Simulation of Faults in Long Transmission Line Using MATLAB Simulink
Simulation of Faults in Long Transmission Line Using MATLAB Simulink
Shashwath Bhandary(171EE139)
Kondeti Chaitanya(171EE122)
April, 2021
1
CONTENTS
Acknowledgement 4
Abstract 5
Introduction 6
Theoretical Background 8
2
DECLARATION
This is to certify that the Major Project Report entitled Simulation of Long
Transmission line using MATLAB Simulink which is being submitted to the
National Institute of Technology Karnataka, Surathkal in partial fulfilment of
the requirements for the award of Bachelor of Technology in Electrical and
Electronics Engineering, in the Department of Electrical and Electronics
Engineering is a bonafide report of the project work carried out by us. The
material contained in this report has not been submitted to any University or
Institution for the award of any degree.
Names:
Chandan G Krishna-(171EE113)
Shashwath Bhandary-(171EE139)
Kondeti Chaitanya-(171EE122)
3
ACKNOWLEDGMENT
4
ABSTRACT
Transmission line protection is an important issue in power system engineering
because 85-87% of power system faults are occurring in transmission lines.
This paper presents a technique to detect and classify the different shunt faults
on a transmission lines for quick and reliable operation of protection schemes.
Discrimination among different types of faults on the transmission lines is
achieved by application of evolutionary programming tools. MATLAB software
is used to simulate different operating and fault conditions on high voltage
transmission line, namely single phase to ground fault, line to line fault, double
line to ground and three phase short circuit. The discrete wavelet transform
(DWT) is applied for decomposition of fault transients, because of its ability to
extract information from the transient signal, simultaneously both in time and
frequency domain. The data sets which are obtained from the DWT are used
for training and testing the SVM architecture. After extracting useful features
from the measured signals, a decision of fault or no fault on any phase or
multiple phases of a transmission line is carried out using three SVM classifiers.
The ground detection task is carried out by a proposed ground index. Gaussian
radial basis kernel function (RBF) has been used, and performances of
classifiers have been evaluated based on fault classification accuracy. In order
to determine the optimal parametric settings of an SVM classifier (such as the
type of kernel function, its associated parameter, and the regularization
parameter c), fivefold cross-validation has been applied to the training set. It is
observed that an SVM with an RBF kernel provides better fault classification
accuracy than that of an SVM with polynomial kernel. It has been found that
the proposed scheme is very fast and accurate and it proved to be a robust
classifier for digital distance protection.
Transmission lines happen to be one of the important subjects in Electrical
Power System curriculum. Unfortunately, the theoretical concepts learned in
the class room cannot be verified in a laboratory. The development of
laboratory model to perform experiments is very much essential. This project
discusses the steps involved in the design and development of laboratory
model of transmission line using MATLAB Simulink. Moreover, the MATLAB
based simulation of the designed line is also presented.
5
INTRODUCTION
7
Theoretical Background
A long transmission line is defined as a transmission line with an effective
length more than 250 km (150 miles). Unlike short transmission lines and
medium transmission lines, it is no longer reasonable to assume that the line
parameters are lumped. To accurately model a long transmission line, we must
consider the exact effect of the distributed parameters over the entire length of
the line. Although this makes the calculation of ABCD parameters of
transmission line more complex, it also allows us to derive expressions for the
voltage and current at any point along the line.
In a long transmission line, the line constants are uniformly distributed over the
entire length of line. This is because the effective circuit length is much higher
than what it was for the former models (long and medium line) and hence we
can no longer make the following approximations:
Rather, for all practical reasons, we should consider the circuit impedance and
admittance being distributed over the entire circuit length as shown in the figure
below. The calculations of circuit parameters, for this reason, are going to be
slightly more rigorous as we will see here. For accurate modelling to determine
circuit parameters let us consider the circuit of the long transmission line as
shown in the diagram below.
8
Here a line of length l > 250km is supplied with a sending end voltage and
current of VS and IS respectively, whereas the VR and IR are the values of
voltage and current obtained from the receiving end. Let us now consider an
element of infinitely small length Δx at a distance x from the receiving end as
shown in the figure where.
Therefore, the voltage drop across the infinitely small element Δx is given by
9
Now to determine the current ΔI, we apply KCL to node A,
Since the term ΔV yΔx is the product of 2 infinitely small values, we can ignore
it for the sake of easier calculation.
The solution of the above second order differential equation is given by.
10
Now comparing equation (1) with equation (5)
Now at x=0, V= VR and I= Ir. Substituting these conditions to equation (7) and
(8) respectively.
11
By trigonometric and exponential operators we know
Thus compared with the general circuit parameters equation, we get the ABCD
parameters of a long transmission line as,
The real part α is called the attenuation constant and the imaginary part β is called
the phase constant. Now Vx of Eq. (5.21) can be written as
12
The instantaneous voltage consists of two terms each of which is a function of
two variables—time and distance. Thus they represent two travelling waves, i.e.
At any instant of time t, νx1 is sinusoidally distributed along the distance from the
receiving-end with amplitude increasing exponentially with distance, as shown in
Fig. 5.11 (α > 0 for a line having resistance).
After time Δt, the distribution advances in distance phase by (ωΔtlβ) Thus this
wave is travelling towards the receiving-end and is the incident wave. Line losses
cause its amplitude to decrease exponentially in going from the sending to the
receiving-end.
Now
After time Δt the voltage distribution retards in distance phase by ωΔtlβ). This is
the reflected wave travelling from the receiving-end to the sending-end with
amplitude decreasing exponentially in going from the receiving-end to the
sending-end, as shown in Fig. 5.12.
13
At any point along the line, the voltage is the sum of incident and reflected voltage
waves present at the point [Eq. (5.32)]. The same is true of current waves.
Expressions for incident and reflected current waves can be similarly written
down by proceeding from Eq. (5.21). If Zc is pure resistance, current waves can
be simply obtained from voltage waves by dividing by Z c.
i.e. the line is terminated in its characteristic impedance, the reflected voltage
wave is zero (VR-ZcIR=0).
A line terminated in its characteristic impedance is called the infinite line. The
incident wave under this condition cannot distinguish between a termination and
an infinite continuation of the line.
Power system engineers normally call Zc the surge impedance. It has a value of
about 400 ohms for an overhead line and its phase angle normally varies from 0°
to — 15°. For underground cables Zc is roughly one-tenth of the value for
overhead lines. The term surge impedance is, however, used in connection with
surges (due to lightning or switching) or transmission lines, where the lines loss
can be neglected such that
14
where |VR| is the line-to-line receiving-end voltage in kV. Sometimes, it is found
convenient to express line loading in per unit of SIL, i.e. as the ratio of the power
transmitted to surge impedance loading.
At any time the voltage and current vary harmonically along the line with respect
to x, the space coordinate. A complete voltage or current cycle along the line
corresponds to a change of 2π rad in the angular argument βx. The corresponding
line length is defined as the wavelength.
If β is expressed in rad/m,
Now time for a phase change of 2π is 1/f s, where f=ω/2π is the frequency in
cycles/s. During this time the wave travels a distance equal to λ, i.e. one
wavelength.
Velocity of propagation of wave,
15
For a single-phase transmission line
Since r and r’ are quite close to each other, when log is taken, it is sufficiently
accurate to assume that In
The actual velocity of the propagation of wave along the line would be somewhat
less than the velocity of light.
Wavelength of a 50 Hz power transmission is approximately given by
16
LOSS LESS LINE
𝐿
ZC = √
𝐶
γ = jω + √(𝐿𝐶)
Observe that for loss less line, Zc becomes a pure resistance. We also know
that γ = α+j β, for this loss less situation we get
α=0
β = w + √𝐿𝐶
Now our previous voltage and current equations for surge impedance loading
reduces to
V(x) = Vr + 𝑒 𝑗𝛽𝑥
I (x) = Ir + 𝑒 𝑗𝛽𝑥
As in case of lossy line here also at any distance x from receiving end the ratio
of voltage and current is always same that is Zc, the surge impedance of the
line. Using the complex algebra you are sure that the magnitude of V(x) is Vr
and I(x) is Ir. Which means that for loss less line the voltage and current at any
distance x from the receiving end is same. It also implies voltage at sending end
is same as voltage at receiving end which is same as voltage at any intermediate
point. So Vs = V(x) = Vr. At Surge Impedance Loading the reactive power
generated by the line capacitance is equal to the reactive power absorbed by the
line inductance for every unit length of line. In Power industry it is said that the
voltage profile is flat. So we conclude that for a lossless line the voltage
magnitude is same throughout the length of line. As in case of lossy line the
term 𝑒 𝑗𝛽𝑥 is the phasor responsible for phase shift. It is simply giving phase
17
shift to the voltage wave along the length of line. The phase angle between
sending and receiving end voltage is 𝑒 𝑗𝛽𝑙 .
It is clear that if the distance between the sending and receiving end is more
then the phase difference between the voltage phasors at both the ends of the
line will be more.
SIL = Vl2 / Zc
Where
Vl = √(3) * Vr
18
Transmission of Energy
When the load is connected directly to the source of energy, or when the
transmission line is short, problems concerning current and voltage can be
solved by applying Ohm’s law. When the transmission line becomes long
enough so the time difference between a change occurring at the generator and
the change appearing at the load becomes appreciable, analysis of the
transmission line becomes important.
Electrical transmission is the process of delivering generating electricity - usually
over long distances - to the distribution grid located in populated areas. An
important part of this process includes transformers which are used to
increase voltage levels to make long distance transmission feasible.
The electrical transmission system combined with power plants, distribution
systems, and sub-stations to form what is known as the . The grid meets
society's electricity needs, and is what gets the electric grid from its generation to
its end use. Since power plants are most often located outside of densely
populated areas, the transmission system must be fairly large.
.
19
DC Applied to a Long Transmission Line
In DC transmission line, the mercury arc rectifier converts the alternating
current into the DC. The DC transmission line transmits the bulk power over
long distance. At the consumer ends the thyratron converts the DC into the AC.
When a battery is connected through a relatively long two-wire transmission
line to a load at the far end of the line. At the instant the switch is closed, neither
current nor voltage exists on the line. When the switch is closed, point A
becomes a positive potential, and point B becomes negative. These points of
difference in potential move down the line. However, as the initial points of
potential leave points A and B, they are followed by new points of difference in
potential which the battery adds at A and B. This is merely saying that the
battery maintains a constant potential difference between points A and B. A
short time after the switch is closedas A and B, respectively. The points of
charge are represented by plus (+) and minus (-) signs along the wires.
The directions of the currents in the wires are represented by the arrow heads on
the line, and the direction of travel is indicated by an arrow below the line.
Conventional lines of force represent the electric field that exists between the
opposite kinds of charge on the wire sections from A to A’ and B to B’. Crosses
(tails of arrows) indicate the magnetic field created by the electric field moving
down the line. The moving electric field and the accompanying magnetic field
constitute an electromagnetic wave that is moving from the generator (battery)
toward the load. This wave travels at approximately the speed of light in free
space. The energy reaching the load is equal to that developed at the battery
(assuming there are no losses in the transmission line). If the load absorbs all of
the energy, the current and voltage will be evenly distributed along the line.
20
Power Flow through a Transmission Line
So far the transmission line performance equation was presented in the
form of voltage and current relationships between sending-and receiving-
ends. Since loads are more often expressed in terms of real (watts/kW)
and reactive (VARs/ kVAR) power, it is convenient to deal with
transmission line equations in the form of sending- and receiving-end
complex power and voltages. While the problem of flow of power in a
general network will be treated in the next chapter, the principles involved
are illustrated here through a single transmission line (2-node/2-bus
system) as shown in Fig. 5.17.
This indeed is the same as Eq. (5.58). The same result holds for Ss. Thus,
we see that Eqs. (5.58) and (5.59) give the three-phase MVA
if Vs and VR are expressed in kV line.
If Eq. (5.58) is expressed in real and imaginary parts, we can write the real
and reactive powers at the receiving-end as
22
It is easy to see from Eq. (5.61) that the received power PR will be
maximum at
Thus, the load must draw this much leading MVAR in order to receive the
maximum real power.
Consider now the special case of a short line with a series impedance Z.
Now
Substituting these in Eqs. (5.61) to (5.64), we get the simplified results for
the short line as
The above short line equation will also apply for a long line when the line
is replaced by its equivalent- π (or nominal- π) and the shunt admittances
23
are lumped with the receiving-end load and sending-end generation. In
fact, this technique is always used in the load flow problem to be treated
in the next chapter.
From Eq.(5.66), the maximum receiving-end power is received, when δ=θ
Several important conclusions that easily follow from Eqs. (5.71) to (5.74)
are enumerated below:
• For R≈0 (which is a valid approximation for a transmission line) the real
power transferred to the receiving-end is proportional to sin δ(≈δ for
small values of δ ), while the reactive power is proportional to the
magnitude of the voltage drop across the line.
24
• The real power received is maximum for δ = 90° and has a value
|Vs||VR|/X. Of course, δ is restricted to values well below 90° from
considerations of stability to be discussed in Chapter 12.
• Maximum real power transferred for. a given line (fixed X) can be
increased by raising its voltage level. It is from this consideration that
voltage levels are being progressively pushed up to transmit larger
chunks of power over longer distances warranted by large size
generating
• For very long lines voltage level cannot be raised beyond the limits
placed by present-day high voltage technology. To increase power
transmitted in such cases, the only choice is to reduce the
line reactance. This is accomplished by adding series capacitors in the
line. This idea will be pursued further in Chapter 12. Series capacitors
would of course increase the severity of line over voltages under
switching conditions.
• As said in 1 above, the VARs (lagging reactive power) delivered by a
line is proportional to the line voltage drop and is independent of
δ. Therefore, in a transmission system if the VARs demand of the load
is large, the voltage profile at that point tends to sag rather sharply. To
maintain a desired voltage profile, the VARs demand of the load must
be met locally by employing positive VAR generators (condensers).
A somewhat more accurate yet approximate result expressing line
voltage drop in terms of active and reactive powers can be written directly
from
25
RESULTS:
For a 300km Transmission line,
26
For a 500km Transmission line,
27
For a 1000km Transmission line,
28
CONCLUSION:
This project explains development of laboratory model of transmission line
using MATLAB Simulink and also steps involved in design, fabrication and
testing of transmission line. The reactive power exchange cannot see
because of the limitations of the metering facilities. However, the effect can
be seen by measuring the voltage at the receiving end. The developed
laboratory model of transmission line is used for performing the
experiments related to transmission line for undergraduate and
postgraduate students. Further, the same model will be used to develop the
laboratory setup for demonstration of different series and shunt FACTS
devices.
BIBLIOGRAPHY:
29