals and joints shall be clean and tight and shall provide good electrical contact.
Current transformers that have been magnetized by measuring the resistance of the winding shall be
demagnetized after the completion of temperature rise tests. (The method of demagnetizing is covered in
9.2.)
The current carrying conductors supplying the instrument transformer shall not act as a heat source or a
heat sink. In order to fulfill this requirement, the temperature of the current carrying conductors at a
distance of 1 m from the transformer primary terminals shall not differ by more than ±5°C from that
measured on the transformer terminals.
In making temperature tests on window-type current transformers, the primary conductor used in the test
shall have a continuous-current capacity in the configuration used and according to recognized authority,
not less than the test current. If more than one primary turn is used, the clearance between the turns and the
transformer body around the outside shall be at least 30 cm. For 55 °C or 65 °C rise type transformers, the
continuous-current capacity of the primary bus shall be based on a temperature rise of 50 °C or less, and the
continuous-current capacity of the primary cable shall be based on a maximum conductor temperature of
75 °C.
The inter-turn overvoltage test shall be performed in accordance with one of the following procedures.
If not otherwise agreed, the choice of the procedure is left to the manufacturer.
80
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Procedure A: with the secondary windings connected to a high impedance peak-reading voltmeter,
gradually increase the substantially sinusoidal primary current at a rated frequency from zero to the
maximum continuous rated current, or until the peak voltage reaches 3500 V, whichever occurs first.
Maintain the primary current for 60 s.
Procedure B: with the primary winding open-circuited, the prescribed test voltage (at some suitable
frequency) shall be applied for 60 s to the terminals of secondary winding, providing that the rms. value of
the secondary current does not exceed the rated secondary current (or rated extended current).
The value of the test frequency shall be not greater than 1000 Hz.
At this frequency, if the voltage value achieved at the rated secondary current (or rated extended current) is
lower than 3500 V peak, the obtained voltage is to be regarded as the test voltage.
When the frequency exceeds twice the rated frequency, the duration of the test may be reduced from 60 s as
shown in Equation (33):
The inter-turn overvoltage test is not a test carried out to verify the suitability of a current transformer to
operate with the secondary winding open-circuited. Current transformers should not be operated with the
secondary winding open-circuited because of the potentially dangerous overvoltage and overheating that
can occur.
To demonstrate the ability of a voltage transformer to meet the temperature limitations of 7.7, the short-
circuit current in each winding is calculated for the condition of rated voltage applied to the primary
terminals, and the secondary winding short-circuited at its terminals. The current density I/A is then
calculated by dividing the short-circuit current by the cross section of the conductor. The value of current
density so obtained for each winding shall not exceed the applicable value calculated using the equations at
the end of 11.1.2, the stray conductor loss ratio K being considered negligible for voltage transformers.
For the purpose of calculating the short-circuit current from the above discussion, the reactance X, and the
resistance R, may be determined by any of the methods described in 8.2, but the resistance shall be
corrected to a temperature that is the average of the initial and maximum temperatures. For any winding:
where
The value of R may be determined from the resistance Ra at a temperature a by Equation (34) and
Equation (35).
81
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
For copper:
a m
234.5 2 A
RR
(34)
234.5 a cm2
a
For EC aluminum:
a m
225 2 A
RR (35)
a 225 a cm2
In a voltage transformer under short-circuit conditions, the current, and therefore the current density, will
decrease during the short circuit due to the change of resistance with the temperature of the winding. The
value of the short-circuit current, as determined by the above paragraph, therefore represents an average
value during the short-circuit period. However, this approximation introduces negligible error in the
calculation of temperature rise within the prescribed limits.
Temperature rise tests shall be made at rated frequency. The power factor of the burden used during
temperature rise tests is not important.
Temperature rise tests at thermal burden rating shall be made at rated primary voltage.
Temperature rise tests, for normal operating conditions, shall be made at 110% rated primary voltage and
with the maximum standard burden for which an accuracy class is published.
82
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Annex A
(informative)
Bibliography
Bibliographical references are resources that provide additional or helpful material but do not need to be
understood or used to implement this standard. Reference to these resources is made for informational use
only.
[B1] Arnold, A. H. M., “Current-transformer testing,” Journal of the IEE, vol. 74, pp. 424444, 1934.
[B2] Arnold, A. H. M., “Precision testing of current transformers,” Journal of the IEE, vol. 68,
pp. 898905, 1930.
[B3] ASTM D117-1996, Standard Guide for Sampling, Test Methods, Specifications, and Guide for
Electrical Insulation Oils of Petroleum Origin.
[B4] Bousman, H. W., and Ten Broeck, R. L., “A capacitance bridge for determining the ratio and phase
angle of potential transformers,” AIEE Transactions, vol. 62, pp. 541545, Aug. 1943.
[B5] Brownlee, A. L., “A primary method of measuring the ratio and phase angle of current
transformers,” AIEE Transactions, vol. 69, part 1, pp. 459460, 1950.
[B6] Buchanan, J. H., “Design, construction, and testing of voltage transformers,” Journal of the IEE, vol.
78, pp. 292316, Mar. 1936.
[B7] Clothier, W. K., and Medina, L., “The absolute calibration of voltage transformers,” Proceedings of
the IEE, vol. 104A, pp. 204214, June 1957.
[B8] Glynne, A., “The use of a simple AC potentiometer for the precision testing of instrument
transformers,” Journal of the IEE, part 11, no. 21, pp. 177181, June 1944.
[B9] Harris, F. K., Electrical Measurements. New York: John Wiley and Sons, Inc., 1952.
[B10] Harris, F. K., et al., “An international comparison of voltage-transformer calibrations to 350 kV,”
IEEE Transactions on Communication and Electronics, vol. 83, pp. 1319, Jan. 1964.
[B11] IEEE Std C57.98™, IEEE Guide for Transformer Impulse Tests.
[B12] Kusters, N. L., and Moore, W. J. M., “The compensated current comparator: A new reference
standard for current-transformer calibrations in industry,” IEEE Transactions on Instrumentation and
Measurement, vol. IM-13, pp. 107114, June/Sept. 1964.
[B13] Kusters, N. L., and Petersons, O., “A transformer-ratio-arm bridge for high-voltage capacitance
measurements,” IEEE Transactions on Communications and Electronics, no. 69, pp. 606611, Nov. 1963.
[B14] Kusters, N. L., “The precise measurement of current ratios,” IEEE Transactions on Instrumentation
and Measurement, vol. IM-13, pp. 197209, Dec. 1964.
[B15] Miljanic, P. N., Kusters, N. L., and Moore, W. J. M., “The application of current comparators to the
calibration of current transformers at ratios up to 36 000/5 amperes,” IEEE Transactions on
Instrumentation and Measurement, vol. IM-17, pp. 196203, Sept. 1968.
[B16] Petersons, O., and Anderson, W. E., “A wide-range high-voltage capacitance bridge with one ppm
accuracy,” IEEE Transactions on Instrumentation and Measurement, vol. IM-24, no. 4, pp. 336344, Dec.
1975.
[B17] Petersons, O., “A self-balancing current comparator,” IEEE Transactions on Instrumentation and
Measurement, vol. IM-15, nos. 1 and 2, pp. 6271, Mar./June 1966.
83
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
[B24] AIEE Committee on Protective Devices, Current Transformer Subcommittee, “Current- and
potential-transformer standardization,” AIEE Transactions, vol. 61, pp. 698706, Sept. 1942.
[B25] ANSI/NCSL Z540.3, Requirements for the Calibration of Measuring and Testing Equipment.
[B26] Arnold, A. H. M., “Dielectric admittances in current transformers,” Proceedings of the IEE, vol. 97,
part II, pp. 692698, 1950.
[B27] Arnold, A. H. M., “The effect of capacitance on the design of torodial current transformers,”
Proceedings of the IEE, vol. 97, part II, no. 60, pp. 797808, Dec. 1950.
[B28] Arnold, A. H. M., “Leakage phenomena in ring-type current transformers,” Journal of the IEE, vol.
74, pp. 413-423, 1934.
[B29] Davis, R., “The design and construction of a shielded resistor for high voltages,” Journal of the IEE,
vol. 79, pp. 10281034, 1931.
[B30] Dunfee, B. L., and Moore, W. J. M., “An international comparison of current-ratio standards at audio
frequencies,” IEEE Transactions on Instrumentation and Measurement, vol. IM-14, pp. 172177, Dec.
1965.
[B31] Foley, A. H., “A direct reading high-voltage capacitance bridge,” AIEE Transactions, vol. 69, part
II, pp. 692698, 1950.
[B32] Hague, B., Instrument TransformersTheir Theory, Characteristics and Testing. London: Sir Isaac
Pitman and Sons, Inc., 1936.
[B33] IEEE Std C57.13.1™-1981, Guide for Field Testing of Relaying Current Transformers. 18
[B34] IEEE Std C37.235™, IEEE Guide for the Application of Rogowski Coils Used for Protective
Relaying Purposes.
[B35] ISO/IEC 17025:2005, General Requirements for the Competence of Testing and Calibration
Laboratories.
17
Bibliographic references [B24] to [B49] constitute a sample of the large amount of useful material covering instrument transformers
that is available. These references are given for the convenience of obtaining more detailed information and a historical perspective on
the subject matter covered in this standard.
18
IEEE publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854,
USA (http://standards/ieee.org/).
84
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
[B36] Kusters, N. L. and Moore, W. J. M., “The development and performance of current comparators for
audio frequencies,” IEEE Transactions on Instrumentation and Measurement, vol. IM-14, pp. 178198,
Dec. 1965.
[B37] McGregor, M. C., et al., “New apparatus at the National Bureau of Standards for absolute
capacitance measurement,” IRE Transactions on Instrumentation, vol. I-7, nos. 3 and 4, pp. 253261, Dec.
1958.
[B38] Miljanic, P. N., “Capacitive error in current comparators,” IEEE Transactions on Instrumentation
and Measurement, vol. IM-13, pp. 210216, Dec. 1964.
[B39] Moreton, S. D., “A simple method for the determination of bushing-current-transformer
characteristics,” AIEE Transactions, vol. 62, pp. 581585, Sept. 1943.
[B40] NEMA SG4, Alternating Current High-Voltage Circuit Breakers.
[B41] Park, J. H., “Accuracy of high-range current transformers,” NBS Journal of Research, vol. 14,
pp. 367392, 1935.
[B42] Pfuntner, R. A., “The accuracy of current transformers adjacent to high-current buses,” AIEE
Transactions, vol. 70, part II, pp. 16561662, 1951.
[B43] Settles, J. L., Farber, W. R., and Conner, E. E., “The analytical and graphical determination of
complete potential transformer characteristics,” AIEE Transactions, part III, pp. 12131219, 1960.
[B44] Silsbee, F. B., “A study of the inductance of four terminal resistance standards,” United States
Bureau of Standards Scientific Papers, no. 281, pp. 375422, 1916.
[B45] Silsbee, F. B., “Notes on the design of four terminal resistance standard for alternating currents,”
NBS Journal of Research, vol. 4, pp. 73107, Jan. 1930.
[B46] Silsbee, F. B., “Precautions against stray magnetic fields in measurements with large alternating
currents,” AIEE Transactions, vol. 48, pp. 13011306, Oct. 1929.
[B47] Weller, C. T., “A 132 kV shielded potentiometer for determining the accuracy of potential
transformers,” AIEE Transactions, vol. 48, pp. 790807, July 1929.
[B48] Woods, C. A., Jr., and Bottonari, S. A., “Overcurrent performance of bushing-type current
transformers,” AIEE Transactions, vol. 59, pp. 554560, Sept. 1940.
[B49] Zocholl, S. E., Analyzing and applying current transformers, Schweitzer Engineering Laboratories,
Inc., 2004.
85
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Annex B
(normative)
B.1 Introduction
Over the years there has been much ambiguity in the treatment of BCTs and how they apply to the
guidelines set forth in this standard. It is the purpose of this annex to define the ratings, selection and test
requirements for BCTs.
B.2 Scope
This annex will cover BCTs as they apply to power transformers, step-voltage regulators, power circuit
breakers, isolated phase bus compartments, generators, and other equipment where they might be used.
This shall apply to any window-type current transformer rated 0.6 kV or less, intended to rely on, in
addition to its own insulation, any combination of conductor insulation and air, oil or gas medium, as a
complete insulation system satisfying the equipment dielectric requirements.
For the purpose of this annex, a BCT is a window-type current transformer wound on a toroidal core with
uniformly distributed windings having negligible leakage reactance (see Figure B.1). It shall have a
nominal voltage rating of 0.6 kV having no BIL rating (unless otherwise stated by the manufacturer). The
primary winding is typically in the form of a lead wire, cable, bus bar, or terminal or wall bushing. This
conductor is typically a single turn centrally located in the window (see The IEEE Standards Dictionary
Online).
PRIMARY
CONDUCTOR
H1
SECONDARY
WINDING
X2 X1
Metering performance shall be in accordance with 6.3 and relaying performance shall be in accordance
with 6.4. It is permissible to have dual ratings that are one having both relaying and metering performance
simultaneously.
86
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
When used in control functions such as for temperature indication (hot spot), load tap changing (LTC) or
automatic voltage regulation (AVR), neither metering nor relaying class designations apply. The ratio may
be selected by the full load current and may not necessarily coordinate with a standard current ratio. An
accuracy limit of ±1% shall be used at rated current with a 50 VA burden. There will be no limit on phase
error. Verification at 100% rated current at rated burden is required. A direct or indirect test (by composite
error measurement) may be used at the discretion of the manufacturer.
NOTE—Step-voltage regulators are nominally 0.2 A secondary with 3.5 VA burden and are covered in IEEE
Std C57.15. If BCTs are used with 5A secondary and assigned conventional metering or protection ratings, then this
annex shall apply.
For indication purposes with ammeters, class 1.2 or higher shall be used with no limit on phase error.
Verification at 100% rated current at rated burden is required. A direct or indirect test (by composite error
measurement) may be used at the discretion of the manufacturer.
In the case of metering class 0.6 or better, if the BCT is a dual ratio, both taps shall have a defined metering
accuracy, and tested per Figure 7.
It is not desirable to have a metering class for a multi-ratio winding with more than two available ratios
unless all available ratios have defined accuracy classes. The accuracy performance will worsen and the
burden may decrease as the ratio decreases. If none are specified the manufacturer shall verify only the
defined tap per Figure 7, and all other ratios shall have no guarantees of performance. If other ratios are
defined the manufacture shall verify performance of the lowest ratio with the highest accuracy class and
burden. Performing tests at other ratios is subject to agreement between the producer and the user.
87
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
The ambient temperature for which the basis of continuous duty is assigned shall be determined by its
application as shown in Table B.1. The reference ambient temperature shall be indicated on the BCT
nameplate if other than 30 °C.
The temperature class of the insulation system for determining the maximum allowable rise shall be, as a
minimum, Class 105 °C. If the insulation system is greater than Class 105 °C as shown in Table B.2, then it
shall be stated on the BCT nameplate.
All major insulation components used throughout the BCT assembly shall be thermally coordinated with its
temperature class per Table B.2, and suitable for the environment it will be subjected to as indicated in
Table B.1.
For the purpose of determining temperature rise in a BCT, there will be no consideration of hot spot
allowance. The secondary turns are usually evenly distributed and the primary is typically a single
conductor passing through the BCT window with little to no contribution of heat to the secondary winding.
The limit of allowable temperature rise shall simply be the difference of the insulation class and the
ambient temperature rating.
Maximum allowable Temperature Rise, ΔT = Insulation Class - Ambient Temperature Rating (B.1)
88
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Maximum
Maximum allowable Maximum allowable
Insulation Maximum allowable winding
winding rise @ 30 winding rise @ 55
class working rise @ 90 °C
°C average ambient °C average ambient
designation temperature average ambient
(°C) (°C)
(°C) (°C)
Class 105 105 65 40 15
Class 120 120 80 55 30
Class 130 130 90 65 —
Class 155 155 115 90 —
Class 180 180 140 115 —
Class 200 200 160 135 —
Class 220 220 180 155 —
If the maximum temperature rise is not the difference between the insulation class and ambient temperature
rating, then it shall be conveyed to the end user on the BCT nameplate. It shall also be stated on published
characteristic curves.
For example:
a) If the rated ambient temperature is 95 °C and the insulation is Class 105, the rise is 10 °C; only the
ambient temperature needs to be stated.
b) If the rated ambient temperature is 75 °C, the insulation is Class 105, and the rise is 30 °C; only the
ambient temperature needs to be stated.
c) If the rated ambient temperature is 55 °C and the insulation is Class 130, but the rise is only 30 °C,
then all three items shall be stated.
For the purpose of this annex all terms relating to the maximum continuous duty of a BCT shall be referred
to as RF. That will include such terms as thermal RF (TRF), continuous thermal RF (CTRF), continuous
current RF (CCRF), and the like.
The maximum current ratio should be based upon the maximum continuous current rating of the bushing or
conductor it is being used on, including any short-time overload conditions that may affect its temperature
rise. In some cases the current ratio may be selected to 125% of the maximum rated current, or to the next
standard ratio. The assigned RF times the rated primary current shall be an absolute limit in accordance
with Table B.1.
When selecting a current ratio higher than the bushing current rating, the RF can be set to match the
bushing rating. For example, a GSU transformer with a 1200 A rated bushing and a 12 000:5 CT ratio to
match upstream CTs, the RF could be stated as 0.1.
In the case of a multi-ratio winding, unless otherwise stated, the RF assigned shall apply to all available
taps.
When using low ratio CTs or tap connections of a multi-ratio CT on bushings or conductors of much higher
ampacity, the apparatus in which the CT is being installed shall be properly de-rated in accordance with the
CT ratio ratings.
89
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
Rating factors shall be assigned in accordance with 6.5 unless agreed upon by the manufacturer and end
customer.
The use of the de-rating chart (Figure 1) is not applicable for BCTs. In the case of lower ambient
temperatures it should not be assumed that the RF can increase. Such considerations shall be discussed with
the BCT manufacturer.
When using low ratio CTs or tap connections of a multi-ratio CT on bushings or conductors of much higher
ampacity while intended to be used at lower currents, the apparatus in which the CT is being installed shall
be properly coordinated with the CT ratings.
NOTE—For high voltage power circuit breakers see NEMA SG-4, IEEE Std C37.04, and IEEE Std C37.010 for more
guidance.
Short-time ratings for BCTs shall be assigned as a multiple of rated current and shall apply to the maximum
current ratio unless otherwise stated.
Short-time thermal ratings may be calculated based on the cross-sectional area of magnet wire used in the
secondary winding per 11.1.2. This rating is given as a symmetrical rms value. To maintain alignment with
power circuit breaker ratings, short-time thermal ratings may be provided for three-second durations.
Mechanical short-time ratings of a BCT, for all practical purposes, may be considered unlimited, but in
reality is limited by the conductor it is installed upon. For this reason the short-time mechanical rating is
arbitrarily set to 2.7 times the calculated one-second short-time thermal rating, and is the peak value of the
first asymmetrical major loop.
The user shall keep in mind that these short-time ratings are not necessarily the same as those of the
primary conductor, which may have different limitations.
BCTs are typically mounted around bushing shanks along the ground plane and are seldom ever in direct
contact with the primary current carrying conductor. They may also be used in conjunction with air, oil or
gas to meet a higher dielectric level. For this reason they cannot be effectively tested to satisfy any applied
withstand and impulse level on their own. The qualification of the insulation system which includes the
BCT in its assembly shall be the responsibility of the equipment manufacturer, or based on successful
industry practices. By default a BCT would have a nominal voltage rating of 0.6 kV class with no BIL
rating, even though they are used on systems at much higher levels.
B.7 Construction
B.7.1 Polarity
The H1 polarity marking should be visible. This mark may be in the form of a stripe, dot, or letters. It may
also be denoted on the nameplate.
90
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
If secondary leads are provided they shall be identified by color, permanent markings on the lead wire
insulation, or some other acceptable means provided it cannot be easily removed.
Secondary leads shall be considered as an extension of the secondary winding and therefore are not part of
the total secondary burden. For application purposes, the manufacturer may provide the lead resistance, in
Ω/ft, separate from the winding resistance since they have no control as to how much may be removed
upon installation. This may typically be stated on the published characteristic curves.
All windings including turns between taps (when provided) shall be fully distributed about the core
periphery. Tap arrangements shall be in accordance with Table 11, or some derivative when applicable. In
the case of configurations not defined in Table 11, taps shall be specified by the end user, and all taps shall
be divisible by 5 as a minimum. No tap less than 5 turns shall be provided.
In the case of those BCTs used for control functions such as hot spot sensing, winding temperature
indicators, or load tap changers, some taps (if provided) may not be fully distributed as they are typically
small portions above and/or below the main winding, which shall be fully distributed.
B.7.4 Finish
BCTs are typically classified as indoor type. In application they are contained in an enclosure protecting
them from direct exposure to sunlight and weather elements. The insulation system used throughout the
BCT assembly shall be compatible with its insulation rating and the environment for which it will be used
in accordance with Table B.1.
This is a special type of BCT that has an insulation system protecting the BCT coil assembly from the
direct exposure of weather. They are externally mounted on a terminal bushing with adequate support.
They require no protective cover or housing. A unit of this construction may have a nominal BIL rating of
10 kV or higher, as defined by the manufacturer, and shall be stated on its nameplate. The protective
insulation shall be suitable for use in outdoor environments.
This is a special type of BCT that is designed specifically for use on generator terminal bushings or in
isolated phase compartments where high currents are present. These are typically constructed with higher
temperature class materials. Due to the nature of the application and magnitudes of operating current, this
construction may require means of shielding the secondary winding from the effects of external stray flux
from adjacent and return conductors.
91
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
B.7.5 Nameplates
The nameplate shall comply with 6.8 and may include the following information:
Information left off the nameplate due to available space or other reasons shall be communicated to the end
user either on the published characteristic curves, outline drawing, or some other official means acceptable
to the end user.
a) Induced voltage test (per 6.7.2 and 8.5.4). In the case of high current ratios where the exciting
voltage may well exceed 1600 V, the induced level shall be 2 times the saturation voltage or 3200
V rms (4.5 kV peak), whichever is less.
b) Turns verification. This test can be made with any suitable configuration or method provided that it
can distinguish ±1 turn from the nominal turns. The actual turns allowance shall be in compliance
with the accuracy class limits for relaying and/or metering class as assigned.
c) Polarity verification (per 8.3).
d) Secondary winding resistance (per 8.4).
e) Accuracy tests (per Figure 7, 8.1, 8.2, and 9.1).
NOTE—This test may require inducing primary currents to very high magnitudes (>20 000A) which can lead
to difficulties obtaining 100% rated currents. These tests are normally performed in a laboratory environment
that require special equipment and setup. If by type test and/or calculations it can be successfully demonstrated
to meet the accuracy requirements, then lower measuring levels for compliance may be performed provided
they are not less than 50% rated current, they are properly reported, and they are mutually agreed upon
between manufacturer and end user.
1) In the case of non-revenue metering applications where the current ratio is non-standard, a
composite error test may be performed to prove compliance provided phase error is of no
importance. This is a secondary excitation test performed at a level equivalent to rated current
with rated burden, where the measured exciting current can be considered the error current.
See 9.1.1, 9.1.2, and 9.1.3.
92
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
2) For high current ratios that exceed the current rating of one primary loop, multiple primary
loops may be used provided they are equally spaced about the core periphery and the return
path influence is negligible.
3) For those windings that incorporate an internal shield as an integral part of the secondary
winding, or a shield that is isolated from the secondary winding, the accuracy shall remain
within its prescribed class when the primary loop is severely off center, or when multiple
primary loops are distributed not more than 50% of the core periphery.
Type tests for BCTs can be conducted to verify construction type and design calculations that can
effectively cover a wide range of physical size, ratio and accuracy classes. The following type tests shall be
performed in accordance with 4.8.1:
a) Temperature rise test (per 11.2). This test shall be conducted on the secondary winding only. Some
consideration shall be taken into account regarding the environment, conductor orientation, and
stacking of multiple BCTs.
b) Short-time ratings (per 6.6 and 11.1). Calculations shall be sufficient in lieu of test.
c) Inter-turn overvoltage test (per 6.7.1 and 12.3).
B.10 Installation
It is not the intent of this annex to provide instruction on mounting techniques but to advise of some
cautionary measures in the installation process. When using a method of clamping (plates, rings, brackets,
bars, etc.) caution shall be employed when applying force onto BCTs. The clamping mechanism should not
deform itself or the BCT when tightened. Excessive force may alter the characteristic output of the BCT.
The clamping force should be distributed as evenly as possible along the BCT surface. When possible some
means to cushion the BCT from the force should be employed. For special mounting arrangements and
configurations, consult with the manufacturer.
When the primary conductor through a BCT is a shielded cable, caution shall be used when grounding of
the shield. In some cases it may be necessary to route the shield back through the window of the BCT
before terminating it to ground, thus avoiding the creation of a shorted electrical turn around the BCT core.
This condition will result in the BCT not operating correctly.
Grounding of metallic parts and outer casings should be in accordance with IEEE Std C57.13.3.
In most cases the external slip-over BCT is installed over a bushing terminal outside of the tank or
structure, and suspended about the bushing flange with brackets. Excessive force in this case is not so much
detrimental to the performance as it is to its external insulation system. The BCT should be at or below the
bushings effective ground plane. As a precaution to protect the BCT from a flashover event, it is
recommended that a ground shield be installed. When connecting the ground shield to ground, routing of
the lead shall be in a manner that will not cause an electrical shorted turn around the BCT. If a shorted turn
is created, the BCT will not operate correctly.
93
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C57.13-2016
IEEE Standard for Requirements for Instrument Transformers
In the case whereby the external slip-over BCT is in direct contact with the tank or structure wall, and the
surface temperature of that wall is elevated above the ambient air temperature, consideration shall be taken
in regards to the possible effects on temperature rise, as well as long term effects of the insulation itself. If
at all possible the BCT should be separated from the wall to allow air flow.
BCTs can be mounted and installed in a wide variety of arrangements. For common field tests and
methods, please refer to IEEE Std C57.13.1.
In the case of revenue metering, it is very difficult to verify accuracy once installed. There are some
methods used that will provide results that may demonstrate a BCT to meet class, but may not necessarily
match the original factory test results. It shall be the responsibility of the end user to determine the
acceptance and validity of any method or portable device that does not:
This is a special type of BCT that is constructed without an iron core. The secondary is wound on a non-
magnetic former. Beyond this deviation it will have the same appearance as any other BCT.
The mutual inductance of the BLC is set such that a voltage output is induced per ampere of primary
current. The typical value is 0.005 Ω where for every 1000 A of primary current a 5 V output is induced in
the secondary winding; other ratios are possible. This relationship remains linear through the highest fault
level encountered. For maximum power transfer, the BLC may be specified by its R, X, and Z elements.
The voltage output shall be ±1% at rated current with the primary conductor centrally located, and remain
±1% when rotated about the primary conductor. The output shall be ±1% when the primary conductor is
offset up to 25% from center. When performing this test the primary loop shall consist of one turn where
there is no external influence from the return path and adjacent iron-core elements. The secondary leads, if
provided, shall be twisted to minimize induced voltages from external sources. In addition to accuracy
verification, the R, X and Z components shall be measured and reported.
Depending on its finish construction, BLCs can also be hindered by excessive mechanical forces. All of its
parameters are geometrically controlled therefore any changes to its geometry can change its self-
impedances. When making the connection, twisted leads are recommended.
By virtue of its construction, the BLC can be easily influenced by external magnetic forces. When
installing it is best that the BLC be positioned as far away from any iron core and return conductor path as
physically possible. The geometry of the enclosure may affect its output. If the BLC is to be adjacent to, or
sandwiched between conventional iron-core CTs, the effective output of the BLC will be influenced. In
these situations the output can be up to ±10% of rated voltage.
NOTE—This is not to be confused with Rogowski coils as they are not the same. Rogowski coils are addressed under
IEEE Std C37.235 [B34].
94
Copyright © 2016 IEEE. All rights reserved.
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.
IEEE
standards.ieee.org
Phone: +1 732 981 0060 Fax: +1 732 562 1571
© IEEE
Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on June 29,2016 at 06:02:47 UTC from IEEE Xplore. Restrictions apply.