Fireclass Prec En13 User - 0
Fireclass Prec En13 User - 0
PAGE 1 of 13
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 USER CHECKED BY: AJC
ISSUE No. & DATE: 0 17/04/13
List of Contents
1. OPERATION – FIRE AND FAULT CONDITIONS ....... 3 1.18. SILENCING ALARMS DURING THE DELAY ........ 8
1.1. IF A FIRE IS DETECTED: ................................. 3 1.19. RESOUNDING ALARMS AFTER THE DELAY
1.2. TO SILENCE THE FIRE ALARM SOUNDERS: ...... 3 [ALARMS PREVIOUSLY SILENCED] .................. 9
1.3. TO RESOUND THE FIRE ALARM SOUNDERS 5. OPERATING INSTRUCTIONS FOR OPTIONAL CLOCK
AFTER THEY HAVE BEEN SILENCED: ................ 3 MODULE ........................................................... 9
1.4. TO RESET THE PANEL FROM A FIRE ALARM: ... 3 1.20. TO DISPLAY ALARM EVENT COUNT: .............. 9
1.5. TO OPERATE THE FIRE ALARM SOUNDERS IN 1.21. TO ACCESS THE USER CLOCK MODULE EDIT
EVACUATE MODE: ........................................ 3 FUNCTIONS.................................................. 9
1.6. IF A FAULT IS DETECTED: ............................... 3 6. REPEATER PANEL USER OPERATION - FIRE AND
1.7. TO SILENCE THE BUZZER: ............................. 3 FAULT CONDITIONS ......................................... 10
2. USER INDICATIONS – 16 ZONE PANEL WITH 1.22. IF A FIRE IS DETECTED: ............................... 10
OPTIONAL CLOCK MODULE ................................ 4 1.23. TO SILENCE THE FIRE ALARM SOUNDERS: .... 10
3. USER CONTROLS – 16 ZONE PANEL WITH 1.24. TO RESOUND THE FIRE ALARM SOUNDERS
OPTIONAL CLOCK MODULE ................................ 5 AFTER THEY HAVE BEEN SILENCED: ............. 10
4. CONTROLS – DISABLEMENT AND TEST 1.25. TO RESET THE PANEL & REPEATER(S) FROM A
CONDITIONS ...................................................... 6 FIRE ALARM: .............................................. 10
1.8. DISABLE & ENABLE A ZONE OR ZONES .......... 6 1.26. TO OPERATE THE FIRE ALARM SOUNDERS IN
1.9. DISABLE & ENABLE ALL SOUNDERS: .............. 6 EVACUATE MODE: ...................................... 10
1.10. DISABLE & ENABLE THE FIRE ROUTING 1.27. IF A FAULT IS DETECTED:............................. 10
OUTPUT: ...................................................... 6 1.28. TO SILENCE THE BUZZER: .......................... 10
1.11. DISABLE & ENABLE THE FAULT ROUTING 7. PRECEPT EN REPEATER PANEL OPERATION [16
OUTPUT: ...................................................... 7 ZONE PANEL SHOWN] ...................................... 11
1.12. DISABLE & ENABLE FIRE PROTECTION 8. PRECEPT EN REPEATER PANEL USER CONTROLS
OUTPUT(S):.................................................. 7 [16 ZONE PANEL SHOWN] ................................ 12
1.13. SET & CLEAR ONE MAN ZONE TEST:............. 7 9. ROUTINE TESTING AND MAINTENANCE .............. 13
1.14. SET & CLEAR ONE MAN SOUNDER TEST: ...... 8 10. USER RESPONSIBILITIES .................................. 13
1.15. ENABLE/DISABLE DELAY MODE: .................... 8 11. PRECEPT EN13 ISOLATE/DE-ISOLATE/TEST MODE
1.16. OVERRIDE THE DELAY MODE: ....................... 8 SELECT FLOWCHART ...................................... 13
ST ND
1.17. EXTEND THE DELAY [FROM 1 STAGE TO 2
STAGE]: ....................................................... 8
Danger
This equipment contains hazardous voltages that can cause death, serious personal
injury, or equipment damage.
This equipment contains no user serviceable parts. Refer all maintenance to suitably
qualified personnel.
PAGE 2 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
2) Press the Silence Alarms/Resound button
1. Operation – Fire and Fault once only.
Conditions 3) Set the Access Controls Keyswitch back to
position “0” to lock the controls.
1.1. If a fire is detected:
1.4. To reset the panel from a Fire
On the Precept EN13 Fire Alarm Panel:
Alarm:
1) The general Fire LED will flash and the buzzer
will sound 1) After the fire has been extinguished, turn the
Access Controls Keyswitch on the panel door
2) The relevant zone Fire LED will flash, to position “1”.
indicating the location of the fire.
2) Press the Reset button.
3) If the Delay is OFF [Delay LED off]:
3) The General Fire LED and the Zone Fire LED
The Fire Routing output and LED will operate will clear.
immediately
4) Set the Access Controls Keyswitch back to
The Fire Alarm sounders will operate position “0” to lock the controls.
immediately
1.5. To operate the fire alarm sounders
The Fire Protection output will operate
immediately
in Evacuate Mode:
4) If the Delay is ON [Delay LED flashing]: 1) Turn the Access Controls Keyswitch on the
panel door to position “1”.
The Fire Routing output and LED will operate
2) Press the Evacuate button.
after a delay [if the Fire Routing
fault/disabled LED is illuminated]. 3) The Evacuate LED will light and the panel
buzzer will operate.
The Fire Alarm sounders will operate after a
delay [if Sounder fault/disabled LED is 4) All fire alarm sounders will operate.
illuminated]. 5) Press the Silence/Resound Alarm button to
The Fire Protection output will operate after a silence the fire alarm sounders and clear the
delay [if Fire Protection fault/disabled LED Evacuate LED.
is illuminated]. 6) Set the Access Controls Keyswitch back to
Locate the source of the fire alarm (an LED will be position “0” to lock the controls.
visible on the detector which has been activated). 1.6. If a fault is detected:
1.2. To Silence the fire alarm sounders: 1) The panel buzzer will sound.
1) Turn the Access Controls Keyswitch on the 2) The General Fault LED will flash.
panel door to position “1”. 3) One or more fault LEDs will flash; identifying
2) Press the Silence Alarms/Resound button which element of the system is faulty.
once only. 4) When the fault is corrected the fault indication
3) The fire alarm sounders will become silent. will clear automatically unless the panel is
4) The General Fire LED and the Zone Fire LED configured to latched fault mode – in which
will become steady. case, operating the Reset button will clear the
fault indication.
5) Set the Access Controls Keyswitch back to
position “0” to lock the controls. 1.7. To Silence the Buzzer:
1.3. To resound the fire alarm sounders 1) Press the Silence Buzzer button.
after they have been silenced: 2) The Silence Buzzer button LED will light.
1) Turn the Access Controls Keyswitch on the 3) The buzzer will silence.
panel door to position “1”.
PAGE 3 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16
PAGE 4 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16
PAGE 5 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 6 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
To quit the disable/enable mode: 4) The cursor indication will pulse the yellow
1) To exit the Select Mode, press the Select Zone 1 fault/disabled/test LED.
On/Off button. To select the Fire Protection Output:
2) The Select On LED will clear. Use the Select ↑ button to move the pulsed
3) The cursor indication will clear. cursor indication up through the fault LEDs
4) Set the Access Controls Keyswitch back to until it pulses the Fire Protection
position “0” to lock the controls. Fault/Disabled LED. [The Select ↓ button
moves the cursor down].
1.11. Disable & Enable the Fault
To disable the Fire Protection Output:
Routing Output:
1) Press the Disable button to disable the Fire
To Access disable/enable mode: Protection Output.
1) Turn the Access Controls Keyswitch on the 2) The Fire Protection Fault/Disabled LED will
panel door to position “1”. change to the “On-flash” indication while the
2) Press the Select On/Off button to enter the cursor is on it, changing to steady if the cursor
Select Mode: is moved.
3) The Select On LED will light. 3) The general Disablement LED will light.
4) The cursor indication will pulse the yellow To enable the Fire Protection Output:
Zone 1 fault/disabled/test LED. 1) Press the Enable button to enable the Fire
To select the Fault Routing Output: Protection Output.
Use the Select ↑ button to move the pulsed 2) The Fire Protection Fault/Disabled LED will
cursor indication up through the fault LEDs until change to the “Off-flash” indication while the
it pulses the Fault Routing Fault/Disabled LED. cursor is on it, changing to off if the cursor is
[The Select ↓ button moves the cursor down]. moved on.
To disable the Fault Routing Output: 3) The general Disablement LED will be cleared if
1) Press the Disable button to disable the Fault no other disablements are present.
Routing Output. To quit the disable/enable mode:
2) The Fault Routing Fault/Disabled LED will 1) To exit the Select Mode, press the Select
change to the “On-flash” indication while the On/Off button.
cursor is on it, changing to steady if the cursor 2) The Select On LED will clear.
is moved. 3) The cursor indication will clear.
3) The general Disablement LED will light. 4) Set the Access Controls Keyswitch back to
To enable the Fault Routing Output: position “0” to lock the controls.
1) Press the Enable button to enable the Fault 1.13. Set & Clear One Man Zone Test:
Routing Output.
To access test selection mode:
2) The Fault Routing Fault/Disabled LED will
change to the “Off-flash” indication while the 1) Turn the Access Controls Keyswitch on the
cursor is on it, changing to off if the cursor is panel door to position “1”.
moved on. 2) Press the Select On/Off button to enter the
3) The general Disablement LED will be cleared if Select Mode:
no other disablements are present. 3) The Select On LED will light.
To quit the disable/enable mode: 4) The cursor indication will pulse the yellow
1) To exit the Select Mode, press the Select Zone 1 fault/disabled/test LED.
On/Off button. To select the zone to be tested:
2) The Select On LED will clear. Use the Select ↓ button to move the pulsed
3) The cursor indication will clear. cursor indication down through the fault LEDs
until it pulses on the required zone. [The Select
4) Set the Access Controls Keyswitch back to
↑ button moves the cursor up].
position “0” to lock the controls.
To apply the test mode to the selected zone:
1.12. Disable & Enable Fire Protection
1) Press the Test button to activate the test
Output(s): condition on the selected zone.
To Access disable/enable mode: 2) The zone fault/disabled LED will change to the
1) Turn the Access Controls Keyswitch on the “On-flash” indication while the cursor is on it,
panel door to position “1”. changing to steady if the cursor is moved on.
2) Press the Select On/Off button to enter the 3) The general Test LED will light.
Select Mode: To clear the test mode on the selected zone:
3) The Select On LED will light. 1) Press the Test button again or press the
Enable button to clear the test condition
PAGE 7 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
enabling normal operation of the selected 1.15. Enable/Disable Delay Mode:
zone.
To access delay mode selection:
2) The zone fault/disabled LED will change to the
Turn the Access Controls Keyswitch on the
“Off-flash” indication while the cursor is on it,
panel door to position “1”.
changing to off if the cursor is moved on.
3) The general Test LED will be cleared if no To enable the delay:
other circuits are in the test condition. 1) Press the Delay On/Off/Override button once
to enable the Delay Mode.
To quit the zone test selection mode:
2) The Delay On/Off LED will light.
1) To exit the Select Mode, press the Select
On/Off button. To display the outputs configured to be
2) The Select On LED will clear. delayed:
3) The cursor indication will clear. 1) With the panel in the quiescent condition select
the Access Controls Keyswitch to position “1”.
4) Set the Access Controls Keyswitch back to
position “0” to lock the controls. 2) Press and hold the Disablement button.
3) The fault/disabled LED on each output set to
1.14. Set & Clear One Man Sounder the delay mode will illuminate.
Test: 4) The indications will clear when the
To access test selection mode: Disablement button is released.
1) Turn the Access Controls Keyswitch on the To disable the delay:
panel door to position “1”. 1) With the Delay On, press the Delay
2) Press the Select On/Off button to enter the On/Off/Override button once to disable the
Select Mode: Delay Mode.
3) The Select On LED will light. 2) The Delay On/Off LED will clear.
4) The cursor indication will pulse the yellow To quit delay mode selection:
Zone 1 fault/disabled/test LED.
Set the Access Controls Keyswitch back to
To select the sounders: position “0” to lock the controls.
Use the Select ↑ button to move the pulsed 1.16. Override the Delay Mode:
cursor indication up through the fault LEDs
until it pulses the Sounder Fault/Disabled and When the Delay is running:
Sounder Test LEDs. [The Select ↓ button 1) The Delay On/Off LED will flash.
moves the cursor down]. 2) The general Fire and zone fire LEDs will flash.
To activate the sounder test: 3) The panel buzzer will operate.
1) Press the Test button to start the sounder test. Press the Delay On/Off/Override button while
2) The Sounder Test LED will change to the “On- the Delay On/Off LED is flashing to override the
flash” indication while the cursor is on it, delay allowing all delayed outputs to operate
changing to steady if the cursor is moved. immediately.
3) The general Test LED will light. 1.17. Extend the Delay [from 1st stage
4) The sounders will operate for 2 seconds every to 2nd Stage]:
15 seconds until the test mode is switched off.
When the panel is configured to the two stage
To terminate the sounder test: delay mode and before 60 seconds has elapsed
1) Press the Test button again or press the since the fire alarm triggered:
Enable button to clear the test condition 1) Press the Silence Buzzer button.
enabling normal operation of sounders.
2) The Silence Buzzer button LED will light.
2) The sounders will silence.
The buzzer will silence.
3) The Sounder Test LED will change to the “Off- nd
flash” indication while the cursor is on it, The 2 stage delay will start.
changing to off if the cursor is moved on. 1.18. Silencing Alarms during the
4) The general Test LED will be cleared if no Delay
other circuits are in the test condition.
Turn the Access Controls Keyswitch on the
To quit test selection mode: panel door to position “1”.
1) To exit the Select Mode, press the Select Press the Silence Alarms/Resound button.
On/Off button.
1) The General Fire LED and the Zone Fire LED
2) The Select On LED will clear. become steady.
3) The cursor indication will clear.
2) The sounders will not operate after the delay
4) Set the Access Controls Keyswitch back to has timed out.
position “0” to lock the controls.
PAGE 8 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Set the Access Controls Keyswitch back to To set Current Time:
position “0” to lock the controls. Press SELECT ↓, to enter current Time Set Display:
1.19. Resounding Alarms after the HH:MM:SS
HH flashing
Delay [Alarms previously silenced] Time Set
Turn the Access Controls Keyswitch on the
panel door to position “1”. Press ENABLE (+) or DISABLE (-) to change HH to
desired value (00 to 23)
Press the Silence Alarms/Resound button.
1) The General Fire LED will flash. Press SELECT ↓, Time Set Display:
2) The sounders operate. HH:MM:SS
MM flashing
Set the Access Controls Keyswitch back to Time Set
position “0” to lock the controls.
Press ENABLE (+) or DISABLE (-) to change MM to
5. Operating Instructions for desired value (00 to 59)
Optional Clock Module Press SELECT ↓, Time Set Display:
Normal Time Display (no LCD backlight): HH:MM:SS
SS flashing
HH:MM:SS HH:MM:SS Time Set
or
D/N ON D/N OFF
Press ENABLE (+) or DISABLE (-) to reset the SS
1.20. To Display Alarm Event Count: value to zero.
To display current alarm count, press the Test
Press SELECT ↓, Time Set Display to exit to
Display button. Alarm count display:
Day/Night mode On/Off Set Display:
D/N ON D/N OFF
ALARMS:- NNNN = or
Change? Change?
NNNN.. 0000 to 9999
Pressing SELECT ↓ repeats the cursor/display
The Test Display button does not need to be held
changes as above.
pressed. The Alarm Count will be displayed for 5
Pressing SELECT ↑ repeats the cursor/display
seconds and then the display will return to normal.
changes as above in reverse.
Note: If the Alarm Counter feature is not enabled
then the normal time will still be displayed and the To exit Clock Module Menu:
LCD backlight will illuminate when Test Display is
operated. Press SELECT ON/OFF: Module switches off the
LCD Backlight and exits configuration mode.
1.21. To access the User Clock Module Normal Time Display:
Edit Functions HH:MM:SS HH:MM:SS
or
Select Access Control key switch to position 1. D/N ON D/N OFF
Press the SELECT ON/OFF switch.
On completion of editing, return the Access Control
Use the “Up/down” keys to scroll the cursor LED
Keyswitch to position 0.
indication through the selectable options on the
panel display LEDs until the LCD backlight
illuminates. Normal Time Display:
HH:MM:SS HH:MM:SS
or
D/N ON D/N OFF
PAGE 9 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
2) Press the Reset button.
6. Repeater Panel User Operation 3) The General Fire LED and the Zone Fire LED
- Fire and Fault Conditions will clear.
4) Set the Access Controls Keyswitch back to
1.22. If a fire is detected: position “0” to lock the controls.
On the Precept EN Repeater Panel:
1.26. To operate the fire alarm
1) The general Fire LED will flash and the buzzer
will sound
sounders in Evacuate Mode:
1) Turn the Access Controls Keyswitch on the
2) The relevant zone Fire LED will flash,
repeater door to position “1”.
indicating the location of the fire.
2) Press the Evacuate button.
3) If the Delay is OFF [Delay LED off]:
3) The Evacuate LED will light and the repeater
The Fire Routing output and LED will
buzzer will operate.
operate immediately
4) All fire alarm sounders will operate.
The Fire Alarm sounders will operate
immediately 5) Press the Silence/Resound Alarm button to
silence the fire alarm sounders and clear the
The Fire Protection output will operate
Evacuate LED.
immediately
6) Set the Access Controls Keyswitch back to
4) If the Delay is ON [Delay LED flashing]:
position “0” to lock the controls.
The Fire Routing output and LED will
operate after a delay [if configured for 1.27. If a fault is detected:
delayed operation]. 1) The repeater buzzer will sound.
The Fire Alarm sounders will operate after a 2) The General Fault LED will flash.
delay [if configured for delayed operation]. 3) One or more fault LEDs will flash; identifying
The Fire Protection output will operate after which element of the system is faulty.
a delay [if configured for delayed 4) When the fault is corrected the fault indication
operation]. will clear automatically unless the panel is
Locate the source of the fire alarm (an LED will configured to latched fault mode – in which
be visible on the detector which has been case, operating the Reset button will clear the
activated). fault indication.
1.23. To Silence the fire alarm 1.28. To Silence the Buzzer:
sounders: 1) Press the Silence Buzzer button.
1) Turn the Access Controls Keyswitch on the 2) The Silence Buzzer button LED will light.
repeater door to position “1”. 3) The buzzer will silence.
2) Press the Silence Alarms/Resound button
once only.
3) The fire alarm sounders will become silent.
4) The General Fire LED and the Zone Fire LED
will become steady.
5) Set the Access Controls Keyswitch back to
position “0” to lock the controls.
1.24. To Resound the fire alarm
sounders after they have been
silenced:
1) Turn the Access Controls Keyswitch on the
repeater door to position “1”.
2) Press the Silence Alarms/Resound button
once only.
3) Set the Access Controls Keyswitch back to
position “0” to lock the controls.
1.25. To Reset the panel & repeater(s)
from a Fire Alarm:
1) After the fire has been extinguished, turn the
Access Controls Keyswitch on the repeater
door to position “1”.
PAGE 10 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET
7
GENERAL TEST
8
GENERAL DISABLEMENT
SILENCE 9
COMMUNICATION FAULT BUZZER
10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED
14
FIRE ROUTING FAULT/DISABLED TEST DISPLAY 15
FAULT ROUTING FAULT/DISABLED 16
FIRE FAULT
1. THE RED ZONE INDICATOR 1. DETERMINE THE CAUSE
O I WILL PULSE SHOWING THE OF THE FAULT.
LOCATION OF THE FIRE. 2. PRESS SILENCE BUZZER.
2. CARRY OUT THE 3. CALL YOUR SERVICE
REQUIRED FIRE DRILL. ENGINEER.
3. TO SILENCE ALARMS SYSTEM FAULT
PRESS SILENCE ALARMS. THE PANEL IS INOPERATIVE.
4. TO RESET FROM THE FIRE ARRANGE FOR
CONDITION PRESS RESET. ALTERNATIVE FIRE
DETECTIN MEASURES.
PAGE 11 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET
7
GENERAL TEST
8
GENERAL DISABLEMENT
SILENCE 9
COMMUNICATION FAULT BUZZER
10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED
14
FIRE ROUTING FAULT/DISABLED TEST DISPLAY 15
FAULT ROUTING FAULT/DISABLED 16
FIRE FAULT
1. THE RED ZONE INDICATOR 1. DETERMINE THE CAUSE
O I WILL PULSE SHOWING THE OF THE FAULT.
LOCATION OF THE FIRE. 2. PRESS SILENCE BUZZER.
2. CARRY OUT THE 3. CALL YOUR SERVICE
REQUIRED FIRE DRILL. ENGINEER.
3. TO SILENCE ALARMS SYSTEM FAULT
PRESS SILENCE ALARMS. THE PANEL IS INOPERATIVE.
4. TO RESET FROM THE FIRE ARRANGE FOR
CONDITION PRESS RESET. ALTERNATIVE FIRE
DETECTIN MEASURES.
Access Controls
Keyswitch:
0 – Controls Locked
1 – Controls Unlocked
Switch
Functionality Button Availability
Description
Operates all sounders continuously and lights the Evacuated When controls are unlocked
Evacuate
LED adjacent to the button until the silence button is operated
Following a fire alarm condition, 1st operation stops sounders. When controls are unlocked
Silence/Resound The General Fire LED and the Zonal fire LED will change from
Alarms flashing to steady. 2nd operation restarts the previously silenced
sounders
When controls are unlocked
and [if silence before reset is
Clears the panel display, resets the zones, outputs and operates
Reset configured] alarms silence switch
the reset relay.
has been operated.
1] Press to stop the buzzer sounding in fire or fault conditions. When controls are locked or
unlocked
2] In 2 Stage Delay Mode, with stage 1 delay running, press to When the panel is in the fire
Silence Buzzer
start stage 2 delay otherwise all delayed outputs operate when condition and the delay is
Stage 1 timer times out. running. Controls are locked or
unlocked
1] Press once to Enable the delay mode, lighting the adjacent 1] When controls are unlocked
delay on LED. Press again to disable the delay mode and turn and delay period is set to a value
off the LED > 0.
Delay
On/Off/Override
2] Overrides the delay when delay is running. All delayed 2] When the panel is in the fire
outputs will operate immediately. condition and the delay is
running.
Press to illuminates all LEDs on the display and operate the When controls are locked or
Test Display buzzer. All indications remain active for approx 5 seconds after unlocked
button release.
PAGE 12 of 13
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN USER CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Turn ACCESS
Zone 1 Fault LED CONTROLS
keyswitch to "1"
Zone 2 Fault LED
Panel
Controls Enabled
Panel
SELECT cursor moves SELECT cursor moves Selected Circuit Selected Circuit Selected Circuit in Test mode. SELECT mode inactive.
to next LED to previous LED returned to normal Disabled. If Zone then Zone Fault LED SELECT cursor clears.
operation. Circuit Fault LED pulses pulses "ON/flash" SELECT LED clears.
LED pulses "OFF/flash" "ON/flash" (Changes to steady when
(Changes to OFF when (Changes to steady cursor is removed).
cursor is removed) when cursor is If Sounders then Sounder
removed) TEST LED is ON.
PAGE 13 of 13