0% found this document useful (0 votes)
32 views4 pages

3TK28301AL20 Datasheet en

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 4

Data sheet 3TK2830-1AL20

SIRIUS safety relay with relay enabling circuits (EC) 230 V AC, 22.5 mm
Screw terminal EC instantaneous: 4 NO EC delayed: 0 MK for retraction: 1
Expansion unit Maximum achieved SIL / PL: as basic unit

General technical data


product brand name SIRIUS
product designation safety relays
design of the product extension unit
protection class IP of the enclosure IP40
protection class IP of the terminal IP20
touch protection against electrical shock finger-safe
insulation voltage rated value 300 V
ambient temperature
● during storage -40 ... +80 °C
● during operation -25 ... +60 °C
air pressure according to SN 31205 90 ... 106 kPa
relative humidity during operation 10 ... 95 %
installation altitude at height above sea level 2 000 m
maximum
vibration resistance according to IEC 60068-2-6 5 ... 500 Hz: 0,075 mm
shock resistance 8g / 10 ms
surge voltage resistance rated value 4 000 V
EMC emitted interference EN 60947-5-1
installation environment regarding EMC This product is suitable for Class A environments only. In household
environments, this device can cause unwanted radio interference. The
user is required to implement appropriate measures in this case.
reference code according to DIN 40719 extended KT
according to IEC 204-2 according to IEC 750
reference code according to EN 61346-2 F
design of the cascading none
product feature cross-circuit-proof No
Safety Integrity Level (SIL)
● according to IEC 61508 3
SIL Claim Limit (subsystem) according to EN 62061 3
performance level (PL)
● according to EN ISO 13849-1 e
category according to EN ISO 13849-1 4
hardware fault tolerance according to IEC 61508 1
safety device type according to IEC 61508-2 Type A
PFHD with high demand rate according to EN 62061 0.0000000012 1/h
Average probability of failure on demand (PFDavg) 0.000001 1/y
with low demand rate acc. to IEC 61508
T1 value for proof test interval or service life 20 y
according to IEC 61508

3TK28301AL20 Subject to change without notice


3/30/2022
Page 1/4 © Copyright Siemens
number of outputs as contact-affected switching
element
● as NC contact
— for signaling function instantaneous contact 0
● as NO contact
— safety-related instantaneous contact 4
— safety-related delayed switching 0
number of outputs as contact-less semiconductor
switching element
● safety-related
— delayed switching 0
— instantaneous contact 0
● for signaling function
— delayed switching 0
— instantaneous contact 0
stop category according to EN 60204-1 0
Inputs
design of input
● cascading input/functional switching No
● feedback input Yes
● start input No
Outputs
type of electrical connection plug-in socket Yes
operating frequency maximum 1 000 1/h
switching capacity current
● of the NO contacts of the relay outputs at DC-13
— at 24 V 5A
— at 115 V 0.2 A
— at 230 V 0.1 A
● of the NO contacts of the relay outputs at AC-15
— at 115 V 5A
— at 230 V 5A
● of the NC contacts of the relay outputs at DC-13
— at 24 V 5A
— at 115 V 0.2 A
— at 230 V 0.1 A
● of the NC contacts of the relay outputs at AC-15
— at 115 V 5A
— at 230 V 5A
thermal current of the switching element with 5A
contacts maximum
electrical endurance (switching cycles) typical 100 000
mechanical service life (switching cycles) typical 10 000 000
design of the fuse link for short-circuit protection of gL/gG: 6 A, or quick: 10 A
the NO contacts of the relay outputs required
DC resistance of the cable maximum 30 Ω
wire length between sensor and electronics 80 m
evaluation device with Cu 1.5 mm² and 150 nF/km
maximum
make time with automatic start
● at AC maximum 200 ms
make time with automatic start after power failure
● maximum 200 ms
backslide delay time in the event of power failure
● maximum 80 ms
recovery time after power failure typical 120 ms
Control circuit/ Control
type of voltage of the control supply voltage AC
control supply voltage frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz

3TK28301AL20 Subject to change without notice


3/30/2022
Page 2/4 © Copyright Siemens
control supply voltage 1 at AC
● at 50 Hz rated value 230 V
● at 60 Hz rated value 230 V
operating range factor control supply voltage rated
value of magnet coil
● at AC
— at 50 Hz 0.85 ... 1.1
— at 60 Hz 0.85 ... 1.1
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting
width 22.5 mm
height 120 mm
depth 120 mm
Connections/ Terminals
type of electrical connection screw-type terminals
type of connectable conductor cross-sections
● solid 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● finely stranded
— with core end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
type of connectable conductor cross-sections at AWG
cables
● solid 2x (20 ... 14)
● stranded 2x (20 ... 14)
Product Function
product function
● light barrier monitoring No
● standstill monitoring No
● protective door monitoring No
● automatic start No
● magnetically operated switch monitoring NC-NO No
● rotation speed monitoring No
● laser scanner monitoring No
● monitored start-up No
● light array monitoring No
● magnetically operated switch monitoring NC-NC No
● EMERGENCY OFF function No
● pressure-sensitive mat monitoring No
suitability for interaction press control No
suitability for use
● safety switch Yes
● position switch monitoring No
● EMERGENCY-OFF circuit monitoring No
● valve monitoring No
● tactile sensor monitoring No
● magnetically operated switch monitoring No
● safety-related circuits No
Certificates/ approvals
certificate of suitability BG, SUVA, UL, CSA, EN 60204-1, EN ISO 12100, EN 954-1, IEC
61508
● TÜV (German technical inspectorate) certificate Yes
● UL approval Yes
● BG BIA approval No
General Product Approval EMC

3TK28301AL20 Subject to change without notice


3/30/2022
Page 3/4 © Copyright Siemens
Functional
Safety/Safety of Test Certificates other
Machinery

Type Examination Special Test Certific- Confirmation


Certificate ate

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3TK2830-1AL20
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3TK2830-1AL20
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3TK2830-1AL20
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3TK2830-1AL20&lang=en

last modified: 1/26/2022

3TK28301AL20 Subject to change without notice


3/30/2022
Page 4/4 © Copyright Siemens

You might also like