E630-NE Data Sheet
E630-NE Data Sheet
MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
Frame Reference Quantity Unit Condition TB2 E/S 630
Max In (A) of Frame 630
Model E630
Number of Poles 3, 4
Type NE
Electrical characteristics
(kA) 480VAC 15
Rated breaking capacity (NEMA) 240VAC 50
Protection
Installation
Front connection (FC)
Extension bar (FB)
Cable clamp (FW) -
Rear connecton (RC)
Plug-in (PM) 2
Din rail mounting (DA) -
Dimensions height (mm) 260
width (mm) 3 pole, (1 pole) 140
4 pole 185
Weight depth (mm) 103
weight (kg) 3 pole, (1 pole) 5.0
4 pole 6.5
Operation
Direct OpeningAction
Toggle operation
Door mounted (HS) / breaker mounted handle (HB)
Motor operation (MC)
Standard Optional - Not Available MCCB cannot be used in IT systems at this voltage.
2 Not fully rated at 50oC refer to Temperature Ratings
Page 1 of 4
DATA SHEET: TEMBREAK 2 E630-NE MCCB
Front connected
With extension bars
(optional)
30
Rear connected
Page 2 of 4
Innovators in Protection Technology
Front connected
30
Page 3 of 4
NE, S630-CE, S630-GE
Innovators in Protection Technology
2 T
hour
IR
1
Ip
40 tR
30 tp
Ig
20 Is d
ts d
10
tg
minute
Ii
6
I
4
40
30
20
Tripping Time
10
1
s econd
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.005
10
20
30
40
50
80
100
125
200
300
400
500
600
1000
1500
2000
3000
8000
4000
5000
Percen t R ated
Current I n P ercent R ated C urrent I R
I n = 630A
I R (A)
LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.85 0.9 0.95 1.0
Characteristics No. 1 2 3 4 5 6
11 21 21 5 10 16
LT tR (s)
at 200% x I R at 600% x I R
Standard I sd xI R 2.5 5 8
ST tsd (s) 0.1 0.2
INST Ii xI R 14(Max: 10 x I n) Note (1)
Ip xI R 0.8
PTA tp (s) 40
GF Ig xI n 0.2
Option Note(3) tg (s) 0.2
IN xI R 1.0/0.5 Note(2)
NP
tN (s) tN=tR
Note
(1) I i max. = 10 x I n. (2) 1.0 x I R or 0.5 x I R can be selected. Characteristic of neutral protection (tN vs. I N) is identical to characteristic of
phase protection (tR vs. I R). (3) When you specify GF on MCCBs with 3 poles the terminal block is automatically fitted to connect with
the external neutral CT for 3 phases 4 wires system. See terminal bl