Siemens FC901 Maintenance Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

Fire Alarm Control Panel

Model FC901-U3/FC901-R3
Installation, Operation and Maintenance Manual

Building Technologies Division


TABLE OF CONTENTS
INTRODUCTION ....................................................................................................................................................... 1
CONTROL PANEL LIMITATIONS ....................................................................................................................... 1
PREFACE ............................................................................................................................................................. 2
DESCRIPTIONS........................................................................................................................................................ 4
FC901 SYSTEM DESCRIPTION .......................................................................................................................... 4
Power Supply ..................................................................................................................................................... 4
Signaling Line Circuit (SLC) ............................................................................................................................... 4
Notification Appliance Circuits............................................................................................................................ 5
Status Relays ..................................................................................................................................................... 5
Programming Port .............................................................................................................................................. 5
DACT.................................................................................................................................................................. 5
OPTIONAL MODULES......................................................................................................................................... 5
City Tie Module (FCI2020-U1) ........................................................................................................................... 5
Battery Sets ........................................................................................................................................................ 5
SLC ADDRESSABLE DEVICES.......................................................................................................................... 6
Smoke Detector.................................................................................................................................................. 6
Heat Detectors.................................................................................................................................................... 6
Addressable Modules (Monitor and Control)...................................................................................................... 6
Manual Stations.................................................................................................................................................. 6
Programming SLC Devices ................................................................................................................................ 6
EVENT HISTORY ................................................................................................................................................. 7
GENERAL DESIGN FEATURES ......................................................................................................................... 8
Environmental..................................................................................................................................................... 8
Power Limiting .................................................................................................................................................... 8
Ground Fault Detection ...................................................................................................................................... 8
NAC Operation ................................................................................................................................................... 8
Security Features ............................................................................................................................................... 8
REGULATORY STANDARDS ............................................................................................................................. 9
Underwriters Laboratories .................................................................................................................................. 9
Federal Communications Commission............................................................................................................... 9
GENERAL SPECIFICATIONS ........................................................................................................................... 10
Environmental................................................................................................................................................... 10
Primary Power Supply...................................................................................................................................... 10
Secondary Power Supply ................................................................................................................................. 10
Auxiliary Power Outputs ................................................................................................................................... 10
Status Relays ................................................................................................................................................... 11
Notification Appliance Circuits.......................................................................................................................... 11
SLC Addressable Device Circuits .................................................................................................................... 11
City Tie Circuits ................................................................................................................................................ 11
DACT Circuits................................................................................................................................................... 12
CONTROL PANEL OPERATION ........................................................................................................................... 13
OPERATION INSTRUCTIONS........................................................................................................................... 13
Standby Condition ............................................................................................................................................ 13
Alarm Conditions .............................................................................................................................................. 13
Trouble Conditions ........................................................................................................................................... 14
Supervisory Conditions .................................................................................................................................... 14
ADDITIONAL OPERATING PROCEDURES ..................................................................................................... 16
Lamp Test......................................................................................................................................................... 16
History .............................................................................................................................................................. 16
FC901 OPERATING INSTRUCTIONS ............................................................................................................... 17
Alarm Operation ............................................................................................................................................... 17
Authorized Personnel Only............................................................................................................................... 17
Trouble Operation............................................................................................................................................. 17

i
Event Scrolling.................................................................................................................................................. 17
Fuse Replacement and Battery Maintenance .................................................................................................. 17
CONTROL PANEL INSTALLATION ...................................................................................................................... 18
PARTS SUPPLIED – FC901 .............................................................................................................................. 19
1. FC901 Enclosure Package........................................................................................................................... 19
2. FC901 Main Board Package ........................................................................................................................ 19
3. FC901 Configuration Kit Package ................................................................................................................ 21
CAUTIONS.......................................................................................................................................................... 22
CONTROL PANEL LOCATION ......................................................................................................................... 22
INSTALLATION .................................................................................................................................................. 22
Enclosure Mounting.......................................................................................................................................... 22
Remove Knock-Outs ........................................................................................................................................ 25
Power Supply Mounting ................................................................................................................................... 26
Ground Wire Installation................................................................................................................................... 27
Battery Installation ............................................................................................................................................ 28
Optional City Tie Mounting ............................................................................................................................... 29
Main Board Assembly Installation .................................................................................................................... 30
Earth Cable Installation .................................................................................................................................... 30
SYSTEM WIRING.................................................................................................................................................... 31
AC Connection ................................................................................................................................................. 31
Battery Connection........................................................................................................................................... 31
WIRING ............................................................................................................................................................... 31
Control Panel Wiring Overview ........................................................................................................................ 32
Wiring Entering Enclosure................................................................................................................................ 32
Install Wiring ..................................................................................................................................................... 32
Wiring Separation ............................................................................................................................................. 33
Internal Structure .............................................................................................................................................. 34
Power Supply and Battery Wiring..................................................................................................................... 35
Status Relays ................................................................................................................................................... 36
Auxiliary Power Outputs Wiring........................................................................................................................ 36
NAC Wiring....................................................................................................................................................... 37
SLC Addressable Device Circuit ...................................................................................................................... 38
SLC Addressable Device Wiring Diagrams...................................................................................................... 41
Optional City Tie/Leased Line .......................................................................................................................... 43
DACT Wiring..................................................................................................................................................... 43
PROGRAMMING THE CONTROL PANEL ............................................................................................................ 44
KEYPAD PROGRAMMING ................................................................................................................................ 44
PC PROGRAMMING .......................................................................................................................................... 44
PROGRAMMING SECURITY ............................................................................................................................. 44
MAINTENANCE ...................................................................................................................................................... 45
GENERAL........................................................................................................................................................... 45
QUICK TEST....................................................................................................................................................... 46
APPENDIX-A: REFERENCE DATA ....................................................................................................................... 48
WIRE SELECTION GUIDES............................................................................................................................... 48
Resistance of Solid Copper Wire ..................................................................................................................... 48
Addressable Device Circuit Wire Selection Guide ........................................................................................... 48
BATTERY SIZE CALCULATIONS..................................................................................................................... 49
Total System Currents...................................................................................................................................... 49
Battery Size ...................................................................................................................................................... 49
APPENDIX-B: COMPATIBLE DEVICES................................................................................................................ 50
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS..................................................................................... 50
Siemens SLC Manual Pull Stations.................................................................................................................. 50
Siemens SLC Modules..................................................................................................................................... 50
Siemens SLC Detectors ................................................................................................................................... 51
Siemens SLC Bases ........................................................................................................................................ 50
Siemens SLC Accessories (ILED-HC, -HW don’t match from compatibility list) ............................................. 50
FD182UL .......................................................................................................................................................... 51

ii
DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS ............................................................................... 52
APPENDIX-C: TROUBLESHOOTING.................................................................................................................... 53
A. General ........................................................................................................................................................ 53
B. System Events ............................................................................................................................................. 54
APPENDIX-D: ALARM VERIFICATION................................................................................................................. 55
APPENDIX-E: APPLICATION SPECIFIC DETECTION ........................................................................................ 56
APPENDIX-F: TESTING/MAINTENANCE ............................................................................................................. 57
APPENDIX-G: LCD, CONTROLS AND INDICATORS .......................................................................................... 58
Communication Port Connector ....................................................................................................................... 58
LEDS, Buzzer and Dedicated Push Buttons .................................................................................................... 58
LCD Display...................................................................................................................................................... 61
APPENDIX-H: OUTPUT FEATURES ..................................................................................................................... 62
Output Activation- and Deactivation- Delays.................................................................................................... 62
APPENDIX-I: PAS / PRE-SIGNAL ......................................................................................................................... 63
PAS .................................................................................................................................................................. 63
Pre-Signal......................................................................................................................................................... 64
APPENDIX-J: DACT INFORMATION OVERVIEW ................................................................................................... 65
APPENDIX-K: GLOSSARY .................................................................................................................................... 70

iii
iv
INTRODUCTION
CONTROL PANEL LIMITATIONS
This control panel may not show an alarm condition without compatible initiating devices
(smoke detectors, etc.) and notification devices (horn, strobes, etc.) connected to it. Electrical
ratings of the initiation and notification appliances must be compatible with the electrical ratings
of the control panel and must be properly interconnected. The wiring used for interconnection
must be large enough to carry the total current for all appliances without excessive voltage
drop.

The control panel must be connected to a dedicated primary electrical source that has a high
degree of reliability and adequate capacity for this control panel. The only means of
disconnecting this power source shall be available only to authorized personnel and clearly
marked "Fire Alarm Circuit Control".

The control panel must also have connected to it a battery set (24V) that has enough capacity
to properly operate the system for 24 hours standby and 5 minutes alarm per UL864 9th
(section 63.2.3 and 63.2.5) . These batteries do lose capacity with age. Batteries must be
replaced when they fail to provide the control panel with the required standby and alarm power
or after 4 years, whichever happens first. These batteries must be checked for performance at
least two (2) times a year or more often if local requirements dictate.

Even though this control panel was made to last for the expected life of the fire alarm system,
any part could fail at any time. Therefore a regular test program should be followed and
documented to make sure that each part of the system is tested as in Chapter 7 of NFPA 72 or
more often if dictated by local code requirements. Malfunctioning units must be replaced or
repaired immediately by factory authorized service personnel.
This control panel is designed to show an alarm condition when the initiating devices
NOTE
connected to it detect specific conditions. These conditions may or may not represent a life-
threatening condition. Also, evacuation of a building or area unnecessarily may subject
individuals to an unnecessary hazard. Therefore, it is most important that the building owner,
manager, or representative promulgate, distribute, and/or post instructions describing steps
to be taken when the fire alarm control panel signals an alarm condition. These instructions
should be developed in cooperation and conformance with representatives of the local
authority having jurisdiction.
As a precautionary measure, it is strongly suggested that one of these steps should be to
notify the local fire department of an abnormal condition even where the DACT option (or
similar device) is included in the system.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.

Program Feature or Option Possible Settings Settings Permitted in UL 864

Supervision/Trouble Resound Not enabled Yes


0-30 hours 1-24 hours

1
PREFACE
Along with the use of this instruction manual, the appropriate following standards and the
manufacturer's instructions for initiating and notification devices should be used to install and
maintain a functioning fire alarm signaling system.

NFPA 72 National Fire Alarm Code

For other standards that may apply contact the authority having jurisdiction.

For NFPA publications, contact:

National Fire Protection Association


Batterymarch Park
Quincy, Massachusetts 02269

FCC PART 68 WARNING


1. This equipment complies with Part 68 of the FCC rules and the requirements adopted by
the ACTA. On bottom of this equipment is a label that contains, among other information, a
product identifier of [US:02XAL00BFCM901]. If requested, this number must be provided to
the telephone company.

2. If this equipment FC901 causes harm to the telephone network, the telephone company will
notify you in advance that temporary discontinuance of service may be required. But if
advance notice isn’t practical, the telephone company will notify the customer as soon as
possible. Also, you will be advised of your right to file a complaint with the FCC if you
believe it is necessary.

3. The telephone company may make changes in this facilities, equipment, operations or
procedures that could affect the operation of the equipment. If this happens the telephone
company will provide advance notice in order for you to make necessary modification to
maintain uninterrupted service.

4. If you experience trouble with this equipment, you disconnect it from the network until the
problem has been corrected or until you are sure that the equipment is not malfunctioning.

5. Please follow instructions for repairing if any (e.g. battery replacement section); otherwise
do not alternate or repair any parts of device except specified.

6. Connection to party line service is subject to state tariffs. Contact the state public utility
commission public service commission or corporation commission for information.

7. If the telephone company requests information on what equipment is connected to their


lines, inform them of:
a) The telephone number that this unit is connected to,
2
b) The ringer equivalence number [0.0B]
c) The USOC jack required [RJ11C], and
d) The FCC Registration Number [US:02XAL00BFCM901]
Items (b) and (d) are indicated on the label. The ringer equivalence number (REN) is used
to determine how many devices can be connected to your telephone line. In most areas,
the sum of the RENs of all devices on any one line should not exceed five (5.0). If too
many devices are attached, they may not ring properly.

Service Requirements
In the event of equipment malfunction, all repairs should be performed by our Company or an
authorized agent. It is the responsibility of users requiring service to report the need for service
to our Company or to one of our authorized agents. Service can be facilitated through our
office at:

SIEMENS INDUSTRY, INC. – BUILDING TECHNOLOGIES DIVISION – FIRE SAFETY


8 FERNWOOD RD., FLORHAM PARK, NJ 07932
+1 973 593 6582

3
DESCRIPTIONS
FC901 SYSTEM DESCRIPTION
The FC901 is a compact but powerful standalone fire alarm control panel. It features advanced
addressable fire detection, keypad and offline programming, notification circuits, a 160 by 64
dots LCD display and event history retention capability. Its typical configuration includes a
power supply, a signaling addressable device circuit, two notification appliance circuits (NAC),
Digital Alarm Communication Transmitter (DACT), four system status relays and a USB
programming port.

All the components of the FC901 control panel are mounted in an 18.1" x 16.5" enclosure. The
FC901 has only one electronic main board which integrates most functional parts together (the
CPU board is mounted to main board before delivery), including DACT, System Display,
signaling line circuit, NAC, serial interface circuits, system status relays, programming port and
battery charging circuit. The main board is mounted on the supporting frame, and it provides
the connections for external field wiring. An optional city tie module can be mounted on the
backside of the main board. The power supply is located under the main board and supporting
frame.

The FC901 features one LCD screen which is used to indicate the specific indications for
system events while LEDs indicate general panel status.

FC901 supports surface mounting and semi-flush mounting. Semi-flush mounting kits are
available for the enclosure.

System status information is provided by a 160 by 64 dots, backlit LCD and by discrete LED
indicators for major control panel functions.

The LCD is used to display event data, including alarms and troubles conditions, zone or
device custom identification of messages, and a log of the system event history. A back light is
included in the display to assure visibility in low light. To conserve power, the back light is only
activated during a reported event or on operation of a display control button.

Individual LEDs on the panel are provided to indicate ALARM, SUPERVISORY, TROUBLE,
NAC SILENCED, AUDIBLES ON, SYSTEM GROUND FAULT and SYSTEM POWER. Direct
push-button controls are provided for SILENCE, UNSILENCE, ACKNOWLEDGE, MENU, OK,
CANCEL, RESET and a four-way button for menu navigation.

Power Supply
A 26V (nominal) power supply provides all operating power to the control panel for both
standby and alarm conditions. Sufficient battery charging capability is available to charge 12-
18 AH sealed lead-acid batteries within code requirements for up to 24 hours of normal
standby operation plus 5 minutes of alarm operation. The battery will be automatically
disconnected at low battery voltage to prevent deep discharge and battery damage.

Signaling Line Circuit (SLC)


The FC901 fire alarm control panel provides a signaling line circuit with the capacity of 50
addressable devices.

4
Notification Appliance Circuits
The FC901 control panel has two independent notification appliance circuit (NACs). It can be
configured as two Class B (Style Y) NACs or one Class A (Style Z) NAC. Each circuit can be
selected to give continuous output or one of five sounding patterns. There is also a system
coder capable of zone operation. All of the NACs are power limited and support
synchronization of listed devices using the Siemens sync protocol.

Serial Interface Circuit


The FC901 control panel has a Serial Interface Circuit that will drive up to 8 remote LCD
annunciators.

Status Relays
Four relays with dry contacts are provided. Three relays are dedicated to alarm, supervisory,
and trouble conditions on the panel. The remaining relay is programmable. The relay contacts
are Form C and are rated for 2A@30VDC resistive.

Programming Port
A USB standard type B plug is provided for temporary connection to a computer for panel
programming and firmware download when using the FX901-U2 System Configuration Tool.

DACT
The Digital Alarm Communication Transmitter (DACT) is integrated on the FC901 main board
and it will send control panel status information to a central or remote receiving station through
the Public Switched Telephone Network (PSTN).

OPTIONAL MODULES
City Tie Module (FCI2020-U1)
The city tie module provides local energy and polarity reversal connections. The polarity
reversal connections provide a trouble circuit and an alarm circuit with optional trouble output.
The city tie board mounts onto the main board.

Battery Sets
The FC901 control panel is designed to use only rechargeable sealed lead-acid batteries for
back-up power. Maximum battery charging capacity for the FC901 is 18AH.

AUXILIARY MODULES
Serial LCD Annunciators
The FSD901 Serial LCD Annunciator consists of a backlit 160 by_64 dot LCD display, -,
acknowledge, silence, unsilence, and reset buttons, a four-way button for event navigation,
seven system status LED indicators and a security key switch. To prevent unauthorized
system operation, the control buttons are only enabled when the key switch is activated. The
display and controls of the FSD901 are the same as those on the front of the control panel.
The backlight activates only upon active button press or when events are present in the
system to conserve power.
Up to 8 annunciators may be addressed by the communication circuit. Each annunciator
requires connection to the Serial Interface circuit on the mainboard, and 24V DC power.

5
SLC ADDRESSABLE DEVICES
Smoke Detector
The control panel processor sends the sensitivity settings to the detectors and polls the
detectors for their status. The detector determines normal, trouble and alarm conditions and
communicates the conditions to the control panel.

Variable Thresholds - The detectors can be set to operate in various pre-programmed profiles,
depending on the environment where the detectors are used.
Operator Alerts - The control panel can indicate a trouble event automatically on the
occurrence of a number of conditions of the detector. The supported conditions include:
„ Channel Active
„ Unconfigured Device
„ Device Type Mismatch
„ Device Communication Trouble
„ Address Invalid
„ Address Unspecified
„ Multiple Device Response
„ Parameter Error
„ Device Type Unknown
„ Fatal Fault
„ General Trouble
„ Dirty
„ Replace

Heat Detectors
Addressable heat sensing detectors may be intermixed on the circuit for locations where heat
sensing may be the most effective detection method. The heat detectors may be programmed
for rate of rise operation or fixed temperature.

Addressable Modules (Monitor and Control)


In addition to detectors, the circuit can communicate with addressable monitor and control
modules. Monitor modules allow remote contact closure initiating devices to generate event
conditions on the system. Control modules provide the system remote relay outputs or
notification appliance circuits

Manual Stations
Addressable manual stations may be intermixed on the circuit with proper response
programmed into the control panel.

Programming SLC Devices


SLC devices can be assigned their electronic address and be tested by using the DPU Device
Programmer/ Loop Tester.

6
EVENT HISTORY
The control panel includes a non-volatile memory recording 1000 system events. Identified
alarm, trouble, supervisory, status and other significant events will be recorded along with the
date and time of occurrence. The history event log can be viewed at the main system display
by operating menu controls from the panel. The history event log can also be transferred from
the panel to a computer using the FX901-U2 system configuration tool.

Events recorded in the history are:

„ Alarm, trouble, supervisory and status conditions


„ Alarm silence/unsilence (Manual)
„ System reset
„ User level login/logout
„ Start and stop of quick test
„ Expiration of quick test Timer
„ Trouble/supervisory reminder
„ Acknowledgment
„ Trouble/supervisory restored to normal

7
GENERAL DESIGN FEATURES
Environmental
The FC901 panels and subassemblies are suitable for use in a dry, indoor or protected
location.

Power Limiting
The AC power connection, battery wiring and four system status relays are not power limited.
All other circuits leaving the control panel meet the requirements for power limited circuits
when installed in accordance with the National Electrical Code and local requirements.

Ground Fault Detection


The control panel provides system ground fault detection. Main board ground fault event is
annunciated as a trouble condition on the system. In addition, the addressable circuit and
serial interface circuit have their own ground detection circuitry and indicator.
System- NAC (+) Ground Fault Threshold <20kΩ
System- NAC (-) Ground Fault Threshold <20kΩ
System- Auxiliary Power (+) Ground Fault Threshold <5kΩ
System- Auxiliary Power (-) Ground Fault Threshold <5kΩ
System- City Tie (+) Ground Fault Threshold <5kΩ
System- City Tie (-) Ground Fault Threshold <5kΩ
SLC grounding detection threshold
SLC(+) – Ground <5kΩ
SLC(-) – Ground <5kΩ

NAC Operation
The notification appliance circuits are controlled by the system microprocessor in accordance
with the site specific system configuration.
The notification appliance circuits can operate audible and visual notification appliances. Each
NAC can provide any of five software-generated codes or continuous operation to audible
notification appliances. Also, each NAC supports synchronization of visual notification
appliances.
Silence Inhibit - The control panel may be programmed to inhibit silence for up to four minutes
from the first alarm.
All of the NACs are power limited.
Security Features
Multi-level password protection of programming functions prevents unauthorized configuration
changes.
Device type supervision: If the device type identifier reported by an addressable detector or
module does not agree with the configuration, the system reports a trouble condition.
Device address supervision: The system checks that all configured devices on the addressable
device circuit respond to an address poll. The system reports a trouble condition if the
following conditions are detected:
8
„ Configured device is missing.
„ Unconfigured device is installed.
„ Two devices are programmed with the same address.
„ Signaling line circuit experiences a wire-to-wire short.
„ Signaling line circuit experiences an earth ground condition.

REGULATORY STANDARDS
The FC901 control panel meets the requirements of industry and government regulatory
agencies as noted.

Underwriters Laboratories
The FC901 control panel is listed under UL Standard 864 for compliance to NFPA Standard 72
for fire service.

Federal Communications Commission


The DACT meets the Class A requirements of the Code of Federal Regulations (CFR 47), Part
15 for electromagnetic field emissions. The DACT also meets the requirements of the Code of
Federal Regulations (CFR 47), Part 68, for connection of equipment to the public switched
telephone network.

9
GENERAL SPECIFICATIONS
Operating specifications for the FC901 are as follows:

Environmental
Operating temperature - 32 - 120°F (0 - 49°C)
Relative humidity - Up to 93% @ 90°F (32°C)
To be installed in a indoor dry protected environment only

Primary Power Supply


Input: 120VAC, 60 Hz or 220 VAC, 50 Hz
@ 2.0A Max.
Supervised
Output: 26VDC @ 6.5A Max.
Max current: 6.5A (2 hours Max.)
Filtered and Regulated

Secondary Power Supply


24V lead-acid battery set
Max. charged voltage: 27.8 VDC
Automatic low battery disconnect voltage: 19.2±0.1VDC
Max. charge current: 0.45A
Battery capacity:12AH to 18AH
Supervised

Auxiliary Power Outputs


Non-resettable power output
Power limited
Alarm status: 0.75A
Normal stand by: 0.05A
Voltage: 19 to 28VDC
Ripple: 0.1 VAC
Special Application

Resettable power output


Power limited
Alarm status: 0.75A
Normal stand by: 0.05A
Voltage: 19 to 28VDC
Ripple: 0.1 VAC
Special Application

10
Status Relays
Non-power limited
One programmable relay
Three non-programmable relays: Trouble, Supervisory, Alarm
Contact rating: 2A, 30VDC maximum
Form C contact

Notification Appliance Circuits


Power limited
Supervised
Current Draw Maximum Line Resistance
2.5A 3.2Ω
2.0A 4.0Ω
1.5A 5.3Ω
1.0A 8.0Ω
0.5A 16.0Ω
Alarm voltage: 16 to 32VDC
Maximum ripple: 0.1VAC
Used for special application only
Two Style Y/Class B or one Style Z/Class A
Total Max. Current: 2.5A

Serial Interface Circuit


Power limited
Supervised
Maximum wire loop resistance: 50 ohms total
Physical layer: RS485

SLC Addressable Device Circuits


32 VDC Max
Power limited
Supervised
Max. current: 0.07A(RMS)
Maximum wire loop resistance: 50Ω
Two Style 4 Class B or one Style 6 Class A circuit
Max. 50 addressable devices

City Tie Circuits


Supply Input:

11
Voltage: 26 VDC
18 – 28 VDC for battery
Current: Max. 0.4A
Supervised

Output:

City Tie-Output 1
Normal output voltage: 19-28VDC (open circuit condition)
Supervisory current: 1mA
Maximum trip current: 400mA
Maximum coil plus wire resistance: 22.5Ω

Leased line-Output 1
Normal output voltage: 19-28VDC (open circuit condition)
Trouble output voltage: 0V
Alarm output voltage: -(19-28)VDC (open circuit condition)
Maximum wire resistance: 2-5KΩ
Maximum short circuit current: 25mA

Leased line-Output 2
Normal output voltage: 19-28VDC (open circuit condition)
Supervisory output voltage: -(19-28)VDC (open circuit condition)
Maximum wire resistance: 2-5KΩ
Maximum short circuit current: 25mA

DACT Circuits
Power limited
Supervised for short or open circuit conditions
Compliance to FCC part 68
Support RJ31X connection
Compatible Digital Alarm Communication Receiver (DACR) list,

Device Module Manufacture


MX8000 Honeywell

CAUTION – To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line
cord.

12
CONTROL PANEL OPERATION
OPERATION INSTRUCTIONS
Standby Condition
In normal standby operation, the green AC POWER ON LED should be illuminated and no
other indicator operating. The display will show the system label and the current time.

Alarm Conditions

ALARM
When the system detects an alarm condition, the alarm LED activates (ON – flashing) and the
local panel buzzer activates in a specific pattern to indicate an alarm condition. Programmed
system outputs, including audible and visual notification appliances, relays activate, and the
LCD display indicates the zone or point initiating the alarm.

Upon receipt of an alarm, building occupants should proceed in accordance with the
established emergency response plan. System responders should assure that all personnel
are accounted for, and notify the Fire Department.

Operating the ACKNOWLEDGE button will silence the local panel buzzer and change the LED
alarm indicator from flashing to steady. The LCD display will indicate that the active events
have been acknowledged.

To silence the audible and/or visual notification appliances (where permitted by the codes and
control panel programming), press ALARM SILENCE. The notification appliances will be de-
activated, and the alarm silence LED will be off.

POSITIVE Alarm Sequence (PAS)


Activation of an initiating device in an input group programmed for PAS activates the Alarm
LED, LCD display, and the local panel buzzer. System and user-programmed outputs do not
activate immediately.

Operation of the ACKNOWLEDGE button within 15 seconds of the activation of the initiating
devices will delay activation of system and user-programmed outputs between 60 and 180
seconds(selected during system configuration) for the purpose of investigating the alarm. If the
ACKNOWLEDGE button is not operated within 15 seconds, the system and user-programmed
outputs activate at the expiration of the 15 second delay.

If the initiating device and the panel are reset before the programmed delay expires, the alarm
sequence is aborted.

During the investigation period, an alarm condition on a detector programmed for direct alarm
response (such as the key switch on a manual station) will override the programmed delay and
activate the additional user-programmed outputs immediately. User can configure Manned
status of FACP to enable/disable PAS feature. FACP will not perform PAS feature in
Unmanned status. After logged in as L2/L3 user, user can select Unmanned item in operate
menu to enter Unmanned status and bypass all on-going PAS alarms.

13
PRE-SIGNAL ALARMS
Activation of an initiating device in an input group programmed for PRE-SIGNAL, activates the
Alarm LED, LCD display, and the local panel buzzer. System and user-programmed outputs
activate immediately except NAC.

The delay of activation of user-programmed outputs can be programmed from 60 to 180


seconds. If the system is not reset during this period, the NAC outputs will activate.

During the delay period, an alarm condition on a detector programmed for direct alarm
response (such as the key switch on a manual station) will override the programmed delay and
activate the user-programmed NACs immediately.

NOTE Do not reset the system until the alarm condition has been cleared. The LCD display will
indicate the area in which the alarm was detected. The detector or module associated with the
device initiating the alarm will display a light indicating activation (if applicable).
When the alarm condition has been corrected, return the system to standby operation by
pressing the RESET button.

Trouble Conditions
When the system detects a trouble condition, the trouble LED will be flashing, the LCD
displays trouble events and the local panel buzzer activates in specific pattern that
distinguishes the event from an alarm event. Refer to the applicable section of the system
manual to determine the probable cause of the trouble and the action to be taken.

Operating the ACKNOWLEDGE button will silence the local panel buzzer and change the LED
trouble indicator from flashing to steady. The LCD display will indicate that the active events
have been acknowledged.

If the panel is configured for Supervisory/Trouble Resound Reminder, and the trouble condition
is not corrected the local panel buzzer will re-activate when the reminder timer has relapsed to
remind users of the trouble condition.

If the FC901 is configured as “Trouble self restoring”, the system shall return to the “system
normal” status if the trouble condition is restored, unless there are additional events on the
system. If the FC901 is not configured as “Trouble self restoring”, the system reverts to
standby condition only after the RESET button is pressed.

Supervisory Conditions
When the system detects a supervisory condition, the supervisory LED will be flashing, the
LCD display supervisory events, and the local panel buzzer activates in a specific pattern that
distinguishes it from an alarm event.
Operating the ACKNOWLEDGE button will silence the local panel buzzer and change the LED
supervisory indicator from flashing to steady. The LCD display will indicate that the active
events have been acknowledged.

If the panel is configured for Supervisory/Trouble Resound Reminder, and the supervisory
condition is not corrected, the local panel buzzer will re-activate when the reminder timer has
relapsed to remind users of the supervisory condition.

14
If the FC901 is configured as “Supervisory self restoring”, the system shall return to the
“System Normal” status if the supervisory condition is restored unless there are additional
events on the system. If the FC901 is not configured as “Supervisory self restoring”, the
system reverts to standby condition only after the RESET button is pressed.

15
ADDITIONAL OPERATING PROCEDURES
In addition to the basic fire alarm instructions above, several features are included to facilitate
maintenance and increase the versatility of the system. The following are procedures used to
initiate these functions.

Lamp Test
When selected, Lamp Test activates LCD, the buzzer and turns on all the LEDs on the user
interface, then back to its previous state.
To initiate a Lamp Test, proceed as follows:
Press "MENU".
On the MENU display, select "Oper".
Select “Lamp Test “to run.
Note that lamp test operates the indicators only on the units being operated and no record is
reported to system history.
The lamp test lasts 10 seconds. From 0 to 4 seconds LCD test; From 4 to 7 seconds LEDs
test; From 7 to 10 seconds buzzers test. Operator doesn't need to turn it off manually. Lamp
test will automatically quit when it completes.

History
The last 1000 system events are time-tagged and recorded for review in the user level event
history. This history and all user-level functions are available to users with the door key.
Operation of history:
New events overwrite old when filled.
For more information see the Event History section.
Access to history:
To recall past events, proceed as follows:
• Press “MENU” button.
• On the “MENU” display, select “View”.
• Select “History”.
Operate up button adjacent to the LCD for previous event display.
Operate down button adjacent to the LCD for next event display.

16
FC901 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the Alarm LED flashes, LCD displays alarm conditions and the panel buzzer sounds in a
distinct alarm pattern. Local audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are
accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has
been received at the Fire Department.

Authorized Personnel Only


To acknowledge the alarm:
To acknowledge the alarm, press the Acknowledge button. The local buzzer will be silenced and the
Alarm LED will change from on-flashing to on-steady.
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, press the Alarm Silence button.
The silenceable notification appliances will be silenced. The Silenced LED will change from off to on-steady
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a
predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing the
Reset button.
Trouble Operation
Trouble is indicated by:
Trouble LED flashes, LCD displays trouble conditions. Panel buzzer sounds in trouble pattern.

To acknowledge the trouble:


Press the Acknowledge button. The Trouble LED turns on-steady and the buzzer turns off. When the
trouble condition has been cleared, you need to reset the panel to restore to a normal standby condition
if panel is not configured as “Trouble self restoring”. When panel is configured as “Trouble self
restoring”, it will restore automatically to normal standby condition after clearing of trouble condition.

Warning: devices in trouble condition may not report a fire alarm.


Event Scrolling
Viewing Events on the System:
Events are displayed according to the following rules:
1: Events priority:
Unacknowledged Alarm > Unacknowledged Supervisory > Unacknowledged Trouble > Acknowledged
Alarm > Acknowledged Supervisory > Acknowledged Trouble > Status > Test
2: Within events of the same priority, all events are displayed in the order of occurrence with the latest
displayed the first.
3: Status events are displayed according to the event setting. If it is configured as “No display”, it will not
be listed in Event List.

Fuse Replacement and Battery Maintenance


Battery fuse(F304): 15A blade type (Littelfuse: 0257015.PXPV or Bussmann: ATC-15)
City tie fuse(F1-F4): 1.25A cartridge type (Littelfuse: 02151.25P or Schurter: SPT 0001.2505)
This product requires two 12V batteries in series, for a combined voltage of 24V. Replace batteries every 3 to 5
years.
Recommended battery manufacturers:
Power Sonic: PS-12120, PS-12140, PS-12180 Yuasa: NP-12-12
Battery capacity: min. 12Ah / max. 18Ah Charge current: max. 0.45A

For service, contact: _______________________Telephone Number: ______________________________


Frame these instructions and mount them near the control panel for operator reference.

17
FSD901 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the buzzer sounds. Local
audible and visual signals and remote alarm signals operate.

When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel
are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic
signal has been received at the Fire Department.

Authorized Personnel Only


To acknowledge the alarm:
To acknowledge the alarm, enable the control buttons by operating the keyswitch, and press the
Acknowledge button. The local buzzer will be silenced and the Alarm LED will change from on-
flashing to on-steady.
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, press the Alarm Silence
button. The silenceable notification appliances will be silenced, and LED indications will change
from flashing to continuous. The Alarm Silenced LED will be lit.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing
the Reset button.

Trouble Operation
Trouble is indicated by:
Trouble LED flashes, LCD displays trouble conditions. Panel buzzer sounds (pulsing).
To acknowledge the trouble:
Enable the control buttons by operating the keyswitch, and press the Acknowledge button. The
Trouble LED turns on-steady. When the trouble condition has been cleared, you may need to
reset the panel to restore to a normal standby condition.

Warning: Devices in trouble condition may not report a fire alarm.


Event Scrolling
Viewing Events on the System:
Events are displayed in the system by event priority (Unacknowledged Alarm > Unacknowledged
Supervisory > Unacknowledged Trouble > Acknowledged Alarm > Acknowledged Supervisory >
Acknowledged Trouble > Status > Test) followed by event occurrence (latest to oldest event) in a
circular list.
According to settings, some events can be suppressed (not display) on annunciator.

Normal Standby Condition


The green AC Power On LED will be lit and no other indicators on.

For service, contact: ___________________________________________


Telephone Number: _____________________________________________

Frame these instructions and mount them near the annunciator for operator reference.

18
PROGRAMMING THE CONTROL PANEL
KEYPAD PROGRAMMING
Customized programming of the control panel may be accomplished through the keypad
included in the control panel.

PC PROGRAMMING
Programming the panel may also be done by a temporary connection to the programming port
with a computer. This is the recommended method to program the panel.

The Siemens FX901-U2 software is available to allow programming the control panel by
connection to a Personal Computer (PC) with an USB port. This allows ease of operation by
preparing the program in advance and downloading to the control panel in a simple, rapid
operation.

PROGRAMMING SECURITY
The following levels of security protect the system from unauthorized use:

Level 1 (User) – Locked Door


Level 2 (Maintenance) – Locked Door and 4-digit Maintenance Password
Level 3 (Technician) – Locked Door and 4-digit Technical Password

The User Level is also accessible from FSD.

44
MAINTENANCE
GENERAL
The FC901 provides maintenance functions to allow for the setting and controlling of various
features in the system.

The maintenance functions are protected by a four digit password. To access the maintenance
features press the “MENU” button and select Login item in the View menu, enter the four digit
code when prompted and then press “OK”.

FC901 Maintenance is separated into two levels. The user can enter a different password to
enter different levels.

Level 2: Protected by level 2 password, Level 2 provides control functions.


Level 3: Protected by level 3 password, Level 3 provides control functions and parameter
change functions.

The following functions are accessible to L2 and L3 user by selecting items in the Operate
menu.

Disable/Enable Devices
Disable/Enable NACs
Disable/Enable City Tie
Disable/Enable DACT
Disable/Enable Status Relays
Disable/Enable Detector Applications
Disable/Enable PAS
Starting and Configuring Quick Test
Set the Time
Set the Date

The functions listed below are provided specifically to L3 users.


Edit Device Labels
Edit System Labels
Program a Device
Change the Maintenance Password

Disabling any input and output devices, applications will annunciate a trouble
condition.

45
QUICK TEST

The Quick Test mode makes it fast and easy to test a system by eliminating the need to
disconnect panel from remote connections to the Fire Department or other monitoring stations.
In this way, operator can test all devices locally without annunciating any condition to remote
connections.

To configure the Quick Test parameters, enter L2 user level and navigate to the Quick Test
item in the Operate menu. Configure the following parameters prior to starting Quick Test:
• Quick Test Time – FC901 will automatically quit Quick Test mode after the configured
time
• Disable Output – Don’t activate any output on events in Quick Test Mode
• Annunciator Off – Don’t send any events to annunciators in Quick Test Mode.
• History Off – Don’t record any events in History Record in Quick Test Mode
• NAC Off – Don’t activate NAC in Quick Test Mode

To initiate the Quick Test mode, enter L2 user level and navigate through the menu for the
Quick Test option and then select “START”. Test conditions will be annunciated on the panel
to indicate that panel is in Quick Test Mode. Initiation of any addressable device will not
activate associated NACs if “NAC OFF” is enabled in Quick Test mode.

By selecting the Extend (Quick Test) item in the Operate menu, L2 user can extend the quick
test time. L2 user can quit the quick test mode by selecting the Cancel (Quick Test) item in the
Operate menu.

HZM in Quick Test


Testing conventional detectors in Quick Test requires a few more steps than testing
addressable devices. Since the HZM only guarantees that one detector will stay in active at a
time, its detector loop must be reset after each detector is activated. This can be accomplished
in the following ways:
• By shorting the device loop for at least six seconds.
• By interrupting power to the device loop or the active device for at least six seconds.

Either of these methods will cause the active detector to reset.

The previous detector must be clear of smoke after resetting the loop or it will
generate another alarm.

46
This page is left intentionally blank.

47
APPENDIX-A: REFERENCE DATA
This appendix provides reference for the following topics:

Wire selection guides


Battery size calculations

WIRE SELECTION GUIDES


Resistance of Solid Copper Wire
AWG Ohms per Thousand Feet*
18 8.08
16 5.08
14 3.19
12 2.01
*NEC Chapter 9, Table 8.

Addressable Device Circuit Wire Selection Guide


Each addressable device circuit must meet the following requirements:

Total loop resistance - 50 ohm maximum with 50 devices


Total loop capacitance - 0.5uF max line to line per km and 1.0uF max line to shield per km

NOTE The terminal blocks of Siemens SLC devices are rated for a maximum of 14AWG wire.

48
BATTERY SIZE CALCULATIONS
Total System Currents
STANDBY (A) ALARM (A)
Main board 0.178 0.203
NAC 0 2.5
SLC 0.07 0.07
Auxiliary power 0.1 1.5
City tie module 0.001 0.04
Total 0.349 4.313

Use the Total Panel + Modules + Devices for the Battery Size Calculations

Battery Size
Total Standby Hours of Standby AH for
Current Required per NFPA 72 Standby
(from above) Standard
(4, 24 or 90)
A X Hours =

Total Alarm 5 Minutes of Alarm AH for Alarm


Current Operation
(from above) per NFPA 72 Standard
A X Hours =

A.H. for A.H. for Calculated De-rating A.H.


Standby Alarm A.H. Factor Required
Battery
Capacity
+ = X 1.1 =

Notes:
An additional multiplier is included to compensate for the higher discharge rate in alarm.
Battery capacity decreases with age.

49
APPENDIX-B: COMPATIBLE DEVICES
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS
Siemens SLC Manual Pull Stations
Siemens Description
Cat. No.
HMS-S Manual Station, Single Action
HMS-D Manual Station, Double Action
HMS-M Metal Manual Station, Single Action
HMS-2S single action manual pull station with 2-stage key switch

Siemens SLC Modules


Siemens Description
Cat. No.
HTRI-M Transmit-Receive Interface – Mini-Module
HTRI-S Transmit-Receive Interface – Single Monitor Circuit
HTRI-D Transmit-Receive Interface – Dual Monitor Circuit
HTRI-R Transmit-Receive Interface – Dual Monitor Circuit with Programmable Relay
HCP Intelligent Control Point
HLIM Line Isolator Module

Siemens SLC Bases


Siemens Description
Cat. No.
DB-11 Detector Base
DB-11E Detector Base
ADBH-11 Audible Base
DB-HR Relay Base
DB2-HR Relay Base

Siemens SLC Accessories


Siemens Description
Cat. No.
ILED-HC Intelligent Remote Lamp, Ceiling mount
ILED-HW Intelligent Remote Lamp, Wall mount
RL-HC Remote Lamp, Ceiling mount
RL-HW Remote Lamp, Wall mount
AD2-XHR Air Dust Housing with Relay
AD2-P Air Dust Housing

8700 SLC Manual Pull Stations


Siemens Description
Cat. No.
8700-S Manual Station, Single Action
8700-D Manual Station, Double Action
8700M Metal Manual Station, Single Action

50
8700 SLC Detectors
Siemens Description
Cat. No.
8710 Photo Detector
8712 Thermal Detector, Fixed or Fixed/Rate of Rise
8713 Photo/Thermal Detector

8700 SLC Modules


Siemens Description
Cat. No.
8702 single input interface module
8703 dual input interface module
8704 single input interface module with relay
8701 mini single input interface module
8706 intelligent control point
8705 conventional zone module
8709 Line isolator

8700 SLC Bases


Siemens Description
Cat. No.
8853B Detector Base
8715 Detector Audible Base
8716 Relay Base

8700 SLC Accessories


Siemens Description
Cat. No.
8726C Intelligent Remote Lamp, Ceiling mount
8726W Intelligent Remote Lamp, Wall mount
8727C Remote Lamp, Ceiling mount
8727W Remote Lamp, Wall mount
8741 Air Dust Housing with Relay
8743 Air Dust Housing

Notes:
1. Siemens SLC devices, detectors and modules, up to a maximum of 50 addresses may be used.
2. For specific wiring and installation information, read the instructions provided with each device.
3. If more than one HCP is used on a SLC device loop, the loop must be wired Class A or the riser conductors must be installed in
accordance with the Survivability From Attack By Fire requirements in the National Fire Alarm Code, NFPA 72. If wired Class A, at
least one HLIM loop isolator must be installed between each HCP and between the panel and the first and last HCP. See the HLIM
installation instructions for the maximum number of isolators allowed per loop and other wiring instructions.

FD182UL
Point Description
detectors
OP920 Smoke detector
OH920 Smoke heat detector
HI921 Heat detector

51
Global ASA
Point Description
detectors
OOH941 dual optical/thermal multisensor detector
OOHC941 dual optical/thermal

DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS

Please refer to A6V10333532

52
APPENDIX-C: TROUBLESHOOTING
DEFINITIONS FOR EVENT HISTORY ENTRIES

A. General
ENTRY INDICATES
Disabled The device has been disabled
Ground The device is in ground fault
Open The device is in open trouble
Short The device is in short trouble
Overload The SLC line is overloaded
GeneralTrouble The device reports general trouble
Unconfig The system finds a SLC device that is not in the config file
TypeMismatch The SLC device type is not consistent with the config file
CommunicationTrouble The communication between the device and the panel is abnormal
Multiple Device Response More than one SLC device has the same address
TypeUnknown The device type is unknown to the panel
Dirty The SLC device is dirty
Replace The SLC device needs to be replaced
ParameterError The SLC device has invalid parameter setting
AddressInvalid The address of SLC device is invalid
AddressUnspecified The SLC device has no address
ACFail The AC power of the system is in trouble
MessageLost The DACT lost some messages because of limited memory space
FatalFault The SLC device reported fatal fault trouble
VoltageLow The battery voltage is too low
VoltageHigh The battery voltage is too high
OverCurrent The NAC is in over current state
CircuitTrouble The battery charge circuit is in trouble
BatteryAbsent The battery is missing

53
B. System Events
ENTRY INDICATES/NOTES
Reset Panel reset
Silence Silence all silenceable outputs
Unsilence Unsilence all silenced outputs
Test Start quick test
QuitTest Exit quick test
Acknowledge Panel events acknowledged
Unacknowledge Resound of the trouble/supervisory
LogIn User level login
LogOut User level logout

54
APPENDIX-D: ALARM VERIFICATION

A - Smoke detector goes into alarm. (LED on device turns to red)


AB - Retard Period, FACP senses detector in alarm and delays alarm signal for 50s. In this
period, no alarm event reports on FACP.
BC - Confirmation Period, Detector is operational for alarm at point B. If detector is still in alarm
at point B, FACP will report alarm. If detector is not in alarm, system returns to standby. If the
detector re-alarms at any time during the confirmation period the FACP will alarm. The period
length is 60s.
CD – Restart next alarm verification period if new alarm occurs.

55
APPENDIX-E: APPLICATION SPECIFIC
DETECTION

Application Specific Detection (ASD) allows the system designer to program a detector’s
sensitivity, pre-alarm threshold, and other alarm-related parameters using English descriptions
of the detector's environment (application). This eliminates the need for detailed knowledge of
smoke detector terminology and operation. The designer can set all of the critical detector
parameters by simply selecting an application description that closely fits the one where the
detector is to be installed.

For example, to use ASD to select the optimal parameters for a detector in a hotel lobby,
select the LOBBY application in the FX901-U2 tool for that device. The system will
automatically transmit the factory determined sensitivity, pre-alarm threshold, and detection
algorithm (R-algorithm) to the corresponding device. This eliminates the guesswork of
selecting these parameters for different environments.

ASD APPLICATIONS of H-series and 8700-series detector


ASD Application ASD Description
Disable No Applications (Standard Photo/thermal Detector)
Office (Retail) Reasonably clean, climate controlled atmosphere
Airborne dust, equipment, fork truck and light to medium dock
Warehouse (Light Manufacturing)
area exhaust fumes
Relatively clean area, temperature changes, cellular phones,
Lobby
smoking
Very controlled environment, clean, temperature closely
Computer Room regulated, high cost clean machinery operating, no smoking, high
air velocity
Airborne dust and temperature changes, living quarters, cooking
Dormitory
fumes, smoking
Healthcare Higher level risk, relatively clean, electronic equipment
Parking Garage Airborne dust, car and diesel fumes, temperature swings
Normal to somewhat dirty environment, heat from running
Equipment Storage (Transformer) Room
equipment
Sensitive materials or equipment storage, clean dust-free
Precious Storage (Sensitive Environment)
environment, earliest warning desired
Dirty, dusty, humid, operating equipment, RF present, wide
Hostile Environment
temperature swings
Duct (Open air or duct housing) Dirty, dusty, humid, wide temperature swings, high air velocity

56
APPENDIX-F: TESTING/MAINTENANCE
If the system is connected to the fire department, etc., or actuates an internal system, disarm
the appropriate outputs before servicing to prevent actuation. Notify the fire department and
personnel at your facility that a System test is being performed so that any alarm sounding can
be ignored during the test. Notify the fire department before resetting the system.

Inspection, Testing, and Maintenance of the fire alarm system should be performed in
accordance with NFPA 72, The National Fire Alarm Code and all applicable local codes.

BATTERY MAINTENANCE
Perform the following tests at the recommended interval. Replace the battery set every four
years or if any of the test criteria are not met.

Initiation / Reacceptance
1. Charger Test—With the batteries fully charged and connected to the charger, measure the
voltage across the battery set. It must read 27.3V +/- 0.3V.
2. Discharge Test—With full system alarm load, the voltage on a fully charged battery must
not fall below 20.4V after 30 minutes.
3. Load Voltage Test—With full system alarm load, the voltage on a fully charged battery must
not fall below 24.6V after one minute.

Testing Interval
1. Semiannually—Perform the Load Voltage Test.
2. Annually—Perform the Charger Test and Discharge Test.

57
APPENDIX-G: LCD, CONTROLS AND
INDICATORS
The FC901 has a buzzer, 7 LEDs, 4 navigational push buttons, 4 dedicated push buttons,
alphanumeric keypad, 3 menu control buttons (menu, cancel, ok) and a communication port
connector.

Communication Port Connector


The communication port is connected to the USB port of the computer that has the FX901-U2
programming tool. This is used to upload and/or download panel configuration if this method of
programming is used.

The computer must be disconnected from the panel if not in use.

LEDS, Buzzer and Dedicated Push Buttons


The LEDs operate as follows:

This indicates that the system's power works


Steady ON normally. Both the main power and battery are
in normal status.
Power Green This indicates that the system is not powered
OFF on yet. This LED can be OFF only when the
system is shut down.
This indicates that the main power is in trouble
Flashing
status and system is working on battery.
This indicates that there are alarm events, and
Steady ON
all alarm events have been acknowledged.
This indicates that there is no alarm event in
OFF
Alarm Red system.
This indicates that there are alarm events in
Flashing system, but some of them have not been
acknowledged.
The Silenced LED can only be steady on when
the following conditions are all met:
1. There are activated silenceable devices,
Steady ON
and all of them have been silenced.
Silenced Yellow 2. There is no non-silenceable NAC
activated.
The Silenced LED will be OFF when above
OFF
conditions cannot be met.

This indicates that there are trouble events,


Steady ON
and all of them have been acknowledged.
This indicates that there is no trouble event in
Trouble Yellow OFF
system.
This indicates that there are trouble events in
Flashing system, but some of them have not been
acknowledged.
This indicates that there are supervisory
Supervisory Yellow Steady ON events, and all of them have been
acknowledged.

58
This indicates that there is no supervisory
OFF
event in system.
This indicates that there are supervisory events
Flashing in system, but some of them have not been
acknowledged.
This indicates that there are Ground Fault
Steady ON
events in system.
This indicates that there is no Ground Fault
Ground Fault Yellow OFF
event in system.
This indicates that there are ground fault
Flashing events in system, but some of them have not
been acknowledged.
The Audibles On LED can only be steady on
when any of the following conditions are met:
1. There are activated NACs and some of
Steady ON
them are not silenced.
Audibles On Red
2. There are silenceable devices activated
and some of them are not silenced.
The Audibles On LED will be OFF when above
OFF
conditions are not met.

The buzzer operates as follows:

Normally OFF – indicates that the system is in normal condition or all events in the system
have been acknowledged.
ON (200 pulse per minute) – indicates that at least ONE unacknowledged alarm is present in
the system.
ON (85 pulse per minute) – indicates that at least ONE unacknowledged non-alarm (trouble,
supervisory) event is present in the system.

59
The buttons operates as follows:

Silences all silenceable devices in system. This will cause all activated
Alarm Silence Press
silenceable devices to become silenced.

Acknowledge Press Acknowledges all unacknowledged events in system.

Clears all obsolete events and resets all devices, except those disabled ones
Reset Press
and hold-through-reset devices in system.

Unsilences all silenced devices in system. This will cause all silenced devices to
Unsilence Press
become activated.

Menu Press Menu button for PMI operation.

OK Press OK button for PMI operation.

C Press Cancel button for PMI operation.


Numeric buttons for PMI operation. They are used to enter the password to
access the maintenance and technician modes of the panel. It allows the user to
0-9 Press program the panel using these keypads without using the FX901-U2
programming tool.

* Press * button for PMI operation.

# Press # button for PMI operation.

Four-way button Press A four-way button for menu navigation.

60
LCD Display
The LCD operates as follows:

Line 1 – Index and Category of current selected event, User level, current time
Line 2 – Acknowledged status, Event Type
Line 3 – Customer text of the device associated with the event
Line 4 – Time when the event happened
Line 5~7 – Another event followed

The LCD can display two events at a time. User can cycle through a circular list once the first
event or last event message is reached.

Events are displayed according to the following rules:


1: Events priority:
Unacknowledged Alarm > Unacknowledged Supervisory > Unacknowledged Trouble >
Acknowledged Alarm > Acknowledged Supervisory > Acknowledged Trouble > Status > Test
2: Within events of the same priority, all events are displayed in the order of occurrence the
latest displayed the first.
3: Status events are displayed according to the event setting. If it is configured as “No display”,
it will not be listed in Event List.

When Supervisory is configured as Non-SelfRestoring, a Supervisory OUT Event will be


displayed in the event list when supervisory condition disappears. This also applies to Trouble
and Status.

61
APPENDIX-H: OUTPUT FEATURES
Output Activation- and Deactivation- Delays
Each output device has a selection for Activation delay and Deactivation delay when it is
installed in the configuration. The Activation delay refers to the delay in which the output will
activate after the reception of its activation command. If the Activation delay is set to 0 (default
setting), the output immediately activates. The Deactivation delay refers to the delay in which
the output will deactivate after the reception of its deactivation command. If the Deactivation
delay is set to 0 (default setting), the output immediately deactivates.

Output device during activation delay will not respond to deactivate command. This means an
output device with activation delay will definitely be activated after receiving activate command.
Output device during deactivation delay will respond to activate command immediately and the
deactivation delay will be cancelled.

Assuming an output channel on SLC is configured to be interlocked by supervisory condition of


FACP with ActivationDelay of 10s and Deactivation Delay of 10s. When FACP enters
supervisory condition at 00”00’, the output channel will be activated at 00”10’. Then if the
supervisory condition goes at 00”30’, the output channel will be deactivated at 00”40’.
On
On Activate
Deactivate
Command
Command

ON

Output State

OFF

Activation Deactivation
Delay Delay

NOTE This function only apply to IO module on SLC

62
APPENDIX-I: PAS / PRE-SIGNAL
PAS (Positive Alarm Sequence) and Pre-Signal features allow the user to delay the activation
of the audibles, strobes and other output devices when an initial alarm is detected. Output can
be interlocked by zones. When an initial alarm is detected, all outputs except remote devices
(off-premises devices like general relays and city tie) associated with PAS Zone (Zone
configured with PAS feature) will be activated immediately. When PAS delay timer elapses,
other remote devices will also be activated.The delay timers are configurable.

PAS
When an alarm causing device associated with a zone with PAS feature is initiated, the alarm
condition is reported on the panel. The activation of its related remote outputs (e.g. output
relays) are delayed for 15 seconds (PAS delay time) waiting for a manual acknowledgement
response.
If no response is received within 15 seconds, the panel proceeds to activate the associated
remote outputs. See Figure A.
If the alarm event is acknowledged during the PAS delay time, the programmable PAS
investigation time (60-180 seconds) is added to the PAS delay time before remote outputs are
activated. See Figure B.
However, if a 2nd alarm is initiated anytime during the PAS delay time or PAS investigation
time, the remote output devices are immediately activated. See Figure C.
Pressing the Reset button at anytime during the PAS sequence will initiate a reset condition
and restore the panel to stand-by state.

1st Alarm
Initiated

Panel
PAS Reset
Delay
time
Remote Figure A
devices ON 15s PAS Normal
Sequence
Remote
devices OFF

Alarm
Acknowledge Figure B
Remote
Investigation time
devices ON When Ack
before PAS
Remote delay time
devices OFF

2nd Alarm
Initiated

Remote Figure C
devices ON When 2nd
Alarm is
Remote Initiated
devices OFF

63
Pre-Signal
When an alarm causing device in a Pre-Signal input group is initiated, the alarm condition is
reported at the panel. Its associated NACs are not activated until the programmed
investigation delay has relapsed or 2nd Alarm is initiated anytime during the Pre-Signal delay
time (see figure below).

1st Alarm Panel


Initiated Reset

Figure A
Audible ON
Pre-Signal Delay time Pre-Signal
Normal
Sequence
Audible OFF

2nd Alarm
Initiated

Figure B
Audible ON
When 2nd
Alarm is
Initiated
Audible OFF

Pressing the reset button at anytime during the Pre-Signal sequence will initiate a reset
condition and restore the panel to stand-by state.

64
APPENDIX-J: DACT INFORMATION OVERVIEW
The DACT (Digital Alarm Communicator Transmitter) is an optional module for the FC901
control panel that allows transmission of event information to a remote receiver at a monitoring
station using a dial-up modem connection. These events are transmitted in one of the following
formats:
„ SIADCS 8
„ SIADCS 20
„ ADEMCO Contact ID
„ 4/2 1400 HZ
„ 3/1 1400 HZ
„ 3/1 2300 HZ
„ 4/2 2300 HZ
A few aspects of the operation of the DACT are clarified below.

Lines / Accounts
The DACT supports two independent lines and can report to two separate accounts. “Lines”
should not be confused with “accounts”. “Lines” are the actual telephone cords that plug into
the DACT module, which are in turn connected to the PSTN (Public Service Telephone
Network). If line 1 is not functioning (no dial tone, etc.), the DACT will try line 2 instead.
“Accounts” are the phone numbers that the DACT dials. Once the DACT has found a “live” line
to dial out on, it transmits the event(s) on that line, starting with the first account that is
configured to send that event. If the first account does not respond after the programmed
number of attempts (busy, account not responding, etc.), the DACT will automatically attempt
to send the event to the second account, providing the event is set to report for that account.
The DACT may be configured for connection to lines that are set up for Rotary and/or Tone
dialing. See the FC901 Programming Manual, P/N 315-0494033, for details.

Must / Can / Must Not


Each event type (Alarm, Alarm Restoral, etc.) can be configured as “Must”, “Can” or “Must Not”
report independently for each account. If configured as “Must Not” report, the DACT will not
report the event to that account. If configured as “Can” report, the DACT will only attempt to
report the event to the account if it has not reported it on the other account. If configured as
“Must” report, the DACT will attempt to report the event to the account even if it has already
reported it to the other account. In summary:

Must Report The event will be reported to this account even if it has reported it to the other
account.
Can Report The event will only report to this account if it has not been successfully
reported to the other account.
Must Not Report The event will never report to this account.

65
To configure an event to be reported to Account 1 and Account 2, set it to Must report on both.
If the event needs to be reported to either Account 1 or Account 2, set it to Can report on both.
If it has to be reported to Account 1, but only needs to be reported on Account 2 if Account 1 is
temporarily out-of-order, set the event to Must Report on Account 1 and Can Report on
Account 2.

Following are examples for illustration purposes.

Scenario 1 – Must/Must
Alarm Event is set to Must Report on Account 1 and 2.

Step 1:
Panel goes into alarm.

N Account 1
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
Account 2

Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.

Account 1
Step 4:
Panel switches to Account
2 and attempts to transmit,
but is unsuccessful too.
N Account 2

Step 5:
Panel keeps trying to send event to Account 2 until the programmed Number
Of Attempts has been reached.

Done.

Note: If both accounts failed to send an event within configured Number of Attempts, the event
will be discarded and a message lost condition will be declared on panel. This means the
panel will not try infinitely to send an event and each account can try at most (programmed
Number of Attempts) times. This applies to all Scenarios of DACT transmission.

66
Scenario 2 – Must/Can
Alarm Event is set to Must Report on Account 1 and Can
Report on Account 2. Panel fails on Account 1 the first
time.

Step 1:
Panel goes into alarm.

N Account 1
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
Account 2

Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.

Account 1
Step 4:
Panel switches to Account
2 and attempts to transmit,
but is unsuccessful too.
N Account 2

Step 5:
Panel keeps trying to send event to Account 2 until the programmed Number
Of Attempts has been reached.

Done.

67
68
Scenario 4 – Can/Can
Alarm Event is set to Can Report on Account 1 and
Account 2. Panel succeeds on Account 2 before Account
1.

Step 1:
Panel goes into alarm.

N Account 1
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
Account 2

Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.

Account 1
Step 4:
Panel switches to Account
2 and successfully
transmits the event.
Y Account 2

Done.

Note: The same sequence of events would happen if Account 2 was set to
Must Report.

69
APPENDIX-K: GLOSSARY
AC Power Fail. Refers to a condition in which AC power loss is detected by the system.

Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm
for fire from a manual station, a waterflow alarm, or an automatic smoke detector.

Alarm Silence Inhibit. An option that prevents an operator from silencing the notification
appliances for a preset period of time.

Alarm System. A combination of compatible initiating devices, control panels, and notification
appliances designed and installed to produce an alarm signal in the event of a fire.

Alarm Verification. A preset option that causes the control panel to verify alarms originated by
smoke detectors before indicating an alarm.

Annunciator. A remotely located, electrically powered display, separate from the control
panel, containing LEDs or lamps to indicate the states of the fire alarm system.

Audible Signal. An audible signal is a sound made by one or more audible notification
appliances, such as bells or horns, in response to the operation of an initiating device.

Auto-Silence. The capability of a control to automatically silence the notification appliances


after a preset period of time.

Class A Circuit. An initiating device or notification appliance circuit within which all
components remain fully functional, even though a single open or ground exists in the circuit.

Class B Circuit. An initiating device or notification appliance circuit within which some or all
components may be disabled with a single open exists in the circuit.

Detector - FirePrint™. An intelligent fire detector that blends photoelectric, thermal and neural
network technologies for superior protection without false alarms.

Detector - Smoke, Photoelectric Type. A detector employing the photoelectric principle of


reflection or obstruction of light by smoke.

Detector - Thermal Type. An addressable thermal sensor that is programmable as either a


fixed temperature (135° F) or as a rate of rise detector.

Enable / Disable. Refers to the state of individual circuits (inputs and outputs) or logic
functions regardless of the presence of its corresponding modules.

End Of Line (EOL). A device used to terminate a supervised circuit.

Ground Fault. A trouble condition in which a low resistance has been detected between the
system wiring and conduit ground.

Hold-Thru Reset Condition. Refers to a condition where the hold-thru reset output will remain
in its current state before and after the reset until the OFF time delay has elapsed. Initiation of

70
fan restart usage has higher priority than the OFF time delay and will therefore immediately
deactivate the hold-thru reset outputs.

Initiating Device. A manually or automatically operated device such as a manual pull station,
smoke detector, heat detector, waterflow switch or tamper switch.

Initiating Device Circuit (IDC). A circuit to which initiating devices are connected.

Labeled. Equipment or materials to which have been attached a label, symbol, or other
identifying mark of an organization acceptable to the authority having jurisdiction and
concerned with product evaluation, that maintains periodic inspection of the production of such
labeled equipment or materials. And by whose labeling the manufacturer indicates compliance
with appropriate standards or performance in a specified manner.

Listed. Equipment or materials included in a list published by an organization acceptable to


the authority having jurisdiction and concerned with product evaluation, that maintains periodic
inspection of production of listed equipment or materials. And whose listing states either that
the equipment or material meets appropriate standards or has been tested and found suitable
for use in a specified manner.

NEC. National Electrical Code also published as NFPA standard 70.

Notification Appliance. An electrically operated appliance used to indicate the system status
such as a bell, horn, strobe light or speaker.

Notification Appliance Circuit (NAC). A circuit to which notification appliances are


connected.

Power Supply. That portion of the fire alarm control panel, which provides the power needed
to operate all control panel modules, as well as that, needed to operate all electrically powered
initiating devices and all notification appliances.

Programming Tool. Refers to an external proprietary software package that allows the user to
program the panel (FXS360 for the FC901 panel).

Quick Test. A term pertaining to the test mode of the system, that automatically resets after a
service technician tests initiating devices.

Reset Condition. Condition in which the panel is forced to return to its normal state, usually
performed by pressing the “SYTEM RESET” button after all known events / conditions are
cleared.

Supervisory. A signal indicating the operation of a supervisory device.

Supervisory Device. A device that monitors the condition of a sprinkler system such as a
gate-valve switch, water-level switch, low pressure switch, low temperature switch or fire pump
monitor.

Trouble Signal. An audible signal indicating trouble of any nature, such as a circuit break or
ground, occurring in the device or wiring associated with a fire alarm signal.

71
Waterflow Switch. An assembly approved for service and so constructed and installed that
any flow of water from a sprinkler system equal to or greater than that from a single automatic
sprinkler head will result in activation of this switch and subsequent indication of an alarm
condition.

Zone. A designated area of a building. Commonly, zone, is interchanged with initiating device
circuit.

Serial interface circuit. Circuit connect to announciator.

Signaling line circuit. Circuit connect to field devices.

72
Beijing Siemens Cerberus Electronics Limited © 2011 Copyright by
No.1,Fengzhidonglu, Xibeiwang, HaiDian District, Beijing Siemens Cerberus Electronics Ltd.
Beijing, 100094, China Data and design subject to change without notice.
Tel: +10 6476 8806
Fax: +10 6476 8899

Document no. A6V10336754_a_en_-- Manual FC901


Edition 07.2011

You might also like