YMvK Dca-S2 0.6 - 1 KV
YMvK Dca-S2 0.6 - 1 KV
YMvK Dca-S2 0.6 - 1 KV
Power cable according to Dutch standard with fire classification Dca-s2,d2,a3 for
usage in low voltage installations up to 0.6/1 kV in housing, residential and simular
installation with a medium fire hazard level
DESCRIPTION
Applications
YMvK Dca 0.6/1 kVis a power cable for general use in construction works subject to
performance requirements on reaction to fire. YMvK Dca 0.6/1 kV is suitable for
application in low voltage installations up to 0.6/1 kV, according to NEN 1010. It meets
the requirements according to fire classification Dca-s2,d2,a3 for usage in buildings
and civil engineering works with a medium fire hazard level (NEN 8012).
Thanks to its improved flexibility YMvK Dca-s2 FLEX 0.6/1 kV is easier to install then
the non-flexible version.YMvK Dca FLEX 0.6.1 kV is available from 35 mm2.
STANDARDS
YMvK Dca-s2 FLEX 0.6/1 kV Easy Strippablehas an improved design with an
easier to strip cable sheaths. With Easy Strippable you can remove the sheath in International HD 604.4D
a single smooth motion over a length of up to 100 cm.
National KEMA 42 C-1-4-D
Design
1. Conductor:
Conductors untill 10 mm2: Bare copper, solid, class 1
Conductors from 10 mm2: Bare copper, stranded, class 2
2. Insulation: XLPE
3. Inner covering: filling compound
4. Outer sheath: PVC
Colour: Grey
UV resistance: Yes
Lead free Rated Voltage Uo/U Mechanical Bending factor Minimum Operating temp. Max.conductor U.V resistance
Yes (Um) resistance to when laying installation -20 - 95 °C temp.in service EN 50289-4-17
0.6/1 kV impacts 10 (xD) temperature 90 °C method A, for
Good 0 °C 720h
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 1 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
CHARACTERISTICS
Construction characteristics
Conductor material Bare copper
Insulation XLPE (chemical)
Protection Filler
Outer sheath PVC
Sheath colour Grey
Lead free Yes
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Mechanical characteristics
Mechanical resistance to impacts Good
Usage characteristics
Field of application Standard
Bending factor when laying 10 (xD)
One single bending at each end minimum 8 (xD)
Minimum installation temperature 0 °C
Operating temperature, range -20 - 95 °C
Max. conductor temperature in service 90 °C
U.V resistance EN 50289-4-17 method A, for 720h
PRODUCT LIST
Nexans Country Name Number of Conductor cross- Nominal outer
Ref. Ref. cores section diameter
[mm²] [mm]
YMvK Dca-s2 0.6/1 kV Easy
10559894 - 2 1.5 10.4
Strippable 2x1.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559791 - 2 1.5 10.4
Strippable 2x1.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559792 - 2 1.5 10.4
Strippable 2x1.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559718 - 2 2.5 11.2
Strippable 2x2.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559716 - 2 2.5 11.2
Strippable 2x2.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559853 - 2 2.5 11.2
Strippable 2x2.5 MM2
10559866 - YMvK Dca-s2 0.6/1 kV 2x4 MM2 2 4 12.2
YMvK Dca-s2 0.6/1 kV 2x4 MM2
10559745 - 2 4 12.2
(R100)
YMvK Dca-s2 0.6/1 kV 2x4 MM2
10559744 - 2 4 12.2
(B500)
10559868 - YMvK Dca-s2 0.6/1 kV 2x6 MM2 2 6 13.5
= Make to order, = In stock,
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 2 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 3 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 4 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 5 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 6 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
Conductor cross-section
[mm²] Cu Cu Cu Cu
1.5 19 23 24 -
2.5 26 31 33 -
4 35 42 45 -
6 45 54 58 -
10 61 75 80 -
16 81 100 107 -
25 106 133 138 161
35 131 164 171 200
50 158 198 209 242
70 200 253 269 310
95 241 306 328 377
120 278 354 382 437
150 318 393 441 504
185 362 449 506 575
240 424 528 599 679
300 486 603 693 783
400 - - - 940
500 - - - 1083
630 - - - 1254
A1 Insulated conductors in conduit in B1 Insulated conductors in C Single-core or multi-core
a thermally insulated wall conduit on a wooden wall cable on a wooden wall
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 7 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu
1.5 19 22 24 25 27 26
2.5 25 30 33 33 35 36
4 33 40 45 43 46 49
6 42 51 58 53 58 53
10 57 69 80 71 77 86
16 76 91 107 91 100 115
25 99 119 138 116 129 149
35 121 146 171 139 155 185
50 145 175 209 164 183 225
70 183 221 269 203 225 286
95 220 265 328 239 270 352
120 253 305 382 271 306 410
150 290 334 441 306 343 473
185 329 384 506 343 387 542
240 386 459 599 395 448 641
300 442 532 693 446 502 741
A2 Multi-core cable in conduit in a B2 Multi-core cable in conduit on a C Single-core or multi-core
thermally insulated wall wooden wall cable on a wooden wall
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 8 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu Cu
1.5 17 20 22 21 23 - -
2.5 23 28 30 28 30 - -
4 31 37 40 36 39 - -
6 40 48 52 44 49 - -
10 54 66 71 58 65 - -
16 73 88 96 75 84 - -
25 95 117 119 96 107 135 141
35 117 144 147 115 129 169 176
50 141 175 179 135 153 207 216
70 179 222 229 167 188 268 279
95 216 269 278 197 226 328 342
120 249 312 322 223 257 383 400
150 285 342 371 251 287 444 464
185 324 384 424 281 324 510 533
240 380 450 500 324 375 607 634
300 435 514 576 365 419 703 736
400 - - - - - 823 868
500 - - - - - 946 998
630 - - - - - 1088 1151
A1 Insulated conductors in conduit B1 Insulated conductors in conduit on a D1 Single or Multi-core cable
in a thermally insulated wall wooden wall in ducts in the ground
D2 Single or Multi-core cables
C Single-core or multi-core cable F Single-core trefoil cables,
designed to be buried directly in the
on a wooden wall touching in free air
ground
F Single-core flat cables, touching
in free air
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 9 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]
Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu
1.5 17 20 21 22 23 23
2.5 22 26 28 30 30 32
4 30 35 36 40 39 42
6 38 44 44 52 49 54
10 51 60 58 71 65 75
16 68 80 75 96 84 100
25 89 105 96 119 107 127
35 109 128 115 147 129 158
50 130 154 135 179 153 192
70 164 194 167 229 188 246
95 197 233 197 278 226 298
120 227 268 223 322 257 346
150 259 300 251 371 287 399
185 295 340 281 424 324 456
240 346 398 324 500 375 538
300 396 455 365 576 419 621
A2 Multi-core cable in conduit in a B2 Multi-core cable in conduit on a D1 Multi-core cable in ducts in
thermally insulated wall wooden wall the ground
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 10 / 10