YMvK Dca-S2 0.6 - 1 KV

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

YMvK Dca-s2 0.

6/1 kV / YMvK Dca-s2 Contact


FLEX 0.6/1 kV Product Management
[email protected]

Power cable according to Dutch standard with fire classification Dca-s2,d2,a3 for
usage in low voltage installations up to 0.6/1 kV in housing, residential and simular
installation with a medium fire hazard level

DESCRIPTION
Applications
YMvK Dca 0.6/1 kVis a power cable for general use in construction works subject to
performance requirements on reaction to fire. YMvK Dca 0.6/1 kV is suitable for
application in low voltage installations up to 0.6/1 kV, according to NEN 1010. It meets
the requirements according to fire classification Dca-s2,d2,a3 for usage in buildings
and civil engineering works with a medium fire hazard level (NEN 8012).
Thanks to its improved flexibility YMvK Dca-s2 FLEX 0.6/1 kV is easier to install then
the non-flexible version.YMvK Dca FLEX 0.6.1 kV is available from 35 mm2.
STANDARDS
YMvK Dca-s2 FLEX 0.6/1 kV Easy Strippablehas an improved design with an
easier to strip cable sheaths. With Easy Strippable you can remove the sheath in International HD 604.4D
a single smooth motion over a length of up to 100 cm.
National KEMA 42 C-1-4-D
Design
1. Conductor:
Conductors untill 10 mm2: Bare copper, solid, class 1
Conductors from 10 mm2: Bare copper, stranded, class 2
2. Insulation: XLPE
3. Inner covering: filling compound
4. Outer sheath: PVC
Colour: Grey
UV resistance: Yes

Lead free Rated Voltage Uo/U Mechanical Bending factor Minimum Operating temp. Max.conductor U.V resistance
Yes (Um) resistance to when laying installation -20 - 95 °C temp.in service EN 50289-4-17
0.6/1 kV impacts 10 (xD) temperature 90 °C method A, for
Good 0 °C 720h

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 1 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

CHARACTERISTICS
Construction characteristics
Conductor material Bare copper
Insulation XLPE (chemical)
Protection Filler
Outer sheath PVC
Sheath colour Grey
Lead free Yes
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Mechanical characteristics
Mechanical resistance to impacts Good
Usage characteristics
Field of application Standard
Bending factor when laying 10 (xD)
One single bending at each end minimum 8 (xD)
Minimum installation temperature 0 °C
Operating temperature, range -20 - 95 °C
Max. conductor temperature in service 90 °C
U.V resistance EN 50289-4-17 method A, for 720h

PRODUCT LIST
Nexans Country Name Number of Conductor cross- Nominal outer
Ref. Ref. cores section diameter
[mm²] [mm]
YMvK Dca-s2 0.6/1 kV Easy
10559894 - 2 1.5 10.4
Strippable 2x1.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559791 - 2 1.5 10.4
Strippable 2x1.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559792 - 2 1.5 10.4
Strippable 2x1.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559718 - 2 2.5 11.2
Strippable 2x2.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559716 - 2 2.5 11.2
Strippable 2x2.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559853 - 2 2.5 11.2
Strippable 2x2.5 MM2
10559866 - YMvK Dca-s2 0.6/1 kV 2x4 MM2 2 4 12.2
YMvK Dca-s2 0.6/1 kV 2x4 MM2
10559745 - 2 4 12.2
(R100)
YMvK Dca-s2 0.6/1 kV 2x4 MM2
10559744 - 2 4 12.2
(B500)
10559868 - YMvK Dca-s2 0.6/1 kV 2x6 MM2 2 6 13.5
= Make to order, = In stock,

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 2 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

Nexans Country Name Number of Conductor cross- Nominal outer


Ref. Ref. cores section diameter
[mm²] [mm]
YMvK Dca-s2 0.6/1 kV 2x6 MM2
10559752 - 2 6 13.5
(R100)
YMvK Dca-s2 0.6/1 kV 2x6 MM2
10559739 - 2 6 13.5
(B500)
YMvK Dca-s2 0.6/1 kV Easy
10559892 - 3 1.5 10.8
Strippable 3G1.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559809 - 3 1.5 10.8
Strippable 3G1.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559804 - 3 1.5 10.8
Strippable 3G1.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559857 - 3 2.5 11.7
Strippable 3G2.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559737 - 3 2.5 11.7
Strippable 3G2.5 MM2 (R50)
YMvK Dca-s2 0.6/1 kV Easy
10559730 - 3 2.5 11.7
Strippable 3G2.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559729 - 3 2.5 11.7
Strippable 3G2.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559734 - 3 2.5 11.7
Strippable 3G2.5 MM2 (B1000)
10559852 - YMvK Dca-s2 0.6/1 kV 3G4 MM2 3 4 12.8
YMvK Dca-s2 0.6/1 kV 3G4 MM2
10559728 - 3 4 12.8
(R100)
YMvK Dca-s2 0.6/1 kV 3G4 MM2
10559732 - 3 4 12.8
(B500)
10559871 - YMvK Dca-s2 0.6/1 kV 3G6 MM2 3 6 13.5
YMvK Dca-s2 0.6/1 kV 3G6 MM2
10559738 - 3 6 13.5
(R100)
YMvK Dca-s2 0.6/1 kV 3G6 MM2
10559742 - 3 6 13.5
(B500)
YMvK Dca-s2 0.6/1 kV Easy
10559869 - 4 1.5 11.5
Strippable 4G1.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559800 - 4 1.5 11.5
Strippable 4G1.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559801 - 4 1.5 11.5
Strippable 4G1.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559864 - 4 2.5 12.5
Strippable 4G2.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559805 - 4 2.5 12.5
Strippable 4G2.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559802 - 4 2.5 12.5
Strippable 4G2.5 MM2 (B500)
10559856 - YMvK Dca-s2 0.6/1 kV 4G4 MM2 4 4 13.5
YMvK Dca-s2 0.6/1 kV 4G4 MM2
10559733 - 4 4 13.5
(R100)
= Make to order, = In stock,

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 3 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

Nexans Country Name Number of Conductor cross- Nominal outer


Ref. Ref. cores section diameter
[mm²] [mm]
YMvK Dca-s2 0.6/1 kV 4G4 MM2
10559735 - 4 4 13.5
(B500)
10559895 - YMvK Dca-s2 0.6/1 kV 4G6 MM2 4 6 14.6
YMvK Dca-s2 0.6/1 kV 4G6 MM
10559795 - 4 6 14.6
(R100)
YMvK Dca-s2 0.6/1 kV 4G6 MM2
10559794 - 4 6 14.6
(B500)
YMvK Dca-s2 0.6/1 kV Easy
10559870 - 5 1.5 12.3
Strippable 5G1.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559799 - 5 1.5 12.3
Strippable 5G1.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559806 - 5 1.5 12.3
Strippable 5G1.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559893 - 5 2.5 13.3
Strippable 5G2.5 MM2
YMvK Dca-s2 0.6/1 kV Easy
10559808 - 5 2.5 13.3
Strippable 5G2.5 MM2 (R50)
YMvK Dca-s2 0.6/1 kV Easy
10559807 - 5 2.5 13.3
Strippable 5G2.5 MM2 (R100)
YMvK Dca-s2 0.6/1 kV Easy
10559803 - 5 2.5 13.3
Strippable 5G2.5 MM2 (B500)
YMvK Dca-s2 0.6/1 kV Easy
10559749 - 5 2.5 13.3
Strippable 5G2.5 MM2 (B1000)
10559858 - YMvK Dca-s2 0.6/1 kV 5G4 MM2 5 4 14.5
YMvK Dca-s2 0.6/1 kV 5G4 MM2
10559797 - 5 4 14.5
(R100)
YMvK Dca-s2 0.6/1 kV 5G4 MM2
10559796 - 5 4 14.5
(B500)
10559863 - YMvK Dca-s2 0.6/1 kV 5G6 MM2 5 6 15.8
YMvK Dca-s2 0.6/1 kV 5G6 MM2
10559775 - 5 6 15.8
(R100)
YMvK Dca-s2 0.6/1 kV 5G6 MM2
10559776 - 5 6 15.8
(B500)
10559941 - YMvK Dca-s2 0.6/1 kV 5G10 mm2 5 10 20.5
10559942 - YMvK Dca-s2 0.6/1 kV 5G16 mm2 5 16 23.0
10559993 - YMvK Dca-s2 0.6/1 kV 5G25 mm2 5 25 27.1
10559890 - YMvK Dca-s2 0.6/1 kV 6G1.5 MM2 6 1.5 13.6
YMvK Dca-s2 0.6/1 kV 6G1.5 MM2
10559746 - 6 1.5 13.6
(R100)
YMvK Dca-s2 0.6/1 kV 6G1.5 mm2
10559754 - 6 1.5 13.6
(B500)
10559889 - YMvK Dca-s2 0.6/1 kV 6G2.5 MM2 6 2.5 14.8
YMvK Dca-s2 0.6/1 kV 6G2.5 MM2
10559743 - 6 2.5 14.8
(R100)
10559896 - YMvK Dca-s2 0.6/1 kV 7G1.5 MM2 7 1.5 13.6
= Make to order, = In stock,

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 4 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

Nexans Country Name Number of Conductor cross- Nominal outer


Ref. Ref. cores section diameter
[mm²] [mm]
YMvK Dca-s2 0.6/1 kV 7G1.5 MM2
10559750 - 7 1.5 13.6
(R100)
YMvK Dca-s2 0.6/1 kV 7G1.5 MM2
10559768 - 7 1.5 13.6
(B500)
10559888 - YMvK Dca-s2 0.6/1 kV 7G2.5 MM2 7 2.5 14.8
YMvK Dca-s2 0.6/1 kV 7G2.5 MM2
10559740 - 7 2.5 14.8
(R100)
YMvK Dca-s2 0.6/1 kV 7G2.5 MM2
10559764 - 7 2.5 14.8
(B500)
10559865 - YMvK Dca-s2 0.6/1 kV 8G1.5 8 1.5 14.6
10559793 - YMvK Dca-s2 0.6/1 kV 8G1.5 (R100) 8 1.5 14.6
10559867 - YMvK Dca-s2 0.6/1 kV 8G2.5 MM2 8 2.5 15.8
10559986 - YMvK Dca-s2 0.6/1 kV 2x10 mm2 2 10 16.4
10559979 - YMvK Dca-s2 0.6/1 kV 2x16 mm2 2 16 18.3
10559969 - YMvK Dca-s2 0.6/1 kV 2x25 mm2 2 25 21.3
10559982 - YMvK Dca-s2 0.6/1 kV 3x10 mm2 3 10 17.3
10559983 - YMvK Dca-s2 0.6/1 kV 3x16 mm2 3 16 19.4
10559910 - YMvK Dca-s2 0.6/1 kV 3x25 mm2 3 25 23.0
10559981 - YMvK Dca-s2 0.6/1 kv 4G10 mm2 4 10 18.8
10559985 - YMvK Dca-s2 0.6/1 kV 4G16 mm2 4 16 21.1
10559952 - YMvK Dca-s2 0.6/1kV 4G25 mm2 4 25 25.3
YMvK Dca-s2 FLEX 0.6/1 kV 1x35
10559949 - 1 35 12.5
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 1x50
10559987 - 1 50 13.5
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 1x70
10559950 - 1 70 15.8
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 1x95
10559951 - 1 95 18.0
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 1x120
10559958 - 1 120 19.5
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 1x150
10559961 - 1 150 21.9
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 1x185
10559962 - 1 185 24.2
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 1x240
10559960 - 1 240 26.9
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 2x35
10560002 - 2 35 23.8
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 2x50
10559918 - 2 50 26.7
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 2x70
10559919 - 2 70 31.2
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 3x35
10559940 - 3 35 25.4
mm2
= Make to order, = In stock,

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 5 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

Nexans Country Name Number of Conductor cross- Nominal outer


Ref. Ref. cores section diameter
[mm²] [mm]
YMvK Dca-s2 FLEX 0.6/1 kV 3x50
10559914 - 3 50 29.1
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 3x70
10559899 - 3 70 34.0
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 3x95
10559916 - 3 95 37.2
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 3x120
10559930 - 3 120 40.7
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 3x150
10559921 - 3 150 45.8
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 3x185
10559908 - 3 185 51.1
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4x70
10559944 - 4 70 37.4
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4x95
10559959 - 4 95 41.3
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G35
10559974 - 4 35 27.8
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G50
10559972 - 4 50 31.8
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G70
10559955 - 4 70 37.4
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G95
10559945 - 4 95 41.3
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G120
10559931 - 4 120 45.5
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G150
10559924 - 4 150 50.8
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G185
10559935 - 4 185 57.0
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 4G240
10559938 - 4 240 63.6
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 5G35
10559984 - 5 35 30.6
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 5G50
10559925 - 5 50 34.8
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 5G70
10559954 - 5 70 41.2
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 5G95
10559967 - 5 95 46.0
mm2
YMvK Dca-s2 FLEX 0.6/1 kV 5G120
10559929 - 5 120 50.3
mm2
= Make to order, = In stock,

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 6 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

CURRENT CAPACITY TABLE PR SINGLE PHASE SINGLE CORE

Conductor cross-section
[mm²] Cu Cu Cu Cu
1.5 19 23 24 -
2.5 26 31 33 -
4 35 42 45 -
6 45 54 58 -
10 61 75 80 -
16 81 100 107 -
25 106 133 138 161
35 131 164 171 200
50 158 198 209 242
70 200 253 269 310
95 241 306 328 377
120 278 354 382 437
150 318 393 441 504
185 362 449 506 575
240 424 528 599 679
300 486 603 693 783
400 - - - 940
500 - - - 1083
630 - - - 1254
A1 Insulated conductors in conduit in B1 Insulated conductors in C Single-core or multi-core
a thermally insulated wall conduit on a wooden wall cable on a wooden wall

F Single-core flat cables, touching in


free air

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 7 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

CURRENT CAPACITY TABLE PR SINGLE PHASE MULTICORE

Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu
1.5 19 22 24 25 27 26
2.5 25 30 33 33 35 36
4 33 40 45 43 46 49
6 42 51 58 53 58 53
10 57 69 80 71 77 86
16 76 91 107 91 100 115
25 99 119 138 116 129 149
35 121 146 171 139 155 185
50 145 175 209 164 183 225
70 183 221 269 203 225 286
95 220 265 328 239 270 352
120 253 305 382 271 306 410
150 290 334 441 306 343 473
185 329 384 506 343 387 542
240 386 459 599 395 448 641
300 442 532 693 446 502 741
A2 Multi-core cable in conduit in a B2 Multi-core cable in conduit on a C Single-core or multi-core
thermally insulated wall wooden wall cable on a wooden wall

D1 Multi-core cable in ducts in the D2 Multi-core cables designed to be


E Multi-core cable in free air
ground buried directly in the ground

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 8 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

CURRENT CAPACITY TABLE PR THREE PHASE SINGLE CORE

Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu Cu
1.5 17 20 22 21 23 - -
2.5 23 28 30 28 30 - -
4 31 37 40 36 39 - -
6 40 48 52 44 49 - -
10 54 66 71 58 65 - -
16 73 88 96 75 84 - -
25 95 117 119 96 107 135 141
35 117 144 147 115 129 169 176
50 141 175 179 135 153 207 216
70 179 222 229 167 188 268 279
95 216 269 278 197 226 328 342
120 249 312 322 223 257 383 400
150 285 342 371 251 287 444 464
185 324 384 424 281 324 510 533
240 380 450 500 324 375 607 634
300 435 514 576 365 419 703 736
400 - - - - - 823 868
500 - - - - - 946 998
630 - - - - - 1088 1151
A1 Insulated conductors in conduit B1 Insulated conductors in conduit on a D1 Single or Multi-core cable
in a thermally insulated wall wooden wall in ducts in the ground
D2 Single or Multi-core cables
C Single-core or multi-core cable F Single-core trefoil cables,
designed to be buried directly in the
on a wooden wall touching in free air
ground
F Single-core flat cables, touching
in free air

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 9 / 10
YMvK Dca-s2 0.6/1 kV / YMvK Dca-s2 Contact
FLEX 0.6/1 kV Product Management
[email protected]

CURRENT CAPACITY TABLE PR THREE PHASE MULTICORE NL

Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu
1.5 17 20 21 22 23 23
2.5 22 26 28 30 30 32
4 30 35 36 40 39 42
6 38 44 44 52 49 54
10 51 60 58 71 65 75
16 68 80 75 96 84 100
25 89 105 96 119 107 127
35 109 128 115 147 129 158
50 130 154 135 179 153 192
70 164 194 167 229 188 246
95 197 233 197 278 226 298
120 227 268 223 322 257 346
150 259 300 251 371 287 399
185 295 340 281 424 324 456
240 346 398 324 500 375 538
300 396 455 365 576 419 621
A2 Multi-core cable in conduit in a B2 Multi-core cable in conduit on a D1 Multi-core cable in ducts in
thermally insulated wall wooden wall the ground

C Single-core or multi-core cable D2 Multi-core cables designed to be


E Multi-core cable in free air
on a wooden wall buried directly in the ground

SELLING AND DELIVERY INFORMATION


Marking
YMvK Dca (FLEX) n (x or G) s mm²
NEXANS BENELUX
KEMA KEUR
Meter Marking

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 1/14/22 www.nexans.nl Page 10 / 10