TUGAS BESAR - Report

This document appears to be a report summarizing the results of a building lighting simulation conducted in DIALux. It includes descriptions of the site, building, and storey being modeled. Lighting calculations were performed for two light scenes - one for typical lighting and one to determine daylight factor. The results showed the average illuminance, minimum illuminance, maximum illuminance, and daylight factor for a classroom workplane met or exceeded targets. Locational details like Jakarta were provided for the daylight calculations.

Uploaded by

Anonymous Nite
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views29 pages

TUGAS BESAR - Report

This document appears to be a report summarizing the results of a building lighting simulation conducted in DIALux. It includes descriptions of the site, building, and storey being modeled. Lighting calculations were performed for two light scenes - one for typical lighting and one to determine daylight factor. The results showed the average illuminance, minimum illuminance, maximum illuminance, and daylight factor for a classroom workplane met or exceeded targets. Locational details like Jakarta were provided for the daylight calculations.

Uploaded by

Anonymous Nite
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

Date 12/10/2021

TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA


052001900077

Created with DIALux


TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Preliminary remarks

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.

The daylight was also taken into account for the calculations in the
course of this planning. The following parameters formed the basis
for the calculations:

Location: Jakarta
Zenith luminance: 5434 cd/m²
Pollution category: Medium to heavy traffic, dust exposure under 600
microgram/cubic metre
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Content

Cover page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .


Preliminary remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Site 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Site 1

Building 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Site 1 - Building 1

Storey 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calculation objects / Light scene for daylight factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 .............................

Site 1 - Building 1 - Storey 1

classroom
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 .............................
Summary / Light scene for daylight factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 .............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 .............................
Calculation objects / Light scene for daylight factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 .............................
Workplane (classroom) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . 21 .............................
Daylight factor effective area (classroom) / Light scene 1 / Daylight factor . . . . . . . . . . . . . . . . . . . . . . . . . . .22 .............................
Workplane (classroom) / Light scene for daylight factor / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23.............................
illuminance (adaptive)
Daylight factor effective area (classroom) / Light scene for daylight factor / . . . . . . . . . . . . . . . . . . . . . . . . . .24
.............................
Daylight factor

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
.............................
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Description

4
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Site 1
Description

5
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1
Description

6
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1
Description

7
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 (Light scene 1)


Calculation objects

8
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Work planes

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target)

Workplane (classroom) 223 lx 14.7 lx 788 lx 15.2 53.6 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.760 m, Wall zone: 0.000 m

Daylight

Properties Dm Dmin Dmax Ē/Emin Emax/Emin Index

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 9:00 AM (SE Asia Standard Time).

9
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 (Light scene for daylight factor)


Calculation objects

10
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 (Light scene for daylight factor)


Calculation objects

Work planes

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target)

Workplane (classroom) 312 lx 20.5 lx 1101 lx 15.2 53.7 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.760 m, Wall zone: 0.000 m

Daylight

Properties Dm Dmin Dmax Ē/Emin Emax/Emin Index

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 12:00 PM (SE Asia Standard Time).

11
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom


Description

12
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene 1)


Summary

Ground area: 54.45 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | 13
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Daylight D 1.892 % - - DF1

Workplane Ēperpendicular 223 lx ≥ 500 lx WP1

Ē/E min 15.2 - - WP1

Consumption values Consumption 0 kWh/a max. 50 kWh/a

Room Lighting power density 0.00 W/m² - -

0.00 W/m²/100 lx - -

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 9:00 AM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

14
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene for daylight factor)


Summary

Ground area: 54.45 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | 15
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene for daylight factor)


Summary

Results

Symbol Calculated Target Check Index

Daylight D 1.892 % - - DF1

Workplane Ēperpendicular 312 lx ≥ 500 lx WP1

Ē/E min 15.2 - - WP1

Consumption values Consumption 0 kWh/a max. 50 kWh/a

Room Lighting power density 0.00 W/m² - -

0.00 W/m²/100 lx - -

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 12:00 PM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

16
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene 1)


Calculation objects

17
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene 1)


Calculation objects

Work planes

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target)

Workplane (classroom) 223 lx 14.7 lx 788 lx 15.2 53.6 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.760 m, Wall zone: 0.000 m

Daylight

Properties Dm Dmin Dmax Ē/Emin Emax/Emin Index

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 9:00 AM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

18
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene for daylight factor)


Calculation objects

19
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene for daylight factor)


Calculation objects

Work planes

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target)

Workplane (classroom) 312 lx 20.5 lx 1101 lx 15.2 53.7 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.760 m, Wall zone: 0.000 m

Daylight

Properties Dm Dmin Dmax Ē/Emin Emax/Emin Index

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 12:00 PM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

20
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene 1)


Workplane (classroom)

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target)

Workplane (classroom) 223 lx 14.7 lx 788 lx 15.2 53.6 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.760 m, Wall zone: 0.000 m

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 9:00 AM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

21
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene 1)


Daylight factor effective area (classroom)

Properties Dm Dmin Dmax Ē/Emin Emax/Emin Index

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 9:00 AM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

22
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene for daylight factor)


Workplane (classroom)

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target)

Workplane (classroom) 312 lx 20.5 lx 1101 lx 15.2 53.7 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.760 m, Wall zone: 0.000 m

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 12:00 PM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

23
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Building 1 · Storey 1 · classroom (Light scene for daylight factor)


Daylight factor effective area (classroom)

Properties Dm Dmin Dmax Ē/Emin Emax/Emin Index

Daylight factor effective area (classroom) 1.892 % 0.537 % 4.636 % - - DF1


Daylight factor
Height: 0.850 m, Wall zone: 1.000 m

Utilisation profile: 24 - LIGHTING FOR EDUCATION, Classrooms; Arts, Art Studios

Notes on planning:
Daylight proportion for Overcast Sky on 6/21/2021 at 12:00 PM (SE Asia Standard Time). The ambient conditions for "classroom" are clean.

24
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464- 1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated color temperature) Body temperature of a thermal radiator that serves
to describe its light color. Unit: Kelvin [K]. The lesser the numerical value the redder; the
greater the numerical value the bluer the light color. The color temperature of gas-
discharge lamps and semi-conductors are termed "correlated color temperature" in
contrast to the color temperature of thermal radiators. Allocation of the light colors to
the color temperature ranges acc. to EN 12464-1: Light color - color temperature [K ]
warm white (ww) 5.300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

CRI (Engl. color rendering index) Designation for the color rendering index of a luminaire or
a lamp acc. to DIN 6169: 1976 or CIE 13.3: 1995. The general color rendering index Ra
(or CRI) is a dimensionless figure that describes the quality of a white light source in
regards to its similarity with the remission spectra of defined 8 test colors (see DIN 6169
or CIE 1974) to a reference light source.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky. Formula symbol:
D (Engl. daylight factor) Unit: %

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

25
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Glossary

Eta (η) (light output ratio) The light output ratio describes what percentage of the luminous flux
of a free radiating lamp (or LED module) is emitted by the luminaire when installed. Unit:
%

g1 Often also Uo (Engl. overall uniformity) Designates the overall uniformity of the
illuminance on a surface. It is the quotient from Emin to Ē and is required, for instance, in
standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be
determined anywhere in space (inside or outside). The illuminance is not a product
feature because it is a recipient value. Luxometers are used for measuring. Unit: Lux
Abbreviation: lx Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator) Lighting energy numeric indicator acc. to EN
15193 Unit: kWh/m² year

26
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Glossary

Light loss factor See MF

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005 Lamp flux maintenance
factor that takes the luminous flux reduction into account of a luminaire or an LED
module in the course of the operating time. The lamp flux maintenance factor is
specified as a decimal digit and can have a maximum value of 1 (no luminous flux
reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005 Luminaire maintenance factor
that takes the soiling into account of the luminaire in the course of the operating time.
The luminaire maintenance factor is specified as a decimal digit and can have a
maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005 Lamp survival factor that takes the total
failure into account of a luminaire in the course of the operating time. The lamp survival
factor is specified as a decimal digit and can have a maximum value of 1 (no failures
existing within the time concerned or prompt replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It
is the only photometric value that the human eye can perceive. Unit: Candela per square
meter Abbreviation: cd/m² Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W. This ratio can be formed for the lamp or LED module (lamp or module light
output), the lamp or module with control gear (system light output) and the complete
luminaire (luminaire light output).

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux. Unit: Lumen
Abbreviation: lm Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit. Unit: Candela
Abbreviation: cd Formula symbol: I

27
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Glossary

MF (Engl. maintenance factor)/acc. to CIE 97: 2005 Maintenance factor as decimal number
between 0 and 1 that describes the ratio of the new value of a photometric planning
parameter (e.g. of the illuminance) to a maintenance value after a certain time. The
maintenance factor takes into account the soiling of luminaires and rooms as well as the
luminous flux reduction and the failure of light sources. The maintenance factor is taken
into account either overall or determined in detail acc. to CIE 97: 2005 by the formula
RMF x LMF x LLMF x LSF.

P (Engl. power) Electric power consumption Unit: watt Abbreviation: W

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the color of the surface.

RMF (Engl. room maintenance factor)/acc. to CIE 97: 2005 Room maintenance factor that
takes the soiling into account of the space encompassing surfaces in the course of the
operating time. The room maintenance factor is specified as a decimal digit and can
have a maximum value of 1 (no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

UGR (max) (unified glare rating) Measure for the psychological glare effect in interiors. In addition to
luminaire luminance, the UGR value also depends on the position of the observer, the
viewing direction and the ambient luminance. Among other things, EN 12464-1 specifies
maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

28
TUGAS BESAR SIMULASI BANGUNAN 12PM - MUTHIA 052001900077

Glossary

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls that is not taken into account for
the calculation.

Workplane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.