ATVSSP Wiring Diagram-2
ATVSSP Wiring Diagram-2
Beaver, PA
Cutler-Hammer
Power Distribution Components Division
One Tuscarawas Road
Beaver, PA 15009
Standard Features
Test Pushbutton
Simulates a power failure in the logic. Will cause the Generator to start, and load to transfer
to the Emergency Source.
Logic Disconnect
Plugs provided to disconnect the logic circuitry for maintenance purposes.
Auxiliary Contacts
Auxiliary contacts integral to the switching devices rated at 120 VAC, 10 amps. These may
be applied for customer use, and may be applied to certain customer specified options.
The drawing package can be used as a point to point wiring diagram for maintenance and
diagnostic purposes for Solid State Logic SPB Transfer Switches, all voltages.
Page 1
Basic Solid State Intelligence Panel Wiring exclusive of added option functions.
Page 2
Power Switching Panel basic wiring exclusive of added option functions.
Page 3 - 18
Wiring for optional functions.
Page 19
Legend Sheet describing symbols used throughout this document.
Note: Unnumbered sheets may be added to this document on specific occasions to illustrate
custom options additions per order instructions.
All transfer switch units will be standardly wired as indicated by Pages 1 and 2. The
Intelligence Panel and Power Panel are interconnected via keyed plug/socket connectors
(P1-S1/P2-S2). Your specific unit may be equipped with certain optional functions as noted
which require additional wiring as shown on pages 3 - 18.
Wiring for optionally added functions will typically interface with the basic unit wiring
(Pages 1-2) which should be used as the base reference.
Note: BOLD lines on option wiring indicate components and wiring added to the basic
wiring diagram to accomplish that specific option function.
Westinghouse SPB Automatic Transfer Switch
Legend for Wiring Diagram Symbols
Symbol Description Page 19
AM Ammeter
Ex Power Terminal Emergency Source (x = Terminal Number)
EASx Emergency Lockout ( x = contact number)
EC Engine Cooloff Relay Coil
ECx Engine Cooloff Relay Contact ( x = contact number)
EL Emergency Position Indicator Light
EMPB Emergency Pushbutton for Manual Operation
EMR Emergency Relay (Manual Operation)
ER Emergency Relay Coil
ERx Emergency Relay Contact ( x = contact number)
ERA Emergency Auxiliary Relay Coil
ERAx Emergency Auxiliary Relay Contact ( x = contact number)
ERTM Generator Run Time Meter
ESx Emergency Auxiliary Switch ( x = contact number)
ET1 Emergency Transformer ( Line Voltage to 120vac - 2 windings)
ET2 Emergency Transformer (120 to 24vac CT)
ET3 Emergency Transformer ( Line Voltage to 12vac)
ET4 Emergency Transformer (Line Voltage to 12vac)
FPSS Four Position Selector Switch (Option 7)
FR Frequency Sensing Relay
Fx Fuse (x = Fuse Number)
KF Failsafe Relay
KS Load Shed Relay
KT Trip Relay (Used w/Option 16)
KV Voting Relay
MSS Maintenance Selector Switch
NASx Normal Lockout (x = contact number)
Nx Power Terminal, Normal ( x = Terminal number)
NL Normal Position Indicator Light
NMPB Normal Pushbutton for Manual Operation
NR Normal Relay Coil
NRx Normal Relay Contact ( x = contact number)
NRA Normal Auxiliary Relay Coil
NRAx Normal Auxiliary Relay Contact ( x = contact number)
NSx Normal Auxiliary Switch ( x = contact number)
NT1 Normal Transformer (Line Voltage to 120vac - 2 windings)
NT2 Normal Transformer (120 to 24vac CT)
NT3 Normal Transformer (Line Voltage to 12vac)
NT4 Normal Transformer (Line Voltage to 12vac)
Px-y Plug ( x = number, y = Terminal number)
PBEN Bypass TDEN Pushbutton
PBNE Bypass TDNE Pushbutton
PBRE Pushbutton Reset Emergency Trip
PBRN Reset Normal Breaker Trip Pushbutton
PE Plant Exerciser
PSDR Pre-Transfer Signal Device Relay
PSDT Pre-Transfer Signal Device Timer
PSS Preferred Source Selector Switch
Sx-y Socket ( x = number, y = terminal number)
SDL Service Disconnect Light
SDSS Service Disconnect Selector Switch
SD Services Disconnected Light
SE Emergency Source Available Indicator Light
SN Normal Source Available Indicator Light
Tx Power Terminal, Load ( x = Terminal Number)
TDCL Time Delay Crank Time Limiter
TDEC Time Delay Engine Cool Down
TDEN Time Delay Emergency to Normal
TDES Time Delay Engine Start
TDNC Time Delay Neutral
TDNE Time Delay Normal to Emergency
TE Emergency Trip Indicator Light
TM Transfer Motor and Brake
TN Normal Trip Indicator Light
TPB Test Pushbutton
TSS Test Selector Switch
VM Voltmeter