Install & Service Manual - PBS16A
Install & Service Manual - PBS16A
SYSTEM PBS-16 A
The information in this manual is subject to change without notice and does not represent
a commitment on the part of WORMALD SIGNALCO A/S. Distributors will be updated
at regular intervals, but are responsible themselves for maintaining their own copies up-
dated. WORMALD SIGNALCO A/S makes no warranty of any kind with regard to this
document. Use, duplication, translation or disclosure is allowed at the responsibility of the
user.
SERVICING MANUAL
INSTALLATIONAM) PREFACE
PBS16 SYSEh4 PAGE (ii)
CONTENTS
SAFETY
INTRODUCTION
GENERAL DESCRIPTION
MODULE DESCRIPTIONS
CARD DESCRIPTIONS
INSTALLATION
COMMISSIONING
SERVICING
'APPEDICES
INDEX
INSTALLATION AND SERVICING UANUAL PREFACE
P S 1 6 SYSTEM PAGE (iii)
APPENDICES
Default Programme
Dip-switch Settings
Printer Connections
IF-16 Connections
Technical Specifications
Conditions of Sale
INDEX
INSTALLATION AND SERVICING MANUAL SAFEIY AND WARRANTTES
P S 1 6 SYSIB.4 PAGE 1
INSTALLATION
AND
SERVICING MANUAL
SAFETY
The PBS-16 system is powered by one or more charger units delivering 24V DC each with a
secondary voltage supply consisting of a bank of 24V batteries. The charger units are con-
nected to the mains and care must be taken when working with such a unit, disconnecting it
from the mains if necessary.
.. . There is no other part.of the PBS-16 system-thatisxun directly from the mains.Note that
. . .equipment controlled by the PBS-16 system may be powered directly from the mains, and
that this must be checked for the specific installation.
Please note that repairs or modifications to the equipment without written consent from
WORMALD SIGNALCO A/S invalidates the warranty.
CHAPTER ONE
INTRODUCTION
WARNING!
The modular construction enables the system to be engineered to suit individual installa-
tion requirements, while retaining its full range of facilities.
Because systems are individually engineered, the installation, commissioning and servicing
information given here must be supported by the installation drawings for installation and
commissioning, by the record drawings for servicing, and by other data for the particular
installation.
This manual gives, or gives reference to, all the information necessary for the installation,
commissioning and servicing of the PBS-16 Fire Alarm System.
It begins by defining three distinct sets of input conditions, followed by an outline descrip-
tion of the basic system, based on a block diagram, and introducing the PBS-16 module.
. . . . This is followed by an outline description of the remaining modules in the PBS-16 system,
with a block diagram showing their use in an expanded system.
All the above provides background information for the installation, commissioning and
. . . . . servicing information,.which follows.
Appendices give data on recommended input devices, and other reference data.
INSTALLATIONAND SERVICING MANUAL CHAPTER TWO: GENERAL DESCRIPTION
PBS-16S
Y
ST
E
M PAGE 4
CHAPTER TWO
GENERAL DESCRIPTION
CONTENTS
INPUT SYSTEMS
Conventional Detectors
Addressable Conventional (Digital) Detectors
Addressable Analogue Sensors
EXPANDED SYSTEM
ILLUSTRATIONS
Fig
CHAPTER TWO
GENERAL DESCRIPTION .
Three distinct systems of input devices are possible in the PBS-16 alarm system.
Manual Call Points (MCPs) and other hard-contact devices may be used with any of these
types.
It is not possible to mix lines and loops in the same system. Within the same system all
modules must either have loops connected to them or they must all have lines connected.
Different types of lines or loops cannot be mixed on the same module. However, PBS-16
and US-16 modules in the same system may have lines or loops of different types. Some
care must be taken when modules with different types of detection lines or loops are linked
together. The PS-16 controlling the whole system must have core software made for an
analogue system if any one of the modules in the system have loops or lines with analogue
sensors. Otherwise the PS-16 core software may be of the digital addressed type.
. The markings on theEPROMS indicate what type of loops or lines they are intended to .
work with, and also if they are for a loop or a line configuration. Please refer to Appendix
H for further detail on processor and EPROM markings.
. , . A Conventional Line is a pair of wires with detection devices connected across it. An
End
Of Line (EOL) device enables a 4.5 mA current to flow through the line, thus confirming
that it is not open circuit.
The operation of any device produces a short circuit, increasing the current flow through it
INSTALLATIONAND SERVICING MANUAL CHAPTER TWO: GENERAL DESCRIPTION
PBS-16 SYSTEM PAGE 6
. A Conventional Loop has both ends of the pair of wires connected to the Control Panel,
enabling monitoring from either end. This provides a safeguard against a break in the
wires. With each loop occupying two line inputs to. the Control Panel, only half as many
loops may be connected, as lines.
The Control Panel is able to distinguish between 4.5mA (quiescent), 20mA (alarm) and
. zero current (fault), but cannot identify the device within the line or loop.
Instead of detection devices being connected across the line or loop, address units are so
connected, and the detectors are connected to these.
The Control Panel addresses each unit in turn. When addressed, the address unit reports
its status.
In this system, the same three conditions are possible as in the Conventional system; that is,
a 4.5mA current pulse represents the quiescent condition, a 20mA pulse the alarm condi-
tion, and zero current, a fault condition. The significant difference is that the Control
Panel is able to identify the particular address initiating an alarm or fault condition.
One type of address unit has one detector associated with it. Other address units enable
one or more MCPs or other hard contact devices to be connected to one address unit, thus
forming a sub-zone. Any sub-zone has an EOL device to enable open circuit fault monitor-
ing. This EOL device is normally a resistor which is placed inside the furthermost unit on
the line connected to the address unit. Alarm or fault identification is only as far as the
address of the sub-zone. The Control Panel cannot detect which device within the sub-
zone produced the alarm or fault.
Instead of detectors being connected across the line or loop, address units are so con-
nected, and analogue sensors are connected to them.
An analogue sensor provides an output that is a function of the value of the parameter
being monitored. It does not have a changeover between quiescent and alarm conditions.
That threshold is provided by the Control Panel, where its value is preset, and compensa-
tion is made for ageing effects of the sensor, thus reducing the number of false alarms from
this cause. When compensation limits are reached, a fault condition, rather than an alarm
condition, is produced by the Control Panel.
INSTALLATIONAND SERVICING MANUAL CHAPTER TWO: GENERAL DESCRIPTION
PBS-16
SYSI'EM PAGE 7
The Control Panel addresses each unit in turn. When addressed, each unit reports its
status.
One type of address unit has one analogue sensor associated with it.
The address unit has only two current levels: zero for a fault condition and 20mA for moni-
toring. The 20 mA current pulse is of variable duration, the duration being a measure of
the analogue value of the parameter-being measured by the sensor.
Interpretation of the analogue value into quiescent or alarm condition is a function of the
Control Panel.
Other types of address unit enable MCPs and other hard contact devices to be connected
to the line or loop. Several hard contact devices may be connected to the same address
unit, thus forming a sub-zone. This zone is monitored for open circuit by including an EOL
resistor in the device connected furthest away from the address unit.
The basic system has a number of detectors or sensors connected to each of a number of
inputs to the PBS-16 module. Equipment intended for operation if there is a fire alarm is
connected to output relays fitted in the PBS-16 module.
(a) A PS-16 Information and Control Panel, which carries displays and a keypad,
enabling operator control of the system, and providing information to the
operator.
(b) A US-16 Control and Monitor Unit, which contains the data collection, data
processing and output equipment.
The PS-16 module is microprocessor-based, and operates under the control of a predeter-
mined programme. It continuously checks the keypad for any input from an operator, and
guides the operator by using the Message Display while a function is being entered. When
the function is correctly entered it processes the request made by the operator. It displays
. , requested data in the Message Display and passes.on required data to the other modules.
The PS-16 module also interrogates each US-16 module in the system at regular intervals
to ensure that the communication between the various modules functions properly. The
PS-16 module also displays all alarms and fault messages received from other modules.
The module continuously scans each line or loop in turn, and within each line or loop,
monitors the output of each detector or sensor for a normal return, a fault condition or an
alarm condition. It also monitors the Control Panel for any keypad input from an operator,
and runs a self-test programme. Each cycle of operations is completed in approximately
two seconds.
So long as normal conditions are maintained, there is no output from the Control Panel.
INSTALLATIONAND SERVICING MANUAL CHAPTERTWO: GENERAL DESCRIPTION
PBS-16 SYSTEM PAGE 8
2.2.1 Inputs
Inputs may be address units associated with addressable sensors or detectors, or from
conventional detectors. In each case, each device is connected across a pair of wires.
There may be up to 32 conventional detectors connected across one pair of wires, or 96
addressable sensors or detectors.
If one end of.the pair of wires is connected to the PBS-16 module, and the other end termi-
nated, the pair of wires' is called a Line: There may be up to 16 lines connected to the
module, allowing up to 96 X 16 = 1536 sensors.
If both ends of the pair of wires connect to the module, the pair of wires is called a Loop.
Up to eight loops may be connected, allowing up to 768 sensors.
Each line or loop is identified by a two-digit address, using numbers consecutively from 01
upwards. .The loop or line number is derived from the address of the US-16 it is connected
to. Each address unit in a line or loop is similarly identified, from 01 up to 96. Thus each
address unit (and consequently, each sensor) has an unique four-digit address consisting of
the Line/loop address followed by its own two-digit number.
The PBS-16 module scans each address in turn, monitoring the condition of the associated
sensor. Analogue values are fed through an analogue to digital converter in the Control
Panel before being processed further. The module also monitors the Control Panel keypad
to determine if it is being used, and monitors the auxiliary inputs. Also the com bus is
continuously monitored for fault or input from other modules connected in the system.
From its own stored reference data, the module is able to determine if each sensor is in its
normal state, in a fault condition, or in an alarm condition.
For the normal condition of the sensors, the data processing produces no outputs, but if
one sensor shows an abnormal condition on two successive scans, then outputs are pro-
duced.
For a fire alarm condition, an output provides data to the displays; data is stored, and if a
printer is connected to then-system, the data is printed out;:Separately, according to the
reference data for the particular sensor, other selected outputs are provided. The refer-
ence data is contained in the customised Cause and Effect programme, or in its absence, in
the default programme.
INSTALLATION AND SERVICING MANUAL CHAPTERTWO : GENERAL DESCRIPTION
PBS-16SYSTEM PAGE 9
. Output relays are fitted in the PBS-16 module to provide control of external equipment,
and a selection of these relays is operated by the processor, when it responds to an alarm
condition.
. . This external equipment is special-to-installation. It will include alarm sounders, and may
, include such items as quenching systems, plant shut-down equipment, extended alarm to . .
Data and control outputs are provided onto a data bus which connects to other modules
that may be included in the system.
Two further (optional) data buses enables-the connection of other systems: a computer-
..ggraphics, text and printer package; a BMS system; a portable computer interface pro-
gramme (PBSVIEW).
. Figure 2.1 gives an overview of the inputs and outputs available in the basic PBS-16 system,
while figure 2.6 indicates a few possibilities in an extended system.
The Information and Control Panel (the PS-16 module) is included in the PBS-16 module.
Data is provided to the panel: .the data accesses a standard message programme and a
customised message programme (carried on an EPROM onthe-:panel). These pro-
grammes provide appropriate messages for display. The keypad fitted is monitored by the
processor.
. . . A number of functions are available to the operator or service engineer by use of the key-
pad. Most of these functions require the use of an access code. Control is interactive, since
. the microprocessor uses the displays to respond (prompting the operator to provide data
needed to carry out the function), and to display data requested.
Since conventional detectors cannot be monitored individually, the PBS-16 system is lim-
ited to the knowledge of which line or loop is signalling an alarm. Thus, each line or loop
, is, in effect, a zone:: The basic system permits eight loops or 16 lines, but this can be in- .
creased significantly by the addition of extension modules to the system, so that the system
can include a large number of small zones. For each zone, a relevant text message is dis-
played, and for each zone, a customised programme selects which output relays are oper-
ated by an alarm from that zone.
For an expanded system, a number of modules are available, in addition to the PBS-16
module. They are linked by an internal communications data bus, which permits up to
.
.
. INSTALLATION AND SERVICING MANUAL CHAPTER TWO: GENERAL DESCRIPTION
PBS-16SYSTEM PAGE 10
Each module operates Gom a 24V DC supply, which is fed via a PBS-16 or a US-16 module
from either a centralised or a local supply.
I
PS-16 I
INFORMATION AND I
CONTROL PANEL I
DISPLAY
I
MAINS MONITORING .
PBS-16 MODULE
0 0 0' 0 0 0
LOOP TO CONTROL PANEL
MAXIMUM 32 DETECTORS.
. I
0 0 0 0 0 0
Hard-contact devices (MCP's, door switches, etc) may be any normally-open type.
. .
NID58
,.-' I- ,- .-
2KC
TCA-70-LS
Address unit
with Nittan
detector. EOL
Sub-zone
with EOL
resistor fitted
in the last
device
connected.
AX-87D is an Address Unit (ADU) for use with one or more hard-contact devices (MCP's,
door switches, etc). With more than one device, they constitute a sub-zone. The AX-87D
always requires an EOL resistor to be fitted in the last device connected on the line
branching off from it.
3RB6D is an ADU for use with the same range of detectors as the AX-87D.
+O . ...
LINE TO CONTROL PANEL.
MAXIMUM 96 ADDRESS ADU ADU ADU
UNITS.
t
I I
KR62 0 0
0
MCP I
I
BRK 1800C
.
BRK 2800EC
BRK 5850EC
Sub-zone
with EOL
resistor fitted
in the last
device
connected.
AX-87D is an Address Unit (ADU) for use with one or more .hard-contact devices (MCP's,
door switches, etc). With more than one device, they constitute a sub-zone. The AX-87D
always requires an EOL resistor to be fitted in the last device connected on the Line
branching off from it.
Nittan NID58F,
2KC,
TCA-70-LS
B201D is an ADU for use with the BRK 1800EC, 2800EC and 5850EC detectors.
. ,.. . ..
LINE TO CONIROL PANEL +O
MAXIMUM % ADDRESS ADU ADU ADU
UNITS
I I
KR62
0 0
0
MCP
AW Range of
detectors
Sub-zone.
with EOL
resistor fined
in the last
device
connected.
AX-87AD is an Address Unit (ADU) for use with 'one or more .hard-contact devices
(MCP's, door switches, etc). With more than one device, they constitute a sub-zone. The
AX-87AD always requires an EOL resistor to be fitted in the last device connected on the
line branching off from it.
. . . . . .
8 DETECTIONLOOPS
OR 16DETECTIONLINES.
TO 2.5)
(SEE FIGS 2.2
CONTROL
AND 3 CONTROL RELAY OUTPUTS
MONITOR
UNIT
3 x 24V DC, 1A OUTPUTS
RS-232C, 20mA LOOP OR RS-485 FOR CONNECTION US-16
OF A PC OR OTHER PBS-16SYSTEMS.(Only available
whena COM-16 cardis fitted).
COMMON FAULT RELAY
RS-232C PORT (USUALLY USED FOR PRINTER).
(Onlyavailablewhen a COM-16 cardis fitted).
MAINS IN
EARTH CONNECTION
L. . .
BATTERY
RELAYSLAVE
Unit. UP TO 56OUTPUTS DEPENDING ON
ANY ONE OF WHICH RS-UNIT IS C
O
NN
E
CT
E
D
RS-16, RS-32 OR
The internal communicationbus is linked through modules connected.l h e links RS 56.
arebrokenin master PBS-16 Up to 15modules (including PBS-16) may be . .
p countsas
connected. Each unitcontaininga l o ocard one module. SRP-16 is
not included when calculatingnumber ofmodulesbut it mustbe included when
the totalload on the communicationbus is considered. Each module connected
draws approximately1.5mA (PBS-16 module draws 2.5mA). The totalload
should not e x e e d27mA.
24VDC INPUT
MIMIC PANEL
MADE OF LOOP CARD
PLACED ON IF-16
24V DC INPUT UP TO 240 LEDS CAN BE
CONTROL Four RS-units may be CONTROLLED BY ONE LOOP
AND connectedto the loopcard. CARD. (Max. 4 X RS-56 in addition
MONITORING to the loop cardsown 16 outputs). If
INPUTSAND OUTPUTSAS FOR
UNIT more outputs are required a second
Imp cardmust be added. Each Imp
U S - 1INCLUDED
6 W PBS-16 US16 card counts as one module.
I
RELAY SLAVE L
SRP-l6
UP TO 56 OUTPUTS DEPENDING ON UNIT. REPEATER 24V DC WPUT
WHICH RS-UNITIS CONNECTED ANY ONE OF PANEL
RS-16, RS-32 OR
RS-56.
I-
+ 24V DC INPUT
MASTER MASTER
RELAY RELAY
UNIT UNIT 16 SEPERATELY PROGRAMABLE
R E L AO
YU TPUTS
16 SEPERATELYPROGRAMABLE RU-16 RU-16
RELAY OUTPUTS
16ANALOGUE I N P U T E
SACH
TREATED AS A LOOP
I I
UP TO 224 OUTPUTSDEPENDING ON
HOW MANYAND WHICH TYPE OF
RELAY SLAVE
I RELAY SLAVE
UP TO FOUR
UP TO W OUTPUTS DEPENDING OH
HOW M A N AND WHICH TYPE O F
Y
RS-UNITSARE CONNECTED
RS-16,RS-32ORRS-56 I RS-16, RS-32OR RS-UNITS ARE CONNECTED
. CHAPTER THREE
MODULE DESCRIPTIONS
CONTENTS
3.1 PBS-16
ILLUSTRATIONS
Fig
CHAPTER THREE
The modules of the PBS-16 system are listed here, with a brief description of each.
This carries all the lamps and displays giving information to the operator, and a keypad
that enables him to control and operate the system. A customisedEPROM, carrying the
text message appropriate to each address, is located at the back of the PS-16's printed
circuit board. This customised text is displayed on the second line of the Message Display.
It is displayed in addition to the normal first line text for fire or fault.
. The PS-16 controls and supervises the internal communication bus. This data bus is used
,
for communication with all US-16 modules in the system, including the one the PS-16 is
connected to. The internal data bus goes through the 40-way ribbon cable, and terminals
are provided on the US-16 module for connection of other units to this data bus.
The PS-16 also controls the two communication channels on the COM-16 Communication
Card if such a card is present on the US-16 the PS-16 is connected to.
If no COM-16 Communication Card is used in the system the PS-16 card can be mounted
remote from the US-16 it belongs to. It is then just connected to 24V DC and the internal
communication bus. If there is a Communication Card on the US-16 motherboard the PS-
16 ribbon cable must be plugged into the P1 connector. The ribbon cable can be extended,
.
but the maximum total length is 2 metres when a Communication Card is used:
This unit consists of a Loop Card and a motherboard. The processor on the Loop Card
operates independently of other processors in the system, but is programmed to act upon
input received on the internal communication loop from the PS-16 control panel or other
modules connected to the com bus.
. ' INSTALLATION AND SERVICING MANUAL CHAPTER THREE: MODULE DESCRIPTIONS
PBS-16SYSTEM PAGE 18
. The US-16 is a data collection, processingand output unit. It is used in conjunction with
the PS-16 module, as part of the PBS-16 module. It receives inputs from the lines or loops
of sensors and from three auxiliary inputs. In addition it receives input on the internal
communication bus from the operator's keypad on the PS-16 module or other units con-
nected to the combus. It provides outputs to the lamps and displays on the PS-16 module,
to its own alarm buzzer, and to output relays. It connects to an internal data bus, enabling
communication with up to 1 4other modules of the PBS-16 system.. By the addition of a
Comms Card, it provides an external RS232C data bus connection to an optional computer
text, graphics and printer package. A Communication Card may only be added to a US-16
module that has a PS-16 module directly connected to it. This is because the Communica-
tion Card is controlled by the PS-16 module through the 40-way ribbon cable.
. A number (up to 14) of the US-16 modules may be used without the PS-16 module, as
. . ... .extension units in the system, permitting the connection of further complete sets of inputs
and outputs to the system.
Each unit has its own unique address on the internal communication bus. This address
should be between 1 and 15 and is set by a 4-pole dip-switch located on the US-16 mother-
board. The addresses selected for US-16 modules must run consecutively from 1 up to the
number of US-16 modules connected. All US-16 connected to the com bus must have a
.. lower address than other type of units connected. No holes are allowed in the address .
range on the com bus.
The loop or line number of the detection circuits connected t o an US-l6 is determined by
considering the address of the module on the data bus,the type of detectioncircuits in the .
system (lines or loops), and finally the number of the detection input the line or loop is
connected to. -Appendix I gives information on which loop or line numbers corresponds to
the different addresses on the communication bus.
Each US-16 module may carry a customised Cause and Effect EPROM (on the Loop
Card). This determines which outputs are operated by each alarm. In default of this
. . . INSTALLATION AND SERVICING MANUAL CHAPTER THREE MODULE DESCRIPTIONS
PBS-16SYSTEM PAGE 19
EPROM being fitted, the permanent built-in Default programme is operative. Data on the
. ... Default programme is given in Appendix A. Data on the customised programme is given
.
in Part 2 of the Operator's Manual.
This provides a remote repeat of the displays on the PS-16 module. It is connected to the
internal communication bus and acts on the messages transmitted on this data bus. The
SW-16 has no specific address on the com bus, but the load on the communication bus by
connecting it must be considered. It has a 2 X 40 character Message Display and two LEDs.
. In addition it has four buttons, a buzzer and contacts for fault and fire alarms. It also has a
dip-switch which determines the function of the silence key, determines if a global reset
from the SW-16 is allowed, and determines the function of relay 2 which is the fault con-
tact.
How to operate the SRP-16 and how to configure it with the DIP-switch is explained in
Appendix L.
Upon a fault or fire alarm being signalled on the internal communication loop the SRP-16 .
display the appropriate alarm message in the 2x40 character Message Display. It also starts
flashing its yellow or red LEDs depending on the type of alarm received. When a fire
alarm is accepted by pressing 'Silence' the red LEDs change from flashing to steady on.
A EPROM containing customised text similar to the one placed on the back of the PS-16
module may also be fitted at the back of the SRP-16 PCB. This EPROM may be identical
to the one included on the PS-16. In this case the second line text on the SRP-16 is identi-
. cal to the one shown on the PS-16 panel. This is not a must and the EPROM may be
programmed to give different messages on the second line from the ones displayed on the
second line on the PS-16 Message Display.
Cause and Effect of the SRP-16 is possible, but is limited to turning on the two relays upon
fire from specific addresses. The relays may only be turned off upon a system reset.
. .. .. . ... . .This carries 16 programmable relays and can support four Relay Slave Units. The RU-16
consists of a Loop Card and a motherboard. The Loop Card controls the relays on the
motherboard as well as the outputs provided by relay slave units connected to the RU-16.
The motherboard provides, in addition to the slot for the Loop Card, connection terminals
for the internal communication-bus, 16 output relays,--and for four-relay slave units.
The Loop Card in the RU-16 can control up to 240 outputs with four RS-56 units con-
nected. The processor on the Loop Card operates independently of the other processors in
the system, but it acts upon messages received on the internal communication loop from
the PS-16 control module or other modules connected to the com bus.
' ' INSTALLATION AND SERVICING MANUAL CHAPTER THREE MODULE DESCRIPTIONS
P S 1 6 SYSTEA4 PAGE 20
Each RU-16 must have a unique address on the communication bus. The address is set in
a special Cause and Effect program since the RU-16 does not have a dip-switch for this
purpose. This is one of the reasons why the Loop Card fitted in the RU-16 always must
have a Cause and Effect EPROM fitted. The address of the RU-16s in the system must
always be higher than any US-16 modules connected to-the internal communication bus.
The addresses should run consecutively from the first available address on the corn bus.
This is the same as the RU-16 except that the motherboard has terminals for connection of
16.analogue inputs and 24VDC output. The .l6 analogue inputs are protected and accepts
input currents between 0 and 50 rnA, producing a voltage across the 100 ohm measuring
resistor between OV and 5V. Each input is addressed as if it were a line or loop and has a 6
bit resolution. This means that current changes as small as 0.8 mA (80 mV) may be de-
tected.
The RU-161 also has two switches which physically disconnects the two blocks of eight
relays on the motherboard. Two red LEDs are also included, and they light up when the
corresponding switch isolating a block of relays is operated.
Note-that the two LEDs is the only warning given that one or both switches have been
operated. No fault warning will be displayed .on the Control Panelif these switches are
operated leaving all or part of the output relays inoperable.
These carry 16,32, and 56 individually addressable outputs and connect to the RU-16
Master Relay Unit, the RU-161 or the US-16 module. The RS-16 have 16 relay outputs
while the two other RS-Units have current driver outputs. The RS-Units are operated and
controlled by the Loop Cards included in the units they are connected to. The function of
each output must be specified in the Cause and Effect EPROM included on the Loop Card
controlling them.
The US-16 module can support any one of these units, while the RU-16.and RU-161 can
each support four of these units. Different types of Relay Slave units may be connected to
. . the same RU-l6 or.RU-161,but this requires extra care and planning during programming
and testing. See Appendix K.
A Loop Card carrying the same core software as is used to control the RU-16 or RU-161
may be placed on a PCB called IF-16. This unit may be used as a mimic driver. Up to four
RS-Units may be connected to it. The RS-Unit's outputs are controlled by the Loop Card.
With four RS-56 cards connected the Loop Card is able to drive up to 240 LEDs. More
\ Loop Cards placed on IF-16s may be added if more outputs are required. Each Loop Card
i
INSTALLATION AND SERVICING ~ w A L m R T H R E E MODULE DESCRIPTIONS
P S 1 6 SY!XJ34 PAGE 21
Each module consisting of a Loop Card and an IF-16 must have its own unique address on
the internal communication bus. The address is set in the Cause and Effect eprom as for
the RU-16 and RU-161. .The address must be selected so.that no US-16 has a higher ad-
dress number, and so that there are no gaps in thenaddresssequence on the com bus.
The IF-16 also provides connection terminals for three digital auxiliary inputs, (input On =
5V; input Off = OV),.and 16 analogue inputs. These inputs are not noise or over-voltage
:
protected and special care must be taken when they are used. (See Appendix J.) The
digital or analogue inputs are, apart from lack of protection, identical to the digital inputs
on the US-16 (Aux. Inputs) or the analogue inputs on the RU-161. These inputs are in
Cause and Effect treated in exactly the same way as the corresponding US-16 and RU-16
inputs.
In addition the IF-16 provides an output terminal for an external buzzer. When the IF-16
is used with a Loop Card the 3 straps must be fitted (see fig. 3.1). These straps enable the
5V regulator that is included on the IF-16 card. The straps must be removed if a RS-56 is
placed on the IF-16.
The BRP-16 panel is designed as a result of special requirements put forward by approvals
. bodies in Norway .and Sweden.. The panel is meant to provide the fire brigade with a stan-
dard interface to fire alarm systems. The fire brigade has no need to know how to operate
a specific Fire Alarm Panel, since the system can be operated from the BRP-16 connected.
Fire Alarm Panels produced by different manufacturers have the same user interface. The
panels look alike, they have.the same keys .and.indicators.and they are operated in the .
same way.
The BRP-16 module is connected to the internal communication bus, but it does not have
its own address on the bus. It is therefore not included when the number of modules con-
nected is counted. But it must be included when considering the total load connected to the
com bus.
, . . , .,. .
- . INSTALLATION AND SERVICING MANUAL CHAPTER THREE: MODULE DESCRIPTIONS
P S 1 6 SYSI'Eh4 PAGE 22
Two versions of the panel exists. One version has a 2 X 40 character Message Display
, .. . similar to the PS-16 Message Display. The other version has a four-digit seven-segment
Address Display fitted instead of the Message Display. The Address Display is similar to
the one included on the PS-16.
The panel has a lock and three keys which are.used.tooperatethe panel. The BRP-16 can
only be operated after it has been unlocked by using a special Fire Brigade key. The panel
also has a number of LEDs that indicate the system status.
1;. '-:.INSTALLATION AND SERVICING MANUAL . CHAPTER FOUR: CARD DESCRIPTIONS
P S 1 6 SYSTEM PAGE W
CHAPTER FOUR
CARD DESCRIPTIONS
CONTENTS
CHAPTER FOUR
CARD DESCRIPTIONS
This chapter describes some of the electronic cards used in the PBS-16 system.
The Loop Card is a plug-in card containing a microprocessor, memory and a number of
input and output channels. The card is used to control US-16, RU-16 and RU-161 modules
as well as Mimic Panels. .The US-16, RU-16 and RU-161 each have a slot reserved for the
Loop Card. In Mimic Panels the Loop Card is normally used together with the IF-16 card
which provides a plug-in slot and connection terminals.
The Loop Card's microprocessor have an internal EPROM which carries the main soft-
ware programme. There is two main types of..core:software .(main.softwareprogramme):
The markings on the processor indicates what type of software is included in it. Refer to
Appendix H for information on Loop Card microprocessor markings.
The Loop Card has the following input and output capabilities:
Which of these input and output lines are available and what they are used for depends on
the type of core software fitted, and which type of module it is used with.
The Loop Card also has a socket marked V4 which is reserved fora special Cause and
Effect programme. The Cause and Effect programme may modify the Loop Card's re-
sponse to fire alarms, fault messages, local inputs or messages it receives via the internal
communication bus. A Cause and Effect programme is usually included to meet special
requests put forward by the customer. The function of the Cause and Effect fitted on Loop
Cards in a specific system is specified in the Operator's Manual Part 2.
... ,..
.' INSTALLATION AND SERVICING MANUAL CHAFTER FOUR: CARD DESCRVITONS
PS16S Y m PAGE 25
A Loop Card used in a PBS-16 or US-16 module does not need to have a Cause and Effect
programme fitted to operate. The general rule is that all Loop Cards controlling Relay
Units or modules with RS-Units connected require a Cause and Effect EPROM.
L The COM-16 card is a plug-in card. A slot is provided on the US-16 motherboard for the
ainsertion of a COM-16 card. This slot may only be used if a PS-16 module is directly con-
nected to the motherboard. Hence, the COM-16 card may only be used with the PBS-16
module. The reason for this is that the Com-16 card is actually controlled by the micro-
processor included on the PS-16 card. The control signals are passed from the PS-16 mod-
ule to the COM-16 card through the 40-way ribbon cable. The PS-16 module must be
connected to the motherboard through the ribbon cable and the maximum total length of
the ribbon cable allowed is 2 metres.
.-.. ..The most common reason for including a COM-16 card is that a printer is required in the
- system.. Other reasons is that communication with other peripheral equipment or other
PBS-16 systems is necessary.
The COM-16 card provides two communication ports. Port one is always configured as
RS-232C. Port two may be configured as:
RS-232C,
RS-485,
or 20 rnA current loop.
The communication speed (Baud rate), and the configuration of port two is selected by
using the three DIP-switches included on the card. Appendix E explains how to set up the
Communication Card.
Since the Communication Card is controlled by the PS-16 module will the PS-16 core
software determine which port configurations may be used for port two and what informa-
tion is sent to the two ports. The Baud Rates selected for the ports are dependent.on the
equipment connected.
The IF-16 card is used as an interface card for the PBS16SA Loop Card and the RS-56
Output Driver Card. It consists of a slot for. plugging in a.Loop Card or a RS-56 and two
wire terminal blocks. It -also-has a 5VDC regulator.:which.isrenabledwhen the straps di-
rectly above connection terminal X1 is included.
The 5VDC regulator must be enabled when it is used with a Loop Card since the Loop
Card does not have its own 5V regulator. The straps enabling the 5VDC regulator must be
removed before it is used with a RS-56.
. .
: ' "C I .INSTALLATIONAND SERVICING MANUAL CHAPER FOUR: CARD DESCRIF'TIONS
P S 1 6 SYSTEM PAGE 26
Appendix J shows which function each of the connection terminals have when the IF-16 is
used with the Loop Card or the RS-56.
This is a Relay Slave Unit or .Relay Expansion Unit. - It has 56 switchable 24VDC outputs.
The RS-56 card is similar in size and shape to the PBS16SA Loop Card, and it is usually .
:-..usedtogether with the IF-16 Interface Card.
The IF-16's 5VDC regulator must be disabled when used together with the RS-56. The
.:-.. -: regulator is disabled when the three strapslocated directly above terminal block X1 is cut
or not fitted at all.
.The RS-56 has no microprocessor itself, and is always used together with a Loop Card
B -. which controls the 56 outputs. How many RS-56 can be controlled by a single Loop Card is
I dependent on the type of core software included in its microprocessor. A Loop Card in a
US-16 may only control one RS-56 while a Loop Card fitted with RU-16 software may
control up to four RS-56. The combination of one Loop Card and four RS-56 gives a
maximum of 240 outputs that can be controlled by a single Loop Card.
. , ,, The RS-32 has 32 red LEDs. The outputs are controlled by the processor on a Loop Card.
The RS-32 is normally used together with the PBS-16 module to give zone indication for
. . ..firealarms in the system. It is then connected to the terminals provided on the US-16
motherboard for the connection of a RS-Unit.
In some countries it is mandatory that a RS-32 is included with the PBS-16 module to give
zone indication.
The RS-32 may also be connected to Relay Units or Loop Cards placed on IF-16 Interface
Cards.
. .. .. . ...
. .i . - . ;':' FKIXLLAT'ION AND SERVICING MANUAL CHAPTER FIVE: INSTALLATION
PBSl6 SYSTEM PAGE 27
CHAPTER FlVE
INSTALLATION
5.1 GENERAL
5.1.1 Mechanical Installation
5.1.2 . . Electrical Installation
5.3 INPUTS
5.3.1 Short Circuit Isolators
5.3.2 Conventional Detectors
5.3.3 Addressable Sensors
5.3.3.1 AnalogueSystem
5.3.3.2 Digital System
5.3.4 Auxiliary Inputs
5.4 OUTPUTS
5.4.1 Sounders
5.4.2 Control Relay Outputs And The Fault Alarm Relay
5.4.3 24V DC Outputs
5.4.4 Fault Output (Total Power Failure)
5.4.5 RS Unit Connections
TABLES
Table
Power supplies to a PBS-16 system may be centralised or distributed. That is, there may be
one Charger Unit and battery supplying one PBS-16 module with 24V DC, from which all
other modules are supplied (centralised), or each'PBS-16 aid .US-16 module may have its . .
. own Charger Unit and battery (distributed); and distribute.:its.supplyto other local mod-.
ules.
CAUTION!
At the Installation stage, although cables must be run to the mains supply and correctly
terminated, they must remain isolated from the supply.. Wiring must be taken to the 24V ..
DC batteries and terminated correctly for the batteries, but -the connections to the batteries
must not be made. There must be no way in which mains or battery.co~ectionscould be
made accidentally.
The 24V DC supply wiring from the Charger Unit goes to a PBS-16 or US-16 module and
is distributed from there to other modules. Although the wiring is to be installed and
correctly terminated, the connections into modules from the PBS-16 or US-16 are not to be
made. Instead, they are to be temporarily insulated. .
Where the 24V DC supply cables are connected (that is, battery cable into Charger Unit,
battery supply cable between Charger Unit and PBS-16 or US-16, mains-derived 24V DC
supply cable between Charger Unit and PBS-16 or US-16), great care must be taken to
ensure that the correct polarity is observed. There can be no reverse polarity protection,
and damage can result from a reversed connection.
. - r. : :. A PBS-16 or US-16 that isconnected to a Charger Unit monitors the supply. Other PBS-16 .
and US-16 modules are to have their monitoring disabled. .
(a) On the motherboard of the PBS-16 or US-16, remove the test load PTC resis-
. tors R52 and R71. These two resistors are located directly below relay W.
5.3 INPUTS
Any one PBS-16 or US-16 module may have lines or loops of conventional detectors con-
nected to it, or it may have lines or loops of addressable sensors connected to it. It may not
have both. However, within one system, one PBS-16 or.US-16 mayihave conventional . .
NOTE: . All line and loop wiring is polarised and must be kept floating with respect to
,.. the power supply and system earth.
A line has one end of its pair of wires connected to terminal block X3 on the PBS-16 or
;: US-16. : The line length is limited to 1000 metres maximum. That -is,lOOOm for each of the
: wires in the pair.. Or .in other .words a maximum of 1000 metres from, say, the positive
. . terminal on the US-16 module to the positive terminal on the device furthest away from
A loop has both ends of the pair of wires connected to the terminal block X3. The loop
a length is limited to 1000 metres. That is, 1000 metres for each wire in the pair of wires. Or
in other words, a maximum of 1000 metres from, say, the positive terminal on one end of
the loop to the positive terminal on the other end of the loop. Connections are as shown in .
Table 5.3.
Up to a maximum of three short circuit isolators may be installed in any loop. These divide
the loop up into four sections, and have the effect of limiting the number of detectors or
. sensors put out of service by a short circuit on the loop.
This unit has connection terminals for connection of an LED which operates when the
units reacts to a short circuit on the loop. I£a LED is not fitted a short circuit connection
must be made between those two terminals.
For a line, the end of line device is normally a 3.9 kohm resistor.
D SkKVICING MANUAL
...I I V J ~ A L L A ~ ~AUNN CHAPTER FIVE: INSTALLATION
P S 1 6 SYSEh4 PAGE 28
ILLUSTRATIONS
Figure
CHAPTER Fn7E
INSTALLATION . . -
5.1 GENERAL
5.1.1 Mechanical Installation
All work must be to the quality required by Company Standards, or as required by the
standards specified in the special-to-installation data package.
All units, racks, or other enclosures of system equipment, including junction boxes must be
connected by suitable conductors to a proper electrical earth. This is to provide protection
from electrical interference and static discharges.
For the same reason, particular attention should be paid to ensure that the connection of
screens on cables is in accordance with the drawings.
Suitable cabling for each part of the installation is specified in the special-to-installation
. . data package, but is summarised here. See Table 5.1 for recommended cabling.
-.* . v -
-. . .INSTALLATIONAND SERVICLNG MANUAL CHAF'TE,R FFE INSTALLATION
P S 1 6 SYSTEM PAGE 30
Note 1: Dependent on the load characterisitcs of the devices used. The sections shown
in these cases are indicative only.
. Note 2: : Maximum impedance refers to the total length of wire, i.e. the pair multiplied
.- by two, but.maximum capacitance refers to the total length of the pair. . . .
Note that the wire section for the power supply input terminals on the US-16 motherboard
is maximum 4mm2. All other.terminals are for maximurn.2.5 mm2::::.:.
I .
: ' .. ;"~'INSTAUATlONAND
SERVICING MANUAL CHAPTER FIVE INSTALLATION
PBSM SYSEM PAGE 33
I -Loop Connections at X3 I
I 1 I 1 + (low end)
-
I
2
3 2 + (low end)
4 -
5 3 + (low end)
6 -
7 4 + (low end)
8
9 5 + (low end)
10 -
11 6 + (low end)
12 -
13 7 + (low end)
14 -
15 8 + (low end)
1 + (high end)
2 + (high end)
20
21 3 + (high end)
22 -
23 4 + (high end)
24 -
25 5 + (high end)
26 -
27 6 + (high end)
28 -
29 7 + (high end)
30 -
31 8 + (high end)
NOTE: With more than one US-16 module in the system, the line or loop numbers for
. . modules other than the master PBS-16 start at higher numbers. See Appendix I.
. ..+I ..:
- INSTALLATION AND SERVICING MANUAL CHAFTER FIVE: INSTALLATION
PBS16 SYSEM PAGE 34
Address units are connected across each line or loop. Each address unit represents one
address. Each address unit has connected to it one or more sensors; all of which are repre-
sented by that address. .Anaddress unit may be.in the.base of;asensor, or it may be in a . .
Analogue sensors provide data to an analogue address unit. The analogue address unit,
when scanned, produces an output pulse of 20 mA, whose duration indicates the analogue
value read by the sensor.
A 12.8111s pulse is the response which is equal to 100% when using function 20. 100% is
normally the limit above which the US-16 or PBS-16 interprets the response as a fire alarm.
. - S .- The normal response of an analogue sensor varies a little depending on type and the envi-
, ronrnent, but is normally between 30% and 50% when using function 20.
Conventional sensors provide data to a digital address unit. The digital address unit, when
scanned, produces an output pulse whose amplitude indicates the status of the device. A
4.5 mA pulse is the normal response, while a 20 rnA:pulse.xepresents an alarm condition.
. . _ Three pairs of auxiliaq input terminals are provided as shown in Table 5.4.
- . Inputs number 1 and 2 require an external voltage source. The source may be one of the
24V DC outputs available. Input no. 3 does not require an external voltage source since it
is already supplied with 24V DC on terminal 27 from 24V DC output no. 1. Fig. 5.1 shows
how the inputs could be connected. The input is activated when the corresponding switch
is pressed.
The default programme uses only input number 3. The panel enters the Evacuate mode
when this input is activated. The input is activated by putting a short circuit between the
input terminals. Inputs number 1 and 2 are disabled in the default programme. Refer to
, . -, :. . Part 2 of the Operator's Manual to find.out how these inputs are used for the particular. - : :-
installation.
Note, however, that terminal 27 gets its voltage through fuse.F3,-(thatis the one protecting
24V DC output no. l), and that this input will not.work if fuse F3 is removed or is blown.
Auxiliary Connections
Input No. at X4
l +ve . 23
-ve 24
2 +ve 25
-ve 26
3 +ve 27
-ve 28
BLOCK
5.4 OUTPUTS
5.4.1 Sounders
Four monitored 24V DC sounder outputs, each rated at 0.6A are provided as shown in Fig
5.2. These outputs are protected by solid state fuses. A 10k end of line resistor is used to
monitor the line for open circuit and short circuit. Each device connected to the line must
. . be polarised as shown in figure 5.2. If the device is not polarised a diode must be con- -
nected in series with it as shown in fig 5.2. The polarity is reversed during alarm to turn the
connected devices on.
Fusing is solid state, enabling the system to detect short-circuit faults, which give rise to the
. .
' '; :INSTALLATIONAND SERVICING MANUAL
' CHAPTER FIVE: INSTALLATION
P S 1 6 SY- PAGE 36
. . TERMINAL BLOCK X4
X4
EOL
RESISTOR
(10 kohm)
SOUNDERS -.
4
-))@l
.- .-.-. _._._._
8
WITH -.-.-.-.-.-._._._. d : 9. . .L
~L. . - . A.-.-
-.-.-._._
POLARISING DIODE
.. - ..Foursets of voltage free contacts are provided at terminal block 4,- as shown in Table.5.5.
Each contact is rated for 2A at 24V DC. -
' . .
The Control Relays (1 to 3) are all normally operated when a fire is detected in the system.
The operation of these relays may be modified in cause and Effect programming. Consult
the special-to-installation documentation, (Operator's Manual part 2), to find out if the
operation of any of these relays have been modified.
The Fault Alarm relay is in the default programme operated when a fault is detected in the
system. This relay is normally not energised.
Note that Fault.Alarm Relay is not operated whenever the front panel is indicating a fault .
condition by flashing its amber LEDs. A few typical examples of when this relay is not op-
erated, (even though the front panels amber LEDs are flashing), are when the system is not
initialised, or when something is disconnected.. -.TheFault Alarm relay's operation may be
modified in Cause and Effect programming. Consult the special-to-installation documenta-
tion to find out if the Fault Alarm relay's operation has been modified.
Note that the three Control Relays may be isolated (in software) by using function 10 from
the front panel. The Fault Alarm Relay may not be isolated in the same way, even if it has
j been redefined in Cause and Effect programming.
1
. . -.,.... L
.
.. ..
:' INSTALLATIONAND SERVICING MANUAL CHAPTER FIVE INSTALLATION
PBS-16 SYSIEM PAGE 37
Three DC outputs, each fused at lA, are provided at terminal block X4, terminals
B ( + ) , 30; 31(+), 32 and 33(+), 34. (See fig. 5.1.)
Note that fuse F3, which is the one protecting DC output no. 1, may blow due to an over-
load on terminal 27 (input no. 3) since this output is used to provide power to that input.
A fault warning is given if any one of the fuses is removed or blown. The fault message
looks like this:
Each PBS-16 and US-16 motherboard has an open collector output brought out to terminal
block X4, terminals 21 and 22. The transistor opens when the internal panel voltage drops
below 15V. The change from short circuit to open circuit signals total power failure.
. .
...,. .
= INSTALLATION AND SERVICING MANUAL CHAFTER FIVE INSTALLATION
P S 1 6 SYSTEM PAGE 38
Each PBS-16 and US-16 motherboard has a pair of connections for an RS Unit. Any one
of the RS-16, RS-32 or RS-56 units may be connected. Connection details are shown in Fig
5.3,5.4 and 5.5.
L----------------------,,---------------------J
CHAPTER SIX
COMMISSIONING
CONTENTS
INTRODUCTION
Inputs
Cause and Effect (C&E) and Default Programmes
Outputs
RECORD KEEPING
POWER UP
LxNE/LOOP COMMISSIONING
Wiring Checks
Electrical Checks
Auxiliary Inputs
INITIALISATION
Description
Initialisation Procedure
Testing After Initialisation
Completed Input Initialisation
OUTPUTS
Sounder Outputs
Control Relay Outputs
The Fault Alarm Relay
Total Power Failure
24V DC Outputs
Overall Output Check
BASIC SYSTEM
F . 1':. -!
INSTALLATIONAND SERVICING MANUAL CHA'PTER SIX: COMMISSIOMNG
P m 1 6 SYSTEM PAGE 40
EXTENDED SYSTEM
DIP Switches
Connections to Internal Bus ,. ..
TABLES
Table
ILLUSTRATIONS
Fig
CHAPTER SIX
COMMISSIONING' ' '.
6.1 INTRODUCTION
The commissioning process is a gradual build-up, .bringing subsections of the system into
working order one by one until a section is complete and functional, and repeating this
process for each section. The sections are then brought together into working order, one
by one, until the system is complete. An overall functional check of the system is then
carried out.
6.1.1 Inputs
Inputs may be lines or loops; devices on these lines or loops may be addressable analogue
or digital, or they may be conventional (non-addressable). Separate commissioning proce-
dures are given for addressable and conventional inputs. Differences between analogue
and digital devices are dealt with as they occur.
Each system has a built-in Default programme. That is, in default of (in the absence of) a
customised Cause and Effect programme, the system is programmed to give a standard set
of responses to inputs.
. - This commissioning procedure is written for the Default Cause and Effect programme, and
may be carried out as written. Alternatively, the commissioning procedure may be used
with the customised Cause and Effect programme operating. Notes are included in the text
to cover differences arising when the customised programme is used.
Where a customised programme has been produced, it is normally installed in the equip-
ment at the factory, and commissioning is normally with it in operation.
6.1.3 Outputs
It may not be desirable for some output devices to be switched repeatedly as system testing
. progresses. Thus, for example, once a line of sounders has been proved, it is disconnected
(function 07) until all other output devices have been proved. When all the devices are
known to be working correctly, they are all reconnected (functions 08,11), and overall tests
are carried out.
'. ' ji INSTALLATIONAND SERVICING MANUAL CHAFIER SIX: COMMISSIONING
P m 1 6 SYSTEM PAGE 42
Ensure that you keep a full written record of the entire commissioning procedure, including
a specification of any problems encountered, and the final system initialisation parameters
(i.e. a "map" of the system configuration).
(a) Hardware:
: ..:.. .; Types of modules in the system and their addresses on-t he internal communication
bus.
(b) Software:
: . : Core software versions for eachof the modules in the system, including the PS-16
module.
Listing of custom text. If possible a diskette containing a copy of the text file should
be kept with the record. The record should also show how the text EPROM is
marked, so it is possible to identify which version of the text the EPROM holds.
Listings of the Cause and Effect programme for each sub-unit and how the various
EPROMs are marked. Again it would be useful to keep a diskette with copies of the
Cause and Effect programmes with the record.
All modifications, extensions, updates etc must be carefully added to the record described
above.
Power supplies to a PBS-16 system may be centralised or distributed. That is, there may be
one Charger Unit and battery supplying one PBS-16 module with 24V DC, from which all
other modules are supplied (centralised), or each PBS-16 and,US-16 module may have its .
own Charger Unit and battery (distributed).
Discover which arrangement applies for the system you are commissioning.
At each PBS-16/US-16 motherboard not associated with a Charger Unit, disable the re-
dundant supply monitoring, as follows:
Remove the two PTC resistors R52 and R71 (the test load resistors). They are
located just below the relays on the right hand side of the US-16 motherboard.
Fit a 10 kohm resistor across each of the four sounders X411 (+,-); X412 (+,-);
X413 (+,-); X414 (+,-) to close the sounder monitor circuits during testing.
: .Ensure that the connections are made correctly, as shown in Fig 6.1, between the
Charger.Unit, battery, and PBS-16/US-16 motherboard.
Note that the power supply you are using may have terminals marked differently to
the markings shown in figure 6.1. Please refer to the installation instructions that
accompanied your power supply for further detail.
CAUTION!
l0 (+)
I------ = - W 1 (BATI'ERY +)
Internal
connection for
I
!
- ,=
F-
() 24VDCBATI'ERY SUPPLY
m
x2/2' (BATI'ERY -)
battery
!
I
!L 5. - d (-1
! 6 (+) PBS-l6
L.-.-. <
X or
POWER SUPPLY
(CHARGER UNIT) BA'ITERY
US-16 *$
(+l
8 1 X111 (CHARGER +)
(-1 24V DC MAIN SUPPyl
9
P
* X112 (CHARGER -)
BATI'ERY CHECK
d X113 (BA'IT. CON.)
MAINS CHECK
X114 (MAINS CON.),
6.3.1 Monitoring
A battery supervision signal is sent from the motherboard via terminal X113 to the Charger
Unit, requesting a reduction in voltage to approximately 18V, to check the presence of the
battery. This occurs every ten seconds. In addition, every hour a load of approximately
1.5A is applied to the battery to check its charge level. This is via R52 and R71 on the
motherboard.. A Battery Fault alarm is given if, during this test, the battery voltage at
terminal block X2 falls below 23.6V + /-0.3V.
The rectified, smoothed main DC supply (before regulation) is brought to terminal X114
for supervision. A Mains Fault alarm is given if this signal disappears. The presence of a
smoothing capacitor in the supply may delay this alarm by up to 30 seconds.
The following procedures should be completed for equipment supplied from one Charger
. . . . , .: : Unit before starting on equipment supplied from other charger Units.
6.4 POWERUP
Connect and switch on the supply to the Charger Uqit. Replace the battery fuses F1 and
F2. Ensure that the green Mains On lamp is lit at the Control Panel.
Silence any alarms and ignore any fault indications on the displays. Use function 18 to set
the date and time.
2 .. .
.<-INSTALLATIONAND SERVICING MANUAL CHAPTERSIX: COMMISSIONING
P S 1 6 SY- PAGE 45
F1 BATTERY FAULT
CENTRAL NO. ..
F2 BATI'ERY FAULT
CENTRAL NO. ..
F3 FAULT POWER FUSE NO. 1
CENTRAL NO. ..
F4 FAULT POWER FUSE NO. 2
CENTRAL NO. ..
F5 - '.' FAULT P0WER:FUSE;NO.3 .. . -:
CENTRAL NO. ..
Remove the mains supply from the Charger Unit and check that the fault message is:
MAINS FAULT
CENTRAL NO. ..
. . . . . . If the module under test is a PBS-16 which will have other modules connected to it at
a later stage, cut the bridging links:
Check that the fault message, which may take up to two minutes to appear, is:
Replace the links, using temporary connections (These will be removed when the
other modules are connected). (Section 6.10.2).
IIIOI-I~UN ANU bCKVIClNCi hl.ANUAL WAFTER SIX: COMMISSIONING
P m 1 6 SYSTEhf PAGE 46
Earth your hands, then remove the Loop Card from socket P3. Check that the fault
message is:
LOOPCARD FAULT
CENTRAL NO. ..
Note that it may take up to three minutes for this fault message to appear.
. - Refit the Loop Card, taking care not to damage it or its socket.
CAUTION!
1 0 i
1 W
2 0 K
( W S ) 7
BRIDGING LINKS 3
4
0
@
2
X
3
a
@ cn
OUT 3
0 -
+
All the Lines (or Loops) are checked individually, starting with Line/Loop 1.
I
Check visually that all devices are installqd and in a proper condition: that all wiring is in
accordance with the drawings.
If Conventional lines are installed, pleasure the overall line resistance. It should
equal the value of the end-of-line terminating resistor (3.9kohm).
If Addressed lines are installed, measure the overall line resistance with a multimeter.
INSTALLATION AND SERVICING MANUAL CHAF'TER SIX: COMMISSIONING
PS16S Y m M PAGE 47
Make sure the positive lead from the meter is applied to the positive line terminal.
The resistance measured should be relatively high (megohms). A small resistance
may indicate a short circuit or address units connected the wrong way around.
Continuity is checked by short-circuiting the positive and negative lead at the far end
of the line and then measuring the overall resistance on the line. It should now be
close to zero. The maximum impedance allowed is 80 ohms. Remove the short
circuit and check that the line resistance has changed to a very high value.
Also with the loop/line disconnected measure the resistance from the positive wire to
the 24VDC supply. Check the resistance both to the +24V and OV. (Use either the
auxiliary 24V Supply terminals, Battery terminals, or the Charger connection
terminals.) The resistance measured should be very high in both cases since the
detection loops/lines should be floating with respect to the 24VDC supply.
Also the resistance between the negative wire of the loop/line and the 24VDC
terminals should be checked in the same way. Again the resistance should be high.
CAUTION!
If any Fire or Fault alarms appear, take careful written note of the exact wording of the
alarm message(s). Investigate and correct the cause of each, dealing with them one by one.
NOTE: One fault may cause several messages, and one fault may cover up others.
Once any alarms have been corrected, simulate the following fault conditions on the Line
or Loop.
(a) Open circuit. This should be made at each end of the Line or Loop, in turn.
(b) Short circuit. Short-circuit each line. On a Loop, where Short Circuit Isolators
(SCIs) are fitted, a short circuit should be applied in each section in turn.
In each case, check that the fault is reported on the display and that the correct fault
messages are displayed.
INSTALLATION A N D SERVICING MANUAL CHAPTER SIX: COMMISSIONING
P S 1 6 SYSTEM PAGE 48
Use function 20 (List Detector Values) to check that each address installed is giving a
reading in its quiescent state greater than the fault level.
NOTE: Any reading less than 2% on a digital line or loop, or less than 21% on an
analogue line or loop causes the address to be ignored during initialisation.
Detector responses are detailed in Appendix A of the Operating Manual.
Three pairs of auxiliary input terminals are provided at terminal block X3. In the Default
programme, only the third pair, Auxiliary Input 3, at X3127 (+ve) and X3/28(-ve) are
functional.
Short-circuit these terminals and listen to hear if the alarm bell relay operates. If
sounders are connected to alarm bell circuits 1,2,3, or 4 then these will be turned on.
The above test may not have the desired effect if a cause and effect program has modified
either the relay logic or the auxiliary input logic.
If the customised Cause and Effects programme is in use, discover from its documentation
which of the auxiliary inputs are functional, and check them as above.
6.7 INITIALISATION
6.7.1 Description
Before initialisation, the PBS-16 or US-16 module has no information about the devices
connected to it. This applies to the input circuits and to modules on the communications
'bus. The system makes the assumption that anything up to the maximum number of input
devices and modules may be connected. All alarm signals received are correctly reported,
but there is no indication if any devices are missing.
When initialisation takes place, the system creates and stores a map of the installation at
that time. This provides a reference so that the absence of a response from a device indi-
cated on the map creates an alarm.
INSTALLATION AND SERVICING MANUAL CHAPTER SIX: COMMISSIONING
P S 1 6 SYSXEM PAGE 49
If further lines/loops or devices are added after initialisation, the system does not recog-
nise them, and re-initialisation is necessary for them to be included on the map. There is
one exception to this:
An alarm device with an address one higher than the highest initialised address is moni-
tored for fire alarm (but not for fault alarm). This exception is to facilitate the testing of
small modifications to the system before re-initialising.
NOTE: Initialisation only includes in the system map those devices giving a response
greater than or equal to 2% (digital systems), or greater than 20% (analogue
systems).
As each line or loop is connected and found correct, the system is initialised. The system is
re-initialised when the next line or loop is added, and so on until all the lines or loops have
been connected and initialised. Between each time the panel is initialised, its previous
initialisation parameters must be cleared either by using Function 34 or by disconnecting
the power supply.
At the Printer,
Initialisation takes up to five minutes, and during this time the system must not be touched.
If the PBSVIEW servicing and commissioning tool is connected it must not be in the Auto
Update mode. Preferably it should be in the Message mode, or disconnected altogether.
Any fire alarm occurring during this period overrides the initialisation sequence, which
must then be restarted when the system is again quiescent.
Upon completion of initialisation, the module performs an automatic system reset (only the
green Mains On lamp is lit). The printer prints out the message: . .
\
.Function 31 produces a printout of the list of initialised devices and units, and constitutes a
INSTALLATION AND SERVICING MANUAL CHAPTER SIX: COMMISSIONING
PBS-16 S Y m M PAGE 50
complete specification of the configuration of the system. This may be compared at any
time with the printout obtained from function 16 (Search Faults), as a check for deviations.
When a line or loop has been initialised, carry out the following tests:
(a) Check the response of the highest address. If this is present, all the others must be.
(b) Make a random check for a fire alarm or fault alarm by (for example) unplugging an
input device.
When the next line or loop is connected and the system is quiescent, carry out the initialisa-
tion procedure again. Make sure all previous initialisation parameters have been cleared
either by using function 34 or by disconnecting the power supply.
When all lines or loops are initialised, carry out tests using Disconnect Loop (function 4)
and Reconnect Loop (function 5).
Use function 4 to disconnect each line or loop in turn. The line or loop voltage is still
present. Only alarm messages related to detector alarms are blocked off, so a fire alarm
created on the loop is ignored by the panel. The scanning of the loop or line and updating
of the detector value registers continues as normal. This means that the servicing and
commissioning tool PBSVIEW is able to check detectors even on disconnected loops or
lines.
Messages relating to overload and short circuit are not blocked when a loop or line is
disconnected.
Use function 5 to reconnect each line or loop in turn. Check that fault or fire alarms come
through from the reconnected line or loop.
Carry out tests using Disconnect Detector (function 1) and Reconnect Detector (func-
tion 2).
Use function 1 to disconnect randomly selected devices on the various lines or loops. Cre-
ate a fault or fire alarm at each of the devices disconnected. There should be no response
from the system. You may not use PBSVIEW to simulate a fire or fault on the discon-
nected devices. The test may be performed by removing the detector head or by injecting
test gas into the detector head.
\
Use function 2 to reconnect the devices. Check that alarms from the reconnected devices
come through.
6.8 OUTPUTS
There are four separate sounder outputs from the PBS-16 module. In turn, for the circuit
to be connected to each, carry out the following procedure.
Check visually that all devices are installed and in a proper condition.
CAUTION!
Check that all devices are correctly polarised and fitted with a correctly polarised external
diode if necessary. Also check that all four alarm bell circuits are fitted with a 10kohm
EOL resistor.
When the wiring is correct, connect the cable to its terminals on Terminal Block X4, ensur-
ing that the correct polarity is observed. See Table 6.2 for connections.
The four alarm bell circuits (sounder outputs) are monitored for open and short circuit,
and the messages described in section 6.4.1 are displayed in the PS-16 Message Display
upon the detection of a fault on the alarm bell outputs.
The outputs are protected by a solid state fuse and each output is rated at 0.6A resistive. ...
load.
Inject a fire alarm at Auxiliary Input 3 by connecting a short circuit between terminals
X4127 and X4/28.
NOTE: This is valid for the Default programme. For the customised programme, find a
suitable fire alarm input from its documentation. The alarm may be injected by
the PBSVIEW servicing and commissioning tool if it is connected.
Check that the disconnected sounder circuits do not operate when a fire alarm is injected
as described earlier.
l +ve 1
-ve 2
2 +ve 3
-ve 4
3 +ve 5
-ve 6
4 +ve 7
-ve 8
(a) Simulate a fire alarm either by using PBSVIEW or by operating a manual call point
connected to one if the detector loop inputs.
(b) All three control relay outputs are operated by this input.
For the customised programme, find suitable fire alarm inputs from its documentation to
operate the control relay outputs. The alarm may be injected by the PBSVIEW servicing
and commissioning tool if it is connected.
Check visually that all devices are installed and in a proper condition.
\
Check that all wiring is in accordance with the drawings and with the specification.
.. / .
INSTALLATION AND SERVICING MAKUAL CHAPTER SIX: COMMISSIONkiG
P S 1 6 SYSIBA PAGE 53
Carry out the following procedure for each of the three output circuits in turn.
When the wiring is correct, connect the cable to its terminals on Terminal Block X4. See
Table 5.5 for connections.
Use function 12 to check which control relay outputs are disconnected, and use function 11
to reconnect these after the test is completed.
(a) Make a fault by removing one of the 24V supply fuses (F3, F4 or F5).
(a) Find a suitable input from the cutomised programmme's documentation, and simu-
late this input.
Check visually that all devices are installed and in a proper condition.
Check that all wiring is in accordance with the drawings and with the specification. When
the wiring is correct, connect the cable to its terminals on Terminal Block X4. See Table
5.5 for connections.
Cause the relay to operate by simulating a suitable input, and check that the circuit oper-
ates correctly.
Check visually that all devices are installed and in a proper condition.
Check that all wiring is in accordance with the drawings and with the specification.
INSTALLATION AND SERVICING MANUAL CHAPTER SIX: COMMISSIONING
P m 1 6 SYSTEM PAGE 53
Short-circuit the end of the cable that is to connect to terminal block X4, terminals 21 and
22. Connect the alarm device and its power supply to the other end of the cable. Check
that the alarm device does not operate.
Check that the output device does not operate when the module is powered.
NOTE: The device connected to the Total Power Failure terminals must have its own
separate power supply.
Check visually that all devices are installed and in a proper condition.
Check that all wiring is in accordance with the drawings and with the specification. .. .
Carry out the following procedure for each of the three output circuits in turn.
When the wiring is correct, check that the circuit r,esistance is appropriate for a 1A maxi-
mum, 24V DC supply. Remove the 1A fuses. Check that the correct fault messages are
displayed in the Message Display, and printed by the printer. The fault message is de-
scribed in section 6.4.3. Connect the cable to its terminals on Terminal Block X4. See
Table 6.3.
When each module to be operated from these supplies is ready for test, the associated fuse
should be refitted (section 6.10.4).
I DC Output
Circuit No.
Terminal Block X4
Connector No.
Fuse No.
I
INSTALLATION AND SERVICING MAhUAL CHAPTER SIX. COMMISSIONING
P S 1 6 SYSEM PAGE 55
When all the output circuits have been checked individually and found to be correct, recon-
nect the 24V DC Output terminals on terminal block X4, ensuring that each circuit is
connected to its correct terminals, and that the correct polarity is observed.
Use function 14 to reconnect all currently disconnected lines or loops, detectors, sounder
circuits and the control relay outputs.
The panel should now be reset. Wait a little while to make sure that no fault messages
relating to the outputs comes through.
Where a customised Cause and Effect programme is in use, select and inject alarms to
check that all output circuits operate correctly.
All parts of the system operating from the single PBS-16 or US-16 module have been tested
at this stage. It remains to reinitialise the system, and to carry out a detailed check of the
system messages and of the cause and effect responses.
Most of the records required may be obtained as printouts from the system.
When all connected circuits have been found correct, initialise the system as described in
section 6.7.2.
It is mandatory that an alarm is simulated at every input address. For each alarm, check
that the Message Display shows the correct message, as listed in the customised system
data.
Use function 14 to reconnect all currently disconnected lines or loops, detectors, sounder
circuits and control relays.
It is mandatory that all the relevant causes in the system are simulated. For each, check
that the correct effects are being produced in all the output circuits and devices.
For a system which has the PBS-16 module, but no extension modules, commissioning is
now complete. Records should also be completed (section 6.2).
For extended systems, the next stages are to test the remaining modules in isolation, then
connect them, one by one, through the internal system communications bus to the Master
PBS-16, initialise the complete system and run an overall test. The system is then ready for
a thorough check and recording of its performance.
Each module including a Loop Card must have its own unique address on the internal
communication bus. The address is either set on a DIP switch included on the US-16
motherboard or in the Cause and Effect EPROM. The addresses allocated form a continu-
ous sequence from 01 upwards, and are to be found in the customised documentation
package. Coding for setting the DIP switches is given in Appendix C.
For connection to the bus, each module has a pair of wires entering and a pair of wires
leaving the module. The wires are linked inside the module, providing continuity for the
bus, only if the module is connected. Because connected addresses must be in an unbroken
sequence, the first module to be added to the bus must have the address 02.
During commissioning of the master PBS-16, the internal bus has been disconnected at
terminal block X515 to 8. Before starting to commission any other modules, disconnect
them all from the bus.
If all modules are connected to the communication bus and a complete loop have
been formed, disconnect the temporary links 5 to 7,6 to 8, on terminal block W that
were fitted at para 6.5. This enables two-way monitoring of the bus. A break will not
be detected if the links are not removed. The links must therefore not be removed
until the communication bus forms a complete loop.
When each module has been tested in isolation, it is ready for connection to the bus. Be-.
fore it is connected, set its DIP switch to the correct address for the module.
When one module has been connected to the bus, it should be fully commissioned and
initialised before the next module is connected.
MSTALLATION AND SERVICING MANUAL C H A F E R SIX: COMMISSIONING
P S 1 6 SYSTE3M PAGE 57
Carry out the procedures given in para 6.3 and 6.4, that is, Power Supplies Connections,
and Power Up.
(a) Test the US-16 as a completely autonomous alarm system with a PS-16 Information
and Control Panel connected. PBSVIEW (Appendix B) may also be connected in
addition to the PS-16 panel.
(b) Connect the internal system communications bus (para 6.10.2) to use the facilities of
the PBS-16 already commissioned.
In either case, the continued checking and commissioning of the US-16 is as already de-
scribed.
Repeat this procedure for each PBS-16 and US-16 when its turn for commissioning is
reached.
All modules except for the PBS-16 and US-16, receive their power supplies from either a
PBS-16 or a US-16. The only exceptions are RS-Units which may get their power via a
RU-161. For each module to be commissioned, connect the 24V DC power supply from its
parent module, ensuring first that there are no other connections to the module, and ensur-
ing that the supply polarity is correct.
Cany out tests on the module in isolation. These tests are specified for the modules in
Appendix D.
Connect each module, in its address sequence, to the bus and check that it produces the
correct responses. Relay Slave Units (RS-16, RS-32, RS-56) should be added to the parent
Relay Unit or US-16 module and checked as soon as it has been commissioned.
Each time commissioning has been completed on one module, the system should be re-
initialised.
Because the internal bus can continue to function with a break in it, it is necessary to check
that the bus is complete. When all modules have been connected, short circuit one end of
the bus at the master PBS-16 and measure the resistance of the bus from the other end. Its
value should be close to 0 ohm. The maximum impedance allowed is 20 ohms.
INSTALLATION AND SERVICING MANUAL CHAPTER SIX: COMMISSIONING
P S 1 6 SYSJEM PAGE 58
CAUTION!
It is mandatory that an alarm is simulated at every input address. For each alarm, check
that the Message Display shows the correct message, as listed in the customised system
data.
Use function 14 to reconnect all currently disconnected lines or loops, detectors, sounder
circuits and the control relays.
It is mandatory that all the relevant causes in the system are simulated. For each, check
that the correct effects are being produced in all the output circuits and devices.
CHAPTER SEVEN
SERVICING
CONTENTS
AUTOMATIC MONITORING
False Alarm Reduction
Fault Alarms
System Data
ROUTINE SERVICING
TROUBLE SHOOTING
The PS-16 Card Is 'Dead'
No Power At The US-16 Motherboard
Loop Card Fault
The COM-16 Communication Card Does Not Work
RS-Units (RS-16, RS-32, RS-56) Do Not Work
Open Circuit On The Communication Loop Is Not Detected
Open Circuit On Alarm Bell Circuits
Short Circuit On Alarm Bell Circuit
Open Circuit On Detection Loops Or Lines
Earth Fault
No Response From Address Units Or Detectors
TABLES
Table
CHAPTER SEVEN
SERVICING
The PBS-16 system is self monitoring. Power supplies are monitored: a no-volt alarm is
provided if they fall below acceptable levels, and separate alarms are provided if output
supplies fail. The microprocessor control and display circuits are self-tested every two
seconds, and provide a system fault alarm if they fail.
When the system has been set up and is initialised, it creates and stores a map of the instal-
lation at that time. This provides a reference so that absence of response from a device
indicated on the map creates an alarm. It also provides a reference level for each alarm
device, so that it may define fault alarm and fire alarm thresholds for each input, and re-
spond accordingly.
A comparison of actual signal level with the reference level is made automatically every 24
hours for each device, and if a drift in value is noted, a partial correction is made to the
stored reference value. Too much correction could result in an alarm condition being
missed: too little correction, and a drift in sensor response with time could result in a false
alarm. A balance is achieved to minimise the false alarm rate without jeopardising the
genuine alarm signal.
Note that this feature only applies to systems using analogue sensors.
When a fault alarm is produced, a message is displayed on the PBS-16 Message Display,
indicating the nature of the fault. If a Printer is connected, the message is also printed out.
By use of the functions available from the keypad more information can be obtained. Most
of these functions are described in the PBS-16 Operators Manual. Others, which are serv--..
icing functions only, are described in Appendix G of this manual.
Information necessary for servicing the system is largely contained in this manual.
On a large installation, the number of sensors can run into many thousands, so it is an
enormous advantage that routine monitoring of all devices is performed approximately
every two seconds. Printouts of the results of the monitoring should be made, checked and . - .
filed by the s e ~ c engineer
e on a regular basis. This provides records against which the
system can be checked if or when a fault condition does occur.
This section is not meant as a complete guide to all problems that may arise with a PBS-16
system during installation, commissioning, servicing or normal operation. The purpose of
this section is to give a few ideas of what to do when certain things happen, and hopefully
to help you search for the cause of the problem in a structured and efficient way.
Very often the PBS-16 system itself will give the engineer or technician working with the
installation a good indication of what the problem is. The engineer or technician should,
however, remember that the accuracy of the fault messages displayed in the PS-16 Message
Display is dependent on how 'Standard' the installation-is. For example, the panel will ..- . .
always assume that the address units on the detector loops or lines are physically placed in
sequence. If this is not the case for your installation, fault messages regarding faults on the
lines or loops may not be accurate.
It is very important that the cause of the fault is found and cured. Sometimes it is easier to
remove the symptom of the problem, than it is to actually put the fault right. But when this
is done, the fault is still there, even though the fault message never appears because the
symptom has been cured. This puts the proper and safe operation of the system at risk.
A typical example of this problem is to disconnect the earth lead on the US-16 mother-
board from the cabinet. This disables monitoring of earth fault, and the panel is not able
to detect such a fault. This action does not cure the problem, but merely removes the
panel's ability to see the fault. The earth fault is still there and may cause more problems
in the future.
Below you will find a number of problems listed and suggestions of what can be wrong, and
what to do to rectify the problem.
Symptom:
Message Display shows nothing and all LEDs are off. No sound is heard when push-
ing a key on the keypad. No lights come on when the lamp test button is pressed. It
is not possible to receive or send any messages on the communication bus when
PBSVIEW is used.
LUSTALLATION AND SERVICISG .%JUAL CHAPTER SEVEN: SERVICING
PBS-16 S Y S E M PAGE 62
Possible cause:
The ribbon cable is not plugged in on the motherboard. Faulty component on the
card short circuiting the power supply. PS-16 card itself faulty or fault on other cards
connected to .the same power supply. Faults on power supply and discharged batter-
ies. Incorrect connection of the power supply.
What to do:
Check that the ribbon cable is properly connected to the connector on the mother-
board. Check the voltage level at the motherboard's Charger and Battery connection
terminals. The voltage should be above 24V DC on both terminals. If this is not the
case check the charger and battery connections and all fuses as described in section
7.3.2. If the power supply and the batteries are OK and no fuses are blown you
should try changing the PS-16 card.
Symptom:
No voltage measured on the Charger 24V DC terminals or the 24V DC Battery con-
nection terminals. Loop Card and other cards connected to the motherboard does
not work. Loop Card fault message displayed in the PS-16's Message Display. De-
tectors on the detection loops or lines does not respond. The auxiliary inputs do not
work. Alarm bells and control relays do not operate.
Possible cause:
Blown fuses and incorrect connection of the power supply. Flat batteries and discon-
nected or faulty Charger Unit. Faulty motherboard or other equipment connected to
the motherboard.
What to do:
Check that the charger and battery connection is correct. A typical charger and
battery connection is shown in figure 7.1. Check fuses F1 and F2 on the mother-
board. Check all fuses on the Charger Unit. If possible determine the cause of blown
fuses and put it right before replacing them. If the fuses blow again the battery and
the Charger Unit should be disconnected from the motherboard.
If there are no blown fuses, the battery and Charger Unit should be disconnected.
Make sure there is no risk of short circuiting the loose wire ends. Check the mains
connection to the Charger Unit. Check that the mains voltage is present at the
Charger Unit with a volt meter. Measure the voltage output from the Charger Unit.
If the mains voltage is present at the charger, and all fuses are intact, and there is still
no voltage at the charger 24VDC output, the Charger Unit should be replaced. If the
voltage is present at the output, the connection between the charger and the mother-
board should be checked by measuring the voltage between the 24V DC wire and the
INSTALLATION AND SERVICING MANUAL CHAPTER SEVEN: SERVICING
P S 1 6 SY!TEh4 PAGE 63
OV wire at the PBS-16 end. (They should be disconnected from the motherboard
while the voltage is measured).
If 24VDC is present at the charger output when it is disconnected from the mother-
board it is likely that the motherboard itself (or other cards connected to it) has an - -
- l . .
internal short circuit. This is checked by disconnecting the battery and the charger
and measuring the resistance between the +24V terminal and the OV terminal. The
resistance should be at least a few kohms. A short circuit is indicated by a very low
resistance. Try to locate the short circuit by removing the connected cards one by one
(Loop Card, Communication Card, PS-16 front card). The resistance should go up to
a few kohms when the card with the short circuit is removed. If the short circuit is on
the motherboard all the connected equipment should be disconnected and the resis-
tance rechecked. If it is still very low the motherboard should be replaced.
Check the voltage across the batteries (at the batteries themselves). The batteries
may be completely discharged and must be allowed to be recharged before it is pos-
sible to reset the panel without the battery fault message coming up in the Message
Display. This might happen if the charger has not been working for a long period.
Check the battery connection by measuring the voltage at each pair of terminals the :-
battery voltage passes through, ending up at the Battery connection terminals on the
US-16 motherboard.
Reconnect the charger and batteries when you are satisfied that they are not dam-
aged in any way and that the connections are correct. The procedure for powering up
the system described in chapter 5 should be followed.
Symptom:
The PS-16 Message Display shows Loop Card Fault. The buzzer on the unit the
Loop Card is connected to sounds. Not able to read any loop or detector values
either from the PS-16 or from PBSVIEW.
Possible cause:
The Loop Card is not powered. Cause and Effect contains an 'eternal loop' causing . . . .
the microprocessor to do nothing. Missing components on card. Microprocessor on
Loop Card is faulty, or other major component failure. Cause and Effect EPROM
faulty or incorrectly fitted. Wrong address set in Cause and Effect for Loop Cards
used in RU-16, RU-161 or together with IF-16. Wrong address set on DIP switch on
the US-16 motherboard.
What to do:
Check that the 24V DC supply to the unit the Loop Card is used with is intact. Check
that the Loop Card is put into the correct slot on the PBS-16 or US-16 motherboard.
INSTALLATION AND SERVICING iMAiiUAL CHAPTER SEVEN: SERVICING
P S 1 6 SYSTEM PAGE 61
The slot reserved for the Loop Card is marked P3 on the motherboard. Check that
the Loop Card is pressed all the way down onto the connector.
An 'eternal loop' in the Cause and Effect software will cause the Loop Cards watch
dog to restart the card after a short time. The card may therefore seem to be working
fine for some of the time, and then seem to freeze for a short period. The Cause and
Effect must be thoroughly checked for the possibility of such loops.
Check that all main components necessary are fitted properly on the card. The card
should have a processor fitted in the socket labeled V1, and it should have a RAM
chip located in the socket labeled V3. These two components are absolutely essential
for correct operation. If the Loop Card is not fitted in a PBS-16 or a US-16 a Cause
and Effect EPROM must also be included in the socket marked V4.
If the microprocessor is faulty or the card has some other major component failure
the card probably will not work at all, or will perhaps give very strange responses to
the inputs. Touch the main components to find out if any of them are overheating.
An overheated component may be faulty and should be replaced if possible.
Check that the Cause and Effect EPROM, if included, is fitted the right way around
and that all the pins are properly inserted into the socket. A little notch on the socket
and on the EPROM indicates which way around the chip should be inserted.
Check that the correct address is set in Cause and Effect for Loop Cards used with
the RU-16, RU-161 and the IF-16. Check that the correct address is set on the DIP
switch (Sl) on the motherboard for Loop Cards fitted in PBS-16s or US-16s.
Symptom:
The printer does not print. No telegrams are being sent through the other port.
Possible cause:
The card is not powered. The card is not pressed all the way down onto the connec-
tor. The PS-16 card is not connected to the PBS-16 motherboard. PS-16 is pro-
grammed to support a different port configuration than the one you have selected.
The communication ports are incorrectly set up. The equipment is connected to the
wrong port. The equipment connected is incorrectly configured. The card is dam-
aged.
What to do:
Make sure the power is completely removed before you remove or insert the
COM-16 card. It is extremely sensitive to rough treatment, and will almost certainly
INSTALLATION AND SERVICING MA\UAL CHAPTER SEVEN: SERVICING
P S 1 6SYSEM PAGE 65
Check that the unit the Communication Card is connected to is powered. Check that
the card is pressed all the way down onto the connector. Check that the ribbon cable
from the PS-16 front card is properly connected.
If the PS-16 front card is not working the Communication Card will not work either.
The reason for this is that it is the PS-16 card that controls the Communication Card.
Make sure that the front card program is meant to work with the port configuration
you have selected. See Appendix E.
Check that the external equipment is connected to the correct port. Check that the
COM-16 is set up for the correct baud rate on the two ports, and that port 2 (P2) is
correctly configured. Check that only one switch on each DIP switch is set to on.
Check that the equipment connected to the communication port is powered and
turned on and that it indicates no faults. (E.g. Printer alarm due to lack of paper.)
Check that the equipment connected is correctly set up and matches the set up of the
COM-16 port it is connected to. . .
Symptom:
Cause and Effect controls do not work. Lamp test for Mimic Panels does not work.
Possible cause:
What to do:
Check that the RS-Unit is correctly connected. This must be done very carefully. .
This is particular true for a RS-56 used with a IF-16 card. It is very easy to put a wire
into the terminal neighbouring the one it should have been put into. Make sure you . .
do not look at the card at an angle while checking the connections, but are looking
straight down onto the IF-16 card. OtheMise it is difficult to see exactly which termi-
nal the wire is connected to.
Check the voltage at the 24V DC terminals with a volt meter. If no voltage is present
re-check the wiring and the fuses of the power supply it is connected to. For a RS-56
INSTALLATION AND SERVICING MANUAL CHAPTER SEVEN: SERVICING
PBS16 S Y m M PAGE 66
used with a IF-16 card make sure that the straps on the IF-16 card are not fitted. Cut
the straps if they are included. Make sure that the card is pressed all the way down
onto the connector and that no pins are bent.
The RS-Unit ought to be powered from the same supply as the Loop Card that con- .. .
trols it is powered from. The power supplies must at least have a common OV. For a
RS-56 the equipment that it controls must also be powered frorn the same supply, or
at least have a common OV connection.
Check that the Cause and Effect EPROM is correctly fitted on the Loop Card con-
trolling the RS-Unit. Check that:
Thoroughly check the Cause and Effect for setting of correct address and parameters.
Check that the programme contains no 'bugs' that causes the programme to do ,
'funny' things.
Check that the Loop Card controlling the RS-Unit has contact with the rest of the
system by for example using function 26 (Send Software Version Number) on the
PS-16 or by using PBSVIEW. If there is no communication with the Loop Card the
fault must be found and rectified.
Make sure that the equipment the RS-Unit controls is not faulty, and that it is cor-
rectly connected to the RS-Unit.
Symptom:
No fault message when there is one open circuit on the communication bus.
Possible cause:
The bridging links ST2 and ST3 on the motherboard in the main PBS-16 module have
not been removed.
What to do:
Remove the bridging links ST2 and ST3 on the motherboard that the PS-16 front card
controlling the Communication Loop is connected to.
INSTALLATION AND SERVICWG MANUAL- CHAF'TER SEVEN: SERVICING
PBS16 SYSTE,M PACE 67
Symptom:
Fault message indicating open circuit on Alarm Bell Circuit no. X on Central no. Y. .
Sounder devices connected do not sound.
Possible cause:
Missing EOL resistor. EOL resistor of too large value. Terminal block not pressed
all the way in. Loose connection. Broken wire.
What to do:
Physically disconnect the faulty alarm bell circuit. Measure the resistance between
the two wires. This resistance should be very close to the End Of Line Resistance
which should be 10 kohm. If the resistance measured is larger than 10 kohm but not
several hundred kohms it is probably either a poor connection or a wrong EOL resis-
tor value. Check the EOL resistor, and replace with a new one if missing or found to
be faulty.
If it is not the EOL resistor that is broken or missing the following procedure could
be used: With the alarm bell circuit physically disconnected, move along from the
end of the line towards the motherboard it is connected to one device at a time. At
each device measure the resistance on the line. The resistance should always be very
close to the EOL resistance. When this is not true the stretch of wire causing the
problem is located.
Symptom:
Short circuit message for Alarm Bell Circuit no. X, Central no. Y is displayed in the
PS-16 Message Display. The Alarm Bell Circuit does not operate.
Possible cause:
A diode is fitted as a EOL device rather than a 10 kohm resistor. An EOL resistor of.
the wrong value is fitted. Sounder devices not polarised or connected the wrong way .
around. A regular short circuit connection.
What to do:
Check that the Alarm Bell Circuit is correctly connected to the motherboard. .
Physically disconnect the faulty Alarm Bell Circuit. Measure the resistance between
the two wires. If the resistance is not close to zero it is not a straight short circuit
l connection. Check the EOL device is not faulty and is of the correct value. It should
J ,
INSTALLATION SERVICIXG lMANUAL CHAPTT)R SEVEN: SERVICING
P S 1 6 SYSlEM PAGE 68
be a 10 kohm resistor.
Check each sounder device in turn making sure that it is connected the right way
around and that external diodes have been fitted (the right way around) if required.
Also check that the devices do not have an internal short circuit.
Reconnect the unit to the rest of the line, and move to the sounder device before the
one you just checked. Disconnect the end of the line closer to the motherboard and
measure the resistance between the positive and negative terminal on the sounder
device. It should again be equal to 10 kohm. Continue this procedure until the resis-
tance measured is much smaller than the EOL resistance. The stretch of wire or
sounder device with a short circuit has now been found.
Symptom:
Fault message displayed on the PS-16 Message Display. Panel does not see all
devices on the line during initialisation. Panel gives an incorrect address range when
using function 24 on the PS-16 or when using PBSVIEW.
Possible cause:
One end of a loop is not connected. A loose connection. A broken wire. A detector
head has been removed. Terminal block not fitted properly. Unstable address unit
answering at a wrong address or at an address higher than the highest address on the
loop or line. A short circuit isolator on the loop does not have the LED or short
circuit link fitted.
Note that if a detection loop has a short circuit isolator, one gets an open circuit
message in addition to the short circuit message when the short circuit isolator oper-
ates. This is quite normal, and there is no need to look for an open circuit on the Line
after the short circuit has been cleared.
What to do:
Carefully note the open circuit message reported in the PS-16 Message Display.
Remember that if the address units are not placed in the correct physical sequence on
the loop or line the fault message given may not be accurate.
The fault message given always indicates the last address the panel sees on the line or
loop before the open circuit. (From the low end of the loop.) If the fault message
INSTALLATION AND SERVICING I U N U A L CHAPTER SEVEN: SERVICING
P S 1 6 SYSIEM PAGE 69
given specifies no address, (in an addressed system), but only the loop or line number,
an open circuit is detected before the first address on the line or loop. If the fault
message indicates the last address on the loop the break is detected between
that address unit and the panel.
For a loop:
Disconnect both ends of the problem loop. At one end of the loop tie the plus and
the minus wire together. Measure the resistance between the two wire ends from the
other end of the loop. This value should be very high if there is still an open circuit
on the loop. If it is high, check the connections to the address unit indicated in the
fault message and the connections to the address unit following it on the loop.
For a Line:
Disconnect the affected line and tie the positive and negative wire ends at the far end
of the line together. Measure the overall resistance of the wiring. The resistance
must no be more than 80 ohms. If the measurement indicates an open circuit, the
connections to the address unit indicated in the fault message and the one following it
should be checked.
An open circuit may be caused by an AX87IS short circuit isolator that either has the
LED fitted the wrong way around or that has not had a short circuit link installed
instead of the LED. The AX87IS must always have either a LED or a short circuit
link installed.
If the open circuit message given indicates the last detector on the loop it is possible
that the fault is caused by an unstable address unit that answers at several addresses
during the scan. This is very difficult to detect without using PBSVIEW.
When PBSVIEW is not available there is really only one way to tackle the problem
provided the address units are placed physically in sequence on the loops or lines:
For a loop system disconnect one end of all loops, then use function 33 to put the
system into Line mode. Break the problem line, let's say, in the middle. Leave the
system for a while and see if the open circuit message comes up again. Depending on
what happens you will need to either move further away from the panel or closer to it
and do the same there.
If the system operates just fine with the break in the middle you must reconnect the
broken line, and find a new place further along the line where it can be broken again.
If the fault does not go away you will have to move closer to the panel and break the
line there. This procedure is repeated until the faulty address unit has been located.
Another problem is an address unit that does not answer. Check the address unit
following the one indicated in the fault message. Some address units require EOL re-
sistors. Check that it is fitted, if required, and that it is the correct value. If all else
fails try to change the detector head, detector base or the address unit.
INSTALLATION AND SERVICING MANUAL CHAPTER SEVEM SERVICLVG
P m 1 6 SYSTEM PAGE 70
Symptom:
The Earth Fault message is displayed in the PS-16 Message Display. Short circuits on
Alarm Bell Circuits or Detection Lines or Loops. Problems with the communication
loop.
Possible cause:
What to do:
The part of the system with the earth fault must be found. This is done by step by
step disconnecting part of the equipment, resetting the panel, and waiting for the
Earth Fault message to come up again. When the earth fault message does not come
up, the equipment with the earth fault has been localised. The Earth Fault is then .
found by checking the circuitry of the faulty equipment.
NOTE:
In a system with more than one motherboard the following situation may occur: Two
US-16 have different power supplies connected, but the power supplies are refer-
enced against each other by connecting the panels OV DC together. This is not nor-
mally done, but may be necessary if RS-Units connected to the two panels control the
same equipment. In this case an earth fault is indicated on one of the panels if the
power is removed on the other one. The way to check that this really is the cause of
the earth fault is to disconnect the earth fault lead (yellow and green lead) from the
chassis on the panel that is not powered. The lead should be reconnected when the
power is put back on. The earth fault indication is avoided all together if the lead is
disconnected before removing the power.
Symptom:
The addressing on the loop or line seems to be working. If for example test gas is
inserted into a detector, the detector indicates an alarm, but nothing happens in the
rest of the system. -When looking at the detector values in PBSVIEW some addresses .,
give no response.
Possible cause:
The detection loop or line is disconnected in software. There is a short circuit be-
tween OV in the panel and the negative wire of the detection loop. Missing EOL
INSTALLATION AND SERVICING MANUAL CHAETER SEVEN: SERVICING
P S 1 6 SYSTEM PACE 71
resistors in address units such as AX83D, AX87D and AX87AD. Missing detector .
What to do:
A short circuit between OV in the panel and the negative wire of the detection loop
will disable all measuring of detector answers. To find out if such a short circuit exists
disconnect the detection loop or line completely and measure the resistance between
the negative loop wire and the motherboard OV terminal (For example the Battery
negative terminal). The negative terminal of the detection loops is not the same as
the negative terminal of the battery, charger or 24V DC outputs.
Check the address units that do not answer. Check that the detector head is properly
inserted. Check that the EOL resistor, if required, is inserted and of the .. correct . . . .
, . ..
value. Check that the address coding is correct.
7.4 -
TROUBLE SHOOTING QUICK REFERENCE
Table 7.1 gives a quick reference to what might be wrong when certain fault messages are
displayed in the PS-16's Message Display. The table also specifies which buzzers operate,
if the PS-16's amber LEDs should flash, and if the fault relay will operate. Finally a short
list of suggested actions are included. The table is by no means complete, but gives a brief
and useful reference for the most common fault messages.
INSTALLATION AND SERVICING MANUAL CHAYIER SEVEN: SERVICING
PBS16 SYSEM PAGE 72
-Charger output
INSTALLATION AND SERVICISG MANUAL APPENDICES
PBS-16 S Y m M PAGE 73
APPENDICES
CONTENTS
DEFAULT PROGRAMME
Fault Alarm Inputs
Fire Alarm Inputs
Auxiliary Inputs
DIP-SWITCH SETTINGS
PRINTER CONNECTIONS
IF-16 CONNECTIONS
Using The IF-16 With A Loop Card
Using The IF-16 With An RS-56
TECHNICAL SPECIFICATIONS
CONDITIONS OF SALE
INDEX
INSTALLATION AND SERVICING MANUAL APPEKDIX A: THE DEFAULT PROGRAMME
P S 1 6 SYSTEM PAGE 75
APPENDIX A
THE DEFAULT PROGRAMME
The Default programme defines the effect of inputs on the outputs from the PBS-16 or US-
16 module. The programme is in permanent store on the Loop Card, and takes effect
when no customised Cause and Effect EPROM is fitted to the card.
The effects produced by fault alarm inputs at the PS-16 Information and Control Panel are
unchanged by the presence or absence of the customised Cause and Effect programme.
In the Default programme, apart from the displayed addresses, all alarm inputs produce
the same effects.
(c) Output signals on the internal communications bus operate all fire alarm outputs on
all modules on the bus.
A3 Auxiliary Inputs
Auxiliary inputs 1 and 2 are disabled. Auxiliary input 3 (terminal block X4, terminals 27 ,
and 28) is enabled, and has the effect of putting the system into the Evacuate Mode when it
is operated. During Evacuate Mode all the alarm bell circuits are activated.
INSTALLATION AND SERVICING MANUAL APPENDIX B: SERVICE AND COMMISSIONING TOOLS
PBS-16 S Y S l E i PAGE 76
APPENDIX B
SERVICE AND COMMISSIONING TOOLS ' '
For hard copies: 80 column printer with RS-232C serial port Centronics
interface
(The following is a copy of the README file on the PBSVIEW distribution disk).
SYSTEM SETUP
This diskette contains all necessary software for testing and commissioning PBS-16 systems.
The software can be used on IBM PCs, ATs or compatibles with MS-DOS 2.1 or later
version.
This software is hardware-lock protected, that is, the enclosed hardware lock marked
SIGNALCO SOFTWARE LOCK TYPE W 0 3 must be installed on the computer serial port
,i
-
COMl for this software to run.
LUSTALLATION AND SERVICIKG MkVUAL APPELDIX B: SERVICE kW COMM1SSIOhIXG TOOLS
P S 1 6 SYSTEM PAGE 77
Connect the PBS-16 communication interface to the PBS-16 communication loop. Observe
correct polarity. The PC end of this interface connects to the computer COMl serial input
on the back of the hardware lock.
1. Start the program by typing PBSVIEW. This loads the communication handler and
starts the main program.
2. The opening window is Messages. From this window you can go to two other win-
dows, Values and Diagnostics, depending on what information is required from the
PBS-16 system.
3. You can start a log session by pressing the L key. The program then asks you to
specify a file name to write the log to. You also have to specify the bit pattern for the
first two bytes that the PBSVIEW shall trigger on. Entering an X for any of the bits
indicates a 'don't care' for that particular bit. Specifying all X's will cause the pro-
gram to trigger on the first occurring telegram. Pressing 'L' again causes the program
to stop logging and to write the log to the specified file. The log is automatically
saved if you exit the program.
MESSAGES WINDOW
This window displays all messages transmitted on the internal communication bus. From
this window you can also push telegrams onto the communication bus, that is, simulate
telegrams sent from any unit.
Key Function
Home - Causes the Log-window to display the first log entries in the current
log buffer.
End - Causes the Log-window to display the last log entries in the current
log buffer.
Page Up - Displays the preceding page of the log buffer.
Page Down - Displays the following page of the log buffer.
Left Arrow - Places the first entry in the current log buffer, that occurred after the
log triggered, in the middle of the log-window.
Up Arrow - Scrolls the log-window one line up.
Down Arrow - Scrolls the log-window one line down.
VALUES WINDOW
From this window information internal to the Loop Card microprocessor can be acquired.
The values presented on this screen are the same values as used by the microprocessor for
checking fire and fault levels from any detector.
),
F1 Det Vals - Requesting loop no. and presenting the values read from each detec-
INSTALLATION AND SERVICING ,MANUAL APPENDIX B: SERVICE AND COMMISSIONING TOOLS
PS16 PAGE 79
tor connected to this loop. The top line of the screen will indicate
loop number. The second line indicates static current supplied to .
this loop. (Will indicate abnormal power consumption due to short
circuit or power consuming units connected to the loop).
F2 Type Vals - Presenting values read when type checking during initiation.
F3 Adj. values- Current adjustment values for analogue detectors.
F7 Update Mode- Switching between manual and automatic updating of values on
screen. When in automatic updating mode, any detector with un-
stable reading or faulty addressing unit is easily recognized.
F8 Diag. - Switching to diagnostics window.
F9 Messages - Switching to messages window.
F10 Exit - Exiting PBSVIEW and return to DOS.
H,h - Read values on same loop but from high end of loop. Loop type must be set to
Loops.
L - Start/stop log.
P,p - Dump-print screen to printer connected to LPT1.
r - Request update. For updating values while in manual mode.
Space- Alternative menu.
. - (Full stop). Filter on/off. The filter equals the specified trigger pattern. While
filter is on, all Loop Card check telegrams, Loop Card reply telegrams and front
card acknowledge telegrams are not logged. These will be logged if filter is
turned off by pressing full stop.
DIAGNOSTICS WINDOW
This window has been implemented to enable an automatic scan of all units and detector
values. The routines used are the same as from the VALUES window. The computer
collects all data and compares these with a set of recommended values and gives a rough
estimate of the findings. This is of value as a quick indication of the state of a system, while
for more elaborate analysis the VALUES window is recommended.
F1 Check All - Start checking of all units and unit addresses in order to give a :
total system overview.
F2 Check Unit - Start checking of a specific unit address.
F3 Loop Currents - Shows the loop currents for all units connected on com. loop. -.. .
F7 Detail - Set detail of checking.
F9 Values - Switching to values window.
F10 Exit - Exit PBSVIEW and return to DOS
. - (Full Stop). Filter on/off. The filter equals the specified trigger pattern. While
filter is on, all Loop Card check telegrams, Loop Card reply telegrams and front
card acknowledge telegrams are not logged. These will be logged if filter is . .
When contacting A/S Signalco for help during commissioning and servicing, a printout of
the PBSVIEW-screen is very helpful to us when recommending actions to be taken.
Logging the messages that are sent on the PBS-16 system's internal communication loop .
can be a valuable tool when trying to find spurious messages and their cause. The logfile
will record when the message was sent, and it will also show the bytes transmitted. A short
description of the telegram is also included.
Another type of telegram is the string telegram. The string telegram does not have a fixed
length and takes the following form:
When the log function is activated, a filename must be specified for the logfile. The file-
1 name may include drive specification and a path as well as the actual filename. The
2'
INSTALLATIONAND
SERVICING MANUAL APPE~BIXB: SERVICE AND COMMISSIONINGTOOLS
P S 1 6 SYSIEM PAGE 81
logfile's extension is always LOG. The drive specification, path and filename must not
exceed 24 characters.
The filter specified gives the program the condition for starting the log. The two bytes
specified by the filter must match the first two bytes of the transmitted telegram for the
program to trigger. If, for example, we wanted to start logging only after having received a
fire message from address number two then the two bytes must be specified as follows:
Byte 1 : 0000 0010 - The first four bits specify the to address, and the last
four bits the from address.
Byte 2 : 00001010 - This is the function code for fire expressed in binary.
The code for fire is 10 decimal.
Any bit in the two bytes may be specified as don't care by entering an x instead of 0 or 1. If
byte 1 above had been specified as 'XXXXXXXX' then the program would have triggered
on any telegram where byte 2 was 10.
If no filter is specified, (byte 1 and byte 2 specified as XXXXXXXX), then the program
will trigger on the first telegram it sees.
After the program has triggered it will log every telegram that occurs. But it will not log
Loop Card check telegrams, Loop Card reply telegrams and front card acknowledge tele-
grams if the filter is left on. It is recommended that a filter is used since the logfile would
get extremely large if the log was left on for a long time.
-
Often we don't know what trigger to specify, but at the same time we don't want to log all
the Loop Card check related telegrams. In this case the following procedure may be fol-
lowed:
2. As soon as the message Waiting for trigger is displayed, the filter is turned off
by pressing '.' (full stop). Now wait for the program to trigger. It will trigger on
the first telegram it sees. Normally this would be a Loop Card check telegram.
3. Turn the filter back on to prevent the program from logging any subsequent
Loop Card check related telegrams. The program will continue to log even
though a telegram matching the specified trigger never was found.
Things to remember:
All parts of the PBSVIEW program may be used while logging, however, one must remem-
ber that all messages sent from PBSVIEW are logged. This means that one for example
would get a huge file filled with PBSVIEW requests and Loop Card answers if the auto
mode is on while detector values are being checked.
\
. /'
INSTALLATION AND SERVICING MANUAL APPENDIX B: SERVICE AND COMMISSlONING TOOLS
P S 1 6SYSEM PAGE 82
If telegrams are constantly being sent on the communication loop the PBSVIEW program
may 'crash' if one attempts to select the log function. The reason for this seems to be that
the input communication buffer overflows while the program halts to read log parameters .-
such as logfile name and trigger bytes. This situation should not arise under normal
circumstances, but only happens if a new telegram is constantly being sent only millisec-
onds after the previous sending has ended.
I N S l . A L M I I O N AND SERVICING MANUAL APPENDIX C: DIP-SWITCH SElTINGS
P S 1 6 SYSTEM PAGE 83
APPENDIX C
DIP-SWITCH SETTINGS
On each PBS-16 and US-16 module, there is a DIP-Switch, whose setting determines the
address of the module, and the addresses of lines and loops associated with it. The DIP-
Switch is binary-coded, and the code for each module is given in the customised documen-
tation. It is possible for PBS-16 and US-16 modules to have addresses on the communica-
tion loop between 1 and 15. Note that no 'holes' are allowed in the address range on the
communication loop, and that the addressing of PBS-16s or US-16s connected to the loop
must start with address no. 1.
.,
Also RU-16s or other units with their own Loop Card have their own address on the com-
munication loop, but these units have no DIP switch for setting the address. Instead the
address is programmed into the Cause and Effect programme included on the Loop Card.
The general rule for assigning addresses on the communication loop is that PBS-16s and
US-16s are always given addresses from 1 up to the total number of such units in the sys-
tem. Other units with Loop Cards, such as the RU-161, are then numbered starting with
the first available address and numbered sequentially up to the total number of Loop Cards
in the system. No 'holes' in the address range on the communication loop are allowed, and
the total number of Loop Cards in the system must never be greater than 15.
Also each address unit has a DIP-switch which determines which address the address unit is
given on the detection line or detection loop it is connected to. Address units may be given
addresses between 1 and 96, but remember that no 'holes' are allowed in the address range
on any one loop or line. It is, however, allowed to start addressing at, say, address no. 12,
provided the addressing is sequential from this number up to the highest address on the
line or loop leaving no 'holes' or 'gaps'.
DIP-switch coding and its significance is given in Table C.1. Codes are to be set for each
module in accordance with the table and the customer documentation.
When setting the address, the DIP-switch location corresponding to the bit number should
be set as specified in the table. One (1) signifies that the switch position should be set to
On, while Zero (0) means that it should be Off. The switch position number corresponds
to the bit number in the binary digit.
> DIP-switch positions 1 , 4 and 5 should be set to On (1) and the rest should be set to Off (0).
-
l'
INSTALLATION AND SERVICING MANUAL APPENDIX C: DIPSWITCH SEITINGS
P m 1 6 SYSTEiM PAGE 84
Table C.l
A = Address
NOTE: A zero (0) specifies a DIP-switch position set to OFF, and a one (1) specifies
that the corresponding DIP-switch position should be set to ON.
\
.A
INSTALLATION AND SERVICIXG ILWIYUAL APPENDIX D: TESIIXG MODULES IN ISOLATION
P m 1 6S
Y- PAGE 85
APPENDIX D
The only module that can be fully checked in isolation is the PBS-16 module. The reason
for this is that it is only this module that have a man/machine interface (PS-16 Control and
Information Panel). The PBSVIEW test and commissioning tool may only be used if the
internal Communication Bus is operational. This Comms Bus is a current loop, and the
current originates from the PS-16 panel. It is therefore not possible to connect PBSVIEW
to a module that is not in some way linked to a PS-16 Control and Information panel.
The PBS-16 module can be fully tested in isolation. The US-16 motherboard the PS-16 is
connected to will normally have its DIP-switch set to address 1. This may not be the case if
there is more than one PBS-16 module in the system, or if a different numbering conven-
tion have been used. To proceed with the test the US-16 motherboard DIP-switch marked
S1 must be set to address 1. How to do this is explained in Appendix C.
The module is now tested as explained in chapter 6, sections 6.1 up to 6.9.2 inclusive. A
complete test of the module have now been carried out. If the modules address on the
Comms Bus is different to 1 must the S1 DIP-switch be correctly set before the module is
connected to the rest of the system.
Note that the ST2 and ST3 bridging links, (see fig. 6.2), on the US-16 motherboard should
only be cut if the module is the main PBS-16 module in the system. If there is only one
PBS-16 module should the links be cut on that unit.
Also the US-16 module may be fully tested in isolation if a PS-16 Control and Information
panel is temporarily connected to it. The module then,effectivelybecomes a PBS-16 mod- , ..
ule and testing is as explained for that module. Note that the bridging links ST2 and ST3
never should be cut on a US-16 module.
If a PS-16 panel is not available is only a series of visual inspections possible before con-
nection to the Internal Communication Bus.
a. Check that all wiring for the charger and battery connection is correct. If the module
is not used to monitor the battery or charger should this monitoring have been dis-
abled. This is done by removing two PTC resistors and connecting a short circuit
between X1/4 (Mains Con.) and X2/1 (Battery +). The two PTC resistors are
WALLATION AYD ~ERVICIXG
MANUAL APPEXDIX D: TESTING ,MODULES I N ISOLATION
P S 1 6 SY!XEIM PAGE 86
marked R52 and R71 and are located directly below the relays on the US-16 mother-
board.
Check that the Loop Card is present and is correctly plugged into the P3 edge con-
nector. The card must be pushed all the way down unto the connector. Also check
that the Loop Card has the correct type of software plugged in. See Appendix H for
microprocessor markings and Operator's Manual Part 2 for Cause and Effect
EPROM markings.
Check that the S1 switch is set to the correct address. See Appendix C.
Check all detector lines or loops for short circuits and open circuits. Make sure all
wires are correctly terminated.
Check the alarm bell circuits for short circuits and open circuits. Check that the EOL
resistor (10 kohm) is correctly connected and of the correct value. Check that the
sounder devices are polarised and connected the correct way around.
Check all circuits connected to the Control Relays and the Fault Relay.
Check that the circuitry connected to the Voltage Failure terminals operate.
Check that the equipment powered from the three 24V DC outputs are not short
circuit.
If an RS-unit is connected check that it is correctly connected. See figures 5.3'5.4 and
5.5. Also check that all circuits connected to this unit is correctly wired and have no
short circuits.
1. All faults revealed during the checks specified in points (a) to (k) must be put right.
The module should now be connected to the Communication Bus. The module is
powered up as explained in sections 6.3 and 6.4 and commissioning continues as
explained in section 6.10.3.
These modules may only be visually inspected before they are connected to the Communi-
cation Bus and powered up.
1 c. Check the wiring of all connected circuits. This is particular important for the IF-16
1'
lNSTALLATION AND SERVICING M W A L APPENDIX D: TESTING MODULES IN ISOLATIOK
P S 1 6 SYSIEM PACE 87
with loop card since no protection is provided for its inputs or outputs.
d. Check that all wires are terminated correctly at the correct terminal.
e. Check that RS-units are correctly connected and that all circuits connected to them
have no short circuits or other wiring faults.
f. Check that the Loop Card is pushed all the way onto the edge connector. Check that
the Loop Card is fitted with the correct microprocessor and Cause and Effect
EPROM. An EPROM must always be included on the Loop Card controlling Relay
Units. Microprocessor markings are explained in Appendix H, while C&E EPROM
markings are explained in Operator's Manual Part 2.
g. Correct all faults found during points (a) to (f). Connect the module to the Commu-
nication Bus and carry on the commissioning procedure as explained in section 6.10.4.
These units are inspected during the inspection of the modules they are connected to. See
D.2 and D.3.
b. Check Operator's Manual Part 2 to find out if a Text EPROM should be fitted at the
back of the SRP-16's PCB. Check that EPROM is fitted correctly and that the mark-
ing matches the marking specified in Operator's Manual Part 2.
d. Connect the Communication Bus and check that the correct messages are displayed
when faults or fires are simulated.
e. Check that- the module operates as configured. Check Silence and Reset. Check
Operator's Manual Part 2 to find out if any Cause and Effect for the SRP-16's relays
is included, and test this for correct response if it is.
I N S T A U T I O N AND SERVICING MANUAL APPENDIX E: SEITING UP THE COM-16 COMMUNICATIONCARD
P S 1 6 SYSIEU PAGE 88
APPENDIX E
The COM-16 Communication Card may only be used in a US-16 that has a PS-16 front
connected. The combination of a PS-16 and a US-16 is usually referred to as a PBS-16.
The Communication Card is controlled by the PS-16 card through the 40-way ribbon cable
used to connect the PS-16 to the US-16 motherboard. The COM-16 card is placed in the
slot provided on the motherboard.
CAUTION!
The Communication Card has two communication ports. Port 1 is a RS-232C port and is
usually used for printer connection. Port 1is the connector marked P3, and it is the left-
most connector. The DIP switch marked S1 is used to select the communication speed (ie.
the Baud rate) for this port. This switch is located to the far right on the card. Baud rates
available are 300,600,1200,2400,4800 and 9600. Normally the 9600 baud rate is used
when a printer is connected. Note that only one of the switches in S1 may be set to ON at
the same time. A good way to remember which switch belongs to which port is to remem-
ber that the rightmost switch belongs to the leftmost port.
Port 2 is normally used for communication with other PBS-16 systems or a computer. Port
2 is the connector marked P2. Three different configurations may be selected for this port.
This is done with DIP switch S3. Only one of the switches in S3 may be set to On at any
one time. The marking on the card indicates how to select between the following configu-
rations:
RS-232C
20mA current loop
RS485
NOTE that RS-232C is also the normal configuration for Port 2, and that the PS-16 soft-
ware determines which configurations may be used in your system See Operator's Manual
Part 2.
i
The Baud rate for Port 2 is selected by using DIP switch S2. The normal speed for commu-
.J nication with a computer using the PBSVIEW diagnostic software is 2400. Note that only
one of the switches in S2 may be set to ON at any one time.
INSTALLATION AND SERVICING MANUAL APPENDIX F: PRJNlER CONNECTIONS
P S 1 6 SYSIEM PACE 89
APPENDIX F
PRINTER CONNECTIONS
For a printer to be used with the system, there must be a COM-16 Card fitted in socket P2
on the Loop Card on the master PBS-16 module.
CAUTION!
PBS-16 Printer
(25 pin) (25 pin)
INSTALLATION AiiD SERVICING MANUAL APPESDIX F: PRINTER CONNECTIONS
P m 1 6 SYSIEM P.4GE 90
PBS-16 Printer
(25 pin) (9 pin)
For some languages the Message Display on the PS-16 card and on the SRP-16 are able to
. . display special characters unique to that language. For these languages some care must be
taken to make sure that the printer you connect can be set up to print these special charac-
ters without using special software escape codes. Normally this is no problem unless the
special characters have ASCII codes greater than 127. If the special characters for the
language you want to use have ASCII codes greater than 127 the printer you want to con-
nect must be set up to support these characters. The selection of the correct character set
must be done on the printer either in hardware or from a special printer menu. The PBS-
16 supports no escape codes, and will therefore only support the printers where the correct
character set may be selected without using such codes. Please refer to your printer's user
manual or ask your printer dealer for further advice.
INSTALLATION AND SERVICING MANUAL APPENDIX G: KEYPAD SERVICE FUNCTIONS
PBS16 S Y S E M PAGE 91
APPENDIX G
The Operating Manual lists and describes the use of many of the functions available by use
of the keypad. These include functions 1 to 15, 17 and 18.
These functions are primarily for the use of service personnel, and some of them may not
be available on all panels.
The functions written in bold are only available when a printer or computer is connected to
the system.
Function
16 Search Faults
APPENDIX H
PBS16SA
AD Ver. 3.0
The first line refers to what type of card the processor belongs to. PBS16SA is the official
name of the Loop Card. This line does not specify where this Loop Card is used.
The second line specifies exactly what type of software has been burnt into the processor's
internal EPROM. This line consists of a few letters indicating the program type and a . ..
version identifier.
RU16 Processor intended to be used on a Loop Card placed in a RU-16. Later ver-
sions of this software (Version 3.0 or later) are also compatible with the
RU-161. This chip may also be used on a Loop Card on the IF-16 interface card
to make a mimic driver.
RU16I Identical to same version of the RU16 software. Very few chips with this mark-
ing have been made, and in the future, probably only the RU16 marking will be
used, since they are identical.
The version number indicated on the marking label is the same as the version number one
gets by using function 26 from the PS-16 Control Panel.
INSTALLATION AND SERVICING MANUAL APPENDIX H: MICROPROCESSORAND EPROM MARKINGS
P S 1 6S
Y- PAGE 93
H 2 EPROM Markings
This section only applies to EPROMs contained in the core software for the PS-16 Control
Panel (that is, the PBS-16 front card).
PBS16FA
ADEN Ver. 3.11
As for the Loop Card processors, the first line only indicates what type of card the EPROM
is made to work with. PBS16FA is equivalent to the PS-16 card, or the PBS-16 front card
as it is sometimes known.
The second line consists of four letter indicating loop or line type, line or loop configura-
tion, and language used for the text display. The rest of the line is for version number
identification.
The two first letters have the same meaning as the letters on the second line of the marking
of the Loop Card processors. (Only those intended to be used with a Loop Card placed in
a US-16 module). The last two letters indicate the language.
The version number indicated on the marking label is the same as the version number one
gets by using function 26 from the PS-16 Control Panel. A PS-16 panel always has address
0 (zero), even if there is more than one control panel in the system.
1
INSTALIATION AND SERVICIXG LMANUAL APPENDIX I: LOOP AND LINE NUMBERS
P S 1 6 SY!nEM PAGE 9.1
APPENDIX I
The quiescent current on a loop may be read by using function 19 on the front panel.
When there is more than one module in the system, the loops or lines are numbered ac-
cording to the address on the communication bus given to the unit they are connected to.
Table L1 shows which loop or line numbers corresponds to the different addresses on the
communication bus.
Function 19 may also be used to read the value on one of the RU-161 analogue inputs. But
when this is done the following points must be remembered:
1. In a line system the RU-161 analogue input gets the same number as the correspond-
ing line would have had if the RU-161 had been a US-16. So if the RU-161 has ad-
dress 5 on the communication bus inputs 1to 16 are referred to as lines 65 to 80 when
using function 19.
2. In a loop system function 19 cannot be used in the same way. The reason for this is
that function 19 only returns the value read on the low end of a loop. This means that
only the first eight of the RU-16I's inputs can be checked from the keyboard. The
other eight inputs (analogue inputs 9-16) can be checked by using PBSVIEW. The
easiest way to do this is to press F3 while in Diagnostic Mode. This automatically
puts up all loop currents read from both ends of the loop for every module connected.
The loop or line number may also be calculated by considering the module address, system
configuration, and the detection input number the line or loop is connected to. The equa-
tions below show how this is done:
Table 1.1
APPENDIX J
IF-l6 CONNECTIONS
The IF-16 Interface Card has a edge connector which is used for either plugging in a Loop
Card or a RS-56 Output Driver Card. Two rows of connection terminal blocks enable
wires to be connected to the plugged-in card's various input and output lines. The card has
a 5V regulator which is enabled when the straps located directly above connection terminal
block X1 is fitted.
It is absolutely essential that one look directly down on the card when a wire is connected
to the card. It is very easy to connect a wire to the neighbouring terminal if one is at an
angle to the card while the wire is being inserted into the terminal block.
The IF-16 on-board 5V regulator must be enabled. This is done by fitting the straps lo-
cated directly above connection terminal block XI.
When the Loop Card is used together with the IF-16 a wide range of the Loop Cards input
and output possibilities are available.
16 Analogue inputs.
3 Digital inputs.
The Loop Card must carry the same Core Software as the Loop Cards used in a RU-16 or
a RU-161. The 16 analogue inputs, the 16 24VDC outputs and the connection terminals for
RS-Units are, apart from lack of protection and missing relays, identical to the correspond-
ing inputs and outputs on the RU-161. The three digital inputs are, apart from missing
protection, the same as the auxiliary inputs on the US-16. In Cause and Effect the inputs
and outputs provided are used in exactly the same way as the corresponding inputs and
outputs on the RU-161 and the US-16.
INSTALLATION A h D SERVICING MANUAL APPEVDIX J: IF-16 CONNECTIONS
P S 1 6 SYSTEM PAGE 97
WARNING!
The inputs and outputs have no protection against overloading, over-voltage or noise. If
this is required must this be fitted externally or other modules must be used. It is abso-
lutely essential that input and output currents are kept within the specified limits.
Note that the 24VDC input may be connected to terminals X112 and X113 or X212 and
X2/3. The 24VDC connection terminals not used for 24VDC feed becomes a spare set of
connection terminals for 24VDC output. So if the 24VDC feed is connected to the termi-
nals in block X1 can the 24VDC feed to other equipment be taken from the terminals in
block X . .
Figure J.l shows the function of each of the connections terminals on the IF-16 when used
with a Loop Card.
Outputs 1 to 16 can drive relays or LEDs, but the maximum current drive per output is 100
mA.
Inputs 1 to 16 can take voltage between OV and 5V. The input impedance is 100 ohms. A
series resistor should be fitted to limit the possible input current to maximum 50 mA.
The clock and data outputs are common for all RS-Units connected, but a separate enable
line is provided for each RS-Unit. The RS-Enable line used determines the output num-
bers associated with the various RS-Units.
The IF-16 on-board 5V regulator must be disabled. It is disabled if the straps located
directly above terminal connection block X1 are cut or not fitted at all.
The RS-56 used together with the IF-16 provides 56 24VDC switchable outputs. These
outputs are suitable for driving LEDs or relays. The RS-56 is controlled by the Loop Card
it is connected to, and the Cause and Effect fitted on that card determines which outputs
are operated upon certain events in the system.
Note that the maximum current.allowed drawn from a single output is 100 mA. The maxi-
mum total load (all 56 outputs) allowed is 2A.
INSTALLATION AND SERVICIXG MANUAL APPEhDIX J: IF-16 CONNECTIONS
P S 1 6 SYSIEN PAGE 98
I
-
ts=l X1
NC 1 1
+24VDC 2 2 +UVDC
OVDC 3 3 OV DC
NC 4 4 KC
ANALOGUE INPUT I s 5 OLTPUT l
AYALOGUE I W U T 2 6 PI 6 OUTPUT2
ANALOGUE INPUT 3 7 7 OUTPLT 3
A i L O G U E II\;PUT4 8 8 OUTPUT4
AYALOGUE INPUT S 9 9 OLTPUT S
ANALOGUE IXPUT 6 10 10 OUTPUT6
ANALOGUE ISPUT 7 i i 11 O ~ r n U 7T
ANALOGUE ISPUT 8 12 12 OUTPbT 8
AXALOGUE IXPUT 9 1 3 13 ObTPUT 9
ANALOGUE IXPUT 10 14 14 OUTPUT l0
A U L O G U E IhTUT 11 15 15 O b T P b T 11
ANALOGUE ISPUT 12 16 16 OIA-F'UT 12
ANALOGUE ISPUT 13 l7 17 OUTPUT D
ANALOGUE IXPUT 14 '8 18 ObiTPUT 14
ANALOGUE ISPUT 15 '9 19 OUTPUT IS
AWALOGUE ISPUT 16 20 20 OLTPUT 16
NC 21 21
h'c 22 22
Mfhsv I PUT2 23 23
INPUT1 24 24
ENABLE XO. 4 25 25 ESABLE NO. 2
ENABLE NO. 3 26 26 EXABLE SO. 1
CLOCKOliTPbT 27 27 DATA OUTPLT
NC 28 23 NC
COhl. BUS. (+) 29 29 COh1. BUS. (-)
NC M 30 KC
OVDC 31 31 NC
OVDC 32 32
Connections available on the IF-16 when used with the PBS16SA Loop Card. This combination is also able to
drive up to four RS-units (ie. RS-16, RS-32 or RS-56).
NOTE: Outputs 1 to 16 can drive relays or LEDs. The maximum drive current is lOOm.4 per output.
The Clock and Data outputs are common for all RS-units connected. A seperate Enable output is provided for
each connected RS-unit and sets the range of relay numbers associated with each individual card.
Inputs 1 to 16 can handle maximum +5V DC. The input impedance is 100 ohms.
NOTE: No protection is provided on 5V inputs and outputs. Burnout will occur if maximum ratings are
exceeded.
a
+BVDC 1
2 OV DC
OLVUTI 3 3 OUTPUT 2
OUTPUT3 4 OUTPUT 4
OUTPUTS 5 5 OUTPUT 6
oLwUT7 6 PI 6 OLTPUT 8
OUTPUT9 7 7 OUTPUT l 0
OUTPLT 11 a OUTPUT 12
OUTPUT13 9 OUTPUT 14
O b V U T 15 '0 l0 OUTPUT 16
OLTPUT 17 1' 11 OLTPUT l 8
OLTPUT 19 12 12 OUTPUT 20
Ou'lTUT 21 l 3 13 OUTPUT22
Obm'UTU l4 I4 OUTPUT 24
OLTPW 25 l 5 15 OUTPUT 26
OLTPLT27 1" 16 OUTPUT 28
O L T P U T ~ ~17 I: OUTPUT30
OLTPUT31 18 18 OUTPUT 32
OUTPUT33 l9 19 OUTPLT 33
OLTPUT35 20 20 OUTPUT 36
OLTPUT37 21 21 OLTPUT 38
OUTPUT39 22 22 OUTPUT40
OUTPUT41 23 23 OUTPUT 42
O L T P U T ~ ~24 24 OUTPUT 44
OLTPUT45 25 :
2 ObTPUT 46
OUTPUT47 26 26 OUTPUT48
0 ~ ~ ~ 1 x 4279 27 OUTPLT 50
ObTPbTS1 28 28 OUTPUT52
OLTPUT53 29 29 OLTPUT 54
OLTPUTSS 30 30 OUTPUT56
3l ENABLE
CLOCKINPUT 32 s2 DATA IXPLT
Connections available on the IF-16 when used with the RS-56 output driver card.
NOTE: Outputs 1 to 56 can drive relays or LEDs. The maximum drive current is lOOrnA per output. The
total current for all 56 outputs combined must not exceed 2A.
Fig. 5.2 IF-16 Connections When Used With The RS-56 Card
INSTALLATION AlVD SERVICING LMANUAL APPENDIX K: CONNECnlVG RS16, RS32 AND m 5 6 TO RELAY UNITS
P m 1 6 SYSIEM PAGE 100
APPENDIX K
The following units may all have up to four RS-Units connected to them:
RU-16
RU- 161
Loop Card Placed On IF-16 Card. (See fig. J.1)
Through the rest of this appendix I will refer to all these units as Relay Units.
In Cause and Effect certain parameters are set to signal certain things to the microproces-
sor. Parameter 11 (P[11]) is used to inform the microprocessor if the loop card is control-
ling RS-16s or RS-56s. This parameter must always be set if the Relay Unit has a RS-32 or
a RS-56 connected.
In the tables below the output numbers listed is the relay number used in Cause and Effect
programming.
Table K.1 lists the outputs available when only RS-16s are connected to the Relay Unit.
Table K.2 lists the outputs available when only RS-32s are connected to the Relay Unit.
-
Note that gaps are left in the output number range when RS-32s are connected. The rea-
' . son for this is that the Relay Unit does not know what type of relay units it has connected.
All it knows is that it is,not RS-16s that it has connected. It therefore assumes that each
RS-Unit connected is a RS-56. This means that it will shift out 56 bits of data for every RS-
Unit. The RS-32 only needs 32 bits of data and loses the 24 first bits shifted out. So output
one on the RS-32 becomes what would have been output 25 if a RS-56 had been con-
nected.
Table K.3 lists the outputs available when only RS-56s are connected to the Relay Unit.
INSTALLATION AND SERVICING MANUAL APPENDIX K: CONNECTING RS-16, S 3 2 AhII S 5 6 TO RELAY UNITS
PBS16 SY!iXEN PAGE 101
Normally all RS-Units connected to the same Relay Unit is of the same type, but with some
care planning it is possible to connect different types of RS-Units to the same RU-16.
It is while making the Cause and Effect programme that this care must be taken. The
reason for this is that the Loop Card can, in Cause and Effect, be told that wether it has
RS-16s or RS-56s connected. If different types of RS-Units are to be mixed the Loop Card
must be told that it has RS-56s connected. This is done by setting parameter 11(P[11])in
INSTALLATION AND SERVICISG 5L4NUAL APPESDIX K COSNECTISG RS-16,S 3 2 ASD S 5 6 TO RELAY USlTS
PBS-16 SYSTE.? PAGE 102
The effect of connecting different types of RS-Units to the same Relay Unit is similar to
what happens when only RS-32s are connected to it. This is explained in section K.1.
What happens is that the output numbers available will vary depending on what type of RS-
Units are connected and on which RS-Enable line it is connected to.
The Relay Unit assumes it has up to four RS-56s connected to it. The RS-56s outputs
would, in Cause and Effect, be numbered from 17 to 240. The output numbers for each
connected RS-Unit is shown in Table K.3.
An RS-56 connected will always occupy the output numbers specified in table K.3 for that
particular RS-Unit. The last available output on the RS-Unit connected will always have
the same output number as an RS-56 connected to the same RS-Enable line would have
had. If the RS-Unit is connected to RS-Enable line no. 3 will the last output on that RS-
Unit have the output number 184. (See Table K.3).
The output number for the first output on the RS-Unit is found by simply taking the nurn-
ber already found, add one, and then subtract the number of outputs on the RS-Unit con-
nected. If the first number we found was 184 and we have connected an RS-16 to RS-
Enable line no. 3 then the first output number is:
Table K.4 shows the output numbers we would have got if we had had the following RS-
Units connected to a Relay Unit:
Table K.4 Output Numbers Available With Different Types Of RS-Units Connected.
APPENDIX L
The SRP-16 has a four pole DIP-switch located at the back of the PCB. Only three of the
four switches are used and table L.l describes their function.
The SRP-16 has one row containing four keys. Numbering the keys from left to right they
have the following functions:
Key 1 LIGHT.
The Message Display's backlight is turned on while this key is pressed. The light is
turned off when the key is released.
The lamps bracketing the Message Display is turned on when this key is pressed.
The SRP-16's internal buzzer is turned off when this key is pressed. If DIP-switch
position 1 is set to On will this key, when pressed, give a system Silence, silencing all
audible alarms in the system.
If more than one alarm have been received is each message in turn displayed in the
INSTALLAnON AND SERVICING MANUAL APPENDIX L: CONFIGURISG A h D OPERATING THE SRP-16
PBS-16 S Y S E M PAGE 104
Keys 3 + 4 RESET
If DIP-switch position 1 is set to On a Global Reset is issued when keys 3 and 4 are
pressed at the same time. Pressing this combination has no effect if DIP-switch posi-
tion 1 is set to Off.
STALLAT AT ION A S D SERVICIXG ,MA.YUAL APPESDIX LW TECHNCAL SPECIFICATIOI\;S
P S 1 6 SYSEIM PAGE 105
APPENDIX M
TECHNICAL SPECIFICATIONS
Mains:
Standby supply:
Nominal: 24 VDC
Tolerance: +20% / -10%
Quiescent current:
Current drawn during fault (max):
Current drawn during fire (ma,,):
Add for buzzer operating:
Quiescent current: 70 mA
Add for each relay operated: 30 mA
Current drawn during fault: 90 mA
Current drawn during fire (silence not pressed): 290 mA (peak)
Current drawn during fire (silence not pressed): 230 mA (average)
Current drawn during fire (silence pressed): 160 mA
For the detection circuits the current drawn is the same both in the quiescent state
and in the fire state. The current to be added is determined by using the following
formulae:
Including PS-16 front card, PBS16TE2 motherboard, PBS16SA Loop Card. No detectors
connected.
For the detection circuits the current is the same both in the quiescent state and in
the fire state. The current to be added is determined by using the following formulae:
Quiescent current:
Add for buzzer operating:
Add for each energised relay:
Total current with all relays energised:
Relays:
16 relays all of which are single throw with C, NO and NC connection terminals
provided. Relays rated at 24 VDC/ 2A.
Quiescent current:
Add for buzzer operating:
Add for each energised relay:
Total current with all relays energised:
Relays:
16 relays all of which are single throw with C, NO and NC connection terminals
provided. Relays rated at 24 VDC/ 2A.
Inputs:
16 analogue inputs. Inputs are protected against short circuit and overvoltage.
Quiescent current:
Add for each energised relay:
Total current with all relays energised:
Relays:
16 relays all of which are single throw with C, NO and NC connection terminals
provided. Relays rated at 24 VDC/ 2A.
lSSTALLATlON AND SERVICISG MASUAL APPESDIX M: TECHSICAL SPECIFICATIOXS
PS16S Y m M PACE 108
Quiescent current:
Current drawn during fault in system:
Average:
Peak:
During fire in the system:
Quiescent current. 20 mA
Current drawn during fire in the system:
With only one detector indicating fire: 170 mA
With more than one detector ind. fire: 195 mA
Add for each special indicator LED lit: 10 mA
Address units:
Example:
For address 14, which is 00001110 in binary, the quiescent current would be:
For address units that have devices connected to it (e.g. detectors and sensors), the
current drawn by this device must be added to find the total current consumed by
each address on the line or loop.
Current consumption:
INSTALLATION ASD SERVICISG ~IASUAL APPESDIX W TECHSICAL SPECIFICATIONS
P S 1 6 SYSTEM PAGE 109
Quiescent current:
Add for each diode that is lit up:
Total current with all diodes on:
Quiescent current: 30 mA
With no load connected each activated output will draw: 2 mA
Maximum output current (single output): 100 mA
Maximum total current drawn from the outputs: 2A
The current consumed by the whole module is found by adding the current drawn
. . from each activated output to the quiescent current. The 2 mA current must be
added for each activated output.
Example:
Only five outputs are used, and each output drives a 50 mA load. The total current
consumed by the modules will be:
Quiescent current: 20 mA
Add for each unloaded output that is operated: 2mA
Analogue inputs:
16 analogue inputs. Inputs are not protected and damage will occur if maximum
ratings are exceeded.
Digital inputs:
This combination also offers one external buzzer connection, and four sets of connec-
tion terminals for RS-units. Used together with four RS-56 cards the Loop Card can
control up to 240 outputs.
INSTALLATION AND SERVlClSG m X L A L APPENDIX N: COlVDITlONS OF SALE
PBS-16 SYSTEM PAGE 111
APPENDIX N
CONDITIONS OF SALE
(As of 14.03.1990)
1. GENERAL
All quotations are made and all orders are accepted subject to the following terms
and conditions, and no addition hereto or variation therein shall be made unless
agreed in writing by both parties.
2. PRICE
Prices are per unit in NOK, ex-works in Oslo, exclusive of packaging, VAT and/or
taxes.
3. TERMS OF PAYMENT
5. DELIVERY
Products will be delivered ex-works our stock in Oslo unless stated otherwise. Any
times quoted for despatch shall be treated as estimates only. In all cases, the time for
despatch shall be extended by a period of time equivalent to that incurred as a result
of the instructions or lack of instructions from the client, industrial dispute, or any
cause whatsoever beyond our control.
If, due to instructions or lack of instructions from the customer, despatch in accor-
dance with the order is delayed for 14 days after the customer has been notified that
the goods are ready for despatch, the goods become the property of the customer who
shall arrange delivery or storage. It should be noted that in accordance with clause 2
(Price) the goods will be invoiced and if at all possible, stored in our warehouse at
IXXALLATION AND SERVICISG MASUAI, APPENDIX N: CONDITIONS OF SALE
PBS-16 SY5fEM PAGE 112
that time (current rate is fixed at NOK 25,- per square meter/per month). Should
storage, however, not be feasible, the best possible alternative will be found and all
resulting charges invoiced to the customer.
7. CLAIMS
Unless otherwise agreed, defective goods or goods not in compliance with the order
must be reported as being so within one week after receipt by the customer. If an in-
surance policy has been requested by the client in accordance with clause 5, it should
be noted that the client will be responsible to introduce the claim to the insurer.
A twelve calendar month warranty from the date of delivery will cover all goods
which have defects in material or workmanship, and which have been used for the ap-
propriate purpose in the manner recommended, on the condition that these parts
should be returned if we so require.
To qualify for repair under guarantee, the products must be returned to our works
properly packed, freight prepaid, together with an order listing the number and type
of products being returned, the serial numbers of the products, and details of defects
or fault symptoms.
Our liability under this clause shall be in lieu of any warranty or condition implied by
law as to the quality or fitness for any particular purpose of the goods. Also, unless
otherwise stipulated in this clause this warranty specifically excludes incidental and
consequential damages of every type and description resulting from any claimed
defect in material or workmanship, including but not limited to, personal injuries and
property damages.
9. LEGAL JURISDICTION
Unless otherwise agreed in writing the contract shall be subject to and governed by
Norwegian Law, and treated by the Norwegian courts.
ISSTALLATIOS A S D SERVlClSG .MANUAL INDEX
P m 1 6 SYSE.M PAGE 113
INDEX
Mains PBSVEW
1,31,43-45, 62,72,85,105 9,49-52,57, 61, 63, 66,68-70,76-77,79-S2,S5,
Mains Check 8S,94
44 Polarity
Mains Fault 31,3436, 43, 51,55,57,77
44-45,72 Port
Maintenance 25,61-65,76,78,88
91 Power Fuse
Major Component Failure 37,45
63 Power Supply
Manual Call Points (See MCP) 30-32, 43-45, 49-50, 51,57, 60, 62, 65-66, 70,72,
89
Manual Control Printer
9 8-9, 18,25, 42, 49,54, 60, 64-65,76,78-79,88-91
Marking Processor
5,24, 43,86-SS, 92-93 5, 7,9, 17, 19,24-26,60, 63-64,78, 86-87,92-93,
hlCP 100
5-7, 11-14 PS-16
Rleggars 5,7,9, 17-19,22,25, 42, 51,57,61-68,70-72, 75,
47, 51, 58 85,8S, 90-93,105-106
Message Quiescent Current
7,9, 17, 19,24,35-37,4547, 49-51, 55,5S, 94,105-109
60-63,66-72,75,77-80,87, 103 Re-initialised
Message Display 49,57
7, 17, 19,22,51,55, 58, 60-63,67-68,70-72,90, Reconnect Detector
103-103 50
Mimic Driver Reconnect Loop
20,92 50
Mimic Panel Relay Slave Unit
24, 26, 65 10,15, 18, 19,20, 26, 57,87, 107
Modem Relay Unit
78,91 15, 19-20, 24-26, 57,8647, 100-102,107
hlonitoring Relays
6-8,30-31,43-44,56, 60-61,85 7,9, 10, 15, 18-20, 26,30,42-13,55,5S, 62,75,
blotherboard 86-S7,96-99,106-107
17-20,25-26,30-31,37-38,33-46,56, 61-68, Reset
70-71,85436,SS, 105-107 19,45,49,55,63,70,77,87,103-103
Next Alarm Reset Alarm
103 49
Nittan Resistor
11-14,32 6-7,20,31-32,35-36,43,46,51,67-69,71-72,
Open Circuit 85-S6,97,107,109
5-7,35,37,45,47,66-69,72,8h Ribbon Cable
Operator Control 17-1S,25,62,65,B
7 RS-16
Outputs 10, 15,20,3S, 57, 65,87,9S, 100-102,107
2,6-10, 15,lS-21,21-26,30,33-37,41-12,51-55, RS-U2C
58,60,62-63,71-72,75,86-87,96-102, 106, 10,15,25,76,8S
109-110 RS-31
Parameters 10, 15,20,26,38,57,65,87,9S, 100-102, 109
42,49-50,66,82,89,91, 100 RS-483
Parity 10,15,25,30,88
89 RS-S6
PBS-16 10, 15, 20-21, 25-26, 57,65-66,70,86-87,96-95,
1-2,5,7-10, 15, 17-IS, 24-26,31-34,37-33, 100-10',110
43-45,48,51,55-57,60-61,63.61,66,70,75-77, RS-Units
i 80,83,85,8~-~,93,106 10,15,20-21, 25-26,57,65-66,70,86-87,96,
PRS16SA 97-93,100-102,110
24-26,92,105-107, 109
ISSTALLATIOS ASD SERVICIXG .CL\SUAL ISDEX
PBSlB SY5XE.M PAGE 116