Vol A Drivers Manual of Wap5
Vol A Drivers Manual of Wap5
. ,
p:' .
. .
.~
... CARRIAGE D~REC~ORATE/COMPUTER
WING
COVERING LETTER i
0 OFFICIAL OF
15 CATEGORY OF DOCUMENTS
A) COMPUTER GENERATED GOOD QUALITY A -
B) COMPUTER GENERATED (DOT MATRIX)
Ti ?'.-.->.r-,-r-.,
D) HAND WRITTEN
. .. - - -- . ..
Indian Railways WAP-5 Contents
Driver's Manual
CONTENTS
1 Introduction
1 .I Use of the Driver's Manual
1.2 Inspection sheet for amendments
1.3 Abbreviations
3.2 Driving
3.2.1 Reverser
3.2.2 TEIBE Throttle
3.2.3 TEIBE meters
3.2.4 Constant Speed Control (CSC)
3.2.5 MEMOTEL (speed recorder and indicator)
3.2.6 Limitation of acceleration Ideceleration
Traction equipment
General description
Main transformer
Converter unit
Line converter (NSR)
DC-Link
Drive converter
Main diagram traction converter
Traction motors
Gear transmission system
CONTENTS
1 Introduction
1.1 Use of the Driver's Manual
1.2 Inspection sheet for amendments
1.3 Abbreviations
Layout of locomotive
Overview
Roof layout
Underframe layout
Bogie layout
Machine room
Driver's cab
TractiveIBraking effort
Tractive effortlspeed-diagram (at wheel rim)
PushIPull Diagram
3.2 Driving
3.2.1 Reverser
3.2.2 TElBE Throttle
3.2.3 TUBE meters
3.2.4 Constant Speed Control (CSC)
3.2.5 MEMOTEL (speed recorder and indicator)
3.2.6 Limitation of acceleration I deceleration
Safety systems
Vigilance control module (Automatic Vigilance Control)
Dead man mode
Resetting of penalty brakes
Vigilance Mode
Alarm operation
Fire detection system
Reset of the fire alarm
Fire extinguishers
Protection concept
General
Interlocking concept (for Maintenance 1 Repair)
Protective measures
Protective shut down
Disturbance with VCB "OFF"
Traction interlock
StartIRunning Interlock
Catenary voltage
Transformer
Line converter
Traction motors
Auxiliary converters (BUR)
Hotel load
Oil pump and fan
Battery
Control electronics
Reciprocal monitoring of the processors
Train bus
VCB
3.11.12.4 Converter
3.11.12.5 Software
3.11.12.6 CEL Temperature
3.1 1.12.7 Speed sensors on traction motor
3.11.12.8 Harmonic Filter circuit
Redundancy
Auxiliary circuits
Traction motor
Central Electronics (CEL)
Failure of HBBl
Failure of HBB2
Failure of ST01
Failure of ST02
Failure of FLGl
Failure of FLG2
Failure of DDAl
Failure of DDA2
Failure of DIA 1
Controls
Panel A
Panel B
Panel C
Panel D
Windshield wipertwasher unit
Comfort equipment
Detailed layout of light switches and sockets (driver's cab)
Detailed layout of light switches and sockets (machine room)
Auxiliary circuits, cubicle-I (HBI)
Auxiliary circuits, cubicle-2 (HB2)
Control cubicle-1 (SB1)
Control cubicle-:! (SB2)
Driver's inspection
Preparations
Activating driver's cab
Raising the pantograph
Closing main circuit breaker
Switching on the main compressors
Operating mode "OFF"
Operating mode "AUTO"
Operating mode "MAN"
DrivingIBraking
Driving
Braking
Emergency braking
Shutting down
Switch off main circuit breaker
Lower pantograph
Deactivating driver's cab
Active functions with deactivated driver's cab
Indication lamp A
Indication lamp B
Pushbuttons
Push button A
Push button B
Push button C
Digital display
Hotel load
Neutral section
Multiple operation
Multiple operation with two locomotives
Pantograph
Main circuit breaker
Regenerative brake
Constant Speed Control (CSC)
Anti-spin protection
Hotel load
Compressor control
Parking brake
Emergency brake
Other brake functions
Coupling
Uncoupling
Sanding
Fire alarm
Trailing mode
Banking mode
Towing mode
Making a live locomotive dead and then towing it
Making a dead locomotive ready for towing
(When brakes are already applied)
Towing a dead locomotive
(When no brakes are applied on the dead locomotive)
-- -
Faults
General
Fault message priorities
Isolating of sub-systems
Overview of sub-systems
Restrictions due to isolating of various sub-systems
Acknowledgement of fault messages
Fault messages with priority 1
Fault messages with priority 2
Resetting the status of the locomotive
Status display of the sub-systems
Select Main Menu screen
Select Vehicle Diagnostics (move 5" with arrow keys)
Key to Codes
Browse
Train configuration
Energy consumption
5.2 Earthing
6 Index
7 illustrations
1 l ntroduction
Chapter Contents
1 Introduction
2 Brief description of the loco
3 System description
4 Vehicle operation
5 Faults
6 Index
7 Illustrations
This final verslon of the Driver's Manual for the WAP5 passenger locomotive was compiled
by Bombardier Transportation (India) Ltd., New Delhi.
- ~-~~
The company reserves all rights to this document and the object described within it.
Reproduction, passing information to third parties or using the contents of this document is prohibited
without the prior approval of the company. Bombardier transportation India Ltd.
1.3 Abbreviations
ALG Drive Control Unit Drive Inverter and Line Converter Control
ASC Drive Converter Control
ASR Drive Converter
BL Key switch
BLCP Spring-loaded switch Main compressors AUTO mode
BLDJ Spring-loaded switch Main circuit breaker
BLHO Spring-loaded switch Hotel load
BLPR Switch Headlights
BPCS llluminated push-button, green Constant speed control
BPFA llluminated push-button, yellow, Acknowledgment all fault
messages
BPFL llluminated push-button, yellow Emergency flash light
BPPB llluminated push-button, red Parking brake
BPVG Push-button, green Vigilance
BPVR Push-button, yellow Acknowledge vigilance
BUR Auxiliary Converter
BZ-V-0 Buzzer
CEL Central Electronics
CSC Constant Speed Control
DDA Display Data Control
. DDS Diagnostic Data Set
DIA Diagnostic Control
EC Error class
FBV Vehicle Bus Administrator
FLG Vehicle Control Unit
GTO Gate Turn Off Switch
HB Cubicle Auxiliary Circuits
HBB Processor
HRA Switch Cab blowerlheating
LSAF lndication lamp, red Train parting
LSCE lndication lamp, amber Overtemperature CEL
LSDJ lndication lamp, red Main circuit breaker
,LSFl lndication lamp, red Fault message, priority 1
LSHO lndication lamp, yellow Hotel load
LSP lndication lamp, yellow Wheelslipping
LSVW lndication lamp, yellow Vigilance Warning
MCB Main Circuit Breaker
MCE MICAS-S2 Control Electronics
The two axle, two motor Bo-Bo bogie assembly, is one of the major parts of the
locomotive. Two bogie assemblies support the entire weight of the locomotive and provide
a means for transmission of the tractive effort to the rails.
The bogies are designed to withstand the stresses and vibrations resulting from normal
rolling stock applications. An important function of the bogie is to absorb and isolate shock
caused by variations in the roadbed. The suspension systems minimise the transmission
of these shocks to the locomotive underframe.
The traction motors are suspended in the bogie frame and connected to the gear box
through a crowned coupling. The motors transmit their energy to the driving axles through
a gear box mounted on the driving axle. The force from the driving axles is transmitted to
the contact point between the wheel tread and the rail. Traction force is, in turn,
L
transmitted through the axle journal boxes and guide rods to the bogie frame. The push-
pull link rod, connected between the bogie transom and car underframe, transmits the
tractive forces to the car body.
The WAP-5 is equipped with the following pneumatic braking systems: automatic train
brake, direct loco brake, parking brake, and anti-spin brake. Slowing or stopping the
locomotive is achieved by use of pneumatically operated disc brakes. Brake discs are
positioned on each side of the wheel and secured by bolts to the wheel web. #$ brake
cylinder and calliper assemblies are positioned to enable the brake pads to clar@against
the surface of the brake discs, and secured to anchorage points on the bogie %me. As
CW.
with the tractive effort, braking effort is transmitted to the bogie frame by the axle journal
boxes and guide rods and from the bogie frame to the locomotive by the traction rods.
Isolation and absorption of shock loads and vibration is performed by the primary and
secondary suspension. Movement between the car body and bogie is smoothly controlled
by the primary and secondary suspension. Although the springs permit free movement in
any direction, lateral buffers and dampers limit the amount and rate of lateral movement.
Rebound limit chains and vertical dampers limit the amount and rate of the vertical
rebound of the locomotive car body. Yaw (longitudinal) dampers control the car body pitch
rate. Guide rods control the fore and aft movement between the axles and the bogie frame,
while the link rod controls the fore and aft movement between the bogies and the
locomotive car body.
The primary suspension, located between the axles and the bogie frame, is provided by
twin coil springs on the axle journal box fore and aft of the axle line. Vertical hydraulic
dampers are used to dampen the rebound rate of the springs. This "Flexicoil" arrangement
perm~tslateral movement of the axle. Longitudinal control of the axle, and the transmiss~on
of tractive and braking effort to the bogie frame, is provided by guide rods connected
between the axle journal boxes and bogie frame. Spheribloc rubber bushes in the guide
rods allow the axle lateral movement without undue restriction.
Secondary suspension, is also provided by coil springs and vertical hydraulic dampers.
located between the bogie frame and the locomotive underframe on each side of the
bogie. The weight of the locomotive car body is carried by the secondary suspension
springs. The "FlexiFloat" arrangement of the secondary suspension allows the locomotive
car body to move both laterally and vertically within certain lim~tsrelative to the bogies.
- Traction converter
The machine room contains one traction converter per bogie with 2-point switching. This
comprises a line converter (NSR) and a 3-phase drive converter (ASR).
The traction motors are supplied with power directly by two relevant bogie selective drive
converters with appropriate control electronics.
- Axle drive
Two externally ventilated three-phase asynchronous squirrel cage motors of Type 6 FXA
7059 are installed on both bogies. The two traction motors on each bogie are supplied with
power by one traction converter.
-- - - -.- -
- - - . .. -
- -- . - - -- - -- ---
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 2 - Page 2
Indian Railways WAP-5 Brief description of the loco
Drivers Manual
- Harmonic filter
The harmonic filter consisting of resistor and capacitor reduces the high frequency
harmonics.
- Auxiliary circuits
Three modular auxiliary converters (BUR) are used to supply power to the 3-phase
auxiliary circuit motors. The auxiliary circuits are designed in a bogie-selective manner.
All functions of the locomotive are controlled by the control electronics. It takes the form of
bus stations with processors.
The bus stations communicate with each other via fibre optic cables which are resistant to
the effects of Electro Magnetic Interference (EMI). The diagnostic equipment comprises a
diagnosis computer with monitor and keyboard in the driver's cab. This provides an
effective support for the duties of the locomotive driver and maintenance personnel.
The locomotive is equipped for multiple unit control with locomotives of the same kind. :!
However, no more than two locomotives can be connected together. Commands are
transmitted by the UIC cable.
- Comfort equipment
Every driver's cab is equipped with two fans and a unit for recirculating and heating @ air.
8
u
Ch
(\I
. ~ ~ . . . . .. -- - - - . .- .- - - - - .. . .
ABB ~ r a n s ~ o r t a t i oSystems
n Ltd. ldent No. 3EHW411116 Chap. 2 - Page 4
Indian Railways WAP-5 Brief description of the loco
Drivers Manual
. - - - -- - - - -. . - - -
A B Transportation
~ Systems Ltd. ldent No. 3EHW411116 Chap. 2 - Page 6
Indian Railways W A P d Brief description of the loco
Driver's Manual
2.4.1 Overview
. . . . . . . -
. - .- ..-.
Chap. 2 - Page 8
~
-~ ~ . ~ - ~
AEIB Transportation Systems Ltd. ldent No. 3 ~ ~ ~ 4 1 1 1 1 6chap.^% - page' 14
Indian Railways WAP-5 Brief description of the loco
Driver's Manual
empty page
3 System description
Note:
If regenerative brake fails, pneumatic brake effort on loco can be controlled by
angle transmitter, except when processor HBB2 or FLG2 fails. C*,
Em-
-
TE -
D -
-
BE -
@#
BEu. -
-
If regenerative brak~ngeffort exceeds 10 kN, the automatic locomotive brake is inhibited.
If the regenerative brake is not available or if it fails during a braking operation, the
pneumatic locomot~vebrake automatically takes over its function, except in the case, when
VCB IS opened by the spring-loaded switch "BLDJ".
The full electrical braking effort is reduced from 10 kmlh to 0 kN at 0 kmlh.
Note:
Even i f the electrical and pneumatic brakes are activated together due to a fault
in the system, excessive braking of the locomot~veis avoided because the anti-
spin/slide control system reduces the electrical braking effort.
. - - - . - - . ~-
..--- . ~ . .
4BB Transpor'ation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 2
Indian Railways WAP-5 System Description
Drivers Manual
Fig
Note:
Ifthe electronic brake control system fails, a priority 1 fault message appears
on the display and an emergency brake is triggered. A StaNRunning interlock
is initiated whenever:
- Brake pipe pressure falls below 4.75 kg/crn2 and
- the speed of the locomotive exceeds 10 km/h and
- there is brake cylinder pressure on the loco as indicated on the instruments
on panel B
-. .~
-. . - -. - ~ - - - - -. . ~ - - . - ~.- . - - . . - .
ABB Transportation Systems Ltd. ldent No. 3EHW411116 chap-. 3 - Page 4
Indian Railways WAP-5 System Description
Drivers Manual
The direct brake acts on the brake discs of the locomotive and is only able to brake the
loco. In multiple operation, the direct brake also acts on the slave locomotive. Due to its
direct action it is used whenever careful graduated braking 1s required (e.9. shunting).
The brake handle (1) is only active when the driver's cab is activated.
A StartIRunning Interlock is initiated whenever speed of the loco is above 10 km/h and
there is brake cylinder pressure on the loco indicated on the instrument on panel B.
Note:
c
For t in operation, the handle has to be set to the release stop, in the fully
clock ise direction.
In special situations, e.g. hill start (starting on gradients), the direct brake can
be applied.
- - . . . - - - - - - - - - - .
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 6
Indian Railways WAP-5 System Description
Drivers Manual
C ;
Warning:
The use of the parking brake release handle outside the loco is strictly
forb~ddenin normal operarlon!
Before shunting or towing the dead locomotive, it must be ensured that the
park~ngbrakes are released.
If the BL key switch in the manned driver's cab is turned OFF, the MCE
automatically applies the parking brake.
Warning:
Before switching "OFF"the BL key, it must be ensured that the locomotive is
stand still.
--
ABB Transportation Systems Ltd. ldent No. 3EHW411116 ~64.-
3 Page 8
Indian Railways WAP-5 System Description
Drivers Manual
Note:
The emergency stop button is only active in the activated driver's cab. However,
its function is not dependent on the speed of the locomotive. When the
emergency stop button is pressed, the main circuit breaker opens and the
pantograph is lowered.
Emergency braking is actuated directly in all cases and is not controlled by the MCE.
However, the MCE responds to emergency braking by reducing traction effort to 0.
If an emergency braking operation is triggered in multiple operation, it is transferred to the
slave locomotive also.
3.2 Driving
3.2.1 Reverser
.~ . . - .. ~ -.~-.. ~. .. - . ..
ABB Transpor!ation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 10
Indian Railways WAP-5 System Description
Drivers Manual
The TEIBE throttle controls traction and the electric braking effort of the locomotive with an
angle transmitter and auxiliary contacts.
The TEIBE throttle has the following three end positions:
0 0 0
-
-- --
-
--
-
-
--
-
0000
LSDJ LSHO LSP LSAF
-- --
UBA
U BOGIE1 BOGIE2 0
ZBAN
In case the angle transmitter fails, the auxiliary contacts act in the following positions:
This system enables the train to maintain a constant speed automatically and
151.4 can be activated at any speed above 5 krnlh by pressing the illuminated push-
button "BPCS" (constant speed control).
TUBE demand throttle must be greater than zero.
The CSC has access to 100 % traction and braking force, i.e. the position of the
TElBE throttle (angle transmitter drive controller) has no impact on the effective
speed.
The WAP-5 loconiot~veis designed for operational speeds between 0 and 160 km/h.
- .- .- - .. . . - - - - - - - - -. --
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 12
Indian Railways WAP-5 System Description
Drivers Manual
The speed of the locomotive is monitored and recorded by the MEMOTEL. If the maximum
permitted speed setting is exceeded, the system initiates the following actions:
1. Speed 105%
buzzer: continuous tone 745 Hz
2. Speed 110%
Emergency braking is initiated
Fault message priority 2: maximum speed exceeded
Note:
If the speed indicator fails, a fault message with priority 2 appears on the
terminal.
Note:
For multiple operation. the master locomotive determines the acceleration of the
train.
The train driver can brake the train using the regenerative brake as well as the
pneumatic brake.
OI
3.2.7 Anti-spin protectionlanti-slide protection
8
v
-3
The automatic anti-spin protectionlanti-slide protection is initiated as soon as t m ' Vr a t i o
between effective tractivelbraking effort and requested tractivelbraking effort is less than
0.5.
As required, one or more of the following actions islare initiated:
1. Reduction of tractive effort to the adhesion limit from the electronics of the
traction converter (independently on each bogie).
2. If required, the wheel-spin brake is activated.
3. The sanding valves are activated depending on direction of travel.
Note:
92 A wheel spin/slide is indicated by the yellow illuminated indication lamp "LSP
(panel A).
3.2.8 Sanding
192.1 Sanding can be initiated by the driver by pressing the "SANDING" foot switch,
or automatically by the anti-spin protection unit.
Depending on the direction of travel, only the sanding valves of the wheels of
the leading axles of each bogie are activated.
- -- - - -
ABB Transportat~onSystems Ltd. ldent ~ 0 . 3 ~ ~ ~ 4 1 1 1 1 Chap.
6 3 - Page 14
Indian Railways WAP-5 System Description
Drivers Manual
'.--- yV/ \
2 - - \-/ Ly-J
A B C D E
Main Line converter DC-Link Drive Traction
transformer converter motors
- - - - . . . - - - - .
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 16
I
Indian Railways W A P d System Description
Drivers Manual
1 Pantograph
3 Primary voltage transformer
4 Earthing switch to VCB
5 Main circuit breaker (VCB)
7 Main transformer
8.1 Filter contactor
8.3 Resistor harmonic filter
8.4 Capacitor bank harmonic filter
9 Surge arrestor
10 Earth return brush
11 Earthing choke
12 Valve set 2*ZV
12.3 Precharging contactor of converters
12.4 Contactor converter
13 Valve set ZV + MV
14 Precharging resistors of converters
15.1 Resistor of over-voltage protection unit
15.3 Series resonant circujt choke
15.4 Capacitor bank of series resonant circuit
15.5. Capacitor bank of DCLink
15.82 Earthing switch of DCLink
20 Traction motors
Due to technical and economical reasons electric traction vehicles are nowadays provided
with three-phase asynchronous traction motors. The three-phase voltage required for
operating the traction motors is generated on the vehicle by means of the traction
converter connected between the vehicle's main transformator (single phase) and the
traction motors.
The traction converter allows the train not only to drive but also to brake electrically.
To control the tractive or braking effort, and hence the speed of the vehicle, b o a h e
frequency and the amplitude of the three-phase converter output voltage are contin@sly
changed according to the demand from the driver's cab. This allows conthous
adjustment of the driving or braking torque of the traction motors, which means tl% the
driving speed changes smoothly.
When braking electrically the traction motors act as generators. In the converter the
resulting three-phase electrical energy is converted into single-phase energy which is fed
back into the line (recuperation brake).
Output voltage of the Traction converter 2180 V
Output current 740 A
Output power 2105 kW
89.4 An earth fault detection is integrated at the output of the Line converter.
The tank is filled with transformer oil. An oil level sight glass is located'in the machine
room. (See figure 3.10.)
Mineral transformer oil (type Shell Diala DX) is used for cooling the tank.
Two cooling circuits are provided to cool the transformer tank. The two oil pumps of the
transformer oil circuit are mounted on the tank. A sensor measures the oil temperature.
The maximum allowable oil temperature is 150 "C.
-- -- - -
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 . - Page 20
Indian Railways WAP-5 System Description
Drivers Manual
The converter unit has the task for converting power between the transformer and the
asynchronous traction motors in such a way that optimum tractive or braking effort can be
generated at any speed.
Due to GTO technology, the line is ideally loaded with a power factor of almost 1.
A 2-point circuit converter unit is installed on each bogie. The line converter (NSR)
converts the constant frequency AC voltage supplied by the transformer into DC voltage
(intermediate link).
The drive converter (ASR) generates a 3-phase system with variable voltage and
frequency. The energy flow is reversed during regenerative braking.
The power elements of the converter unit (line converter, drive converter) are oil-cooled.
The power semiconductors and all snubber circuits are installed in the valve set tank.
The 2-point circuit valve set in simple terms, performs the function of two static
changeover switches in each case.
he line converter of a bogie comprises two identical valve sets. These connect the
secondary traction windings of the transformer to the DC-Link.
The power passing through the line converter and the traction converter is not equal at
every time interval. Compensation of these energy differences is performed in the
intermediate voltage link.
The capacitor bank in the DC-Link maintains DC-Link voltage at a constant level.
To retain control of over-voltages in the DC-Link, the DC-Link is equippefiith an
overvoltage protection unit (MUB). This consists of a resistor and a GTO. In @se of a
protective shut-down the GTOs of ASR & NSR are blocked and the energy st&ed in the
( U
DC-Link is converted into heat in the MUB.
The drive converter (ASR) of a bogie comprises two valve sets. These connect the 2-point
intermediate voltage link to the three phases of the traction motors.
On the traction side, it must be possible to set the terminal voltage and the frequency in an
infinitely variable manner. To achieve desired values, the cycle pattern is generated with
three different control principles:
- ISR (Indirect Self Control) in the lower frequency range.
- DSR (Direct Self Control) in the middle frequency range up to motor rated frequency.
- Full block process for the range above that of the motor rated frequency (weak field
area).
- -. - . --. - -- -- - -- -- ,
iBB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 -- Page 22
Indian Railways WAP-5 System Description
Drivers Manual
The traction motors are asynchronous squirrel cage motors adapted in electrical terms to
the traction converter providing the power source.
Both traction motors of one bogie are ventilated by one traction motor blower. The traction
motors are connected to the gearbox.
Each traction motor is equipped with two temperature sensors and two motor speed
sensors.
The ZF HURTH crown gear coupling provides for the transmission of rotational forces
between the traction motor and gearbox. One drive coupling half is pressed onto the
traction motor output shaft and the gearbox input shaft.
This dual cardanic-acting coupling transfers the torque from the motor to the transmission
and can compensate for radial, axial and angular shaft shifting. The inner-toothed
coupling sleeves are mounted rigidly on the motor and transmission shaft.
The coupling is equipped with separate, closed lubricant chambers in each coupling half.
When removing or installing the motor or transmission, the lubricant chambers remain
closed, eliminating the possibility of the tooth becoming dirty. The sealing elements are
each arranged on the side facing the motor or transmission. With this, and the possibility to
integrate the labyrinth seals from the motor and transmission with the coupling sleeves, a
maximum of tooth center spacing is achieved.
This means a relatively small coupling star diffraction angle for radial shifts and:
In
- low required crowning of the toothing ag
w
- low specific loading at the tooth face 8-
c
w
- increased operating safety and longer service life
Another advantage lies in the very low weight of the movable coupling stars. In conjunction
with the spherically shaped tooth-tip centering, imbalances are also avoided in the
unloaded state (vehicle rolling) depending on backlash. This is particularly important at
high driving speeds, i.e. at high engine speeds. Maintenance is limited to a visual check
for oil leaks or damage, an oil and membrane change during major transmission and
vehicle inspections. It is also possible to attach a magnet wheel for a speed sensor on the
coupling sleeve.
The gear coupling consists of a star coupling (pinion) within a geared sleeve. The star has
curved teeth to allow for minor misalignment and movement between the motor and gear
box.
. - - . . . ~ .~. - ..
~ .--- . ~ . . . ? . . . . . ... .
H-.
System Description
Drivers Manual h' I
1 Pantograph
5 Main Circuit breaker (VCB)
7 Main transformer
10 Earth Return brush
40 Fuse auxiliary converter input
47 Main compressors
47.2 Contactors main compressors
50.11 Rectifier module auxiliary converters
50.12 Inverter module auxiliary converters
50.9 3-phase output choke
51.1 Capacitor bank DC-Link, auxiliary converters
51.3 DC-Link choke, auxiliary converters
52 Contactors for auxiliary circuits
52.4 Contactor scavenge blowers
52.5 Contactor oil pumps
53 Traction motor blowers
55 Scavenge blowers to traction motor blowers
59 Oil cooling unit (Transformer, converter)
62 Oil pump transformer
63 Oil pump converter
1050.1 Auxiliary converter, Box 1 (BURI)
1050.2 Auxiliary converter, Box 2 (BUR2+BUR3)
4
3
. System Description
4. Ramp up the BUR frequency from OHz to 50 Hz with the rate of 5 HdSec.
5. 3 sec after the BUR is running on 50 Hz, the unloading valve shall be de-
energsed.
If one compressor is running and the pressure switch requires the second
compressor to start up, the following sequence will happen:
Ramp down the auxiliary inverter (BUR 3) frequency from 50 Hz to 0 Hz at the
rate of 2 Hzlsec. At the same time release the air with opening of unloading
valve.
-- . ~ - ~ - -- - -- -
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 26
Indian Railways WAP-5 System Description
Drivers Manual
--
=-%
-
L--------,_-y--- J
The auxiliary transformator is located in the cubicle-1 (HB1) and supplies the following
systems with single phase power:
- 415 V AC for the two machine room blowers
- 415 V AC for the two scavenge blowers to MR blowers
- 415 V AC for cab heating elements (cab 1 and 2)
- 110 V AC for cab heater fans and crew fans (cab 1 and 2)
89.5 At the output of the transformator an earth fault relay is connected to detect
earth fault in this circuit.
The following circuit breakers are provided for protection of auxiliary motors:
54.1 Circuit breaker to MR Blower
56.1 Circuit breaker to scavenge blower MR
69.61 Circuit breaker cab ventilation
69.62 Circuit breaker cab heater
69.71 Circuit breaker crew fan
3.4.3.1 General
The ventilation system is based on a three-stage design, with ventilation being controlled
by the equipment temperatures.
Note:
If one of the on-board converters (BUR) fail the whole load is distributed
between' the two remaining BURS. They can continue to supply the auxiliary
circuits, practically without losses and full traction is also available.
The machine room blower and the corresponding scavenge blowers are fed
directly from the auxiliary circuit transformer and therefore operate
independently of the MCE, as soon as the VCB is closed. Therefore the loco
can be cooled even if MCE is not in operation.
rc
The blowers on the traction motor and the oil cooling units are i n d i v ~ a l l y
supplied for each bogie by the auxiliary converter (BUR). 03
tf.
0.
However, if two BUR fail, there is no traction available and the power sup/§& to
the auxiliary circuit fails.
Reaction:
LOCO DEAD
Each of the three ventilation systems is using a centrifugal filter panel where contaminated
air is rernoved via a scavenge flow system. The efficiency of the filter panel is dependent
on the removal of contaminants by the scavenge system, and therefore it is important that
the scavenge system meets the minimum flow rate requirements.
-- - - - - -
exoansion tank
Note:
The oil pumps run continuously as soon as the auxiliary converters are switched
on.
-~ - - -- . - - - - . .. . ~ ---- .-
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 32
Indian Railways WAPd System Description
Drivers Manual
172 In this operating mode, the driver moves the "BLCP" switch into the position
"MAN. Both compressors run as long as the VCB is closed and the switch is
set in the position "MAN".
The compressors are not cut out even if the main reservoir.pressure exceeds
10.5 kg/cd The compressors are, however, protected against overpressure by
their safety valves.
172.4 The auxiliary compressor is used if the prevailing pressure is too low to raise the
pantograph. While the control circuit is switched on, the auxiliary compressor is
controlled by a pneumaticswitch independent of the MCE. If the pressure is low,
the auxiliary pressure will start automatically on switching on the control circuit
till the pressure reaches 6.0 kg/cm2.
284.5 The air dryer is actuated when at least one of the main compressor is switched
on.
3.5.1 Battery
111 The battery is a NiCd accumulator, which consists of 78 cells, which are
connected, in series. The nominal capacity is 199 AhlC5A (C5A means that the
capacity is 199 Ah assuming the battery has discharged in 5 h).
The battery s divided in two halves, which are located on each side of the locomotive.
All electrical components in the control current circuit are designed for a nominal voltage ot
110 VDC t. 25% / - 30%.
Note:
If due to a fault the battery ceases to be charged, a fully charged battery is able
to supply the control circuits with power for approx. 5 hours.
. . . .- ~. -.. - -. .- .
-
~~
3.6.1 General
A sequential control checks the operating status and determines the order in which
operations are carried out. It includes nodes (states), which are connected by transitions.
The state of a system or subsystem can thus be simple and logically controlled. The
sequential control can only be in one defined state at any one time.
The master sequential control (MSC) defines the current state of the locomotive with the
aid of a node number. The node number is the central reference for all the system
processors and is therefore decisive for maintaining the proper locomotive operating
procedures. The MSC also performs various protection functions, e.g. the main circuit
breaker can only be closed after the MSC has reached the corresponding node or state.
A sub-sequential control defines the current state of a processor with the aid of a node
number. It is generally controlled by the MSC.
The most impohant functions are duplicated to enable the locomotive to remain in
operation in spite of the failure of a sub-system.
- ------ ~. - -. ~. -
ABB ~ r a n i ~ o r t a t i o
Systems
n Ltd. ldent No. 3EHW411116 Chap. 3 - Page 36
Indian Railways WAPQ System Description
Drivers Manual
The vehicle bus directs the information flow to the different computers by fiber-optic cable.
The networking of signals takes place solely in the computers which means that the
control electronics system always has a complete picture of the status of the locomotive at
all times. This is a major benefit, especially when dealing with faults in the system.
A control electronics level with at least one computer and a connection to the vehicle bus
is defined as a bus station.
The following third party systems are operated by their own control electronics and
independent from the above mentioned bus concept:
Brake control (Pneumatic brake systems)
Automatic Vigilance
Fire detection
MEMOTEL
The WAP-5 locomotive is equipped with a safety system, which initiates rapid braking if
there is doubt about the train driver's presence in the cab, or about his level of vigilance.
Release of the foot pedal at any time causes an automatic switch to the "Deadman" safety
mode. In this mode the a~diblewarning is sounded after 60 seconds and the brake
application and power cut off initiated after further 8 seconds. Resetting from the driver's
controls is not possible, pressing of the vigilance pedal or the push-button "BPVG" is the
only means of resetting the system.
Reaction:
An acoustic alarm is triggered and the emergency brake is applied after 8 secs.
Note:
The acknowledgement of the alarm of the vigilance unit can be done by
pressing the foot switch "VIGILANCE or the push button "BPVG" on assistant
driver's desk (panel D).
Note:
A reset cannot he made for at least 120 seconds after penalty brakes are
applied.
-- . - - - .. - ---
ABB Transportation Systems Ltd. ldent No. ~ E H W %1116 Chap. 3 - Page 38
Indian Railways WAP-5 System Description
Drivers Manual
236 the train crew must press the green push-button 'BPVGn, on panel "D".
If one of these four conditions is achieved, the monitoring cycle is reset and the
60 second cycle starts again.
Reaction:
An intermittent signal sounds in the driver's cab (546 Hz), from the buzzer BZ-
V-0-F.
242.1 The yellow vigilance warning indication lamp "LSVW" is lit continuously. N
CO
03
w
0\
Acknowledgement of the alarm: 'a
235 Press and release the "VIGILANCE foot switch or the push-button "BPVG".
Note:
-
If the acoustic alarm is not acknowledged within 8 seconds, rapid braking is
initiated.
212 The locomotive is equipped with a fire detection system in the machine room.
Through a ring line with apertures at regular distances air in the machine room is extracted
with a fan and checked for traces of smoke by a detector.
- .- - - - -. - - .- . - - - - - -
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 49
lndian Railways WAP-5 System Description
Drivers Manual
Press "Reset" button on the Fire Detection Equipment in the machine room.
163.1 Press "BPFA" acknowledge button in the driver's cab. The yellow lamp
extinguishes.
A fire alarm is recorded by the monitoring system.
The detection of a failed fire detection unit will create a priority 2 fault message.
Afterwards, there is no limitation to drive the loco.
3.8.1.1 Fan
69.7 In the driver's cab, there are two fans in the top corners, each vertically and
horizontally adjustable. The one in the top left corner :s for the train driver and
the one in the top right corner is for the assistant driver The switches for
operating these fans are located on the front of each fan.
69.6 The cab is equipped with a recirculating air blower connected to a heater.
65.6 The rotary switch cab heater is located on the right side beside panel D on the
assistant driver's side and has 3 settings:
"0 Blower switched off.
"COOL" Blower switched on.
"HEAT" Blower switched on with heating.
There are two apertures on the roof of the cab on left and right sides, fitted with revolvable
blades, which ventilate the cab while the train is in motion.
To clean the windshield, each of the two windshields is fitted with a pneumatically-driven
wiper blade, the speed of which is continuously adjustable. If the pneumatic fails, the wiper
can be operated manually. The operating switch for the wipers is located on the driver's
desk towards the assistant driver's side.
In addition, a spray device is fitted. The water tank for this is located on the right side of
the driver's cab below the window.
~- -.. ~. . - . - -~ . . -~ ~ . .
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 42
Indian Railways WAP-5 System Description
Drivers Manual
The Hotel load is supplied by a separate secondary winding of the main transformer:
Voltage: 750 VAC
Frequency: 50 Hz
Power: 850 kVA
169.1 The spring-loaded hotel load supply switch "BLHO" in the driver's cab switches
contactor 32 via the MCE. When it is closed, the yellow hotel load supply indication
169.3 lamp "LSHO" lights up in the cab. The hotel load is connected to the train via the
35 four-pin hotel.loadsockets. There are two hotel load sockets outside at both ends
of the loco. (See Fig. 4.21)
Warning:
- Never connect the hotel load cable to another loco.
- 'Never connect the hotel load cable to acoach when the pantograph is
raised.
32 In multiple operation the hotel load supply contactor on the master loco s h a a e
in "OFF-position. Only the slave loco, which is coupled to the train, is a b w
feed the hotel load supply. 0-
C\r
169.1 The command of the hotel load switch on the master loco will be transmittedto
the slave loco by train bus. If the VCB is closed the hotel load,supply contactor
will close only on the slave loco.
169.3 The yellow indication lamp "LSHO will be illuminated on the master loco, if the
hotel load supply contactor on the slave loco is closed.
3.11.1 General
To prevent high voltage reaching the locomotive while high voltage components are
accessible, the locomotive is equipped with a lock and key based interlocking system. This
operates with differect coloured keys and starts in the following manner:
Key A (light blue) and B (yellow)
By locking the pantograph valve at Pneumatic Panel (PP), key A becomes free.
Key A unlocks the earthing switch on the main circuit breaker. If this IS moved into earthing
position, the locomotive is earthed and both B keys become free.
~~ ~~ -
.... -- --- - - .. .. ..
- - ~. -. ~~
Key B is used to unlock the key multiplier No. 1 for key C. Key multiplier No. 1 is located in
the machine room behind the cab.
Note:
The second B key (yellow) can be kept in the custody of a responsible
supervisor for additional safety.
Note:
The following actions have to be taken before the above-mentioned procedure
is executed: ~n
--
CO
125 1. set the 'BL'key switch to the position "0" og
-
-a
112.1 2 set circuit breaker "Control Circuits Locomotive" on 582 to position "oP
To cancel the earthing of the locomotive, proceed in reverse sequence.
-- - --
ABB ~ r a n s p o ~ a t i o n ~Ltd.
~ s t ~ sldent No. 3EHW411116 Chap 3 - Page 46
Indian Railways WAP-5 System Description
Drivers Manual
Note:
The traction interlock is released as soon as the reason is eliminated and the
train driver moves the TEBE throttle through position " 0 Releasing this
interlock never occurs automatically but always requires manual intewention.
-- -- - - - --
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - page78
Indian Railways WAP-5 System Description
Drivers Manual
The StartIRunning Interlock means that traction is set to " 0 with a ramp of approx.
100 kN/s. However, the regenerative brake is still available.
Reasons for the StartIRunning Interlock:
- Parking brake applied.
- Direct loco brake applied.
- Automatic brake applied.
- The pressure in the main reservoir has fallen below 5.6 kg/cm2.
293.2 - The isolating cock brake pipe control system is closed.
- Fire alarm
- Emergency exhaust isolating cock
Note:
The interlock is released as soon as the reason is eliminated and the train driver
moves the T U B E throttle through the "0" position. The StartIRunning lnterlock
is never released automatically but always requires manual intervention.
If catenary voltage moves outside the permitted range of 17 kV to 30 kV, the VCB
switches off automatically
ON I
T
OFF
i
-- . -- -. - -- ~ - -- . -
A 6 6 ~ra&~ortati& Systems Ltd. ldent No. 3EHW411116 Chap. 3 - page 50
Indian Railways WAPd System Description
Drivers Manual
The primary and the secondary traction windings are equipped with overcurrent sensors.
The pressure of the transformer oil is monitored by a range of different measurements.
Furthermore, the oil pump circuit breakers and the temperature of the transformer oil
circuit are monitored. If one circuit breaker (MCB) is triggered, a fault message with
priority 2 is issued.
JOOh I
--
ABB ~rans~ortation
Systems Ltd. ldent No. 3EHW411116 Chap. 3 - page 52
Indian Railways W A P d System Description
Drivers Manual
100%
i
i
i
II.
GTO pulsing
inhibited
! I I b VOiI(OC)
0 64 66
The traction motors are protected against excess current by the converter. Appropriate
protective measures are implemented in the ALG processor.
The motors are also protected against excessive speed and excessive temperature.
In addition:
- current in the secondary winding of the auxiliary circuits is monitored.
- an earth fault in one of the secondary winding of the auxiliary circuits is detected.
- an earth fault 415 V (single phase) is detected.
62;63 The transformer and converter oil pumps are monitored by:
62.1 ;63.1 - The status of the MCBs
- The oil pressure in the convener and transformer.
53;53.1 The traction motor blowers are monitored by the status of the MCBs.
59i59.1 The oil cooling blowers are monitored by the status of the MCBs.
53.1;591 If one of the MCBs has tripped, a fault message with priority 2 is issued.
-- - -
1. The control circuits are switched off when the driver's cab is activated and
none of the pantographs is raised for more than 10 minutes (this does not
apply during simulation mode).
2. If the output current of the battery charger drops below 10 A, a fault message
with priority 2 appears on the display in the driver's cab.
3. If battery voltage drops below 92 V for more than 30 seconds, a fault
messagelwarning with priority 2 appears on the display in the driver's cab.
4. If battery voltage drops below 86 V, an interlock ensures correct switch-off
procedure. A priority 1 fault message appears on the display in the driver's
cab.
5. If battery voltage drops below 82 V, then loco will be shut down and all
control circuits shall be switched off under all operating conditions.
All processors linked to the vehicle bus transmit a monitoring signal to the master vehicle
control unit (FLG 1 or 2, i.e. to the Master processor).
A failure of a processor or of the link via the vehicle bus is detected by the FLG because it
is unable to receive the corresponding monitoring signal. When this occurs, the VCB is
switched off. In a similar manner, the FLG transmits a monitoring signal to all other bus
stations. Failure of the FLG processor or of the link via the vehicle bus is detected by the
bus stations because they were unable to receive the corresponding monitoring signalD
If the monitoring signal fails only briefly, the protective function trips the VCB. +
Q,
Tt
If it fails for longer than 30 seconds, the affected processor is isolated. 0.
L %<
The train bus during multiple operation is controlled in a similar manner by monitoring the
corresponding signals between slave and master locomotive and between master and
slave.
If a train bus fault is detected on the master locomotive, the master locomotive generates
a fault message with priority 1, without tripping the VCB.
3.11.12.3 VCB
The correct position of the VCB is monitored by the MCE. The following switch modes on
the auxiliary contacts ar2 recognized:
1. One NIO contact remains in the "OFF' position for 1 second after the
command to switch on: Stuck-Off is detected and the command to switch on
is resetted and a priority 1 fault message is generated.
2. One N/O contact remains in the "ONn position for 1 second after the switch-
off command has been given: Stuck-"ON" is detected and the command to
switch off IS resetted, a priority 1 fault message .s generated: LOCO DEAD
Protective actions:
VCB in OFF Position VCB control changed to redundant processor
VCB in ON Position: Converter contactor opens
Hotel load contactor opens
Pantograph lowers
3.11.12.5 Software
When the wrong software is loaded (e.g software for WAG 9 installed on WAP-5). a fault
message with priority 1 is issued and the pantograph cannot be raised into position. (This
is for the knowledge of maintenance/commissioning staff.)
. . -.. . . . . .. - . -- .. . . ~~~
ABB ~ r a n s ~ o ? a t ~ o n ~ ~Ltd.
s t e m s ldent No. 3EHW411116 Chap. 3 - Page 56
Indian Railways WAP-5 System Description
Drivers Manual
The sensors are monitored by the converter electronics. A defective sensor does not
however disconnect the corresponding bogie.
An earth fault in the harmonic filter circuit is detected. The harmonic filter circuit is also
protected against overcurrent.
3.12 Redundancy
Certain important systems are double or installed with redundancy to ensure the
locomotive remains as functional as possible whenever faults occur.
The auxiliary converters (BURs) supply the voltage for the auxiliary circuits (3 x 415 V).
If one BUR fails, the other two can continue to supply the auxiliary circuits, practically
without losses and full traction is also available.
However, if two BURs fail, there is no traction available and the power supply to the
auxiliary circuits fails.
Reaction:
LOCO DEAD
Every bogie is equipped with a separate converter. At every major fault, each bogie can be
isolated from the etectrical power supply. The locomotive can then still be driven at half
traction power.
The CEL, which contains the processors FLG, HBB and STB, can be found in control
circuits 1 and 2 (SB1 and SB2).
38.1 If HBB1 fails, cab 1 is isolated and, since the earth fault relay on the hotel load
is no longer being monitored, the hotel load must also be disconnected.
. . ~ . A ~ - . . . . . ~. .
ABB Transportation Systems Ltd. ldent No. 3EHW411116 Chap. 3 - Page 58
Indian Railways WAP-5 System Description
Drivers Manual
Reaction:
A change of driver's cab is necessary, if the driver has been driving from cab 1.
Reaction:
A change of driver's cab is required, if the driver has been driving from cab 2.
In addition, the following functions fail or are only avaiiable to a limited extent:
1. The parking brake can only be released manually on the PP.
2. The regenerative brake is no longer available.
3. The Vigilance control module has to be isolated manually (message for the train driver).
4. Pantograph 1 not operative.
5. The following pressure switches are no longer monitored:
- Direct brake
- Pantograph 1 and 2
- Train parting
- Low-pressure main reservoir
- Brake feed pipe
- Brake cylinder, bogies 1 and 2.
Reaction:
A change of driver's cab is necessary, if the driver has been driving from cab 1.
Y
n addition, the following functions fail:
1. Air dryer
2. Hotel load
3. Anti-spin protection valve, bogie 1
4. Switch Failure mode operation
5. Switch S~mulationmode
6. Switch bogie cutout.
Reaction:
A change of driver's cab is necessary, if the driver has been driving from cab 2.
--- - - -
ABB Transportat on Systems Ltd. ldent No. 3EHW411116 Chap. 3 - page 60
Indian Railways W A P d System Description
Drivers Manual
Note:
Once STB2 has been isolated on the slave locomotive and a fire alarm has
been triggered, this cannot be detected on the master locomotive.
Note:
See failure mode operation Chapter 4 Page 62, or drive from cab-2
Note:
See failure mode operation Chapter 4 Page 62, or drive from cab- 1.
- .- ~ . ~ ~.
.~... ----
~~ --
~~~~
3.13.1 General
The simulation mode serves as a check on the MCE software when commissioning the
locomotive and during maintenance work without risk to the locomotive. In this mode, the
pantograph control module and the concerning fault messages are not active.
The functions of the locomotive are similar to normal conditions but the catenary voltage is
absent.
The simulation mode can also be activated if the locomotive and the DC-Link of the
converter are earthed.
125 1. Move cab activating key switch in the driver's cab into Position "On.
-
2. Wait until control electronics is switched off.
179 3. Move key switch on cubicle SB1 into position "SIM".
Note:
h
Note:
MEMOTEL is not activated in simulation mode. The simulated speed is
displayed on the screen.
In simulation mode, the battery is not charged and none of the main
compressors is operating. Parking brake is applied by the MCE and cannot be
268 released by !he push button in the driver's cab.
Note:
The sander and the wheel flange lubrication are inactive.
VEHICLE OPERATION
10
-- -" -- \-
4.3 Controls
4.3.1 Panel A
Panel A is located in the centre of the field of view of the train driver
It contains the following controls and displays:
1 2 3 4 5 6 7 8 9
10
0
\ \ \
\ \ 0
I 0
UBA
- - -
U BOGIE1 BOGIE2
- ~. ~ - - -- - - .-- -
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 4
indianRailways WAP-5 Vehicle operation
Driver's Manual
4.3.2 Panel B
A 5 6 rans sport at ion Systems Ltd. Ident No. 3EHW411116 en Chap. 4 - Page 5
Indian Railways WAP-5 Vehicle operation
Drivtx's Manual
. . . . ~~ ~. ~
- -.- - - -. . - - .. . - . < . . . - - .-
4.3.3 Panel C
~~ -- -. - - -- - . - .. - .~ .~ .. . .~ ..
~ .
Panel D
P Parking position
0 Neutral position
-- .-am- - - -- - - - -. -
Fig. 4.9 Detailed layout of light switches and sockets (driver's cab)
325.21 Lamp driver's desk illumination
324 Switch driver's cab lighting
324.21 Switch driver's desk illumination
324.22 Assistant driver's switch desk illumination
334.1 Socket hand lamp
337 Switch hand lamp
325.22 Lamp Assistant driver's desk illumination
325 FL-Lamp driver's cab lighting
- ~ .
ABB Transportation Systems Ltd. ldent No. 3EHW411116 e r Chap.4 - Page 10
Indian Railways WAP-5 Vehicle operation
Driver's Manual
. - -- - - -- - - --
.. - - .~ . -
-- - - - -- - -- . -- - - -
ABB Transportat~onSystems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 14
Indian Railways WAP-5 Vehicle operation
Driver's Manual
.. ---. - - - -
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 16
Indian Railways WAP-5 Vehicle operation
Driver's Manual
.- - ---
ABB Transportat~onSystems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 18
Indian Railways WAP-5 Vehicle operation
Driver's Manual
Filter cubicle
- -- - - - -- - - --. .. -- - -- - -
- < - -
-
- . - -_ I-_I-_ - -. ..
Note:
Towed "DEAD" means that the towed loco is completely "DEAD".
Trail "DEAD" means that on the master loco no tractive effort is available, but the
driver's cab of the master loco still controls the slave locomotive.
_ _ __ -~-- - . ---
- - - ..
- -. . - ~. .~ - . ~
- - -
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 26
Indian Railways WAP-5 Vehicle operation
Driver's Manual
1 2 1
4.4.1 Commissioning
4.4.1.1 Preparations
- --- - . .. . -
.
Preconditions:
The temperature in the central electronics (CEL) must be c 700 C. The
catenary voltage (UJ must be in the range of 17.5 kV and 30 kV
(7 7.5 kV <- Up, < 30 kV).
Reaction:
The MCE control electronics (= MICAS-S2) are switched on
Start self lests (duration approx. 2 mins.).
An Information message "Trainbus configuration running, please wait" appears
on the diagnostic display screen.
Self test of all indication lamps starts (duration 10 seconds).
- - -
At the end of the self test of all indication lamps they have the following status:
Panel A: LSDJ (1) lit (Main circuit breaker in "OFF" Position)
LSHO off
LSP off
LSAF off
LSVW off
LSCE off
Panel 5: LSFl off
'Note:
166 If the temperature inside the CEL is higher than 70- C, the amber "LSGE"lamp
(2)lights up on panel A.
Reaction:
The machine room blowers and the corresponding scavenge blowers inside &?GEL
block start to run. Once the temperature in the CEL block has dropped belorno-C,
the amber indication lamp "LSCE"extinguishes (2).
w
0.
&
'
Action 2: Open main circuit breaker (move switch "BLDJ" (5) briefly into "OFF"
Pos.).
Lower pantograph (move switch "ZPT" (4) briefly intoVDN" Pos.).
Turn key switch (3) into position "0".
Action 3: Turn key switch (3) into Pos. "D".
Subseauent procedure (refer to 4.4.1.2).
I LSVW -..- I
2
Fig. 4.24 Panel A
Check the position of all isolating cocks: pantograph 1 & 2 (D&M Pos. 8), VCB
(D&M Pos.5) and Key Switch Pantograph (D&M Pos. 85) on pneumatic
manifold.
129.1 One of the following options can be preselected on the "Pantograph selection"
rotary switch (on the PP in the machine room):
Pos. I The pantograph towards cab 1 end is selected, irrespective of
whichever cab is active
Pos. AUTO The pantograph towards the inactive driver's cab is selected.
Pos. II The pantograph towards cab 2 end is selected, irrespective of
whichever cab is active
Note:
Normally, the rotary switch will be in position " A U T O The switch will be
required to be thrown to Pos. I or Pos. I1 when there is a need to isolate one of
the pantographs.
.. -. . .
Reaction:
The pantograph is raised. Information message on the diagnostic display.
74 The catenary voltage is displayed on the voltmeter "U" (I), once the
pantograph makes contact with the overhead wire.
Note:
48 If there is insufficient pressure to raise the pantograph, the auxiliary
compressor is switched on automatically by pressure switch 172.4 on the
pneumatic panel (PP).
The auxiliary compressor will stop automatically after it has built up a pressure
of 6 kg/mz.
Wait until auxiliary compressor has stopped running.
pqmi
UBA
LSDJ LSHO LSP LSAF
U
ZBAN LSVW
1l
172 If the spring-loaded switch "BLCP" is kept in the position "OFF', both main
compressors are switched off.
-- - .- a-- - - -- -
ABB Transportation Systems Ltd. ldent No 3EHW411116 en Chap.4 - Page 34
Indian Railways WAP-5 vehicle operation
Driver's Manual
172 In this operating mode, the driver moves the spring-loaded switch "BCLP" into
the position "MAN". Both compressors run as long as the VCB is closed and
the switch is kept pressed in the position "MAN".
Note:
In the "MAN" mode, the compressors are not cut out even if the main reservoir
pressure exceeds 10.5 kg/cnf
A mechanical interlock between reverser ( 1 ) and the TE/BE throttle (2) means
that the reverser can only be actuated i f the TE/BE throttle is on '0' and the
speed of the locomotive is 0 km/h.
- -- - -
Driving
"BPPB"
3. bring the direct brake handle to the "Release stop" in the fully
clockwise direction
4. bring the automatic train handle to the position "Run" and wait until
the brake pipe pressure has reached 5 kglcmZ
5. check the flow indicator and ensure that there i s not a high air flow
when the brakes have been released
The illuminated push-button "BPPB" must not be lit up and there must
not be an isolation message that the brake pipe i s isolated from the E70.
6. set the TWBE throttle to the desired position in the range 0 to TE
,,
(tractive effort)
Note:
In order to improve adhesion and to avoid wheel spinning the sanding valves
can be activated by pressing the foot switch "SANDING'!
The automatic air train brake is cut out only on the loco as long as the foot
switch "PVEF" is pressed down and as long the pressure in the automatic air
train brake pipe is not lowered.
m
Braking
a
0\
cu
1. set the TElBE throttle to the desired position in the range 0 to BE,
(braking effort)
2. move the handle of the automatic train brake from the position "Run"
to "Initial Application". If more brake force i s required move the
handle to the desired position between "Initial Application" and "Full
Service".
For gradual release of the automatic train brake move the handle in th6
clockwise direction between "FullService" and "Initial Application".
For full release move the handle to position 1. I
3. when the train stops, set the direct loco brake handle to the desire
position within the "Operational range"
I
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap. 4 - Page 3
Indian Railways W A P d Vehicle operation
Driver's Manual
-. - -.-- .- - - ------ --
4. apply the parking brake
Note:
The regenerative brake is only effective if brake cylinder pressure is "0"
(See panel 8,Brake Cylinder Pressure Gauge)
To initialize the brakes of the train after coupling move handle of the automatic
train brake to position "Release". This position has also to be chosen for a fast
release of the train brakes.
The emergency brake is independent of the control electronics. It can be activated in the
following ways:
1. pressing the push-button emergency stop
2. setting the automatic train brake handle to the position "Emergency"
3. operating the emergency brake cock in the driver's cab (assistant
driver's side)
Reaction:
.- .- -- -- - -
a- -- .- - -
Reaction:
The MCE remains in self-hold mode for 10 minutes while the cab is being
deactivated. An appropriate priority 2 message appears on the screen. During
this 10 minute period, the driver's cab can be changed or the train can be
prepared for multiple operation .
10 minutes after the pantograph has been lowered, the self-hold setting is
interrupted and the MCE shuts down.
Note:
125 If the key switch is moved from Pos. "D" to Pos. "0" without the train driver
opening the VCB, and the pantograph lowering, this initiates an automatic
shut-down.
The MCE can be shut down immediately by moving the BL key from Pos "O" to
Pos. " C . Ensure that the electronics is switched OFF and then remove the
key from PosJ'0".
A
Warning:
-=i
Before switching "OFF" the BL Key, it must be ensured that the lo9~motiveis
stand still. cu
While the cab is deactivated (key switch in position " 0 ), the following functions remain
operative:
1. MEMOTEL functions
2. Catenary voltage display
3. Emergency brake cock on assistant driver's side
4. Cab and desk lighting
5. Windshield wipers
6. Fault display screen
7. Marker lights switches
8. Cab venting and heating
9. Crew fans
10. Hand lamp
125 1. Move key switch " B Y into position "0" and remove the key.
2. Set automatic brake controller to position "Neutral" and remove
.handle.
3. Release direct brake.
4. Change driver's cab and insert key.
5. Move key switch "BL" into position "D".
6. Insert automatic brake controller handle and set to "Run" position.
Note:
After moving the key switch "BL" to position "0: the MCE remains active for
10 minutes. The change of driver's cab should take place during this time.
If the MCE has to be restarted, it takes longer to set up the locomotive because
peripheral tests have to be carried out.
125 1. Move key switch "BL" on master locomotive into position "O",jyd
remove the key. 0-
8
2. Set automatic brake controller to position "Neutral" -3
0.
3. Release direct brake. cu
4. Set the brake feed pipe cock 136 to the " Close" position.
5. change the loco and Set the brake feed pipe cock 136 to the "Open"
position on this previous slave loco.
6. Insert key in driver's cab of previous slave loco.
7. Move key switch "BL" into position "D".
Note:
The change of driver's cab has to take place within this 10 minute period
otherwise the MCE has to be restarted.
Note:
The automatic vigilance control system is activated only if speed is greater
than 1.5 km/h and brakes are released (brake cylinder pressure is below 1
kg/cnf).
Reaction:
An intermittent signal sounds in the driver's cab (546 Hz), from the buzzer B Z - V U F .
-- - - - - - --
a -- --
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 42
Indian Railways WAPQ Vehicle operation
Driver's Manual
235 Press and release the "VIGILANCE" foot switch or the push-button "BPVG".
Release of the foot pedal at any time causes an automatic switch to the "Deadman"
safety mode. In this mode the audible warning is sounded after 60 seconds and the brake
application and power cut off initiated after further 8 seconds. Resetting from the driver's
controls is not possible; pressing of the vigilance pedal or the push-button "BPVG is the
only means of resetting the system.
Reaction:
An acoustic alarm is triggered and emergency brake is applied after 8 seconds.
The acknowledgement of the alarm of the vigilance unit can be done by pressing either
the push button "BPVG" on assistant driver's desk (panel D) or pressing the foot.
Note:
A reset cannot be made for at least 120 seconds after penalty brakes are
applied.
The fire detection unit is equipped with two smoke sensors and detects any fire in the
machine room by checking the machine room air at for smoke.
- 1. The first detector which detects smoke triggers an alarm:
An intermittent signal (1170 Hz) sounds in the driver's cab, from the buzzer BZ-V-0-F
A fault message priority 2 appears on the monitor
Note:
The machine room has to be inspected.
Note:
The driver takes the specified course of action.
4 lndication lamp B
speed, fault message
Fault in MEMOTEL, incorrect speed indication c\r
w
*
5 Interlock Interlock of cover
6 Push button C Selection of amendment mode, digital display (can be
locked)
7 RS232 interface Interface for the Service Computer (can be locked)
8 Push button I3 Alters the digital value (can be locked)
9 Memory Card
10 Push button A Selection of digital display for lighting control
Note:
Memory Card and interface for Service Computer are not available in Cab I.
Note:
If a fault is detected, lamp B lights up.
The brightness of the scale and the light intensity of the digital display can be
adapted to suit the light conditions in the driver's cab.
If push button A is pressed for longer than 2 seconds, brightness rises in linear
fashion in intervals of approx. 8 seconds from 0 to 100% intensity and starts
again from 0%.
The selected brightness is displayed on the digital display as a percentage
value and, when push button A is released, the selected brightness value is
stored in memory.
- Data are being read out or deleted with the help of a service device
-- - .- -- - . -- -- - .
... -
OI
4.7.2.4.2 Push button B c\r
Note:
All setting work only by Service Personnel.
Push button C:
1. Activates the amendment mode for the digital display unit.
2. Selects the digit to be amended.
- - - ---
- - .- --
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 48
Indian Railways WAP-5 Vehicle operation
Driver's Manual
151.4 When the locomotive is moving at a certain speed, pressing the illuminated
push-button "BPCS will maintain the speed automatically.
The push-button "BPCS" remains illuminated when constant speed control is
active.
CSC has access to 100 % traction and braking force, i.e. the position of the
TEIBE throttle (angle transmitter) has no impact on the effective speed.
Note:
To minimize oscillation, the CSC should be set during a slow acceleration
phase.
-11 11
oboo
LSDJ LSHO LSP LSAF
I
ZBAN
LSCE BL
169.1 The hotel load switch "BLHO" (2) has the following positions:
Pos. "ON": Hotel load switched on
Pos. "0": Neutral
Pos. "OFF": Hotel load switched off
169.3 When the hotel load contactor is closed, the yellow indication lamp "LSHO" (1)
lights up in the driver's cab.
Note:
If the hotel load is switched off for some reason, it does not switch back on
automatically. Instead, the train driver must move the hotel load switch
"BLHO" (2) back into the "0N"position.
If the main circuit breaker is switched off, the hotel load contactor opens
simultaneously.
- -- -
- - - .. . -- - -- --
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 50
Indian Railways WAP-5 Vehicle operation
Driver's Manual
Warning:
- Never connect the hotel load cable to another loco.
- Never connect the hotel load cable to a coach when the pantograph is
raised.
4.10.1 When driving on a neutral section, all necessary actions to comply with Indian
Railways regulations must be taken manually by the train driver.
Warning:
I n multiple operation, both the most distant pantographs are raised if "pantograph
selection switches" in both the locomotives are in position "AUTO". The train bus
connecttons define the free end of each locomotive.
The command from the master locomotive to raisellower the pantographs also controls
the pantographs on the slave locomotive.
. .- ----- -. - - .- -. - -- -.- .
Note:
179 Whenever the simulation key switches on the master and slave locomotives
are not in the same position, the pantographs are not active (fault message).
The command from the master locomotive to switch the main circuit breaker "ONI'OFF
also controls the main circuit breaker on the slave locomotive.
The VCB on the slave locomotive is switched on after a delay of 0.5 seconds following the
switch on of the VCB on the master locomotive. When switching off, there is no delay.
Note:
If the VCB on the slave locomotive cannot be closed due to a fault, an
appropriate fault message appears on the screen.
During multiple operation, there is a limitation on the regenerative brake on the slave
locomotive. This limitation reduces forces on the loco buffers (prevention of derailing).
The anti-spin protection of the slave locomotive is independent of the master locomotive.
32 During multiple operation, the hotel load contactor on the master locomotive
must be in the "OFF' position. Only the slave locomotive is capable of
supplying power to the hotel load.
169.1 The command for switching on the hotel load is transmitted to the slave
locomotive by the train bus. Whenever the VCB is closed, the hotel load
contactor is only closed on the slave locomotive if the driver on the master loco
presses the spring-loaded switch "BLHO" to the "ON" position.
169.3 The yellow indication lamp "LSHO" acknowledges this operation in the driver's
cab of the master locomotive.
Before the contactor of the hotel load can be closed, both locomotives must be set up.
If it is not possible to activate the hotel load contactor on the slave locomotive, an
appropriate fault message appears on the screen.
Warning:
- Never connect the hotel load cable to another loco.
172 The selected position of the compressor switch is transmitted to the slave
locomotive.
In the "Man" and "Off positions, all main compressors in both locomot~vesare
controlled directly.
In the position "Auto", there are the following options:
172.2 1. A main reservoir pressure below 8 kg/cmz on the master or slave
locomotive activates a particular compressor on both locomotives. Each
locomotive switches alternately and independently between its two
compressors.
-. -
172.3 2. A main reservoir pressure below 8.5 kg/cm2 on the master or slave
locomotive activates all compressors on both locomotives at the same time.
269.4 3. At a main reservoir pressure below 6.4 kg/cmz, each locomotive
independently controls its compressors.
The multiple unit cannot drive if one of the parking brakes is applied.
Note:
268 An activated parking brake on the master or slave locomotive is indicated in
the activated driver's cab of the master locomotive by the red illuminated push
button "BPPB'!
An emergency brake on the slave locomotive can only be initiated in the following
manner:
1. By actuating the brake handle of the automatic train brake to "Emergency"
position
2. By actuating the emergency brake cock on the assistant driver's side
269.1 If the pressure switch 269.1 on the master or slave locomotive registers
actuation of the emergency brake, the ensuing command for emergency
braking applies to both locomotives.
The master for all other emergency braking commands is the master f:
locomotive in the double (multiple) unit. 6
d
-
m
C\:
4.11.1.10 Other brake functions -. .- ,
269.6 If the pressure switch (269.6) registers a pressure in the brake cylinder of any
bogie, and if speed exceeds 10 kmlh, tractive effort is set to 0.
Note:
If the electrical brake on one of the two locomotives fails, the electrical brake
on the other locomotive remains functional.
3.11.2 Coupling
Example:
Note:
If configuration proves impossible, (or if no slave locomotive is available)
locomotive number 00000 appears.
If more than one driver's cab is activated in both locomotives, one is shut down
and a corresponding message appears on the displays in both locomotives.
Starting position:
Master and slave locomotives are available and both are ready.
1. Shut down both locomotives in accordance with regulations (VCB switched
off, pantograph lowered).
2. Remove the UIC cable and disconnect the locomotives pneumatically and
mechanically.
3. Both the locomotives are now ready for setting up as a single locomotive.
Note:
If for any reason the train bus link is interrupted, or if both locomotives are set
up or in motion, the system protection initiates a monitored shut down of the
slave locomotive.
Reaction: oc3
0-
The pantograph of the slave locomotive is lowered and a corresponcPTfg fault
message appears on the screen of the master locomotive. (U
192 Sanding on both locos can be initiated by the driver by pressing the sanding
foot switch on the master loco.
A fire detection on the slave locomotive initiates an audio signal on the master locomotive
(1 170 Hz).
In addition, the VCB on the slave locomotive is switched off and a priority 1 fault message
appears on the displays of both locomotives.
Note:
All equipments on the master locomotive are supplied by the battery and are
functional for a maximum of 5 hours, if battery is fully charged.
153 1. Set switch "ZBAN "Banking operation" to position " O N (Panel A).
2. Set up the loco in the normal manner.
3. Cock position 136 and 70 should be "Close" on Pneumatic Panel.
Note:
The brake pipe on the locomotives is not filled by the slave locomotive but, in
emergencies, on the slave locomotive the train brake can be actuated.
During the Set Up, the train driver receives a priority 2 message that banking
mode is active.
-
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 58
Indian Railways WAP-5 Vehicle operation
Driver's Manual
Switch off the BLDJ. (Main Circuit Breaker). Lower the Pantograph.
Note:
Check that the pantograph isolating cocks 8 are closed.
The "AUTO A9" Brake Controller should be in the "NEUTRAL" position in both cabs of the
dead locomotive.
The "DIRECT SA9" Brake Controller should be in the "RELEASED" position in both cabs
on the dead locomotive. e
0
Pull the distributor releaser on the dead locomotive to exhaust any residual pressur@
the brake cylinders. o.
n
l
Connect the Brake Pipes and the Feed Pipes of the leading and dead locomotive and
open the BP and FP end cocks.
Release the Parking Brake by operating the release push button on the latched solenoid
valve (30) on the brake frame, and lock in position.
Check the condition of the Parking Brake Gauge in the drivers cab, this should indicate
5.0 KglCm 2 .
The brake rigging should be loose and the brake pads away from the discs,
Note:
In normal locomotive running conditions the cab Parking Brake Gauge should
indicate 6.OKg/Cm2 Nominal.
4.14.2 Making a dead locomotive ready for towing ( When brakes are already
applied)
1. Couple the live locomotive to the dead locomotive.
2. The "AUTO A9" Brake Controllers should be in the "NEUTRAL" position
in both cabs of the dead locomotive.
3. The "DIRECT SA9" Brake Controller should be in the "RELEASEDn
position in both cabs on the dead locomotive.
4. Pull the distributor releaser on the dead locomotive to exhaust any
residual pressure in the brake cylinders.
5. Close isolating cock 70 (E70Brake Pipe Isolating Cock).
6. Close isolating cock 74 (Emergency I Vigilance isolating cock).
7. Close isolating cock 136 (Brake Feed pipe isolating cock).
8. Open isolating cock 47 (Dead Engine cock).
Note:
Check that the pantograph isolating cocks 8 are closed.
Connect the Brake Pipes and the Feed Pipes of the leading and dead
locomotive and open the BP and FP end cocks.
Release the Parking Brake by operating the release push button on the
latched solenoid valve (30) on the brake frame, and lock in position.
Check the condition of the Parking Brake Gauge in the drivers cab, this
should indicate 5 OKglCm2.
- --
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 60
Indian Railways WAP-5 Vehicle operation
Driver's Manual
Note:
The brake rigging should be loose and the brake pads away from the brake
discs.
Double check if the Parking Brake has fully released on the respective wheels
by moving the shoe hangers and checking for clearance between the shoe and
wheel brake disc.
The locomotive is now ready to be towed.
Note:
In normal locomotive running conditions the cab Parking Brake gauge should
indicate 6.0 Kg/Cm Nominal
4.14.3 Towing a dead locomotive (When no brake are applied o n the dead
Locomotive)
1. Bring the live locomotive adjacent to the dead locomotive
2. Close isolating cock 70 (E70 Brake Pipe Isolating Cock)
3. Close isolating cock 74 (Emergency /Vigilance isolating cock).
4. Close isolating cock 136 (Brake Feed pipe isolating cock).
5. Open isolating cock 47 (Dead Engine Cock).
6. Connect the Brake Pipes of both the locomotives and open their
respective end cocks, allowing- sufficient time for the pneumatic
system to charge on the dead locomotive prior to moving to t h w e x t
step. o*
7. Apply the "AUTO A 9 brakes on the lead locomotive to Full ~ e g c e .
8. Close the Brake Pipe end cocks on both the locomotive!?and
disconnect the brake pipes.
9. Couple the live locomotive to the dead locomotive and follow the
steps as outlined for point 2.0.
Warning:
Do not connect the UIC cable between the loco and the towing vehicle.
4.15.1 Definition
150.1 This mode allows the locomotive to operate even if the angle transmitter of the
TEiBE throttle has failed.
In this mode, driving and electrical braking are controlled by the auxiliary contacts on the
TEIBE throttle.
Driving in failure mode becomes necessary if the difference between auxiliary contacts
and the absolute value of the angle transmitter is greater than 25% of the full range
because of a defective master controller.
The following steps are initiated with a time delay of 2 sec:
1. Traction is set to 0 by the MCE.
2. A priority 2 fault message is displayed.
152 3. The driver must now move the rotary switch "Failure Mode Operation" in
the mach~neroom (SB1) into position I.
This deactivates the angle transmitter.
4. The driver must move the TUBE throttle into position " 0 .
5. The driver must acknowledge the fault message.
6. The driver can now select a new TEIBE throttle value.
4.16.1 General
A lot of information can be called up on screen describing the status of the locomotive
and its sub-systems.
If a fault occurs, the following messages appear automatically on the screen:
Fault messages.
Messages on isolated sub-systems.
lnformation messages.
-- .- - -- . - - -.- -
This information appears on screen if the locomotive is fault-free or if it has been selected
on display with the CLEAR button.
This screen simply shows the time and date on the top line. The display screen is
0 t h e ~ i s eempty which means that any display of fault messages will immediately attract
the train driver's attention.
Note:
A few sub-programs are equipped with a time limit. If the keyboard on the
display screen is not used for more than 60 seconds, the system changes over
automatically to the stand-by screen.
- -- --- - .
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap.4 - Page 66
Indian Railways WAP-5
Driver's Manual
FAULTS
5.1 General
Most faults are detected by the relevant monitoring equipment and are reported to the train
driver by indication lamps or displays on the screen.
Note:
163.1 If a fault message appears on screen, the yellow illuminated push button
"BPFA" lights up. If this is a fault message of priority 1, the red indication 'lamp
"LSFI" starts flashing at the same time. 00
-
CI
163 If a fault message with priority 1 is displayed, a fault message with priori@ is
suppressed on the screen. o. '
rV
A fault message with priority 2 remains on the screen until it is overwritten by a
fault message with priority 1 or by a subsequent fault with priority 2.
- .~
- - .. - . -. - --- - -~ -
Warning:
See chapter 5.1.3.3 for resetting of the locomotive.
A t the end of the journey the driver must inform the maintenance staff to check
and, if necessav, repair the locomotive.
1. lsolation of one traction bogie: Only half traction and braking power available.
2. lsolation of both traction bogies: No traction and braking power available.
3. lsolation of harmonic filter: Speak to TLC before proceeding further.
4. lsolation of HBBI: Cab-1 isolated, driving possible from cab-2 only.
5. lsolation of HBB2: C a b 2 isolated, driving possible from cab-1 only.
6. lsolation of STBI: Cab-1 isolated, driving possible from cab-2 only.
7. lsolation of STB2: Cab-2 isolated, driving possible from cab-1 only.
8. lsolation of FLGI : No multiple operation.
9. lsolation of FLG2: No regenerative brake.
Note:
All priority 1 faults are acknowledged simultaneously when the
acknowiedgement button is pressed. However. if the train driver first wishes to
see whch faults have been reported, he must press the "ENTER" key before
acknowledging the faults. When he does this, all faults are displayed in the
follov~ingsequence:
Faults in the individual sub-systems of the master locomotive
Faults in the individual sub-systems of the slave locomotive
By pressing the "CLEAR" button, the highest priority fault is displayed once
agai~.
Also, afler the last fault message has appeared, the fault with the highest
priorily IS displayed once again (ring buffer principle).
Note:
If a faui't message with priority 1 is displayed, any priority 2 fault message
present at the same time is not displayed on the screen.
Dependent on the degree and frequency of a certain failure the control electronics tries to
restore or isolate tP,e co~cernedsub-system.
in case of blocking the tram traffic due to isolation of too many sub-systems it may be
helpful to Setup the locomotive in original conditions.
To reset the locomotive, the following procedure has to be carried out:
1. VCB off
2. Lower pantograph
3. .
BL Key switch to Zero position, i.e MCE complete oft
4. Wait 1 minute
5. Setup locomotive again as usual
- --- - - - - -- ---
ABB Transportatior Systems Ltd. ldent No. 3EHW411116 en Chap. 5 - Page 4
Indian Railways WAPB Faults
Driver's Manual
Vehicle diagnostics
> 1. Loco 30001
2. Loco 30002
- -
Sub::equent procedure: Select the desired locomotive (move ">" with arrow keys)
Press "ENTER" key.
L Press the "HOME" key to return the system to the Main Menu.
--- -- - . . .. -- .- - - A - - - - ..a -
ABB Transpor?ation Systems Ltd. ldent No. 3EHW411116 en Chap 5 -- Page 6
Indian Railways WAP-5
Driver's Manual
Vehicle diagnostics
> 1. Loco 30001
2. Loco 30002 92
3. Browse mode
Example:
Fig. 5.3
Status of locomotive 30001: No sub-system isolated
At least one fault with priority 1
Status of locomotive 30002: At least one sub-system isolated
At least one fault with priority 2
5.1.6 Browse
With the help of the Browse Menu, all current sub-system isolations and fault nessar;es
can be displayed.
1
j Vehicle diagnostics Loco Status
1. Loco 30001
t 2. LOCO 30002
, > 3. Srowse mode
i Train configuration
I
I
LOCO30001 LOCO30002
- . - .
- - - - - - - - - - -- - . -- -- - . - - - - - - - - - - . -
Energy consumption is recorded and displayed on screen in kwh (kilowatt hours). The
value is stored in the database of processor DIA1, i.e. the cumulative consumption is
displayed on screen.
Display energy consumption:
In Main Menu, place "z" on "process information".
1. Vehicle diagnostics
2. Information trainbus
> 1. ~ n e r consumption
g ~
2. Commissioning data
Energy consumption
LOCO
30001 XXXXXXXX k w h
Note:
After 50'000'000 kwh the counter starts again at 0.
5.2 Earthing
- - . -- . - ---- - .
- -- - - - - -
a -- - -
. .- -. - . . - ~
A fault message is displayed on the screen in the cab and gives the following information:
5.3.1.1 Example
5.3.1.1.1 Explanations
SSO2:Traction bogie 1
6 IE 1 ISOLATED ; O n l y h a l f traction
5
and br*ng parer available
ress <enter>
11 I
- - - -a,-- ~ -- - - - -
dF0102P1 VCB STUCK IN OFF POSITION VCB control changed 1 st Press BLDJ to
Try to close the VCB again to redundant processor close VCB
d ~ 0 1 0 3 ~ 1LOW PRESSURE PANTOIFAULTY - LSDJ Pantograph will not be Wait for aux. Check isolating cock;
PANT0 raised Reservoir Check auxiliary reservoir
Check iso. cock, aux reservoir pressure pressure reaches pressure; Q h s k
5.2 kgIcm2 --
auxiliary c o m p ~ e ~ r
-
VOLTAGE OUT OF LIMITS LSDJ VCB off
atch catenary voltmeter
Bring throttle to
" 0 " position. Wait
lose VCB when voltage is OK for catenary
voltage to reach
within limits
29491s;
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap. 5 - Page 15
Indian Railways WAP-5 Faults
Dr~ver'sManual
-~ -
I ; circuit are open or not'
JI
STUCK I
-- -. - -.----
CB tripped CB cannot be closed.
sk for relief loco
ain converters blocked
!
I
Check overcurrent relay
heck overcurrent relay flag flag
I
1
1
t +- - . +I + -+-+ -- - -+--- ___3 ___(
i 1 2nd 1 IMAINPOWER ~ C can
B not be closed !
ISOLATED
VCB nh~bited
,Loco is dead
~ ~
/&k for rebel loco
< 1
? . . . +.I. + , . . - - .- 4
I
; Is: ,iJress BLDJ to
I ry to close the VCB ngair plose VCB
* - . . i . -
:~lAlhPOWtR ~vCBcan not be closad :
ISOLATED psk for relief loco
'VCG int~ibitea
'Locti is dead !
A ~ - . ~
- .~- -- ~ -~- ~
-~.. ~~ -~ .---. ~~
~FO101
P2
RVERTEMPERATURE CONTROL
ELECTRONIC
o be checked during maintenance
LSCE Control electronics
c w o r will not close
C
Put BL key to "C"
osition
ait for LSCE to
extinguish
-F0102P2 TRANSFORMER OIL PRESSURE NOT TElBE reducecl Check manually whether
3K Increase ventilatiqn transformer oil pumps
Any oil pump circuit not working -- trips
VCB work or not
TEIBE will be reduced 4
- -- -
o be checked
, ' 7 - - ~-
- 7--- - - - -- -- - -.-
. 2nd , j - 3 0 ~ 1 1S0eATED:':nfor~
~ m-A'lt*p"c7C i l : ~ Y ,
, t:-:ij nd.f i ~ d c t ~ o
and
n
lelectricai braking
bower available !
+-- - - 7 --- - - $
t1st7Press
-BLDJ to I _--A
F0202PI~&"ERTER CONTACTOR STUCK ,
I
! ,-lose VCB
I Rc:o close the VCB again
+-4 -
- ~~. C------- _--- .- !
2nd
nly half traction and
I
lectrical braking
ower available
-- -- - . .
SUPPLY STUCK OFF , I
I
- . -
- t. - - -- -L -
1
I, ' 2nd '
i I
1
! 1
+ .- .- + - - +-- !
. . -- - .
I
../ + - - * - - . .- - .
ONVERTER 1 OIL TEMPERATURE 8 1 1st ]press BLDJ to
I
pry to close the VCB again I heck manually whetner I
I I bil cooling unit works o!
I
hot
- . .
I
. .+
I
* - . . . .*. +.. & . . . .-+-- -.
-t--~ ~
I
i~~
-
- - --
I I i
I
2nd ;
b
BOGIE 1 1SOLATED;lnform mainterrance staff
nly hal! traction and I
Blectrical braking
I
!
I powor available 11
i ,
. i -L.
. . -- . 2 . - . .- ~~ - - -- ---.-I J
- - -- --- - - -- - - - -- - -- --- -
ABB *nsportatron Systems Ltd. ldent No 3EHW411116 en Chap. 5 - P* 18
lndian Railways WAP-5 Faults
Driver's Manual
"F0206P1 CONVERTER 1 OIL PRESSURE NOT Ist Press BLDJ to Check oil level converter
OK close VCB 1 expansion tank
Check oil level Check manually whether
Try to close the VCB again converter oil pump 1
works or not
- 7 - -
. - ~~
- -. -- 7 --
r 0204P2 'FAULTY MOTOR TEMPERATURE. 1 Ilnform maintenance staff 1
!
i"
ENSORS
Normal operation can continue
y o be checked during maintenance
i- +- .-
F0205P2 'EQUIPMENT TEMPERATURF H1GH
---- A
f
"
!NOT OK
Normal operation can continue I I e checked during
o be checked during maintenance
boaie 2
Try to close the VCB again if tripped 1 --
lose VCB
I
'&GGISOLATED; inform maintenance staff
nly half traction and
I
2I n d I' -
lectrical braking
bower available , I
I Is! ' ~ r e s sBLDJ to
I klose VCB
.+ .
--
-
~BOGIE2 ISOLATED; t ~-
Inform
~
maintenance staff\
$nly half traction and 1
,electrical braklng I I
power ava~lable
+I
- -- * - + --
F0303Pl ATE UNIT SLlFPLY STGCK OFF 1 1 st Press BLDJ to
ry to close the VCB again I
klose VCB
- - . - .
- -
Systems Ltd.
A60 msportat~on
lndi8f~ailwa~ s
WAP-5 Faults
Driver's Manual
-F0306P1 CONVERTER 2 OIL PRESSURE NOT 1st Check oil level; Check oil level converter
OK Press BLDJ to 2 expansion tank
Check oil level close VCB Check manually whether
Try to close the VCB again converter oil pump works
or not
294918
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap. 5 - Page 21
Indian Railways WAP-5 Faults
Driver's Manual
-~ . ~ . .~- - -- - . - . - -- .-. . .- - . - -- - 1 -7
F0301P2 /EARTH FAULT IN CONVERTER 2 /inform maintenance staff,
Normal operation can continuo I
--
ko
be checked dunng matntenance I
I
. - - . . . -+ . C ~ . . . . .--.. - i . ..* . . . ---+--+ - .. - . . .++ ......
: F0302P2 ~ A C T I O NMOTOR OVERSPEED ' e educe speed ;
I
h~
is being reduced
Reduce loco speed
- - - - .+
. . . . . . . . .
.. . . + ......... 1
I
I F0303P2
f UB RFSISTANCE TOO HOT IN
CONVERTER 3
?&dl1for 30 seconds
h a i t for 30
seconds
press BLDJ
o close VCB
~- I
I
i
F0304P2 i ~ ~ MOTOR
LSENSORS
- - -
~ ~ TEMPERATURE
T Y /
I
1
1
Inform maintenance staff
- . -.
ormal operation can continue
be checked during maintenance
-.-
it-i i
F0305P2 IEQUIPMENT TEMPERATURE HIGH $
I
I
1
hE3l/~
--
is being reduced
a
. -. . -- - . . ,. - .- - - I i
' F0306P2 1 3 LINK
~
.'NOT OK
CAPACITORS PRiSSLlRE I !
maintenance 1
I
~. - ~
6504:
.... ..+. . . . --.+
:Reduce braking effort
---- --.
F0401P1 /HARMONIC FILTER CURRENT TO0
. . . . . . .
:
+ +.
i
. .
1st 'press BLDJ to
. . t . . . . - - + .. . .
4
Varmonic
her
HIGH I /close VCB
'Try to c!ose the VCB aqain I I I i
. . + . . -
*
1
p.
2nd :Raduce speed to
40 km/h !ISOLATED
i40 kmfh
- - I.. I .
._. . . -. . . . .
- - --- -. - -~- -- ~
-- - -. - -~. - .-
ABB Tmsportation Systems Ltd. ldent No. 3EHW411116 en Chap. 5 - p a 2 2
Indian Railways WAP-5
Driver's Manual
',
2nd Hotel Load isolated lnform maintenance staff
F0502P2 HOTEL LOAD CONTACTOR STUCK For unlcoupling Inform maintenance staff
ON hotel load trip Work on hotel load is
For unlcoupling hotel load trip VCB VCB allowed with VCB open1
?n ..
cYQV10
4I
ABR Transoartation Svstems Ltd. ldent No. 3EHW411116 en Chap. 5 - Page 23
Indian Railways WAP-5
Driver's Manual
-.-.,.-
. . . . . .
'2".-
. _ - _ - .* -- " ~ ~ ~ ~ .
c36C.7P' 3ib';IRBANCE IN PROCESSOR : 1 st ~ r e s BLDJ
s to
AUX. jdr' : close VCB
lconverter 1
Try to close the VCa ,. .. t
+ . ~ ... +! -4 7' -
- - -1 - I
. . .............
;Aux. Converter1
..
jlnform maintenance staff
I
- i : will
.. be reduced -I --
........ ~ ~ ~. ~ ~ ~
- + ~+ . t . . . f >-
i
CONVERTER 1 I 1st !Press BLDJ to
ry to close the VCB again I
I .......... +~. -- - .~ ~. -- -4
1 2nd ux. Converter1 Inform maintenance staff 1
i ', 'solated
1
I
ax.beventilation
ill reduced level
;.. .... +
I I ux. Converter 1 heck contactors;
ontactor 52/4 or 52/5 stuck off
..................... . .+ . . . . . . . . . . .
l ay get isolated gform maintenance
staff;
- -
t----
BUR1 Press
I
, /acknowledge to
1 Press acknowledge to reconfigure to
!
,pS07:
iAux.
..........
Convener 2
/ .-
FO707P'
. .f--
.,-
!BUR,
--
-.
-t--
I
i-
Is1 ,Press BLDJ to
plose VCB
-
I I
4
I
I
f - - -4. . - . 4. + .t2,?~ . . . -. + ........... + ---
I p x . Converter 2 'lnform ma~ntenancestaff 1
1l
I
I rsolated
I Max ventilation level
(will be reducea
i
I
i- . . 4
2 :
t +. . i
,
:
*~
- i ~. j
- ~~ ~- ~ - - . - . .. -~. . . .
~. .~ ~ ~~
-.-- ....... ........ ..~ - --
ABB mnsportation Systems Ltd dent No. 3EHW4 11 I 16 er. Chap. 5 -- Ph 34
lndm Railways W A P d
Driver's Manual
--
ABB Transportation Systems Ltd. d y 4 920 ldent No. 3EHW411116 en Chap. 5 - Page 25
Indian Railways W A P d Faults
Driver's Manual
,. T -- , -- - - - - .. . .. . . ~
~.~~~ ..~ . . . ? . , ~~- .- .- -- -.- -. - ---, - ----
F
~
7
SSO9: F0901Pl /BATTERYVOLTAGE TOO I OW Ma~nPower isolated sk for relief loco I
;Battery :Electronics will switch off PCB can no1 be ,
i
!?B":hibited I
; -- - . 4 --- . .. . . . .. . . .. . . .
t + ~ ~ - .- . .,..! ,.. . .
boco is dead
+.-~
1 fio r relief loco 4 .
FT)902P1 -OW BATTERY VOLTAGE :Press BLDJ to
n;u;i..C?-- bninq Swi!chea oft : lopen VCB
open VCB, lower PkiL i 3 !press ZPT to
L
i~vdcrPanto
1 i
I
!
i
4 . . .,. -- .-
i
1
LONGER THAN 10 ;
I
I I
. .-
A -- - - - . -- -.-~-
~
-. - - - - - ~ - - -
ABB '41sportation Systems Ltd. ldent No. 3EHW4 I 1 116 en Chap. 5 - Pw 26
lndiah Railways WAPQ Faults
Driver's Manual
SS10: JFIOOIPl FAULT IN BRAKE ELECTRONICS Bring TE/BE Ask for relief loco
Brake Emergency brake applied throttle to " 0
system No Traction allowed position
-
"F1002P1 LOW PRESSURE MAIN RESERVOIR BringTELBE Checkwhether
No traction allowed till pressure throttle~to"' compressor work or not
reaches 6.4 kgIcrn2 position. check t?airifZKeavy
-.~
--
Wait until a leakageit pneumatic
plessure of 6.4
kgicm2 si-
,-
system J
-
r'e&hFd
-.
-F1003P1 VIGILANCE EMERGENCY BRAKE Bring TWBE
APPLICATION throttle to "0"
Bring TWBE throttle to zero position
Press vigilance reset pushbutton Press vigilance
reset pushbutton
- -- -
P
.-.r- - ,-'
F1007P1 REGENERATIVE BRAKE FAILURE
~ - - .-
I
+ -- !
~~
-T
~- ~
I
.. +
I
- +Bring TUBE
+-
power available
r
. .. ._I_)
I
. --. 4
THE LOCO ihrottle to '0'
'To t ~ i * d S ' = , 1ti.*e: r;i,*
;;:*. F-:~.?J?*.:- 1 bosition 1 I I
i 'Bring TVBE throttle to zero :heset 1
I
-- t - -1 --
--
NOT ALLOWED WITH
PPLIED BRAKES
Release loco brakes
IBring TEBE throttle to zero
- - L --- - -- -
t- - -- - - -. .. .- - --
'F1031P2 '1OCO IS IN BANKING MODE I oco brake con!roller
l o c o brake controller isolated I I
.tmergency brakes can be applied
4I - - --
I1
F100"2 L
LARM CHAIN PULLING
heck the coaches
--
+
: -
ractlon power may get reduced,
if temperatdres exceed ~-
--- --
- '
--
t
~ 1 1 0 2 L~ R
2 T H FAULT 415/110V CIRCUIT
Normal operation can continue
To be checked during maintenance
- ~
- i i -
-
!
- 7 --
lnforrn rnalntenance
I
staff -
I
- -- - - - -- -- - ---- . -- -
AUB Wnsportatlon Systems Ltd. ldent No 3EHW411116 en Chap. 5 - P c r p 28
lndiw~ailwa~ WAP-5
s Faults
Driver's Manual
SS14: F1401P1 DISTURBANCE IN PROCESSOR HBB2 Change to Cab1 Inform maintenance staff
Cab 2 Cab 2 may get isolated;Drive,from Cab 1 (see chapter 4.5)
REFER TO DRIVER'S MANUAL
'ln
c 7
ABB Transportation Systems Ltd. ldent No. 3EHW411116 en Chap. 5 - Page 29
Indian Railways WAP-5 Faults
Driver's Manl~al
"- - .- " -- ~~
-- T -- ~~ ~~
- . - - 7 -- --- 1
IN PROCESSOR STB2, change to Cab 1 I F f o r m maintenance staff
ab 2 may get iso1ated;Drive from Cab 3 '(see chapter 4 5)
I
MANUAL. ' I
? - i - + + - .. + . -- ~ '1
F1433P1 REVERSER DkFtC7 IVE Change lo Cao 1 ,.3;:;1,1nn.,a:nt:r,~~:? ::!~f!
Dr~vefrom Cab 1 :(see chapter 4.5) I
t, t
Fire detection
_
F1501P I FIRE IN MACHINE ROOM
Extinguish the fire
.- - .- -t
1 LSFI
'~'JZZ~
- I
xtinguish the fire by
aintenance staff ,
I
'
I
F1501P2 FAULTIN FIRE DETECTION UNIT
(No fire detection DOSSible i
I 1
I
nform maintenance staff
I
3. - - 1 p r m a operation'can
~ continue .l--
.J -
SMOKE IN MACHINE
I nform maintenance staff
llnspect machine room
t. -1. -- - - .
-. - ~- - - - f ~. i
'?
-- - --.
(SS16: F1601P1 $PEED LlMlT EXCEEDED ILSVW I
I
!
(Speedo
lmeter 1
Emergency brakes appiied
prig
TUBE throttle to zero
I
1
I
I
,..-
I
* - .- . - -- - + +
I F1601P2 'FAULT IN SPEEDOMETER nform maintenance staff
I I ,No dlsplay of speed in the cab I
Drive carefully, use diagn. screen I
I I
nta 1 srmulat'on I
hode. screen 9) /
L
iSS17:
.. &
- -- -- - - -- - -
F1704P1 SIMULATION SWITCH POSITION NOT Bring TUBE Check simulation key
MATCHING throttle to "0" position on master/slave
Check simulation key on master/slave loco 4
SS18: F1801P1 DISTURBANCE IN PROCESSOR FLG2 FLG2 isolated Inform maintenance staff
Processor FLG2 will be isolated
FLG2
F1802P1 SOFTWARE MISMATCH WAP-5 Inform maintenance stzff
NAG-9 Check software
Panto will not raise Ask for relief loco
4
F1803P1 FAULT IN ANGLE TRANSMITTER OF Bring TWBE Operate switch failure
THROlTLE throttle to " 0 mode J
Bring TUBE throttle to zero Drive loco in Inform maintenance staff
3perate switch failure mode failure mode
operation (see
chapter 4.14)
F1804P1 SIMULATION SWITCH POSITION NOT Bring TEIBE Check simulation key
MATCHING throttle to "0" position on master/slave
Check simulation key on masterlslave loco /
L .
39AQ3? , L "
. , . .- - .- . - -- - f- -7
DISTURBANCE IN PROCESSOR DlAl !Inform maintenance staff j
'DIA1 will be isolated 1
I
- --I - - No Fault data will be stored - - - - 1 - + . +. . . . - -C 4
kls:
I
' '1
' F l 9 0 1 ~ 1)OMMUNICATION DISTURBANCE Press BLDJ to heck cable for multiple ,
Trainb21.s ry to close the VCB again plose VCB
!:klultiple operation not possible ,Inform maintenance staff'
oco is dead
.
ps02: 1
Traction 1
bogie 1 '
I
I
. - . -4
!
- ----
I
+~- - - - -- ; - & -~- _ 1_?__- . _ II - -
--
t- -"- --
.+--+ -- -- 1
3~04: 'YARMONIC FILTER ISOLATtD
'Harmonic ; speak to TLC peak to T;C
_-__ ' 'Press <enter,
1 . -
T i
$so5 ;HOTEL LOAD ISOLATED
/Hotel Load , :Driving still possiblo I
I
,Press <enten II
I I
! i I
----- - - -- - -- - -- - - -
ABB E r l s p o r t n t i o n Systems Ltd. ldent No. 3EtiW411116 e n Chap 5 - P ; P 32
-
lndian-~ailwa~s
WAP-5 Faults
Driver's Manual
-
SS06: AUXILIARY CONVERTER 1 ISOLATED Press <enter> AUXILIARY Inform maintenance staff
Aux. Driving still possible CONVERTER 1
converter 1 Press <enter> ISOLATED
Max. ventilation level
will be reduced
-
SS07: AUXILIARY CONVERTER 2 ISOLATED Press <enter> AUXILIARY Inform maintenance staff
Aux. Driving still possible CONVERTER 2
converter 2 Press centers ISOLATED
Max. ventilation level
will be reduced
SS08: AUXILIARY CONVERTER 3 ISOLATED Press <enteh AUXILIARY Inform maintenance staff
Aux. Driving still possible CONVERTER 3
converter 3 Press <enfen ISOLATED
Max. ventilation level
will be reduced
SS13: CAB 1 ISOLATED Press <enters CAB 1 ISOLATED Inform maintenance staff
Cab 1 Drive from Cab 2 Change to
Press <enter> Cab2 (see
chapter 4.5)
SS14: CAB 2 ISOLATED Press <enter> CAB 2 ISOLATED Inform maintenance staff
Cab 2 Drive from Cab 1 Change to cab-
Press <enter> 1 (see chapter
4.5)
SS17: FLGl ISOLATED Press <enters FLGl ISOLATED Inform maintenance staff
FLG 1 Refer to Driver's Manual No multiple operation
Press centers possible
SS18: FLG2 ISOLATED Press <enter> FLG2 ISOLATED Inform maintenance staff
FLG 2 Refer to Driver's Manual No electrical brake
Press <enter> power available
SS19: TRAINBUS ISOLATED Press centen TRAINBUS Inform maintenance staff
Trainbus Multiple operation not possible . ISOLATEDNo
Press <enteb multiple operation
possible
i
therwise after 10 min. MCE switches
Information
. . . .- . . .
NOT BE AVAILABLE
~RACTION! ' t ! ~
I
~- J p~~ntlres
--..
Bring TEBE
-
iw
i??? N THIS LOCO OR ON THE SLAVE , throttle to "0"
and set it again
~-
1 -ait
8, \
-- ; ~ l e a s e w a i-
~-. . - .~
. . -_-_ .. ~i
i~. ..
I
:information
05
1
~lnformation
FULLTWBE RESTORED
~ P A N RAISING
T~
--+- I . + . I .- --
_-I I
ploase wait _ ~ - -
- - -. . . .- - -- - - -- -- -- - -
--e
- a - --
6 INDEX
Air dryers
Alarm
- chain pulling
- triggering by vigilance control
Anti-spin protectionlanti-slide protection
Automatic train brake (pneumatic)
Automatic Vigilance Control
Auxiliary circuit equipment
Auxiliary circuits
Auxiliary circuits, cubicle-1 (HB1)
Auxiliary circuits, cubicle-2 (HB2)
Auxiliary compressor
Auxiliary converters (BUR)
Axle drive
Banking mode
Battery
Bogie layout
Braking Concept. Oveiview
Bus concept
Bus stations
Catenary voltage
Central electronics
Central electronics temperature
Comfort equipment
Commissioning of the loco
Compressed air
- generation of
Compressors
- Operating mode "AUTO"
- Operating mode "OFF"
- Operating mode "MAN"
Constant Speed Control (CSC)
Control cubicle-1 (SB1)
Control cubicle2 (SB2)
Control circuit
Control current distribution
Control electronics
Converter
Cooling concept
Coupling
- multiple operation
DC-Link
Dead man mode
Digital display
Dimensions of the locomotive.
Master Controller
MEMOTEL
Multiple operation
Multiple unit
Neutral section
Oil circuits
Oil pumps
Operating concept
Outside connections
Outside controls
Ovelview subsystems
Pantograph
- raising of
- lower of
Parking brake
Pneumatic brake systems
Pneumatic panel
- back face of
- front of
Protection
- of converter
- of battery
- of traction motors
- of auxiliary converters (BUR)
- of line converter
- of oil pumps
- of transformer
- of hotel load
Protection concept
Protective measures
Push/Pull Diagram
Reciprocal monitoring of the processors
Redundancy
Regenerative brake
Resetting the status of the locomotive
Reverser
Roof layout
Safety (Automatic Vigilance Control)
Safety systems
Sanding
Scavenge blowers
Screen structure
Shutting down the loco
Sight glasses
Single phase auxiliary circuit
Simulation mode
Software
-faults of
7 ILLUSTRATIONS
Fig. 2.1 Dimensions of the locomotive
Fig. 2.2 Layout of the locomotive
Fig. 2.3 Roof layout
Fig. 2.4 Underframe layout
Fig. 2.5 Bogie layout
Fig. 2.6 Detailed layout of machine room
Fig. 2.7 Overview driver's cab
Fig. 2.8 Tractive effodspeed-diagram
Fig. 2.9 PushIPull-Diagram
Fig. 3.1 Master Controller
Fig. 3.2 Main diagram pneumatic brake systems
Fig. 3.3 Automatic train brake
Fig. 3.4 Panel B
Fig. 3.5 Direct brake
Fig. 3.6 Pressure gauge
Fig. 3.7 Master Controller
Fig. 3.8 TEIBE meters
Fig. 3.9 Main diagram traction equipment
Fig. 3.10 Oil sight glass
Fig. 3.1 1 O v e ~ i e wconverter unit
Fig. 3.12 Main diagram traction converter
Fig. 3.13 Main diagram auxiliary circuit equipment
Fig. 3.14 Main diagram single phase 41511 10 V auxiliary circuit
Fig. 3.15 Scavenge blower
Fig. 3.16 Overview oil circuits
Fig. 3.17 Main diagram control electronics
Fig. 3.18 Fire alarm system
Fig. 3.1 9 Location of the fire extinguishers
' Fig. 3.20 Interlocking concept
Fig. 3.21 Switching hysteresis, main circuit breaker
Fig. 3.22 Diagram PbogielBOil Transformer
Fig. 3.23 Diagram PbogieIBOil Converter
Fig. 4.1 Overview driver's cab
Fig. 4.2 Operating concept
Fig. 4.3 Panel A
Fig. 4.4 Panel B
Fig. 4.5 Panel C
Fig. 4.6 Panel D
Fig. 4.7 Windshield wiperlwasher unit
Fig. 4.8 BlowerIHeating
Fig. 4.9 Detailed layout of light switches and sockets (driver's cab)
Fig. 4.10 Detailed layout of light switches (machine room)
Fig. 4.1 1 Auxiliary circuits, cubicle-1
P
~ - ~~ - ~ - -~~ ~~~ - --- --