Fireclass Prec en Inst - 0
Fireclass Prec en Inst - 0
PAGE 1 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
List of Contents
PAGE 2 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
R0
C1631 repeater
1 2 3
CEL C1631
R1
ISSUE 0
R2
interface
[ optional]
Mains
transformer Removable chassis
1
2 DELAY/
4 MINUTES
8
Mains transformer
Batteries Motherboard
Batteries
PAGE 3 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
C1631 repeater
ZONE ZONE ALARM AU interface
CHANG
INPUTS OUTPUTS REPEATER
ACTIV
RESE
X
CLAS
EVAC
CIRCUITS CIRCUITS
E
EVA
OUTPUTS
RST
BUZ
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.
N/T
S
DIS
SC
A
B
1 2 3 4
C
SIL
O
.
.
0
.
.
1 2 3 4 + - + - + - + - 24V
V
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21
[optional]
O/ C/ C/ O/ C/ O/ N/
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - +
P
FAULT - +
P
FIRE - +
P
FIRE -
P
RESEC
9 T
0 1 2ZONE 3 4 5 6 ROUTING ROUTING PROTECTION
CIRCUITS
EXPANSION
J1
J1
J1 J1 J1
7
J1 J1 J1
6 5 4
2 1 0
7
6
J
I/O
8 7
J J
Removable chassis
J2
0
SW
1 R
Motherboard
EXPANSION
1
0
R J2
CEL C1631
ZONE
2
1 0
ISSUE 0
R
3
2
~ ~
TB23
1
J
DISPLA
J
Y
Mains
1
SW SW
INHIBIT F/P ON 2 SILENCE BEFORE
1
1
DELAYRESET
ON
2 DELA
3
Motherboard
AUTONON-LATCH
CONFIG MINUTE
Y/
L 4 S L
4
ZONES
transformer
1 CONFIG I/S 2
8
5
ZONESM/S
CONFIG ZONAL L
6
ZONES
CONFIG DELAY ALARMS
PULSE NON-ALARM 3
7
ZONES
CONFIG DELAY ZONES
SILENT ZONE L J18
8
O/PS TEST 4 B
2 STAGE BUZZER
9
DELAYON EVAC
ALARMS DISABLE
LATCHED TB11 TB13 L
ORIG
0
1
0
1
ONLY FAULTS FS 5
N1 BATTERY - BAT + THER
1 FUSE T M
Batteries
Batteries
C1631 repeater
ZONE ZONE ALARM AUX INPUTS OUTPUTS REPEATER ZONE CIRCUITS FI
interface
CHAN
+ 17 - + 18 - + 19 - + 20 - + 21 - + 22 - + 23 - + 24 -
ACTI
RES
[optional]
GE
CIRCUITS CIRCUITS
CLA
D1
EVA
VE
ET
OUTPUTS
SS
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.
AC
EV
C.
RS
BU
A
B
SC
1 2 3 4
T.
Z.
N/
DI
S.
O
SI
L.
1 2 3 4 + - + - + - + - 24V 0V
TB TB TB TB TB TB TB TB
TB TB TB TB TB TB TB TB TB TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB2 TB2 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 0 2 4 5 6 7 8 9 0 1
Removable
O/ C C/ O/ C/ O/ N/ + 25 - + 26 - + 27 - + 28 - + 29 - + 30 - + 31 - + 32 -
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - P
+ FAULT /- +
P
FIRE - +
P
FIRE -
P
RESC
9
I/O EXPANSION
CIRCUITS
J1
J1
J1 J1 J1
J1 J1 J1
7
6 5 4
2 1 0
7
8 7 6
J J J
J
1
chassis
ZONE EXPANSION J2
0
TO MOTHERBOARD
S
W1 R
1 2 3
0
R J2 J
CEL C1631
ISSUE 0
1
R 0 1
2
Motherboard
17 -32 zone
~ ~
1
J
TB2
expansion
3
DISPL
J
AY
S S
INHIBIT F/P SILENCE BEFORE
board
W1 W2
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
ON NLZ
DELAY ALARM SIL RESET
1
DELAY& RESET
ON DEL
2 MINUT
AUTO
CONFIG NON- AY/
L 4 ES L
LATCH I/S
CONFIG ZONES
1 8 2
ZONESM/S
CONFIG ZONAL J1
L
ZONES
CONFIG DELAY ALARMS
PULSE NON- 8B
3
Mains
ZONES
CONFIG ALARM
SILENT ZONES
ZONE L
DELAY
2 STAGE O/PS TEST
BUZZER 4
DELAY DISABLE TB1 TB1 L
ORI ALARMS ON LATCHED
0
1
0
1
FS 1 3 5
GN1 EVAC ONLY FAULTS BATTERY - BA + THE
1 FUSE TT RM
Batteries
Batteries
PAGE 4 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 4 – 2/4 Zone Precept EN panel - General Assembly (with optional clock module)
PAGE 5 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 5 – 8/16 Zone Precept EN panel - General Assembly (with optional clock module)
PAGE 6 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 6 – 32 Zone Precept EN panel - General Assembly (with optional clock module)
PAGE 7 of 31
Typical Zone Wiring Typical Alarm Circuit Wiring Typical Input Circuit Wiring
22uF capacitor end-of-line device for Remote Silence, Evac, Reset &
-observe polarity Class Change,
EQUIPMENT:
+ 1A 2A -
Manual call point
Typical remote
with 680R resistor
0
output wiring
+ -
+ 1 2 -
+ - 2k2 0.5W
resistor
Typical zonal
output wiring Terminal identification
09/03/12
notes:
+
Cl/C = Class Change.
+ -
B Act = Buzzer Active
Connect to - RST = Reset
24V DC Aux DC 24V
+ -
relay + Repeater Wiring - see
Detector base with Figure 9 - Repeater
Schottky Diode connection diagram
6. Typical wiring schematic – 16 Zone
FIRECLASS PREC EN INST
1 2 3 4 1+ 1- 2+ 2- 3+ 3- 4+ 4- 5+ 5- 6+ 6- 7+ 7- 8+ 8- 1+ 1- 2+ 2- 3+ 3- 4+ 4 - 24V 0V Sil Evac RST Cl/C Dis Evac BAct A B Scn N/C
Lower terminal tier
PAGE 8 of 31
Lower terminal tier Zone O/Ps Zone Circuits Alarm Circuits Aux DC Inputs Outputs Repeater RST
FIRECLASS PRECEPT EN
Upper terminal tier Zone Circuits Aux DC Fault Routing Fire Routing Fire Protection RST Upper terminal tier
9+ 9 - 10 + 10 - 11 + 11 - 12 + 12 - 13 + 13 - 14 + 14 - 15 + 15 - 16 + 16 - 24V 0V O/+ P C/- C/+ P O/- C/+ P O/- P N/O
Figure 7 – Typical Wiring Diagram
Fire Routing, Fault Routing & Fire Protection O/P configuration - Output specification: Fire and Fault Routing
output wiring shown for the
When configured as monitored/powered outputs: When configured as volt-free changeover relays : monitored/powered
configuration
For Fire Routing and Fire Protection O/Ps: For Fire Routing and Fire Protection O/Ps:
Quiescent: 5V DC Volt free relay contacts shown in quiescent [de-energised]
Relay local to fault Relay local to fire
Active [fire]: 24V nom] condition.
routing equipment routing equipment
equipment equipment
For Fault Routing O/P: For Fault Output:
Quiescent: 24V DC [nom] Volt free relay contacts shown in healthy [energised]
Active [fault]: 5V condition.
Field relay spec:
Connections: Coil resistance - 2.6K to 4.5K Ohms
Connections:
Connect to normally open or normally closed contact as Voltage 24V DC Nom
Observe correct polarity.
required.[P= Pole, C= Closed, O = Open] [min 18V, max 30V]
[+ = Positive, - = Negative]
Applied voltage must not exceed 30V DC. Fitted with suppression diode as shown.
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Class change
Aux
Reset N/C
Buz Active
Zone O/Ps Zone Circuits Alarm Circuits
DC
EVAC
1 2 3 4 5 6 7 8 1 2 3 4
EVAC
GND
RST
DIS
24V
SIL
0V
1 2 3 4 + - + - + - + - + - + - + - + - + - + - + - + - A B
Lower
terminal tier
Upper
terminal tier
+ - + - + - + - + - + - + - + -
O/+
C/+
C/+
24 V
0V
P
C/-
P
O/-
P
O/-
N/O
P
9 10 11 12 13 14 15 16
Zone Circuits Aux Fault Fire Fire Reset
Precept DC Routing Routing Protection
O/- = Normally Open or -ve
2 O/+ = Normally Open or +ve
4 P = Pole
C/+ = Normally Closed or +ve
8 C/- = Normally Closed or -ve
16/32
Grey fill indicates I/O available on selected panel
Zone Circuits
17 18 19 20 21 22 23 24
+ - + - + - + - + - + - + - + -
+ - + - + - + - + - + - + - + -
25 26 27 28 29 30 31 32
Zone Circuits
PAGE 9 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Zone Reset
Detection Relay
Inputs Output
J6,J7,J8
Fault Routing Connector
Output for C1632,
configuration J10,J11,J12 Zone
Fire Routing J14,J15,J16 Expansion
links
Output Fire Protection Output Board
configuration links configuration links
J1
Display C1631
Connector Repeater
Interface
Secondary
AC from
transformer
Configuration
mode enabled FS1
LED indicator Battery
Fuse J18
Power Supply LED Earth Fault
indicators: Monitoring
Battery OUTPUT OK
Terminals Link
Configuration Battery/Charger Fault
switches Configuration Charger Fault
SW1/1 to SW1/10 switches Battery Mains Fault
SW2/1 to Thermistor
SW2/10 Terminals
PAGE 10 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Secondary AC
Supply from
Transformer
28V, 0V DC
Power output
Mains
Fault
Output
Common
Fault
Output
PAGE 12 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 13 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
11.2 Installation Instructions 9. Remove the chassis from the enclosure and
1. Carefully remove the control panel from the place carefully to one side.
packing and lay the panel on a flat surface. NOTE: The door and chassis both contain
2. Open the door of the panel. PCBs with sensitive and fragile electronic
components on them. You must place them
3. Locate the spares bag and check that the
in an area that is clean, dry and dust-free,
following items are present:
where they will not be damaged. You can
Precept EN Precept EN place them inside the original packing box
Item
2/4 8/16/32 but you must ensure that sufficient soft
T1AH250V T3.15AH250V packing is used to keep the door and chassis
Mains Fuse 20mm 20mm separated.
1 off 1 off
F5AL250V 10. Identify the three indented holes in the backbox
F2AL250V 20mm [8/16] that are used to mount the enclosure.
Battery Fuse 20mm
F6.3AL250V 11. Place the enclosure in the desired location and
1 off
20mm [32] mark the position of the top indented hole.
EOL capacitors for Remove the enclosure and fit a suitable fixing to
22μF, 35V axial. 22μF, 35V axial.
normal zone
2/4 off 8/16/32 off
the wall. Hang the enclosure from the top fixing
monitoring point and ensure that it is level. Mark the
EOL resistors for locations of the other two mounting holes.
3K9 0.25W 3K9 0.25W
alarm circuits and
4/8 off 12/20/36 off 12. Remove the enclosure from the wall and fit
I.S. zones.
Key Ref.: Key Ref.: suitable fixings to the two remaining mounting
Engineer‟s door points. Fix the enclosure to the wall using all
801 [Flat] 801 [Flat]
keys three mounting points.
1 off 1 off
Key Ref.: Key Ref.: 13. Carefully remove the required knock-outs in the
Access Control
801 [Tubular] 801 [Tubular] panel enclosure and gland all field wiring in
keys
1 off 1 off
place ensuring that the cable conductors are of
Positive battery Red Red
sufficient length inside the enclosure. Ensure
lead 1 off 1 off
Negative battery Black Black that all conductors are clearly labelled. DO NOT
lead 1 off 1 off remove knock-outs from any unused cable
Battery coupling Blue Blue entries. Any unused cable entries which are
lead 1 off 1 off open must be sealed with a suitable plug
Battery terminal Precept EN 32 (available separately).
N/A
insulation boot only 14. Connect the earth drain wires of the field cabling
to the brass earth bar positioned at the top of the
11.2.1 Panel Installation Instructions backbox. Up to two drain wires may be
1. Disconnect the display ribbon cable from the connected to each terminal.
motherboard header. 15. Ensure that continuity of any cable shield is
2. Disconnect the earth strap connecting the door maintained through to the last device on the
and backbox via the spade terminal on the door. circuit. The shield must only be connected to
enclosure earth in the panel by using the earth
3. Unscrew the hinge pin at the bottom of the door
bars provided. [Different requirements apply for
whilst supporting the door. Swing the bottom of
the screen of data cable used for connecting
the door clear of the backbox and pull the door
repeaters - see 11.2.2 below].
away from the top hinge pin.
16. Connect the incoming protective earth conductor
4. Place the door carefully to one side and replace
to the Earth terminal in the mains terminal block.
the bottom hinge pin in the backbox.
This is the primary earth point and is labelled
5. Unscrew and remove the two lower chassis [also labelled E]. See Section 5.
screws and only slacken the top two mounting
17. Clear any dust and debris from inside the
screws.
enclosure.
6. Carefully lift the chassis upward to align the
18. Connect the mains-in Live cable to the mains
screw heads with the large holes in the chassis
terminal block [L terminal] as indicated in section
keyholes. Lift the chassis clear of the upper
5.
screws and rest the chassis in the bottom of the
enclosure. Take care not to strain the wires that 19. Connect the mains-in Neutral cable to the mains
remain connected to the backbox. terminal block [N terminal] as indicated in
section 5.
7. Disconnect the earth strap connecting the
backbox and chassis at the earth bar. 20. Secure the mains-in cable to the cable clamp
adjacent the mains terminal using the cable tie
8. Disconnect the flying leads from the transformer
supplied. NOTE: The clamp should be over the
to the mains terminal block and earth bar.
outer cable insulation.
PAGE 14 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
21. Reinstallation of the chassis is the reverse of 26. Connect the blue battery lead between the
removal. Reconnect all wires and ensure none positive (red) terminal of the left-hand battery
are trapped between the chassis and backbox. and the negative (black) terminal of the right-
Do not connect the field wiring at this stage. hand battery. Note that the batteries will not
22. Refit the door. The refitting procedure is the power the panel until the mains supply is
reverse of removal. Ensure that the earth strap energised.
and ribbon cable are reconnected correctly.
11.2.2 Optional C1631 Repeater Interface
23. Place the left-hand battery into the bottom of the Installation
enclosure. The terminals should be positioned
towards the centre of the enclosure and the Warning: Observe anti-static precautions
battery should be adjacent to the left side of the 1. Ensure that the panel and repeaters are
backbox, fixed by the raised indents in the powered down and the main and standby
backbox, one above the battery and one to the supplies are disconnected.
right. 2. On the fire alarm panel and each repeater,
24. Place the right-hand battery into the bottom of remove the jumper link at J22 (adjacent to J9)
the panel. The terminals should be positioned and fit a C1631 repeater interface to connectors
towards the centre of the enclosure and the J13 and J9 located immediately to the left of the
battery should be adjacent to the right side of Zone Expansion ribbon connector on the right-
the backbox located by the raised indents in the hand side of the C1627 motherboard. See
back box above the battery and to the left. Figure 10. The board should be held in place by
25. Connect the black battery lead to the power the 12mm high plastic spacer provided.
supply “Batt -” [battery negative] terminal and 3. Connect the RS485 data cable as shown in
connect the red battery lead to the power supply Figure 13.
“Batt +” [battery positive] positive terminal 4. If the repeater is powered from the panel then
[situated on the motherboard for the Precept EN connect the Aux 24Vdc supply from the panel to
2/4, 8 and 16 panels and repeater panel or on the repeater.
the separate power supply board in the Precept
5. Connect the repeater mains power supply (if
EN 32 panel]. The location of the motherboard
required) to the L, N and E terminals as
battery terminals are shown in Figure 10 &
described above for the panel.
Figure 12. Fit the connector on the end of the
black lead onto the negative (black) terminal of Note: Use only RS485 screened data cable.
the left-hand battery. Fit the connector on the
end of the red lead onto the positive (red)
terminal of the right-hand battery.
Repeater Repeater
GND
GND
A
B
A
PAGE 15 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
12. Commissioning iii) Functional testing of all circuits and field devices
to check each circuit and function in turn to
ensure correct operation of the entire system.
12.1 Introduction
The following equipment should be available where In this way any faults may be located quickly and
possible to minimise commissioning time: accurately. The general procedures are as follows:
i) VHF/UHF Portable Radio (for two engineers) 1. Alarm circuits should be checked first. The
correct operation of each sounder should be
ii) Multi-meter or equivalent
checked for correct audibility as specified in
12.2 Commissioning Checklist BS5839:1, using the Evacuate function.
1. Before commissioning, the engineer should 2. Detection zones should be commissioned next.
check the following: The purpose is to establish the correct
functioning of each device and checking for
i) All field wiring has been inspected and tested correct indication at the control panel. The panel
in accordance with Manufacturer‟s wiring responses as configured should be checked at
recommendations, current issues of this time.
BS5839:1 and BS7671 IEE wiring
3. All ancillary inputs and outputs should be
regulations.
commissioned and the functionality confirmed.
ii) All field cables are glanded into the control 4. Fire protection signals should be tested.
panel cabinet.
5. Fire and fault routing signalling should be tested.
iii) Detector bases are terminated but detector
heads are not fitted. Any devices with WARNING: Before testing, the engineer must be
electronic components are not fitted. aware both of the operation of all devices fitted to
Terminations to devices with electronic the auxiliary circuits and of the consequences of
components should be linked through to their operation.
maintain cable continuity. 12.4 Pre-Commissioning Wiring Check
iv) Manual Call Points are not connected but NOTE: This pre-commissioning wiring check
cable is linked through to maintain continuity. procedure should be followed to test all wiring
prior to specific commissioning of any
v) No end-of-line devices (e.g. alarm circuit
detection, alarm and auxiliary circuits.
EOL resistor) are fitted in the field.
1. Ensure that no devices are connected to the
2. The following information should be available to
detection zones and alarm circuits, but that the
the commissioning team:
cables are linked through at the device locations
i) Detection layout drawings. to achieve a continuous circuit.
ii)Wiring schematic diagram. 2. Ensure that the resistance of all cables to earth
iii)
Control Panel installation manuals. and between cores is at least 2M.
iv)Installation manuals for all equipment Check the following:
connected to the system. i) Positive to earth resistance is 2MΩ or
v) Site specific configuration details. greater.
Experience has shown that tracing wiring faults ii) Negative to earth resistance is 2MΩ or
on long circuits that are routed through risers greater.
etc. can be difficult without knowledge of the iii) Positive to negative resistance is 2MΩ or
wiring route. greater.
It is recommended that the electrical installer be 3. Connect a wire link as the end-of-line device on
made available until basic wiring continuity is each of the zones and alarm circuits. At the
proven. A minimum of two persons (e.g. panel end, measure the resistance across the
engineer and mate) is recommended for efficient positive & negative ends of the cables for each
commissioning. of the circuits; ensuring the value does not
exceed 20Ω. Remember to remove the wire
12.3 Commissioning Procedure Overview
links after the tests.
Commissioning is broken in to 3 sections:
Correct polarity throughout all circuits must be
i) Pre-commissioning wiring check.
maintained. Rectify any faults.
ii) Powering the panel up with no field wiring
connected, configuring the panel in accordance All bells, detector heads and call points should
with the site-specific requirements and carrying now be connected and the correct end-of-line
out a functional check. devices fitted. Use the spare end-of-line devices
supplied and leave the EOL devices in the panel
PAGE 16 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
terminals at this stage. Remember to remove 12.6 Configuration
any links fitted to detector bases. Be very careful
to maintain correct polarity at each device. 12.6.1 Basic Default Configuration
Warning: Intrinsically safe zone arrangement. When first powered up, the Precept EN can be
operated in the standard default mode without any
End-of-line capacitors cannot be connected
additional configuration.
to zones monitoring Intrinsically Safe
detection devices in hazardous areas. To do The basic default mode is:
so will risk causing an explosion in the All zones latching fire, non-delay, standard [non-
hazardous area. End-of-line resistors with a intrinsically safe]
value of 3K9Ω must be used, which comply Fire Routing, Fire Protection and Sounder
with the requirements laid down in the outputs not delayed.
installation data sheets provided with the I.S.
barrier and the I.S. fire detection devices. 12.6.2 Site-Specific Configuration
In order for detector head removal
monitoring to function correctly when It is possible to tailor the functionality of the Precept
resistors are used as the end-of-line devices, EN fire alarm panel in line with site-specific
any diodes in the detector bases that are in requirements. Details of the site configurable
circuit when the detector head is removed options and the configuration process are provided
must be disconnected. in section 15.1. Charts are provided in the System
Log Book for planning/recording the actual
The panel must be configured to monitor configuration. This configuration is not lost when
Intrinsically Safe zones. the panel is powered down.
The first device on an Intrinsically Safe zone
must be an I.S. Zener Barrier or Galvanic 12.7 Commissioning Procedure
Isolator. Detectors and Manual Call Points on After completion of the pre-commissioning wiring
the Safe side of the barrier are not permitted. check, power-up and configuration, commission the
To comply with the requirements of BS5839, circuits in line with the following guide.
all manual call points should be located in
the zone cabling between the I.S. 12.7.1 Alarm Circuits
Barrier/Isolator and the first detector. Any 1. Remove the resistor from the first alarm circuit
manual call point or detector located on the terminal and connect the first alarm circuit wiring
“end-of-line” side of a detector will be to the terminals, observing correct polarity.
rendered inoperative if the detector head is Check that any alarm fault indications clear after
removed. a few seconds.
12.5 Powering up 2. Use the Alarm Test facility [see Precept EN User
1. Prior to powering up, the panel will have been Manual] or press Evacuate to operate the
installed in accordance with the installation sounders. Check that all sounders connected to
instructions, all cabling will have been fully the alarm circuit operate.
installed and tested, glanded into the panel 3. Deselect the Alarms Test condition or if
enclosure but not connected to the panel “Evacuate” was used, press silence alarms to
terminals. The mains supply should be isolated stop the sounders operating.
externally to the panel. 4. Repeat steps 1 to 3 for the second and any
2. Check the battery connections are correct. subsequent alarm circuits.
3. Remove the mains supply fuse from the panel
mains terminal block. Once the permit to 12.7.2 Zones
energise the mains supply is in place, energise 1. Work logically and systematically through each
the mains and check the voltage and polarity are zone.
correct before replacing the panel fuse.
2. Zone fault conditions:
4. The panel will power up and if all the end of line
o Remove the end-of-line device from the zone 1
devices are correctly terminated in the panel and
terminals and connect the cables of the zone 1
the battery is OK, the panel should be silent,
circuit to the panel terminals, observing the
displaying only the Power Supply On indication.
correct polarity. Check that any zone 1 fault
5. Turn the Access Keyswitch to “1” and press the indications clear after a few seconds.
Test Display button. The panel should respond
o Check the fault monitoring of the cable is
by lighting all indications and sounding the
correct by applying an open circuit then a short
buzzer. This will continue for a few seconds after
circuit at the end-of-line device (in the field).
the button is released.
Check that the fault condition is indicated on
zone 1 on the fire panel.
PAGE 17 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
o Remove the circuit faults, restoring the circuit The internal buzzer sounds.
to the healthy condition and confirm that the The fault relay operates.
fault indication clears.
5. Repeat steps 1 to 4, one zone at a time, until all
3. Zone fire conditions the zones are commissioned.
o Starting with the device nearest the panel, 6. Any faults that are found must be traced and
operate each manual call point and detection rectified before proceeding.
device on the zone in turn.
o After operation of each device confirm: 12.7.3 Class Change Input
The fire indication is provided on the panel 1. Connect the Class Change switch to the class
on the correct zone. change input on the motherboard.
The fire alarm devices operate correctly in 2. Operate the class change switch and observe:
line with the panel configuration.
i) The alarms sound for 5 seconds then stop.
The Fire Routing and Fire protection outputs ii) The internal buzzer on the panel does not
operate correctly in line with the panel operate.
configuration.
iii) The internal buzzer on repeaters does not
o Press the Silence Alarms and the Reset operate.
buttons after each device test and check the
alarm clears (Manual Call Points must be 3. De-activate the class change switch
manually reset before resetting the panel).
12.7.4 Fire and Fault Routing Outputs
4. Detector removal operation.
o Remove the 1st detector along the zone cable 1. Remove the resistor from the Fire Routing
[counting from the panel] on zone 1 and output circuit terminals and connect the field
observe the following: wiring to the terminals, observing correct
polarity. Check that any fault indications clear
The appropriate amber zone fault LED after a few seconds.
illuminates
2. To operate the output, initiate a fire condition on
The internal buzzer sounds a zone. Check that the fire signal is received at
The fault relay operates the receiving station. Silence and reset the fire
o For non I.S. zone applications: alarm panel to clear the output.
Operate a manual call point between the 3. Remove the resistor from the Fault Routing
detector that has been removed and the EOL output circuit terminals and connect the field
capacitor. Check that the panel reacts as wiring to the terminals, observing correct
described above for a fire condition. polarity. Check that any fault indications clear
after a few seconds.
Refit the detector, reset the manual call point,
press the “Silence Alarms” button and then 4. Initiate a fault condition on the fire alarm panel to
the “System Reset” button on the panel‟s signal a fault to the remote receiving station.
display board and check that the control 5. Confirm the receipt of the fault warning at the
panel returns to its normal state. receiving station.
Repeat for all detectors on the zone. 6. Open-circuit the output wiring of each circuit in
turn, Confirm the fire alarm panel indicates Fire
o For I.S. zone applications:
Routing and Fault Routing faults appropriately.
Remove the 1st detector in the zone cable
7. Reconnect the cabling and confirm the faults
[counting from the panel] and operate a
clear.
manual call point ensuring that the correct
fire alarm condition is raised on the panel
12.7.5 Fire Protection control signal
(assuming the installation complies with
BS5839). 1. Ensure any fire protection equipment to be
Continue to check the operation of all other controlled via the Fire Protection output is locked
manual call points on the zone, resetting the off/safe before attempting any connection,
manual call point and silencing/resetting the testing or commissioning.
panel at each stage. 2. Remove the resistor from the Fire Protection
Refit the detector and check that the control output circuit terminal and connect the field
panel returns to its normal state. wiring to the terminals, observing correct
polarity. Check that any fault indications clear
Continue to test each of the other detectors after a few seconds.
in turn, checking on each removal that:
3. Initiate a fire condition on a zone to operate the
The appropriate amber zone fault LED output. Check that the fire signal operates the
illuminates
PAGE 18 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
interface relay adjacent the fire protection the alarms operate and the internal buzzer
equipment. operates on all repeaters.
4. Open-circuit the field wiring and confirm that the 3. Press the “Silence” button on the fire alarm
fire alarm panel indicates Fire Protection output panel. Check that the alarm circuits silence and
fault. the internal buzzer silences on all repeaters.
5. Reconnect the cabling and confirm the faults 4. Repeat steps 2 and 3 for each repeater.
clear. 5. Operate a Manual Call Point on zone 1 and
6. Final testing and commissioning of the loop check for correct fire indication at each repeater.
through to the fire protection equipment, 6. Press the “Silence Alarms” button on a repeater
including test [simulated] activation of the and check that the alarms are silenced and the
equipment, should be carried out at the Zone 1 fire LED is constantly illuminated on all
appropriate time in conjunction with the engineer repeater panels.
responsible for the fire protection system.
7. Press the “Reset” button on a repeater and
check that the panel and repeaters return to the
12.7.6 Ancillary inputs
quiescent state.
Remote Silence Alarms, Reset and Evacuate inputs 8. Repeat steps 5 to 7 for each zone and ensure
should each be tested by the activation of the “Silence Alarms” and “Reset” operate correctly
remote equipment. The response should be verified from each repeater.
for each signal.
9. Set the DIL switches on the C1631 Repeater
Interface card in the fire alarm panel OFF (No
12.7.7 Ancillary outputs
Repeaters). Check that all repeaters indicate a
The correct operation of equipment connected to “Comms. Fault”.
the Zone Outputs, Disablement Active, Evacuate 10. Set the C1631 Repeater Interface card DIL
Active and Buzzer Active outputs should be verified switches in the fire alarm panel back to their
in turn by initiating a fire condition on each of the previous settings and check that the repeaters
appropriate zones; disabling/enabling a zone; return to normal.
operating the Evacuate button on the panel‟s
11. Set the first repeater address to 0. Check that
display.
the panel indicates a “Repeater fault” and any
additional repeaters display a steady “Comms
12.7.8 Repeaters fault” LED.
1. Power-up the Panel and then the Repeaters. 12. Set the first repeater address back to normal
Only the “Power Supply On” LEDs should be and check that the panel and repeaters return to
illuminated on the Panel and Repeaters. normal.
2. At Repeater 1, turn the Access control switch to 13. Repeat steps 11 and 12 for any other connected
“1”, and press the “Evacuate” button. Check that repeaters.
PAGE 19 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16
PAGE 20 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5
SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16
PAGE 21 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 24 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
SW 2/8 - Silent Zone Test: 15.8 Configuring the Fire Routing, Fire
Select sounder response in One Man [Detector] Protection and Fault routing O/Ps
Test Mode: To configure the Fire Routing Output to volt-free
o OFF: Sounders operate once on each test. relay contacts, remove links J10, J11 and J12.
[These links are combined in a single block].
o ON: Sounders do not respond to a zone test.
To configure the Fire Protection Output to volt-free
relay contacts, remove links J14, J15 and J16.
SW 2/9 - Buzzer Disable: [These links are combined in a single block].
Enable/disable panel fire/fault buzzer. To configure the Fault Routing Output to volt-free
o OFF: Buzzer is enabled. relay contacts, remove links J6, J7 and J8. [These
o ON: Buzzer is disabled. General Disablement links are combined in a single block].
LED illuminated. These links are located below the associated
Not EN54 compliant function. Provided for output in the top right hand section of the
commissioning purposes only. C1627 motherboard. See Figure 10.
15.7 Configurable Options via DIL switch 16. Clock Module Configuration
selection on Repeater Interface Board: and Setting
DIL switch SW1 on the C1631 Repeater
Interface PCB is used to set the quantity of 16.1 Standard Module Engineer Mode:
repeaters and the repeater addresses as
follows: 16.1.1 To zero the Alarm Counter:
o To set the repeater quantity, set SW1 on the This is an ACCESS LEVEL 4 operation.
C1631 fitted to the fire alarm panel in line with
Open panel door and move the DIL switch 1, pole 2
Table 2.
on clock module PCB to the ON position. Return
Table 2 – C1631 Setting Repeater Quantity the DIL switch to the OFF position.
Repeater S/W S/W S/W 16.1.2 To access the Engineer‟s Clock Module
Quantity 1/1 1/2 1/3 Edit Functions
0 Off Off Off
1 On Off Off Normal Time Display:
2 Off On Off HH:MM:SS HH:MM:SS
or
3 On On Off D/N ON D/N OFF
4 Off Off On
5 On Off On Select Access Control key switch to position 1.
Press the SELECT ON/OFF switch.
o To set the addresses of the individual repeater
panels, set SW1 on the C1631 fitted to each Use the “Up/down” keys to scroll the cursor LED
repeater panel in line with Table 3. Note that indication through the selectable options on the
each repeater must have a different address. display LEDs until LCD backlight illuminates.
Normal Time Display:
Table 3 – C1631 Setting Repeater Addresses HH:MM:SS HH:MM:SS
or
Repeater S/W S/W S/W D/N ON D/N OFF
Address 1/1 1/2 1/3
0* Off Off Off
To change the Day/Night Mode
1 On Off Off
2 Off On Off
3 On On Off Press SELECT ON/OFF.
4 Off Off On Delay On/Off Set Display:
5 On Off On D/N ON D/N OFF
* Note: Address 0 = repeater disabled. or
Change? Change?
PAGE 25 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
On the rear of the Clock Module PCB, move the Press ENABLE (+) or DISABLE (-) to change SS
DIL switch 1, pole 1 on to the ON position. to desired value (00 to 59)
Pressing ENABLE (+) or DISABLE (-) toggles To set Day/Night Mode Off Time
setting between D/N ON and D/N OFF.
To set current time Press SELECT ↓, to access day/night OFF Time
Set display:
Press SELECT ↓, to access current Time Set HH:MM:SS HH flashing
display: OFF Time
HH:MM:SS HH flashing
Time Set Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23)
Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23) Press SELECT ↓, OFF Time Set display:
HH:MM:SS MM flashing
Press SELECT ↓, Time Set display: OFF Time
HH:MM:SS MM flashing
Time Set Press ENABLE (+) or DISABLE (-) to change
MM to desired value (00 to 59)
Press ENABLE (+) or DISABLE (-) to change
MM to desired value (00 to 59) Press SELECT ↓, OFF Time Set display:
HH:MM:SS SS flashing
Press SELECT ↓, Time Set display: OFF Time
HH:MM:SS SS flashing
Time Set Press ENABLE (+) or DISABLE (-) to change SS
to desired value (00 to 59)
Press ENABLE (+) or DISABLE (-) to reset the
SS value to zero. Press SELECT ↓, to exit back to Delay On/Off
Set display:
To set Day/Night Mode On Time D/N ON D/N OFF
or
Change? Change?
Press SELECT ↓, to access day/night mode ON
Time Set display: Pressing SELECT ↓ repeats the cursor/display
HH:MM:SS HH flashing changes as above.
ON Time Pressing SELECT ↑ repeats the cursor/display
changes as above in reverse.
Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23) To exit Clock Module menu:
Return WP DIL switch on TIMER MODULE to
Press SELECT ↓, ON Time Set display: OFF position.
HH:MM:SS MM flashing
ON Time Press SELECT ON/OFF: Module switches off
the LCD Backlight and exits configuration mode,
Normal Time display:
Press ENABLE (+) or DISABLE (-) to change HH:MM:SS HH:MM:SS
MM to desired value (00 to 59) or
D/N ON D/N OFF
PAGE 26 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Table 4 – C1651 Clock Module DIL Switch and
16.2 Configuring the Clock Module
Link Settings
The Clock Module is configured by setting Link 1
and DIL switch 1, both located on the rear of the
C1651 Clock Module PCB [accessed by opening LINK 1
the panel door]. Position Function
st
NOTE: Link 1 & DIL switch 1 are only available Fitted 1 fire alarm time display mode
at ACCESS level 4, i.e. they can only be set by Removed Day/Night mode
suitably trained and qualified personnel.
DIL Switch 1
Link 1 DIL
Position Function
Switch
1 Off Clock Module menu configuration disabled
Off
1 On Clock Module menu configuration enabled
1 Off No effect
On
1 On No effect
Off 2 Off Day/Night Mode and Fire Event Counter mode enabled
Day/Night Mode enabled, Fire Event Counter mode disabled.
Off 2 On
[To zero Fire Event Counter, select “On” momentarily then return to “Off.”].
st
On 2 Off 1 alarm fire time and Fire Event Counter mode enabled
st
1 alarm fire time enabled, Fire Event Counter mode disabled.
On 2 On
[To zero Fire Event Counter, select “On” momentarily then return to “Off.”].
PAGE 27 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
LK1 - Select
operating mode
DIL switch S1 -
Select config mode,
reset/disable counter
PAGE 28 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
PAGE 29 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
W
L = 133 L = 151 L = 151 L = 181 L = 133 L = 133 L = 133
W = 67 W = 65 W = 98 W = 76 W = 67 W = 67 W = 67
H = 60 H = 94 H = 94 H = 167 H = 60 H = 60 H = 60
HT H
HT = 66 HT = 98 HT = 100 HT = 167 HT = 66 HT = 66 HT = 66
L
Environmental
All Panels
Specification
Operating temperature: -5ºC to 40ºC
Operating humidity: 5% to 95%
PAGE 30 of 31
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN INST CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
0086
09
0086-CPD-555921
EN54-2
Control and indicating equipment for fire detection and fire alarm systems for buildings
Provided options:
Outputs to fire alarm devices.
Output to fire alarm routing equipment.
Outputs to Fire Protection Equipment - Output type B
Output to fault warning routing equipment.
Test condition.
Alarm Counter.
Delays to Outputs
EN54-4
Power supply equipment for fire detection and fire alarm systems for buildings
PAGE 31 of 31