Pulse Jet Filter Operation and Maintenance Manual: 312 SOUTH HWY. 73, PO BOX 398 FALLS CITY, NE 68355-0398 800-500-9777

Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

®

PULSE JET FILTER


OPERATION AND
MAINTENANCE
MANUAL

312 SOUTH HWY. 73, PO BOX 398


FALLS CITY, NE 68355-0398
800-500-9777

Revision Date 02/18/09


800-500-9777

Index
Introduction ............................................................................................................ 3
Safety Precautions ................................................................................................. 4
Definitions .............................................................................................................. 5
The Filtration Process ............................................................................................ 7
Solenoid and Diaphragm Valve .......................................................................... 9
Pulse Jet Theory of Operation .......................................................................... 10
E-86 Theory of Operation ................................................................................. 11
Filter Media Properties ......................................................................................... 12
Installation............................................................................................................ 15
Filter .................................................................................................................. 15
Compressed Air ................................................................................................ 15
Lubrication ........................................................................................................ 15
Top Access Bag and Cage Installation ............................................................. 15
Bottom Access Cartridge Installation ................................................................ 16
E86 Cartridge Installation.................................................................................. 17
Explosion Vents ................................................................................................ 18
Operation ............................................................................................................. 20
Maintenance ........................................................................................................ 21
Lubrication ........................................................................................................ 21
Timer Adjustments ............................................................................................ 21
Cleaning and Repair ......................................................................................... 21
Solenoid and Diaphragm Valves....................................................................... 21
Filter Elements .................................................................................................. 21
Rotary Valve (Airlock) ....................................................................................... 21
Screw Conveyor................................................................................................ 21
Troubleshooting Pulse Jet Filters......................................................................... 22
Magnehelic Gauge Operation .............................................................................. 27

NOTE: SCHEMATICS DRAWINGS LOCATED AT END OF MANUAL


800-500-9777

Introduction
AIRLANCO, along with all of our employees, thank you for selecting us to fulfill your needs for
environmental control equipment.

Pulse jet filters provide a mechanically simple, efficient, and economical means to separate
particulate from a gas stream. The absolute minimum of moving parts enhances the efficiency and
durability of the system. This manual will provide the information needed for an operator or
maintenance technician to understand the process of fabric filtration and the mechanical operation
of your AIRLANCO pulse jet filter. Understanding these basic principles will assure that this filter
will provide years of dependable service with minimum maintenance.

Receiving Your Equipment


A visual inspection of your equipment should be performed before it is removed from the truck.
Dents, scratches, and other damage should be noted and photographed. The structural integrity of
the filter housing will be adversely affected by dents. AIRLANCO should be notified of any structural
damage to your equipment immediately. Packing lists should be checked thoroughly and shortages
should also be reported to AIRLANCO. It is the purchaser’s responsibility to file shortage reports
and damage claims with the carrier and the supplier. The carrier is responsible for any damage to
the equipment while it is in transit.

3
FAX 402-245-5196 www.airlanco.com
800-500-9777

Safety Precautions
Warnings

• Do not operate this equipment without guards, access doors, and covers secured.
• Lock out power before servicing this equipment.
• This equipment is automatically controlled and will start at any time without warning.
• Do not enter access plenum while system fan is operating: airflow can pull service door closed
causing severe injury or entrapment.
• OSHA considers some filter housings a confined space. Follow procedures set forth by your
safety administrator.

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PERSONAL INJURY OR


PROPERTY DAMAGE!

READ AND UNDERSTAND SAFETY DECALS! (See below)

4
FAX 402-245-5196 www.airlanco.com
800-500-9777

Definitions

ACR Air to Cloth Ratio. The velocity that a gas moves through filter media.
Divide the gas volumetric flow rate (cfm) by the total area of filtration
media in (sq. ft.)

Agglomeration To gather into a mass.

Bag Filter element, sock. Usually supported by a wire cage.

Blinding Filter media becomes air impermeable due to moisture, temperature, or


other causes.

Cake Agglomeration of dust particles on the surface of a filter element.

Can Velocity Upward speed of air moving through a filter housing (fpm). Divide the
gas volumetric flow (cfm) by the cross sectional area of the baghouse
(sq. ft.)

Cartridge Filter Filter element consisting of a pleated filter media supported on a steel
or plastic skeletal frame.

CFM Cubic Feet per Minute – gas flow rate.

Clean Air Plenum Section of a baghouse directly above the tubesheet and filter bags or
cartridges.

Dew Point The temperature at which water vapor in a gas will condense into a
liquid state.

Filter Cake The accumulation of dust on a filter element before cleaning. This cake
assists in the filtration of dust.

Filter Element Refers to a filter bag or cartridge.

Header The pressurized reservoir that contains the compressed air supply for
pulsing.

Inch of Water A unit of pressure equal to the pressure exerted by a column of water
one inch in height at a standard temperature. 27.7 in. wg. = 1psi.

Interstitial Velocity The apparent velocity of a gas as it passes through the filter element
matrix. It is found by dividing the gas flow rate (cfm) by the cross
sectional area of the filter housing less the area occupied by the filter
elements.

Pressure Drop The resistance of flow of a fluid between two points.

Pulse Duration The length of time a cleaning pulse lasts.

Pulse Frequency The time between pulses in a baghouse cleaning system.

Pulse Jet Generic name given to all pulsing dust collectors.

5
FAX 402-245-5196 www.airlanco.com
800-500-9777

Purge Pipe Pipe with holes in it that extends into a filter clean air plenum and
delivers cleaning air from the header to the filter elements.

Re-entrainment The phenomenon whereby dust is collected from the air stream and
then is returned to the air stream. Occurs when dust is pulsed from a
filter element and then caught by an upward moving air stream.

Seeding The application of a relatively coarse, dry dust to a filter element before
start-up to provide an initial filter cake for immediate high efficiency and
to protect filter elements from blinding.

Tubesheet The steel plate from which the filter elements are suspended. Separates
the clean air and dirty sections of the baghouse.

Venturi Device used to increase the efficiency of a compressed air pulse.

6
FAX 402-245-5196 www.airlanco.com
800-500-9777

The Filtration Process


Filtration is a dry method of particulate collection in which an array of many individual targets is
assembled into a porous structure through which aerosol-laden gas is passed. In a filter, the
collection target is the filter media. Inertial, diffusional, electrostatic, and direct interception are the
primary forces that influence the collection of dry particulate on the filter media. As collection
proceeds, particles impinge upon previously collected particles and a deposit is built up which in
turn becomes the principal collection medium. This agglomeration of particles is referred to as a
“filter cake”. Filtration efficiency is not maximized until this filter cake has formed.

As the dust cake builds on the filter element surface, it becomes increasingly difficult for the gas to
pass through the element. A differential pressure gauge mounted on the filter measures the force
required to move air through the filter media. Normal pressure drop for a filter will fall in the range of
1 to 5 inches of water after the elements are broken in. The differential pressure reading will
increase as the elements get dirty. The dust cake must eventually be removed from the filter
element surface or airflow will fall to unacceptable levels.

Pulse jet filters are continuous self-cleaning units. A high-pressure blast of clean, dry compressed
air is injected into each filter element at periodic intervals. This air is stored in a reservoir called a
header. Several purge pipes are attached to the header and extend into the clean air plenum above
rows of filter bags or cartridges. Holes are drilled in the purge pipes directly above each of the filter
elements. Several elements are cleaned by one purge pipe. A solid state timer controls a solenoid
that opens a diaphragm valve allowing air to flow from the reservoir into the purge pipe and filter
element. The element experiences a shock wave while air is forced through it in a direction
opposite to the dirty air flow. A portion of the dust cake will fall away from the bag into the filter’s
hopper. It is normal for some of the dust to re-entrain itself onto the filter element.

High Temperature Precautions


Moisture is one of the most predominant causes for fabric filter failures. Care must be taken in
applications involving high humidity gas streams. Dryers and other combustion processes pose the
greatest danger for condensation in the filter. The filters and gas stream temperatures must be
o
maintained at 50 F above the dew point of the gas stream. Excursions near or below the dew point
of the gas stream will result in condensation of the gas on the baghouse and filter media. This
moisture will change the desired dust cake into an undesirable mud cake, which is difficult to
remove and may permanently damage the filter media. Corrosion is also intensified under these
conditions. Filters operating under high humidity conditions at any temperature should be protected
o
from gas condensation. This will require heating the filter to 50 F above the gas stream temperature
and insulation of the filter and ducting. Failure to take these precautions will result in unsatisfactory
performance of the equipment and possible catastrophic failure of the filter media.

Mechanical Operation
AIRLANCO Pulse Jet Filters are available with continuous or "on demand" cleaning control.
Cleaning duration and frequency are adjustable on the timer board. Dwyer Photohelic® pressure
switches can be used to control the cleaning cycle, which will conserve energy, reduce element
wear, and lower emissions by maintaining a set pressure drop across the filter elements. Filter bags
are made from felted fibers and are supported on a rigid wire cage. Filter cartridges are made from
pleated filter media and supported on skeletal frames. The composition of the fiber will vary
depending on the dust and gas chemistry, temperature, and gas stream humidity. Consult
AIRLANCO engineering (800-500-9777) for further information on the characteristics and types of
available filter media.

7
FAX 402-245-5196 www.airlanco.com
800-500-9777

THE FILTRATION PROCESS - Continued


Filter elements are suspended in the filter from the tubesheet in one of the following configurations:

Top access filter with bag and cage elements


A filter bag is inserted into the tubesheet and held in place with a snap band. A wire
cage is then inserted into the bag for support. The cage collar rests on top of the
tubesheet.

Bottom access filter with bag and cage elements


A wire cage is slipped into each bag for support. This bag and cage assembly is
attached to bag cups on the underside of the tubesheet with a clamp.

Top access filter with cartridge elements


Cartridges are self supporting. The cartridge is inserted through the top face of the
tubesheet. A flexible tab at the top of the cartridge snaps through the tubesheet,
locking the cartridge into place.

Bottom access filter with cartridge elements


Cartridges are self supporting. The cartridge is equipped with a flexible collar that
slips over the bag cup on the bottom side of the tubesheet. The cartridge is then
secured with a clamp.

Dust is collected on the surface of the filter media and eventually forms a cake. When a pulse of
compressed air is injected into the filter element, a shock wave is induced that causes the dust
cake to break away. Some of this air will pass through the filter media in a reverse direction and
further separate the dust cake from it. The name "Reverse Pulse Jet" is derived from this cleaning
method. Separated dust falls into the hopper where it is removed through an airlock or other airtight
device. The airlock prevents air from entering the hopper through its discharge. Leakage at the
hopper's discharge will cause re-entrainment of dust onto the filter elements, which could contribute
to high differential pressures.

The solid state programmable timer is available with 3 to 32 output connections. A potentiometer is
provided for the adjustment of the pulse duration and frequency. Duration of the pulse is factory set
at 50 milliseconds. Frequency of the pulse is factory set at 10 to 15 seconds.

8
FAX 402-245-5196 www.airlanco.com
800-500-9777

Solenoid and Diaphragm Valve

Cleaning air passes from the header through a large diaphragm valve, through the purge pipe, then
into the filter element. This diaphragm valve is controlled by the timer board with a normally closed
solenoid valve (see illustration below).

TIMER BOARD SOLENOID VALVE


ENCLOSURE ENCLOSURE

VENT TO ATMOSPHERE

DIAPHRAGM VALVE OPEN

AIR TO PURGE PIPE

HEADER
AIR FLOW

FILTER ELEMENT

9
FAX 402-245-5196 www.airlanco.com
800-500-9777

Pulse Jet Theory of Operation


(BAG AND CAGE PULSE JET FILTER)

TIMER BOARD PURGE CLEAN AIR


SOLENOID VALVE ENCLOSURE PIPE PLENUM
ENCLOSURE
CLEAN AIR
EXHAUST
3
SEQUENCE OF OPERATION
4 5
7
1 Dust laden air or gas enters the dust
DIAPHRAGM
VALVE collector through the inlet.
COMPRESSED AIR
HEADER TUBE SHEET 2 Air passes through the filter media while
solids are retained on the media's surface.
MAGNEHELIC®
GAUGE
3 A signal from the timer actuates the opening
FILTER ELEMENT of the normally closed solenoid valve.

4 Opening of the solenoid valve releases


NO-TOOL the air pressure in the tube connecting
ACCESS DOOR DIRTY AIR
HOUSING the solenoid to the diaphragm valve, causing
the valve to open.
5 A momentary pulse of compressed air flows from
the air header down the purge pipe and out into each
filter bag. This momentary pulse takes all bags in
one row off line through pressure reversal.
DIRTY AIR
INLET 6 Solids are released to fall into the filter
hopper or bin.
6
2 7 Filtered air exits through the clean air
1
HOPPER plenum exhaust.

AIRLOCK

10
FAX 402-245-5196 www.airlanco.com
800-500-9777

E-86 Theory of Operation


(CARTRIDGE PULSE JET FILTER)

DIRTY AIR SEQUENCE OF OPERATION


TUBE SHEET
INLET
CLEAN AIR
EXHAUST Dust laden air or gas enters the
CLEAN AIR 1
1 PLENUM dust collector through the inlet.
2
DIRTY AIR 7 5 Air passes through the filter media
2
HOUSING while solids are retained on the
PURGE media's surface.
PIPE
CARTRIDGE
3
A signal from the timer actuates
MAGNEHELIC®
GAUGE the opening of the normally close
solenoid valve.
3
Opening of the solenoid valve
SOLENOID AND 4
TIMER BOARD releases the air pressure in the
6
ENCLOSURES tube connecting the solenoid to
the diaphragm valve causing the
valve to open.
4
HOPPER
DIAPHRAGM VALVE A momentary pulse of compressed
5
COMPRESSED AIR air flows from the air header down
HEADER the purge pipe and out into each
filter cartridge. This momentary
pulse takes all cartridges in one
row off line through pressure
AIRLOCK
reversal.

6
Solids are released to fall into the
filter hopper or bin.

Filtered air exits through the clean air


7
plenum exhaust.

11
FAX 402-245-5196 www.airlanco.com
800-500-9777

Filter Media Properties


Filter media is manufactured from various materials, which provide different beneficial
characteristics. Below is a Fabric Selection chart, which summarizes some of the properties of
common fabric materials.

STRENGTH &
RESISTANCE

RESISTANCE

RESISTANCE

RESISTANCE

PROPERTIES
FILTRATION

OPERATING
ABRASION

RELATIVE
SOLVENT

TEMP °F
ALKALI

FLAME

COST
ACID

MATERIAL

Polypropylene E E E E P G 1 180
Acrylic G F G G P G 2 260
Polyester G G G E G E 1 275
Ryton E E E G E V 6 375
Nomex F G V G E E 4 425
Teflon E E E G E F 8 450
Fiberglass E F E P E F 3 500
P-84 V F V G E E 5 500

P = Poor, F = Fair, G = Good, V = Very good, E = Excellent

Polypropylene
This synthetic is available in both continuous filament and staple fiber form and is produced as
either a felt or woven material. Its major limitation is its low maximum continuous operating
temperature of 180°F (88°C). Oxidizing agents, copper, and related salts damage polypropylene.
Its primary benefit is that it is non-hygroscopic (does not chemically react with water). It exhibits
great resistance to static build-up and abrasion, and provides a slick surface for good dust cake
release during bag cleaning. Polypropylene is widely used in the food, detergent, chemical
processing, pharmaceutical, and tobacco industries.

Acrylic
These synthetic fibers offer good hydrolytic resistance over a limited temperature range, 260°F
(127°C) continuous, 275°F (135°C) surge. The homopolymer versions, such as Draylon T®
produced by Farbenfabriken Bayer AG, are normally recommended. Acrylic fibers are used in the
manufacture of ferrous and nonferrous metals, carbon black, cement, lime, fertilizers, and following
spray-dryers in coal-fired burners. They are also used extensively in wet-filtration applications.

Polyester
Today, polyesters are among the most widely used fabrics for general applications below 275°F
(135°C), their maximum continuous-use temperature. Their maximum surge temperature is about
300°F (149°C). Polyester fibers are produced in both filament and staple form and are available in
both woven and felted fabrics. The primary damaging agents are water (hydrolysis) and
concentrated sulfuric, nitric, and carbolic acids. They have good resistance to weak alkalies and fair
resistance to strong alkalies at low temperatures. They have good resistance to most oxidizing
agents and excellent resistance to most organic solvents.

12
FAX 402-245-5196 www.airlanco.com
800-500-9777

Ryton
This is a relatively new synthetic fiber with a moderate temperature range, 375°F (190°C)
continuous, 450°F, (232°C) surge. It will hydrolyze, but only at temperatures above 375°F. It has
excellent resistance to both acids and alkalies, which makes it very useful in combustion-control
applications. Its early applications have been on industrial coal-fired boilers, waste-to-energy
incineration (with and without spray dryers), titanium dioxide, and installations where Nomex does
not perform well due to chemical or hydrolytic attack.

Nomex
This is a commonly used fiber for applications in the 275-400°F (135-204°C) range. It is produced in
both filament and staple fiber form and is available as both woven and felted fabrics. It has
excellent thermal stability, shrinking less than 1% at 350°F (177°C). The fiber is flame resistant, but
when impregnated with combustible dusts, will support combustion that will melt and destroy the
o
fabric. Nomex will begin to hydrolyze at 375 F (190°C) when the relative humidity is 10% or greater.
Hydrolysis changes the normal white or gray fabric to a red-brown color. The presence of acids will
catalyze the hydrolysis process. Unacceptably short bag life will result where sulfur oxides (SOx)
and moisture are present and frequent dew point excursions occur, such as in coal-fired boilers.
Some acid-retardant finishes have been developed for Nomex, but have been found to improve bag
life by no more than 50%, leaving most bag life cycles unacceptably short.

®
Teflon (PTFE)
Teflon® is unique among synthetics in its ability to resist chemical attack across the entire pH range
throughout its operating temperature range of 450°F (232°C) continuous, to 500°F (260°C) surge.
This fluorocarbon fiber is non-adhesive, has zero moisture absorption, and is unaffected by mildew
or ultraviolet light. The primary shortcomings of Teflon® are its high cost and relatively poor
abrasion resistance. However, the higher cost can often be justified through longer bag life in
extremely corrosive atmospheres. Felted Teflon® is also produced in combination with staple glass
fibers and marketed by DuPont as Tefaire®. This combination produces some improved filtration
and flow characteristics. Applications of Teflon® include coal-fired boilers, waste-to-energy
incinerators, carbon black, titanium dioxide, primary and secondary smelting operations, and
chemical processing.

Fiberglass
Most fiberglass fabrics are woven from minute 0.00015 inch (.0038 mm) filaments. Many variations
of yarn construction, fabric weaves, and fabric finishes are available. It is also produced in a felted
form. Fiberglass has the highest operating temperature range available in conventional fabrics:
500°F (260°C) continuous, 550°F (288°C) surge. Above 500°F (260° C), the fiberglass itself is not
directly damaged, but the finish which provides yarn-to-yarn lubrication begins to vaporize, resulting
in accelerated mechanical wear of the glass fibers. Fiberglass is noncombustible, has zero moisture
absorption (cannot hydrolyze), has excellent dimensional stability, and has reasonably good
strength characteristics. Woven glass fabrics have high tensile strength characteristics but relatively
low flex strength, especially in the fill (circumference) direction of the bag, and low abrasion
resistance. Care must be taken to minimize flexing and rubbing. Fiberglass fabrics have relatively
good resistance to acids, but impurities in the glass fibers are attacked by hydrofluoric,
concentrated sulfuric, and hot phosphoric acids. They also have poor resistance to hot solutions of
weak alkalies, acid anhydrides, and metallic oxides. For these reasons, glass fabrics should not be
operated below the acid dew point. Fiberglass fabrics are used extensively with coal-fired boilers
and high temperature metals applications.

P-84
P-84 is an aromatic polymer fiber produced in felt form only. The unique shape of the fiber
produces improved capture efficiency characteristics. This fabric is specified at 500°F. Composites
are available that take advantage of the superior filtration characteristics of P-84 while reducing its
cost. Any of the previous felted materials can be combined with P-84 to produce a fabric composite
that exhibits the characteristics of both materials.

13
FAX 402-245-5196 www.airlanco.com
800-500-9777

Media Treatments

Surface Treatment of Filtration Media


Various types of surface treatment are available to enhance the filter media performance.
Discussion of these treatments and their benefits are beyond the scope of this manual. Please
consult AIRLANCO at 800-500-9777 for further information on this subject.

Pre-coating Filter Media


Fine, moist, or adhesive dusts will contribute to premature blinding of filter media. Pre-coating of the
filter media with a layer of an inert dust of known particle size distribution, such as calcium
carbonate (CaCO3), can minimize problems associated with these types of dusts. Consult
AIRLANCO at 800-500-9777 for information and recommendations regarding the pre-coating of
your filter bags.

14
FAX 402-245-5196 www.airlanco.com
Installation 800-500-9777
Filter
AIRLANCO pulse jet filters, depending on size, will be shipped either as complete units or in
sections. All units require the installation of the filter elements along with connections to 110 VAC
and compressed air. Larger filters are shipped in major sub assemblies that are bolted together at
the job site and set on the foundation. Refer to the general arrangement drawing for details on the
number of sub-assemblies and the extent of assembly required for your unit.

Compressed Air
AIRLANCO pulse jet filters having bags and cages require 90-100 psi clean (5 micron filter), dry
(dew point -40°F), compressed air. Cartridge filters require 60 psi max. This supply is connected to
the filter header. The general arrangement drawing will note the location and pipe size for the
compressed air feed.

Lubrication
There are no lubrication requirements on a pulse jet filter. However, discharge devices such as a
rotary airlock will require lubrication. Refer to the specific manuals for lubrication of this equipment.

Top Access Bag and Cage Installation

Step 1 CAGE TOP

Lower the bottom of the bag through the hole in TUBESHEET


TUBESHEET

the tubesheet.
STAINLESS STEEL SNAP BAND
Step 2
Fold the snap band (bag top) to insert it into the
tubesheet hole.
GROUND WIRE PLACED
Step 3 BETWEEN BAG CUFF
AND TUBESHEET
Fit the groove of the snap band to the edge of
the tubesheet and allow the band to snap into
place.
Step 4
Check the fit of the snap band. It should fit
securely all around with no wrinkles in the snap
band. The top of the bag should be above the WIRE CAGE
tubesheet approximately 3/8”.
Step 5
Slide the cage into the bag until it rests on the tubesheet.

Optional Grounding Strip


If the bags are equipped with a grounding strip, fold the wire over the top of the bag and down its
side prior to fitting in the tubesheet. The wire should be between the bag cuff and the tubesheet as
shown in the illustration.
15
FAX 402-245-5196 www.airlanco.com
Bottom Access Cartridge Installation 800-500-9777

Step 1
BAG CUP
Before entering the filter, slide the
GROOVE
clamp band over the rubber collar
at the top end of the cartridge.
CLAMP BAND

Step 2
LIP

Enter the filter and fit the cartridge


COLLAR
collar over the bag cup.

Step 3 FILTER MEDIA

Move the cartridge up and down


over the bag cup until the raised
lip inside the cartridge collar snaps
into the groove in the bag cup.

Step 4

Tighten clamp until cartridge cannot


be turned by hand.

Bottom Access Bag and Cage Installation

Step 1
BAG CUP

Before entering filter housing, slide


cage into bag. Align seam in bag
with split in cage collar. CLAMP BAND

Step 2
SPLIT TOP
CAGE COLLAR
Fold top 3" of bag and ground strip
(if supplied) into cage.

Step 3 SUPPORT CAGE

Slide clamp band over bag and


cage, aligning it above the
cage collar ridge. FILTER BAG

Step 4

Enter filter housing with bag,


cage, and clamp band assembly.
Slide the cage collar over the bag
cup until locking ridges are
engaged. Position clamp screw
90° from bag seam. Tighten
clamp band until bag and cage
assembly cannot be turned by hand.

16
FAX 402-245-5196 www.airlanco.com
800-500-9777

E86 Cartridge Installation

OUTSIDE
CARTRIDGE OPEN END
WING NUTS PLATE COLLAR

CLOSED END GUIDE ROD

WELDED
STUDS

Check the sealing gaskets on the cartridge before installation. They should be secure on both ends.
Loose gaskets may be re-attached with silicone caulk. Minor damage may be repaired with silicone
caulk. Major damage will require replacement of the gasket. Contact AIRLANCO (800-500-9777)
for replacement parts.

Insert the cartridge into the cartridge plate hole. Avoid contact between pleated media and edges,
as this could damage the media. Align the flange holes with the studs in the cartridge plate. Tighten
the wing nuts by hand until the flange touches the cartridge plate, fully compressing the gasket. Do
not use tools.

17
FAX 402-245-5196 www.airlanco.com
R INSTALLATION INSTRUCTIONS
Explosion Vents
CORPORATION
06-308

WARNING
• Read these instructions carefully and completely
before attempting to unpack, install or service the
explosion vent.
• Handle the explosion vent with extreme care. DO
NOT bend, poke, or in any way distort the explosion
vent.
• Do not locate vent assembly where personnel are
exposed to the vent or the area above or in front of the
vent, as they may be injured by the release of pressure,
flame, noise, particles, and/or process material.
• Locate the explosion vent so that the discharge does
not ignite other combustibles, resulting in an ensuing
fire or secondary explosion.
• Interfacing equipment and/or machinery must also be
protected.
• Flow arrows on round explosion vent tags, or explosion
vent tag for square and rectangular vents must be
directed to the atmospheric side of the process.
Provisions shall be made to prevent personnel from
standing or walking on vents, as they risk falling
through. 4. Two personnel are recommended for handling of all
• The vent opening is to be left free and clear. Nothing, vents larger than 24” x 30” (600 x 1000 mm)
i.e. goods or products, is allowed to obstruct the vent (rectangular) and 30” (800 mm) (round) or larger.
area as this will decrease vent efficiency. 5. CV-SF vents require vent frames with back-up bars to
• Install the enclosed DANGER sign in a conspicuous properly function (consult Fike for design
location near the zone of potential danger. requirements).

GENERAL INSTALLATION
An explosion vent is a pressure relief device, designed to WARNING: The vent opening should be left free and
give an instantaneous opening at a predetermined clear. Do not insulate any part of the explosion
pressure. Its purpose is to protect the equipment from vent or frame without consulting Fike.
excessive pressures caused by dust or gas deflagrations.
Important: When explosion vents are installed
INSPECTION/PREPARATION horizontally, the use of drainage/weep holes in the
WARNING: Always handle the explosion vent with holddown frame is required.
extreme caution. Handle the explosion vent by its
edges only. Damage to the functional area (center) 1. Use base/inlet of explosion vent frame as a template
or seat area of the explosion vent may adversely to indicate placement of explosion vent on the vessel
affect the performance of the explosion vent. Read or duct to be protected.
the explosion vent tag completely before installing 2. Cut the vessel or duct opening to the marked size.
to confirm that the size and type are correct for your The marked size should match the size identified on
system. the vent tag.
3. Weld or bolt the inlet angle frame to the vessel or
1. Carefully remove the explosion vent from its packaging duct.
container.
2. Inspect the explosion vent for damage. Important: The explosion vent frame must be installed
3. If foreign material is present, carefully clean the such that the seat area is flat and bolt holes remain
explosion vent with a solvent that is compatible with perpendicular (square and rectangular vent frames) or
your media. circular (round vent frames).
India Pvt. Ltd., +91-20-5453336, sameerp@pn2.vsnl.net.in | Fike Japan Corp., +81-3-3595-1291, office@fikejapan.co.jp | Fike Asia Pacific, Malaysia, +60 (3) 7859-1462, fikeap@fike.com
4. If sealing is a particular concern due to the nature of

Canada Inc., 905-681-3100, fikecanada@fike.com | Fike Europe B.v.b.a., Belgium, +32-14-210031, fike-europe@fike.com | Fike Latina Ldta, Brasil, +55-11-45251277,vendas@fike.com.br
the process, apply a process compatible silicone
sealant or gasket to provide seal between explosion
vent and inlet frame.
5. If using a gasket, select a gasket material that is
compatible with the process, with a suggested
thickness of 1/16" (1.5 mm) maximum. The gasket

United Kingdon, +44-1-622-677081, sales@fike.co.uk | Fike France, +33-1-30-31-31-32, Fike.france@fike-france.fr | Fike Deutschland, +49-621-32-1670, info@fike.de |
is to have the same inside diameter and outside
diameter as the explosion vent frame.
6. Install the explosion vent and outlet flange aligning
the bolt holes. DO NOT force the explosion vent hole
alignment.
7. Apply light oil to the threads and install the nuts and
bolts hand tight.
8. Torque each bolt to the value identified on the explosion
vent tag.

Caution: The torque values should not be exceeded as


this may cause failure of the bolt and/or damage to the
vent.

BURST INDICATOR
The explosion vents can have as an option an integrated
electric burst indicator designed for intrinsically safe
service. Refer to Burst Indicator Instructions / Drawing for
electrical and dimensional specifications.

Caution: Unacceptably high voltage or currents will


permanently damage the electrical system and the use
of a non approved intrinsically safe power supply may even
be the eventual ignition source of a dust or gas explosion.

Italia +39-02-2952-4166, webmaster@fike.it | Fike Iberica +34-93-6000-800, fike@fike.es


All burst indicators must be installed in an intrinsically
safe circuit which conforms to the applicable national
standard.

WARNING: Do not bend the electrical cable at any


angle at a distance of less than 8 inch (20cm) from
the mechanical bracing part and do not lift the
explosion vent by the electrical cable, as this may
damage the electrical circuit.

WARNING: The maximum torque values as


mentioned on the nameplate must not be exceeded
as this will permanently damage the electrical
circuit.
MAINTENANCE
The explosion vent is maintenance-free due to its basic
design and concept. Periodic visual inspections should
be performed in accordance to the operating parameters
and severity of service. All operational system parameters
should be observed as a standard maintenance practice.
The explosion vent must be replaced if they appear
damaged, corroded, or leaking.

Note: Severe service is defined as rapid changes in


pressure, high pressure, high temperature, or corrosive
process.
R

Fike Corporation World Headquarters • Blue Springs, Missouri U.S.A.


Phone 816 229-3405 • Fax 816 229-4615 • e-mail fmpsales@fike.com • www.fike.com
Fike
Fike
Fike

Fike

CORPORATION
P/N 06-308-1-2 Copyright  2004 by Fike Corporation. All rights reserved.
800-500-9777

Operation
Proper startup and shutdown procedures are very important in the successful operation of a bag
house filter. A typical ambient air dust collection system should follow this sequence of operation.

1. Start the dust removal system that transfers collected material from the filter
hopper. This could include rotary airlocks, pneumatic conveying equipment, etc.
This step is not applicable for Style II bin vent filters.

2. Start the bag house cleaning mechanism. Before starting additional equipment, let
the cleaning mechanism run long enough to allow the filter temperature and
humidity to stabilize with ambient conditions and to remove any material that may
have been left from the previous day’s operation. This is most important in high
humidity climates.

3. Start the main system fan.

4. Start the operation or process where dust is being collected.

Reverse the order of the above sequence to shut down the bag house.

1. Shut down the operation or process where dust is being collected.

2. Shut down the main system fan.

3. Shut down the bag house cleaning mechanism after allowing the collected material
to be discharged from the collector.

4. Shut down the dust removal system that transfers material from the filter hopper
(not applicable for Style II bin vent filters).

20
FAX 402-245-5196 www.airlanco.com
800-500-9777

Maintenance
Very little maintenance is required to achieve maximum efficiency and life from your AIRLANCO
pulse jet filter. The following items should be periodically serviced.

Lubrication
Pulse jet filters have no lubrication requirements.

Timer Adjustments
Do not change the timer adjustments until the filter has had several weeks to stabilize. This break-in
period is required for the filter media to develop a stable dust cake. After the break-in period, the
pulse interval can be increased in order to conserve energy and compressed air. Increase the pulse
interval by adjusting the potentiometer clearly marked on the timer board. Adjust in 5 second
increments allowing 24 hrs of operation between adjustments. Observe the differential pressure of
the unit after 24 hrs. The pulse interval can be extended until an increase in differential pressure is
observed in the filter. Do not change the pulse duration. It should be 40 to 50 milliseconds for
best results.

Cleaning and Repair


The external portion of this unit should be treated as any other metal surface that is subject to
corrosion. Periodic cleaning and painting when required.

Dust may enter the clean air plenum through a leaking or broken filter element. Remove
accumulated dust from clean air plenum and replace filter element immediately. Dust in the clean
air side of a filter element will reduce the life and performance of the element.

Solenoid and Diaphragm Valves


The solenoid and diaphragm valves may require periodic maintenance depending on the quality of
the compressed air supplied to the unit.

Filter Elements
Filter elements do not require any periodic maintenance. However, at some point the elements will
require replacement. This will be indicated by persistent high differential pressure across the
elements. Many factors affect the life of filter elements. Refer to the section on troubleshooting if
low element life or persistent wear problems are evident.

Rotary Valve (Airlock)


Refer to airlock operation and maintenance manual.

Screw Conveyor
The roller chain drive should be kept tight enough so that the chain cannot "climb the sprocket" and
should be oiled lightly once per month. The auger bearings have been factory pre-lubricated with
high quality grease and for normal conditions of service require no further lubrication. Periodic
lubrication may be advisable when service is abnormal with respect to speed, temperature,
exposure to moisture, dirt, or corrosive chemicals, or where extremely long life is required. Remove
pipe plug and replace with a standard grease fitting to lubricate.

21
FAX 402-245-5196 www.airlanco.com
800-500-9777

Troubleshooting Pulse Jet Filters

The pulse jet is a continuous self-cleaning filter.


A jet of high-pressure air from a compressed air
header is directed into each bag at periodic
intervals. Air is distributed to each row of filter
bags through a diaphragm valve and blow tube
equipped with drilled nozzles. The high-pressure
reverse flow of air momentarily stops the normal
flow and creates a shock wave that knocks the
dust from each bag. A percentage of the dust
cake will fall away from the bag into the filter
hopper. It is normal for some of the dust to re-
entrain on to the bag.

Troubleshooting the pulse jet is a straight


forward process, but does require some
preliminary information to simplify the process.
Complete the worksheet on the following page
before calling AIRLANCO (800-500-9777) for
service.

22
FAX 402-245-5196 www.airlanco.com
800-500-9777

Pulse Jet Troubleshooting Worksheet

Customer Name

Location

Contact Name

Phone Cell Phone Fax

Email Address

Filter Model Serial #

How long has the filter been in service?

When did the problem start?

Please provide a complete description of the problem and a detailed description of the system layout.

Are the airlock and discharge auger operating, and in the correct rotation?

Airlock Model # Airlock Serial #

Is the timer board energized?

Control Voltage 110V 220V 24VDC Other

Does the filter have an adequate supply of compressed air, and is it turned on?

Is the compressed air supply regulated to 90-100 PSIG for bags or to 60 PSIG for cartridges?

Are any bags, cartridges, and/or blank-out plugs missing?

Check the tubing between the solenoid valves and diaphracm valves for cracks or splits.

23
FAX 402-245-5196 www.airlanco.com
800-500-9777

Problem: High differential pressure across tubesheet


(Possible causes with solutions)

Bad Gauge
Check the gauge by blowing into it. Do not use compressed air that could damage the gauge.
Replace the gauge if the needle does not move.

Leaking Gauge Lines


Check the full length of both lines for cracks, splits or breaks. Replace both lines with new tubing.
Copper tubing may be recommended if the environment is harsh. Clogged gauge lines will give the
same result. Check the small filter, located on the inside of the baghouse just below the tubesheet.
Clean or replace it as required.

Low Header Pressure


Pulse jet filters require 90 – 100 PSIG for bags and 60 PSIG for cartridges. Ensure that the pipe to
the filter is of adequate diameter for the length of the run. Check for leaks in the supply line and
other equipment. Check the filter diaphragm and solenoid valves for correct operation. A ruptured
diaphragm valve or a stuck solenoid valve will drain a compressor. A cracked or broken line from
the solenoid valve to the diaphragm valve will have the same effect.

Timer board malfunction


Most timers in use today are solid state. They either work or they do not. Timers are equipped with
a slow blow fuse to protect from power surges. If a timer does not function, replace the fuse.
Replace the timer board if fuse replacement doesn’t correct the problem.

Timer board adjustments


The filter cleaning pulse will be at equal and regular intervals when the timer board is operating
correctly. Pulse frequency (the time between cleaning pulses) is factory set at 15 seconds. It may
be adjusted to optimize cleaning efficiency and compressed air use. Allow 24 hours of operation
between adjustments to permit the filter to stabilize. Over cleaning will reduce filter element life
expectancy and use excessive compressed air. Pulse duration (length of cleaning pulse) is factory
set at 40 to 50 milliseconds. Typically, this setting should be maintained for best cleaning and air
use.

Media Blinding
Excessive moisture is the most common cause of blinding. High humidity, condensation, and leaks
in the duct are typical sources. In high humidity areas, the filter should be operated under no load
until air temperatures stabilize. The air stream temperature crossing the dew point, either from
ambient high humidity or from process moisture, causes condensation. It may be necessary to pre-
heat and insulate the filter to avoid dew point issues. Duct leaks are found by inspection and routine
preventive maintenance.

Interstitial or “Can” Velocity too high


Check the system airflow with the original design values. The fan speed may have been increased,
duct layout may have been modified, or other changes made in the system may have reduced static
pressure. Any increase in CFM will increase interstitial velocity and tend to “float” dust in the filter. A
change in the process could result in smaller particle sizes in the dust, which would have the same
effect as increased CFM. In either case, it may be necessary to install a larger filter or reduce
airflow to the original design.

Bag Fit on Cages


Check the bag fit on cages with a pinch test. You should be able to pinch at least ½” of fabric at any
position. Bags that are too tight will not allow the bag to “pop”, knocking the dust cake loose when
cleaned. Replace the bags if they are too tight.

24
FAX 402-245-5196 www.airlanco.com
800-500-9777

Rotary Valve (Airlock) Leakage


Air leakage through a worn out valve rotor into the filter hopper will re-entrain dust onto the filter
bags. Air leakage will also keep the collected dust from properly feeding out of the hopper,
potentially plugging the filter. Replace the airlock.

High Dust Load


Filters can handle very high dust loads under normal conditions when properly sized. Has
something changed in the process, to either increase material flow or to decrease particle size?
Compare current operating conditions to the original design. It may be necessary to install a larger
filter or reduce airflow to the original design.

Problem: Low differential pressure across the tubesheet


Bad Gauge
Check the gauge by blowing into it. Do not use compressed air that could damage the gauge.
Replace the gauge if the needle does not move.

Leaking Gauge Lines


Check the full length of both lines for cracks, splits or breaks. Replace both lines with new tubing.
Copper tubing may be recommended if the environment is harsh. Clogged gauge lines will give the
same result. Check the small filter in the line. It is located on the inside of the baghouse just below
the tubesheet. Clean or replace it as required.

Holes in Bags
Replace all bags. See section on poor bag life.

System Air Volume too low


Check the duct system for plugs and closed blast gates. Check the main system fan for correct
RPM or a closed damper.

Bag & Cage Installation


Look for dust in the clean air plenum or discharging from the system fan. Bags may be missing or
may not be properly installed in the tubesheet. Refer to the instruction manual for correct
installation.

Blank-Out Plugs
Plugs may be missing or improperly installed. Refer to the instruction manual for correct installation.

Problem: Dust in exhaust air


Start Up Period
Allow the filter to run for 48 to 96 hours to establish a dust cake. Some applications will require
“seeding” or pre-coating the bags with an appropriate material to establish a cake.

Holes in Bags
Replace all bags. See section on poor bag life.

Bag & Cage Installation


Look for dust in the clean air plenum or discharging from the system fan. Bags may be missing or
may not be properly installed in the tubesheet. Refer to the instruction manual for correct
installation.

Blank-Out Plugs
Plugs may be missing or improperly installed. Refer to the instruction manual for correct installation.
25
FAX 402-245-5196 www.airlanco.com
800-500-9777
Problem: Poor Bag Life
Abrasion
Provide an inlet transition to make use of the full inlet area. Stubbing a duct onto a plate on the inlet
will result in high velocity. Do not mount a duct elbow directly on the filter inlet, as this will cause
eccentric loading and potentially damaging airflows.

Damaged Cages
Filter cages that are bent, have broken wires, or have corrosion will cause premature failure of the
filter bags. Inspect and replace as soon as possible. Corrosion problems may require coated or
stainless steel cages.

High Air Volumes


High air to cloth ratios can shorten filter bag life. Compare current operating conditions to the
original design.

Media Blinding
Excessive moisture is the most common cause of blinding. High humidity, condensation and leaks
in the duct are typical sources. In high humidity areas, the filter should be operated under no load
until air temperatures stabilize. The air stream temperature crossing the dew point, either from
ambient high humidity or from process moisture, causes condensation. It may be necessary to pre-
heat and insulate the filter to avoid dew point issues. Duct leaks are found by inspection and routine
preventive maintenance.

Incorrect Filter Media


High temperatures, chemical content, and dust composition will affect filter media life. Consult
AIRLANCO (800-500-9777) for alternative media selections.

Problem: Hopper Plugging


Cleaning System malfunction
Refer to the section on High Differential Pressure.

Rotary Valve (Airlock) Leakage


Air leakage through a worn out valve rotor into the filter hopper will re-entrain dust onto the filter
bags. Air leakage will also keep the collected dust from properly feeding out of the hopper,
potentially plugging the filter. Replace the airlock.

Airlock/Auger Speed
If your filter is equipped with an auger/airlock combination slave drive and operating conditions have
changed, the airlock/auger speed may need to be increased.

The above is intended as a quick reference for common problems that may be
encountered with a pulse jet dust filter. If you are experiencing any difficulties that
are not covered here or have any questions concerning your AIRLANCO filter,
complete the worksheet on page 21 and contact AIRLANCO at www.airlanco.com
or at 800-500-9777.

26
FAX 402-245-5196 www.airlanco.com
800-500-9777

Magnehelic Gauge Operation

TOP PLENUM

1/4" TUBING
CLEAN AIR
EXHAUST TUBESHEET
HIGH PRESSURE
DIRTY AIR HOUSING
(BAG HOUSE)

4 6
BAGHOUSE 2 8

10
0

MAGNEHELIC
FILTER BAGS
OR CARTRIDGES

LOW PRESSURE
CLEAN AIR
DISCHARGE CONE (TOP PLENUM)
DIRTY AIR
ZERO SET
INLET

FILTERED MATERIAL
DISCHARGE

The Magnehelic® gauge is used to measure the differential pressure between the clean gas side
(top plenum) and the dirty gas side of the baghouse. It measures the force required to pass air
through the filter media.

Normal pressure drop for a filter will fall in the range of 1 to 5 inches of water after the elements
establish a dust cake. The differential pressure reading will increase as the elements get dirty.
Eventually, the dust cake must be removed from the filter element surface or air flow will fall to
unacceptable levels.

27
FAX 402-245-5196 www.airlanco.com
CONTROL SWITCH
CONTACTS SOLID STATE
TIMER BOARD
EXTERNAL PRESSURE
SWITCH CONTACTS OFF & ON TIME
HIGH LOW
ADJUSTMENTS
NC NC NC
(FACTORY SET)
NO NO NO NO JUMPERS
COM COM

120 VAC

L1 L2
PROGRAM WIRE

3A FUSE
PHOTOHELIC SWITCH
3000 SERIES STYLE HH
SOLENOID
C 1 2 3 4 VALVES

PREWIRED AT FACTORY

L1 120 VAC L2
SWITCH LOGIC

CONTROL CONTACTS CLOSE WHEN HIGH SET POINT IS REACHED


AND FILTER PULSING TIMER IS ACTIVATED.
CONTACTS REMAIN CLOSED UNTIL LOW SET POINT IS CROSSED. A 4-21-97 RELEASED TO PRODUCTION MW
CONTROL CONTACTS RESET TO OPEN WHEN LOW SETPOINT IS REACHED
AND FILTER PULSING TIMER IS DE-ACTIVATED. REV DATE DESCRIPTION BY
THIS DRAWING IS THE SOLE PROPERTY OF AIRLANCO (THE CO.) DWN. BY: MW
UNLESS OTHERWISE NOTED: AND SHALL NOT BE REPRODUCED, LOANED OR USED IN ANY MANNER FALLS CITY, NE
ALL DIMENSIONS ARE IN INCHES. WITHOUT THE EXPRESS PERMISSION OF THE CO. SCALE: NONE
TOLERANCES:
DECIMAL FRACTION OVERALL
AIRLANCO ELECTRICAL SCHEMATIC FOR JOB NO: DATE: 4-21-97
.XX +/- 0.03 +/- 1/16 <120 +/- 3/8 PHOTOHELIC "ON DEMAND" P/I: REVISION: A
.XXX +/- 0.005 >120 +/- 1
CONTROL OF TIMER CIRCUIT P/N: DWG: 10884
OPTIONAL EXTERNAL
CONTROL SWITCH
(LEAVE FACTORY-INSTALLED
JUMPER IN PLACE)

OFF & ON TIME ADJUSTMENTS


(FACTORY SET)

PROGRAM WIRE
3/4

3A FUSE C 1 2 3 4
L1
120 VAC (BY INSTALLER) L2

SOLENOID VALVES
(PREWIRED AT FACTORY)

A 1-23-97 RELEASED FOR INFORMATION MLH


REV DATE DESCRIPTION BY
THIS DRAWING IS THE SOLE PROPERTY OF AIRLANCO (THE CO.) DWN. BY: MLH
UNLESS OTHERWISE NOTED: AND SHALL NOT BE REPRODUCED, LOANED OR USED IN ANY MANNER FALLS CITY, NE
ALL DIMENSIONS ARE IN INCHES. WITHOUT THE EXPRESS PERMISSION OF THE CO. SCALE: NONE
TOLERANCES:
DECIMAL FRACTION OVERALL
AIRLANCO WIRING DIAGRAM FOR JOB NO: DATE: 1-23-97
.XX +/- 0.03 +/- 1/16 <120 +/- 3/8 TIMER BOARD P/I: REVISION: A
.XXX +/- 0.005 >120 +/- 1
P/N: DWG: 10835
OFF & ON TIME ADJUSTMENTS
(FACTORY SET)

PROGRAM WIRE

N.C.

3A FUSE
C 1 2
L1
N.O. 120 VAC (BY INSTALLER) L2
SOLENOID VALVES
LIMIT SWITCH (PREWIRED AT FACTORY)
SHOWN IN DOOR
OPEN POSITION
(PREWIRED AT FACTORY)

B 8-30-01 REVISED AND REDRAWN MLH


REV DATE DESCRIPTION BY
THIS DRAWING IS THE SOLE PROPERTY OF AIRLANCO (THE CO.) DWN. BY: MLH
UNLESS OTHERWISE NOTED: AND SHALL NOT BE REPRODUCED, LOANED OR USED IN ANY MANNER FALLS CITY, NE
ALL DIMENSIONS ARE IN INCHES. WITHOUT THE EXPRESS PERMISSION OF THE CO. SCALE: NONE
TOLERANCES:
DECIMAL FRACTION OVERALL
AIRLANCO WIRING DIAGRAM FOR JOB NO: DATE: 10-25-96
.XX +/- 0.03 +/- 1/16 <120 +/- 3/8 BAG DUMP STATION P/I: REVISION: B
.XXX +/- 0.005 >120 +/- 1
W/ LIMIT SWITCH P/N: DWG: 10809
LIMIT SWITCH BYPASS

TIMER BOARD
JUMPER

L1 L2 13
21
DOOR
LIMIT SWITCH
22 14

95 T1
T1 2 1 L1460VAC
NC T2
T2 4 3 L2460VAC
TO T3
FAN T3 6 5 L3460VAC

A2 A1

L2 120VAC L1 120VAC

WITH DOOR OPEN FAN STARTS, TIMER STOPS.


BYPASS SWITCH STOPS FAN FOR CARTRIDGE CHANGE.

A 3-11-02 RELEASED FOR PRODUCTION MDK


REV DATE DESCRIPTION BY
THIS DRAWING IS THE SOLE PROPERTY OF AIRLANCO (THE CO.) DWN. BY: MDK
UNLESS OTHERWISE NOTED: AND SHALL NOT BE REPRODUCED, LOANED OR USED IN ANY MANNER FALLS CITY, NE
ALL DIMENSIONS ARE IN INCHES. WITHOUT THE EXPRESS PERMISSION OF THE CO. SCALE: NONE
TOLERANCES:
DECIMAL FRACTION OVERALL
AIRLANCO WIRING DIAGRAM FOR BAG DUMP JOB NO: DATE: 3-11-02
.XX +/- 0.03 +/- 1/16 <120 +/- 3/8 STATION WITH DOOR LIMIT SWITCH P/I: REVISION: A
.XXX +/- 0.005 >120 +/- 1
& BYPASS P/N: DWG: 11835

You might also like