Di50-60e 5 Panel Meter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

DI-50E, DI-60E,

DI-60AE Tiger
Digital Panel Meter

A powerful, super-intelligent 5-digit modular panel meter with advanced software


features for monitoring, measurement, control, and communication applications in a 96x48 case

General Features Module Compatibility

• Modular construction with interchangeable input and ✔ TIGER FAMILY: More than 75 different Plug-in
output modules. I-Series Input Signal Conditioners are approved for
• Able to receive single and dual input signals from one of more Texmate’s Tiger Family of meters.
than 75 input signal conditioners. See www.texmate.com for an up to date listing.
• Optional output module that can support a relay module with up to
six relays; an analog output module with user selectable isolated Description
voltage (0-10 VDC) or isolated current (0-20 mA); and a serial out-
put module with either isolated RS-232, isolated RS-485, or non-
The Texmate Tiger is a super-intelligent digital panel meter with pro-
isolated TTL logic level serial output.
grammable logic and advanced digital signal processing capabilities.
• Auto-sensing high or optional low voltage AC / DC power supply.
Its innovative modular design creates a highly flexible meter able to
• Built-in 5 / 10 / 24 VDC sensor excitation voltage.
process almost any input signal type from one of more than 75 sin-
• Optional red or green, 7- or 15-segment, 0.56” high LEDs gle and dual input signal conditioner types. With relay, analog, and
• Easy to program using front panel buttons or PC software. serial communications output options available on an output module,
• Internal program safety lockout switch to prevent tampering. the meter becomes a powerful instrument for monitoring, measure-
• Provision for external LOCK, HOLD, and TEST switch. ment, control, and communication applications.
• Six programmable setpoints with front panel annunciator LEDs. An auto-sensing high or optional low voltage AC / DC power supply
• Smart digital filtering and input averaging. circuit means the meter can be powered from almost any power
• Optional NEMA-4 front cover. supply source. User selectable 5, 10, or 24 VDC excitation voltages
• Seven-level display and annunciator brightness control. are available to power the input module.

• Can perform dual channel tasks. The meter uses smart digital filtering and input averaging. The
• Can be customized for O.E.M. applications. meter’s resident software is designed to allow maximum user flexi-
bility through logical menus. All programming takes place in the
• Make your O.E.M. meter perform complex functions but appear
simple to use by hiding set-up codes, etc. main or setpoint programming modes. The meter has a wide range
of built-in software features. For more details on software features
• Texmate developed PC software for meter programming (serial
output module required). see Specifications on Page 2.

The Meter Center - Chandler, AZ (800) 230-6008 www.MeterCenter.com 1


General Features
Specifications
Input Configuration: ......More than 75 single and dual input signal Programming Buttons
conditioners available covering almost PROGRAM: ..................Move from one program step to the next
every input signal type. UP: ......................................Increase the value of the displayed parameter
Optional Output Module DOWN: ..........................Decrease the value of the displayed parameter
Relay Module: ..............14 standard relay configuration options
available using a combination of 5 A / 240
VAC Form A, 10 A / 240 VAC Form C Overrange Indications ....
relays and open collector outputs (max six Underrange Indications..
relays). See Ordering Information
Analog Output Module: ..Isolated 0 to 20 mA, or 0 to 10 VDC
(digitally calibrated): Internal Resolution: ....16-bits
Accuracy: 0.02% over full scale
Conversion Mode: ......Dual slope; bipolar. Depends on Input
Resolution: 1/45000
signal conditioner selected.
Compliance: 10 V
Update Rate: 7 readings per second Accuracy:......................±0.05% of reading + 2 digit (typical)

Serial Output Module: ..Communication: Isolated ASCII, or ModBus, Conversion Rate: ........Typically 10 samples per second for 50 Hz;
or Profibus with direct printer interface 5 samples per second for 60 Hz
Isolated RS-232, or isolated RS-485, or Temp. Coefficient: ......Typically 30 ppm/ °C
non-isolated TTL serial output:
Mains Input Polarity: ..Auto
Data: 7/8 bits
Baud: 300, 600, 1200, 2400, 4800, 9600, Decimal Point:..............Front panel, user programmable to five
19200, or 57.6 k. positions
Parity: Off, odd, or even Warm Up Time: ............10 minutes
Bus Address: 1 to 255
Operating Temp.: ........0-50 °C
Display Range:
DI-50E ............................–19999 to 32766, or –19990 to 99990 with Case Dimensions: ......3.78" W x 1.89" H x 4.84" D (96 x 48 x 117
fixed LSD zero selected mm)
DI-60E, DI-60AE............–32766 to 32766, or –199990 to 327660 Case Material: ..............Polycarbonate
with fixed LSD zero selected. Totalizer and
Lens Cover: ..................NEMA-4, (optional)
counter functions to 999999
Input Impedance:........Depends on input signal conditioner Application Functions Include:
selected (1 MΩ for DCV ) Linearization ..................32-point linearization is used to convert
non-linear curves to straight sections over
Display: ........................7 segment, 0.56” (14.2 mm) LEDs for the length of the curve.
DI-50T and DI-60T. 14 segment, 0.56”
(14.2mm) for DI-60AT. Red standard, or Totalizator ......................The totalizator calculates the total of a
optional green LEDs. process signal being metered by accumu-
lating an input process variable over time.
Annunciators: ..............Six red LEDs on front panel; one annunci-
ator per setpoint Counter Function ..........A multitude of counter applications are
supported.
Power Requirements
Standard High Voltage: Between 85-265 VAC or 95-370 VDC Timer ..............................Timer functions are supported in either time-
up, time-down, or real-time clock modes.
Optional Low Voltage:....Between 9-32 VAC or 10-60 VDC
Math Function ................The math function can calculate the sum,
Excitation Voltage: ........User selectable 5 / 10 / 20 VDC
difference, ratio, and product of two inputs.
Setpoints:......................Setpoint 1 activates Relay 1 This, for example, can be used to produce
Setpoint 2 activates Relay 2 a tare reading during weighing operations.
Setpoint 3 activates Relay 3 Peak and Valley ............The meter can retain peak and valley
Setpoint 4 activates Relay 4 (min/max) information and recall this on
the front panel.
Setpoint 5 resets selected register or acti-
vates Relay 5 Remote Setpoint Input ..Remote setpoint input via channel 2.
Setpoint 6 resets selected register or acti- Primary Input
vates Relay 6 Compensation................Provides compensation to the primary input
channel (CH1) via channels 1, 2, 3, 4

Page 2 The Meter Meter Center - Chandler, AZ (800) 230-6008 www.Metercenter.com


General Features
Controls and Indicators Continued

Front Panel Functions When the SETPOINT LOCKOUT switch is set to the OFF position,
the setpoints can be programmed.
Program Button Once the setpoint values have been entered and the SETPOINT
The PROGRAM button is used to move from one program step to LOCKOUT switch set to position 1, the setpoints can be viewed but not
the next.When pressed at the same time as the UP button, it initiates changed. All other programming functions, except setpoint control func-
the main programming mode. When pressed at the same time as tions, can be carried out provided the PROGRAM LOCKOUT switch is
the DOWN button, it initiates the setpoint programming mode. set to OFF. See the Display PCB without Faceplate and Bezel diagram.
Up Button Error Message “Err”
When in the operational display, pressing the UP button initiates the Error messages usually occur during calibration procedures. The
viewing setpoints 2, 4, 6, and peak readings routine. Once into the three most likely causes of an error message are:
routine, pressing the UP button moves through the steps of the routine. 1) The full scale and zero signals were too similar. The high input (full
When setting a displayed parameter during programming, the UP scale) signal must be at least 1000 counts greater than the low
button is used to increase the value of the displayed parameter. input (zero) signal (positive and negative values are allowed).
2) The scaling requirement exceeded the capability of the meter
Down Button (–19999 to +32766).
When in the operational display, pressing the DOWN button initiates
3) No input signal present, or incorrect connections.
the viewing setpoints 1, 3, 5, and valley readings routine. Once
into the routine, pressing the DOWN button moves through the Rear Panel Functions
steps of the routine.
When setting a displayed parameter during programming, the DOWN
Program Lockout Pin
button is used to decrease the value of the displayed parameter. By connecting the LOCK pin (pin 8 on the main PCB) to the COM-
MON pin (pin 11 on the main PCB), the set-up program is locked out.
Annunciator LEDs The programmed meter parameters and setpoints can be viewed
The annunciator LEDs may be programmed to indicate the alarm sta- but not changed when the meter is in the "locked out" mode.
tus.They are labeled from left to right: SP1, SP2, SP3, SP4, SP5, SP6.
Hold Reading Pin
UP
TEXMATE Button When the HOLD pin (pin 9) is connected to the COMMON pin (11)
the displayed reading is frozen. However, A/D conversions continue
and as soon as pin 9 is disconnected from pin 11 by the switch, the
Prog.
updated reading is instantly displayed when released by a switch
SP1 SP2 SP3 SP4 SP5 SP6
DOWN contact. The HOLD pin can also be used to reset the following:
Button
PROGRAM LED Annunciators • Reset of total while in the total display.
Button P for Setpoints 1-6
• Reset of peak while in the peak display.
Display with Faceplate and Bezel
• Reset of valley while in the valley display.
• Reset of tare, peak, and valley while in the tare function.
Seven Segment LED Displays • If the relays are latched, they are also reset with the above total,
The five, seven segment LED displays are used to display the meter peak, valley, or tare setting.
input signal readings. They also display the programming codes
and settings during programming. The display is available in red, Serial Output

green, or super bright red LEDs. Relay Outputs 24 23 22 21 20 19 Analog Output

Program Lockout Switch 32 31 30 29 28 27 26 25

Function Pins
18 17 16

AC/DC Power
Pin 18 for Dual
Analog output ONLY

When the PROGRAM LOCKOUT switch is set to the OFF position, Input Module
(See specific input module data
sheet for connection details)

all programmable meter functions can be changed except for set- 1 2 3 4 5 6 8 9 10 11 12 14 15

ting the setpoints.


LOCK HOLD TEST COMMON CAPTURE
When set to position 2, the PROGRAM LOCKOUT switch prevents any
programming changes being made to the meter functions except for Rear Panel
setting the setpoints. If programming is attempted, the meter displays
'LOC'. Position 2 allows programming parameters to be viewed but not
changed. See the Display PCB without Faceplate and Bezel diagram.
Display Test and Reset Pin
When the TEST pin (pin 10) is connected to the COMMON pin
Setpoint Lockout Switch (pin 11), all segments of the display light up and five eights and
five decimal points (8.8.8.8.8.) are displayed for three seconds.
Seven Segment PROGRAM This detects any missing segments in the display. The micro-
LED Display LOCKOUT processor is also reset during this time, losing all RAM settings
Switch
such as peak and valley, and any settings set up in Code 9.
ON

2
1

Common Pin
To activate the HOLD, TEST and RESET, or LOCK pins from the
SETPOINT rear of the meter, the respective pins have to be connected to the
LOCKOUT
Switch COMMON pin (pin 11).
Display PCB without Faceplate and Bezel

The MeterCenter - Chandler, AZ (800) 230-6008 www.MeterCenter.com page 3


Case Dimensions
PANEL CUTOUT FRONT VIEW SIDE VIEW Top Connector TOP VIEW
1/8 DIN Cutout spacers 8 places 14.5 mm (0.57")
1/8 DIN (96x48) DIN Cutout spacers
3.0mm
(0.125") Mosaic Fitting 87.6mm
8 places (3.45") To open rear
43.4mm 45 mm 48 mm 43.4 mm 41 mm 95.6 mm
41mm (1.71") (1.77") (1.89") (1.73") (1.61") cover, use a small (3.76")
(1.61") 91.6 mm flat blade screw
91.6mm Snug Fitting (3.6")
4.45mm (3.6") driver. Press down
(0.175") DIN lightly to release
Cutout 87.6 mm
8 places Loose Fitting 96 mm catch on top or (3.45")
92 mm 4.0 mm 117 mm (3.78") Spacer
96 mm bottom of case and mosaic
(3.62") (0.16") typical (3.78") 5.7 mm (4.61") Bottom Connector fitting
(0.22") 11.43mm (0.45") leaver outwards.
Panel adaptor plates are available
to retrofit most existing panel cutouts. Metal Surround Case: These dimensions are increased
by 1.27mm (0.05") when the metal surround case is installed.
3.56mm (0.14") 1.27mm (0.05")
DIN Cutout Spacer Connector Socket

For additional strength, extra Mounting Slide Clips


can be ordered and doubled up one behind the
other. (P/N: 75-DMTCLIPF)

When extra panel


Texmate's 96x48mm case is particularly suitable for mounting tightness is required,
mounting in mosaic panels or insulative panels up to 2" order the optional screw mount clip.
thick. They can also stack mount, 2 up in existing cutouts Various bezel colors Mounts in panels
up to 2" thick . P/N.(OP-MTLCLIP)
for 1/4 DIN (96x96mm) or 4 up in 1/2 DIN (96X192mm). are available. Black is standard.

Installation

Installation Instructions WARNING


STEP A Prepare the Panel AC and DC power supply voltages
are hazardous. Make sure the
1) Cut a hole in the panel to suit the panel power supply is isolated before
cutout. See Case Dimensions for panel cutout connecting to the meter.
sizes.
STEP B Install the Meter 2) Connect the power cables to the connector
pins (See Connector Pinouts for details).
1) Remove both mounting clips from the meter.
2) Push the meter into the panel cutout from the
front of the panel. 1

3) Attach both mounting clips to the meter from


the rear of the panel and push them towards
the front of the panel until the meter is firmly
held.
2
STEP C Connect the Cables

1) Connect all input and output signal cables to


the connector pins (See Connector Pinouts
for details).

The Meter Center - Chandler, AZ (800) 230-6008 www.MeterCenter.com Page 4


Ordering Information
BASE PART # DISPLAY POWER SUPPLY INPUT MODULE ANALOG OUTPUT SERIAL OUTPUT RELAY OUTPUT SPECIAL

DI-60E OA____
Add to the basic model number the order code suffix for each standard option required. The last suffix is to
indicate how many different special options and or accessories that you may require to be included with this product.
Ordering Example: DI-60T-DR-PS1-IA01-AIC-R1-OA2 plus CR-CHANGE and a OP-N4X/96X48, $225 + N/C + N/C + 35 + 50 + 30 + 5+ 20 = $365
IT02 . . .RTD, 100Ω Pt. 2/3/4-wire . . . . . . . . ..... .... . . . . . . . . . . . . . . . . .$35
BASIC MODEL NUMBER IT12 . . .RTD, 120Ω Nickel 2/3/4-wire . . . . . . ..... .... . . . . . . . . . . . . . . . . .$45
DI-50E . . . 96x48mm, Tiger, 5 Digit, E Version . . . . . . . . . .$180 IT13 . . .RTD, 10Ω Copper 2/3/4-wire . . . . . . ..... .... . . . . . . . . . . . . . . . . .$40
DI-60AE . . 96x48mm, Tiger, 6 Digit, Alphanumeric, E Version .$275 IW01 . . .AC-Watts, 300V/1A AC, Single Phase 2-wire ... . . . . . . . . . . . . . . . . .$65
DI-60E . . . 96x48mm, Tiger, 6 Digit, E Version . . . . . . . . . .$225 IW02 . . .AC-Watts, 300V/5A AC, Single Phase 2-wire ... . . . . . . . . . . . . . . . . .$65
IW03 . . .DC-Watts, 10V/50mV DC (0-100.00) ..... .... . . . . . . . . . . . . . . . . .$65
Standard Options for this Model Number
ANALOG OUTPUT
Order Code Suffix Description List
AIC . . .Isolated 16 Bit Current Output, 4-20mA . . . . . . . . . . . . . . . .$50
DISPLAY AIV . . .Isolated 16 Bit Voltage Output, 0-10VDC . . . . . . . . . . . . . . .$50
DR . .Red LED, 0.56 inch high . . . . . . . . . . . . . . . . . . . .N/C S2 . . .Isolated RS-232 (Requires Cable, See Options) . . . . . . . . . .$65
DB . . . .Super–bright Red LED, 0.56 inch high . . . . . . . . . . . . . . . . . . .$25 S4 . . .Isolated RS-485 (Requires Cables, See Options) . . . . . . . . .$85
DG . . .Green LED, 0.56 inch high . . . . . . . . . . . . . . . . . . . . . . . . . . .$10 S5 . . .Isolated ModBus, ASCII Code Compatible . . . . . . . . . . . . . .$95

POWER SUPPLY RELAY OUTPUT


PS1 . .85 - 265VAC / 95 - 370VDC . . . . . . . . . . . . . . . . . . .N/C R1 . . .Single 5A Form A Relay . . . . . . . . . . . . . . . . . . . . . . . . . . .$30
PS2 . . .18 - 48VAC / 10 - 72VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$35 R2 . . .Dual 5A Form A Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . .$60
R3 . . .Three 5A Form A Relays . . . . . . . . . . . . . . . . . . . . . . . . . . .$90
INPUT MODULES (Partial List. See www.texmate.com) R4 . . .Four 5A Form A Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . .$120
R5 . . .Five 5 A Form A Relays . . . . . . . . . . . . . . . . . . . . . . . . . . .$150
Unless otherwise specified Texmate will ship all modules precalibrated with factory R6 . . .Six 5 A Form A Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . .$180
preselected ranges and/or scalings as shown in BOLD type. R11 . . .Single 10A Form C Relay . . . . . . . . . . . . . . . . . . . . . . . . . .$35
IA01 . . .AC-Volts Scaled RMS, 200/600V AC . . . . . . . . . . . . . . . . . . . . . . . . . . .$35 R12 . . .Dual 10A Form C Relays . . . . . . . . . . . . . . . . . . . . . . . . . .$70
IA02 . . .AC-Volts Scaled RMS, 200mV/2V/20V AC . . . . . . . . . . . . . . . . . . . . . . .$35 R13 . . .Dual 10A Form C & One 5A Form A Relays . . . . . . . . . . . . . .$105
IA03 . . .AC-mA Scaled RMS, 2/20/200mA AC . . . . . . . . . . . . . . . . . . . . . . . . . .$35 R14 . . .Dual 10A Form C & Dual 5A Form A Relays . . . . . . . . . . . . .$140
IA04 . . .AC-Amps Scaled RMS, 0-1 Amp AC (0-100.00) . . . . . . . . . . . . . . . . .$40 R15 . . .Single 10A Form C & Dual 5A Form A Relays . . . . . . . . . . . .$95
IA05 . . .AC-Amps Scaled RMS, 0-5 Amp AC (0-100.00) . . . . . . . . . . . . . . . . .$40 R16 . . .Single 10A Form C & Single 5A Form A Relays . . . . . . . . . . .$65
IA06 . . .AC-Volts True RMS, 200/600V AC . . . . . . . . . . . . . . . . . . . . . . . . . . . .$55 R17 . . .Single 10A Form C & Three 5A Form A Relays . . . . . . . . . . .$125
IA07 . . .AC-Volts True RMS, 200mV/2V/20V AC . . . . . . . . . . . . . . . . . . . . . . . . .$55
IA08 . . .AC-mA True RMS, 2/20/200mA AC . . . . . . . . . . . . . . . . . . . . . . . . . . . .$55 Special Options and Accessories
IA09 . . .AC-Amps True RMS, 0-1 Amp AC (0-100.00) . . . . . . . . . . . . . . . . . . .$55
IA10 . . .AC-Millivolt, Scaled RMS, 100mV AC . . . . . . . . . . . . . . . . . . . . . . . . .$55 Part Number Description List
IA11 . . .AC-Amps True RMS, 0-5 Amp AC (0-100.00) . . . . . . . . . . . . . . . . . . .$55
IA12 . . .AC-Millivolt, True RMS, 100mV AC . . . . . . . . . . . . . . . . . . . . . . . . . . .$55 SPECIAL OPTIONS (Specify Inputs or Outputs & Req. Reading)
ID01 . . .DC-Volts, 2/20/200V/Custom w/24V DC Exc . . . . . . . . . . . . . . . . . . . . .$25 76-DI60EG/N4 . . . "Touch" Faceplate, Green, factory installed. NEMA4 .$8
ID02 . . .DC-Millivolt, 20/50/100/200mV DC w/24V DC Exc . . . . . . . . . . . . . . . . .$35 76-DI60ER/N4 . . . "Touch" Faceplate, Red, factory installed. NEMA4 . . .$8
ID03 . . .DC-Milliamp, 2/20/200mA DC w/24V DC Exc . . . . . . . . . . . . . . . . . . . . .$25 OP-P256K/R–E . .256K Processor with RTC . . . . . . . . . . . . . . . . . . . . .$105
ID04 . . .DC-Amps, 5A DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$50 OP-P256K–E . . . .256K Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . .$60
ID05 . . .DC-Volts 2/20/200/Custom V DC w/Offset and 24V Exc. . . . . . . . . . . . . .$45 OP-P32K/R–E . . .32K Processor with RTC . . . . . . . . . . . . . . . . . . . . . .$75
ID06 . . .DC-Volts 2/20/200/Custom V DC w/Ext.Decimal Select . . . . . . . . . . . . . .$35 OP-P32K–E . . . .32K Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$30
ID07 . . .DC-Milliamp, 2/20/200mA DC w/Offset and 24V Exc . . . . . . . . . . . . . . . .$35 CR-CHANGE . . . .Calibrated Range Change to another Standard Range . .$5
ID08 . . .DC-Volts, 2/20/200/Custom V DC w/Ext.LIN Table Select . . . . . . . . . . . .$45 CS-I/50 . . . . . . .Custom scaling within standard/custom range - 5 digit . . . .$14
ID09 . . .DC-Amps, 1A DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$50 CS-I/60 . . . . . . .Custom scaling within standard/custom range - 6 digit . . . .$16
IDD1 . . .Dual DC Volts, 2V DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$65 CSR-I/50 . . . . . .Custom selectable range installation or mod - 5 digit .$38
IDD2 . . .Dual DC-Millivolts, 50mV DC(100.00) . . . . . . . . . . . . . . . . . . . . . . . .$65 CSR-I/60 . . . . . .Custom selectable range installation or mod - 6 digit .$41
IDD3 . . .Dual DC-Millivolts, 50mV DC(100.00) . . . . . . . . . . . . . . . . . . . . . . . .$65 CSS-I/50 . . . . . .Custom special scaling beyond standard range - 5 digit . . . . .$50
IDD4 . . .Dual Input, Volts/millivolts 2V/50mV DC(100.00) . . . . . . . . . . . . . . . .$65 CSS-I/60 . . . . . .Custom special scaling beyond standard range - 6 digit . . . .$55
IDP1 . . .Dual Process Loop,4-20mA (0-100.00) . . . . . . . . . . . . . . . . . . . . . . .$65 COA-I/Single . . .Custom output, Special scaling of single analog output . . . .$20
IDP2 . . .Dual Input,4-20mA (0-100.00)/3-wire RTD . . . . . . . . . . . . . . . . . . . .$65 COA-I/Dual . . . . .Custom output, Special scaling of dual analog output .$35
IDP3 . . .Dual Input,4-20mA(0-100.00)/K/R/S/T/J Thermocouple . . . . . . . . . . . .$65 COR-I/RELAY . . .Custom output, Relays installed non-standard . . . . . . .$20
IDR1 . . .Dual Resistance Input, 0.2/2/20KΩ . . . . . . . . . . . . . . . . . . . . . . . . . . . .$65 CCP-I/SETUP . . .Custom configuration, Programmable functions - Setup . . . .$20
IDS1 . . .Dual Strain Gage Input,4 wire 2mV/V . . . . . . . . . . . . . . . . . . . . . . . . .$125 CCP-I/INSTL . . . .Custom configuration, Programmable functions - Install . . . .$5
IDS2 . . .Dual Pressure Input,4 wire 2mV/V . . . . . . . . . . . . . . . . . . . . . . . . . . .$125 CLT-I/SETUP . . . .Custom Linearization Table - Setup . . . . . . . . . . . . . .$20
IDT1 . . .Dual Thermocouple Input J/K/R/T . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$75 CLT-I/INSTL . . . .Custom Linearization Table - Installation . . . . . . . . . .$5
IDT2 . . .Dual RTD Input, 2/3-wire, 100Ω Pt . . . . . . . . . . . . . . . . . . . . . . . . . . .$65 CMP-I/SETUP . . .Custom Macro Program - Setup . . . . . . . . . . . . . . . .$40
IF01 . . .Frequency/RPM, 5 ranges; .04Hz-320KHz, 24V exc. . . . . . . . . . . . . . . . . $45 CMP-I/INSTL . . .Custom Macro Program - Installation . . . . . . . . . . . .$5
IF02 . . .Line Frequency, 50-500VAC, 5 ranges; .04Hz-320kHz . . . . . . . . . . . . . . .$65
IF03 . . .Frequency, 1-50VAC, 5-30VDC, 5 ranges; .04Hz-320kHz . . . . . . . . . . . . .$65 ACCESSORIES (Specify Serial # for Custom Artwork Installation)
IF04 . . .Frequency/RPM, 2mV/5V with Excitation . . . . . . . . . . . . . . . . . . . . . . . .$65 75-DBBZ9648F . . .Black Bezel for 96x48mm Case . . . . . . . . . . . . . . . .$2
IP01 . . .Process Loop, 4-20mA(0-100.00) . . . . . . . . . . . . . . . . . . . . . . . . . . .$35 75-DMTCLIPF . . . .Side Slide Brackets (2 pc) - extra set, extra strength .$2
IP02 . . .Process Loop, 4-20mA(0-100.00) w/24VDC Exc . . . . . . . . . . . . . . . . .$45 93-PLUG2P-DP . . .Extra Screw Terminal Conn., 2 Pin Power Plug . . . . .$2
IP03 . . .Process Input, 1-5V DC(0-100.00) w Offset, 24V Exc . . . . . . . . . . . . . .$45 93-PLUG2P-DR . . .Extra Screw Terminal Conn., 2 Pin Plug . . . . . . . . . .$2
IP06 . . .Process Loop, 4-20mA(0-100.00) w/24VDC Exc and Autocal . . . . . . . .$45 93-PLUG3P-DR . . .Extra Screw Terminal Conn., 3 Pin Plug . . . . . . . . . .$3
IP07 . . .Universal Process 2V/5V/10V/20V/200V/2mA/20mA/Custom . . . . . . . . . .$30 93-PLUG4P-DR . . .Extra Screw Terminal Conn., 4 Pin Plug . . . . . . . . . .$4
IP08 . . .Universal Process 2V/5V/10V/20V/200V/2mA/20mA/Custom w/Autocal . .$55 CV-485/232 . . . . .RS485 to RS232 Converter . . . . . . . . . . . . . . . . . . .$75
IPT1 . . .Prototype Board for Custom Design . . . . . . . . . . . . . . . . . . . . . . . . . . . .$15 OM-CABLE232 . . .Cable, 6ft, for RS232: RJ6 phone plug to DB9 female plug . .$10
IR01 . . .Resistance, 2/3/4-Wire, 200Ω/2KΩ/20KΩ . . . . . . . . . . . . . . . . . . . . . .$35 OM-CABLE485 . . .Cable, 6ft, for RS485: RJ6 phone plug to DB9 female plug . .$10
IR02 . . .3 wire Potentiometer 1KΩ min (0-100.00) . . . . . . . . . . . . . . . . . . . . .$40 OP-MCLP96X48 . .Screw Mounting Clips (2 pc) - to screw tighten slide brackets .$6
IS01 . . .Strain Gage 5/10VDC Exc., 20/2mV/V, 4/6-wire . . . . . . . . . . . . . . . . . .$55 OP-MTL96X48 . . .Metal Surround Case, includes screw mounting clips .$16
IS02 . . .Pressure 5/10VDC Exc., 20/2mV/V, 4/6-wire . . . . . . . . . . . . . . . . . . . . .$55 OP-N4X/96X48 . . .96x48mm clear lockable front cover–NEMA 4X, splash proof . .$20
IS03 . . .Pressure 5/10VDC Exc., 20/2mV/V, 4/6-wire w/Autocal . . . . . . . . . . . . .$65
IS04 . . .Pressure Ext Exc., 20/2mV/V, 4/6–wire . . . . . . . . . . . . . . . . . . . . . . . . .$45 Many other options and accessories are available. See full price list for more details.
IT01 . . .Thermocouple, J/K/R/S/T/B/N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$30
Prices subject to change without notice.

The Meter Center (800) 230-6008 www.MeterCenter.com

You might also like