M7 Manual - Eng GE
M7 Manual - Eng GE
1. Introduction 7
2. M7 FRONT PANEL 8
2.1. M7 interface 9
2.1.a. M7 mode key selector 9
2.1.b. M7 command buttons 9
2.1.c. Interface buttons 9
2.2. Status led 10
2.2.a. Warning led 10
2.3. PASSWORDS 10
3. OPERATIONAL MODES 11
3 | Electronics M7
Index
7. MAINTENANCE 31
4 | Electronics M7
Index
12.1. M7 Controller 59
12.1.a. WIRING 60
12.1.b. ELECTRICAL RATINGS 63
12.1.c. DIMENSIONS 65
12.2. M7J Controller 66
12.2.a. WIRING 67
12.2.b. ELECTRICAL RATINGS 69
12.2.c. DIMENSIONS 71
12.3. Pump Irrigation Mode M7 Controller 72
12.3.a. ELECTRICAL RATINGS 76
12.3.b. DIMENSIONS 77
12.4. Pump Irrigation Mode M7J Controller 78
12.4.a. WIRING 79
12.4.b. ELECTRICAL RATINGS 82
5 | Electronics M7
6 | Electronics M7
Chapter 2
Introduction
M7 CONTROLLER
1. Introduction
•• Automatic external start; M7 device provides a digi-
tal input in order to start the generator set (only in AUTO
The M7 device is a monitoring and mode).
control electronic system for
electrical engine generator sets. •• Programmable inputs; M7 device provides up to 2 digi-
The M7 device is a compact module tal input that can be set up to carry up the following fea-
place in the front panel that tures:
develops the following features: -- 2 programmables warnings.
•• User’s interface. The M7 controller provides information -- Alternative configuration.
about the status of the generator set and, at the same time,
allows the user to interact with it; using M7 keyboard, user -- Manual override.
is able to configure the functions of the unit. M7 controller -- Aditional emergency stop.
allows to check the last 100 failures registered and a detai-
led information of the generator set of the last 10 failures. -- Generator set breaker confirmation.
•• Generator set control. M7 controller keep the generator
set in working order, including engine control and electrical
•• Generator set outputs; M7 device provides up to 5
signal monitoring the generator set, including engine and
outputs that carry up the following features:
electrical signal. Every signal, sensor and actuator is con-
nected to the rear part of the M device (see appendix III). -- Preheating or glow plug.
•• Electrical generator set signals. -- Engine control (fuel output or stop pulse).
M7 device provides the following electrical supply mea- -- Crank output.
surements:
-- PULL and HOLD injector outputs (case type YANMAR
-- Phase to neutral voltage. engines).
-- Phase to phase voltage. -- Battery charging alternator excitation.
-- Phase current. -- General warning output.
-- Frequency.
-- Real, apparent and reactive power. •• Configurable outputs; M7 device provides 2 configura-
ble outputs that can be set up to carry up the following
-- Power factor.
feature:
M7 controller provides the following engine signals:
-- Short circuit and overcurrent electronic protection.
•• Engine warning digital input:
-- Dummy load.
-- Fuel reserve.
-- Fuel pump transfer.
-- Oil pressure.
-- Engine running.
-- High coolant temperature.
-- Generator set breaker.
-- Coolant level.
-- Input detection
-- Emergency stop.
•• Counters:
•• Engine warning analog input:
-- Working time.
-- Fuel level.
-- Succeeded starts.
-- Pressure.
-- Failed starts.
-- Coolant temperature.
-- Total energy.
-- Battery charger alternator voltage.
-- Battery voltage.
7 | Electronics M7
Chapter 3
M7 front panel
2. M7 FRONT PANEL
M7 controller has a 128x64 pixel resolution backlight display and a warning LED to indicate the generator set state. Buttons
allow the user to command and program the generator set.
NOTE: The display enters in low consumption mode (off the backlighting) after 10 minutes without any detection on the
keyboard.
2. BUTTONS
A. Interface buttons.
B. Command buttons
3. STATUS LED
C. Warning led.
8 | Electronics M7
Chapter 3
M7 front panel
2.1. M7 interface
9 | Electronics M7
Chapter 3
M7 front panel
2.3. PASSWORDS
The M7 controller has 2 passwords levels of four digits
to avoid non authorised access. Those different access
levels are:
•• User level (default password:1111). The user level
allows access to M7 main menu.
•• Maintenance level (default password:1911). The
maintenance level allows to configure procedure.
10 | Electronics M7
Chapter 4
Operational modes
3. OPERATIONAL MODES
WITH cooling
WITHOUT cooling
11 | Electronics M7
Chapter 5
Working mode
4. WORKING MODE
12 | Electronics M7
Chapter 5
Working mode
also becomes active until any of the engine started con- •• Engine stop. After the cooling down of the engine,
ditions is detected for a maximum programmable length M7 controller stops the engine using the PC output ac-
(Times table parameter 403). If M7 does not detect cording to the programmed stop configuration (Confi-
any running engine condition for this length, M7 waits guration table parameter 106). As a condition of the
for a time (Times table parameter 401); afterwards and engine stop, can be selected:
automatically M7 controller will begin a new cranking at-
-- Generator voltage (Configuration table parame-
tempt again. The maximum number of cranking attempts
ter 102). The engine would be considered stopped
before M7 controller will trigger the START FAILURE
when no generator voltage is detected (Thresholds
alarm is 4 by default (Thresholds table parameter 301).
table parameter 314).
-- Battery charger alternator voltage: (Configura-
tion table parameter 103). The engine will be consi-
dered stopped when no battery charge alternator vol-
tage is detected (Thresholds table parameter 315).
ENGINE STARTED: Once the engine running condition -- Engine speed (tabla Configuración parámetro
is detected, M7 controller waits for a programmable 104). The engine would be considered stopped when
electrical stabilization time (Times table parameter no engine speed calculated by the magnetic pick-up
405) before the genset breaker activation. in the flywheel is detected. To activate the pick-up cal-
culation through the engine ring gear, the number of
teeth of the gear must be set up (Thresholds table
parameter 317); in case the programmed number
of teeth in the ring gear is “0”, the frequency of the
pick-up will be calculated through the generator fre-
ENGINE STABLE: After the stabilization time, M7 con- quency as per the equivalence-ratio 50Hz/1500 rpm,
troller ends the starting engine process. 50Hz/3000 rpm or 60Hz/1800 rpm.o 60Hz/1800rpm
To stop the starting cycle, just press the STOP button. (Configuration table parameter 108).
-- Low Oil Pressure (Configuration table parame-
ter 105). The Low Oil Pressure condition considers
NOTE: The starting process is the same either in manual the engine stopped when it detects that the sensor
(by pressing buttons) or auto (external start, scheduler or is closed. Exception for this “Engine Start Detec-
manual override…) mode. tion” option is SCANIA engines and also the sensors
which have self- electrical supply.
13 | Electronics M7
Chapter 5
Working mode
STOP OPERATING PROCESS. PRACTICAL EXAMPLE COOLING DOWN: Pressing the STOP button once, the
stop cycle will start with the engine cooling process after
deactivating the genset breaker.
NOTE: Before initiating the stop cycle, it is advisable
that the main genset circuit breaker be switched OFF
STOP: Once the cooling time is over (Times table para-
meter 407), PC output is activated or deactivated, accor-
The genset can be stopped in several ways:
ding the type of engine (Configuration table parame-
1. Manual: Press STOP button once. The genset stops ter 106), to carry on with the stopping cycle.
with cooling down.
2. Manual: Press STOP button tow times. The genset
STOPPED: M7 controller will finish the engine stopping
stops without cooling down.
process when ALL stopped engine conditions has been
3. Place the activation key in “O” position. The genset stops validate for a programmable length (Alarms table para-
without cooling down. meter 1071). If after a period of 90” any stopped engine
condition has not been validated yet, Stop Failure alarm
4. Automatic: The genset stops with cooling down cycle
will be activated.
after the deactivation of the command which automati-
cally started the genset.
Crank
ARR Time 403
Preheating
PR Time 402
Crank
ARR Time 403
Preheating
PR Time 402
Stop
PC Engine running Time 408
Configuration 106: value 1 (PE/PR)
Crank
ARR Time 403
Stop
PR Time 408
PC Engine running
Configuration 106: value 2 (PD/PE)
Crank
ARR Time 403
Preheating
PR Time 402
PULL
PC 1”
HOLD
PD Engine running Stop
Configuration 106: value 3 (PR/PULL+HOLD)
14 | Electronics M7
Chapter 5
Working mode
4.1.c. Battery charger alternator teristics of the electronic protection feature (Thresholds
table parameter 307 and 308) and (table Alarms para-
M7 energizes the battery charger alternator, by means meters 1028, 1029 and 1030 –overload- and parame-
of a triggering pulse of configurable duration (Times ta- ters 1058 and 1060 –short circuit-). When any of the
ble parameter 406) during the strarting engine process overload or short-circuit alarms is activated, the output
through the D+ pin. When this pulse ends, M7 begins assigned to this function remains active.
testing the voltage made by the battery charge alterna-
tor.
The voltage produced by the battery charge alternator 4.2.b. Transfer fuel pump
can be used as starting engine condition (Configuration Any of 3 free programmable outputs can be set up as
table parameter 103). For that purpose, M7 expects to Transfer fuel pump feature (Out1, Out 2 or Out 3) by M7
measure through D+ pin, voltage values exceeding the configuration (Configuration table parameters 122 a
alternator voltage detection threshold (Thresholds table 124 value 3). Once the transfer pump option is activa-
parameter 315). ted, pump output will be automatically active according
M7 can be configured to raise an Alternator Voltage to the minimum activation level (Thresholds table pa-
alarm (Alarms table parameter 1010 a 1012) if it is de- rameter 326) and will be automatically deactivate accor-
tected a low voltage level provided by the battery charge ding to the maximum activation level (Thresholds table
alternator through D+. parameter 327).
Gauging system for the fuel tank: For an accurate
fuel level measurement (needed for the fuel pump and
4.2. Generator features fuel level alarm functions) a calibration of the tank level
sender must be done, by having access to both the mi-
Additional genset control features using 3 free program-
nimum and maximum parameters of the level sender
mable outputs of M7:
(Measures table parameters 202 and 203). To adjust
the minimum fuel level of the tank it must be set up the
parameter 202 of Measures table with the fuel gauge
•• Out1: 2A output PD (Configuration table parameter in the lowest tank position. To adjust the maximum fuel
122). PD configuration is only available if engine configu- level of the tank, it must be set up the parameter 203 of
ration is different of PULL/HOLD mode (Configuration the Meassures table with the fuel gauge in the upper-
table parameters 106, value 3); PD output is used only most tank position.
as HOLD output in the control process of the engine if
the engine configuration is: PULL/HOLD.
•• Out2: relay output MN (Configuration table parame- 4.2.c. Dummy load
ter 123). MN default manufactured setting is: short cir- Any of 3 free programmable outputs can be set up as
cuit and overload electronic protection (value 1). Dummy Load feature (Out1, Out 2 or Out 3) by M7 con-
•• Out3: 2A output CON (Configuration table parame- figuration (Configuration table parameters 122 a 124
ter 124). CON default manufactured setting is: genset value 2).
breaker (value 5). This option makes it possible to activate a charging rack
separate from the installation´s load, in order to prevent
the generating set from operating without a load or with
4.2.a. Electronic protection (over- low-load thresholds, so as to avoid excessive oil con-
load and short-circuit) sumption in the engine and keep the engine functioning
•• Any of 3 free programmable outputs can be set up with an optimum load.
to develop electronic protection feature (Out1, Out2 or The programmable output configured as dummy load
Out3) by M7 configuration (Configuration table para- feature is activated when the genset power consump-
meter 122 a 124 value 1). By default, relay Out2 (MN) is tion is lower than the programmed threshold (Thres-
programmed as electronic protection feature (Configu- holds table parameter 328). The dummy load output is
ration table parameter 123). deactivated when the power consumption of the genset
•• Electronic protection is a characteristic that allows the is greater than the programmed threshold (Thresholds
activation of an output on the controller when the over- table parameter 329).
load and short-circuit alarm is activated. Threshold and Condition for enabling the dummy load output is that the
conditions of these alarms must be set to fit the charac- engine must be running and stable.
15 | Electronics M7
Chapter 5
Working mode
16 | Electronics M7
Chapter 6 M7 inputs and outputs
Programmable output 3
Programmable output 1
Programmable output 2
Inputs
Pressing UP/DOWN buttons, the user gain access to the
The following pictures identify active inputs: analog inputs readings.
Oil pressure
Fuel reserve
High temperature
Coolant level
Oil pressure
Engine temperature
17 | Electronics M7
Chapter 6 M7 inputs and outputs
5.1.a. Presets inputs NOTE: Emergency stop input power off the PC and S1/
PD outputs in order to assure the stop of the engine. In
M7 controller has 5 digital inptus, whose working pro- engine models that need an excitation pulse to stop the
cess is already preset. engine (table Configuration parameter 106 value 2),
Emergency stop input MUST be wired to -BAT in order to
never disable power of engine control outputs. Likewise,
a programmable input (table Configuration parameter
120 or 121), should be set up to provide the emergency
External start signal. stop function without engine control powering off option.
Digital signal reporting to the controller that the engine This function only works when the M7 controller is in
pressure switch has detected a failure and sets on an automatic mode.
alarm due to the low oil pressure (Alarms table para- The input configured as manual override meets the fire
meters 1004 to 1006). safety regulations and accordingly the working genset
cannot be interrupted under any condition except overs-
peed and emergency stop, including alarms or schedule
disabling mode (only M7C option).Three different manual
override working modes can be configured (Configura-
Coolant level. tion table parameter 110):
Digital signal reporting to the controller that an alarm tri- -- 0: Manual override disabling. The manual override
ggered due to low coolant level (Alarms table parame- process is not managed, despite of having an asso-
ters 1016 to 1018). ciated programmable input.
-- 1: External start (AE). When the manual override
input is activated, M7 controller waits for an External
start condition in order to start the genset in override
mode. M7 stops the genset when both external start
Emergency stop. and manual override inputs are inactive.
Digital signal reporting to the controller that an immedia- -- 2: Manual override starting. M7 starts the genset
te stop without cooling must be done. Emergency stop immediately when manual override input is active,
input disables by powering hardware the engine control without awaiting any other starting condition. To stop
in order to force the engine stop process. the device, it is necessary to change to manual mode
and stop the controller with the pushing buttons.
18 | Electronics M7
Chapter 6 M7 inputs and outputs
19 | Electronics M7
Chapter 6 M7 inputs and outputs
Battery charger alternator voltage (D+). Engine cranking output.. (ARR). Power Output.
The analog voltage input allows supervising the value of The engine cranking output (ARR) of the M7 controller
the voltage generated by the genset. Such an input is is an output connected to a high voltage short-circuitable
used to diagnose the possible abnormal working of the driver (40 A) which activates the cranking in the engine
alternator when a low voltage level while the engine is starting process. The activation of the engine starting re-
on work is detected. Under such condition an alarm sig- mains until any programmed starting condition is detec-
nal of the battery alternator will be triggered. (Alarms ted (Configuration table parameter from 102 to 105)
table parameter from 1010 to 1012). during a maximum programmable length (Times table
parameter 403).
In that way, the voltage can be programmed to detect a
starting condition (Configuration table parameter 103)
by means of setting an alternator voltage threshold for
started engine (Thresholds table parameter 315).
Engine control (PC): Fuel output/Engine stop output/
Enable engine/PULL. Power Output.
Engine control output (PC) of M7 controller is connec-
5.3. Magnetic pickup (PKC1, PKC2) ted to a high voltage short-circuitable driver (40 A) that
The pick-up input from the flywheel controls the rotation controls the state of the engine depending of 4 different
speed of the engine in revolutions per minute (rpm). To configurations (Configuration table parameter 106):
activate the pick-up calculation through the engine ring •• Fuel output. Engine control output configured as fuel
gear, the number of teeth of the gear must be introduced enable output (Configuration table parameter 106 va-
(Thresholds table parameter 317). In case of the pro- lue) is activated 500ms after the pre-heating output is
grammed number of teeth is “0” the controller is confi- disabled and it is deactivated when M7 controller stops
gured to have not available the pick-up and the rotation the engine.
speed will be calculated through the genset frequency
using the speed equivalence-ratio 50Hz/1500 rpm or •• Engine stop output. Engine control output configured
50Hz/3000 rpm and 60Hz/1800rmp or 60Hz/3600rpm as engine stop output (Configuration table parameter
(Configuration table parameter 108). 106 value 1) is activated during a programmable time
(Times table parameter 408) when M7 controller stops
M7 controller can be configured to trigger an overspeed the engine. In this mode, Emergency stop input of M7
alarm (Alarms table parameters from 1022 to 1024) as controller MUST be connected to –BAT to be disable the
well as an underspeed alarm (Alarms table parameters unpowering engine control mode; set up the program-
from 1025 to 1027) taking into account the mechanical mable input wired to emergency stop button in order to
speed given by the pick-up. develop this feature (Configuration table parameter
120 o 121 value 5).
20 | Electronics M7
Chapter 6 M7 inputs and outputs
Electronic protection
(see section 4.2.1)
Battery charge alternator excitation output (D+). Di-
gital output.
Fuel transfer pump
D+ output of M7 controller is in charge of exciting the (see section 4.2.2)
battery charge alternator during the starting process for a
programmable length (Times table parameter 406).
Dummy load
(see section 4.2.4)
21 | Electronics M7
Chapter 7 M7 Controller alarms
6. M7 controller alarms
22 | Electronics M7
Chapter 7 M7 Controller alarms
ALARM LIST
The alarm and the active warning list can be grouped in the following way (according the MANUFACTURER DEFAULT
SETTINGS):
E01 High coolant temperature Alarm Immediate engine stop with no cooling
E02 Low oil pressure Alarm Immediate engine stop with no cooling
E06 Low coolant level Alarm Immediate engine stop with no cooling
E19 Low fuel level by sensor Warning Engine does not stop
23 | Electronics M7
Chapter 7 M7 Controller alarms
E12 Maximum genset voltage Alarm Immediate engine stop with no cooling
E13 Maximum genset frequency Alarm Immediate engine stop with no cooling
E25 Electrical Genset signal drop Alarm Engine stop with cooling
24 | Electronics M7
Chapter 7 M7 Controller alarms
The high coolant temperature alarm of the M7 controller PEM input can be configured as normally open or nor-
is associated to the specific high coolant temperature di- mally closed (Configuration table parameter 115).
gital input (ATA). The status of such input must be valida-
ted for a stabilization time (Times table parameter 413) NOTE: PEM input activation powers off the engine
before the high coolant temperature alarms triggers. control outputs (PC and S1/PD) in order to assure the
ATA input can be configured as normally open or norma- stop of some model of engines (table Configuration
lly closed (Configuration table parameter 113). parameter 106 value 0 and 3.) PEM input MUST be
plugged to –BAT for engine models that need a pulse to
The high coolant temperature alarm is configured be stopped (Configuration table parameter 106 value
(Alarms table parameter 1001) to be checked: Always. 1). So, for this pulse stop engine models, Emergency stop
A delay can be set up to wait for checking stable condi- feature has to be done by an alternative programmable
tions (Alarms table parameter 1002). input (Configuration table parameter 120 or 121 value
5).
This alarm is configured (Alarms table parameter 1003)
to carry out by default: the immediate engine stop.
The emergency stop alarm always stops the engine wi-
thout cooling. No delay can be associated to that action,
as it is immediately executed after the emergency stop
Low oil pressure. input is detected (PEM).
The low oil pressure alarm of the M7 is associated to the
specific low oil pressure digital input (BPA). The status of
such input must be validated for a stabilization time (Ti-
mes table parameter 412) before the low oil pressure
Battery charge alternator failure.
alarm triggers.
The battery charge alternator failure alarm of the M7
BPA input can be configured as normally open or norma-
controller is associated to the battery charge alternator
lly closed (Configuration table parameter 112).
voltage analog input (D+). The voltage value of such input
The low oil pressure alarm is configured (Alarms table must be over the voltage threshold of the started engine
parameter 1004) to be detected: From the started en- detection (Thresholds table parameter 315); if not, the
gine condition. battery charge alternator failure alarm is triggered.
A delay can be set up to wait for checking stable condi- The battery charge alternator alarm is configured (Alarms
tions (Alarms table parameter 1005). table parameter 1010) to be checked from the started
engine condition.
This alarm is configured (Alarms table parameter 1006)
to carry out the following action: Immediate engine stop. A stabilization time can be associated to the battery char-
ge alternator alarm (Alarms table 1011) During this time
the obtained voltage values must be kept under the star-
ted engine detection threshold (through the D+ input) as
a condition for the battery charge alternator failure alarm
to be triggered.
This alarm is configured by default (Alarms table para-
meter 1012) to be only a warning (do not stop the engi-
ne).
25 | Electronics M7
Chapter 7 M7 Controller alarms
26 | Electronics M7
Chapter 7 M7 Controller alarms
27 | Electronics M7
Chapter 7 M7 Controller alarms
Short circuit.
The short circuit alarm of the M7 controller is associated
Low oil pressure by sensor. to real amperage value when any of the phases are over
the maximum short circuit programmed limits (Thres-
The low oil pressure by sensor alarm of the M7 controller
holds table parameter 308).
is associated to the oil pressure analog input (T). The low
oil pressure by sensor alarm triggers when the pressure The phases that are checked to detect short circuit alarm
readings are under the programmed limits (Thresholds are selected depending on the genset configuration
table parameter 319). (Configuration table parameter 101):
The low oil pressure by sensor alarm is configured •• Single-phase configuration, phase 1 is tested.
(Alarms table parameter 1052) to be checked always.
•• Two-phase configuration, phase 1 and 2 are tested.
A stabilization time can be associated to the low oil pres-
sure by sensor alarm (Alarms table parameter 1053). •• Three-phase configuration with neutral or three-phase
During this time the pressure values must be detected without neutral, phase 1, 2 and 3 are tested.
under the programmed limits. (Thresholds table para- The short circuit alarm is configured (Alarms table pa-
meter 319). rameter 1058) to be checked form engine nominal con-
This alarm is initially configured (Alarms table parame- dition.
ter 1054) to be only a warning (do not stop the engine).
28 | Electronics M7
Chapter 7 M7 Controller alarms
29 | Electronics M7
Chapter 7 M7 Controller alarms
Programmable alarm 1.
Genset breaker.
The programmable alarm 1 of the M7 controller is acti-
vated by programming one of the general digital inputs The M7 controller verifies the activation of genset
(ENT1 or ENT2) as programmable alarm 1 mode (Con- breaker using any of the programmable inputs (ENT1 o
figuration table parameters 120 y 121). The status of ENT2, table Configuration parameter 120 y 121). The
such input must be validated during a stabilization time status of such input must be validated during a stabili-
(Times table parameter 417, 418) before triggering the zation time before triggering the genset breaker alarm
programmable alarm 1. (Times table parameter 417, 418).
The programmable alarm 1 is configured by default The genset breaker alarm is configured by default
(Alarms table parameter 1079) to not be checked. (Alarms table parameter 1091) to not be checked.
A delay time (Alarms table parameter 1080) can be as- A delay time can be programmed in order to assure
sociated to the programmable alarm 1 in order to restrain enough time between genset breaker activation and the
the moment in which the alarm conditions are checked. feedback (Alarms table parameter 1092).
This alarm is initially configured (Alarms table parame- This alarm is initially configured (Alarms table parame-
ter 1081) to be only a warning (do not stop the engine). ter 1093) to be only a warning (do not stop the engine).
The programmable alarm 2 of the M7 controller activated Engine communication error is only available in M7J con-
by associating one of the general digital inputs (ENT1 or troller with J1939 option. M7J verifies the communica-
ENT2) as programmable alarm 1 mode (Configuration tion with the engine control unit through the J1939 bus
table parameters 120 y 121). The status of such input (J1939 table parameter 1).
must be validated during a stabilization time (Times ta- Engine communication error is configured by default
ble parameter 417, 418) before triggering the program- (Alarms table parameter 1094) to be checked from
mable alarm 2. starting process.
The programmable alarm 2 alarm is configured by default A stabilization time can be associated to the engine com-
(Alarms table parameter 1082) to not be checked. munication error (Alarms table parameter 1094).
A delay time (Alarms table parameter 1083) can be as- This alarm is initially configured (Alarms table parame-
sociated to the programmable alarm 2 in order to restrain ter 1096) to be only a warning (do not stop the engine).
the moment in which the alarm conditions are checked.
This alarm is initially configured (Alarms table parame-
ter 1084) to be only a warning (do not stop the engine).
Maintenance.
M7 controller triggers the Maintenance alarm when the
engine hours counter is over a programmable mainte-
nance time. This alarm only is a warning and it cannot
stop the engine. In order to erase this alarm from the list,
the user must set a new maintenance time (see section
7.2.1).
30 | Electronics M7
Chapter 8 Maintenance
7. MAINTENANCE
31 | Electronics M7
Chapter 8 Maintenance
Serve notice. In order to erase the maintenance war- curve. When the fuel level is being programmed, the va-
ning from the alarm list, user must reload the maintenan- lue in Ω is the present measure of the gauge.
ce meter pressing the key and programming a new
3. The temperature values of the points for the sensor cur-
maintenance value.
ve should be entered in centigrade. Positive and negative
Cancellation. PT cancel the current maintenance meter, temperature values are allowed in the points program-
it must be reload with a 0 value; any maintenance war- ming of the sensor curve.
ning will be also erased.
4. The pressure values of the points for the sensor curve
Remaining time should be entered in kilopascals. Only positive pressure
(fixed mode display) values are allowed in the programming of points of the
sensor curve.
5. The fuel sensor curve is applied to the % of fuel tank.
1 : 2 4
6. The pressure curve is applied to the oil pressure sensor.
▲
◄ ▼
Resistance (downward)
32 | Electronics M7
Chapter 8 Maintenance
TEMPERATURE PRESSURE
Dot VDO 323-803-001-008 VDO 360-081-030-009
Resistance Temperature Resistance Pressure
Ω ºC Ω kPa
1 1716 -40 184 1000
2 9134 -30 170 900
3 6764 -25 163 850
4 5067 -20 156 800
5 3834 -15 140 700
6 2930 -10 124 600
7 2249 -5 107 500
8 1743 0 90 400
9 1364 5 71 300
10 1075 10 52 200
11 850 15 42 150
12 677 20 31 100
13 543 25 21 50
14 439 30 10 0
15 357 35 - -
16 291 40 - -
17 240 45 - -
18 197 50 - -
19 161 55 - -
20 134 60 - -
21 114 65 - -
22 97 70 - -
23 82 75 - -
24 70 80 - -
25 60 85 - -
26 51 90 - -
27 44 95 - -
28 38 100 - -
29 33 105 - -
30 29 110 - -
31 26 115 - -
32 22 120 - -
33 | Electronics M7
Chapter 9 Options
8. OPTIONs
Start
Engine Active Failure Erased of CIU
ENGINE Stop DROOP
measurements1 alarms record failure record Mode
(J1939)
General − 012 − − − − −
SCANIA 012 012 012 012 012 12 2
VOLVO
012 012 012 012 012 12 2
EMS1
VOLVO
012 012 012 012 012 12 2
EMS2
VOLVO
012 012 012 012 012 − −
EDC4
IVECO NEF − 012 − − − 12 −
IVECO
− 012 012 − − 12 −
CURSOR
JOHN
− 012 012 012 012 − −
DEERE
YANMAR − 012 012 012 012 − −
MTU 012 012 012 − − − −
0
: Mode 0 (J1939 table parameter 604)
1
: Mode 1 (J1939 table parameter 604)
2
: Mode 2 (J1939 table parameter 604)
34 | Electronics M7
Chapter 9 Options
•• Inlet temperature.
•• Torque.
8.3. Heater
M7T controller regulates the internal temperature in or-
8.1.b. J1939 engine control der to assure that the M7T controller temperature never
M7J controller allows 3 different modes of engine con- is under 0ºC using an internal sensor and a heater. The
trol by J1939 (J1939 table parameter 604): present internal temperature is displayed in menu.
•• Mode 0: M7J displays engine measures, alarms and
fault log management.
•• Mode 1: M7J displays engine measures, alarms and
fault log management and speed regulation.
•• Mode 2: M7J displays engine measures, alarms and
fault log management, speed regulation and replace-
ment of CiU (only VOLVO and SCANIA engines).
35 | Electronics M7
Chapter 10 (Annex I) Parameters
CONFIGURATION
Index Psw Description Value
0- Three-phase
without neutral
1- Three-phase
Three-phase, bi-phase, single-phase, or three-phase 2- Bi-phase
101 2 1
without neutral, delta or delta without neutral 3- Single-phase
4- Delta
5- Delta without neutral
6- Bi-phase selector
102 2 Phase voltage as start condition 3 0-Off
0-Not checked
103 2 Alternator voltage as starting condition 3 1-Started engine condition
2- Stopped engine
104 2 PICK-UP input as starting condition 3 condition
3- Started and stopped
105 2 LOP input as starting condition 2 engine condition
0-PD/PR
1-PE/PR
106 2 Engine control 0
2-PD/PE
3-PR/PULL/HOLD
0-Not installed
107 2 Voltage transformer 0
1-Transformer rate 400/600
0-50Hz/1500rpm
Rotation speed of the engine ring gear
108 2 0 60Hz/1800rpm
related with genset voltage frequency
1-50Hz/3000rpm
Silent mode 0-Enable buzzer
109 2 0
M7 buzzer disabled mode 1-Disable buzzer
0-Not allowed
1- Starting due to External
110 3 Manual override mode 0
start input or scheduler
1- Starting due to manual override.
111 2 RC input configuration 1
36 | Electronics M7
Chapter 10 (Annex I) Parameters
CONFIGURATION
Index Psw Description Value
MEASSURES
Index Psw Description Value
Conversion factor of the amperage transformers
201 2 100
Common factor to the real amperage values IR,IS,IT
202 2 Fuel level regulation EMPTY
37 | Electronics M7
Chapter 10 (Annex I) Parameters
THRESHOLDS TABLE
Index Psw Description Value Range
318 2 Tank level for low fuel alarm condition 10% 0..30
0.5-3 bar
319 2 Pressure level for oil low pressure alarma 1.2 bar
7-43 psi
80-105ºC
320 2 Temperature level for high coolant temperature alarm 98ºC
175-220ºF
326 2 Fuel pump activation Minimum tank level 30% 15%-40%
TIMES TABLE
Index Psw Description Value Range
Time between cranking
401 2 Time between one cranking attempt and another. 5’’ 3’’..15’’
All the engine control outputs are deactivated
402 2 Glow plug pre-heating time 0’’ 0’’..180’’
Cranking time
403 2 Maximum waiting time before detecting the started engine 5’’ 1’’..30’’
condition. During this time the cranking output (ARR) is active.
Load activation delay
404 2 Time from the detection of the engine started 3’’ 1’’..600’’
condition to the genset breaker activation.
38 | Electronics M7
Chapter 10 (Annex I) Parameters
TIMES TABLE
Index Psw Description Value Range
Nominal condition time
405 2 Time from the detection of the engine starting condition to 2” 2”..15”
the quality validation of the electrical generated signal.
Time of excitation of battery charger alternator time
406 2 Being this time, the voltage generates by battery charger 3’’ 1’’..10’’
alternator is checked.
Cooling time
407 2 Length of the stopping phase where the engine is running 120’’ 0’’..1800’’
without load.
Length of pulse stop activation
408 2 10’’ 1’’..30’’
Length of the activation of stop engine output.
0’’..1800’’
(if 0, alarm output
Delay of start by external order
activation will
409 2 Time between the detection of external start and start of 0’’
be active during
the engine; during this time, alarm output (AL) is active.
the start process
for 5 seconds)
Maximum time for alarm activation
The alarm output will be activated (together with the flashing of
0-Unlimited
410 2 the reset button and the buzzer on the display) when corresponds 15”
1”..1800”
within this limited time. Value 0, alarm output is active until user
press button.
411 2 RC input filter 1.0’’ 0.0’’..5.0’’
39 | Electronics M7
Chapter 10 (Annex I) Parameters
ALTERNATIVE CONFIGURATION
Parameter Psw Description Value
0- Three-phase without neutral
1-Three-phase
Three-phase, bi-phase or single- 2- Bi-phase
501 2 phase without neutral, delta 1 3- single-phase
or delta without neutral. 4- Delta
5- Delta without neutral
6- Bi-phase selector
509 2 Fine adjust speed (only M7J option) 125 0-250: Speed adjust (±75 rpm).
1
Configuration table parameter 119.
603 2 Fine adjust speed (only M7J option) 125 0-250: Speed adjust (±75 rpm).
0: Meassures mode
1: Speed control
604 3 Control mode 0
2: CIU mode (only VOLVO
and SCANIA engines)
0 - Droop Disable
605 3 Droop 0
1..250- Droop value x0,1%
0-Disable
606 2 Limiter of sudden change in speed 0
1-1000 limiter value (rpm/seg)
40 | Electronics M7
Chapter 10 (Annex I) Parameters
ALARMS
Parameter Psw Description Value
0-Disable
1-Always enabled
2- Checking from starting
3-Checking from
1001 3 Check management 1
started (Running)
E01: High coolant temperature
4- Checking from nominal
condition (electrical signal stable
and genset breaker active)
1002 3 Delay 0’’ 0”…5”
0-Only warning (do
not stop engine)
1003 3 Action 1
1-Stop engine inmediatly
2-Stop engine after cooling down
41 | Electronics M7
Chapter 10 (Annex I) Parameters
ALARMS
Parameter Psw Description Value
2 Action 0 0..2
1051
2 Action 0 0..2
1054
42 | Electronics M7
Chapter 10 (Annex I) Parameters
ALARMS
Parameter Psw Description Value
1060 2 Action 2 0..2
1072 - Action 1
Alarm management
1094 2 1 0..4
E32: Engine communication error
(only option M7J)
1095 2 Delay 1’ 0”…30”
43 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
5 0 . 3 H z
V 1 N 2 3 0 V I 1 0 A
V 2 N 2 3 0 V I 2 0 A
V 3 N 2 3 0 V I 3 0 A
Voltage Currents
phase-neutral
5 0 . 3 H z
V 1 2 4 0 2 V I 1 9 7 A
V 2 3 4 0 0 V I 2 1 0 3 A
V 3 1 4 0 1 V I 3 5 8 A
Voltage between
phases
Fuel level
Voltage & (only if fuel
Frequency current gauge installed)
5 0 . 0 H z 7 5 %
V 1 N 2 3 0 V I 1 3 4 5 A
7 0 º C 6 . 7 B A R
1 0 0 H
Working hours
Engine coolant temperature Oil pressure
(Measures table parámeter 205: (Measures table parameter
Celsius or Farenheit) 204: bars o Psi)
44 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
1 5 0 0 r p m 1 0 0 H
7 5 %
External start states: USB connection
2 6 V 7 0 º C List of genset breaker
states:
2 4 V 6 . 7 B A R
open
45 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
1 k V A R φ 3 0 . 9 9 L
◄ ▼
46 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
Maintenance:
• digital inputs
• digital outputs
0 0 0 0 • analog inputs
• J1939 variables (only M7J option)
Parameters
(only maintenance or upper pas-
sword level)
From the status screen: enter in password
validation screen Counters
Form the password validation screen: validate
value.
Fault log
Cancel password.
Passwords
▲
◄▼
47 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
10.8. Maintenance
Preheating
2 4 0 Ω
Engine control (fuel/stop/pull)
2 3 3 Ω 5 4 Ω
Alarm ◄ ▲ 2 9 º C
Output S3
Measure (Ω) of fuel gauge input.
Battery charge alternator
Measure (Ω) oil pressure input.
Output S1
Measure (Ω) coolant temperature.
Output S2
Internal temperature (M7T option).
◄ ▼
Fuel reserve
Coolant level
External start
Emergency stop
Input 1
Input 2
48 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
Battery voltage
49 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
50 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
1 0 : 0 0 1 1 : 3 0 1 2 / 1 8
▲ --- 0 0 : 0 0 0 0 : 0 0
1 2 . 3 3 2
◄▼ --- 0 0 : 0 0 0 0 : 0 0
▲ 1 3 . 4 1 8
Seasonal event
◄ ▼ 1 4 . 7 5 0
3 3 2 . 1 8 1 2 / 1 8
▲
▲ →
→ 1111 :: 00 00 :: 55 55 1 1 : 0 8 : 4 1
◄▼
◄ ▼ 22 77 // 00 66 // 11 22 ▲ 4 1 8
Date (dd/mm/yy) ◄ ▼ 1 5
Flash code
51 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
1 2 / 1 8
1 2 . 3 3 2
100 200 300 400
▲ 1 3 . 4 1 8
▲
◄ ▼ 1 4 . 7 5 0 ◄ ▼ 500 1000
Value
Password levels:
User
Maintenance
Administrator P 1 0 1 . . . . . . . . . 4
▲ P 1 0 2 . . . . . . . . . 5
◄▼ P 1 0 3 . . . . . . . . . 0
1 1 1 1 Parameter index
0 0 0 0 Parameter tables:
Measurements parameters
Thresholds parameters
Times parameters
Alarms
Alternative configuration
Curve of sensors
52 | Electronics M7
Chapter 11 (Annex II) M7 controller interface
◄▼
P . 1 Ω 7 4 0 TM 3 0
P . 2 Ω 3 2 2 TM 5 0
◄▼P . 3 Ω 1 5 5 TM 7 0
53 | Electronics M7
Chapter 12 (Annex III) M7 configuration application
11.2. INTRODUCTION
The M7 configuration application features are
•• Set up M7 parameters
•• Erase of fault log.
•• Configuration files management (saved/load configura- M7 controller model only use USB port in order to com-
tion) municate with M7 configuration application. If the USB
is not listed in the Port Select field, reboot the system.
M7x compatible models are:
If the problem persists, check driver availability (see USB
•• M7 drivers installation section).
•• M7x Password fields:
•• M7J
•• M7xJ
54 | Electronics M7
Chapter 12 (Annex III) M7 configuration application
11.3.b. Password
11.4. MAIN SCREEN
Once validated into the system the main screen is dis-
played.
User must validate a 4 characters password and press
validate button. Depending of the password level:
•• M7 controller checks a correct password; if the pas-
sword has maintenance level or upper, the M7 configu-
ration application will be launched.
•• M7 controller checks a wrong password; the M7 con-
figuration application will be closed.
It is divided in 3 parts:
55 | Electronics M7
Chapter 12 (Annex III) M7 configuration application
Meassures Alarms
Sensors Configuration
11.4.b. SENSORS TABLE
Alternative
Time
configuration
56 | Electronics M7
Chapter 12 (Annex III) M7 configuration application
11.4.c. Toolbar
11.5. M7 controller driver
First time PC detects the M7 controller, it will try to ins-
tall it automatically.
57 | Electronics M7
Chapter 12 (Annex III) M7 configuration application
58 | Electronics M7
Chapter 13
(Annex IV) Technical data
12.1. M7 Controller
59 | Electronics M7
Chapter 13
(Annex IV) Technical data
12.1.a. WIRING
60 | Electronics M7
Chapter 13
(Annex IV) Technical data
61 | Electronics M7
Chapter 13
(Annex IV) Technical data
62 | Electronics M7
Chapter 13
(Annex IV) Technical data
63 | Electronics M7
Chapter 13
(Annex IV) Technical data
64 | Electronics M7
Chapter 13
(Annex IV) Technical data
12.1.c. DIMENSIONS
65 | Electronics M7
Chapter 13
(Annex IV) Technical data
66 | Electronics M7
Chapter 13
(Annex IV) Technical data
12.2.a. WIRING
67 | Electronics M7
Chapter 13
(Annex IV) Technical data
68 | Electronics M7
Chapter 13
(Annex IV) Technical data
69 | Electronics M7
Chapter 13
(Annex IV) Technical data
70 | Electronics M7
Chapter 13
(Annex IV) Technical data
12.2.c. DIMENSIONS
71 | Electronics M7
Chapter 13
(Annex IV) Technical data
72 | Electronics M7
Chapter 13
(Annex IV) Technical data
73 | Electronics M7
Chapter 13
(Annex IV) Technical data
74 | Electronics M7
Chapter 13
(Annex IV) Technical data
75 | Electronics M7
Chapter 13
(Annex IV) Technical data
76 | Electronics M7
Chapter 13
(Annex IV) Technical data
12.3.b. DIMENSIONS
77 | Electronics M7
Chapter 13
(Annex IV) Technical data
78 | Electronics M7
Chapter 13
(Annex IV) Technical data
12.4.a. WIRING
79 | Electronics M7
Chapter 13
(Annex IV) Technical data
80 | Electronics M7
Chapter 13
(Annex IV) Technical data
81 | Electronics M7
Chapter 13
(Annex IV) Technical data
82 | Electronics M7
Chapter 13
(Annex IV) Technical data
83 | Electronics M7
HIMOINSA HEADQUARTERS
Ctra. Murcia - San Javier, km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 +34 902 19 11 28
Fax +34 968 19 12 17 Export fax +34 968 33 43 03
Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA
Subsidiaries:
ITALY | PORTUGAL | POLAND | GERMANY | SINGAPORE
UAE | MEXICO | PANAMÁ | ARGENTINA | ANGOLA
[email protected] | www.himoinsa.com
P0213M7GE_EN_rev1.1