Grundfos Pump UPM3 DB GB 12-05-2014
Grundfos Pump UPM3 DB GB 12-05-2014
Grundfos Pump UPM3 DB GB 12-05-2014
UPM3
UPM3, UPM3 HYBRID, UPM3 AUTO, UPM3 AUTO L, UPM3 FLEX AS,
UPM3 FLEX AC
1 x 230 V, 50 Hz
UPM3
3. Performance range 9
6. Technical description 24
Exploded view 24
Sectional drawing 24
Material specification 25
Description of components 25
7. Installation 29
Mechanical installation 29
Electrical installation 30
8. Startup 34
9. Disposal 35
14. Accessories 52
2
UPM3
1
1. Introduction
Introduction
UPM3 - PWM variants
UPM3 7.5 m
UPM3 7m
(only externally controlled PWM A/C
UPM3 6m
profile)
UPM3 5m
UPM3 4m
Note:
PWM A/C: externally controlled via PWM profile A or
profile C (see page 19)
PWM: pulse-width modulation
PP: Proportional Pressure
CP: Constant Pressure
CC: Constant Curve
AA: AUTOADAPT
3
UPM3
1
Applications
Introduction
In a modern heating, cooling and domestic hot water The secondary circulator is often a self-controlled,
supply system there are different circuits in which stand-alone circulator which is e.g. mounted in a
UPM3 circulators in different versions can be placed. heating kit, and reacts on the changing flow demand of
We need to differentiate between the heating (or the heat consumers like radiators or underfloor heating
cooling) production and its distribution. On the circuits. If an automatic bypass valve is installed to
production side there are some applications using ensure a minimum flow, you must adjust the differential
circulators in primary or internal circuits e.g. for pressure control of the circulator in a way to ensure the
geothermal or solar thermal brine circuits as today’s function of the circulator. For example, select a
UPM GEO or SOLAR PM. constant pressure curve that is higher than the
The distribution side is often separated into two circuits differential pressure of the valve.
- a primary and a secondary circuit - in order to keep
the flow and/or temperature independent from each
other. You can use a heat exchanger, a hydraulic
separator or a buffer tank for this separation. The
primary circulator is mostly integrated into the heating
appliance and it is controlled by it via a digital signal
(e.g. PWM) to ensure the optimum operation of for
instance the boiler. In a combi-boiler, the circulator
supplies both the heating system and the hot water
supply.
Heat producers Heat consumers
Solar charging kit
Freshwater
station Heating kit
Underfloor
heating kit
Fig. 1 Complete domestic heating system combined with renewable energy sources
4
UPM3
1
In indirect heated DHW systems, the circulator might Examples of systems
Introduction
be placed on both sides of the heat exchanger. In a
DHW cylinder, potable water is stored and usually
heated indirectly by primary heating water from the
boiler either by an external plate heat exchanger or by
an internal indirect coil. Especially in renewable energy
sourced systems, the primary heating water gets
stored and instant hot water is created by fresh water
stations. Hot water recirculation circulators circulate
the potable water on the secondary side from the taps
back to the water heater to ensure comfort and to
avoid legionella.
5
UPM3
2
6
UPM3
2
Identification
7
UPM3
2
Nameplate Terminal box side
Features and benefits
1 2 3 4
I1/1(A) P1(W) MPa
Min. X.XX XX
Max. X.XX XXX X.X
1 5 6
2
GFNJX 7
UP M3 8 ((,;;3DUW; PL.avg. < XXW 9
15 - XX XXX
4 XXXV~XX/XXHz IPXXX TFXXX 14
8
UPM3
3
3. Performance range
Performance range
p H
Pump curves: [kPa] [m]
80
8
UPM3 xx-75 70
7
UPM3 xx-70
60
6
UPM3 xx-60
50
UPM3 xx-50 5
UPM3 xx-40 40
4
30 3
20 2
10 1
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [l/s]
9
UPM3
3
Performance range
10
UPM3
4
Pump electronics
9
select the speed (speed command) and as feedback &1<)
signal. The PWM frequency on the feedback signal is Signal ref.
N
N
d % = 100 x t/T %&%
Example Rating
IiH ≤ 10 mA
d % = 100 x 0.6 / 2 = 30 %
(depending on UiH)
UiH
UiL
Abbreviation Description
T Period of time [sec.]
d Duty cycle [t/T]
UiH High-level input voltage
UiL Low-level input voltage
IiH High-level input current
11
UPM3
4
PWM input signal profile A (heating) PWM feedback signal - power consumption
UPM external control mode and signals
Standby (stop)
Alarm stop: Fault, blocked pump
PWM input signal [%] Alarm stop: Electrical fault
Warning Saturation at 70 W
Fig. 6 PWM input profile A (heating)
M
PW
PWM input signal
Pump status
[%]
%
W/
≤ 10 Maximum speed: max.
:1
> 84 / ≤ 91
Slo
Minimum speed: IN
12
UPM3
4
PWM feedback signal - flow estimation (on
100
Standby (stop)
90 Alarm stop: fault, blocked pump
Alarm stop: electrical fault
80
Warning Saturation at 2.1 [m3/h]
70
60
M
50 PW
/%
h]
40 3/
[m
03
0.
e:
30
p
S lo
20
TM05 7493 1213
10
Data
13
UPM3
5
HYBRID variants
The setting options can be delivered as pre-configured
settings.
Externally Internally Number of
Variant Application Functionality Factory-set
controlled controlled settings
PP 3+ AA
Full access to all available modes PWM A 4
HYBRID Any HVAC system CP 3+ AA 20 PP3
and curves PWM C 4
CC 4
PP 3+ AA
Heating kits DHW Full access to all self-controlled
AUTO CP 3+ AA 12 PP3
System modes and curves
CC 4
Full access to all self-controlled PP 3
Heating kits DHW
AUTO L modes and curves, except CP 3 10 PP3
System
AUTOADAPT CC 4
Heating and/or solar Full access to externally controlled PWM A 4
FLEX AC 8 A7m
Thermal systems profiles and heads PWM C 4
FLEX AS Heating appliances Runs with or without PWM signal PWM A 4 CC 4 4 A7m
14
UPM3
5
User interface Operation area
100 %
Alarm status
If the circulator has detected one or more alarms, the
Fig. 10 User interface with one push button and five LEDs
bi-colored LED 1 switches from green to red. When an
The user interface shows: alarm is active, the LEDs indicate the alarm type as
• performance view (during operation) defined in the table below. If multiple alarms are active
at the same time, the LEDs only show the error with
– operation status
the highest priority. The priority is defined by the
– alarm status sequence of the table.
• settings view (after pressing the button). When there is no active alarm anymore, the user
During operation, the display shows the performance interface switches back to operation mode.
view. If you press the button, the user interface
switches the view or runs in the setting selection Display Indication Pump operation Counter action
mode. One red LED + Trying to start
Rotor is Wait or deblock
one yellow LED again every 1.33
blocked. the shaft.
(LED 5) seconds.
Performance view One red LED + Supply
Only warning, Control the
one yellow LED voltage too
The performance view shows either the operation (LED 4) low.
pump runs. supply voltage.
status or the alarm status. Pump is stopped Control the
One red LED +
Electrical because of low supply voltage /
Operation status one yellow LED
error. supply voltage or Exchange the
(LED 3)
When the circulator is running, LED 1 is green. The serious failure. pump.
four yellow LEDs indicate the current power
consumption (P1) as shown in the table below. See fig. Settings view
11. When the operation mode is active, all active LEDs You can switch from the performance view to the
are constantly on in order to differentiate this mode settings view by pressing the push button. The LEDs
from the select setting mode. If the circulator is indicate the actual setting. The settings view shows
stopped by an external signal, LED 1 flashes green. which mode controls the circulator. No settings can be
made at this stage. After 2 seconds, the display
Performance in % of
Display Indication
P1 MAX
switches back to performance view.
One green Standby (only externally If LED 1 is green, it indicates operation or internal
0
LED (flashing) controlled) control. If LED 1 is red, it indicates alarm or external
One green control. LED 2 and 3 indicate the different control
LED + one Low performance 0-25
yellow LED
modes and LED 4 and 5 indicate the different curves.
One green
LED 1 LED 2 LED 3 LED 4 LED 5
LED + two Medium low performance 25-50
yellow LED Proportional pressure green ●
One green Constant pressure green ●
LED + three Medium high performance 50-75 Constant curve green ● ●
yellow LED
PWM A profile red ●
One green
PWM B profile red ●
LED + four High performance 75-100
yellow LED Curve 1
Curve 2 ●
Curve 3 ● ●
Curve 4/AUTOADAPT ●
15
UPM3
5
Navigation User interface control modes for
UPM3 HYBRID control modes, user interface and settings
• For standard UPM3 HYBRID, UPM3 AUTO, UPM3 * The circulator is factory-set to start in this control mode.
AUTO L this is proportional pressure, curve 3
• For UPM3 FLEX AC and UPM3 FLEX AS this is UPM3 FLEX AC
PWM profile A, curve 4. This circulator is for external PWM signal control with
In the "select setting" mode the circulator starts at this profile A or C.
control mode. The preset mode is marked with this It gives the opportunity to define the maximum curve of
symbol * in the tables below. the pump operation and its profile.
PWM profile A (heating)
Setting selection
You can choose between the performance view and UPM3 xx-70 LED1 LED2 LED3 LED4 LED5
[m] red yellow yellow yellow yellow
settings view.
4 ● ●
If you press the button for 2 to 10 seconds, the user
5 ● ● ●
interface switches to "setting selection" if the user 6 ● ● ● ●
interface is unlocked. You can change the settings as 7* ● ● ●
they appear. The settings appear in a particular order
* The circulator is factory-set to start in this control mode.
in a closed loop. When you release the button, the
user interface switches back to the performance view PWM profile C (solar)
and the last setting is stored.
UPM3 xx-70 LED1 LED2 LED3 LED4 LED5
[m] red yellow yellow yellow yellow
4 ● ●
PERFORMANCE SETTING MENU
5 ● ● ●
> 10 s.
6 ● ● ● ●
> 2 s. 7 ● ● ●
X
SELECTED SETTING
2 s.
TM06 0856 1014
10 s.
16
UPM3
5
UPM3 AUTO L UPM3 HYBRID
Proportional pressure mode UPM3 xx-50 UPM3 xx-70 LED1 LED2 LED3 LED4 LED5
[m] [m] red yellow yellow yellow yellow
17
UPM3
5
Toggling the settings of UPM3 Settings navigation
UPM3 HYBRID control modes, user interface and settings
2. Release the button for more than 2 seconds. The AUTOADAPT AUTOADAPT
"operation status".
1 1
3. Press the button for more than 2 seconds and the
2 2
circulator switches to "setting selection". The LEDs
flash and show the current setting mode. Please
3 3
note that if the key lock is disabled, the circulator AUTOADAPT AUTOADAPT
for 2 seconds. 5m 7m
18
UPM3
5
Control mode explanation Constant curve
curve.
The AUTOADAPT function enables the circulator to
control the pump performance automatically within a
defined performance range.
• Adjusting the pump performance to the size of the
system. UPM3 xx-50 UPM3 xx-70
PWM profile
[m] [m]
• Adjusting the pump performance to the variations in C1 2 4
load over time. C2 3 5
In constant pressure AUTOADAPT, the circulator is set C3 4 6
to constant-pressure control. C4 (max.) 5 7
19
UPM3
5
Pump control in heating systems
UPM3 HYBRID control modes, user interface and settings
H
The heating required in a building varies greatly during
2
the day due to changing outdoor temperatures, solar
radiation and heat emanating from people, electric 1
appliances, etc.
DH 2
Add to this that the need for heating may vary from one A2
A1
section of the building to another and that the
thermostatic valves of some radiators may have been
H
2
1
DH 1 A2
A1
TM06 0857 1014
Q
Fig. 16 Uncontrolled circulator
20
UPM3
5
AUTOADAPT AUTOADAPT three-step task
21
UPM3
5
As default the AUTOADAPT is preset to operate the Curve selector
UPM3 HYBRID control modes, user interface and settings
0.2
0.18
0.16
0.12
0.1
0.08
Reference
TM06 0845 1014
0.06
Area A Q
0.04 duty point
0.02 Fig. 23 New lower proportional pressure curve
0
30 30.5 31 31.5 32 32.5 33 33.5 34
Time [days]
22
UPM3
5
Selection of control mode
PWM profile C
23
UPM3
6
6. Technical description
Technical description
Exploded view
15 14 12 10 8 13 7 5 4 3 1 2
Sectional drawing
4 3 1 2
15
14
24
UPM3
6
Material specification Description of components
Technical description
The Grundfos UMP3 circulators are of the canned-
Pos. Component Material EN/DIN
rotor type as circulator and motor form an integral unit
Control box Composite PC-GF10 FR without shaft seal and with only one gasket for sealing
PCB with SMD and four screws for fastening the stator housing to the
1 Control electronics
components
pump housing. The bearings are lubricated by the
Control box heat sink Aluminium
pumped liquid as the rotor can is filled with water. The
2 Front foil LEXAN 8A13F
focus has been on using eco-friendly materials as well
3 Stator housing Aluminium, silumin
as on limiting the number of materials.
Stator Copper wire
4
Stator lamination Laminated iron Motor description
Push deblocking The efficiency of the three-phase, 4-pole,
device
synchronous, electronically commutated permanent-
Plunger Stainless steel 1.4404
magnet (ECM/PM) motor type is considerably higher
Spring Stainless steel 1.4310
5 compared to a conventional asynchronous squirrel-
Housing for spring Stainless steel 1.4401
cage motor.
Guide disc Stainless steel 1.4401
Housing for sealing Stainless steel 1.4401 The ECM/PM motor is designed according to the
Sealing EPDM canned-rotor principle. The design of the mechanical
6 Radial bearing Ceramics motor components has mainly focused on these
7 Rotor can Stainless steel 1.4401 features:
8 Shaft Ceramics • reliable with stainless steel rotor can in one part and
Rotor NdFeB a specific formed EPDM gasket
Rotor tube Stainless steel 1.4521 • simple design meaning as few components as
9 1.4401/ possible, each with several functions
Rotor cladding Stainless steel
1.4301
• high efficient due to permanent magnets and low-
Bush Stainless steel 1.4301
friction bearings.
Thrust bearing Carbon
10 The motor is cooled by the pumped liquid which
Thrust bearing retainer EPDM
11 Screws Steel, eco-lubric coated reduces the sound pressure level to a minimum. Being
12 Bearing plate Stainless steel 1.4301 software-protected, the circulator requires no further
13 Gasket EPDM motor protection.
14 Impeller Composite/PES 30 % GF Stator housing
EN-GJL-
15 Pump housing Cast iron GG15
150 The aluminium die-cast stator housing with four fixing
16 Neck ring Stainless steel 1.4301 holes is following the design of the well-accepted
Grundfos UP pumps. It enables easy change of motor
positions by removing the four screws holding the
stator housing and turning the housing to the desired
position. There are two versions: one without drain
hole as IP44, and one with one drain hole in two
possible positions as IPX4D. During operation, the
drain hole must always point downwards. UPM3 is
IP44 as standard and IPX4D as an option for
condensing applications. TM05 9258 3613
25
UPM3
6
Stator and windings
Technical description
TM06 02915013
Fig. 27 Stator
Rotor can
The rotor can is drawn out of one sheet of stainless- Fig. 30 Sectional drawing of deblocking device
steel. It contains the grinded and honed upper radial
Shaft with rotor
bearing. On top the rotor can has a hole on which the
deblocking device is welded. The shaft is made of ceramics. To avoid precipitation of
calcium in the radial bearings, the shaft has been
plunge-ground at the journal bearings. It has a
through-going hole to ensure good lubrication and
cooling of the upper bearing. The rotor can does not
need to be vented as air inside the rotor chamber will
escape the system through the through-going hole of
the shaft.
TM05 9247 3613
26
UPM3
6
Thrust bearing Running unit
Technical description
The antimony-free carbon thrust bearing is fitted to the The unit is a pre-mounted combination of shaft with
shaft in a flexible EPDM retainer. rotor, thrust bearing with retainer, bearing plate and
In combination with the bearing plate, the thrust impeller. The running unit is inserted into the rotor can
bearing prevents forces from being transmitted axially with the upper radial bearing. The unit runs as a
to rotor and rotor can. bearing system, ceramic/ceramic, with almost no wear
as long as it is lubricated. During production the unit is
lubricated with glycerine. When the unit is mounted in
a water-filled system, the system water lubricates the
Bearing plate
The bearing plate is made of stainless steel. The
Fig. 36 Gasket
Impeller
The composite impeller is of the radial type with curved
blades. The impeller shaft with rotor and bearing plate
is assembled in one unit to eliminate possible
TM06 0846 1014
Fig. 34 Impeller
27
UPM3
6
Pump housing
Technical description
Control box
The UPM3 control box housing is made of two
composite parts welded together with an aluminium
heat sink on top and covered by a front foil which
cannot be removed. Power and signal connectors are
integrated. There are two versions available with
signal connection designed for Grundfos UPER/UPM
connector or TE Mini Superseal connector.
The control box contains the PCBs for internal power
supply, control and communication. The control box
includes all relevant functions and EMC filter
components. It is available with different hard- and
software, mainly different regarding internal or external
control, with or without user interface and
communication signal as PWM.
TM06 0826 1014
28
UPM3
7
7. Installation
Installation
Mechanical installation Ambient temperature
Mounting dimensions can be found in the data sheets. The ambient temperature must not exceed 70 °C
(measured in a distance of not more than 5 cm in front
Arrows on the pump housing indicate the liquid flow
of the front foil at its lower edge).
direction through the circulator. The circulator is
designed to be installed with horizontal shaft pumping Note: The dew point of the air at ambient temperature
upwards, downwards or horizontally. should always be lower than the liquid temperature,
otherwise condensation may form in the stator
Note: The circulator must always be installed with
housing.
horizontal motor shaft within ± 5 °.
The circulator should be installed in the system in such Relative air humidity
a way that no major amount of air flowing through the
circulator or gathering in the pump housing will affect The relative air humidity must not exceed 95 % in a
the circulator when it is out of operation. If, in addition, non-condensing environment.
a non-return valve is installed in the flow pipe, there is
a high risk of dry running as the air cannot pass the
Storage temperature
valve. -40 to +75 °C.
29
UPM3
7
Electrical installation Inrush current
Installation
The electrical connection and protection must be All electronic circulators contain electronic units that
carried out in accordance with local regulations. must be protected by filters including capacitors and
ECM circulators frequency converters with AC/DC
• The circulator requires no external motor protection.
rectifiers containing capacitors to equalize the waves.
• Check that the supply voltage and frequency This is not the case in most asynchronous circulators.
correspond to the values stated on the nameplate.
• The circulator must not be used with an external EMC-filter Rectifier Bulk capacitor
speed control which varies the supply voltage.
• If an earth leakage circuit breaker is used, check
N
PE
Fig. 40 Symbol on earth leakage circuit breaker If you use a relay to switch the power supply of the
circulator, you risk excessive wear on the relay contact
Leakage current surface.
The pump mains filter will cause a discharge current to To avoid such problems there are different external
earth during operation. and internal solutions.
Leakage current: < 3.5 mA.
High-voltage test
The circulator incorporates filter components that are
connected to protective earth. Therefore, a standard
high-voltage test cannot be made without damaging
the filters.
30
UPM3
7
External solutions in the controller of the Relay and PTC (active - standard for UPM3 HYBRID
Installation
appliance unit variants)
• Specific relays with silver tin oxide (AgSnO2) inrush We recommend that you use this option for circulators
relay contacts. that are not in permanent operation and can be
• Switching at ZERO crossing. interrupted by a relay of the controller of the appliance.
• Standby operation - circulator only switches via the
Weak Comp.
PWM signal. PTC2 L1 1 D15
L 2 2 3
~ +
electronics (active)
UPM3 circulators are available with different hardware: Fig. 43 Relay and PTC
NTC resistor (passive - option for UPM3)
At startup the relay is open. In this mode the PTC
We recommend that you use this option for circulators resistor is able to limit the inrush current down to a
that are permanently connected to the grid and level of approximately 4 A.
switched on/off by external PWM signal.
During operation the relay is closed. In this mode the
Weak Comp. resistor is by-passed so that efficient operation is
2
L1 1
2
D15
3 guaranteed.
L ~ +
TM06 0820 1014
NTC C10 +
C6
C44
VDR3 C43 1 4
~ - ,QWUHOD\
C14
LQ
C4 RSHUDWLRQ Motor start Motor in operation
N
3 4
31
UPM3
7
Power supply connection Safety
Installation
The circulator must be connected to the power supply • Additional locking latch with pull-out force > 100 N.
with the TE Superseal connector. Adapters are • Lock to be opened only with a screw driver.
available for the use of cables with Molex or Volex
Availability
connectors.
• Worldwide as TE standard.
TE Superseal power connector
Grundfos FCI (used for UPER/UPM)
32
UPM3
7
Overview of technical data
Installation
Feature Specification
CE mark EMC Directive (2004/108/EC)
Standards used: EN 61000-6-2:2005, EN 61000-6-3:2007, EN 55014-1:2006, EN 55014-2:1997,
Low Voltage Directive (2006/95/EC)
Conformity with following relevant EC Directives
Standards used: EN 60335-1:2012, EN 60335-2-51:2003 + A1, Ecodesign Directive (2009/125/EC)
Standards used: EN 16297-1:2012, -2:2012, -3:2012
Ecodesign ErP ready 2015 Fulfilling Ecodesign requirements in 2015, EEI ≤ 0.20, EN16297/3 or -/2
REACh compliancy REACh Directive 1907/2006 (see page 55)
WEEE Directive 2012/19/EU (see page 55)
WEEE compliancy
Circulators are not in scope
RoHS compliancy RoHS Directive 2011/65/EU (see page 55)
VDE certificate: No. 40039416 (see page 54)
VDE Approval It proves the conformity with the essential safety requirements of the EC Low Voltage Directive
(2006/95/EC) including amendments.
VDE code GFNJB and GFNJC
Enclosure class: IP44 (standard without drain holes). Option: IP X4D (with drain hole)
TF class TF110 at 70 °C ambient temperature
High voltage protection EN 60335-1 1000 VAC
Drinking water approvals (WRAS, KTW, DVGW All pump head components will be compliant
W270, etc.) Specific compliant pump housings will be available
Feature Specification
Deblocking software Continuously restarting after 1.33 seconds with max. torque
Deblocking device Manual deblocking device, access from front side
Dry run ability - first start 1 minute (3 x 20 seconds), all circulators will be lubricated with glycerine
Dry run ability - during operation Rotor can filled with water: fulfils EN 60335-2-51
Expected lifetime > 100,000 h (with specified load profile)
Expected lifetime > 500,000 cycles
Minimum switching time power on/off With NTC: 1 min, with relay. No specific requirements
Flow estimation Available depending on the housing, accuracy: see PWM specification
Inrush current With relay: < 4 A, With NTC: < 10 A
Equipment class I (EN 60335-1)
Insulation class F (EN 60335-1)
Maximum leakage current ≤ 3.5 mA (EN 60335-1)
Speed range 563 to 5,991 min-1 (depending on the variant)
Maximum ambient temperature 70 °C
Maximum media temperature 95 °C on composite housings, 110 °C on cast iron housings
Maximum system pressure 1 MPa (10 bar) (depending on the housing material)
Minimum inlet pressure 0.05 MPa (0.5 bar) at 95 °C liquid temperature
Minimum media temperature 0 °C (IP44: above dew point of ambient air)
Minimum supply voltage 160 VAC (with reduced performance)
The motor is protected by the electronics in the control box and requires no external motor
Motor protection
protection.
Peak temperature Temperature = 130 °C, (for peak ≤ 30 min)
Nominal supply voltage EU: 1 x 230 V + 10 %/- 15 %, 50 Hz
Reaction time until the motor runs at 90 % < 1.5 seconds for cold start, warm start and speed change
Reaction time until the return signal is valid < 3.3 seconds for cold start, warm start and speed change
Relative air humidity Maximum 95 %, non-condensing environment.
Storage temperature -40 to +75 °C
33
UPM3
8
8. Startup
Startup
Warning
The use of this product requires
experience with and knowledge of the
product.
Persons with reduced physical, sensory
or mental capabilities must not use this
product, unless they are under
supervision or have been instructed in
the use of the product by a person
responsible for their safety.
Children must not use or play with this
product.
34
UPM3
9
9. Disposal
Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
• Use the public or private waste collection service.
• If this is not possible, contact the nearest Grundfos
company or service workshop.
35
UPM3
10
36
UPM3
11
37
UPM3
12
38
UPM3
13
Data sheets
13. Data sheets
UPM3 15-75 130, 25-75 130, 25-75 180
p H
[kPa] [m] High efficiency
8
70
7
60 6 Ready for Ecodesign
50 5 2015
40 4
30 3
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
P1 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
EEI ≤ 0.20 Part 3
Q [l/s]
[W]
60 PL,avg ≤ 28 W
50
40
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 15-75 130 130 90 72 45 36 92 128 G1 1.8
UPM3 25-75 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 25-75 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
39
Data sheets UPM3
13
UPM3 15-70 130, 25-70 130, 25-70 180
p H
[kPa] [m] High efficiency
7
60
6
50 5 Ready for Ecodesign
40 4 2015
30 3
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
P1 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [l/s]
[W]
EEI ≤ 0.20 Part 3
50 PL,avg ≤ 23 W
40
30
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 15-70 130 130 90 72 45 36 92 128 G1 1.8
UPM3 25-70 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 25-70 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
40
UPM3 Data sheets
13
50 5
Ready for Ecodesign
40 4
2015
30 3
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 Q [m³/h]
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 Q [m³/h]
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 15-60 130 130 90 72 45 36 92 128 G1 1.8
UPM3 25-60 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 25-60 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
41
Data sheets UPM3
13
UPM3 15-50 130, 25-50 130, 25-50 180
40 4
Ready for Ecodesign
30 3 2015
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 Q [m³/h]
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 Q [l/s]
P1
[W] EEI ≤ 0.20 Part 3
35
30 PL,avg ≤ 16 W
25
20
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 15-50 130 130 90 72 45 36 92 128 G1 1.8
UPM3 25-50 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 25-50 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
42
UPM3 Data sheets
13
30 3
Ready for Ecodesign
2015
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 Q [m³/h]
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Q [l/s]
P1
[W] EEI ≤ 0.20 Part 3
25 PL,avg ≤ 12 W
20
15
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 Q [m³/h]
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 15-40 130 130 90 72 45 36 92 128 G1 1.8
UPM3 25-40 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 25-40 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
43
Data sheets UPM3
13
UPM3 FLEX AC 15-70 130, 25-70 130, 25-70 180
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 Q [m³/h]
30
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 Q [m³/h]
Performance curve
Note: For PWM speed curves see data sheet UPM3 15-70 130, 25-70 130, 25-70 180.
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 FLEX AC 15-70 130 130 90 72 45 36 92 128 G1 1.8
UPM3 FLEX AC 15-70 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 FLEX AC 15-70 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
44
UPM3 Data sheets
13
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 Q [m³/h]
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [l/s]
P1
[W] EEI ≤ 0.20 Part 3
50 PL,avg ≤ 23 W
40
30
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 Q [m³/h]
Performance curve
Note: For PWM speed curves see data sheet UPM3 15-70 130, 25-70 130, 25-70 180.
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 FLEX AC 15-70 130 130 90 72 45 36 92 128 G1 1.8
UPM3 FLEX AC 15-70 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 FLEX AC 15-70 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
45
Data sheets UPM3
13
UPM3 AUTO L 15-70 130, 25-70 130, 25-70 180
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
P1 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [l/s] EEI ≤ 0.20 Part 2
[W]
50
PL,avg ≤ 25 W
40
30
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 AUTO L 15-70 130 130 90 72 45 36 92 128 G1 1.8
UPM3 AUTO L 25-70 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 AUTO L 25-70 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
46
UPM3 Data sheets
13
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 Q [m³/h]
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 AUTO L 15-50 130 130 90 72 45 36 92 128 G1 1.8
UPM3 AUTO L 25-50 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 AUTO L 25-50 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
47
Data sheets UPM3
13
UPM3 AUTO 15-70 130, 25-70 130, 25-70 180
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
P1 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [l/s]
[W]
EEI ≤ 0.20 Part 2
50 PL,avg ≤ 25 W
40
30
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 AUTO 15-70 130 130 90 72 45 36 92 128 G1 1.8
UPM3 AUTO 25-70 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 AUTO 25-70 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
48
UPM3 Data sheets
13
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 Q [m³/h]
Performance curve
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 AUTO 15-50 130 130 90 72 45 36 92 128 G1 1.8
UPM3 AUTO 25-50 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 AUTO 25-50 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
49
Data sheets UPM3
13
UPM3 HYBRID 15-70 130, 25-70 130, 25-70 180
p H
[kPa] [m] High efficiency
7
60
6
50 5
Ready for Ecodesign
40 4
2015
30 3
20 2
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
30
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h]
Performance curve
Note: For PWM speed curves see data sheet UPM3 15-70 130, 25-70 130, 25-70 180.
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 HYBRID 15-70 130 130 90 72 45 36 92 128 G1 1.8
UPM3 HYBRID 25-70 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 HYBRID 25-70 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
50
UPM3 Data sheets
13
10 1
0 0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 Q [m³/h]
Performance curve
Note: For PWM speed curves see data sheet UPM3 15-70 130, 25-70 130, 25-70 180.
Dimensions [mm]
Pump type Connections Weight [kg]
L1 L3 B1 B2 H1 H2 H3
UPM3 HYBRID 15-50 130 130 90 72 45 36 92 128 G1 1.8
UPM3 HYBRID 25-50 130 130 90 72 45 36 92 128 G 1 1/2 1.9
UPM3 HYBRID 25-50 180 180 90 72 45 36 92 128 G 1 1/2 2.0
Technical data
System pressure Max. 1.0 MPa (10 bar) Enclosure class IP44 (non-condensing)
0.05 MPa (0.50 bar) at 95 °C liquid
Minimum inlet pressure Motor protection No external protection needed
temperature
Liquid temperature +2 °C to +110 °C (TF110) Approval and marking VDE, CE
51
UPM3
14
14. Accessories
Accessories
Length Product
Picture Product description
[mm] number
52
UPM3
14
Gaskets
Accessories
Product
Description
number
Gasket 1" (D29,5/D21x2) 504023
Gasket 1 1/2" (D44/D32x2), rubber 520046
Insulation kits
Insulation kits for warm water applications are
available on request. Insulation kits for warm water
applications contain two insulation shells. The
thickness of the insulation shells corresponds to the
nominal diameter of the pump. The insulation kit is
tailor-made for the individual pump type and encloses
the entire pump housing. Both insulation shells are
easy to fit around the pump.
Diffusion-tight insulation shells for cold water
applications are not available.
Quick guides
Quick guides for different UPM3 HYBRID variants are
available on request.
53
UPM3
15
EC declaration of conformity
We, Grundfos, declare under our sole responsibility that the products GFNJB (UPM variants with user interface) and
GFNJC (other UPM3 variants), to which this declaration relates, are in conformity with these Council directives on the
approximation of the laws of the EC member states:
Low Voltage Directive (2006/95/EC)
Standards used:
• EN 60335-1:2012/AC:2014
• EN 60335-2-51:2003/A1:2008/A2:2012
EMC Directive (2004/108/EC)
Standards used:
• EN 55014-1:2006/A1:2009
• EN 55014-2:1997/A1:2001/A2:2008
Ecodesign Directive (2009/125/EC)
Commission Regulation (EC) No 641/2009
Commission Regulation (EC) No 622/20012
Standards used:
• EN 16297-1:2012
• EN 16297-2:2012
• EN 16297-3:2012
Warning
The use of this product requires experience with and knowledge of the product. Persons with reduced physical,
sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in
the use of the product by a person responsible for their safety. Children must not use or play with this product.
Preben Jakobsen
Technical Manager - HVAC OEM
GRUNDFOS Holding A/S
Poul Due Jensens Vej 7
8850 Bjerringbro, Denmark
Person authorised to compile technical file and
empowered to sign the EC declaration of conformity.
VDE certificate
These pumps are certified by VDE.
Product code: GFNJB or GFNJC
VDE certificate No. 40039416
This Marks Approval forms the basis of the CE declaration of conformity and the CE marking by the manufacturer or
his agent and proves the conformity with the essential safety requirements of the EC Low Voltage Directive (2006/95/
EC) including amendments.
54
UPM3
15
REACH compliancy - Chemical Management - Grundfos Focus List
Torben Brændgaard
Group Environment Manager
55
ECM: 1120472
98644852 0314
www.grundfos.com
Telephone: +45 87 50 50 50
GRUNDFOS HVAC OEM Division . DK-8850 Bjerringbro . Denmark
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S