Short Circuit Analysis in Unbalanced Distribution Networks: R. Ebrahimi, S. Jamali, A. Gholami and A.Babaei
Short Circuit Analysis in Unbalanced Distribution Networks: R. Ebrahimi, S. Jamali, A. Gholami and A.Babaei
ABSTRACT
In this paper a short circuit analysis algorithm for radial three-phase distribution networks, based on two relationship
matrices method, is presented. Two relationship matrices, the bus-current-injection-to-branch current matrix and the
bus-current-to-bus-voltage matrix are used to represent the special topological characteristics of distribution networks.
These two matrices can be accomplished by simple building algorithms and are easily implemented. The proposed short
circuit analysis method is developed from these two matrices and can be used to analyze the various types of
unsymmetrical faults only by one model. This model is included from four impedances that their amounts can be set
from zero to extreme. Therefore, each kind of unsymmetrical faults is modelled by adjusting these impedances suitably.
Since the proposed method does not use the traditional admittance matrix and only uses one model for fault
calculations, therefore, the proposed method can achieve the advantages of reducing computation time, improving
accuracy and efficiency, with lower memory requirements especially. Simulation results such as phase current and post-
fault voltage profiles obtained using the proposed technique and IEEE 34-bus network are presented and discussed.
Keywords: Short circuit analysis method, Unsymmetrical fault, Unbalanced Distribution networks, Four impedances
model.
Authorized licensed use limited to: University of Moratuwa. Downloaded on September 07,2021 at 05:46:12 UTC from IEEE Xplore. Restrictions apply.
phase line model between bus i and j. Step 1: For a distribution system with n buses (total
available phase-buses), form BIBC matrix in
dimension n × n . So the equivalent system and
substation transformer impedances consider in BIBC.
Authorized licensed use limited to: University of Moratuwa. Downloaded on September 07,2021 at 05:46:12 UTC from IEEE Xplore. Restrictions apply.
4 TECHNICAL APPROACH fault position, respectively. Also the voltage boundary
conditions on bus k can be written as:
The two primary considerations is developing of an Vka, f = Z f 1 I ka, f + Z f 4 I k , f
effective solution technique for short circuit analysis are
Vkb, f = Z f 2 I kb, f + Z f 4 I k , f (9)
the using a suitable model to simulation fault on system
and selection an suitable method to calculate short Vk , f = Z f 3 I k , f + Z f 4 I k , f
c c
circuit parameters. In this paper, only a suitable model Where Vka, f , Vka, f and Vka, f are the voltages phases a, b
is used to simulation faults on network that is very
simple and useful. Also, the selected method to and c on fault condition respectively.
calculation short circuit parameters is based on
relationship matrices BIBC and BCBV according to After the fault occurs at bas k, the fault-bus currents will
their properties. flow and make the bus voltages of phases. Therefore,
the voltages variation after the fault can be expressed as:
4.1 Four Impedance Model ∆Vka, f = Vka, 0 − Z f 1 I ka, f − Z f 4 I k , f
Most of faults that occur on distribution system are ∆Vkb, f = Vkb, 0 − Z f 2 I kb, f − Z f 4 I k , f (10)
unsymmetrical faults. Unsymmetrical faults include ∆Vkc, f = Vkc, 0 − Z f 3 I kc, f − Z f 4 I k , f
single line (SLG), double line-to-ground (DLG), line-to-
line (L-L) and three line-to-ground etc. Usually, short Where Vkabc abc
, 0 and Vk , f are the pre-fault voltage and after-
circuit analysis methods for calculation fault parameter fault voltage, respectively. Substituting (7) into (4), the
use separated models for any type of faults that increase variation of the branch currents generated by the fault
the volume of calculations and memory requirements. In current can be expressed as:
this paper any types of unsymmetrical faults is
simulated by only one model that called four impedance
[ ] [
B f = [BIBC ] 0 ... I ka, f I kb, f I kc, f 0 T (11) ]
model [8]. As figure 2 shown, this model consists of Equation (11) can be written as:
four variable impedances that three impedances are on ⎡ I ka, f ⎤
three phases and another is located between phases and
ground.
[ ] [ ⎢
B f = BIBCka BIBCkb BIBCkc ⎢ I kb, f ⎥
⎥
] (12)
⎢ I kc, f ⎥
⎣ ⎦
Where BIBCkabc are the columns vectors of BIBC
matrix corresponding to three phases of bus k. By
substituting (12) into (6), the variation of the bus
voltages by the fault branch expressed as:
T
⎡ BIBCka ⎤ ⎡ I ka, f ⎤
⎢ ⎥ ⎢ ⎥
[ ∆V ] = [ BCBV ] ⎢ BIBCkb ⎥ ⎢ I kb, f ⎥ (13)
⎢ BIBCkc ⎥ ⎢ I kc, f ⎥
⎣ ⎦ ⎣ ⎦
Equation (13) can be formulated as:
T
Figure 2 Four impedance model. ⎡∆Vka, f ⎤ ⎡ BCBVka ⎤ ⎡ BIBCka ⎤ ⎡ I ka, f ⎤
⎢ b ⎥ ⎢ b⎥⎢ b⎥ ⎢ b ⎥
These impedances can be set from zero to extreme (for ⎢∆Vk , f ⎥ = ⎢ BCBVk ⎥ ⎢ BIBCk ⎥ ⎢I k , f ⎥ (14)
example 1e12). Therefore, any type of unsymmetrical ⎢∆Vkc, f ⎥ ⎢ BCBVkc ⎥ ⎢ BIBCkc ⎥ ⎢ I kc, f ⎥
faults can be modeled by setting these impedances ⎣ ⎦ ⎣ ⎦⎣ ⎦ ⎣ ⎦
suitably. For example, if Z f 1 and Z f 4 set be zero and Where BCBVkabc are the rows vectors of BCBV matrix
another impedances be 1e12, this model converted to corresponding to three phases of bus k. Equation (14)
single line-to-ground fault. Therefore each kind of faults can be written by substituting (8) and (10) into (14) as:
will be simulated by this model easily. ⎡Vka, 0 − Z f 1 I ka, f − ( I ka, f + I kb, f + I kc, f ) Z f 4 ⎤
⎢ b ⎥
⎢Vk , 0 − Z f 2 I k , f − ( I k , f + I k , f + I k , f ) Z f 4 ⎥ =
b a b c
Authorized licensed use limited to: University of Moratuwa. Downloaded on September 07,2021 at 05:46:12 UTC from IEEE Xplore. Restrictions apply.
faults on three buses are considered and the results are
shown in table 1.
(16)
Where [Z s ] - Zs4
Zf4
Therefore, the fault currents cab be calculated by:
Zs2 + Zs4
Zf4 ,41
Zs4
Zf3 -Jr-Zf4
B U s ~o
4
13
I SiigIe I~e I
A
900 A
272 A
a
1109 A
331 A
ee 0hise tO
b
1178 A
357 A
c
1151 A
349 A
k-';,,
,01
,
LV;o
20
Where [Zsc] is the matrix related to the fault-bus voltage Also, fault currents for buses that are near to substation
and current at the fault position. Various types of faults are higher. For example, the fault current on bus 4 is
higher than buses 13 and 20.
can be simulated by changing Zsl to Zs4 that represent
in Z s matrix and then Zsc matrix respectively. After the Finding fault path currents is another useful property of
fault current at the fault position is calculated, the NEDA program. Figure 4 shows that the fault path
branch currents and bus voltages caused by the fault can current when a single-phase to ground fault occurs on
be calculated directly using 12 and 14, respectively. phase a of bus 4.
•u•u•u••u•••••••u••u••u•ùu•u•u••••u••••••u••••••u••u••u•••u••••u••u•••u•u•
i i iii iiii i
5 TEST CASE AND RESULTS
21
~
99
33
figure 4 shows the constant current on phase a only.
Authorized licensed use limited to: University of Moratuwa. Downloaded on September 07,2021 at 05:46:12 UTC from IEEE Xplore. Restrictions apply.
Figure 6 shows that this feeder is unbalanced; therefore, been shown, the fault current magnitudes and the effect
an exact three-phase short circuit method can provide of them on voltage profiles depend on type and position
more accurate solutions. In this case, the effects of two of fault to substation. For example, three phases to
faults on the voltage profiles are analyzed. These faults ground fault have the highest current magnitude, so it
are: single line to ground on phase a of bus 4 and a line effects on whole of feeder more than another types.
to line between phase b that the effects of them are Also if the fault occurs near to substation, the fault
shown in figures 6 and 7 respectively. current and its effect on voltage profiles will be more
severe. Since the proposed method employs the actual
three-phase models for short circuit analysis and does
not require building the traditional admittance matrix,
the proposed method can achieve the advantages of high
speed, robust convergence and accuracy with lower
memory requirements especially.
7 REFERENCES
AUTHOR'S ADDRESS
6 CONCLUSIONS
The first author can be contacted at
This paper introduced a method for performing short
circuit analysis in unbalanced distribution networks. Electrical Engineering Department
Two matrices and a simple model are developed to Iran University of Science & Technology
analyze the variations of bus voltages, bus current Narmak
injections and branch currents under fault conditions. Tehran
From the above test results, it can be seen that the Iran
proposed algorithm can be used to handle Email [email protected]
unsymmetrical faults efficiently. As the results have
Authorized licensed use limited to: University of Moratuwa. Downloaded on September 07,2021 at 05:46:12 UTC from IEEE Xplore. Restrictions apply.