EE 340L - Experiment 6: Synchronous Generator - Operation With The Grid
EE 340L - Experiment 6: Synchronous Generator - Operation With The Grid
1. Power Input:
2. Main power switch:
3. Power Supply terminals
4. Operating Mode switch:
5. Function push-button:
6. Start/Stop push-button:
7. Command knob:
8. Liquid crystal display (LCD):
9. Command Input:
10. Shaft Encoder Outputs:
11. Analog Outputs
12. Thermistor Input:
13. USB port connector:
Figure 3: Synchronizing Module.
1. Input Power Terminals (to energize coil of the 3-phase Contactor)
2. Syn. Switch (to energize or de-energize coil of contactor A)
3. Remote control (another alternative to energize or de-energize coil of contactor)
4. Contact terminals (of the two power sources to be synchronized)
5. Lamps switch (toggle switch must be set to I (on) for the indicator lamps to be operational).
6. Synchronizing lamps (indicate the relative level of the voltage across the three corresponding
contact terminals. These are connected in parallel with the circuit breaker contacts).
Procedure:
a) Connect the equipment as shown in Figure 4 below. This circuit represents a
synchronous generator connected to an ac power network through a circuit
breaker (three-phase contactor).
b) Make sure that the main power switch on the Four-Quadrant Dynamometer/
Power Supply is set to the O (off) position, then connect its Power Input to an ac
power outlet. Connect the Power Input of the Data Acquisition and Control
Interface to a 24 V ac power supply. Turn the 24 V ac power supply on.
c) On the Synchronizing Module/Three-Phase Contactor, make sure that the Lamps
switch is set to the (I) position. This ensures that the synchronizing lamps on the
module are operational. Also make sure that the Sync. switch is set to the open
(O) position. This ensures that the synchronous generator is not connected to the
ac power network.
d) Turn on the Four-Quadrant Dynamometer/Power Supply, select dynamometer
operation, then under Function select CW rotation, start the prime mover, then
increase the speed parameter of the prime mover until it reaches 1790 rpm.
e) Turn On the 3-phase Power Supply slowly increase the DC voltage across the
generator field winding until the phase voltage of the generator (E2) is nearly
equal to that of the power supply (E1).
f) On the Synchronizing Module/Three-Phase Contactor, observe the synchronizing
lamps: If they are all flashing simultaneously in synchronism, then we have the
correct phase sequence. If not, this indicates that two of the 3 phases are
crossed. In this latter case, shut off the power supply, cross two of the phase of
the power supply, and start over.
g) In LVDAC-EMS, open the Oscilloscope, then make the appropriate settings in
order to observe the waveforms of the ac power network voltage ( E1) and the
synchronous generator voltage (E2). Select the ac power network voltage (input
E1) as the trigger source of the Oscilloscope. Take a snapshot and describe
briefly what you observed (home assignment).
h) In the Four-Quadrant Dynamometer/Power Supply window, increase the Speed
parameter of the prime mover slowly while watching the flashing rate of the
lamps until the generator speed reaches 1800 rpm. Then adjust the generator
field current until E1 ≈ E2. Make further necessary adjustments till the lamps
become all dark. Observe the waveforms of these voltages on the Oscilloscope,
and when these two voltages are equal in amplitude and in phase (that is when
the lamps go 100% dark) take a snapshot, then it is time to set the Sync. switch
on the Synchronizing Module/Three-Phase Contactor to the closed (I) position to
synchronize the generator to the network. Then note the active and reactive
power supplied by phase 1 of the generator.
P1 = …….. W
Q1 = ……. VAR
Fig. 4: Generator-power system synchronization.
30
40
50
60
70
b) Reactive power control
Adjust the Speed parameter of the prime mover backwards so that the generator active
power is as close as possible to 0 W. Then on the Synchronous Motor/Generator, vary
the setting of the Exciter knob in slow increments, and record the observed reactive
power, real power, and voltage phase voltage E2. Fill in the table below.
-30
-20
-10
10
20
30