Guide For Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 155

Guide for Manual

Guide for Manual


The Shihlin electric SE2-TYPE inverters have been designed with many complex parameterized
functions to meet most of the application requirements from the market. For customers who contact
inverters for the first time, such a complex inverter may cause troubles when using it. So the users
are expected to read each part of this manual carefully so as to master the operating method of the
inverter. In case there is any question, please feel free to contact us.

In Chapter 2 of this manual, all the series and the corresponding specifications of Shihlin electric
SE2-TYPE inverters are listed in detail. Section 2-5 guids customers how to install the inverter and
emphasizes on precautions for safety that much attention should be paid to when utilizing the
inverter.

Chapter 3 guides customers how to use the inverter. In Section 3-1, the operating mode of the
inverter is outlined briefly; in Section 3-2, how to use the operation panel is described, and in
Section 3-3, simple operating steps are explained. Chapter 4 explains the functions of each parameter
in detail.

The definitions of terminologies in this manual are as follows:

1. Output frequency, target frequency, steady output frequency


• The actual output current frequency of the inverter is called ‘output frequency’.
• The frequency set by user (through a operation panel, multi-speed terminals, voltage signal or
current signal) is called ‘target frequency’.
• When the motor starts running, the output frequency of the inverter will gradually accelerate to the
target frequency, and finally run steadily at the target frequency. The output frequency at this time
is called ‘steady output frequency’.

2. There are detailed instructions on parameter settings in Chapter 4. In case users are not familiar
with these settings, arbitrary adjustment of the parameter may result in abnormal operations. All
parameters can be reset to their default values by the parameter of P.998. For the setting
procedure of this parameter, please refer to P.998 in Chapter 4.

3. The ‘operation mode’ of inverter, and the ‘working mode’ of the operation panel:
The operating mode determines the reference source for the target frequency and the signal source
for starting. The Shihlin inverter has totally 9 operating modes. Please refer to Section 3-1 for
details.
The operation panel mainly concerns monitoring of numeric values, setting of parameters and
setting of target frequency. The Shihlin operation panel has totally 5 working modes. Please refer
to Section 3-2 for details.

4. The difference between ‘terminal name’ and ‘function name’:


Near the terminals of the control board or the main board, printed letters can be found. These
letters are used to distinguish each terminal, and thus called ‘terminal name’.
For ‘multi-function control terminal’ and ‘multi-function output terminal’, besides the terminal
name, the ‘function name’ is also necessary to be defined. The function name indicates the actual
functions of the terminal.
1
Guide for Manual
Guide for Manual
When explaining the function for a terminal, the name used is its ‘function name’.

5. The difference between ‘on’ and ‘turn on’:


When explaining the function for the ‘multi-function control terminal’, two words ‘on’ and ‘turn
on’ are often used.
The ‘on’ is used to indicate that the external switch of the terminal is in close state, and thus
belongs to the description of the state.
The ‘turn on’ is employed to describe the action that the external switch of the terminal is shut on
from the open state to the close state, and thus belongs to the description of action.

6. All the ‘P.’s mentioned in this manual mean ‘parameter’.

2
Contents
1. Product Examination................................................................................................... 4

2. Introduction of Shihlin Inverter .................................................................................. 5

3. Primary operation...................................................................................................... 31

4. Parameter description ............................................................................................... 43

5. Inspection and Maintenance ................................................................................... 125

Appendix 1 Parameter list........................................................................................... 128

Appendix 2 Alarm Code List ...................................................................................... 139

Appendix 3 Warning code list..................................................................................... 142

Appendix 4 Troubles and Solutions ............................................................................ 143

Appendix 5 Optional equipment ................................................................................. 144

Appendix 6 Frequency parameters of ultra-high-speed ............................................. 152

3
1. Product Examination
Product Examination

Each SE2-TYPE inverter has been checked strictly before delivery and packed carefully to prevent
from mechanical damage. Please check as follows after opening the package.
• Please check whether it is damaged during transport.
• Please check whether the inverter type is identical with which shown on the package.

1.1 Nameplate instruction:

Style No. : SE2-021-0.75K-DL

Input : 14A 3PH AC380~480V 50/60Hz


Output : 13A MAX 3PH AC380~480V 5.5KW
FREQ. Range : 0.2~1000Hz

Serial NO. : EC00001

MFG. NO. : L2L0072

1.2 Type instruction:


SE2 - 021 - 0.75K - DL
L: with build-in filter
None: without build-in filter

D: with DU03 operation panel


None: without DU03 operation panel
Suitable motor: 0.4K=0.4KW;
0.75K=0.75KW……
Input voltage: 021: 220V 1-PHASE
023: 220V 3-PHASE
043: 440V 3-PHASE
Product series

1.3 Indent symbol instruction:


For example:
Demand
Operation Build-in Indent symbol
Specification
panel filter
SE2-021-0.4K(SE2 Series Single-Phase 220V 0.5HP) Yes Yes SNKSE20210R2KDL
SE2-023-1.5K(SE2 Series Three-Phase 220V 2HP) Yes No SNKSE20231R5KD
SE2-043-2.2K(SE2 Series Three-Phase 440V 3HP) No Yes SNKSE20432R2KL
SE2-043-3.7K(SE2 Series Three-Phase 440V 5HP) No No SNKSE20433R7K

4
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.1 Electric specification

2.1.1 220V Series Single-Phase


Model SE2-021-□□□K 0.4K 0.75K 1.5K 2.2K
HP 0.5 1 2 3
applicable motor capacity
kW 0.4 0.75 1.5 2.2
Rated output capacity kVA (Note) 1.2 1.9 3.0 4.2
Rated output current A (Note) 3.0 5.0 8.0 11.0
Output 150% 60 seconds; 200% 1 second (reverse time
Over-current capability
characteristics)
Maximum output voltage 3 Phase 200~240V AC
Rated power voltage single phase 200~240V 50Hz / 60Hz
Power voltage permissible
single phase 180~264V 50Hz / 60Hz
Power fluctuation
supply Power frequency permissible
±5%
fluctuation
Power source capacity kVA 1.8 3 4.5 6.4
Cooling method Nature cooling Forced air cooling
Weight kg 1.2 1.2 1.9 1.9

2.1.2 220V Series Three-Phase


Model SE2-023-□□□K 0.4K 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K
applicable motor HP 0.5 1 2 3 5 7 10
capacity kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5
Rated output capacity kVA (Note) 1.2 1.9 3.0 4.2 6.7 9.2 12.6
Rated output current A (Note) 3.0 5.0 8.0 11.0 17.5 24 33
Output 150% 60 seconds; 200% 1 second (reverse time
Over-current capability
characteristics)
Maximum output voltage 3 Phase 200~240V AC
Rated power voltage 3 Phase 200~240V 50Hz / 60Hz
Power voltage permissible
3 Phase 170~264V 50Hz / 60Hz
Power fluctuation
supply Power frequency permissible
±5%
fluctuation
Power source capacity kVA 1.8 3 4.5 6.4 10 13.8 19
Nature
Cooling method Forced air cooling
cooling
Weight kg 1.2 1.2 1.2 1.9 1.9 3.8 3.8

5
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.1.3 440V Series Three-Phase


Model SE2-043-□□□K 0.4K 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K
HP 0.5 1 2 3 5 7 10 15
applicable motor capacity
kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
Rated output capacity kVA
1.2 2.0 3.2 4.6 6.9 9.2 13 18
(Note)
Rated output current A (Note) 1.5 2.6 4.2 6.0 9.0 12 17 23
Output
150% 60 Seconds; 200% 1 Second (reverse time
Over-current capability
characteristics)
Maximum output voltage 3 Phase 380~480V
Rated power voltage 3 Phase 380~480V 50Hz / 60Hz
Power voltage permissible
323~506V 50Hz / 60Hz
Power fluctuation
supply Power frequency permissible
±5%
fluctuation
Power source capacity kVA 1.8 3 4.8 6.9 10.4 13.8 19.5 27
Nature
Cooling method Forced air cooling
cooling
Weight kg 1.2 1.2 1.2 1.9 1.9 3.8 3.8 3.8

6
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.2 Common specification (Inverter characteristics)


SVPWM control, V/F control, facility vector control, Speed sensorless
Control method
vector control.
0.2~1000Hz (The starting frequency setting range is 0~600Hz). Please
Output frequency range
refer to P.187 in Chapter 4.
When P.187=0, if the frequency set value is below 100Hz, the resolution
Digital
will be 0.01Hz. If the frequency set value is above 100Hz, the resolution
setting
Resolution for will be 0.1Hz. When P.187=1, the resolution of frequency will be 0.1Hz.
setting frequency When setting DC 0~5V signals, the resolution will be 1/500;
Analog
When setting DC 0~10V or 4~20mA signals, the resolution will be
setting
1/1000.
Output frequency accuracy 0.01Hz
Voltage / frequency output Base voltage (P.19), base frequency (P.3) can be arbitrarily set.
characteristics Constant torque model, variable torque model can be selected (P.14).
Start torque 150% (1Hz): when use the facility vector control.
The torque boost setting range is 0~30% (P.0), auto boost, slip
Torque boost
compensation.
The acceleration/deceleration time (P.7, P.8), resolution:0.01s/0.1s,
Acceleration/deceleration switch by P.21. The setting range is 0.01~360s or 0.1~3600s for
curve characteristics selection. Different ‘acceleration/deceleration curve’ model can be
selected (P.29).
The DC braking action frequency is 0~1000Hz (P.10); the DC braking
DC braking time is 0~60 Seconds (P.11); and the DC braking voltage is 0~30%
(P.12). Linear braking and Idling braking selection (P.71).
Stalling protection The stalling protection level can be set to 0~400% (P.22).
Operation panel setting, DC 0~5V signal setting, DC 0~10V signal
setting, DC 4~20mA signal setting, 2 voltage input or one voltage and
Target frequency setting
one current input to select. Multi-speed stage levels setting,
Communication setting.
PID control Please refer to P.170~P.183 in Chapter 4.
Motor starting (STF, STR), the second function (RT), ‘16-speed
Multi-function control
operation’(RL, RM, RH, REX), external thermal relay (OH), reset
terminals
(RES), etc. (can be set by the user (P.80~P.84, P.86))
Multi-function
Inverter running (RUN), output frequency detection (FU), Up to
output
P.40 frequency (SU), overload detection (OL), zero current detection
terminals (SO,
Multi-functi (OMD), alarm (ALARM), Section detection (PO1), Periodical
SE)
on output detection (PO2), and Pause detection (PO3), Inverter output (BP),
Multi-function
terminals P.85 Commercial power-supply output (GP).
output relay
Multi function Multi-function DC (0~10V)(AM)
analogy meter output: output frequency, output current (P.54).

7
2. Introduction of Shihlin Inverter
Introduction of Inverter

Running status Output frequency monitoring, output current monitoring, and


monitoring output voltage monitoring.
Alarm history monitoring, alarm history clear, all parameters clear,
HELP mode
and soft version read.
Operation panel
Run indication lamp, frequency monitoring indication lamp,
LED indication voltage monitoring indication lamp, current monitoring indication
lamp(6) lamp, mode switching indication lamp, and PU/external terminals
control indication lamp.
RS485 Internal RS485 communication.
Communication Optional function: Terminal block communications expansion board,
function Optional
RJ11, RJ-45, Profibus, DeviceNet Terminal block communication
function
expansion board.
Output short circuit protection,Over-current protection, P-N
over-voltage protection, voltage too low protection, motor over heat
Protection mechanism
protection (P.9), IGBT module over heat protection, braking
/ Alarm function
transistor abnormality protection, communication abnormality
protection, etc.
Ambient
-10 ~ +50℃ (non-freezing)
temperature
Ambient
Below 90%Rh (non-condensing)
humidity
Environmental Storage
-20 ~ +65℃
condition temperature
Environment
In room, no corrosive gas, no flammable gas, no flammable dust
around
Altitude and
Below 1000 meters, below 5.9m/s2 (0.6G).
vibration
Certification Meet the requirements of CE certification standards (the –DL type).

Note: 1.If several multi-function output relays are needed, you can choose the I/O expansion board, on which there
are 2 multi-function output relays. For detailed instruction, please refer to appendix 5.
2. Communications expansion board option details, please refer to Appendix 5.
3. Profibus is the registered trademark of Profibus international.
4. DeviceNet is the registered trademark of ODVA (Open Device Vendor Association).

8
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.3 Mechanical Dimensions

2.3.1 Form

2.3.2 Dimension
Model D(mm) W(mm) H(mm) A(mm) B(mm) C(mm)
SE2-021-0.4K 148 85 148 75 138 Φ5
SE2-021-0.75K 148 85 148 75 138 Φ5
SE2-021-1.5K 186 100 157 90 176 Φ5
SE2-021-2.2K 186 100 157 90 176 Φ5
SE2-023-0.4K 148 85 148 75 138 Φ5
SE2-023-0.75K 148 85 148 75 138 Φ5
SE2-023-1.5K 148 85 148 75 138 Φ5
SE2-023-2.2K 186 100 157 90 176 Φ5
SE2-023-3.7K 186 100 157 90 176 Φ5
SE2-023-5.5K 266 141 201.5 126 244 Φ6
SE2-023-7.5K 266 141 201.5 126 244 Φ6
SE2-043-0.4K 148 85 148 75 138 Φ5
SE2-043-0.75K 148 85 148 75 138 Φ5
SE2-043-1.5K 148 85 148 75 138 Φ5
SE2-043-2.2K 186 100 157 90 176 Φ5
SE2-043-3.7K 186 100 157 90 176 Φ5
SE2-043-5.5K 266 141 201.5 126 244 Φ6
SE2-043-7.5K 266 141 201.5 126 244 Φ6
SE2-043-11K 266 141 201.5 126 244 Φ6

9
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.4 Name of each part

2.4.1 Nameplate and model

Style No. : SE2-021-0.75K-DL

Input : 14A 3PH AC380~480V 50/60Hz


Output : 13A MAX 3PH AC380~480V 5.5KW
FREQ. Range : 0.2~1000Hz

Serial NO. : EC00001

MFG. NO. : L2L0072

2.4.2 SE2-0XX-0.4K~11K (0.5HP~15HP)

When wiring, the wire must go through the ‘wiring outlet’ before connecting with the terminal bank.

10
2. Introduction of Shihlin Inverter
Introduction of Inverter

Note: 1. The enlarge figure of the control-circuit terminal block nameplate is as follows:

2. There’s no screw for the 1-Phase type.

11
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.5 Installation and wiring

2.5.1 Transport
Handling must take the fuselage, not only take cover or any part of the inverter, or it may drop out
then cause dangerous.

2.5.2 Stockpile
This product before installing must be placed in the packaging, if not use, in order to change the
frequency which can meet the company's warranty scope and future maintenance, must pay attention
to the following matters when storage:
1. Must be placed without dirt, dry place.
2. The environment temperature must be stored position in -20℃ to +65℃.
3. Storage location relative humidity must from 0% to 95% range, and no condensation.
4. Avoid stored in contains corrosion gas, liquid environment.
5. The best suitable packing on shelves or mesa.

Note: 1.If meet the standard requirements, such as humidity temperature changes also occurred hurriedly
condensation and icy may occur in this place, should be avoided.
2. Don't directly on the ground, also should be on appropriate shelves, and if the bad surroundings, it should
be placed in the bag of desiccant.
3. If the custody period more than 3 months, the ambient temperature requirements shall not be higher than
30 degrees. It is to consider the electrolytic capacitors no electricity deposited, when high temperature, the
characteristic easy degradation.
4. Inverter installed in the control device or the plate when not used (in construction which especially the
extra humid and dust), inverter should been remove, move put in accordance with the above mentioned
storage conditions appropriate environments.
5. The electrolytic capacitors is long-term no electricity, the characteristic easy degradation. Do not place in
the no state electricity more than one year.

2.5.3 EMC Installation instructions


Inverter is the same as other electrical and electronic equipment, when working in a power system, it
is the electromagnetic interference sources, and also is the electromagnetic receiver. The working
principle of inverter determines that it will produce certain electromagnetic interference and noise, in
order to guarantee the inverter to the electromagnetic environment in certain work, in designed, it
must have a certain interference of electromagnetic interference ability. In order to make the drive
system can normal operation, and meet the challenge which CE declared, please meet the following
several aspects in installation:
1. Field wiring
Power line from power transformer independent power supply, generally uses five core or four core,
forbidden neutral and ground share a thread.

12
2. Introduction of Shihlin Inverter
Introduction of Inverter

Commonly signal wire (weak) and power lines (heavy) are in control cabinet, to inverterr, electric
line of force divided into incoming lines and tail wire. In wiring, signal wire and power lines should
distributed in different regions, in close (within 20cm), parallel lines and interlace lines are
unallowed strictly, and the two cannot be tied together. If the signal cable must pass through between
power lines, the two should maintain a 90 degree Angle. The parallel lines and interlace lines which
of power line can not crisscross wiring or be tied together, especially in occasions which noise filter
installed, it will make coupled noise when the electromagnetic noise through the distributed
capacitance, thus noise filter will out of action.
Generally the same controller with different electric equipment, such as inverter, filter, PLC,
measurement instrument, its transmitter electromagnetic noise to external and bear ability each are
not identical, this requires to classify these equipments, the classification can be divided into strong
noise quipment, and noise sensitive equipment, the similar equipmentmust be installation in the same
area, inhomogeneity equipment must be keep distance more than 20cm.
2. Input noise filter, input and output magnet ring (zero phase reactor)
Increase noise filter in the input terminal, which will isolate the inverter and the other equipment can
effectively reduce the conduction and radiation ability. Install the input reactor this synopsis
recommendation, can satisfy the limits value of conduction and radiation which CE declared. In the
input and output terminal increased the ferrite lateral auxiliary will be better effect.
3. Shield
Good shielding and grounding can greatly reduce the interference of inverter, and can improve the
anti-interference ability of the inverter. Using the good conduct electricity sheet metal sealing, and let
the sheet metal grounding, can satisfy the limits value of radiation which CE declared.
4. Grounding
Inverter at work must be safe and reliable grounding. Grounding is not only for equipment and safety,
but also is the simplest, the most efficient and the lowest cost method to solving the EMC problem,
should be prioritized. Please refer to the "terminal wiring" section.
5. Carrie Wave
The leakage current contains the leakage current from line to line or over the ground. It depends on
the size of the capacitance and the carrier frequency of the wiring system. The carrier frequency is
higher, the motor cable is longer, the cable cross-sectional area is larger, and the leakage current is
larger too. Reduce the carrier frequency can effectively reduce the leakage current, when a long line
of motor (50m above), the output side should be installed ac reactor or sine wave filter, when the
motor line is longer, every distance should to install a reactor.At the same time, reduce carrier
frequency can effectively reduce the conduction and radiation interference, in 2K carrier frequency,
can satisfy the limits value of the conduction and radiation which CE declared.

13
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.5.4 Installation notice


1. Please install in an upright direction 2. Proper clearance shall be kept from surroundings
when installing

3. The ambient temperature shall not exceed the 4. Correct position for installing in a protection
permissible value. cabin.

Ventilating funt

5. Please do not install the inverter on a surface of inflammable material such as wood etc.
6. Please do not install the inverter at places exposed to explosive gas, inflammable dust.
7. Please do not install the inverter at places with airborne oil mist and dust.
8. Please do not install the inverter at places exposed to corrosive gas, salt laden air.
9. Please do not install the inverter in the environment of high temperature and high humidity.

Note: 1.Only qualified electrical professional personnel can carry out the installation, wire arrangement,
dismounting and maintenance.
2. Please ensure to comply with the installation notice. In case the installation notice has not been fully
complied with and damage of the inverter or dangerous accidence thus be resulted in, our company will
not undertake any legal responsibility. In case there is any question when installing, please feel free to
contact us.

14
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.5.5 System wire arrangement of SE2-0XX-0.4K~11K (0.5HP~15HP) series

Power
Please follow the specific
Power power supply requirement
FUSE/NFB
supply shown in this manual.
There may be an inrush
Fuse/NFB current during power up.
Magnetic contactor Please refer to 2.7.1 and
select the correct fuse /NFB.

Input AC Line Reactor


Please do not use a Magnetic
Magnetic contactor as the I/O switch of
contactor the AC motor drive, as it will
reduce the operating life cycle
of the AC drive.

AC line reactor should be


Input AC installed to improve the input
EMI filter Line Reactor power factor. The wiring
distance should be less than
10m. Please refer to 2.7.6.
Braking resistor Zero-phase reactors are used to
R/L1 S/L2 T/L3
P
B
reduce radio noise especially
R B
B when audio equipment installed
PR U
E R
Zero-phase near the inverter. Effective for
Reactor noise reduction on both the
Braking unit input and output sides.
U/T1 V/T2 W/T3
Attenuation quality is good for a
wide range from AM band to
10Mhz. Please refer to 2.7.5.
Zero-phase Reactor
Used to reduce electromagnetic
EMI filter interference.

Output AC Line Reactor Braking unit Used to reduce stopping time of


the motor.

Motor surge voltage


amplitudes depending on
Output AC motor cable length. The output
Line Reactor AC line reactor is necessary to
Motor install on the inverter output
side. Please refer to 2.7.6.

15
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.5.6Terminal wire arrangement of SE2-0XX-0.4K~11K(0.5HP~15HP)series

===== Note: ==============================================================


1. In the above figure, Main circuit and control circuit wiring or ground wiring should be noted that
the thickness of wire.
2. For the usage of external thermal relay, please refer to P.80~P.84, P.86 in Chapter 4.
3. Make sure do not to short PC and SD.
4. In the above figure, Dotted line metal, please refer 2.5.7
5.The SE2-TYPE inverter have internal RS485 communication, and also can uses pluggable
communications expansion boards CB01, CB02, CB03, PD01, DN01; For detailed instructions,
please refer to appendix 5.
=======================================================================

16
2. Introduction of Shihlin Inverter
Introduction of Inverter

Note: 1. For the multi-function control terminals, please refer to P.80~P.84, P.86, and for the multi-function output
terminals, please refer to P.40 in Chapter 4.
2. For SE2-0XX-0.4K~11K (0.5HP~15HP) series, the multi-function control terminals have both the ‘Sink
Input’ mode and the ‘Source Input’ mode. There is a Jumper that can be used to alternate between those
two modes. If the Jumper is on the left side, ‘Sink Input’ mode is chosen, and ‘Source Input’ mode is
chosen while on the right side. Shown as follows:

Sink Input Source Input

No matter what kind of multi-function control terminal it is, all of its outside wire arrangement can be
considered as a simple switch. If the switch is ‘on’, the control signal will be put into the terminal, if the
switch is ‘off’, the control signal is shut off.
If ‘Sink Input’ mode is selected, the function of the terminal is active when it is shorted with SD or
connected with the external PLC. In this mode, the current flows out of the corresponding terminal
when it is ‘on’. Terminal SD is common to the contact input signals. When using an external power
supply for transistor, please use terminal PC as a common to prevent misoperation caused by leakage
current.
Inverter
Inverter
PLC
STF
STF

STR
STR
I PC
PC
DC
DC
SD 24V I SD 24V

Sink Input: the multi-function control Sink Input: the multi-function control terminal
terminal is shorted directly with SD is connected directly with open-collector PLC

Inverter
PLC
STF

STR

PC
DC DC
24V 24V
SD
I
Sink Input: the multi-function control terminal is connected
with open-collector PLC and external power supply

17
2. Introduction of Shihlin Inverter
Introduction of Inverter

If ‘Source Input’ mode is selected, the function of the multi-function control; terminal is active when it is
shorted with PC or connected with the external PLC. In this mode, the current flows into the
corresponding terminal when it is ‘on’. Terminal PC is common to the contact input signals. When using
an external power supply for transistor output, please use terminal SD as a common to prevent
misoperation caused by leakage current.

Inverter Inverter
PLC
STF STF

STR STR

SD SD
I DC DC
24V I 24V
PC PC

Source Input: the multi-function control Source Input: the multi-function control terminal
terminal is shorted directly with PC is connected directly with open-emitter PLC

Inverter
PLC
STF

STR

SD
DC DC
24V 24V
PC
I

Source Input: the multi-function control terminal is


connected with open-emitter PLC and external power supply

Main-circuit terminals
Terminal name Remarks
R/L1- S/L2- T/L3 Connect to the commercial power supply.
U/T1-V/T2-W/T3 Connect to three-phase squirrel-cage motor.
P- PR Connect to brake resistors. (Note1, 2)
P- N Connect to brake unit. (Note3)
The grounding terminal for the case of the inverter. For 220V series, the third type
of grounding shall be adopted. For 440V series, special type of grounding shall be
adopted. (Note 4)

18
2. Introduction of Shihlin Inverter
Introduction of Inverter

Note: 1. For SE2-0XX-0.4K~11K (0.5HP~15HP) series of inverters, the brake resistor isn’t appended when sales.
2. For the related knowledge on regenerative voltage, please refer to P.30 in Chapter 4.
3. P and N are the positive and negative terminals of the internal DC voltage of the inverter. In order to
strengthen the braking capability during deceleration, it is suggested to purchase the option of ‘brake unit’
which is mounted between the terminals P and N. The ‘brake unit’ can effectively dissipate the feedback
energy from the motor to the inverter when decelerating. In case there is any problem on purchasing of
the ‘brake unit’, please feel free to contact us.
4. For safety and reduce noise, grounding terminals of inverter must to be good grounded. To avoid electric
shocks and fire accident, external metal wire of electrical equipment should be short and thick and it
should be connected to the special grounding terminals of inverter. If many of the inverters are placed
together, all inverters must be connected to the common ground. Please refer to the following picture and
determine not formed circuit between grounding terminal.

Best Average Poor

19
2. Introduction of Shihlin Inverter
Introduction of Inverter

Control terminals
Terminal Function
Terminal type Remarks and function description
name name
STF Optional
STR Optional These terminals are multi-function control terminals
M0 Optional (SINK/SOURCE mode switchable).

M1 Optional For detailed descriptions, please refer to P.80~P.84, P.86 in


On-off signal
M2 Optional Chapter 4.
input
RES Optional
Common reference Ground for STF, STR, M0, M1, M2 and
SD SD
RES
In the ‘Source input’ mode, it provides a common power
PC PC
supply for the terminals referred above.
10 --- The internal power is DC 10V at this terminal.
The input point of voltage signal 0~5V or
2 --- P.38
0~10V, is used to set the target frequency.
Analog signal The input point of voltage signal 0~5V or
input 0~10V/input points of current signal
4 --- P.39
4mA~20mA (switch with P.17), is used to set
the target frequency. (Note 1)
5 --- The common reference ground of 2, 4, 10 and AM.
A --- Normally, points A-C are always ‘open-circuit’, and points
Relay output B --- B-C are always ‘short-circuit’.Contact capacity is VDC30V /
C --- VAC230V-0.3A

The terminal can also be called ‘multi-function output


Open collector SO Optional terminal’. The function name can be set by P.40. For detailed
output description, please refer to P.40 in Chapter 4.
SE SE Open collector output reference ground.
Connected with an external analog meter to indicate the
Analog signal
AM --- output frequency or current. Contact capacity is 0~10VDC/2mA.
output
Please refer to P.54, P.55, P.56, P.191, and P.192 in Chapter 4.
Communication DA+ DA+
RS485 serial communication terminal
terminal DB- DB-
Dedicated Do not the connection during normal operation, may cause a
WF WF
terminals malfunction.

20
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.5.7 Wiring precautions


Main circuit wiring:
1. Do not connect the power supply wires to the ‘inverter’s output terminals U-V-W’ which are
designed for connecting motors, otherwise, the inverter may be damaged.
2. Please do not mount filtering capacitors, surge absorbers and electromagnetic contactors at the
output end of the inverter.

3. Please do not use ‘electromagnetic contactors’ or ‘no-fuse switches’ with an online power to start
or stop the motor.
4. Please ensure that the case of inverter and the motor are grounded, to avoid personnel electric
shock.
5. To appropriately select the diameter of the main wires and the corresponding wire terminals, the
no-fuse switches and the electromagnetic contactors, please refer to Section 2.7. And if the
inverter is far away from the motor, please employ a wire with larger diameter to ensure the
voltage drop along the wire within 2V. (The total length of the wire shall not exceed 500 meters)
6. ‘Pressing connection terminals with insulated sleeve’ shall be utilized for the wiring at the power
source side and the load side.
7. In a short period after the power supply is shut off, high voltage still exists between the terminals
P-N, thus please do not touch them within 10 minutes to avoid personnel electric shock.

Control circuit wire arrangement:


1. For wiring of signal input, ‘insulated wires’ must be used,and the ‘metal mesh’ of which must be
put to earth.
2. For wiring of the control board, wires with a diameter of 0.75mm2 are suggested to be used. And
for the stripping of the insulating layer, please comply with the instruction of the following
figure.

3. The control board wire (including signal input wire) shall be far away from the main circuit board
wire. Binding the control board wires together with the main circuit wires is strictly forbidden.
4. In the inverter, the ‘terminal SD’, ‘terminal SE’ and the ‘terminal 5’ are the referencing grounds
for the inner power sources which are isolated from each other.

21
2. Introduction of Shihlin Inverter
Introduction of Inverter

Note: 1. The terminal block screws must be screwed up tightly. Especially the wire cut pieces shall
not be left in the inverter.
2. Only qualified electrical professional personnel can carry out the installation, wire arrangement,
dismounting and maintenance.
3. Please comply with the wire arrangement notice. In case the installation has not been fully complied
with, and damage of the inverter or dangerous accidence thus be resulted in, our company will not
undertake any legal responsibility. In case there is any question on the wire arrangement, please feel
free to contact us.

22
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.6 Mini Jumper instruction


Main power isolated from earth:
1. If the inverter is supplied with a non-gronded power supply (IT power), the Mini jumper
must be cut off to prevent circuit damage (according to IEC61800-3) and reduce earth
leakage current.
2. Please switch the Mini jumper to “On” if the inverter has a build-in filter, but that time, the
earth leakage current will be increased. Please switch the Mini jumper to “Off” if the
inverter has not a build-in filter.
3. The Mini jumper is shown as follows:

==== Note: =============================================================


1. After applying power to the inverter, do not cut off the Mini jumper. Therefore, please make sure
that main power has been switched off before cutting off the Mini jumper.
2. The gap discharge may occur when transient voltage is high than 1000V. Besides, electro-magnetic
compatibility of the inverter will be lower after cutting the Mini jumper.
3. Do not cut the Mini jumper when main power is grounded. To prevent drive damage, the Mini
jumper shall be cut off if the inverter is installed on an ungrounded power system or a high
resistance-grounded (over 30 ohms) power system or a corner grounded TN system.
4. The Mini jumper cannot be cut when Hi-pot tests are performed.
========================================================================
23
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.7 Selection of peripheral equipments

2.7.1 No-fuse switch


Applicable NFB/MCCB type Applicable MC
Power source (Shihlin) type (Shihlin)
Inverter type Motor capacity
capacity Taiwan/
Taiwan Motherland
Motherland
SE2-021-0.4K 220V 0.5HP 1.8kVA NF30 5A BM30SN3P5A S-P11
SE2-021-0.75K 220V 1HP 3kVA NF30 10A BM30SN3P10A S-P11
SE2-021-1.5K 220V 2HP 4.5kVA NF30 15A BM30SN3P15A S-P11
SE2-021-2.2K 220V 3HP 6.4kVA NF30 20A BM30SN3P20A S-P11/ S-P12
SE2-023-0.4K 220V 0.5HP 1.8kVA NF30 5A BM30SN3P5A S-P11
SE2-023-0.75K 220V 1HP 3kVA NF30 10A BM30SN3P10A S-P11
SE2-023-1.5K 220V 2HP 4.5kVA NF30 15A BM30SN3P15A S-P11
SE2-023-2.2K 220V 3HP 6.4kVA NF30 20A BM30SN3P20A S-P11 / S-P12
SE2-023-3.7K 220V 5HP 10kVA NF30 30A BM30SN3P30A S-P21
SE2-023-5.5K 220V 7.5HP 13.8kVA NF50 50A BM60SN3P50A S-P21
SE2-023-7.5K 220V 10HP 19kVA NF100 60A BM60SN3P60A S-P21
SE2-043-0.4K 440V 0.5HP 1.8kVA NF30 3A BM30SN3P3A S-P11
SE2-043-0.75K 440V 1HP 3kVA NF30 5A BM30SN3P5A S-P11
SE2-043-1.5K 440V 2HP 4.8kVA NF30 10A BM30SN3P10A S-P11
SE2-043-2.2K 440V 3HP 6.9kVA NF30 15A BM30SN3P15A S-P21
SE2-043-3.7K 440V 5HP 10.4kVA NF30 20A BM30SN3P20A S-P21
SE2-043-5.5K 440V 7.5HP 13.8kVA NF30 30A BM30SN3P30A S-P21
SE2-043-7.5K 440V 10HP 19.5kVA NF50 50A BM60SN3P50A S-P21
SE2-043-11K 440V 15HP 27kVA NF100 60A BM60SN3P60A S-P21

24
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.7.2 Power cable specification/pressing connection terminals specification


Pressing connection terminal
Power cable specification
specification (used by power cables)
Inverter type Cables for the Cables for the Cables for the Cables for the
power supply output U.V.W power supply output U.V.W
R.S.T (mm2) (mm2) R.S.T (mm ) 2
(mm2)
SE2-021-0.4K 2 2 2-4 2-4
SE2-021-0.75K 2 2 2-4 2-4
SE2-021-1.5K 2 2 2-4 2-4
SE2-021-2.2K 3.5 3.5 5.5 - 4 5.5 - 4

SE2-023-0.4K 2 2 2-4 2-4


SE2-023-0.75K 2 2 2-4 2-4
SE2-023-1.5K 2 2 2-4 2-4
SE2-023-2.2K 2 2 2-4 2-4
SE2-023-3.7K 3.5 3.5 5.5 - 4 5.5 - 4
SE2-023-5.5K 5.5 5.5 5.5 - 5 5.5 - 5
SE2-023-7.5K 14 8 14.5 - 5 8-5

SE2-043-0.4K 2 2 2-4 2-4


SE2-043-0.75K 2 2 2-4 2-4
SE2-043-1.5K 2 2 2-4 2-4
SE2-043-2.2K 2 2 2-4 2-4
SE2-043-3.7K 2 2 2-4 2-4
SE2-043-5.5K 3.5 2 5.5 - 4 2-4
SE2-043-7.5K 3.5 3.5 5.5 - 4 5.5 - 4
SE2-043-11K 5.5 5.5 5.5 - 5 5.5 - 5

25
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.7.3 Brake resistors


Inverter type Brake resistor specification Inverter type Brake resistor specification
SE2-021-0.4K 100W 220Ω SE2-023-5.5K 1000W 25Ω
SE2-021-0.75K 150W 120Ω SE2-023-7.5K 1200W 20Ω
SE2-021-1.5K 300W 60Ω SE2-043-0.4K 80W 1000Ω
SE2-021-2.2K 300W 60Ω SE2-043-0.75K 100W 800Ω
SE2-023-0.4K 100W 220Ω SE2-043-1.5K 200W 320Ω
SE2-023-0.75K 150W 120Ω SE2-043-2.2K 300W 160Ω
SE2-023-1.5K 300W 60Ω SE2-043-3.7K 500W 120Ω
SE2-023-2.2K 300W 60Ω SE2-043-5.5K 1000W 75Ω
SE2-023-3.7K 400W 40Ω SE2-043-7.5K 1200W 75Ω
SE2-043-11K 1800W 40Ω

Note: 1. The brake resistor capacity listed in the above table is based on the condition that the regenerative brake
duty is 10% (that is, in case braking lasts for 5 seconds, another 45 seconds must be provided for heat
dissipation). The brake resistor wattage can be reduced according to the user’s application (quantity of
heat) and the regenerative brake duty. But the resistance must be larger than the value list in the above
table (otherwise damage of the inverter thus be resulted in).
2. In case frequent start and stop operations are required, a larger regenerative brake duty should be set;
meanwhile, a larger brake resistor should be employed correspondingly. If there is any problem about
selection of brake resistors, please feel free to contact us.

2.7.4 EMI filter

Inverter type Schaffner filter type Inverter type Schaffner filter type
SE2-021-0.4K SE2-043-0.4K
NF211B10/01
SE2-021-0.75K SE2-043-0.75K NF311A5/01
SE2-021-1.5K SE2-043-1.5K
NF211B20/01
SE2-021-2.2K SE2-043-2.2K
NF311A10/01
SE2-023-0.4K SE2-043-3.7K
NF311A5/01
SE2-023-0.75K SE2-043-5.5K
NF311A20/05
SE2-023-1.5K NF311A10/01 SE2-043-7.5K
SE2-023-2.2K SE2-043-11K NF311A30/05
NF311A20/05
SE2-023-3.7K
SE2-023-5.5K NF311A30/05
SE2-023-7.5K NF311A36/05

Note: Changzhou multi-pole filter is recommended.

26
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.7.5Zero-phase Reactor

UNIT:mm
P41T63*38*25C

38

63 25

Motor capacity Recommended Wire


Qty. Wiring Method
HP kW Size (mm2)
1/2 0.4
1 0.75 0.5-5.5
2 1.5 1 Diagram A
220V series 3 2.2 3.5-5.5
5 3.7 5.5
7.5 5.5
4 8 Diagram B
10 7.5
1/2 0.4
1 0.75
2 1.5 0.5-5.5
3 2.2 1 Diagram A
440V series
5 3.7
7.5 5.5 3.5-5.5
10 7.5 5.5
15 11 4 8-14 Diagram B

27
2. Introduction of Shihlin Inverter
Introduction of Inverter

Diagram A: Please wind each 4 times around the core.

Diagram B: Please put all wires through 4 cores in series without winding.

28
2. Introduction of Shihlin Inverter
Introduction of Inverter

2.7.6 Input/Output Reactor


Input AC Line Reactor
220V,50/60Hz,Three-phase
Rated Amps of
kW 2% impedance reactor types 4% impedance reactor types
inverter
0.4 3 ACL-0005-EISC-E3M8 ACL-0005-EISC-E5M6
0.75 5 ACL-0005-EISC-E3M8 ACL-0005-EISC-E5M6
1.5 8 ACL-0010-EISC-E1M5 ACL-0010-EISC-E2M8
2.2 11 ACL-0015-EISC-E1M0 ACL-0015-EISC-E1M9
3.7 17.5 ACL-0020-EISC-EM75 ACL-0020-EISC-E1M4
5.5 24 ACL-0030-EISC-EM60 ACL-0030-EISC-EM93
7.5 33 ACL-0040-EISC-EM42 ACL-0040-EISC-EM70

440V,50/60Hz,Three-phase

Rated Amps of
kW 2% impedance reactor types 4% impedance reactor types
inverter
0.4 1.5 ACL-0005-EISC-E3M8 ACL-0005-EISC-E5M6
0.75 2.6 ACL-0005-EISC-E3M8 ACL-0005-EISC- E5M6
1.5 4.2 ACL-0005-EISC-E3M8 ACL-0005-EISC- E5M6
2.2 6 ACL-0007-EISC-E2M5 ACL-0007-EISC-E3M5
3.7 9 ACL-0010-EISC-E1M5 ACL-0010-EISC-E2M8
5.5 12 ACL-0015-EISC-E1M0 ACL-0015-EISC-E1M9
7.5 17 ACL-0020-EISC-EM75 ACL-0020-EISC-E1M4
11 23 ACL-0030-EISC-EM60 ACL-0030-EISC-EM93

Output AC Line Reactor


220V,50/60Hz,Single-phase

Rated Amps of
kW 1% impedance reactor types 2% impedance reactor types
inverter
0.4 3 OCL-0005-EISC-E1M4 OCL-0005-EISC-E2M8
0.75 5 OCL-0005-EISC-E1M4 OCL-0005-EISC-E2M8
1.5 8 OCL-0010-EISC-EM70 OCL-0010-EISC- E1M4
2.2 11 OCL -0015-EISC-EM47 OCL -0015-EISC-EM93

29
2. Introduction of Shihlin Inverter
Introduction of Inverter

220V,50/60Hz,Three-phase
Rated Amps of
kW 1% impedance reactor types 2% impedance reactor types
inverter
0.4 3 OCL-0005-EISC-E1M4 OCL-0005-EISC-E2M8
0.75 5 OCL-0005-EISC-E1M4 OCL-0005-EISC-E2M8
1.5 8 OCL-0010-EISC-EM70 OCL-0010-EISC- E1M4
2.2 11 OCL -0015-EISC-EM47 OCL -0015-EISC-EM93
3.7 17.5 OCL -0020-EISC-EM35 OCL -0020-EISC-EM70
5.5 24 OCL -0030-EISC-EM23 OCL -0030-EISC-EM46
7.5 33 OCL-0040-EISC-EM18 OCL-0040-EISC-EM35

440V,50/60Hz,Three-phase

Rated Amps of
kW 1% impedance reactor types 2% impedance reactor types
inverter
0.4 1.5 OCL-0005-EISC-E1M4 OCL-0005-EISC-E2M8
0.75 2.6 OCL-0005-EISC-E1M4 OCL-0005-EISC-E2M8
1.5 4.2 OCL-0005-EISC-E1M4 OCL-0005-EISC-E2M8
2.2 6 OCL-0007-EISC-E1M0 OCL-0007-EISC-E1M9
3.7 9 OCL-0010-EISC-EM70 OCL-0010-EISC- E1M4
5.5 12 OCL -0015-EISC-EM47 OCL -0015-EISC-EM93
7.5 17 OCL -0020-EISC-EM35 OCL -0020-EISC-EM70
11 23 OCL -0030-EISC-EM23 OCL -0030-EISC-EM46

Note: Shanghai yingfeng filter is recommended.

30
3. Primary operation
Primary operation

3.1 Operating modes of the inverter


● The operation modes are related to the reference source of the target frequency and the signal
source of the motor starting. The Shihlin SE2-TYPE inverter totally has 9 kinds of operation
modes, namely, ‘PU mode’, ‘JOG mode’, ‘external mode’, ‘communication mode’, ‘combined
mode 1’, ‘combined mode 2’ , ‘ combined mode 3’ , ‘combined mode 4’ and ‘combined mode
5’.
Related Operation The reference source of The signal source of
values Remarks
parameters mode target frequency motor starting
FWD REV
PU mode Press the key or on
DU03B operation panel
( ) the DU03B operation
panel
FWD REV The ‘PU
JOG mode Press the key or on mode’,
The set value of P.15
( ) the DU03B operation ‘External
panel mode’ and
0
‘External voltage/current ‘JOG mode’
signal’, ‘combination of are valid and
External terminals
multi-speed stage levels’ interchangeab
External
or External JOG le.
mode
Frequency of each section
( )
in Programmed
External terminal STF
operation mode
(P.131~P.138)
Operation
PU mode The ‘PU
mode Equal to the ‘PU mode’ when P.79=0
( ) mode’ and
selection
‘JOG mode’
P.79 1
JOG mode are valid and
Equal to the ‘JOG mode’ when P.79=0
( ) interchangeab
le.
External
2 mode Equal to the ‘External mode’ when P.79=0
( )
Communica
3 tion mode Communication Communication (Note )
( )
Combined
4 mode 1 DU03B operation panel External terminals
( )
Combined ‘External voltage/current Press the key FWD or REV on
5 mode 2 signal’ or ‘combination of
the DU03B operation
( ) multi-speed stage levels’
panel

31
3. Primary operation
Primary operation

Related Operation The reference source of The signal source of


values Remarks
parameters mode target frequency motor starting
Communication,
Combined
‘combination of
6 mode 3 External terminals
multi-speed stage levels’
( )
or External JOG(P.15) (Note )
Operation
Combined ‘External voltage/current
mode
7 mode 4 signal’ or ‘combination of Communication
selection
( ) multi-speed stage levels’
P.79
DU03B operation panel,
Combined
‘combination of
8 mode 5 External terminals
multi-speed stage levels’
( )
or external JOG(P.15)

Note: If P.79=0, the inverter is in external mode ( ) when it is started, and the operating mode
can be shifted by setting P.79.

32
4. 3. Primary operation
Primary operation

3.1.1 The flow charts for transferring operation modes with DU03B
P.79=0

PU Hz PU Hz
A A
MON V MON V
RUN EXT RUN EXT

PU Hz
A
MON V
RUN EXT

P.79=1

PU Hz PU Hz
A A
MON V MON V
RUN EXT RUN EXT

Note: 1. In ‘PU mode’, the indicating lamp in the operation panel will be lit.
2. In ‘external mode’ the indicating lamp will be lit.
3. In ‘combined mode 1, 2, 3, 4 or 5’, the indicating lamp will be flickered
4. In ‘JOG mode’, the indicating lamp will be lit, and at the same time the display screen
will display while the motor is not running.
5. If P.79=2, 3, 4, 5, 6, 7 or 8, the operation mode will be constant, so there are no flow charts for it.

3.2 Working modes of a operation panel


● The DU03B operation panel can be used to monitor the output frequency, output current, and
output voltage, browse the alarming information, set parameters and target frequency,etc.
Therefore, there are totally 5 working modes for a operation panel, namely, ‘operating mode’,
‘monitoring mode’, ‘frequency setting mode’, ‘parameter setting mode’, and ‘HELP mode’.

3.2.1 The flow charts for transferring working modes with DU03B
Power on state

PU Hz
MON A
V
RUN EXT

After 2 seconds

PU Hz MODE PU Hz
A A
MON V MON V
RUN EXT RUN EXT

MODE MODE

MODE MODE
PU Hz PU Hz PU Hz
A A MON A
MON V MON V V
RUN EXT RUN EXT RUN EXT

33
3. Primary operation
Primary operation

Note: 1. For detailed operating flow in monitoring mode, please refer to Section 3.2.2.
2. For detailed operating flow in frequency setting mode, please refer to Section3.2.3.
3. For detailed operating flow in parameter setting mode, please refer to Section 3.2.4.
4. For detailed operating flow in operating mode, please refer to Section 3.1.1.
5. For detailed operating flow in HELP mode, please refer to Section 3.2.5.

3.2.2 The operating flow charts for monitoring mode with DU03B
● PU mode as an example:
Display output Display
frequency output voltage

PU Hz SET PU Hz
MON
A
MON A
V V
RUN EXT RUN EXT

SET SET

PU Hz SET PU Hz
MON A MON
A
V V
RUN EXT RUN EXT

Display output
Aalarm record
current

Note: 1. When in ‘monitoring output frequency’ mode, the indicating lamp of and will be
lit, and at the same time the screen will display the current output frequency.
2. When in ‘monitoring output voltage’ mode, the indicating lamp of and will be lit, and
the screen will display the current output voltage value.
3. When in ‘monitoring output current’ mode, the indicating lamp of and will be lit, and
the screen will display the current output current value.
4. When in ‘browsing alarm record’ mode, the indicating lamp of will be lit, and the screen will
display the current alarm code.
5. For the alarm codes, please refer to Appendix 2.

3.2.3 The operating flow charts for frequency setting mode with DU03B

Read previous target Read new target


frequency frequency

PU Hz PU Hz
MON
A
MON A
V V
RUN EXT RUN EXT

34
3. Primary operation
Primary operation

Note: 1. When the inverter runs, the frequency can be changed by pressing and .
2. In the frequency setting mode, the indicating lamp will be lit, but will not be lit.
3. When setting frequency in PU mode, the set value can not exceed the upper frequency. When high
frequency is needed, the upper frequency should be changed first.

3.2.4 The operating flow charts for parameter setting mode with DU03B
Parameter setting mode
operating flow chart
PU Hz
MON A
V
RUN EXT

SET The first bit flashes The second bit flashes The third bit flashes

SET
PU Hz SET PU Hz A PU Hz
MON
A
MON A
V V MON V
RUN EXT RUN EXT RUN EXT

SET
SET
SET

PU Hz PU Hz PU Hz
MON A MON A MON A
V V V
RUN EXT RUN EXT RUN EXT

SET

PU Hz A
SET PU Hz PU Hz
A A
MON V MON V MON V
RUN EXT Over RUN EXT RUN EXT
0.5s
Enter the next
setting mode SET Read previous set value
Set value written
Read new set value
and it flashes
PU Hz
MON A
V
RUN EXT

Note: In the parameter setting mode, both the indicating lamp of and will turn off. Please
SET
make sure to hold down the key for more than 0.5s when writing the set value of the parameters.

35
3. Primary operation
Primary operation

3.2.5 The operating flow charts for HELP mode with DU03B
PU Hz
A
MON V
RUN EXT

Alarm history SET

SET
PU Hz PU Hz
A A
MON V MON V
RUN EXT RUN EXT
Flicker

Alarm history clear

SET SET
SET Hz
PU Hz PU Hz PU Hz PU Hz PU A
A A A A V
MON V MON V MON V MON V MON
超过 0.5s EXT
RUN EXT RUN EXT RUN EXT RUN EXT RUN

All parameters
clear
SET SET SET
PU Hz PU Hz PU Hz PU Hz PU Hz
A A A A A
MON V MON V MON V MON V MON V
超过0.5s
RUN EXT RUN EXT RUN EXT RUN EXT RUN EXT

Software version
clear

SET
Flicker
PU Hz PU Hz
A A
MON V MON V
RUN EXT RUN EXT
Software version

Alarm history

P Hz P Hz
MON A MON A
V V
RUN EXT RUN EXT

P Hz P Hz
MON A MON A
V V
RUN EXT RUN EXT

SET SET
Note: 1. In E.HIS monitoring mode, press down the key to display the alarm code (press down the
key again to return to E.HIS monitoring mode), then four latest alarm codes can be displayed by pressing

down the key. For the alarm code, please refer to appendix 2.

SET
2. In Er.CL monitoring mode, press down the key and the screen will display “0” (press down the

SET
key again to return to Er.CL monitoring mode), then change it to “1” with , the screen will

SET
display Er.CL, Hold down the key again for more than 0.5s and the screen will display Er.CL and

MODE
flicker, indicating that all the alarm records are being cleared. At this time, you should press to
return to HELP mode again.

36
3. Primary operation
Primary operation

SET
3. In ALLC monitoring mode, press down the key and the screen will display “0” (press down the

SET
key again to return to ALLC monitoring mode), then change it to “1”with , the screen will

SET
display ALLC, Hold down the key again for more than 0.5s and the screen will display ALLC and
flicker, indicating that all the parameter values are being initialized to the factory default. At this time,
MODE
you should press to return to HELP mode anain.
4. In Sn monitoring mode, the software version of the inverter can be read.

3.3 The basic operation procedure for PU mode (P.79=0 or 1 )


Steps Description

• Change the operation mode to PU mode, and the indicating lamp of will be lit.
Note: 1. When P.79=0, after the power is switched on or the inverter is reset, the inverter will
1
enter external mode first.
2. For selection and shifting of operation modes, please refer to Section 3.1.

• Enter frequency setting mode, and write the target frequency into the memory.
2
Note: For the detailed setting procedure, please refer to Section 3.2.

FWD REV
• Press or , then the motor will run.
• At this time, the indicating lamp of will flicker, indicating that the motor is
running. The DU03B operation panel then enters the monitoring mode automatically. (For
3
detailed descriptions, please refer to P.110 in Chapter 4.)
Note: 1. For the operating flow of monitoring mode, please refer to Section 3.2.
2. While the motor is running, the frequency setting mode is also valid, and thus the target
frequency can be changed to regulate the motor speed.
STOP
RESET
• Press , then the motor will decelerate, till it stops.
4
• The indicating lamp of will not turn off until the inverter stops outputting voltages.

3.4 The basic operation procedure for external mode ( , P.79=0 or 2)

Steps Description
• Change the operation mode to the external mode, and then the indicating lamp of
1 will be lit.

37
3. Primary operation
Primary operation

Steps Description
MODE
Note: 1. When P.79=0, after the power is turned on or the inverter is reset, press to shift to

1 ‘operating mode’. The inverter will enter the external mode first, then press or to
shift to PU mode.
2. When P.79=2, the inverter will always in external mode.
3. For selection and shifting of operation modes, please refer to Section 3.1.
• If the target frequency is set by the input signal across terminal 4-5, please refer to P.39 in
Chapter 4.
• If the target frequency is set by multi-speed stage levels, please refer to P.4 in Chapter 4.
2 • If the target frequency is set by the input signal across terminal 2-5, please refer to P.38 in
Chapter 4.
• If programmable operating mode is chosen, please refer to multi-function terminals
P.80~P.84、P.86 in Chapter 4.
• Turn on STF or STR, the motor will run.
• At this time, the indicating lamp of will flicker which indicates that the motor is
running.
Note: 1. For advanced setting of the starting terminals STF and STR, please refer to P.78 and
3
multi-function terminal P.80~P.84、P.86 in Chapter 4.
2. For the operating procedure of the monitoring mode, please refer to Section 3.2.
3. If programmed operation mode is chosen, STF becomes starting signal and STR becomes pause
signal, they are not Run Forward or Run Reverse terminals anymore.
• Turn off STF or STR, and the motor will decelerate till it stops.
4 • The indicating lamp of will not turn off until the inverter has stopped putting out
voltages.

3.5 The basic operation procedure for JOG mode ( , Pr79=0 or 1)


Steps Description
• Change the operation mode to the JOG mode; and the indicating lamp of will be
1 lit, and the screen will display before the motor runs.
Note: For selection and shifting of the operation modes, please refer to Section 3.1.
FWD REV
• Press down or , then the motor will run. At this time, the indicating lamp of
will flicker which indicates that the motor is running.
FWD REV
2 • When releasing or , the motor will decelerate, till it stops. The indicating lamp
will not turn off until the motor has stopped putting out voltages.
Note: 1. For the operating procedure of the monitoring mode, please refer to Section 3.2.
2. In the JOG mode, the target frequency is the value of P.15, and the acceleration/deceleration
time is the value of P.16. Please refer to Pr.15 in Chapter 4.

38
3. Primary operation
Primary operation

3.6 The basic operation procedure for communication mode ( , P.79=3)


● In communication mode, the user can set parameters, run/stop, and reset the inverter by
communication. Please refer to P.33 for details.

3.7 The basic operation procedure for Combined mode 1 ( , P.79=4 )


Steps Description
• In Combined mode 1, the indicating lamp of will flicker.
1
Note: For selection and shifting of operation modes, please refer to Section 3.1.
• Enter the frequency setting mode, and write the target frequency into the memory.
2
Note: For the operating procedure of the frequency setting mode, please refer to Section 3.2.
• Set the target frequency by DU03B operation panel and start the inverter by the external
terminals.
3 • At this time, the indicating lamp of will flicker which indicated that the motor is
running.
Note: For the operating procedure of the monitoring mode, please refer to Section 3.2.
• Turn off STF or STR, and then the motor will decelerate, till it stops.
4 • The indicating lamp of will not turn off until the inverter has stopped putting out
voltages.

3.8 The basic operation procedure for Combined mode 2 ( , P.79=5


Steps Description
• In Combined mode 2, the indicating lamp of will flicker.
1 Note: For selection and shifting of the operation mode, please refer to Section 3.1.
• The target frequency is set by external terminals:
• If the target frequency is set by the input signal across terminal 4-5, please refer to Pr39 in
Chapter 4.
2
• If the target frequency is set by multi-speed stage levels, please refer to Pr4 in Chapter 4.
• If the target frequency is set by the input signal across terminal 2-5, please refer to Pr38 in
Chapter 4.
FWD REV
• Press down or , and then the motor start running. At this time, the indicating lamp of
will flicker, which indicates that the motor is running.
3
Note: 1. For the operating procedure of the monitoring mode, please refer to Section 3.2.
2. In case the motor is running, the frequency setting mode is also valid, and thus the target
frequency can be changed to regulate the motor speed.
STOP
RESET
• After pressing down , the motor will decelerate, till it stops.
4
• indicating lamp of will not turn off until the inverter has stopped putting out
voltages.

39
3. Primary operation
Primary operation

3.9 The basic operation procedure for Combined mode 3 ( , P.79=6)


● The target frequency is determined by communication. When M0, M1, M2 and REX are ‘on’, the
target frequency is determined by combination of multi-speed stage levels (Please refer to
P.4~P.6, P.80~P.84, P.86). When EXJ is ‘on’, the target frequency is determined by the set value of
P.15. Acceleration/deceleration time is set by the value of P.16. The inverter starting is determined
by external terminals. The functions of P.996, P.998 and P.999 can be accomplished by
communication.

3.10 The basic operation procedure for Combined mode 4 ( , P.79=7)


● The target frequency of the inverter is determined by the external terminals, ‘external voltage
signal’, ‘external current signal’ or ‘combination of multi-speed stage levels’ terminals. The
inverter starting is determined by communication (including ‘Reset’).

3.11 The basic operation procedure for Combined mode 5 ( , P.79=8)


● The target frequency is determined by DU03B operation panel. When M0, M1, M2 and REX are
‘on’, the target frequency is determined by combination of multi-speed stage levels (Please refer
to P.4~P.6, P.80~P.84, P.86). When EXJ is ‘on’, the target frequency is determined by the set value
of P.15. Acceleration/deceleration time is set by the value of P.16. The inverter starting is
determined by external terminals.

3.12 Operation

3.12.1 Check and preparation before operation


Before the start of operation shall examine the following several aspects:
1. Check the wiring is ture or not. Especially check ac motor driver output terminals (V, U, W)
cannot be connected to the power, confirm grounding terminals ground well.
2. Confirm the terminal or the exposure of charged have short circuit or not.
3. Confirm terminal connections, plug connector (optional) and screw fastening are all fastening or
not.
4. Confirm motor have not connect the mechanical device.
5. All switch must disconnected before power on. Ensure the inverter won't start and without
abnormal action when power on.
6. Turn on the power must after cover installation.
7. Wet hand prohibit operation switch.
8. Ensure the following several aspects after power on:
1). Operation panel should be shown no fault.

(1). If the keyboard panel is not chosen, the indicating lamp of POWER is lit, and indicating
lamp of ALARM is not lit。
(2). If the keyboard panel is n chosen, the indicating lamp of and are all lit。

40
3. Primary operation
Primary operation

3.12.2 Operating methods


Various operating methods,please refer to the basic operating procedures of chapter 3 and parameter
description of chapter 4. According to the application requirements and regulations to select the most
appropriate operation method, usually with operating methods are shown below:
The signal source of
Operating methods The reference source of target frequency
motor starting
REV
Operation panel or FWD
or

M0 Parameter
seting:
M1 P.4=40
P.5=30 Input by external
External terminals M2 P.6=10
terminals:STF-SD
signal operation
STR-SD
SD

2-5,4-5

3.12.3 Trial Run


Confirm cables and no abnormalities before the operation you can try running. After power on, the
inverter is in the external mode.

1. After power on, ensure the indicating lamp of power is lit.


2. Please pick a switch between STF and SD or STR and SD.
3. Please pick a potentiometer among 2-5-10 or provide 0 ~ 5V dc between 2 and 5.
4. Please adjust potentiometer or 0 ~ 5V dc a minimum value (under 1V).
5. If STF on, forward rotation; if STR on, reverse rotation; Turn off STF or STR, and the motor will
decelerate till it stops.
6. Ensure the following several aspects:
1). Motor rotation direction is correct or not.
2). Motor rotating smoothly (whether there is no abnormal noise and vibration).
3). Whether or not smooth for acceleration/deceleration.

If there is operation panel, commissioning as follows:


1. Operation panel connected to inverter properly.
2. Change the operation mode to PU mode after power on, and the screen will display 50/60Hz.

3. Press button to set the target frequency is about 5Hz.


STOP
FWD REV RESET
4. Press , forward rotation; press , reverse rotation; press then the motor will decelerate till
it stops.

41
3. Primary operation
Primary operation

5. Ensure the following several aspects:


1). Motor rotation direction is correct or not.
2). Motor rotating smoothly (whether there is no abnormal noise and vibration).
3). Whether or not smooth for acceleration/deceleration.

If there is no abnormal condition, increasing frequency to test run continue, through the above
commissioning, without any abnormal situation, can be put into operation.

Note: If inverter and motor running anomalies, shall be stopped working immediately, and according to the "fault
diagnosis," check anomalies causes. After inverter stop output, but the power terminal (R/S/T) of main
circuit is not disconnected, if you touching the output terminals (U/V/W) of inverter, may occur shock.
Otherwise, even cut off major loop power, because the filter capacitor has recharging voltage, discharge end
need some time, After cut off major loop power, wait for the indicating lamp of power burn out, and use a dc
voltage meter to test intermediate dc loop, confirm below safe voltage value, then you can contact the circuit
which inside inverter.

42
4. Parameter description
Parameter

4.1 Torque Boost (P.0, P.46)


P.0 “Torque Boost” Related parameters

P.46 “Second Torque Boost” P.3“Base frequency”


P.19“Base Voltage”
P.47“Secone base frequency”
P.80~P.84, P.86
“Multi-function terminals selection”

● For an inverter controlled by V/F mode, when the motor starts up, since the output voltage of the
inverter is inadequate, the starting torque is usually inadequate. In this case, the output voltage can
be improved by properly setting the torque boost (P.0), and thus a better starting torque can be
acquired.

Parameter Factory setting Setting range Remarks


6%(0.2Kw~0.75Kw)
4%(1.5Kw~3.7Kw)
0 0~30% ---
3%(5.5Kw~7.5Kw)
2%(11Kw)
46 9999 0~30%, 9999 9999: function invalid

Output
voltage
100%

the set value of


P.0、P.46 Base frequency

Output frequency

<Setting>
• If P.0=6% and P.19=220V, and when output frequency of the inverter is 0.2Hz, the output voltage
0.2Hz
P.19 × ( + P.0 ) = 220V × ( 0.004 + 6% ) = 14.08V
50Hz
is:
• If RT is ‘on’, P.46 “Second Torque Boost” is valid.
Note: 1. If the set value of P.0 is too high, it will result in the action of the current protection of the inverter or the
inverter will be disabling to start smoothly.
2. The Second Function is valid only when P.44≠9999.
3. RT referred in this paragraph is the name of ‘multi-functional control terminal’. For the selection of the
function and use of the multi-function control terminal, please refer to P.80~P.84, P.86. For the wiring,
please refer to section 2-5.

43
4. Parameter description
Parameter

4.2 The output frequency range (P.1, P.2, P.18)


P.1 “Maximum frequency” Related parameters

P.2 “Minimum frequency” P.13“Starting frequency”

P.18 “High-speed maximum


frequency”
The upper limit and the lower limit of the output frequency can be restricted.

Parameter Factory setting Setting range Remarks


1 120Hz 0~120Hz (Note 2) ---
2 0Hz 0~120Hz (Note 2) ---
18 120Hz 120~400Hz (Note 2) ---

Output
frequency
(Hz)

P.2 P.1(P.18) Setting frequency(Hz)

<Setting>
• If the target frequency ≦P
.2, the steady output frequency equals P.2.
• If P.2 < target frequency ≦(P.18),
.1 P the steady output frequency equals target frequency.
• If P.1 (P.18) <target frequency, the steady output frequency equals P.1.
Note: 1. The ‘maximum frequency’ and the ‘high-speed maximum frequency ’are related with each other. If the
target upper limit frequency is in the range of 0~120Hz, P.1 must be used (the setting range of P.1 is
0~120Hz); if the target upper limit frequency is in the range of 120~400Hz, then P.18 must be employed
(the setting range of P.18 is 120~400Hz).
2. If P.187=1, P.1 and P.2 are in the range of 0~1000Hz, P.18 is in the range of 120~1000Hz
3. If P.1 < P.2, the steady output frequency will be clamped to P.1.
4. The set frequency value can not exceed the value of P.1.

4.3 Base Frequency and base Voltage (P.3, P.19, P.47)


P.3 “Base Frequency” Related parameters

P.19 “Base Voltage” P.14“Load pattern selection”


P.80~P.84, P.86
P.47 “Second base frequency” “Multi-function terminals selection”
P.189“Default function”

44
4. Parameter description
Parameter

● The maximum output voltage of the inverter is called ‘base voltage’.


● If the output frequency is lower than the base frequency, the output voltage of the inverter will
increase with the output frequency; if the output frequency has reached the base frequency
(P.3/P.47), the output voltage will just be equal to the base voltage. If the output frequency exceeds
the base frequency and increase continuously, the output voltage will be clamped to the base
voltage.

Parameter Factory setting Setting range Remarks


50Hz When P.189=1
3 0~400Hz (Note 4)
60Hz When P.189=0
220V series inverters: factory setting is 220
19 220V/440V 0~1000V, 9999 440V series inverters: factory setting is 440
9999: function invalid
47 9999 0~400Hz (Note 4) 9999: function invalid

P.19

Output voltage
(V)

Output frequency

P.3(P.47)

<Setting>
• The Base Frequency is set through P.3 and P.47.
• If RT is on, P.47 ‘Second Base Frequency’ is valid. (Note 1)
• The Base voltage is set through P.19. (Note 2)

Note: 1. The Second Function is valid only when P.44≠9999.


2. If P.19=9999, the maximum output voltage of the inverter will depend on the value of the power supply
voltage.
3. RT referred in this paragraph is the name of ‘multi-functional control terminal’. For the selection of the
function and use of the multi-function control terminal, please refer to P.80~P.84, P.86. For the wiring,
please refer to section 2-5.
4. If P.187=1, P.3 and P.47 are in the range of 0~1000Hz.

45
4. Parameter description
Parameter

4.4 Multi-speed (P.4~P.6, P.24~P.27, P.142~P.149)


P.4 “speed 1(high speed)” Related parameters

P.5 “speed 2(medium speed)” P.1“Maximun frequency”


P.2“Minimum frequency”
P.6 “speed 3 (low speed)” P.29“Acceleration/deceleration
P.24~P.27 “speed 4 to 7” pattern selection”
P.79“Operation mode selection”
P.142~P.149 “speed 8 to 15” P.80~P.84, P.86
“Multi-function terminals selection”

Parameter Factory setting Setting range Remarks


4 60Hz 0~400Hz (Note 3) ---
5 30Hz 0~400Hz (Note 3) ---
6 10Hz 0~400Hz (Note 3) ---
24~27 9999 0~400Hz, 9999 (Note 3) 9999, is not chosen
142 0Hz 0~400Hz (Note 3) ---
143~149 9999 0~400Hz, 9999 (Note 3) 9999, is not chosen

<Setting>
• If all the setting values of P.24~P.27 and P.142~P.149 are not 9999, ‘16-speed operation’ is active. It
means that with the combination of RL, RM, RH and REX, there are 16 kinds of speeds in all. For
the setting of the target frequency of the inverter, please refer to the figure below.

Speed
13
Output frequency

Speed
Speed 6
(High speed) 4
speed1 Speed
Speed 7
5
Speed
8 Speed
12
speed
11
Speed
(Medium speed) 9
Speed 2
Speed
10
Speed
14
(Low speed)
Speed 3
Speed
15
Speed
0
REX ON ON ON ON ON ON ON ON

RH ON ON ON ON ON ON ON ON

RM ON ON ON ON ON ON ON ON

RL ON ON ON ON ON ON ON ON

46
4. Parameter description
Parameter
• Provided that the values of P.24~P.27 and P.142~P.149 are all defaulted, ‘3-speed operation’ is
active. In this case, the target frequency can be set as follows (the priority for the terminals is
RL>RM>RH):
Parameter
P.24= P.25= P.26= P.27= P.142= P.143= P.144= P.145= P.146= P.147= P.148= P.149=
Target
9999 9999 9999 9999 9999 9999 9999 9999 9999 9999 9999 9999
frequency
RL
○ ○ ○ ○ ○ ○ ○ ○
(P.6)
RM
○ ○ ○
(P.5)
RH

(P.4)

For example: if P.26=9999, the target frequency is determined by RM (the setting value of P.5).
Note: 1. Only in ‘external mode’, ‘combined mode 2’ or ‘combined mode 4’, the multi-speed is valid.
2. RL, RM, RH and REX mentioned in this section are the function names of the ‘multi-function control
terminal’. (For example: P.80=2, M0 terminal is chosen to perform the RL function). Please refer to
P.80~P.84, P.86 for multi-function selection, and refer to section 2-5 for wiring.
3. If P.187=1, the parameters from P.4 to P.6, from P.24 to P.27 and from P.142 to P.149 are in the range of
0~1000Hz.

4.5 “Acceleration/deceleration time (P.7, P.8, P.20, P.21, P.44, P.45)


P.7 “Acceleration time” Related parameters
P.3 “Base frequency”
P.8 “Deceleration time” P.29 “Acceleration/deceleration
P.20 “Acceleration/deceleration pattern selection”
P.47 “Second base frequency”
reference frequency” P.80~P.84, P.86
P.21 Acceleration/deceleration time “Multi-function terminal selection”
P.189 “Default function”
increments
P.44 “Second acceleration time”
P.45 “Second deceleration time”

● When the output frequency of the inverter is accelerated from 0Hz to P.20, the required time is
defined as ‘acceleration time (P.7)’.
● When the output frequency of the inverter is decelerated from P.20 to 0Hz, the required time is
defined as ‘deceleration time (P.8)’.
● P.21 is used to set the acceleration/deceleration time and minimum setting increments.

47
4. Parameter description
Parameter

Parameter Factory setting Setting range Remarks


0~360s When P.21=0
7 5s
0~3600s When P.21=1
0~360s When P.21=0
8 5s
0~3600s When P.21=1
50Hz 1~400Hz When P.189=1
20
60Hz (Note 2) When P.189=0
0 Minimum setting increments:0.01s
21 0 0, 1
1 Minimum setting increments:0.1s
0~360s When P.21=0
44 9999 0~3600s When P.21=1
9999 Not chosen
0~360s When P.21=0
45 9999 0~3600s When P.21=1
9999 Not chosen

<Setting>
• If P.21=0, the acceleration/deceleration time(P.7, P.8, P.16, P.44, P.45, and P.111~P.118)minimum
increments is 0.01 seconds.
• If P.21=1, the acceleration/deceleration time(P.7, P.8, P.16, P.44, P.45, and P.111~P.118)minimum
increments is 0.1 seconds.
• If RT is ‘on’, the second function is valid. In this case the running characteristics of the motor refer
to the second function.
• If P.44=9999 (default value), all the second function is disabled. In this case, even though RT is ‘on’,
the acceleration time is still the set value of P.7, and the deceleration time is still the set value of P.8,
the torque boost is still the set value of P.0, and the base frequency is still the set value of P.3.
• If P.44≠9999 and P.45=9999, when RT is ‘on’, the acceleration/deceleration time is the ‘set value
of P.44’.
• If P.44≠9999 and P.46=9999, when RT is ‘on’, the torque boost is the ‘set value of P.0’.
If P.44≠9999 and P.46≠9999, when RT is ‘on’, the torque boost is the ‘set value of P.46’.
• If P.44≠9999 and P.47=9999, when RT is ‘on’, the base frequency is the ‘set value of P.3’.
If P.44≠9999 and P.47≠9999, when RT is ‘on’, the base frequency is the ‘set value of P.47’.
Note: 1. The mentioned RT in this paragraph is the function name of ‘multi-function control terminal’. Please refer
to P.80~P.84, P.86 for function selection and features and refer to Section 2-5 for wiring.
2. If P.187=1, P.20 is in the range of 0~1000Hz.

48
4. Parameter description
Parameter

4.6 Electronic thermal relay capacity (P.9)


P.9 “Electronic thermal relay capacity”
Related parameters
P.80~P.84, P.86
“Multi-function terminals selection”

● The ‘electronic thermal relay’ employed the built-in program to simulate a thermal relay to prevent
the motor from overheating.

Parameter Factory setting Setting range Remarks


Rated output current
9 0~500A ---
(refer to the note of appendix 1)

<Setting>
• Please set P.9 as the rated current of the motor at its rated frequency. The rated frequency of a
squirrel-cage inductive motor that made in different countries and areas is different. Please refer to
the nameplate instruction of the motor.
• If P.9=0, the electronic thermal relay is disabled.
• In case the calculated heat by the electronic thermal relay exceeds the upper limit, an alarm will be
output (at this time, the alarm lamp will be lit.), the screen of DU03B will display , and the
output will be stopped.
Note: 1. After the inverter is reset, the thermal accumulating record of the electronic thermal relay will be reset to
zero. Attention should be paid attention to it.
2. When two or more motors are connected to the inverter, they cannot be protected by the electronic
thermal relay. Install an external thermal relay to each motor.
3. When a special motor is employed, the electronic thermal relay is no longer valid. Install an external
thermal relay to each motor.
4. About wiring for an external thermal relay, refer to P.80~P.84, P.86.

4.7 DC injection brake (P.10, P.11, P.12)


P.10 “DC injection brake operation frequency”
P.11 “DC injection brake operation time”
P.12 “DC injection brake voltage”
Parameter Factory setting Setting range Remarks
10 3Hz 0~120Hz (Note 2) ---
11 0.5s 0~60s ---
12 4% 0~30% ---

49
4. Parameter description
Parameter

<Setting>
• After a stop signal is put in (please refer to Chapter 3 for the primary operation), the output
frequency of the inverter will decrease gradually. In case the output frequency reaches the ‘DC
injection brake operation frequency (P.10)’, the DC injection brake will be active.
• During DC injection brake, a DC voltage will be injected into the motor windings by the inverter,
which is used to lock the motor rotor. This voltage is called ‘DC injection brake voltage (P.12)’. The
larger the P.12 value is, the higher the DC brake voltage and the stronger the brake capability.
• The DC brake operation will last a period (the set value of P.11) to overcome the moter inertia. To
achieve an optimum control, P.11 and P.12 should be set properly.
As shown as follows:

Output
frequency
(Hz)

Stop signal input

P.10

Time
DC
braking P.12
voltage

P.11 Time

Note: 1. Users must set P.11 and P.12 appropriately in order to obtain the best control characteristics.
2. If P.187=1, P.10 is in the range of 0~1000Hz.

4.8 Starting frequency (P.13)


P.13 “Starting frequency” Related parameters
P.2“Minimum frequency”

●When the motor starts up, the instant output frequency of the inverter is called ‘starting frequency’.

Parameter Factory setting Setting range Remarks


13 0.5Hz 0~60Hz ---

<Setting>
• If the target frequency of the inverter islower than the setting value of P.13, the motor will not run.
When the signal of the motor start, the output frequency will go up begin with the value of P.13.

50
4. Parameter description
Parameter

Output
frequency
(Hz)

P.13 Startup signal input

Time

4.9 Load pattern selection (P.14, P.98, P.99, P.162~P.169)


P.14 “Load pattern selection” P.167 “Voltage output at middle
P.98 “Middle frequency 1” frequency 4”
P.99 “Voltage output at middle P.168 “Middle frequency 5”
frequency 1” P.169 “Voltage output at middle
P.162 “Middle frequency 2” frequency 5”
P.163 “Voltage output at middle Related parameters
frequency 2” P. 0“Torque boost”
P. 46 “Second torque boost”
P.164 “Middle frequency 3” P.80~P.84, P. 86
P.165 “Voltage output at middle “Multi - function terminals selection”
frequency 3”
P.166 “Middle frequency 4”

Parameter Factory setting Setting range Remarks


When P.14=5~13, it provides 9 kinds
14 0 0~13
of different VF curve.
98 3Hz 0~400Hz (Note 3) ---
99 10% 0~100% ---
162 9999 0~400Hz, 9999 (Note 3) ---
163 0% 0~100% ---
164 9999 0~400Hz, 9999 (Note 3) ---
165 0% 0~100% ---
166 9999 0~400Hz, 9999 (Note 3) ---
167 0% 0~100% ---
168 9999 0~400Hz, 9999 (Note 3) ---
169 0% 0~100% ---
51
4. Parameter description
Parameter

<Setting>
• If P.14=4, suppose that P.19=220V, P.98=5HZ, P.99=10%, when the inverter is running at 5HZ, the
output voltage equals P.99×P.19=10%×220V=22V.
• If RT is ‘on’, P.46 ‘Second Torque Boost’ is valid.
P.14=0 P.14=1
Output voltage

Output voltage
P.19 P.19

P.0 P.0

0 P.3 Output frequency 0 P.3 Output frequency

Applicable to Constant torque loads (conveyer belt etc.) Applicable to Variable torque loads (fans and pumps etc.)

P.14=2 P.14=3
Output voltage

Output voltage

P.19 P.19
g
in
g

at
tin

t
ro
ta
ro

ly
se
d

r
ar

ve g
g
rw

in
tin

Re at
Fo

t
ta

ro
ro

d
y

ar
el

P.0 P.0
rs

r w
ve

Fo
Re

0 P.3 Output frequency 0 P.3 Output frequency

Ascending/descending loads Ascending/descending loads

P.14=4 P.14=5
Output voltage(%)

Output voltage

P. 19
P.19

P.169

P.167

P.165 A
P.0
Output frequency
P.163
0 0.1 P.98=3.0 P.3
P.99

P.0 When P.14=5, The value of A is 7.1%.


0
P.98 P.162 P.164 P.166 P.168 P.3 Output frequency (Hz)

Whether it is high startup torque or descending torque


is due to the set values(Note 1)

52
4. Parameter description
Parameter

P.14=6,7,8 P.14=9,10
Output voltage

Output voltage
P. 19 P. 19

P.0 P.0
Output frequency Output frequency

0 0.1 3.0 P. 3 0 0.1 30 P. 3

When P.14=6, the value of A is 8.7%; when P.14=7, the When P.14=9, the value of A is 20.0%; when P.14=10,
value of A is the value of A is 10.4%; when P.14=8, the the value of A is 25.0%.
value of A is 12.0%.

P.14=11,12,13
Output voltage

P. 19

A
P.0
Output frequency
0 0.1 6 P. 3

When P.14=11, the value of A is 9.3%; when P.14=12,


the value of A is 12.7%; when P.14=13, the value of A
is 16.1%.

Note: 1. Refer to the picture above the form, if need the one point, set values of P.98、P.99, if need two points ,set
values of P.98、P.99、P162、P.163, if need three points, set values of P.98、P.99、P162、P.163、P164、
P.165, like this set every last.
2. If you set value of P.14 from 5 to 13, the curve will invalid when the value of P.0 is larger than the value
of A, the value of P.14 will be equal to P.0
3. If P.187=1, P.98, P.162, P.164, P.166 and P.168 are in the range of 0~1000Hz.

53
4. Parameter description
Parameter

4.10 JOG mode (P.15, P.16)


P.15 “JOG frequency” Related parameters

P.16 “JOG acceleration/deceleration P.20 “Acceleration/deceleration


reference frequency”
time” P.21 “Acceleration/deceleration
time increments”

● In JOG mode, the output frequency is the set value of P.15, and the acceleration/deceleration time
is the set value of P.16.

Parameter Factory setting Setting range Remarks


15 5Hz 0~400Hz (Note 2) ---
0~360s When P.21=0
16 5s
0~3600s When P.21=1
Output frequency

P.20

P.15 Running
forward P.16

P.16 Running Time


backward
P.15

P.20
Press Press
FWD REV

Note: 1. Please refer to Section 3-1 for how to enter the JOG mode.
2. If P.187=1, P.15 is in the range of 0~1000Hz.

4.11 Input signal across terminal 4-5 selection function (P.17)

P.17 “Input signal across terminal 4-5 selection”


● SE series inverters have two analog input channels, terminal 2-5 and terminal 4-5. Only voltage
signal can enter across terminal 2-5, but both voltage signal and current signal can enter across
terminal 4-5, which is switched by P.17.

Parameter Factory setting Setting range Remarks


0 Current signal valid
17 1 0~1
1 Voltage signal valid

54
4. Parameter description
Parameter

4.12 Stall prevention (P.22, P.23, P.66)


P.22 “Stall prevention operation level”
P.23 “Offset coefficient for Stall prevention operation level at double speed”
P.66 “Stall prevention operation level reduction starting frequency”
Related parameters
P.189“Default function”

● With a heavy load, in the case when a motor starts or the target frequency is adjusted (increasing),
the motor speed often can not tightly follow the output frequency. If the motor speed is lower than
the output frequency, the output current will increase to improve the output torque. However, if the
difference between the output frequency and the motor speed is too great, the motor torque will
decrease, which is called ‘stall’.

Parameter Factory setting Setting range Remarks


22 200% 0~400% ---
23 9999 0~200%, 9999 ---
50Hz When P.189=1
66 0~400Hz (Note 2)
60Hz When P.189=0

<Setting>
• During the period when a motor starts or the output frequency increases, the output current of the
inverter will increase. Once the output current exceeds the upper limit pre-set as the following
figure, the adjustment of the output frequency is paused automatically and will continue to proceed
until the motor captures the output frequency (at this moment the output current of the inverter will
decrease correspondingly).
Output current
percentage
Level decreasing
P.22
region
100%
(Full load current)

P.66 Output frequency

P.22-A P.23-100
Level percentage=A+B× ×
P.22-B 100
P.66×P.22A P.66×P.22A
A= B=
Output frequency 400

Note: 1.If P.300=3, the real-time speed sensorless vector control function is selected, P.22 will be the torque limit
level as action.
2. If P.187=1, P.66 is in the range of 0~1000Hz.

55
4. Parameter description
Parameter

4.13 Output frequency filtering constant (P.28)


P.28 “Output frequency filtering constant”
● When the acceleration/deceleration time decreases and the output frequency switches from
high-frequency to low-frequency each other, machine vibration may be caused, which will affect
the product quality.
● We can fliter the output frequency at the moment when high-frequency and low-frequency
switches each other by setting output frequency filtering constant P.28, in order to reduce the
machine vibration. The bigger the set value of P.28, the better the filtering effect, but the
corresponding response delay will increase. If the set value of P.28 is 0, the filtering function is
invalid.

Parameter Factory setting Setting range Remarks


28 0 0~31 ---

4.14 Acceleration/deceleration pattern selection (P.29)


P.29 “Acceleration/deceleration Related parameters
P.3 “Base frequency”
pattern selection” P.7 “Acceleration time”
P.8 “Deceleration time”
P.20 “Acceleration/deceleration
reference frequency”
P.44 “Second acceleration time”
P.45 “Second deceleration time”

Parameter Factory setting Setting range Remarks


29 0 0~2 ---

<Setting>
• When P.29=0 ‘Linear acceleration/deceleration curve’
An acceleration slope is constructed by combination of P.7 and P.20. A deceleration slope is
fabricated by combination of P.8 and P.20.
When the target frequency varies, it increases with the ‘acceleration slope’ or decreases with the
‘deceleration slope’ linearly. Figure below:
Output frequency

P.20
Dec
ope

eler
n sl

atio
atio

n
eler

slop
Acc

P.7 P.8 Time

56
4. Parameter description
Parameter

• When P.29=1, ‘S pattern acceleration/deceleration curve 1’


The acceleration slope is formed by combination of P.7 and P3. The deceleration slope is formed by
combination of P.8 and P.3.
The ‘acceleration /deceleration curve’ possesses S-shape.
The equation for the ascending S pattern curve between 0 and Pr3 is:

The equation for the ascending S pattern curve above Pr3 is:

t: time f: output frequency


Figure below:
Output frequency

pe
slo
n
io
at
ler

P.3
ce
Ac

P.7 Time

Note: This pattern is applicable to main shafts of the working machines.

• When P.29=2, ‘S pattern acceleration/deceleration curve 2’


An acceleration slope is formed by combination of P.7 and P.20. A deceleration slope is formed by
combination of P.8 and P.20.
When the target frequency varies, it increases with the ‘acceleration slope’ or decreases with the
‘deceleration slope’. As shown in the figure below, when the setting value of the inverter is adjusted
from f0 to f2, an acceleration in S pattern is undertook once, and the time is P.7×(f2-f0)/P.20; then if
the frequency is set from f2 to f3, a second acceleration is experienced, and the time is
P.7×(f3-f2)/P.20. Figure below:

f3
Output frequency

ep
slo
ion
t
ra

f2
le
ce
Ac

f0
Time

57
4. Parameter description
Parameter

Note: In this pattern the motor vibration can be reduced substantially during acceleration/deceleration, and thus the
life span of belts and gears is expanded.

4.15 Regenerative brake (P.30, P.70)


P.30 “Regenerative function selection”
P.70 “Special regenerative brake duty”
● At the moment when the output frequency switches from high to low, due to the load inertia, the
motor speed will be higher than the output frequency of the inverter, and thus the generator effect
is formed. It results in high voltage between the main-circuit terminals P and N, which will
damage the inverter. Therefore, a proper brake resistor shall be mounted between the terminals P
and PR to dissipate the fed-back energy.
● There’s a built-in transistor (called as brake transistor) in the inverter. The conducting time ratio of
the transistor is called as ‘regenerative brake duty’. The Higher the regenerative brake duty is, the
more energy the brake resistor consumes, and the stronger the brake capability is.

Parameter Factory setting Setting range Remarks


If regenerative brake duty is 3% fixedly,the value
0
of parameter 70 is failure.
30 0 0~1
The regenerative brake duty is the value witch
1
parameter 70 setting.
70 0 0~30% ---

Note: 1. In occasions where frequent start/stop occurs, a high capacity brake resistor is required.
2. Refer to Section 2-7 for brake resistor selection.

4.16 Soft-PWM (P.31)


P.31 “Soft-PWM selection”
● Soft-PWM is a method witch control the motor noise become melody.
● Motor noise modulation control is when the inverter varied its carrier frequency from time to time
during operation. The metal noise that generates by motor is not a single frequency. This function
selection is to improve the high peak single frequency noise.
● Soft-PWM is valid in V/F curve. It means P.300 must be set to 0.

Parameter Factory setting Setting range Remarks


0 No Soft-PWM selection
31 0
1 When P.72<“5”,with Soft-PWM selection

58
4. Parameter description
Parameter

4.17 Communication function (P.32, P.33, P.36, P.48~P.53, P.153~P.154)


P.32 “Serial communication Baud rate selection”
P.33 “Communication protocol selection”
P.36 “Inverter station number”
P.48 “Data length”
P.49 “STOP bit length”
P.50 “Parity check selection”
P.51 “CR, LF selection”
P.52 “Number of communication retries”
P.53 “Communication check time interval”
P.153 “Communication error handling”
P.154 “Modbus protocol selection”
● When the communication parameters are revised, please reset the inverter.
● The SE2-type inverters have two communication protocols to selection, Shihlin protocol and
Modbus protocol. If the communication expansion board is selected, the corresponding
communication protocol is provided. P.32, P.36, P.52, P.53, and P.153 are applied to both of the
protocols. P.48~P.51 is only applied to the Shihlin protocol and P.154 is only applied to Modbus
protocol.
● Continuous communication, please make the following listed parameters set correctly, otherwise it
will not carry out normal continuous communication.
Factory
Parameter Setting range Remarks
setting
0 Baud rate: 4800bps
32 1 0~2 1 Baud rate: 9600bps
2 Baud rate: 19200bps
0 Modbus protocol
33 1 0, 1
1 Shihlin protocol
36 0 0~254 (Note 1)
0 Data length: 8 bit
48 0 0, 1
1 Data length: 7bit
0 STOP bit length: 1 bit
49 0 0~1
1 STOP bit length: 2 bit
0 Not Given
50 0 0~2 1 odd
2 even

59
4. Parameter description
Parameter

Factory
Parameter Setting range Remarks Parameter
setting
1 Only CR
51 1 1~2
2 CR and LF
52 1 0~10 (Note 2)
do communication overtime test
0~999.8
according to the set value
53 9999 0~999.8s, 9999
9999: No communication overtime test
9999
(Note 3)
0 Warn and coast to stop
153 0 0, 1
1 No warning and keep running
Modbus ASCII mode, Protocol<1,7,N,2>
0
(Note 4)
1 Modbus ASCII mode, Protocol<1,7,E,1>
154 4 0~5 2 Modbus ASCII mode, Protocol<1,7,O,1>
3 Modbus RTU mode, Protocol<1,8,N,2>
4 Modbus RTU mode, Protocol<1,8,E,1>
5 Modbus RTU mode, Protocol<1,8,O,1>

Note: 1. The numbers of inverters witchthe communication interface enables a host computer to control is due to
the wiring mothed and impedance matching. Once Modbus protocol is selected, please set P.33 to nonzero
value.
2. If the time of communication error exceeds the set value of P.52, and P.153 is set to 0, an alarm will be
output, and the screen of DU03B will display .
3. When P.53=9999, there is no time limit.
4. Modbus protocol. Protocol<1,7,N,2> means 1 start bit, 7 data bits, No parity bit, and 2 stop bit. N: no
parity, E: 1-bit even parity, O: 1-bit odd parity.

System configuration of SE2-RS485 communications interface


● For only one inverter connecting to computer

DATA+
RS- 232 / RS- 485
DATA-
cnverter

RS-232 RS-485
DA+

DB-

computer

Station number 1
Inverter 1

60
4. Parameter description
Parameter
● For multi-inverter connecting to computer

DATA+
RS-232 / RS-485
DATA-
converter

RS-232 RS-485

DA+

DA+
DB-

DB-
DB-
DA+
computer

Station number 1 Station number 2 Station number 3


Inverter 1 Inverter 2 Inverter 3

● Two communication protocol of SE2-type inverter, there are Shihlin protocol and Modbus
protocol.
1. Shihlin protocol
● Communication between PC and inverter, ASCII code (hexadecimal) converted automatically.
● PC Data communication between the inverter, please follow the steps.
read date
PC

inverter ① ⑤ time


inverter

PC
write date

Communication type with or without data format for the step:


Operation Operation Write Read Out
No. Description Reset Monitoring
Command Frequency Parameter Parameter
Computer send out
① communication request to A A A A B B
inverter
② Inverter Data Processing time yes yes yes no yes yes
No error
Data responded (request C C C no E E
From inverter accepted)

(check fault of Error
①) (request D D D no D D
rejected)
④ Computer data processing time no no no no no no
No error
Data Responded no no no no C C
(no process)
⑤ from PC (check
Error
fault of ③) no no no no F F
(output ③)
61
4. Parameter description
Parameter

① Communication Request from PC to Inverter

Information number
Format
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A Waiting Sum Stop
ENQ Station Command
(Write data Time Data check Character
*1) Number Code
to Inverter) *2) *7) *3)
B
Waiting Sum Stop
(Read data ENQ Station Command
Time check Character
from *1) Number Code
*2) *7) *3)
Inverter)

③ Computer transmit data to inverter, inverter response data


● Write data

Information number
Format
1 2 3 4 5 6
C ACK Stop Character
Station Number
(Data no error) *1) *3)
D NAK Error Code Stop Character
Station Number
(Data error) *1) *5) *3)
● Readout data

Information number
Format
1 2 3 4 5 6 7 8 9 10 11 12 13
E Stop
STX Station Unit Sum check
(Data no Readout Data ETX Character
*1) Number *4) *7)
error) *3)
Error Stop
D NAK Station
Code Character
(Data error) *1) Number
*5) *3)
⑤ When computer is in data reading, responding data after data receipt from inverter

Information number
Format
1 2 3 4 5
C ACK Stop Character
Station Number
(Data no error) *1) *3)
F NAK Stop Character
Station Number
(Data error) *1) *3)

62
4. Parameter description
Parameter

*1) Description of Control Code (ASCII CODE)

Control Code ASCII CODE Description Control Code ASCII码 Description


NUL H00 NULL ACK H06 Acknowledge
STX H02 Start of Text LF H0A Line Feed
ETX H03 End of Text CR H0D Carriage Return
ENQ H05 Enquiry NAK H15 Negative Acknowledge

*2) Wait time setting is from 0 to 15,unit is 10ms, for example 5 means 50ms.
*3) Stop Character(CR、LF CODE)
From the PC to the inverter for data communication, packet last CR, LF code by way of the PC
is automatically set. The inverter with thePC must also make the necessary settings. If you
select only the CR, then only one register is needed. If you choosen CR and LF, accounted for
the two registers.
*4) Unit: 0 means unit is 1, 1 means unit is 0.1, 2 means unit is 0.01, 3 means unit is 0.001.
*5) Error Code:
Error
Error Item Communication error exception content
Code
H01 Error Parity check which inverter received is different from the initial set.
Sum Check Inverter side of the calculation of the received data value Sum Check
H02
Error and the Sum Check which received are different.
The information which the inverter received is syntax errors, or not
H03 Protocol Error within the specified time information has been received, or CR and LF
code is different from the initial set.
H04 Frame Error STOP bit which inverter received is different from the initial set.
Overflow When the inverter receives data, has not yet been received, the PC in
H05
Error turn write the incoming data.
Mode When the inverter is running or does not in right operation mode for
H0A
Exceptions writing.
Command
H0B Specifies command code which the inverter can not handle.
Code Error.
Data Range The data is outside the range of the specified when set parameters and
H0C
Error frequency.

*6) When the parameters have 9999 properties, write or read HFFFF instead of 9999.
*7) Sum check code
ASCII code data transformed code, Add in binary code; the result (sum) of the next bit (the low
8-bit) is transformed into 2 bit ASCII code (hexadecimal), called the Sum Check Code.

63
4. Parameter description
Parameter
● Communications examples
Example 1.PC to send forward command to the inverter:
Step1. FA commands sent by the PC, using the format A:
Station number Command Code Data
ENQ Waiting Time Sum Check CR
0 HFA H0002
H05 H30 H30 H46 H41 H30 H30 H30 H30 H32 H44 H39 H0D

Calculation Sum Check: H30+H30+H46+H41+H30+H30+H30+H30+H32=H1D9, take the lower 8 bits D9,


converted to ASCII code: H44 H39
Step2. After receiving and processing accurate, the inverter responsed PC, using the format C:

ACK tation number CR


0
H06 H30 H30 H0D

Example 2. PC to send stop command to the inverter:


Step1. FA commands sent by the PC, using the format A:
Station number Command Code Data
ENQ Waiting Time Sum Check CR
0 HFA H0000
H05 H30 H30 H46 H41 H30 H30 H30 H30 H30 H44 H37 H0D

Step2. After receiving and processing accurate, the inverter responsed PC, using the format C:
Station number
ACK CR
0
H06 H30 H30 H0D

Example 3. PC communication to read P.195:


Step1. PC to send Inputting page changing command to the inverter, using the format A:
Station number Command Code Data
ENQ Waiting Time Sum Check CR
0 HFF H0001
H05 H30 H30 H46 H46 H30 H30 H30 H30 H31 H44 H44 H0D

P.195 is in page 1

Step2. After receiving and processing accurate, the inverter responsed PC, using the format C:
Station number
ACK CR
0
H06 H30 H30 H0D

64
4. Parameter description
Parameter

Step3. PC requests the inverter to read the value of P.195, using the format B:
Station number Command Code
ENQ Waiting Time Sum Check CR
0 H5F
H05 H30 H30 H35 H46 H30 H30 H42 H0D

195 minus 100 equals 95, then invert 95 to hexadecimal H5F, and convert5 and F to ASCII CODE H35、H46.

Step4. After inverter receives the information and processes without error, it sends value of P.195 to
PC, using the format E:
Station number Read data
STX Unit ETX Sum Check CR
0 H1770(60Hz)
H02 H30 H30 H31 H37 H37 H30 H32 H03 H36 H31 H0D

Example 4. Change value of P.195 to 50 (initial value is 60):


Step1 and step 2 are the same as step1 and step2 of example 3.
Step 3. PC requests the inverter to inputting 50 into P.195, using the format A:
Station number Command Code Data
ENQ Waiting Time Sum Check CR
0 HDF H1388

H05 H30 H30 H44 H46 H30 H31 H33 H38 H38 H45 H45 H0D

195 minus 100 equal 95, then Minimum unit of P.195 is 0.01, therefore
convert 95 to hexadecimal H5F, 50*100=5000, then convert 5000 to
H5F+H80=HDF. Hexadecimal H1388, and convert 1,3,8,8
to ASCII CODE to send out.
Step 4. After receiving and processing accurate, the inverter responsed PC, using the format C:
Station number
ACK CR
0
H06 H30 H30 H0D

Example 5. Change value of P.195 to 500 (Parameter range 0~400):


Step1 and step 2 are the same as step1 and step2 of example 3.
Step 3. PC requests the inverter to inputting 500 into P.195, using the format A:
Station number Command Code Data
ENQ Waiting Time Sum Check CR
0 HDF HC350
H05 H30 H30 H44 H46 H30 H43 H33 H35 H30 H46 H35 H0D

65
4. Parameter description
Parameter

Step 4. After processing, for information out of range, inverter replies to computer that this
information is incorrect, using the format D:
Station number Error Code
NAK CR
0 H0C
H15 H30 H30 H43 H0D

2. Modbus protocol
1). Information form
● Modbus serial transmission can be divided into two kinds. There are ASCII (American Standard
Code for Information Interchange) and RTU (Remote Terminal Unit) mod.
Response time for
INV
Single

PC(Master) Query Msssage

INV(Slave) ASCII:CR、 LF Response Message


RTU:wait times >= 10ms

Broadcast

PC(Master) Query Messsage

INV(Slave) No Response

(1). Query
PC (primary address) sends a message to the inverter (from the address) which is on the specified address.
(2). Normal Response
After sending a query to receive from PC, inverter to perform the requested function corresponds to the PC
and return to the normal response.
(3). Error Response
Inverter received an invalid function code, address, data, response returned to the PC.
(4). Broadcast
PC designated by the address 0, can send a message to all the inverters. All inverters which received
information from PC performed the requested function, but do not respond to the PC.
2). Communication format
● The master transmited the Query Message to inverter, the inverter response message to the PC, the
address and function code will be copied when normal communication. Bit 7 of function will be
set 1(=H80) and Data Byte will be set by error code when abnormal communication.
● Message form:

Mode Start ①Address ②Function ③Data ④Error check End


ASCII H3A 0D 0A
8 Bit 8 Bit n×8 Bit 2×8 Bit
RTU >=10ms >=10ms

66
4. Parameter description
Parameter

Message Details
Setting range: 0~254, 0 is the broadcast address, the address of inverter is from 1
to 254.
① Address
P.36 can set the address of inverter. When the PC send information from the
inverter and the inverter return information to PC, P.36 must be set.
SE2-type inverters have three functions. The inverter operated according to the
request of the PC, the PC setting function of the table other than the code, the
inverter will return an error response. Response returned from the inverter in
normal response returns to normal function, when returns the error response the
function code should add H80.

② Function Function name Function code Details


Read multiple From the PC may read straight registers
H03
registers to inverter.
Write single From the PC may write a single register
H06
register to inverter.
Write multiple From the PC may write straight
H10
registers registers to inverter.
According to the function code, the data will change. Data includes the start
③ Data
address, the number of register and the write message.
ASCII mode is for the LRC checksum, RTU mode is for the CRC checksum. (On
④ Error check LRC, CRC checksum algorithm detailed instructions please refer to the standard
Modbus protocol specification).

Algorithm of LRC checksum:


LRC check is relatively simple to use. It in ASCII mode to detect the message except the
beginning of the colon field and the end of the carriage return line number. It is only necessary to
transmit the data of each byte stack, and if the result is greater than hexadecimal H100, after removal
of the excess (such as: the results obtained for the hexadecimal H136, only to take H36) can be
reversed then plus 1.
Algorithm of CRC checksum:
1. Installation of a 16-bit register, all bits are 1.
2. The 16-bit operation result which exclusive OR between the 16-bit register high byte and the
beginning of 8-bit byte was put into the register.
3. The 16-bit register move 1-bit towards of the right.
4. If the number right (mark bit) out of the digital is 1, exclusive OR between the generator
polynomial “1010000000000001” and the register operated”, if the number right out of the bit is 0,
then return to the step 3.
5. Repeat step 3 and 4, until out of the 8-bit.
6. Exclusive OR between another 8-bit and this 16-bit register.
7. Repeat from step 3 to 6, until all bytes of the packet have exclusive OR the 16-bit register, and
shift 8 times.
8. The 2 byte CRC error checking of the 16-bit registers that was added to the most significant bit of
the message.
67
4. Parameter description
Parameter

CRC added to the message, the low byte first join, and then the high byte.
● Communication format
(1). Read data (H03)

Address Function Initial address Register number


Mode Start Check End
*1) *2) *3) *4)
ASCII H3A 2char 2char 4char 4char 2char 0D 0A
RTU >=10ms 8bit 8bit 2byte 2byte 2byte >=10ms
Normal response

Address Function Read data Read data


Mode Start number Check End
*1) *2) *5) *6)
ASCII H3A 2char 2char 2char 4char …2N×8bit 2char 0D 0A
RTU >=10ms 8bit 8bit 1byte 2byte …N×8bit 2byte >=10ms

Message Content
*1) Address Set the address to send information, 0 is in vain.
*2) Function code H03
*3) Initial address Set to the address of register to read.
*4) Register number Set to the number of register to read. The number is most 20 can read.
*5) Read data number Twice to *4).
*6) Read data Set information * 4) specified, read the data byte at the level of the order.

(2). Write data (H06)

Address Function Initial address Write data


Mode Start Check End
*1) *2) *3) *4)
ASCII H3A 2char 2char 4char 4char 2char 0D 0A
RTU >=10ms 8bit 8bit 2byte 2byte 2byte >=10ms
Normal response

Address Function Initial address Write data


Mode Start Check End
*1) *2) *3) *4)
ASCII H3A 2char 2char 4char 4char 2char 0D 0A
RTU >=10ms 8bit 8bit 2byte 2byte 2byte >=10ms

68
4. Parameter description
Parameter

Message Content
*1) Address Set the address to send information.
*2) Function code H06
*3) Initial address Set the beginning address of the register which have write function.
*4)Write dada Write data to the specified registerwhich is fixed at 16-bit.
Note: The message of normal response is the same as the query information.

(3). Write Multiple Registers (H10)

Initial Register Data


Address Function Write data
Mode Start address number quantity Check End
*1) *2) *6)
*3) *4) *5)

ASCII H3A 2char 2char 4char 4char 2char 4char …2N×8bit 2char 0D 0A

RTU >=10ms 8bit 8bit 2byte 2byte 1byte 2byte …N×16bit 2byte >=10ms

Normal response

Function Initial address Register number


Mode Start Address *1) Check End
*2) *3) *4)
ASCII H3A 2char 2char 4char 4char 2char 0D 0A
RTU >=10ms 8bit 8bit 2byte 2byte 2byte >=10ms

Message Content
*1) Address Set the address to send information.
*2) Function code H10
*3) Initial address Set the beginning address of the register which has write function.
*4) Register number Set to the number of register to write. The number is most 20 can write.
*5) Data quantity Set range is 2 to 40. Twice to *4).
*6) Write dada Set data * 4) specified, to write data in accordance with the Hi byte, Lo
byte order to set and follow the starting address of the data, the starting
address +1 of the data, the starting address +2 of the data ... to set the
order.
(4). Abnormal response
Query information received from inverter is error which from the functionality, address and data,
than operated abnormal response.

69
4. Parameter description
Parameter

Address Function *2) Error code


Mode Start Check End
*1) H80+ Function code *3)
ASCII H3A 2char 2char 2char 2char 0D 0A
RTU >=10ms 8bit 8bit 8bit 2byte >=10ms

Message Content
*1) Address Set the address to send information.
*2) Function code Function code+H80
*3) Error code Set the code from the follow table.
List of error codes:

Resource Code Meaning Remarks


The inverter can not handle the code which is from the query
Illegal function
H01 message the PC Issued. H03, H06, H08 and H10 are function
code
code.
The inverter can not handle the address which is from the
Inver Illegal data query message the PC Issued. (Outside the address listed in
H02
response address the table, retention parameters, parameters are not allowed to
read and write.)
H03 The inverter can not handle the data which is from the query
Illegal data message the PC Issued. (Outside writing range of the parameters,
there is a specified mode, and other errors.)

Note: Read more than one parameters, even reading the retention parameters, not as an error.

The data issued by the PC, the inverter will detect the following errors, but when an error is detected
no response.
Error detection list:

Error item Error content


Parity error Parity which inverter received is different from the inverter initial set.
The stop bit lengths of the information which the inverter received do not match
Frame error
the inverter initial set of stop bits.
When the inverter receives data, has not yet been received, the PC in turn write
Overflow error
the incoming data.
Inverter side of the data calculated according to the received LRC / CRC check
Check error
result is inconsistent with the received LRC / CRC checksum.

70
4. Parameter description
Parameter
● Communications examples
Example 1.Write CU (communication) mode by Communication
Step 1.PC to modify the inverter mode

Mode Start Address Function Initial address Write data Check End
ASCII H3A H30 H31 H30 H36 H31H30 H30 H30 H30 H30 H30 H30 H45 H39 0D 0A

RTU >=10ms 01 06 10 00 00 00 8D 0A >=10ms

Step 2.After receiving and processing accurate, the inverter responsed PC

Mode Start Address Function Initial address Write data Check End
ASCII H3A H30 H31 H30 H36 H31H30 H30 H30 H30 H30 H30 H30 H45 H39 0D 0A

RTU >=10ms 01 06 10 00 00 00 8D 0A >=10ms

Example 2.PC communication to read P.195:


Step 1.PC requests the inverter to read the value of P.195. The address of P.195 is H00C3。

Mode Start Address Function Initial address Register number Check End
ASCII H3A H30 H31 H30 H33 H30H30 H43 H33 H30 H30 H30 H31 H33 H38 0D 0A

RTU >=10ms 01 03 00 C3 00 01 74 36 >=10ms

Step 2.After inverter receives the information and processes without error; it sends value of P.195 to
PC.

Mode Start Address Function Read data number Read data Check End
ASCII H3A H30 H31 H30 H33 H30 H32 H31 H37 H37 H30 H37 H33 0D 0A

RTU >=10ms 01 03 02 17 70 B6 50 >=10ms


H1770 into decimal is 6000, the unit of P.195 is 0.01,so 6000×0.01=60,60 is the valueof P.195.
Example 3.Change value of P.195 to 50
Step 1.PC requests the inverter to inputting 50 into P.195.

Mode Start Address Function Initial address Write data Check End
ASCII H3A H30 H31 H30 H36 H30H30 H43 H33 H31 H33 H38 H38 H39 H42 0D 0A

RTU >=10ms 01 06 00 C3 13 88 74 A0 >=10ms

Step 2.After receiving and processing accurate, the inverter responsed PC

Mode Start Address Function Initial address Write data Check End
ASCII H3A H30 H31 H30 H36 H30H30 H43 H33 H31 H33 H38 H38 H39 H42 0D 0A

RTU >=10ms 01 06 00 C3 13 88 74 A0 >=10ms

71
4. Parameter description
Parameter
Example 4. PC communication to read parameter from P.0 to P.195:
Step 1.PC requests the inverter to read the value of P.0~P.11. The initial address is H0000.

Mode Start Address Function Initial address Register number Check End
ASCII H3A H30 H31 H30 H33 H30H30 H30 H30 H30 H30 H30 H43 H46 H30 0D 0A

RTU >=10ms 01 03 00 00 00 0C 45 CF >=10ms

Step 2.After receiving and processing accurate, the inverter responsed PC.

Mode Start Address Function Number of read data Read data Check End
ASCII H3A H30 H31 H30 H33 H31 H38 …12×4 char 2char 0D 0A

RTU >=10ms 01 03 18 …12×2 byte 2byte >=10ms

Example 5.PC communication to write parameter from P.0 to P.195:


Step 1.PC requests the inverter to write the value of P.0~P.11.

Register Data Write


Mode Start Address Function Mode Check End
number quantity data

H30 H30 H30 H30 H31 …N×4


ASCII H3A H30 H31 H31 H30 2char 0D 0A
H30 H30 H30 H43 H38 char
…N×2
RTU >=10ms 01 10 00 00 00 0C 18 2byte >=10ms
byte

Step 2.After receiving and processing accurate, the inverter responsed PC.

Mode Start Address Function Initial address Register number Check End
ASCII H3A H30 H31 H31 H30 H30H30 H30 H30 H30 H30 H30 H43 H45 H33 0D 0A

RTU >=10ms 01 10 00 00 00 0C 00 18 >=10ms

3. Communication commands list


● Set the following command codes and data, you can control the various operations, surveillance
and so on.
Modbus Shihlin protocol Information content and its Modbus
Item
code code functions address
Read out operation H0000:CU;
H03 H7B
mode H0001:OPnd;
H0002:JOG; H1000
H06/H10 Write operation mode HFB H0003:H1,H3,H5;
H0004:H2,H4

72
4. Parameter description
Parameter

Shihlin
Modbus Modbus
Item protocol Information content and its functions
code address
code
H0000~H00FF
b8~b15:reserved
b7:Alarm occurrence
b6:Frequency detection
b5:Parameters to default values end.
H03 Inverter State H7A H1001
b4:Overload
b3:Frequency achieved
b2:reverese rotation
b1:Forward rotation
b0:Operation
set frequency H73 H0000~H9C40 H1002
Output
H6F H0000~H9C40 H1003
frequency
Output current H70 H0000~HFFFF H1004
Output voltage H71 H0000~HFFFF H1005
Monitoring

H0000~HFFFF:
H03 H74 H74/H1007:Error code 1 and 2 H1007
b15 b8 b7 b0
Error code 2 Error code 1
Alarm
H75/H1008:Error code 3 and 4
item
b15 b8 b7 b0
H75 Error code 4 Error code 3 H1008
Error code can reference the table in page
108.
H0000~HFFFF
b8~b15: reserved
b7: scram(MRS)
b6: 2nd Acceleration/Declaration
Selection(RT)
H06/H10 Operation command HFA b5: High Speed (RH) H1001
b4: Mid Speed (RM)
b3: :Low Speed (RL)
b2: REV Rotation(STR)
b1: FWD Rotation (STF)
b0: reserved
H9696:The function of P.997
Communication with the PC, because the
H06/H10 Inverter reset HFD H1101
inverter is reset, so the inverter can not be
returned data to the PC.

73
4. Parameter description
Parameter

Shihlin
Modbus Modbus
Item protocol Information content and its functions
code address
code
Operation
H06/H10 HEE H0000~H9C40,write in P.430 H1002
frequency write in
H5A5A H1104

Inverter parameter H9966 H1103


See parameter recovery
H06/H10 and error code HFC H9696 H1106
description table
erased. H55AA H1105
HA5A5 H1102
H03 Parameter read out H00~H63 P.0~P.499,The range and decimal point
Please refer to parameter list. H0000
Every parameter modbus address is the 16 |
H06/H10 Parameter write in H80~HE3 band parameter number. For example: the H01F3
modbus address of P.138 is H008A.
Read H7F H0000:P.0~P.99;
Write/read
H0001:P.100~P.199;
Parameter/
--- H0002:P.200~P.299; ---
page Write HFF H0003:P.300~P.399;
change
H0004:P.400~P.499。
● Parameter recovery description table
Communication P.0~P.191(except P.21,P.189
Data Another Error
P operating parameters and Communication
content parameters code
(Note) parameter )
H5A5A P.999 o o x x
H9966 P.998 o o o x
Communication
H9696 x o x x
999
Communication
H55AA x o o x
998
HA5A5 P.996 x x x o

Note: Communication parameter include P.32、P.33、P.36、P.48~P.53、P.79、P.153 and P.154.

4.18 Speed display (P.37)

P.37 “Speed display”


● In ‘output frequency monitoring mode’, the screen will display the corresponding mechanical
speed.

74
4. Parameter description
Parameter
.
Parameter Factory setting Setting range Remarks
37 0 r/min 0.1~5000r/min 0: output frequency

<Setting>
• The set value of P.37 is the mechanical speed of the inverter when its output frequency is 60Hz.
For example: If the transmitting belt speed is 950 m/minute when the inverter output frequency is
60Hz, P.37 shall be set to 950. In ‘output frequency monitoring mode’, the screen will
display the speed of the transmitting belt.
Note: 1. There’s minute discrepancy between the displayed mechanical speed and the actual one.
2. Please refer to Section 3-2 for detailed operation of the ‘operation panel working mode’.
3. When the output mechanical speed is more than 9998, the screen will display 9999.

4.19 Voltage signal selection and target frequency (P.38, P.59, P.73, P.76,

P.139, P.140, P.141)


P.38 “The maximum output Frequency (the target frequency is set by the input
signal across terminal 2-5/panel knob)”
P.59 “Selection of frequency sources”
Related parameters
P.73 “Voltage signal selection”
P.79 “Operation mode selection”
P.76 “Panel knob signal input frequency bias” P.80~P.84, P.86
P.139 “Voltage signal bias” “Multi-function terminals selection”
P.189 “Default function”
P.140 “Voltage signal gain” P.194 “Bias of the input signal
across terminal 2-5”
P.141 “ Bias polarity of voltage signal and P.195 “Gain of the input signal
across terminal 2-5”
Reverse Motion of Negative Bias”

Parameter Factory setting Setting range Remarks


50Hz When P.189=1
38 1~400Hz (Note 4)
60Hz When P.189=0
59 1 0, 1 ---
The range for the input voltage signal
0
(terminal 2-5/4-5) is 0~5V.
73 0 0, 1
The range for the input voltage signal
1
(terminal 2-5/4-5) is 0~10V.
76 0 0~400Hz (Note 4) ---
139 0% 0%~200% ---
140 100% 0.1%~200% ---
141 0 0~11 ---
75
4. Parameter description
Parameter

< Setting >


• When P.59=0, the target frequency is set by the knob on DU03B operation panel (the range of the
voltage signal given by the knob is 0~5V). The frequency range is set by P.38.

• When P.59=1, the target frequency is set by the button and on DU03B operation panel.
• There are 2 digits in P.141, every digit have the different meaning, relevant positions as following:
P141=
0 :Positive Bias
1 :Negative Bias

0 :Negative Bias: REV Motion Disenabled


1 :Negative Bias: REV Motion Enabled

• If you hope that the frequency is not 0Hz when the panel knob is set at 0V when setting frequency
with the knob, you can realized that by setting P.76. For example: If you hope that the frequency is
10Hz when the knob is set at 0V, you should set P.76=10, at this time the setting range of the
frequency is from 10Hz to the set value of P.38 when you turn the knob. Shown as follows:
Output
frequency
P.38

P.76

0Hz The set range of


the panel knob

• Set the frequency of using negative bias benefits of avoids noise interference greatly. In harsh
environments, the user is advised to avoid using the drive signal which is below 1V to set the
operating frequency.
Now let’s see same examples:
Example 1: This is the most used setting. When the inverter is in ‘external mode’, ‘combined mode
2’ or ‘combined mode 4’, and the frequency is set by terminal 2-5。
Max output
frequency 60Hz
Parameter setting:
P.38 = 60Hz Max operation frequency
P.73 = 1 Voltage signal selection
P.139 = 0% Bias adjustment
P.140 = 100% Gain adjustment
30Hz
P.141 = 0 Positive Bias

0Hz
0V 5V 10V

76
4. Parameter description
Parameter

Example 2: This example shows the influence of changing the bias. When the input is 0V the output
frequency is 10 Hz. At mid-point a potentiometer will give 40 Hz. Once the Maximum
Output Frequency is reached, any further increase of the potentiometer or signal will not
increase the output frequency. (To use the full potentiometer range, please refer to
Example 3.) The value of external input voltage/current 0~8.33V corresponds to the
setting frequency 10~60Hz.
Max output
frequency 60Hz
Parameter setting:
P.38 = 60Hz Max operation frequency
P.73 = 1 Voltage signal selection
P.139 = 16.7% Bias adjustment
P.140 = 100% Gain adjustment
30Hz
P.141 = 0 Positive Bias

P.139 = 10Hz * 100%


10Hz P.38
Bias
adjustment 0Hz
0V 5V 10V

Example 3: This example also shows a popular method. The whole scale of the potentiometer can be
used as desired.
Max output
frequency Parameter setting:
60Hz
P.38 = 60Hz Max operation frequency
P.73 = 1 Voltage signal selection
P.139 =20% Bias adjustment
P.140 = 83.3% Gain adjustment
P.141 = 0 Positive Bias
30Hz
10Hz
P.140 = ( 1 ) * 100%
P.38
10Hz 10Hz
Bias P.139 = * 100%
adjustment P.38*P.140
0Hz
0V 5V 10V

Example 4: This example shows a potentiometer range of 0V to 5 V. Instead of adjusting gain as


example below, you can set P.38 to 120Hz or P.73 to 0 to achieve the same results.
Max output
frequency
60Hz
Parameter setting:
P.38 = 60Hz Max operation frequency
P.73 = 1 Voltage signal selection
P.139 =0% Bias adjustment
P.140 = 200% Gain adjustment
30Hz P.141 = 0 Positive Bias
10V
P.140 = * 100% = 200%
5V
Gain
adjustment

0Hz
0V 5V 10V

77
4. Parameter description
Parameter

Example 5: In this example, a 1V negative bias is used. In noisy environments it is advantageous to


use negative bias to provide a noise margin (1V in this example).

Max output
frequency
60Hz

54Hz Parameter setting:


P.38 = 60Hz Max operation frequency
P.73 = 1 Voltage signal selection
P.139 =10% Bias adjustment
P.140 = 100% Gain adjustment
P.141 = 1 Negative Bias, can not reverse
1V
P.139 = * 100%
10V

0Hz
Negative 0V 1V 10V
Bias 6Hz
6Hz

Example 6: In this example, a negative bias is used to provide a noise margin. Also a potentiometer
frequency gain is used to allow the Maximum Output Frequency to be reached.
Max output
frequency
60Hz
Bias
adjustment

Parameter setting:
P.38 = 60Hz Max operation frequency
P.73 = 1 Voltage signal selection
P.139 =10% Bias adjustment
P.140 = 111% Gain adjustment
P.141 = 1 Negative Bias, can not reverse

10V
P.140 = * 100% = 111.1%
9V
0Hz
0V 1V 10V
Negative
Bias 6.6Hz
6.6Hz

Example 7: In this example, the input is programmed to run a motor in both forward and reverse
direction. The motor will be idle when the potentiometer position is at mid-point of its
scale. Using the settings in this example disables the external FWD and REV controls.
Max output frequency
60Hz
Forward direction

30Hz

0V 0Hz
5V 10V

Parameter setting:
P.38 = 60Hz Max operation frequency
30Hz P.73 = 1 Voltage signal selection
P.139 =50% Bias adjustment
P.140 = 200% Gain adjustment
P.141 = 11 Negative Bias, can reverse
Reverse direction

60Hz

78
4. Parameter description
Parameter

Example 8: In this example, the use of negative slope is shown. Negative slopes are used in
applications for control of pressure, temperature or flow. The sensor that is connected
to the input generates a large signal (10V) at high pressure or flow. With negative slope
settings, the AC motor drive will slow stop the motor. With these settings the AC motor
drive will always run in only one direction (reverse). This can only be changed by
exchanging 2 wires to the motor.
Max output
frequency 60Hz
Negative slope
Parameter setting:
P.38 = 60Hz Max operation frequency
P.73 = 1 Voltage signal selection
P.139 =100% Bias adjustment
P.140 = 100% Gain adjustment
P.141 = 11 Negative Bias, can reverse

0Hz
0V 10V

Note: 1. In ‘external mode’, ‘combined mode 2’ or ‘combined mode 4’, if RH, RM, RL and REX are all ‘off’, the
inverter target frequency is set by the input signal across terminal 2-5/4-5. If AU is ‘on’, the input signal
across terminal 4-5 has higher priority.
2. RL, RM, RH, REX, AU and RUN referred in this paragraph is the function names of ‘multi-function
control terminals’. For the corresponding function selection and features, please refer to Pr80~84, P.86.
For wiring, please refer to Section 2-5.
3. The set value of P.76 must be smaller than the set value of P.38, and if it exceend the set value of P.38, it
will be clamped at the set value of P.38.
4. If P.187=1, P.38 is in the range of 1~1000Hz, P.76 is in the range of 0~1000Hz.

4.20 The input signal across terminal 4-5 and the target frequency (P.39)
P.39 “The maximum output frequency Related parameters
P.17“Input signal across terminal
(the target frequency is set by the
4-5 selection”
input signal across terminal 4-5)” P.73“Voltage signal selection”
P.79“Operation mode selection”
P.80~P.84, P.86
“Multi-function terminals selection”
P.189“Default function”
P.196“Bias of the input signal
across terminal 4-5”
P.197“Gain of the input signal
across terminal 4-5”

Parameter Factory setting Setting range Remarks


50Hz When P.189=1
39 1~400Hz(Note 4)
60Hz When P.189=0
79
4. Parameter description
Parameter

Setting frequency
Setting frequency
P.17=0 P.17=1

P. 39 P. 39

4mA 20mA Input signal across 0V 5V Input signal across


terminal 4-5 0V 10V terminal 4-5

Note: 1. In ‘external mode’, ‘combined mode 2’ or ‘combined mode 4’, if AU is ‘on’, the target frequency of the
inverter is set by the input signal across terminal 4-5.
2. In ‘external mode’, ‘combined mode 2’ or ‘combined mode 4’, if AU and one of RH, RM, RL and REX
are both valid at the same time, the multi-speed has higher priority.
3. RL, RM, RH, REX and AU referred in this paragraph are function names of ‘multi-function control
terminal’. For the corresponding function selection and features, please refer to Pr80~Pr84, P.86. For
wiring, please refer to Section 2-5.
4. If P.187=1, P.39 is in the range of 1~1000Hz.

4.21 Multi-function output (P.40, P.85, P.120)


P.40 “Multi-function output terminal Related parameters
pattern” P.41 “Up-to-frequency sensitivity”
P.85 “Function selection for P.42 “Output frequency detection
for forward rotation”
multi-function relay” P.43 “Output frequency detection
P.120 “The output signal delay time” for reverse rotation”
P.62 “Zero current detection”
P.63 “Zero current detection time”

Factory Setting
Parameter Remarks
setting range
RUN (Inverter running): Signal will be output when the
0 output frequency is equal to or higher than the starting
frequency.
SU (Up to frequency): Signal will be output once the
40 0 0~10 1 output frequency has reached within the set region of the
set frequency.
FU (Output frequency detection): Signal will be output
2 once the output frequency has reached or exceeded the
detection frequency set.

80
4. Parameter description
Parameter

Factory Setting
Parameter Remarks
setting range
OL (Overload detection): Signal will be output once the
3
current limit function is triggered.
OMD (Zero current detection): If the output current
percentage of the inverter is less than the set value of P.62,
4
and lasts for the pre-defined time (the setting value of
P.63), OMD will output signal.
5 ALARM (Alarm detection): Alarm detection
PO1 (Section detection): In programmed operation mode,
6
PO1 signal will be output in the end of each section.
PO2 (Periodical detection): In programmed operation
85 5 0~10 7
mode, PO2 signal will be output in the end of each cycle.
PO3 (Pause detection): In programmed operation mode,
8
PO3 signal will be output when the inverter pauses.
BP (Inverter output): Switch between the inverter
operation and commercial power-supply operation
9
function, when the inverter operation, BP will output
signal.
GP (Commercial power-supply output): Switch between
the inverter operation and commercial power-supply
10
operation function, when the commercial power-supply
operation, GP will output signal.
120 0 0.1~3600s ---

< Setting >


• When P.120=0, if the set condition of P.40 (P.85) is met, the signal will be output directly.
• When P.120=0.1~3600, if the set condition of P.40 (P.85) is met, the signal will be output after the
set time.
For example: FU (Output frequency detection) function (For example: P.42/P.43=40Hz)
Output frequency
detection value
(P.42/P.43)
Output
frequency
(Hz)
40

P.120 P.120

At least 100ms Time (s)

OFF ON OFF ON OFF


FU

81
4. Parameter description
Parameter

Note: 1. The multi-function output terminal is SO, SE. When P.40=0 (the default value), it means ‘RUN’. When a
different value is set, the corresponding function will change as shown in the above table.
2. The internal electrical structures for the multi-function output terminals are ‘open collector output’.
Please refer to Section 2-5-2 and Section 2-5-3 for wiring.
3. When the set value of P.85 is 5(the default value), the function of the multi-function relay ABC is
ALARM. When the value of P.85 is revised, its function changes respectively as the corresponding
function list in the table above.

4.22 Up-to-frequency sensitivity (P.41)


P.41 “Up-to-frequency sensitivity” Related parameters
P.40 “Multi-function output
terminal pattern”
P.85 “Function selection for
multi-function relay”

Parameter Factory setting Setting range Remarks


41 10% 0~100% ---

<Setting>
• If P.41=5%, a signal (SU) is output when the output frequency enter the ‘5% region near the target
frequency’. For example: the target frequency is set to 60Hz, and P.41=5%, then if the output
frequency is between 60±60×5%=63Hz and 57Hz region, the SU signal is output.
Output
frequency Target frequency
(Hz)

Adjustment scope
P.41

Output signal Time(s)


OFF ON OFF
SU

Note: In this paragraph, SU is the function name of ‘multi-function output terminal’. Please refer to P.40 for
function selection and features. About wiring, please refer to section 2-5.

82
4. Parameter description
Parameter

4.23 Output frequency detection (P.42, P.43)


P.42 “Output frequency detection for Related parameters
forward rotation” P.40 “Multi-function output
terminal pattern”
P.43 “Output frequency detection for
P.85 “Function selection for
reverse rotation” multi-function relay”

Parameter Factory setting Setting range Remarks


42 6Hz 0~400Hz (Note 2) ---
43 9999 0~400Hz, 9999 (Note 2) 9999: same as P.42 setting

<Setting>
• If P.42=30 and P.43=20, then a signal (FU) is output when the forward rotation output frequency
exceeds 30Hz or when the reverse rotation output frequency exceeds 20Hz.
• If P.42=30 and P.43=9999 (the default value), then a signal (FU) is output when the forward or
reverse rotation output frequency exceeds 30Hz.

Output
frequency
(Hz) Run forward

P.42

P.43 Time(s)

Run reverse
Output signal

OFF ON OFF ON OFF


FU

Note: 1. In this paragraph FU is the function names of ‘multi-function output terminals’. Please refer to P.40 for
function selection and features. About wiring, please refer to section 2-5.
2. If P.187=1, P.42 and P.43 are in the range of 0~1000Hz.

4.24 AM terminal (P.54~P.56, P.190, P.191)


P.54 “AM terminal function Selection”
P.55 “Frequency monitoring reference”
P.56 “Current monitoring reference”
P.190 “AM output bias”
P.191 “AM output gain”

83
4. Parameter description
Parameter

● Between terminal AM and terminal 5, an electric meter can be connected to indicate the output
current value or the output frequency.

Parameter Factory setting Setting range Remarks


54 0 0, 1 ---
50Hz When P.189=1
55 0~400Hz (Note)
60Hz When P.189=0
56 Rated current 0~500A ---
190 80 0~1024 ---
191 900 0~1024 ---

<Setting>
• When P.54=0, if the output frequency of the inverter is the set value of P.55, a voltage of 10V is
output at terminal AM.
• When P.54=1, if the output current of the inverter is the set value of P.56, a voltage of 10V is output
at terminal AM.
AM
output 10V

P.55 output frequency


P.56 output current
• AM terminal checking steps:
1. Connect an electric meter whose full graduation is 10V between terminal A and terminal 5, and
set P.54 to 0, then please check the meter because of the difference of the accessory.
2. Set P.13 to 0, then start the motor, and fix the output frequency of the inverter at 0Hz.
3. Read the set value of P.190, then the screen will display the current AM output bias.
SET
4. Press , press and hold for 0.5s, the finger of the meter moves upwards, the AM output
SET
bias will increase. Press to change the value of P.190, press and hold for 0.5s, the
finger of the meter moves downwards, the AM output bias will decrease. When adjusting the
scale pointer position to 0 to complete the AM output bias correction work.
5. Adjust and fix the output frequency of the inverter at 60Hz.
6. Read the setting value of P.191, then the screen will display the current AM output gain.

84
4. Parameter description
Parameter
SET
7. Press to adjust the AM output gain, press and hold for 0.5s, the finger of the
meter moves upwards and downwards. When the finger of the meter moves to full range, finish
the checking.

Note: If P.187=1, P.55 is in the range of 0~1000Hz.

4.25 Restart function (P.57, P.58, P.150, P.160)


P.57 “Restart coasting time”
P.58 “Restart voltage rising time”
P.150 “Restart mode selection”
P.160 “Stall prevention operation level when restart”
Parameter Factory setting Setting range Remarks
57 9999 0~30s,9999 9999: restart function invalid
58 10s 0~60s ---
150 0 0~221 ---
When restart, stall prevention
160 120% 0~200%
operation level

<Setting>
• When the motor is running, once the driving power is interrupted, the output voltage will not be
output instantly. When the power is recovered, if P.57=9999, the inverter will not restart
automatically, and if P.57=0.1~5, the motor coasts for a while (the set value of P.57), then the
inverter will restart the motor automatically.
• Once the motor was automatically restarted, the output frequency of the inverter is the target
frequency, but the output voltage is zero. Then the voltage will be increased gradually to the
expected voltage value. The period for voltage increasing is called ‘restart voltage rising time
(P.58)’.
• There are 4 digits in P.150, every digit have the different meaning, relevant positions as following:
P. 150 =
0 : No frequency search
1 : Immediate frequency search
2 :Cheapen voltage
0 : One electrify
1 : Every starting
2 : Stop momentary
0 :No detection of rotation
1 : The detection of rotation
2 :P.78=0 , The direction of rotation
P.78=1 ,2 No direction of rotation

85
4. Parameter description
Parameter

Note: 1. When need restart function, P.150 must be setted.


2. When the value of P.150 is not 0, default linear acceleration/deceleration curve.
3. The detection of rotation of P.150 is only to immediate frequency search.
4. This function is valid in V/F curve. It means P.300 must be set to 0.

4.26 Input signal filter constant (P.60)


P.60 “Input signal filter constant”
● When the running frequency is set by a voltage signal or a current signal, the voltage/current signal
would be processed by an A/D converter. Due to the effect of device accuracy or noises, the
external voltage signal or current signal may fluctuate and thus the running frequency fluctuates.
● The ‘Input signal filter constant setting P.60’ is used to filter the fluctuation of the running
frequency caused by the above factors. The larger the P.60 set value is, the better the filter
performance, but larger delay is resulted in.

Parameter Factory setting Setting range Remarks


60 31 0~31 ---

4.27 Remote control function (P.61)


P.61 “Remote setting function selection”
Related parameters

P.1 “Maximum frequency”


P.7 “Acceleration time”
P.8 “Deceleration time”
P.18 “High-speed maximum
frequency”
P.44 “Second acceleration time”
P.45 “Second deceleration time”

● If the operation box is located away from the control box, you can use contact signals to perform
continuous variable-speed operation, without using analog signals, when in ‘external mode’,
‘combined mode 1’ or ‘combined mode 5’.

Remarks
Factory Setting
Parameter Set Remote set
setting range Frequency setting storage function
value function
0 No ---
1 Yes
61 0 0~3 2 No
Yes No
3 (the remote setting frequency is cleaned
out by STF/STR ‘turn off’)

86
4. Parameter description
Parameter
Output P. 61 =1 、2
frequency
P. 61 =1
(Hz) * P. 61 =2 、3
P. 61 =3

0 Time

ON ON
Acceleration(RH)
ON
Deceleration (RM)

Clear (RL)
ON ON ON ON
Forward rotation(STF)

Power supply ON ON

*external target frequency (except multi-speed) or PU target frequency

<Setting>
• Remote setting function
1. Whether the remote setting function is valid and whether the frequency setting storage function in
the remote setting mode is used or not is selected by P.61.
Set P.61=1~3 (remote setting function is valid), the function of terminals RM, RH and RL are
changed to acceleration (RH), deceleration (RM) and clear (RL). As shown in the following
Figure:
Inverter
Forward rotation
STF
Acceleration RH
Deceleration RM 10
Clear RL 5
SD 2

Wiring of remote contol setting


2. During remote setting, the output frequency of the inverter is:
(frequency set by RH/RM operation+external set frequency other than multi-speeds/PU set
frequency)

• Frequency setting storage function


1. The frequency setting storage function is to storage in memory (EEPROM) the remote-set
frequency (frequency set by RH/RM opertion). Once the power supply is cut off, then on, the
inverter can start running again at the remote-set frequency (When P.61=1).
<Frequency setting storage condition>
(1). The frequency when the start signal (STF/STR) is ‘off’.
(2). When the signals RH (acceleration) and RM (deceleration) are both ‘off’(‘on’), the remote-set
frequency is storaged each minute (The current frequency set value and the last frequency set
value are compared each minute. If they are different, then the current frequency set value is
written in the memory. If RL is on, write will not perform.).

87
4. Parameter description
Parameter

Note: 1. The frequency can be varied by RH (acceleration) and RM (deceleration) between 0 and the maximum
frequency. The upper limit of the setting frequency is the maximum frequency, showen as follows:

Hz

Pr1
Output
frequency
Setting frequency

0Hz

ON
Acceleration(RH)

ON
Deceleration(RH)

Forward rotationSTF) ON

2. When the acceleration or deceleration signal is ‘on’, the output frequency acceletaion/deceleration times
are determined by P.7 (first acceleration time) and P.8 (first deceleration time) (When RT is ‘off’).
3. When P.44 ≠ 9999 (secone acceleration time) and P.45 ≠ 9999 (secone deceleration time), the
acceleration/deceleration times are due to P.44, P.45.
4. When the start signal (STF/STR) is ‘off’, if RH (acceleration)/RM (deceleration) is ‘on’, the target
frequency will also change.
5. When the start signal(STF/STR) becomes ‘off’ from ‘on’, or changing the frequency continually through
RH/RM, please make the frequency setting storage function invalid (P.61=2,3).
6. If the frequency setting storage function is valid (P.61=1), the life of the EEPROM will be shorten because
of frequent write frequency into the EEPROM.
7. Signals RH, RM and RL are determined by P.80~P.84, P.86. If the functions of the terminals are changed,
other functions are likely to be affected. Please make sure the functions of the terminals before changing
their functions.

4.28 Zero current detection (P.62, P.63)


P.62 “Zero current detection level” Related parameters
P.63 “Zero current detection time” P.40 “Multi-function output
terminal pattern”
P.85 “Function selection for
multi-function relay”

Parameter Factory setting Setting range Remarks


62 5% 0~200%, 9999 9999: function invalid
63 0.5s 0.05~1s, 9999 9999: function invalid

<Setting>
88
4. Parameter description
Parameter

• Assume that the rated full-load current of the inverter is 20A, P.62=5% and P.63=0.5s, in this case
if the output current is lower than 20×5%=1A for more than 0.5s, a signal(OMD) is output, which
is depicted in the figure below.

• If the set value of P.62 or P.63 is 9999, the zero current detection is disabled.
Note: In this paragraph OMD is one of the function names of ‘multi-function output terminal’. Please refer to P.40
for function selection and features, and section 2-5 for wiring.

4.29 Retry (P.65, P.67, P.68, P.69)


P.65 “Retry selection”
P.67 “Number of retries at alarm occurrence”
P.68 “Retry waiting time”
P.69 “Retry accumulation times”
● When an alarm occurs, the previous states before the alarm will be restored automatically, which is
called ‘retry’.
● The Retry of the inverter is the conditional execution. For example, the first alarm occurs and the retry
has been executed. Unfortunately, a second alarm occurs successively within P.68*5 seconds. Such
a case is defined as ‘continuous alarms’. In case the continuous alarms occur for more times than
the pre-defined upper limit, a great malfunction is indicated, thus special measures should be taken
manually. At this time, the retry will not be executed any more. The number of pre-defined times is
called ‘number of retries at alarm occurrence (P.67)’.
● If the alarm is not belong to ‘Continuous alarm’, the inveret can perform unlimited number of times reset.
● The period from the moment of alarm to that of retry is defined ‘retry waiting time’.

Parameter Factory setting Setting range Remarks


65 0 0~4 ---
67 0 0~10 ---
68 6s 0~360s ---

89
4. Parameter description
Parameter

<Setting>
• When P.65=0, retry is invalid. When alarm occurs, the voltage output is stopped, the ‘Alarm’ lamp
is lit, and all the inverter functions are disabled.
• When P.65=1, in case ‘over-voltage between P-N’ occurs, the voltage output is stopped. After a
period of waiting time (the set value of P.68), the retry is executed.
• When P.65=2, once ‘over-current’ occurs, the voltage output is stopped. After a period of waiting
time (the set value of P.68), the retry is executed.
• When P.65=3, in case ‘over-voltage between P-N’ or ‘over-current’ occurs, the voltage output is
stopped. After a period of waiting time (the set value of P.68), the retry is executed.
• When P.65=4, retry is effective. When alarm occurs, the voltage output is stopped. After a period of
waiting time (the set value of P.68), the retry is executed.
• When P.67=0, Retry is invalid.
• When P.67≠0, given continuous alarm occurs for times within the pre-defined upper limit of P.67,
retries will be valid. However, once the upper limit is exceeded, the retry is valid no more.
• For each time the retry occurs, the value of P.69 will be increased by 1 automatically, so the number
of P.69 read from the memory just indicates the number of retry accumulation times.
• If P.69 is rewritten with 0, the number of retry executed is erased.

Note: The inverter will retry until the return wait time of P.68 is past. Therefore, this function is selected, the
operator may cause danger, please be careful.

4.30 Brake Selection (P.71)


P.71 “Idling braking and linear braking selection”
Parameter factory setting Setting range Remarks
71 1 0~1 ---

<Setting>
• When P.71=0, it is now idling braking. The output of the inverter will terminate immediately after
STOP
RESET
pressing , and the motor will be ‘racing’
• When P.71=1, it is now beeline brake. The output of the inverter will follow the
STOP
RESET
acceleration/deceleration curve after pressing .

4.31 Carrier frequency (P.72)


P.72 “Carrier frequency”
Parameter Factory setting Setting range Remarks
72 5.0kHz 0.7~14.5kHz ---

90
4. Parameter description
Parameter

<Setting>
• The higher the carrier frequency is, the lower the motor acoustic noise is. Unfortunately, greater
leakage current and larger noises generated by the inverter are resulted in.
• The higher the carrier frequency is, the more energy is dissipated, and the higher the temperature of
the inverter is.
• In case a mechanical resonance occurs in a system with the inverter, P.72 is helpful for improved
the performance just by adjusting its value.

Note: 1. The optimum carrier frequency shall be over 8 times greater than the target frequency.
2. When selected sensorless vector control (P.300=3), the carrier frequency can set to 2kHz, 6kHz, 10kHz,
14kHz. If the setting value is less 6kHz, the carrier frequency is 2kHz; If the setting value is less than
10kHz, the carrier frequency is 6kHz; If the setting value is less than 14kHz, the carrier frequency is
10kHz; If the setting value is more than 14kHz, the carrier frequency is 14kHz.

4.32 Stop or Reset function selection (P.75)


P.75 “Stop or Reset function selection”
Parameter Factory setting Setting range Remarks
75 1 0, 1 ---

<Setting>
STOP

• When P.75=0, it is only suitable for PU mode and H2 mode (combined mode 2). Pressing RESET

STOP

during running is used to stop the motor. Only at trouble state, we can press RESET
for 1.0s to reset
the inverter, and then the inverter will show the power on state.
STOP

• When P.75=1, it is only suitable for the mode chosed. Pressing RESET
during running is used to stop
STOP

the motor. Only at trouble state, we can press RESET


for 1.0s to reset the inverter, and then the
inverter will show the power on state.
Note: 1. In normal or abnormal conditions, the reset can be executed by P.997.
2. There are two built-in program emulational thermally-accumulating relay, namely, ‘electronic thermal
relay’ and ‘IGBT module thermal relay’. Once reset occurs, the values of the two relay for ‘electronic
thermal relay’ and ‘IGBT module thermal relay’ will be set to zero.
3. In any modes except External mode or H2 mode, when P.75=1, the motor can be stopped by pressing
STOP
RESET
, then the inverter displays E0, and all the functions of the inverter are disabled. It can restart as
follows:
(1). Terminate external STF/STR command (In programmed operation mode, there’s no need to
terminate the start signal. The inverter will continue to run at the section where it stopped after
reset.)
STOP
RESET
(2). Press for 1.0s.

91
4. Parameter description
Parameter

4.33 Parameters write protection (P.77)


P.77 “Parameters write protection”
Parameter Factory setting Setting range Remarks
77 0 0~2 ---

<Setting>
• If P.77=0, when the motor stops, all parameters except for P.125 and P.188 can be written, and when
the motor runs, only P.4~P.6, P.24~P.27, P.54~P.56, P.77, P.131~P.138, P.142~P.149, P.190~P.199,
P.230, P.232, P.288 and P.290 can be written.
• If P.77=1, when the motor runs, the parameter-writing is forbidden except P.77. When the motor
stops, only P.77 and P.79 can be written.
• If P.77=2, when motor stops, all parameters except for P.125 and P.188 can be written, and when
motor runs, only P.22, P.72, P. 78, P.79, P.125, P.155 and P.188 can not be written.

4.34 Selection of forward/ reverse rotation prevention (P.78)


P.78 “Selection of forward/ reverse rotation prevention”
Factory Setting
Parameter Remarks
setting range
0 Forward rotation and reverse rotation are both permitted.
REV
1 Reverse rotation is prohibited (Press , the motor will stop).
78 0 0~2

2 Forward rotation is prohibited (Press


FWD
, the moter will stop).

4.35 Operation mode selection (P.79)


P.79 “Operation mode selection”
Factory Setting
Parameter Remarks
setting range
‘PU mode’, ‘external mode’ and ‘JOG mode’ are valid and
0
interchangeable.
1 PU mode’ and ‘JOG mode’ are active and interchangeable.
2 Only ‘external mode’ is valid.
3 Only communication mode’ is valid.
79 0 0~8
4 Only ‘combined mode 1’ is valid.
5 Only ‘combined mode 2’ is valid.
6 Only ‘combined mode 3’ is valid.
7 Only ‘combined mode 4’ is valid.
8 Only ‘combined mode 5’ is valid.

92
4. Parameter description
Parameter

4.36 Multi-function terminals function selection (P.80~P.84, P.86)

P.80~P.84, P.86 “Multi-function terminals function selection”


Para- Termi Factory Setting Function
Value Function description Remarks
meter nal setting range name
In ‘external mode’,
In programmed
‘combined mode 1’, or
operation mode,
0 STF ‘combined mode 3’,
it is used as start
when STF is ‘on’, the
signal terminal.
inverter runs forwards.
In ‘external mode’, In programmed
‘combined mode 1’, or operation mode,
80 M0 2 0~39 1 STR ‘combined mode 3’, it is used as
when STF is ‘on’, the pause signal
inverter runs reverse. terminal.
2 RL Multi-speed Please refer to
3 RM Multi-speed P.4~P.6
Please refer to
4 RH Multi-speed
P.4~P.6
In ‘external mode’,
‘combined mode 2’or
‘combined mode 4’,
when AU is ‘on’, the Please refer to
5 AU
inverter target P.39
frequency is set by the
signal input across
terminal 4-5.
6 OH (Note 3)
When MRS is ‘turned
7 MRS on’, the output
81 M1 3 0~39 terminates.
When RT is ‘on’, the
characteristics are the Please refer to
8 RT
same as the second P.44
function.
In ‘external mode’,
when EXJ is ‘on’,the
EXJ target frequency is set
9 (External by P.15, the
JOG) acceleration/
deceleration time is set
by P.16 (Note 4).

93
4. Parameter description
Parameter

Para- Termi Factory Setting


Value name Function Instruction
meter nal setting range
10 STF+EXJ
11 STR+EXJ
12 STF+RT
13 STR+RT The
82 M2 4 0~39 multiplexed
14 STF+RL function is
15 STR+RL the complex
16 STF+RM of several
basic
17 STR+RM
functions.
18 STF+RH It means
Multiplexed function
19 STR+RH that we can
use one
20 STF+RL+RM
multiplexed
21 STR+RL+RM terminal to
22 STF+RT+RL realize
83 STF 0 0~39 several
23 STR+RT+RL
basic
24 STF+RT+RM functions.
25 STR+RT+RM
26 STF+RT+RL+RM
27 STR+RT+RL+RM
In ‘external mode’,
28 RUN when RUN is ‘on’,
the inverter runs.
In ‘external mode’, it
is used with RUN. Run
The inverter runs forward
29 STF/STR forwards when /reverse
STF/STR is ‘on’, and control
runs reverse when signal
84 STR 1 0~39 STF/STR is ‘off’.
Valid on
30 RES External Reset when alarm
occurs
In ‘external mode’, it
can be used as
three-wire mode with
31 STOP
RUN signal or
STF/STR terminal.
(note 4)
94
4. Parameter description
Parameter

Para- Termi Factory Setting


Value name Function Instruction
meter nal setting range
32 REX Multi-speed
In ‘external mode’, when PO
33 PO is ‘on’, programmed
operation mode is chosen.
When alarms occur, external
34 RES_E
Reset became effective
In ‘external mode’, when
MPO is ‘on’, manually
35 MPO
operation circle mode is
chosen
When TRI is on, triangle
36 TRI
Wave function is chosen
86 RES 30 0~39 Automatic switchover
frequency between inverter
37 GP_BP
and commercial
power-supply operation
Manual swicth to commercial
38 CS
power-supply
In ‘external mode’, it is used
with RUN. The inverter runs
reverse when STF/STR is
STF/STR
39 ‘on’, stop when STF/STR is
+STOP
‘off’. If you need runs
forwards, you should RUN
again.

Note: 1. The default values are: P.80=2 (RL), P.81=3 (RM), P.82=4 (RH), P.83=0 (STF), P.84=1 (STR), P.86=30
(RES).
2. When changing the value of P.80~P.84, P.86, the functions of the terminals are changed. For example,
P.80=2 means that the function of M0 is RL, but if P.80=8, its function changes to RT, as a second
function selection terminal, P.83=0 means that the STR terminal is chosen as running forward terminal,
when P.83=6, its function changes to ‘OH’, it is then external thermal relay terminal.
3. Wiring for external thermal relay (OH): In traditional wiring,
a thermal relay is added to the motor to prevent the motor
from being too hot. Its wring is on the right figure. When
the external thermal relay is separated, the inverter will
indicate alarm, and ‘OHT’ will be displayed on the screen.

4. There are 4 kinds of operating modes to drive the inverter (‘1’ means the terminal closes, ‘0’ means the
terminal opens, X=0,1,2,3,4,6):
(1). two-wire control mode1:
95
4. Parameter description
Parameter

Operating K0
K0 K1
Instructions STF(P.8X=0)
0 0 Stop K1
STR(P.8X=1)
1 0 Run Forward
1 SD
0 Run Reverse
1 1 Stop

(2). two-wire control mode2:


Operating K0
K0 K1
Instrnctions RUN(P.8X=28)
0 0 Stop K1
STF/STR(P.8X=29)
0 1 Sop
Run Forward SD
1 0
1 1 Run Reverse
(3). three-wire control mode2 (with self maintaining function):K1: STOP signal, normally close. If it is
open, the inverter will stop. K2: RNU signal, normally open, and the pulse signal is active.
K0 K1
STF(P.8X=0)

K2
STR(P.8X=1)

STOP(P.8X=31)

SD

(4). three-wire control mode2 (with self maintaining function):K1: STOP signal, normally close. If K1
opened, the inverter will stop. K2: RNU signal, normally open, and the pulse signal is active. If the
external terminal corresponding related parameters settings for 39, when reversing, the motor will stop
until you start again.
K1 K2
RUN(P.8X=28)

Operating
K0 STOP(P.8X=31)
Instruction
0 Run Forward K0
STF/ STR(P.8X=29)
1 Run Reverse

SD

5. In external mode, when PO is ‘on’, the programmed operation mode is chosen. Terminal STF becomes the
start signal. When STF is ‘on’, the inverter begins to run in programmed operation mode at the first
section. When STF is ‘off’, the inverter stops running, and STR becomes the pause signal. When STR is
‘on’, the inverter pauses and continues to run at the section where the inverter paused when STR is ‘off’.
For details, please refer to P.100, P.101~P.108, P.111~P.118, P.121~P.123 and P.131~P.138.
6. In external mode, when MPO is ‘on’, the manually operation circle mode is chosen. For details, please
refer to P.100, P.101~P.108, P.111~P.118, P.121~P.123 and P.131~P.138.
96
4. Parameter description
Parameter

4.37 Slip compensation coefficient (P.89)

P.89 “Slip compensation coefficient”


● We can make the speed of the motor, which runs with rated current, to be much closer to the setting
speed by setting this parameter properly.
● This function is valid in V/F curve. It means P.300 must be set to 0.

Parameter Factory setting Setting range Remarks


0 slip compensation is forbidden
89 0 0~10
10 compensation value is 3% of the target frequency

4.38 Frequency jump (P.91~P.96)

P.91~P.96 “Frequency jump”


● To avoid the system mechanical resonance frequency, 3 sets of jump frequencies are presented,
namely, the first by P.91 and P.92, the second by P.93 and P.94 and the last by P.95 and P.96.

Parameter Factory setting Setting range Remarks


91~96 9999 0~400Hz, 9999(Note 3) 9999, invalid

Output
frequency
(Hz)

P.91 P.92 P.93 P.94 P.95 P.96

<Setting>
• For example: Suppose that P.91 = 45 and P.92 = 50
If the target frequency ≦ 45Hz, the steady output frequency = the target frequency.
If 45Hz < target frequency ≦ 50Hz, the steady output frequen
= 45Hz.
If 50Hz < target frequency, the steady output frequency = the target frequency.
Note: 1. During acceleration/deceleration, the output frequency of the inverter will still pass through the jump
frequency.
2. If P.91=9999 or P.92=9999, the first set of frequency jump is invalid.
If P.93=9999 or P.94=9999, the second set of frequency jump is invalid.
If P.95=9999 or P.96=9999, the third set of frequency jump is invalid.
3. If P.187=1, P.91~P.96 are in the range of 0~1000Hz.
97
4. Parameter description
Parameter

4.39 Programmed operation mode (P.100~P.108, P.111~P.118, P.121~P.123,

P.131~P.138)
P.100 “Minute/second selection”
P.101~P.108 “Runtime of each section”
P.111~P.118 “Acceleration/deceleration time of each section”
P.121 “Run direction in each section”
P.122 “Cycle selection”
P.123 “Acceleration/deceleration time setting selection”
P.131~P.138 “Frequency of each section”
Related parameters

P.7 “Acceleration time”


P.8 “Deceleration time”
P.21 “Acceleration/deceleration
time increments”
P.80~P.84, P.86
“Multi-function terminals selection”

Parameter Factory setting Setting range Remarks


The running time minimum increment is 1
0
minute.
100 1 0, 1
The running time minimum increment is 1
1
second.
101~108 0s 0~6000s ---
0~600s When P.21=0
111~118 0s
0~6000s When P.21=1
0: cycle function invalid;
121 0 0~225
1~8: run circularly
122 0 0~8 ---
123 0 0, 1 ---
131~138 0 0~400Hz (Note 4) ---

<Setting>
1. Programmed operation mode
• The calculation method of runtime and acceleration/deceleration time in each section is in the figure
below:

98
4. Parameter description
Parameter
frequency

P.111 P.112 P.113 P.114 P.116 P.117 P.118


Run forward

P.115 P.118
Run reverse

P.101 P.102 pause P.103 P.104 P.105 P.106


P.107

P.108

• The run direction is set in binary form (8-bit), then translated to decimal form and stored in P.121.
‘1’ means run forward, and ‘0’ means run reverse. The highest bit is the run direction of section 8,
and the lowest bit is the direction of section 1.
For example: Suppose that section 1: run forward, section 2: run reverse, section 3: run reverse,
section 4: run forward, section 5: run reverse, section 6: run forward, section 7: run
forward, section 8: run reverse, than the value in binary form is 01101001:
P.121=0×27+1×26+1×25+0×24+1×23+0×22+0×21+1×20=105
• When P.122=0, it won’t run circularly.
• When the value of P.122 is 1~8, it is the initialization section of the cycle running.
For example: When P.122=3, the inverter will run circularly from the third section to the eighth
section after it finishes its running from the first section to the eighth section.
When P.123=0, the acceleration time is determined by P.7, and the deceleration time is
determined by P.8.
When P.123=1, the acceleration time and deceleration time are both determined by
P.111~P.118.
2. Manually operation circle mode

RL

INV

SD

Manually operation circle mode terminals wiring pattern


• Between RL and SD, connect an impulse type switch.
• After power on, setting P.80=35 according to the terminals wiring, in this time, inverter is standby.
• The mode of operation is in the figure below:

99
4. Parameter description
Parameter

frequency P.135

P.132
P.133
P.131
P.134 P.132
P.131

……

RL
ON ON ON ON ON ON ON ON

Note: 1. The inverter will run the most 8 section, the frequency is determined by P.131~P.138
2. When the frequency is setting, if any section is 0, the inverter will run standby in this section.It means
that in thid mode the value of P.131 is not 0. Like the figure above, no matter how value of P.137 and
P.138, when the press the switch sixth, the inverter will stop.
3. Manually operation circle mode has a single rotation direction. It has nothing to do with P.121 and STF or
STR signal.
4. If P.187=1, P.131~P.138 are in the range of 0~1000Hz.

4.40 Operation panel frequency monitoring selection function (P.110)


P.110 “Operation panel frequency monitoring selection”
Factory Setting
Parameter Remarks
setting range
When the inverter starts, the operation panel enters the
0 monitoring mode automatically, and the screen displays
the output frequency.
When the inverter starts, the screen of the operation
110 0 0, 1, 2 1
panel displays the target frequency.
When the inverter starts, the operation panel enters the
2 monitoring mode automatically, and the screen displays
the output frequency steady.

4.41 Expansion board function (P.125~P.130)


P.125 “Expansion board type”
P.126 “I/0 expansion board input terminal M3 function selection”
P.127 “I/0 expansion board input terminal M4 function selection”
P.128 “I/0 expansion board input terminal M5 function selection”
P.129 “I/0 expansion board output relay1 function selection”
P.130 “I/0 expansion board output relay2 function selection”
100
4. Parameter description
Parameter

Parameter Factory setting Setting range Remarks


125 0 (Note) ---
126 9999 0~39, 9999 The function is the same with
‘multi-function control terminal’. For
0~39
127 9999 0~39, 9999 detailed description, please refer to
P.80~P.84, P.86.
128 9999 0~39, 9999 9999 Function invalid
The function is the same with
129 9999 0~10, 9999 0~10 multi-function output relay (ABC). For
detailed description, please refer to P.85.
130 9999 0~10, 9999 9999 Function invalid

Note: 1. The value of P.125 indicates the type of the expansion board. 0: communication expansion board(include
SE-CB01、SE-CB02、SE-CB03), 1: I/O expansion board (SE-EB01), 2: current source expansion board
(SE-IB01), 4. Profibus expansion board (SE-PD01), 6. DeviceNet expansion board (SE-DN01), 7: No
expansion board. When there is any expansion board is connected to the main machine, the inverter will
detect what kind of expansion board it is. If the first detection result is different from the next one; or they
are the same, but not the three types referred, an alarm will be output, and the screen will display . If
no expansion board is detected, the corresponding parameters are forbidden to read or write, but they are
restored to the default values when we read out P.998 or P.999 and rewrite in them.
2. On the details of the expansion board, refer to optional accessories of Appendix 5.

4.43 Zero-speed function (P.151~P.152)


P.151 “Zero-speed control function selection”
P.152 “Voltage instruction when zero-speed control”
Related parameters
P.13“Starting frequency”

●You must set the value of P13 is zero, when you use to this function.

Parameter Factory setting Setting range Remarks


0 There are no output when zero-speed
151 0 0~1
1 Control by DC (Note 1)
152 5% 0~30% (Note 2)

Note: 1.The output mode selected by the value of P.151, when P.151 is 0 then there is no output, when P.151 is 1
then the value of P152 which is voltage output dc voltage as keep torque.
2. Suppose that P.152=6%, then the output voltage is P.19*6% when zero-speed.
3. This function is valid in V/F curve. It means P.300 must be set to 0.
101
4. Parameter description
Parameter

4.44 Over torque detection (P.155~P.156)


P.155 “Over torque detection lelve”
P.156 “Over torque detection time”
Related parameters
P.40 “Multi-function output
terminal pattern”
P.85 “Function selection for
multi-function relay”

● When the value of P.155 is not 0, the function of over torque detection is selection.
● When the output current is in excess of over torque detection lelve P.155 and over torque detection

time P.156, the display screen of the inverter will display and the motor stop.

Parameter Factory setting Setting range Remarks


0 No detection of over torque
155 0% 0~200% When over torque detection,
0.1~200%
alarm is display and the motor stop
156 1s 0~60s ---

full load current level


100%

Output current (%)


P.155

Invertor display the OL2 alarm,and the output


stopped,the motor stopped too.

time
P. 156

output
OL (Overload alarm)

Reset signal

4.45 External terminal filter function (P.157)


P.157 “External terminals filter function selection”
Parameter Factory setting Setting range
157 4 0~200ms

• P.157 select response time to the signal of external terminal.


102
4. Parameter description
Parameter

4.46 External terminal power enable function (P.158)


P.158 “External terminal power enable”
Parameter Factory setting Setting range
158 0 0~1

• If P.158=1,select the external terminal power enable function.At this situation, if the multi-function
terminal function is STF, STR, RUN or MPO witch have been set, and opposite terminal is
connected before the power on, the inverter will not run, you should connect the terminal again, the
inverter will start running. If P.158=1 the terminal connected before the power on, if power on the
inverter running immediately.

4.47 Energy-saving control (P.159)

P.159 “energy-saving control function”


Parameter Factory setting Setting range Remarks
0 Normal runnig mode
159 0
1 energy-saving runnig mode

● In the energy-saving running mode, the inverter will control the output voltage automatically in
order to reduce the output power losses when the inverter is running.
Note: 1.After select the energy-saving running mode, the deceleration time is longer than the setting value
probability. Also the regular torque load property will produce abnormal voltage easily, please setting the
deceleration time longer.
2. This function is valid in V/F curve. It means P.300 must be set to 0.
3. Big load purposes or frequent deceleration machine, saving energy effect may not too good.

4.48 Multi-function display (P.161)

P.161 “Multi-function display selection”


Factory Setting
Parameter Remarks
setting range
When in ‘monitoring output voltage’ mode, the screen will
0
display the current output voltage value.
When in ‘monitoring output voltage’ mode, the screen will
1
display the current voltage between P and N.
161 0 0~5 When in ‘monitoring output voltage’ mode, the screen will
2
display operating condition , and
When in ‘monitoring output voltage’ mode, the screen will
3
display the value of the input signal across terminal 2-5 (V).
103
4. Parameter description
Parameter

Factory Setting
Parameter Remarks
setting range
When in ‘monitoring output voltage’ mode, the screen will
4 display the value of the input signal across terminal 4-5
160 0 0~5 (mA/V).
When in ‘monitoring output voltage’ mode, the screen will
5
display the current thermal accumulating record for inverter.

4.49 PID control (P.170~P.183)


P.170 “PID selection” P.171 “PID feedback control method
P.172 “PID proportion Gain ” selection”
P.173 “PID integration Gain ” P.174 “PID differential Gain”
P.175 “Abnormal deviation level” P.176 “Exception duration time”
P.177 “Exception handling mode” P.178 “Sleep detect deviation”
P.179 “ Sleep detect duration time” P.180 “Revival level”
P.181 “Outage level” P.182 “Upper integral”
P.183 “Deceleration step length of pressure stability”
● During the operation of PID control, the frequency displayed on the screen is the output frequency
of the inverter.
● The function of Stall Prevention operates according to the setting frequency before PID control.
Please pay attention to the Gain setting during the process of PID Gain setting, for there is case in
which the output current can not be limited absolutely.
● Under PID control, the output frequency is also limited between maximum frequency and
minimum frequency.
● Please refer to the instructions of P.60 about the input signal filter on terminal 4-5 and terminal 2-5.
● The sketch map of PID function is as follows:
Ts : Sampling period=10ms

Parameter Factory setting Setting range Remarks


170 0 0, 1, 2 ---
171 100% 0~1000% ---
172 20 1~100 ---
173 1s 0~100s ---
174 0 0~1000ms ---
175 70% 0~100% ---

104
4. Parameter description
Parameter

Parameter Factory setting Setting range Remarks


176 0s 0~600s ---
0 Coact stop
177 0 0, 1
1 Deceleration stop
178 0 0~100% ---
179 10s 0~255s ---
180 90% 0~100% ---
181 40Hz 0~120Hz (Note) ---
182 60Hz 0~120Hz (Note) ---
183 0.5Hz 0~10Hz (Note) ---

KP =P.172 contravariance
e(t) + U
R
+ + limit W
filter KI =P.173 IM
S P.182
- V
+
T KD =P.174
Output
Set PID module
frequency
frequency
Feedback value

2 4 5

feedback
quantity
P.171 convertor

● PID proportion Gain: Let the output of inverter and error signal proportional relations, only
the system output have steady state error coefficient when proportional control. The larger the
proportion when movement,the faster of speed and the sensitiver of action with system.When the
proportion is too larger, number of shocks increased,adjust time will long,and the system became
instability.

● PID integration Gain: Let the output of inverter and integration of error signal proportional
relations.In order to eliminate steady state error coefficient, need integrational control.The larger
the integration, the integral action will too less to eliminate the steady state error coefficient, The
smaller it will hard to eliminate the steady state error coefficient, when the integration is too less,
the system became instability.

● PID differential Gain: Let the output of inverter and differential of error signal proportional
relations. The differential control can not used solely, it userd with proportion gain and integration
gain to constitute PID control. The differential control can improve the movement performance for
the controlled plant witch has larger inertia or delaide.

105
4. Parameter description
Parameter

● Upper integral: Limit error upper accumulation, when the reeor value along with integral time
accumulation.
● When the pressure feedback meet skew detection value of reach down and reach down time which
the stop detection of time set.
● When the feel-back value is lower than Abnormal deviation level and continue exception duration
time P.176, the PID is exceptional. This time the screen will display , it will select freedom
or brakes according to P.177.
For example: when P.175=60%, P.176=30s, P.177=0, when the feel-back value is lower than 60%
of the target feel-back value and continue 30s, the screen will display , and
freedom stop.
the target
feel-back
value
the feel-back
value

Maximum frequency

P.176

0HZ

• If P.178=0, the value of P.179, P.180 and P.181is invalid. If the value of P.178 is not 0, the PID sleep
function is selected. When the feel-back value and the target feel-back absolute value is lower than
sleep detect deviation and continue sleep detect duration time P.179, the inverter will minish the
output frequency gradually, when the output frequency lower than outage level P.181, the inverter
will brakes stop. When the feel-back value is lower than revival level P.180, the output frequency of
inverter will select PID control function again.
For example: P.178=5%, P.179= 30s, P.180=90%, P.181=40Hz.
When the feel-back value is larger than 95% of the target feel-back value and is lower
than 105% of the target feel-back value, continue 10s, the inverter will minish the
output frequency gradually. When the output frequency is lower than 40Hz, the
inverter will brakes stop. When the feel-back value is lower than 90% of the target
feel-back value, the inverter will revival, the output frequency of inverter will select
PID control function again.

the target feel-back value

Revival level
feedback
below P.179 actually
P.179

Output Minishing the output


frequency frequency gradually

Outage
level
Outage Revival
proccess process
0HZ

106
4. Parameter description
Parameter

<Setting>
• When P.170 = 0, PID is forbidden.
• When P.170 = 1, the feedback value is setting by voltage which from terminal 2-5.
• When P.170 = 2, the feedback value is setting by current which from terminal 4-5.
• PID gain easy setting:
(1).Using pure proportional control, increasing PID proportion Gain progressively, the system to gain
critical concussion.
(2).Adjusting the 80 % PID proportion Gain witch setting in (1), increasing PID integration Gain
progressively, until we have the satisfactory movement performance.
(3).To keep PID integration Gain, adjusting PID proportion Gain and observe control process
improvement, if there is any improvement continued until satisfaction. If not, increasing
originally PID proportion Gain, then adjust PID integration Gain to improve control process. So
repeatedly, until find a satisfactory together the PID proportion Gain and PID integration Gain.
(4).Control process do not use PID differential Gain generally, when use PID differential Gain we
can adjust PID proportion Gain and PID integration Gain properly. And the same steps,
differential time setting repeatedly, until find a satisfactory control process.

Note: If P.187=1, P.181 and P.182 are in the range of 0~1000Hz, P.183 is in the range of 0~100Hz.

4.50 Disconnection processing function of terminal 4-5 (P.184)


P.184 “Disconnection processing function of terminal 4-5”
Parameter Factory setting Setting range Remarks
184 0 0~3 ---

<Setting>
• When P.184 = 0, this function is useless, if the terminal 4-5 is disconnected, the inverter will slow
down to 0Hz.
• When P.184 =1, if the terminal 4-5 is disconnected, the keyboard panel should be shown “AErr”,
the inverter will slow down to 0Hz. If connected the terminal 4-5 again, the alarm code will disappear, the
inverter will be accelerated to the current corresponding to the frequency.
• When P.184 = 2, if the terminal 4-5 is disconnected, the keyboard panel should be shown “AErr”,
the inverter Immediately stop and needs to be reset.
• When P.184 = 3, if the terminal 4-5 is disconnected, the keyboard panel should be shown “AErr”,
the frequency which is before disconnect of the inverter is continuing operation, reconnect the line, the alarm
disappears.

Note: When P.17=1, the terminal 4-5 is is setting by current 4-5, this function will be useless.

107
4. Parameter description
Parameter

4.51 Ultra-high-speed operation function (P.187)


P.187 “Ultra-high-speed operation function selection”
Parameter Factory setting Setting range Remarks
Frequency-dependent parameters set the
0
minimum unit of 0.01Hz.
187 0 0, 1
Frequency-dependent parameters set the
1
minimum unit of 0.1Hz.
• A detailed explanation for P.187, please refer to Appendix 6, ultra-high-speed operation parameters
for frequency.

4.52 Software edition (P.188)


P.188 “Software edition”
● Parameter is not writable and only readable.

4.53 Default function (P.189)


P.189 “Default function”
Parameter Factory setting Setting range Remarks
0 Apply to the 60Hz system
189 1 0, 1
1 Apply to the 50Hz system

● The user can select the frequency witch factory setting is 50Hz or 60Hz according to the different
power frequency and the frequency witch motor factory setting. Correlation parameter directions
are in the chart below:
Minimum
Parameter Name Setting range
setting unit
P.3 Base frequency 0~400Hz 0.01Hz
P.20 Acceleration/deceleration reference frequency 1~400Hz 0.01Hz
The maximum output frequency(the target frequency is
P.38 1~400Hz 0.01Hz
set by the input signal across terminal 2-5/panel knob)
The maximum output frequency(the target frequency is
P.39 1~400Hz 0.01Hz
set by the input signal across terminal 4-5)
P.55 Frequency monitoring reference 0~400Hz 0.01Hz
P.66 Stall prevention operation reduction starting frequency 0~400Hz 0.01Hz
Frequency corresponds to the maximum input voltage
P.195 0~400Hz 0.01Hz
across the terminal 2-5.
Frequency corresponds to the maximum input
P.197 0~400Hz 0.01Hz
voltage/current across the terminal 4-5.
108
4. Parameter description
Parameter

Note: 1. If the customer have some problem because of adjustmenting the factory setting witch in the chart above,
deceleration time , output voltage, voltage signal and setting frequency will be affected probability
2. If the customer need to adjustment the factory setting to 60Hz, the step is below:
(1). Setting P.189=0;
(2).Setting P.998 to resume the factory setting (This time, the factory setting of interrelated parameter is
60Hz, P.189=0) Please refer to P.998 in section 4.
3. If the customers need to resume the 50Hz system, you should set P.189=1, then implement the step 2 in
Note 2 (this time, the factory setting of P.189 is 1).
4. The minimum setting value, you can select P.187 to set. When P.187=1, the minimum setting value of the
above parameters are 0.01Hz. When P.187=0, the minimum setting value of the above parameters are
0.1Hz.

4.54 Input signal across terminal 2-5 (P.192~P.195)


P.192“Minimum input voltage across terminal 2-5”
P.193“Maximum input voltage across terminal 2-5”
P.194“Frequency corresponds to the minimum input voltage across terminal 2-5”
P.195“Frequency corresponds to the maximum input voltage across terminal 2-5”
Related parameters

P.73 “Voltage signal selection”


P.80~P.84, P.86
“Multi-function terminals selection”
P.189 “Default function”

Parameter Factory setting Setting range Remarks


192 0 0~10 ---
193 0 0~10 ---
194 0 0~60Hz(Note4) ---
50Hz P.189=1
195 0~400Hz(Note 4)
60Hz P.189=0

<Setting>
• Emendation steps:
1. Make sure that the voltage signal is correctly put in.
2. Assume that ‘the input voltage equals Value A, and the expected output frequency is 20Hz. Then
adjust the signal to Value A, and write 20 into P.194, also Value A will be weited into P.192.
3. Assume that the input voltage equals Value B, and the expected output frequency is 60Hz. Then
adjust the signal to Value B, and write 60 into P.195, also Value B will be weited into P.193.

109
4. Parameter description
Parameter

Running frequency set value


P.195

P.194

Value A Value B Singal across


terminal 2-5

Note: 1. The equation for the above curve is:


Running frequency-P.194 P.195-P.194

Voltage value-Value A Value B-Value A

2. If the user can not provide the actual stability of the signal input, you can manually set the parameters
P.192 and P.193. The value of P.192 corresponds to the frequency which P.194 set. The value of P.193
corresponds to the frequency which P.195 set. When set the parameters manually, make suse the range of
P.194 and P.195, and then adjust the voltage value of P.192 and P.193.
3. After any of P.192~P.195 is reset, the curve of P.38 is invalid.
4. If P.187=1, P.194 is in the range of 0~600Hz, P.195 is in the range of 0~1000Hz.

4.55 Input signal across terminal 4-5 (P.196~P.199)


P.196“Frequency corresponds to the P.199“Maximum input current/voltage
minimum input current/voltage across across terminal 4-5”
terminal 4-5”
P.197“Frequency corresponds to the Related parameters
maximum input currentvoltage across P.80~P.84, P.86
“Multi-function terminals selection”
terminal 4-5” P.189 “Default function”
P.198“Minimum input current/voltage
across terminal 4-5”

Parameter Factory setting Setting range Remarks


196 0 0~60Hz(Note5) ---
50Hz P.189=1
197 0~400Hz(Note5)
60Hz P.189=0
198 0 0~20 ---
199 0 0~20 ---

<Setting>
110
4. Parameter description
Parameter

• Emendation steps:
1. Make sure that the current signal is correctly put in.
2. Assume that the input current equals Value A, and the expected output frequency is 20Hz. Then
adjust the signal to Value A, and write 20 into P.196, also Value A will be weited into P.198.
3. Assume that the input current equals Value B, and the expected output frequency is 60Hz.Then
adjust the signal to Value B, and write 60 into P.197, also Value B will be weited into P.199.

Running frequency set value P.197

P.196

Value A Value B Signal across


terminal 4-5

Note: 1. The equation for the above figure is:


Running frequency-P.196 P.197-P.196

Current value-Value A Value B-Value A

2. If the user can not provide the actual stability of the signal input, you can manually set the parameters
P.198 and P.199. The value of P.198 corresponds to the frequency which P.196 set. The value of P.199
corresponds to the frequency which P.197 set. When set the parameters manually, make suse the range of
P.196 and P.197, and then adjust the voltage value of P.198 and P.199.
3. After any of P.196~P.197 is reset, the curve of P.39 is invalid.
4. Select the Input signal across terminal 4-5, please refer to P.17.
5. If P.187=1, P.196 is in the range of 0~600Hz, P.197 is in the range of 0~1000Hz.

4.56 Backlash compensation function (P.229~P.233)


P.229 “Backlash compensation function selection”
P.230 “The backlash acceleration stopping frequency”
P.231 “The backlash acceleration stopping time”
P.232 “The backlash deceleration stopping frequency”
P.233 “The backlash deceleration stopping time”
Parameter Factory setting Setting range Remarks
229 0 0~1 ---
230 1Hz 0~400Hz(Note3) ---
231 0.5s 0~360s ---
232 1Hz 0~400Hz(Note3) ---
233 0.5s 0~360s ---

111
4. Parameter description
Parameter
● Backlash countermeasures
What is the Backlash compensation?
Reduction gears have an engagement gap and have a dead zone between forward rotation and
reverse rotation. This dead zone is called backlash, and this gap disables a mechanical system from
following motor rotation.
More specifically, a motor shaft develops excessive torque when the direction of rotation changes
or when constant-speed operation shifts to deceleration, resulting in a sudden motor current
increase or regenerative status.
To avoid backlash, acceleration/deceleration is temporarily stopped. Set the
acceleration/deceleration stopping frequency and time in P.229 to P.233.
Outpot Backlash compensation function
frequency

P.23
2

P.230
P.13

time
P.231 P.233

Note: 1. When set a backlash compensation, acceleration /deceleration time only in part time longer.
2. This function is valid in V/F curve. It means P.300 must be set to 0.
3. If P.187=1, P.230 and P.232 are in the range of 0~1000Hz.

4.57 Triangular wave function (P.234~P.239)


P.234 “Triangular wave function selection”
P.235 “Maximum amplitude”
P.236 “Amplitude compensation for deceleration”
P.237 “Amplitude compensation for acceleration”
P.238 “Amplitude acceleration time”
P.239 “Amplitude deceleration time”
Parameter Factory setting Setting range Remarks
234 0 0~2 ---
235 10% 0~25% ---
236 10% 0~50% ---
237 10% 0~50% ---
238 10s 0~360s/0~3600s If P.21=0, minimum increments of P.238
and P.239 is 0.01 seconds.
239 10s 0~360s/0~3600s If P.21=1, minimum increments of P.238
and P.239 is 0.1 seconds.
112
4. Parameter description
Parameter

<Setting>
• If the value of parameter P.234 is 1, and the signal is on, the triangular wave function is effective.
Please set 36 to any parameter: P.80 ~P.84, P.86, P.126~P.128, corresponding external terminal
assigned for TRI signal.
• If the value of parameter is 2, it means the triangular wave function is effective in anytime.

triangular wave
Output operation
f0﹕Setting value of frequency
frequency f1﹕Generated amplitude for
f2 setting frequency(f0×P.235 )
f1 f2﹕Compensation from acceleration
to deceleration (f1×P.236)
f0
f3﹕Compensation from deceleration
f1 P.7 to acceleration (f1×P.237)
f3
P.8
P.7
P.239 P.238

time
STF
TRI

Note: 1.The output frequency will be limited by the maximum frequency and minimum frequency when the
triangular wave function is effective.
2. If the amplitude compensation (P.236 or P.237) is too larger, over-voltage trip and stall prevention
operation will automatically run, thus the inverter can not run according to the triangular wave function.
3. This function is valid in V/F curve. It means P.300 must be set to 0.

4.58 Auxiliary frequency function (P.240)


P.240 “Auxiliary frequency function selection”

Parameter Factory setting Setting range Remarks


240 0 0~4 ---

<Setting>
• When the value of P.240 is 0, auxiliary frequency function is not selected.
• When the value of P.240 is 1, operation frequency = basic frequency + auxiliary frequency (2-5),
• When the value of P.240 is 2, operation frequency = basic frequency + auxiliary frequency (4-5),
• When the value of P.240 is 3, operation frequency = basic frequency - auxiliary frequency (2-5),
• When the value of P.240 is 4, operation frequency = basic frequency - auxiliary frequency (4-5),
• When the operation frequency is less than P.2, the operation frequency should equal to P.2. When
the operation frequency is more than P.1, the operation frequency should equal to P.1.
Note: Basic frequency is set by the target frequency reference source DU03B, communications or combination of
multi-speed gears.

113
4. Parameter description
Parameter

4.59 DC injection brake function before starting (P.242~P.244)


P.242 “DC injection brake function before starting selection”
P.243 “DC injection brake time before starting”
P.244 “DC injection brake voltage before starting”
Related parameters
P.13“Starting frequency”

Parameter Factory setting Setting range Remarks


242 0 0~1 ---
243 0.5s 0~60s ---
244 4% 0~30% ---

<Setting>
• If P.242=0, the DC injection brake function before starting is not selected. If P.242=1, the DC brake
injection function before starting is selected. When the output frequency reached the starting
frequency (P.13), a DC voltage (P.244) will be injected into the motor windings by the inverter,
which is used to lock the motor rotor. The DC brake operation will last a period (the set value of
P.243), the motor will start.
As shown as follows:

Output
frequency

P.13
time
DC injection
brake voltage
P.244
time
P.243

Note: This function is valid in V/F curve. It means P.300 must be set to 0.

4.60 Bypass-inverter switchover function (P.247~P.250)


P.247 “MC switch interlock time”
P.248 “Start waiting time”
P.249 “Automatic switchover frequency from inverter to bypass operation”
P.250 “Automatic switchover frequencyrange from bypass to inverter operation”
114
4. Parameter description
Parameter

Parameter Factory setting Setting range Remarks


247 1s 0.1~100s ---
248 0.5 s 0.1~100 s ---
249 9999 0~60Hz, 9999 (Note 4) ---
250 9999 0~10Hz, 9999 (Note 4) ---

<Setting>
• Set the frequency to switch inverter operation to bypass operation. Inverter operation is performed
from a start until P.249 is reached, and when the output frequency is at or above P.249, inverter
operation is automatically switched to bypass operation. If set 9999 to P.249, without automatic
switchover.
• If the value of P.250 is not 9999, valid during automatic switchover operation (Pr.249≠9999). When
the frequency command decreases below (Pr.249 - Pr.250) after operation is switched from inverter
operation to bypass operation. The inverter automatically switches operation to inverter operation
and operates at the frequency of frequency command. When the inverter start command (STF/STR)
is turned off, operation is switched to inverter operation also.
• If the value of P.250 is 9999, valid during automatic switchover operation (Pr.249≠9999).When the
inverter start command (STF/STR) is turned off after operation is switched from inverter operation
to bypass operation, operation is switched to inverter operation and the motor decelerates to stop.
The wiring diagram:
The following is the representative wriing diagram of switching the commercial power-supply
operation. P.80 = 37, P.81 = 38, P.40 = 10, P.85 = 9.
MC1

NFB
R U
MC2
S V M
T W

MC1
STF SO
K2
DC24V
M1
K3
SE
M0
K1
MC2
SD A

B
10
DC24V
2 C
5

Please pay attention to the capacity of the output terminals.The terminals which used are according to
different settings for P.40 and P.85 (output terminal function selection).When the output terminal
function select 10, connect the relay which drive the commercial power-supply operation.When the
output terminal function select 9, connect the relay which drive the inverter operation.When the
external input terminal function select 37, selected the switching inverter to commercial
power-supply operation.When the external input terminal function select 38, hand switching signal
CS.
115
4. Parameter description
Parameter

Warning:
1. MC1 and MC2 must be mechanical interlock, the running direction of the inverter operation
and the commercial power-supply operation should be consistent.
2. Bypass-inverter switchover function is effective in external mode.
3. So long as the signal “CS” is on, STF or STR is available.
Sequence diagram of switching the commercial power-supply:
1. Action which no automatical switching in order.

Power supply

MRS

STF

CS

MC2

MC1
P.248 P.58

P.247 P.247 P.57

the commercial
power-supply
The motor speed operation
Inverter Free Free Inverter stop
operation operation operation operation

2. Action which automatical switching in order (P.249≠9999, P.250=9999).

STF

Output
frequency
P.249
Setting
frequency
time

Actual
motor speed
time

MC2

MC1
A A B C D

116
4. Parameter description
Parameter

3. Action which automatical switching in order (P.249≠9999, P.250≠9999).

STF
Output P.249
frequency P.250

Setting time
frequency
Actual
motor speed
time
MC2

MC1
A A B C D A A B C D

When automatical switching, A is P.247, B is P.248, C is P.57, D is P.58.

Note: 1. When the motor is operated at 60Hz (or 50Hz), more efficient operation can be performed by the
commercial power supply than by the inverter. When the motor cannot be stopped for a long time for the
maintenance/inspection of the inverter, it is recommended to provide the commercial power supply circuit.
2. To avoid commercial power supply being applied to the inverter output side when switching between
inverter operation and commercial power supply operation, provide an interlock which the MC of the
commercial power supply side turns on only when the MC of the inverter output side is off. Using the
electronic bypass sequence function that outputs the timing signal for operation of the magnetic contactor,
a complicated commercial power supply switchover interlock can be provided by the inverter.
3. This function is valid in V/F curve. It means P.300 must be set to 0.
4. If P.187=1, P.249 is in the range of 0~600Hz, P.250 is in the range of 0~100Hz.

4.61 Alarm history (P.288~P.291)


P.288 “Ablarm history number”
P.289 “Alarm code”
P.290 “The latest alarm status selection”
P.291 “The latest alarm status”
● The user can read this paragraph parameters to know the frequency, current, voltage and 12 alarm
code which in front of this alarm code when alarm occurred. If execute P.996, this paragraph
parameters will been clear.

117
4. Parameter description
Parameter

Parameter Factory setting Setting range Remarks


288 0 0~12 1~12 are the value of P.288 which are
corresponding to abnormal number of alarm code
289 0 --- E1~E12 the P.289 display.
If P.290=1, P.291 correspond to display frequency
for the latest alarm occurred.
290 0 0~5 If P.290=2, P.291 correspond to display current for
the latest alarm occurred.
If P.290=3, P.291 correspond to display output
voltage for the latest alarm occurred.
If P.290=4, P.291 correspond to display the
accumulation rate of temperature for the latest
291 0 --- alarm occurred.
If P.290=5, P.291*100 correspond to display busbar
voltage for the latest alarm occurred.
If the value of P.288 and P.290 are 0, P.289 and P.291will display 0 too.
The abnormal number of the alarm code:
Abnormal Abnormal Abnormal Abnormal
Alarm code Alarm code Alarm code Alarm code
number number number number
00 (H00) No alarm 33 (H21) OV2 64 (H40) EEP 144 (H90) OHT
16 (H10) OC1 34 (H22) OV3 66 (H42) PIDE 160 (HA0) OPT
17 (H11) OC2 35 (H23) OV0 97 (H61) OLS 192 (HC0) CPU
18 (H12) OC3 48 (H30) THT 98 (H62) OL2 193 (HC1) CPR
19 (H13) OC0 49 (H31) THN 179 (HB3) SCP 194 (HC2) EBE
32 (H20) OV1 50 (H32) NTC 129 (H81) AErr

4.62 Accumulative motor operation time function (P.292, P.293)


P.292 “Accumulative motor operation time (min)”
P.293 “Accumulative motor operation time (day)”
Parameter Factory setting Setting range Remarks
292 0 0~1439min ---
293 0 0~9999day ---

<Setting>
• P.292 means the minutes of accumulative motor operation, execute P.998, cut off the power,
updated value cannot change the value of P.292.Only set 0 to P.292, can clear the accumulation of
time.
118
4. Parameter description
Parameter

• P.293 means the days, execute P.998, cut off the power, updated value cannot change the value of
P.293.Only set 0 to P.293, can clear the accumulation of time.

4.63 Password protection function (P.294, P.295)


P.294 “Password input”
P.295 “Password set”
Parameter Factory setting Setting range Remarks
294 0 0~65535 ---
295 0 2~65535 ---

<Setting>
• P.294 is a parameter which can decrypt, after decryption succeed, the value of P.294 is 0. When
P.295 is after setting a password-protected, P.294 enters the pre-set the password to unlock the
password-protected parameter, then the parameters can modify.
• P.295 is a parameter which can set password. The password must be larger than 1, after succeed to
setting password, the value of P.295 is 1, and after remove the password, the value of P.295 is 0.If
the password is set, the parameters will not change except P.294, nor execute P.998, cut off the
power the password is also exist, only if decreption.

Note: If the password was forgotten, the inverter must return to factory to decrphering.

4.64 Motor control mode (P.300, P.301)


P.300 “Motor control mode selection”
P.301 “Motor parameter auto measurement function selection”
Parameter Factory setting Setting range Remarks
0 V/F control
1 ---
300 0 0~3
2 Facility vector control
3 Speed sensorless vector control
0 No motor parameter auto measurement function
Motor parameter auto measurement function
1
(Measured of the motor is running)
301 0 0~3
Motor parameter auto measurement function
2
(Measurement of the motor is not running)
3 Online auto measurement function

119
4. Parameter description
Parameter

<Setting>
• If P.300 = 0, the inverter have no motor parameter auto measurement function, to normal by V / F
control operation.
• When select the facility vector control, please setting P.300 to 2. We can use this function to
compensate the changes of the frequency when the load of the motor becomes heavier.
• If you need the motor parameter auto measurement function, you must set P.301 to 1 or 2, then
FWD REV
press down or . The screen of the operation panel will display “TUN” and flicker when in
measurement process. If the measurement is success, the operation panel will display “TEND” and
flicker. If the measurement is failure, the operation panel will display “FAL” and flicker. Press
STOP
RESET
down for 1s, return to normal display.
• The step of the motor parameter auto measurement as follow:
Confirm the wiring
(Please refer 2.5.6 )

Set motor parameters


(P.302~P.307)

0
P.301

1 、2

Press down FWD or REV ,The screen


of the operation panel
will display “TUN”

N
Success
Y

If failure, the operation If succeed, the operation


panel will display “FAL” panel will display
and flicker “TEND” and flicker

STOP STOP
Press down RESET Press down RESET

for 1s, return to normal for 1s, return to normal


display. display.

Manually adjust Y
parameter values

N
Manual input parameters
(P.302~P.312), and then wtite
in P.997

Finish

120
4. Parameter description
Parameter

• If you need Speed sensorless vector control, you should set P.300 to 3.
Note: 1. Motor capacity and inverter capacity must be with grade or sub-grade.
2. If P.187=1, the speed sensorless vector control function is invalid.
3. To do auto measurement function, such as permitting motor rotation, set P.301 to 1
(Dynamic measurement), then it should be made load off the motor completely. Such as loading conditions
don't allow the case which the motor rotation when Auto-tuning automatic measurement function, please
set P.301 to 2 (Static measurement).
4. Speed sensorless vector control: measurement by automatic (Auto-tuning) function to enhance the control
performance. Set the motor parameters or do auto measurement function before set P.300 to 3, in ordor to
increase the control accuracy

4.65 Motor pamameter (P.302~P.312)


P.302 “Motor rated power” P.308 “No load excitation current”
P.303 “Motor poles” P.309 “Stator resistance”
P.304 “Motor rated voltage” P.310 “Rotor resistance”
P.305 “Motoe rated frequency” P.311 “Leakage inductance”
P.306 “Motoe rated current” P.312 “Mutual inductance resistance”
P.307 “Motoe rated speed”

Parameter Factory setting Setting range Remarks


302 0 0~160 ---
303 4 0~8 ---
304 220/440V 0~440V ---
50Hz P.189=1
305 0~400Hz
60Hz P.189=0
306 Determined by horsepower 0~500A ---
1410r/min P.189=1
307 0~65535 r/min
1710 r/min P.189=0
308 Determined by horsepower 0~500A ---
309 Determined by horsepower 0~65535 ---
310 Determined by horsepower 0~65535 ---
311 Determined by horsepower 0~65535 ---
312 Determined by horsepower 0~65535 ---

121
4. Parameter description
Parameter

<Setting>
• If the motor and load can be completely disengaged, please select P.301=1, when the motor rotation,
FWD REV
the motor parameters auto measurement, then press down or , the inverter will automatically
calculate the following parameters: P.308~P.312.
• If the motor and load can not be fully disengaged, please select P.301=2, when the motor stopped, the
FWD REV
motor parameters auto measurement, then press down or , the inverter will automatically
calculate the following parameters: P.308~P.312.
• Users can also calculate two parameters according to the motor nameplates. Used in the calculation
of the motor nameplate parameters: Rated voltage U, rated current I, rated frequency f and power

factor η .

• Motor no-load excitation current calculation method and the motor mutual inductance are
calculated as follows, including L6 for motor leakage inductance.

No-load excitation current: I 0 = I × 1 − η 2

U
Mutual inductance: Lm = − L6
2 3 ⋅π ⋅ f ⋅ I0
I0 is the no-load excitation current,Lm is the mutual inductance,L6 is the leakage inductance.
Note: 1. When the inverter and motor with different levels of use, please make sure the input parameters of the
motor nameplate from P.302 to P.307. The vector control mode dependent on motor parameters strongly. If
you need obtain good control performance, you must obtain the exact parameters of the controlled motor.
2. When any one or more parameters have been manually changed, please make a P.997 funcction, in order to
reload new parameters values.

4.66 Speed control gain adjustment (P.320~P.321)


P.320 “Speed control scale coefficient”
P.321 “Speed control integral coefficient”
Parameter Factory setting Setting range Remarks
320 100% 0~2000% ---
321 0.30s 0~20s ---

<Setting>
• P.320 set the speed control proportional gain. (The set value is set too a few bigger, for speed
changing follow instructions will become better, the speed changing caused by external disturbance
will be smaller. )

122
4. Parameter description
Parameter

• P.321 set the speed control integration time. (Because of external disturbance to speed changes, the
value will be set to be smaller, so that to reset time of the original speed is shorter.)
Note: 1. If use P.320 to improve the speed control gain, can improve the response time. But if the value is setting
too high will produce vibration and noise.
2. Reduce the speed control integral coefficient P.321, the reset time of the speed variation is shorter, but if
this value is too small, the overshoot will be produced.

4.67 Parameter copy function (P.994, P.995)


P.994 “Parameter copy readout”
P.995 “Parameter copy write-in”
● When set value into P.994, P.995, Motor rotation must be in a stop, this parameter value is only
valid when P.77=0 and in PU mode. When using same parameters for several inverter value setting.
Use P.994 and P.995 to perform duplication value to other inverter rapidly.
● Procedures of parameter copy:
1. When the first inverter is in PU mode, the value of P.994 is readout (the screen will

display ) and then press “Write”, at the same time the screen is flickering, it means that
the parameter copy from inverter to operation panel is in process. When no more flickering on
the screen is means the parameter copy is done.
2. When the second inverter is in PU mode, the value of P.995 is readout (the the screen

display ) and then press “write” at the same time, then the the screen is flickering it means
the parameter copy from operation panel to inverter EEPROM is in process. When the screen is
no more flickering, the parameter copy is done.

* PU series operation panel need to purchase


Note: 1. Regarding parameter copy function in P.994 and P.995, it is only available on SH-PU series of Inverters.
2. When parameter copy is in process, the value of P.0 to P.390 will be copied and duplicate into Digital Unit
and inverter.

4.68 Alarm log erasure (P.996)


P.996 “Alarm log erasure”
● Once P.996 is read out (after read out, the screen will display ) and rewritten in, all the
abnormal event logs are erased.

123
4. Parameter description
Parameter

4.69 INV Reset (P.997)


P.997 “INV Reset”
● Once P.997 is read out (after read out, the screen will display ) and rewritten in, the
inverter is reset. Once the inverter is reset, the values of the ‘electronic thermal relay’ and the
‘IGBT module thermal relay’ will be set to zero.

4.70 Parameter initialization (P.998, P.999)


P.998 “Parameter total- initialization”
P.999 “Parameter partial- initialization”
● Once P.998 is read out (after read out, the screen will display ) and rewritten in, all
parameters except P.21, P.125, P.187, P.188, P.189, P.292, P.293 will be restored to the default
values.

● Once P.999 is read out (after read out, the screen will display ) and rewritten in, all
parameters except P.21, P.125, P.187, P.188, P.189, P.192, P.194~P.197, P.292, P.293, P.300~P.312
will be restored to the default values.

● Please make sure that do not carry out any other operations before the screen displays ,
which indicates that the corresponding parameters has been restored to the default values.

124
5. Inspection and Maintenance
Inspection and Maintenance

In order to avoid the malfunction and security problems resulting from aging of the devices which is
caused by environmental factors such as temperature, oil fog, dust, vibration, humidity and etc.,
‘daily inspection’ and ‘periodical inspection’ are necessary.
Note: Only fully-qualified electrical professional personnel can carry out installation, wiring, dismounting and
maintenance.

5.1 Daily inspection


1. Check whether the surrounding conditions are normal (including temperature, humidity, dust
density and etc.) at the installment place.
2. Check whether the power supply voltage is normal (the voltages among R, S and T).
3. Check whether wiring is ok (whether the external wiring for the main-circuit board and the
control-board terminal is loose).
4. Check whether the cooling system is abnormal (Whether there’s any abnormal acoustic noise
when operating. whether the wiring is ok.).
5. Check the indicating lamp (Whether the control-board indicating LED lamp, the operation panel
indicating LED lamp and the operation panel screen LED are normal).
6. Check whether the expected performance is maintained.
7. Check whether there’s any abnormal vibration, acoustic noise or smell during running.
8. Check whether there is liquid leaking from the filter capacitors.

5.2 Periodical inspection (during stop)


1. Check the connector and wiring (whether the connector and wiring between the main-circuit
board and control board is ok).
2. Check whether components on the main-circuit board and the control board are overheated.
3. Check whether the electrolytic capacitors on the main-circuit board and control board have liquid
leaking out.
4. Check the IGBT module on the main-circuit board.
5. Clean the dust and contaminants on the circuit board.
6. Check the insulation resistor.
7. Check whether the cooling system is abnormal (Whether the wiring is firm; clean the air filter,
etc).
8. Check screws and belts.
9. Check the external wires and the terminal banks for damage.

5.3 Regular replacement of parts (components)


The corresponding
Items period for Description
replacement
For the axle of a fan, the standard lifetime is about 10~35
Cooling fan 2 years thousand hours. With reference to the time of 24 hours one day,
it is sure that the fan should be replaced every 2 years .

125
5. Inspection and Maintenance
Inspection and Maintenance

The corresponding
Items period for Description
replacement
The filter capacitor is an electrolytic capacitor, and will
Filter deteriorate with time. The deterioration speed is contingent on
5 years
capacitor the ambient conditions. Generally, it shall be replaced every 5
years.

Relay --- If bad contact occurs, please replace it immediately.

Note: Please send the inverters to the factory when replacement of the parts is necessary.

5.4 Inverter insulation resistance measurement


1. Before measurement, first dismount the ‘wiring of the main-circuit
terminals’ and the ‘control board’. Then execute wiring in the way as
the right figure.
2. The measurement is only suitable for the main circuit. Such
measurement is prohibited for control board terminals.
3. The value of the insulation resistance shall be
greater than 5MΩ.
Note: Please do not carry out a high-voltage test, because the built-in semiconductor components will be
damaged by such a test.

5.5 Motor insulation resistance measurement


1. Before measurement, please dismount the motor, and demonstrate
wiring in the way as the right figure.
2. The insulation resistance shall be greater than 5MΩ.

5.6 Motor insulation resistance measurement


Before check, first dismount the external wires for the main-circuit terminals. Then, set your
multi-meter to the ohm-testing position.

Positive Negative Normal Positive Negative Normal


voltage voltage result voltage voltage result
R P Conducting U P Conducting
S P Conducting V P Conducting
Terminal Terminal
T P Conducting W P Conducting
mark mark
Not Not
P R P U
conducting conducting
126
5. Inspection and Maintenance
Inspection and Maintenance

Positive Negative Normal Positive Negative Normal


voltage voltage result voltage voltage result
Not Not
P S P V
conducting conducting
Not Not
P T P W
conducting conducting
Not Not
R N U N
conducting conducting
Terminal Terminal
Not Not
mark S N mark V N
conducting conducting
Not Not
T N W N
conducting conducting
N R Conducting N U Conducting
N S Conducting N V Conducting
N T Conducting N W Conducting

127
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
P.0 Torque boost 0~30% 0.1% (Note 1) P43
P.1 Maximum frequency 0~120Hz 0.01Hz 120Hz P44
P.2 Minimum frequency 0~120Hz 0.01Hz 0Hz P44
50Hz/60Hz
P.3 Base frequency 0~400Hz 0.01Hz P44
(Note 2)
P.4 Speed 1 (high speed) 0~400Hz 0.01Hz 60Hz P46
P.5 Speed 2 (middle speed) 0~400Hz 0.01Hz 30Hz P46
P.6 Speed 3 (low speed) 0~400Hz 0.01Hz 10Hz P46
0~360.00s/
P.7 Acceleration time 0.01s/0.1s 5s P47
0~3600.0s
0~360.00s/
P.8 Deceleration time 0.1s/0.01s 5s P47
0~3600.0s
Electronic thermal relay Motors rated current
P.9 0~500A 0.01A P49
capacity (Note 1)
DC injection brake
P.10 0~120Hz 0.01Hz 3Hz P49
operation frequency
DC injection brake
P.11 0~60s 0.1s 0.5s P49
operation time
P.12 DC injection brake voltage 0~30% 0.1% 4% P49
P.13 Starting frequency 0~60Hz 0.01Hz 0.5Hz P50
P.14 Load pattern selection 0~13 1 0 P51
P.15 JOG frequency 0~400Hz 0.01Hz 5Hz P54
JOG acceleration / 0~360.00s/
P.16 0.1s/0.01s 0.5s P54
deceleration time 0~3600.0s
Input signal across terminal
P.17 0、1 1 0 P54
4-5 selection
High-speed maximum
P.18 120~400Hz 0.01Hz 120Hz P44
frequency
P.19 Base frequency voltage 0~1000V, 9999 0.1V 9999 P44
Acceleration/deceleration 50Hz/60Hz
P.20 1~400Hz 0.01Hz P47
reference frequency (Note 2)
Acceleration/deceleration
P.21 0,1 1 0 P47
time increments
Stall prevention operation
P.22 0~400% 0.1% 200% P55
level
Offset coefficient for Stall
P.23 prevention operation level 0~200%, 9999 0.1% 9999 P55
at double speed
P.24 Speed 4 0~400Hz, 9999 0.01Hz 9999 P46

128
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
P.25 Speed 5 0~400Hz, 9999 0.01Hz 9999 P46
P.26 Speed 6 0~400Hz, 9999 0.01Hz 9999 P46
P.27 Speed 7 0~400Hz, 9999 0.01Hz 9999 P46
Output frequency filtering
P.28 0~31 1 0 P56
constant
Acceleration/deceleration
P.29 0, 1, 2 1 0 P56
pattern selection
Regenerative function
P.30 0, 1 1 0 P58
selection
P.31 Soft-PWM selection 0、1 1 0 P58
Serial communication
P.32 0, 1, 2 1 1 P59
Baud rate selection
Communication protocol
P.33 0, 1 1 0 P59
selection
P.34 Reserved
P.35 Reserved
P.36 Inverter station number 0~254 1 0 P59
P.37 Speed display 0~5000r/min 0.1r/min 0 P74
The maximum output
frequency(the target
50Hz/60Hz
P.38 frequency is set by the 1~400Hz 0.01Hz P75
(Note 2)
input signal across terminal
2-5/panel knob)
The maximum output
frequency(the target
50Hz/60Hz
P.39 frequency is set by the 1~400Hz 0.01Hz P79
(Note 2)
input signal across terminal
4-5)
Multi-function output
P.40 0~10 1 0 P80
terminal pattern
P.41 Up-to-frequency sensitivity 0~100% 0.1% 10% P82
Output frequency detection
P.42 0~400Hz 0.01Hz 6Hz P83
for forward rotation
Output frequency detection
P.43 0~400Hz, 9999 0.01Hz 9999 P83
for reverse rotation
0~360.00s/
P.44 Second acceleration time 0.01s/0.1s 9999 P47
0~3600.0s、9999
0~360.00s/
P.45 Second deceleration time 0.01s/0.1s 9999 P47
0~3600.0s、9999
P.46 Second torque boost 0~30%, 9999 0.1% 9999 P43

129
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
P.47 Second base frequency 0~400Hz, 9999 0.01Hz 9999 P44
P.48 Data length 0, 1 1 0 P59
P.49 Stop bit length 0, 1 1 0 P59
P.50 Parity check selection 0, 1, 2 1 0 P59
P.51 CR and LF selection 1, 2 1 1 P59
Number of
P.52 0~10 1 1 P59
communication reties
Communication check
P.53 0~999.8s, 9999 0.1s 9999 P59
time interval
AM terminal function
P.54 0, 1 1 0 P83
selection
Frequency monitoring 50Hz/60Hz
P.55 0~400Hz 0.01Hz P83
reference (Note 2)
Current monitoring Related output
P.56 0~500A 0.01A P83
reference current
P.57 Retry coasting time 0~30s, 9999 0.1s 9999 P85
P.58 Retry voltage rising time 0~60s 0.1s 10s P85
Selection of frequency
P.59 0, 1 1 1 P75
sources
Input signal filtering
P.60 0~31 1 31 P86
constant
Remote setting function
P.61 0~3 1 0 P86
selection
Zero current detection
P.62 0~200%, 9999 0.1% 5% P88
level
Zero current detection
P.63 0.05~1s, 9999 0.01s 0.5s P88
time
P.64 Reserved
P.65 Retry selection 0~4 1 0 P89
Stall prevention operation
50Hz/60Hz
P.66 reduction level starting 0~400Hz 0.01Hz P55
(Note 2)
frequency
Number of retries at alarm
P.67 0~10 1 0 P89
occurrence
P.68 Retry waiting time 0~360s 0.1s 6s P89
P.69 Retry accumulation times 0 0 0 P89
Special regenerative brake
P.70 0~30% 0.1% 0 P58
duty

130
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
Idling braking and linear
P.71 0, 1 1 1 P90
braking selection
P.72 Carrier frequency 0.7~14.5kHz 0.1kHz 5.0 kHz P90
P.73 Voltage signal selection 0, 1 1 0 P75
P.74 Reversed
Stop or Reset function
P.75 0~1 1 1 P91
selection
Panel knob signal input
P.76 0~400Hz 0.01Hz 0Hz P75
frequency bias
Parameters write
P.77 0, 1, 2 1 0 P92
protection
Selection of forward/
P.78 reverse rotation 0, 1, 2 1 0 P92
prevention
P.79 Operation mode selection 0~8 1 0 P92
Multi-function terminal
P.80 0~39 1 2 P93
M0 function selection
Multi-function terminal
P.81 0~39 1 3 P93
M1 function selection
Multi-function terminal
P.82 0~39 1 4 P93
M2 function selection
Multi-function terminal
P.83 0~39 1 0 P93
STF function selection
Multi-function terminal
P.84 0~39 1 1 P93
STR function selection
Function selection for
P.85 0~10 1 5 P80
multi-function relay
Multi-function terminal
P.86 0~39 1 30 P93
RES function selection
P.87 Reversed
P.88 Reversed
Slip compensation
P.89 0~10 1 0 P97
coefficient
P.90 Reserved
P.91 Frequency jump 1A 0~400Hz, 9999 0.01Hz 9999 P97
P.92 Frequency jump 1B 0~400Hz, 9999 0.01Hz 9999 P97
P.93 Frequency jump 2A 0~400Hz, 9999 0.01Hz 9999 P97
P.94 Frequency jump 2B 0~400Hz, 9999 0.01Hz 9999 P97
P.95 Frequency jump 3A 0~400Hz, 9999 0.01Hz 9999 P97

131
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
P.96 Frequency jump 3B 0~400Hz, 9999 0.01Hz 9999 P97
P.97 Reserved
P.98 Middle frequency 1 0~400Hz 0.01Hz 3Hz P51
Voltage output 1 at middle
P.99 0~100% 0.1 10 P51
frequency
P.100 Minute/second selection 0, 1 1 1 P98
Runtime of section 1 in
P.101 0~6000s 0.1s 0s P98
programmed operation mode
Runtime of section 2 in
P.102 0~6000s 0.1s 0s P98
programmed operation mode
Runtime of section 3 in
P.103 0~6000s 0.1s 0s P98
programmed operation mode
Runtime of section 4 in
P.104 programmed operation 0~6000s 0.1s 0s P98
mode
Runtime of section 5 in
P.105 0~6000s 0.1s 0s P98
programmed operation mode
Runtime of section 6 in
P.106 0~6000s 0.1s 0s P98
programmed operation mode
Runtime of section 7 in
P.107 0~6000s 0.1s 0s P98
programmed operation mode
Runtime of section 8 in
P.108 0~6000s 0.1s 0s P98
programmed operation mode
Operation panel frequency
P.110 0, 1, 2 1 0 P100
monitoring selection
Acceleration/deceleration
P.111 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 1
Acceleration/deceleration
P.112 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 2
Acceleration/deceleration
P.113 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 3
Acceleration/deceleration
P.114 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 4
Acceleration/deceleration
P.115 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 5
Acceleration/deceleration
P.116 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 6
Acceleration/deceleration
P.117 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 7

132
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
Acceleration/deceleration
P.118 0~600s/0~6000s 0.01s/0.1s 0s P98
time of section 8
P.119 Reserved
P.120 The output signal delay time 0~3600s 0.1s 0s P80
P.121 Run direction in each section 0~255 1 0 P98
P.122 Cycle selection 0~8 1 0 P98
Acceleration/deceleration
P.123 0, 1 1 0 P98
time setting selection
P.125 Expansion board type --- --- 0 P100
I/O expansion board input
P.126 terminal M3 function 0~39, 9999 1 9999 P100
selection
I/O expansion board input
P.127 terminal M4 function 0~39, 9999 1 9999 P100
selection
I/O expansion board input
P.128 terminal M5 function 0~39, 9999 1 9999 P100
selection
I/O expansion board output
P.129 0~10, 9999 1 9999 P100
relay1 function selection
I/O expansion board output
P.130 0~10, 9999 1 9999 P100
relay2 function selection
P.131 Frequency of section 1 0~400Hz 0.01Hz 0Hz P98
P.132 Frequency of section 2 0~400Hz 0.01Hz 0Hz P98
P.133 Frequency of section 3 0~400Hz 0.01Hz 0Hz P79
P.134 Frequency of section 4 0~400Hz 0.01Hz 0Hz P98
P.135 Frequency of section 5 0~400Hz 0.01Hz 0Hz P98
P.136 Frequency of section 6 0~400Hz 0.01Hz 0Hz P98
P.137 Frequency of section 7 0~400Hz 0.01Hz 0Hz P98
P.138 Frequency of section 8 0~400Hz 0.01Hz 0Hz P98
P.139 Voltage signal bias 0%~100% 0.1% 0% P75
P.140 Voltage signal gain 0.1%~200% 0.1% 100% P75
Bias polarity of voltage signal
P.141 and reverse motion of 0~11 1 0 P75
negative bias
P.142 Speed 8 0~400Hz 0.01Hz 0Hz P46
P.143 Speed 9 0~400Hz, 9999 0.01Hz 9999 P46
P.144 Speed 10 0~400Hz, 9999 0.01Hz 9999 P46

133
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
P.145 Speed 11 0~400Hz, 9999 0.01Hz 9999 P46
P.146 Speed 12 0~400Hz, 9999 0.01Hz 9999 P46
P.147 Speed 13 0~400Hz, 9999 0.01Hz 9999 P46
P.148 Speed 14 0~400Hz, 9999 0.01Hz 9999 P46
P.149 Speed 15 0~400Hz, 9999 0.01Hz 9999 P46
P.150 Restart mode selection 0~221 1 0 P85
Zero-speed control function
P.151 0, 1 1 0 P101
selection
Voltage instruction when
P.152 0~30% 0.1% 5% P101
zero-speed control
Communication error
P.153 0, 1 1 0 P59
handling
P.154 Modbus protocol selection 0~5 1 4 P59
P.155 Over torque detection lelve 0~200% 0.1% 0% P102
P.156 Over torque detection time 0~60s 0.1s 1 P102
External terminals filter
P.157 0~200ms 1ms 4ms P102
function selection
External terminal power
P.158 0、1 1 0 P103
enable
energy-saving control
P.159 0、1 1 0 P103
function
stall prevention operation
P.160 0~200% 0.1% 120% P85
level when restart
Multi-function display
P.161 0~5 1 0 P103
selection
P.162 Middle frequency 2 0~400Hz、99999 0.01Hz 99999 P51
Voltage output 2 at middle
P.163 0~100% 0.1% 0 P51
frequency
P.164 Middle frequency 3 0~400Hz、99999 0.01Hz 99999 P51
Voltage output 3 at middle
P.165 0~100% 0.1% 0 P51
frequency
P.166 Middle frequency 4 0~400Hz、99999 0.01Hz 99999 P51
Voltage output 4 at middle
P.167 0~100% 0.1% 0 P51
frequency
P.168 Middle frequency 5 0~400Hz、99999 0.01Hz 99999 P51
Voltage output 5 at middle
P.169 0~100% 0.1% 0 P51
frequency
P.170 PID selection 0、1、2 1 0 P104

134
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
PID feedback control method P104
P.171 0~1000% 1% 100%
selection
P.172 PID proportion Gain 1~100 1 20 P104
P.173 PID integration Gain 0~100s 0.1s 1s P104
P.174 PID differential Gain 0~1000ms 1ms 0 P104
P.175 Abnormal deviation level 0~100% 0.1% 70% P104
P.176 Exception duration time 0~600s 0.1s 0s P104
P.177 Exception handling mode 0、1 1 0 P104
P.178 Sleep detect deviation 0~100% 0.1% 0 P104
P.179 Sleep detect duration time 0~255s 0.1s 10s P104
P.180 Revival level 0~100% 0.1% 90% P104
P.181 Outage level 0~120Hz 0.01Hz 40Hz P104
P.182 Upper integral 0~120Hz 0.01Hz 60Hz P104
Deceleration step length of
P.183 0~10Hz 0.01Hz 0.5Hz P104
pressure stability
Disconnection processing
P.184 0~3 0 0 P107
function of terminal 4-5
Ultra-high-speed operation
P.187 0~1 1 0 P108
function selection
P.188 Software edition --- --- --- P108
P.189 Default function 0, 1 1 1 P108
P.190 AM output bias 0~1024 1 80 P83
P.191 AM output gain 0~1024 1 900 P83
Minimum input voltage across
P.192 0~10 0.01 0 P109
terminal 2-5
Maximum input voltage across
P.193 0~10 0.01 0 P109
terminal 2-5
Frequency corresponds to the
P.194 minimum input voltage across 0~60Hz 0.01Hz 0Hz P109
terminal 2-5
Frequency corresponds to the
50Hz/60Hz
P.195 maximum input voltage across 0~400Hz 0.01Hz P109
(注 2)
terminal 2-5
Frequency corresponds to the
P.196 minimum input current/voltage 0~60Hz 0.01Hz 0Hz P110
across terminal 4-5

135
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
Frequency corresponds to the
50Hz/60Hz
P.197 maximum input currentvoltage 0~400Hz 0.01Hz P110
(注 2)
across terminal 4-5
Minimum input current/voltage
P.198 0~20 0.01 0 P110
across terminal 4-5
Maximum input current/voltage
P.199 0~20 0.01 0 P110
across terminal 4-5
Backlash compensation
P.229 0~1 1 0 P111
function selection
The backlash compensation
P.230 0~400Hz 0.01Hz 1Hz P111
acceleration interrupt frequency
The backlash compensation
P.231 0~360s 0.1s 0.5s P111
acceleration interrupt time
The backlash compensation
P.232 0~400Hz 0.01Hz 1Hz P111
deceleration interrupt frequency
The backlash compensation
P.233 0~360 s 0.1s 0.5s P111
deceleration interrupt time
Triangular wave function
P.234 0~2 1 0 P112
selection
P.235 Maximum amplitude 0~25% 0.1% 10% P112
Amplitude compensation for
P.236 0~50% 0.1% 10% P112
deceleration
Amplitude compensation for
P.237 0~50% 0.1% 10% P112
acceleration
0~360s
P.238 Amplitude acceleration time 0.01 s/0.1s 10 s P112
/0~3600 s
0~360s
P.239 Amplitude deceleration time 0.01 s/0.1s 10s P112
/0~3600 s
Auxiliary frequency function
P.240 0~4 1 0 P113
selection
DC injection brake function
P.242 0~1 1 0 P114
before starting selection
DC injection brake time before
P.243 0~60s 0.1s 0.5s P114
starting
DC injection brake voltage
P.244 0~30% 0.1% 4% P114
before starting
P.247 MC switch interlock time 0.1~100s 0.1s 1s P114
P.248 Start waiting time 0.1~100s 0.1s 0.5s P114

136
Appendix 1 Parameter list
Parameter list

Parameter Minimum User setting Reference


Name Setting range Default value
number setting unit value page
Automatic switchover
P.249 frequency from inverter to 0~60Hz,9999 0.01Hz 9999 P114
bypass operation
Automatic switchover
P.250 frequency range from bypass to 0~10Hz,9999 0.01Hz 9999 P114
inverter operation
P.288 Alarm history number 0~12 1 0 P117
P.289 Alarm code --- --- 0 P117
The latest alarm status
P.290 0~5 1 0 P117
selection
P.291 The latest alarm status --- --- 0 P117
Accumulative motor operation
P.292 0~1439min 1min 0min P118
time (min)
Accumulative motor operation
P.293 0~9999day 1day 0day P118
time (day)
P.294 Password input 0~65535 1 0 P119
P.295 Password set 0~65535 1 0 P119
P.300 Motor control mode selection 0~3 1 0 P119
Motor parameter auto
P.301 0~3 1 0 P119
measurement function selection
P.302 Motor rated power 0~160 0.01 0 P121
P.303 Motor poles 0~8 1 4 P121
P.304 Motor rated voltage 0~440V 1V 220/440V P121
50Hz/60Hz
P.305 Motoe rated frequency 0~400Hz 0.01Hz P121
(Note 2)
Determined by
P.306 Motoe rated current 0~500A 0.01 A P121
horsepower
0~65535 1410/1710 r/min
P.307 Motoe rated speed 1 r/min P121
r/min (Note 2)
Determined by
P.308 No load excitation current 0~500A 0.01 A P121
horsepower
Determined by
P.309 Stator resistance 0~65535 0.01 P121
horsepower
Determined by
P.310 Rotor resistance 0~65535 0.01 P121
horsepower
Determined by
P.311 Leakage inductance 0~65535 0.1 P121
horsepower
Determined by
P.312 Mutual inductance resistance 0~65535 0.1 P121
horsepower

137
Appendix 1 Parameter list
Parameter list

Parameter Minimum Default User setting Reference


Name Setting range
number setting unit value value page
Speed control scale
P.320 0~2000% 1% 100% P122
coefficient
Speed control integral
P.321 0~20s 0.01s 0.30s P122
coefficient
P.994 Parameter copy readout Refer to Chapter 4 --- --- --- P123
P.995 Parameter copy write-in Refer to Chapter 4 --- --- --- P123
P.996 Alarm log erasure Refer to Chapter 4 --- --- --- P123
P.997 INV Reset Refer to Chapter 4 --- --- --- P124
P.998 Parameter total- initialization Refer to Chapter 4 --- --- --- P124
P.999 Parameter partial-initialization Refer to Chapter 4 --- --- --- P124

Note: 1.The torque boost, motor rated current and the stator resistance values are in the table as follows:

Inverter Type P. 0 P. 9(A)


SE2-021-0.4KW 6 3.0
SE2-021-0.75KW 6 5.0
SE2-021-1.5KW 4 8.0
SE2-021-2.2KW 4 11.0
SE2-023-0.4KW 6 3.0
SE2-023-0.75KW 6 5.0
SE2-023-1.5KW 4 8.0
SE2-023-2.2KW 4 11.0
SE2-023-3.7KW 4 17.5
SE2-023-5.5KW 3 24.0
SE2-023-7.5KW 3 33.0
SE2-043-0.4KW 6 1.5
SE2-043-0.75KW 6 2.6
SE2-043-1.5KW 4 4.2
SE2-043-2.2KW 4 6.0
SE2-043-3.7KW 4 9.0
SE2-043-5.5KW 3 12.0
SE2-043-7.5KW 3 17.0
SE2-043-11KW 2 23.0
SE2-021-0.2KW 6 1.6
2. The default value is due to the set value of P.189. When P.189=0, the default value is 60Hz, which is
applied to the 60Hz system. When P.189=1, whe default value is 50Hz, which is apply to the 50Hz
system.
3. The minimum value and setting range of all the frequency related parameters can choose by P.187. You can
refer to Appendix 6 for details.

138
Appendix 2 Alarm Code List
Alarm Code

Code Screen Display Cause Troubleshooting


1. Under-voltage for
power supply
2. The RES is ‘on’ 1. Provide a normal power supply
3. Bad connection 2. Shut off RES
between the operation 3. Ensure firm connection between
ERR panel and main the operation panel and the main
machine machine
4. Internal circuit 4. Replace the inverter
malfunction 5. Restart the inverter
5. Wrong operation of
CPU
The inverter may be disturbed. Please
OC1 restart the inverter. If the alarm
Over-current repeated, please send the inverter back
when stop to the factory.

OC1
Over-current
during
The output current is two
acceleration 1. In case the time for acceleration or
times larger than the rated
deceleration is too short, please
OC2 current of the inverter.
prolong it.
Over-current at 2. Avoid abrupt increase of load.
constant speed 3. Check Terminals U, V and W for
short circuit.
OC3
Over-current
during
deceleration

OV0 Check whether the power supply is


Over- voltage normal or abnormal.
when stop

OV1 Over-voltage between


1. In case the time for acceleration or
deceleration is too short, please
Over-voltage Terminal P and Terminal
prolong it.
during N
2. Check the brake resistor between
acceleration
terminal P and PR for loose
OV2 connection.
3. Check whether the values of P.30
Over-voltage at
and P.70 are right or not.
constant speed

139
Appendix 2 Alarm Code List
Alarm Code

Code Screen Display Cause Troubleshooting

OV3
Over-voltage between Terminal
Over-voltage Please refer to OV1, OV2.
P and Terminal N
during
deceleration

THT Avoid the inverter long timely


The IGBT module thermal
The IGBT operating under overload
accumulating relay acts
module is condition
overheating
1. Check whether the set
THN The electronic thermal relay
value of the P.9 is correct
or not (the set value should
Motor operates
comply the actual motor)
overheating
2. Reduce load

OHT 1. Check the capacity of the


The external thermal relay external thermal relay and
The external
operates the motor for matching.
thermal relay
2. Reduce the load
operates.
1. Abnormal communication.
The maximum
OPT communication retry
number is violated. Correctly set the
Peripheral
2. Interrupted communication. communication parameters
devices are
The maximum
abnormal
communication check time
interval is violated.

EEP
The memory ROM fails Send it back to the factory.
Memory is
abnormal

CPU External electromagnetic


Improve external disturbance
disturbance is too strong
CPU error

OLS The load of the motor is too


1. Reduce the load of the
motor.
Stall prevention heavy.
Increase the value of P.22.
protection

140
Appendix 2 Alarm Code List
Alarm Code

Code Screen Display Cause Troubleshooting


4. Exchange a larger capacity
inverter and motor.
5. Check the value which
1. The capacitr of inverter
setting of PID feel-back
and motor is not enough.
signal Gain,setting the value
2. Setting PID target
PIDE value and feed-back
again according to PID
feed-back signal Gain.
PID abnormal value unreasonable
3. Check whether the external
3. peripheral equipment
feedback device (such as
failure
sensor, regulation resistance)
and circuit is normal or
abnormal.
The output current is two Check Terminals U, V and W for
SCP times larger than the rated short circuit. (such as the motor
Over-current current of the inverter. wiring)
1. Reduce the environment
NTC temperature and improve the
The temperature of IGBT
The IGBT air condition
module is too high
module is 2. Check whether the fan of the
overheating inverter is damaged.
1. Check the wiring.
CPR CPU software abnormal 2. Check the parameter setting.
CPU abnormal 3. Improve external disturbance.
The inverter’s first auto
EbE detection result is different Check the connection between the
from the next one, or they are expansion board and the main
Expansion
the same, but not the existing machine.
board abnormal
types of expansion board.
1. Too heavy load of motor.
1. Alleviate the load of motor.
OL2 2. The setting value of
2. Adjustment the setting value
P.155 and P.156 is
Over torque of P.155 and P.156 properly
unreasonable.
abnormal

Note: 1. When the above alarms occur, the inverter will stop. Please deal with these alarms according to the
methods mentioned above.
2. When the above alarms occur, the inverter will stop. Please deal with these alarms according to the
methods mentioned above.
3. The abnormal number of alarm code can refer to page 118.

141
Appendix 3 Warning code list
Warning code

Code Screen Display Cause Troubleshooting

When the output current is


larger than Stall prevention 1. Check if the values of
operation level, the three lights P.22, P.23, and P.66
PU Hz
MON V A on the left side of the screen are proper.
Current stall RUN EXT

flicker, indicating that the 2. Check if the values of


flicker
inverter is in current stall mode. P.7 and P.8 are too
In this case the motor may not small.
run smoothly.
When the voltage between P
and N is too high, the three 1. Add a brake resistor
PU Hz lights on the right side of the between P and PR.
MON V A
Voltage stall RUN EXT
screen flicker, indicating that 2. Check if the values of
flicker the inverter is in voltage stall P.7 and P.8 are too
mode. Then the motor may not small
run smoothly.

LV Input voltage is low.


Supply with the normal
voltage
Low voltage
1. Please increase the
acceleration/decelerati
When the output current is more
on time in case of
than twice the rated current, but
abrupt
PU Hz it doesn’t reach the stall level,
MON V A acceleration/decelera-t
RUN EXT
all the six lights on both side of
LT motion ion.
flicker the screen flicker, indicating
2. Avoid abrupt load
that the inverter is in LT mode.
increasing.
Then the motor may not run
3. Check whether there is
smoothly.
short circuit among
U,V and W.

Note: The above phenomenas are to show the working state of the inverter, and the inverter will not stop. To get
around the above troubles, please adjust the parameters properly or check the power supply and load
carefully.

142
Appendix 4 Troubles and Solutions
Troubles and Solutions

Trouble Check points


Check the • Check that a proper power supply voltage is applied.
Main • Check that the Power Lamp is lit.
circuit • Check that the motor is connected properly.
Check the • Check that the load is not too heavy.
load • Check that the shaft is not locked.
• Check that the starting frequency (P.13) setting is not
greater than the target frequency.
• Check that the operation mode (P.79) setting is correct.
Check the
• Check that the maximum frequency (P.1) is not set to 0.
parameter
• Check that the reverse rotation prevention (P.78) is not
settings
selected.
• Check that the bias and gain (P.194~P.197) setting is correct.
Motor remains stopped
• Check that the frequency jump (P.91~P.96) setting is correct.
• Check that the output stop signal (MRS) is not on. (The
related parameter is P.80~P.84, P.86.)
• Check that the reset signal (RES) is not on. (The related
parameter is P.80~P.84, P.86).
Check the • Check that the external thermal relay does not operate.
control • Check that the ALARM lamp is off and the reset is not
circuit executed.
• Check that voltage/current start signal is input.
• Check that the signal STF/STR is correct.(The related
parameter is P.80~P.84, P.86.)
• Check that wiring for the control circuit is ok.
• Check that the phase sequence of output terminals U, V and W is
Motor rotates in opposite
correct.
direction
• Check that the start signals (STF and STR) are connected properly.
• Check that the load is not too heavy.
• Check that the stall prevention level (P.22) setting is correct.
Speed does not increase.
• Check that the torque boost (P.0) setting is correct.
• Check that the maximum frequency (P.1) setting is correct.
• Check that the acceleration/ deceleration time (P.7, P.8) settings are not
Acceleration/ deceleration too short.
is not smooth • Check that the acceleration/ deceleration pattern (P.29) setting is correct.
• Check that the voltage/current input signal is affected by noises.
• Check that the load is not too heavy.
Motor current is large • Check that the torque boost setting is not too large.
• Checher whether the torque boost (P.0) is set too large.
• Check that the frequency setting signal is not affected by noise.
Speed varies during
• Check that the load is not varying.
operation
• Check that the wiring length for the main circuit is correct.

143
Appendix 5 Optional equipment
Optional equipment

1. Expansion board (Please according to the choose expansion board and the function to set the
parameter from P.126 to P.130)
(1). I/O expansion board(SE-EB01)
3 On-off signal input and 2 Relay output can be expanded, shown as follows:

Terminal Terminal Function


Remarks and function description
type name name
M3 Optional
For detailed descriptions, please refer to P.126~P.128 in
On-off M4 Optional
Chapter 4.
signal input M5 Optional
SD SD Common reference Ground for M3, M4 and M5.
In the ‘source input’ mode, it provides a common power
PC PC
supply for the terminals referred above.
A1 ---
Relay Normally, points A-C are always open-circuit; points B-C
B1 ---
output 1 are always ‘short-circuit’.
C1 ---
These terminals are multi-function relay output. For
A2 ---
Relay detailed description, please refer to P.129~P.130.
B2 ---
output 2 (Note) Contactor capacity: VDC30V / VAC230V­- 0.3A
C2 ---

(2). Terminal block communication expansion board(SE-CB01)


RS485/422 serial communication, both Shinlin protocol and Modbus protocol can be chosed,
Shown as follows:

144
Appendix 5 Optional equipment
Optional equipment

Terminal Function
Terminal type Remarks and function description
name name
SDA SDA
485 SDB SDB
RS485/422 serial communication terminal
communication RDA RDA
terminal RDB RDB
P5S P5S 5V Source
SG SG 5V Ground

(3). Communication expansion board for RJ-11 connector (SE-CB02)


There are two RJ-11 connectors on the board, please use them with the corresponding
transmission cable.

(4). Communication expansion board for RJ-45 connector (SE-CB03)


This communication expansion board use CBL cable to connecte DU01.

(5). 4~20mA current source expansion board (SE-IB01)

145
Appendix 5 Optional equipment
Optional equipment

Terminal Terminal Function


Remarks and function description
type name name
Connected with an external analog meter to indicate the
Analog AMI ---
output frequency or current.
signal
P5S P5S 5V Source
output
5 5 5V Ground

(6). Profibus communication expansion board (SE2-PD01)

1). SE2-PD01 meets EN50170 standards, using profidrive DPV0 standards.


2). SE2-PD01 as a slave for Profibus network, the maximum rate of communication to support
12M.
3). SE2-PD01 using a common terminal form to connect profibus network, addresses is from 1
to 125.
4). Connect SE2-PD01, please use the unshielded twisted pair RS-485 cable (recommended
PROFIBUS approved cable).
5). SE2-PD01 power is supplied by the inverter which connected to it.

Terminal Function
Terminal type Remarks and function description
name name
FG SHIELD Shield ground
D- RxD/TxD- N Profibus Data -
D+ RxD/TxD- P Profibus Data +
Profibus
CNTR RTS Profibus request signal
communication
terminal Data
V- reference 5V Ground and reference Ground for data
potential (C)
V+ +5V 5V Source

SP LED: Instructed the inverter and SE2-PD01 connection status.


NET LED: Instructed SE2-PD01 and the Profibus DP network connection status.
Note: The shihlin inverter can automatically identify the SE2-PD01 communications expansion board, and adjust
the corresponding parameters of its own with the SE2-PD01 to make a successful connection, the user in the
course of communication do not modify the drive parameters, so as not to affect the SE2-PD01 normal work

146
Appendix 5 Optional equipment
Optional equipment
(7). DeviceNet communication expansion board (SE2-DN01)

1). SE2-DN01 meets ODVA DeviceNet standards.


2). SE2-DN01 as a slave for DeviceNet network, support for 125k, 250k, 500k baud rate of
communication
3). SE2-DN01 using a common terminal form to connect DeviceNet network, addresses is from
0 to 63.
4). Connect SE2-DN01, please use the standard DeviceNet specific cable.
5). The power of SE2-DN01 is supplied by the 24V power supply from DeviceNet network.

Terminal Function
Terminal type Remarks and function description
name name
V+ V+ Isolated 24V power supply
CAN+ CAN_H CAN_H signal
DeviceNet
SHIELD SHIELD Network cable shield
communication
CAN- CAN_L CAN_L signal
terminal
V- V- Isolated ground
--- Empty ---

NS LED: Instructed SE2-DN01 and the DeveceNet network connection status.


MS LED: Instructions SE2 - DN01 internal modules working condition.
SP LED: Instructed the inverter and SE2-DN01 Working condition.
Address switch 1~6: Set the communication address of SE2-DN01 in DeviceNet network.
Baud rate setting switch 7~8: Set the communication rate of SE2-DN01.
Note: 1. 00 representative of 125k, 01 representative of 250k, 10 representative of 500k, 11 representative
automatically set baud rate.
2. The shihlin inverter can automatically identify the SE2-DN01 communications expansion board, and adjust
the corresponding parameters of its own with the SE2-DN01 to make a successful connection, the user in
the course of communication do not modify the drive parameters, so as not to affect the SE2-DN01 normal
work

147
Appendix 5 Optional equipment
Optional equipment
2. Operation panel, fixing pedestal and transmission cable
(1). DU03B opreation panel sets (opreation panel and fixing pedestal, the units in the figure
below is mm)

The assembly dimensions of the fixing pedestal are as follows:

NO. Model Name


1 SNKDU03B DU03B operation panel sets

148
Appendix 5 Optional equipment
Optional equipment

(2). DU05 operation panel

The assembly dimensions of the fixing pedestal are as follows:

NO. Model Name


1 SNKDU05 DU05 operation panel

149
Appendix 5 Optional equipment
Optional equipment

(3). DU01 operation panel sets (operation panel and fixing pedestal)

NO. Model Name


1 SNKDU01S DU01 operation panel sets

(4). PU01 operation panel sets

NO. Model Name


1 SNKSHPU01 PU01 operation panel sets

150
Appendix 5 Optional equipment
Optional equipment

(5). CBL: Transmission cable used with the above operation panel

Ordering code instructions:

NO. Model Name Ordering code


1 CBL1R5GT Transmission cable (1.5M) SNKCBL1R5GT
2 CBL03GT Transmission cable (3M) SNKCBL03GT
3 CBL05GT Transmission cable (5M) SNKCBL05GT

151
Appendix 6 Frequency parameters of ultra-high-speed
Frequency parameters

1. After setting the inverter ultra high-speed operation function parameter P.187, please be sure to
set P.998 to adjust the frequency-dependent parameters.
2. In the use of inverter ultra-high-speed operation function, do not use PU series operation panels
to achieve parameter copy function by set P.994 and P.995.
3. Inverter ultra-high speed operation function, by the use of communication written in frequency,
please pay attention to the size of the set value. Because if P.187 = 1, minimum setting unit is 0.1
Hz.
For example: Change value of P.195 to 50 (initial value is 60) in communication example 4.
Step1 and step 2 are the same as step1 and step2 of example 3.
Step 3. The PC requests the inverter to inputting 50 into P.195, using the format A:
Station number Command Waiting Data
ENQ Sum Check CR
0 Code HDF Time H1388
H05 H30 H30 H44 H46 H30 H31 H33 H38 H38 H45 H45 H0D

195 minus 100 equal 95, then Minimum unit of P.195 is 0.1, therefore
convert 95 to hexadecimal H5F, 50*10=500, then convert 500 to
H5F+H80=HDF. Hexadecimal H01F4, and convert 0,1,F,4
to ASCII CODE to send out.
4. On the ultra-high-speed operation function, the can not use the sensor vector speed control
function.
5. When P.187=1, the minimum value and setting range of all the frequency related parameters is follow in the
below table.

Parameter number Name Setting range Minimum setting unit


P.1 Maximum frequency 0~1000Hz 0.1Hz
P.2 Minimum frequency 0~1000Hz 0.1Hz
P.3 Base frequency 0~1000Hz 0.1Hz
P.4 Speed 1 (high speed) 0~1000Hz 0.1Hz
P.5 Speed 2 (middle speed) 0~1000Hz 0.1Hz
P.6 Speed 3 (low speed) 0~1000Hz 0.1Hz
P.10 DC injection brake operation frequency 0~1000Hz 0.1Hz
P.13 Starting frequency 0~600Hz 0.1Hz
P.15 JOG frequency 0~1000Hz 0.1Hz
P.18 High-speed maximum frequency 120~1000Hz 0.1Hz
Acceleration/deceleration reference
P.20 1~1000Hz 0.1Hz
frequency
P.24 Speed 4 0~1000Hz、9999 0.1Hz
P.25 Speed 5 0~1000Hz、9999 0.1Hz
P.26 Speed 6 0~1000Hz、9999 0.1Hz
P.27 Speed 7 0~1000Hz、9999 0.1Hz

152
Appendix 6 Frequency parameters of ultra-high-speed
Frequency parameters

Parameter number Name Setting range Minimum setting unit


The maximum output frequency(the target
P.38 frequency is set by the input signal across 1~1000Hz 0.1Hz
terminal 2-5/panel knob)
The maximum output frequency(the target
P.39 frequency is set by the input signal across 1~1000Hz 0.1Hz
terminal 4-5)
Output frequency detection for forward
P.42 0~1000Hz 0.1Hz
rotation
Output frequency detection for reverse
P.43 0~1000Hz、 9999 0.1Hz
rotation
P.47 Second base frequency 0~1000Hz、
9999 0.1Hz
P.55 Frequency monitoring reference 0~1000Hz 0.1Hz
Stall prevention operation reduction starting
P.66 0~1000Hz 0.1Hz
frequency
P.76 Panel knob signal input frequency bias 0~1000Hz 0.1Hz
P.91 Frequency jump 1A 0~1000Hz、
9999 0.1Hz
P.92 Frequency jump 1B 0~1000Hz、
9999 0.1Hz
P.93 Frequency jump 2A 0~1000Hz、
9999 0.1Hz
P.94 Frequency jump 2B 0~1000Hz、
9999 0.1Hz
P.95 Frequency jump 3A 0~1000Hz、
9999 0.1Hz
P.96 Frequency jump 3B 0~1000Hz、
9999 0.1Hz
P.98 Middle frequency 1 0~1000Hz 0.1Hz
P.131 Frequency of section 1 0~1000Hz 0.1Hz
P.132 Frequency of section 2 0~1000Hz 0.1Hz
P.133 Frequency of section 3 0~1000Hz 0.1Hz
P.134 Frequency of section 4 0~1000Hz 0.1Hz
P.135 Frequency of section 5 0~1000Hz 0.1Hz
P.136 Frequency of section 6 0~1000Hz 0.1Hz
P.137 Frequency of section 7 0~1000Hz 0.1Hz
P.138 Frequency of section 8 0~1000Hz 0.1Hz
P.142 Speed 8 0~1000Hz 0.1Hz
P.143 Speed 9 0~1000Hz、
9999 0.1Hz
P.144 Speed 10 0~1000Hz、
9999 0.1Hz
P.145 Speed 11 0~1000Hz、
9999 0.1Hz
P.146 Speed 12 0~1000Hz、
9999 0.1Hz
P.147 Speed 13 0~1000Hz、
9999 0.1Hz
P.148 Speed 14 0~1000Hz、
9999 0.1Hz
P.149 Speed 15 0~1000Hz、
9999 0.1Hz
153
Appendix 6 Frequency parameters of ultra-high-speed
Frequency parameters

Parameter number Name Setting range Minimum setting unit


P.162 Middle frequency 2 0~1000Hz、9999 0.1Hz
P.164 Middle frequency 3 0~1000Hz、9999 0.1Hz
P.166 Middle frequency 4 0~1000Hz、9999 0.1Hz
P.168 Middle frequency 5 0~1000Hz、9999 0.1Hz
P.181 Outage level 0~1000Hz 0.1Hz
P.182 Upper integral 0~1000Hz 0.1Hz
P.183 Deceleration step length of pressure stability 0~100Hz 0.1Hz
Frequency corresponds to the minimum
P.194 0~600Hz 0.1Hz
input voltage across terminal 2-5
Frequency corresponds to the maximum
P.195 0~1000Hz 0.1Hz
input voltage across terminal 2-5
Frequency corresponds to the minimum
P.196 0~600Hz 0.1Hz
input current/voltage across terminal 4-5
Frequency corresponds to the maximum
P.197 0~1000Hz 0.1Hz
input currentvoltage across terminal 4-5
The backlash compensation acceleration
P.230 0~1000Hz 0.1Hz
interrupt frequency
The backlash compensation deceleration
P.232 0~1000Hz 0.1Hz
interrupt frequency
Automatic switchover frequency from
P.249 0~600Hz,9999 0.1Hz
inverter to bypass operation
Automatic switchover frequency range from
P.250 0~100Hz,9999 0.1Hz
bypass to inverter operation
P.305 Motoe rated frequency 0~1000Hz 0.1Hz

154
Amendment record
Amendment record

Printing Date The manual version Amendment


The first edition

Version: V××
Printing Date: Nov. 2010

155

You might also like