Page 2 of 6 TFP342
SPRINKLER FINISH
TYPE TEMPERATURE BULB NATURAL CHROME LEAD WAX WAX
LIQUID BRASS PLATED COATED COATED OVER LEAD
NOTES:
TABLE A
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES ELO-231B UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
TFP342 Page 3 of 6
"FITTING SIDE"
Operation Installation TOWARDS SPRINKLER
The glass bulb contains a fluid that The Series ELO-231B Sprinklers must FITTING
expands when exposed to heat. When be installed in accordance with the fol-
the rated temperature is reached, the lowing instructions:
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to NOTES
activate and water to flow. Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
WRENCH
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble RECESS
should be present. The diameter of the (END "A")
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C to 3/32 FIGURE 2
inch (2,4 mm) for the 286°F/141°C W-TYPE 3 SPRINKLER
temperature ratings. WRENCH
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi- installed in the pendent position, and
mum of 30 ft.lbs. (40,7 Nm) of torque upright sprinklers are to be installed in
is to be used to install sprinklers with the upright position.
3/4 NPT connections. A leak tight 1/2 Step 2. With pipe thread sealant ap-
inch NPT sprinkler joint should be ob- plied to the pipe threads, hand tighten
tained with a torque of 7 to 14 ft.lbs. the sprinkler into the sprinkler fitting.
(9,5 to 19,0 Nm). A maximum of 21 ft.
lbs. (28,5 Nm) of torque may be used Step 3. Tighten the sprinkler into the
to install sprinklers with 1/2 NPT con- sprinkler fitting using only the W-Type
nections. Higher levels of torque may 3 Sprinkler Wrench (Ref. Figure 2),
distort the sprinkler inlet and cause except that an 8 or 10 inch adjustable
leakage or impairment of the sprinkler. Crescent wrench is to be used for wax
coated sprinklers. With reference to
Do not attempt to make-up for insuffi- Figure 1, the W-Type 3 Sprinkler
cient adjustment in the escutcheon Wrench or the adjustable Crescent
plate by under- or over-tightening the wrench, as applicable is to be applied
sprinkler. Readjust the position of the to the wrench flats.
sprinkler fitting to suit.
When installing wax coated sprinklers
The Series ELO-231B Upright and with the adjustable Crescent wrench,
Pendent Sprinklers must be installed additional care needs to be exercised
in accordance with the following in- to prevent damage to the wax coating
structions. on the sprinkler wrench flats or frame
Step 1. Pendent sprinklers are to be arms and, consequently, exposure of
< 1 > Close
Page 4 of 6 TFP342
TFP342 Page 5 of 6
NOTES
Each wax stick is suitable for retouch-
ing up to twenty-five sprinklers.
The wax used for 286°F sprinklers is
the same as for 200°F sprinklers, and,
therefore, the 286°F sprinkler is limited
to the same maximum ceiling tempera-
ture as the 200°F sprinkler (i.e.,
150°F).