The TF228WN digital thermostat is designed to control a 3-speed fan and valve in fan coil systems. It has features like memorized time off, cycle per hour control, and random startup. The thermostat can control temperature in heating, cooling, and ventilation modes, and has options for manual or automatic fan speed selection. It has an LCD display and allows temperature to be shown in Celsius or Fahrenheit.

Uploaded by

Hạ Nhật
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
949 views12 pages

Remote FCU Manual

The TF228WN digital thermostat is designed to control a 3-speed fan and valve in fan coil systems. It has features like memorized time off, cycle per hour control, and random startup. The thermostat can control temperature in heating, cooling, and ventilation modes, and has options for manual or automatic fan speed selection. It has an LCD display and allows temperature to be shown in Celsius or Fahrenheit.

Uploaded by

Hạ Nhật
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

TF228WN Digital Thermostat

220 VAC, Fan Coil Control


SPECIFICATION DATA

Features
 Memorized time off
 Cycle Per Hour (CPH)
 Random startup
 LCD display with simple user interface
 Room temperature or setpoint temperature display
selectable
 Manual or automatic fan speed selectable
 Temperature units in either °C or °F
 User setting can be stored with power loss
 Freeze protection available
 Four keypad lock options
 Heating and cooling setpoint limitation
 Flush mount on standard 86 wall mounting box

General Specifications
Power supply 220(+10%,-15%)VAC, 50Hz
The TF228WN digital thermostat is designed for 3-speed fan
and valve control in a fan coil system, including: Control PI, On/off output
 2-pipe cool only/heat only/manual changeover
 Ventilation mode Accuracy ±1°C at 21°C
 Manual or automatic 3-speed fan control Rating capacity 3A for fan load,
 Water valve control
2A for zone valve
Besides the basic controls, TF228WN featuring CPH (Cycle Protection class IP20
Per Hour) better maintains the room temperature to the set-
point and memorized time off function can automatically Set point range 10 ~ 32°C
turn off the thermostat to save energy. Display range 0 ~ 37°C
In addition, Honeywell Random start-up function would help Ambient operating limits 0~ +49°C
to maintain power grid stability. Ambient storage limits -30 ~ +49°C
Humidity limits 5~90% RH, non-condensing

1 ECC-CDS-CT01-14A-E01-EN
Table 1. Model Selection

Model Number Backlight Application Power supply Ventilation Automatic Packing


Mode Fan
TF228WN White 2-pipe FCU 220 Vac, 50Hz Y Y bulk packing

TF228WN/U White 2-pipe FCU 220 Vac, 50Hz Y Y unit packing

Product Design Function


Thermostat Appearance Valve Control
Thermostat measures the room temperature via integrated
sensor and maintains the setpoint by delivering on/off valve
control command outputs.
The fan setting can be selected as manual or automatic 3-
speed operation. When in “manual” mode, the fan is switched
to the selected speed via control output FH (high), FM
(Medium) , FL (Low).
While in “automatic“ mode, fan speed depends on the differ-
ence between room temperature and setpoint. When room
temperature reaches the setpoint, the valve will be closed, and
the fan will be closed in the meanwhile.

Fan Speed is high or off


Difference between RT and SP

COOL
2℃
Fan Speed is medium or off
1℃
LCD Display Fan Speed is low or off
Setpoint
Fan Speed is low or off
-1℃

HEAT
Fan Speed is medium or off
-2℃
Fan Speed is high or off

Fig. 1. Fan Speed Ramping Control Algorithm

Temperature Display
The displayed temperature can be set to room temperature or
setpoint. The setting can be changed during ISU (Installation
Set Up) process.

Cycle Per Hour (CPH)


In order to achieve more accurate temperature control, the
CPH function enables the thermostat to open the valve several
times per hour as the room temperature gets close to the se-
point.
The value can be changed in the ISU, but the default values
are 4 for heating and 3 for cooling.

ECC-CDS-CT01-14A-E01-EN 2
Memorized Time 0ff
The time off feature will automatically turn off the thermostat Operating Mode
after a selectable amount of time. To change the time setting,
press and hold the power button for more than 3 seconds and Comfort Mode
press “up” and “down” button to change the value when the In comfort mode, the setpoint can be changed by pressing up
thermostat is working . and down button. Applications include cool only, heat only and
NOTE: The setting range is from 0 to 12 hours. The step is manual heat/cool changeover.
1 hour and the default value is 0.

Ventilation Mode
Press mode button to enter “ventilation” mode. In “ventilation”
mode, no output for valve while the fan will operate at selected
Backlight fan speed.
To turn on the backlight, press any key. The backlight will
timeout 8 seconds after the last key is pressed. When in ISU
and Installation test mode, the backlight will timeout 60 sec-
onds after the last key is pressed.

Keypad Lockout
Keypad lockout can be set in ISU and the default status is “all
keys available”. Keypad lock can be optioned to “mode button
locked”, “Fan and mode buttons locked”, “all buttons (except
power button) locked” and “all buttons locked”.

Dimensions (mm)
Freeze Protection Mode
Freeze protection can be selected as disabled (default) or
enabled in the ISU. In freeze protection mode (only in heating
applications), when thermostat is off and the temperature is
below 6 ℃, the thermostat will activate heating mode until the
temperature rises to 8℃.

3 ECC-CDS-CT01-14A-E01-EN
Wiring Trouble Shooting Tips
If Then...

Heating system  Set the mode to heating by press-


does not respond ing the mode button.
 Make sure the temperature is set
above the room temperature.
 Make sure “heat on” icon shows on
the display.
 Wait 5 minutes for the system to
respond.

Cooling system  Set the mode to cooling by press-


Fig. 2. Honeywell VC4013/VN4013/VS4016 Wiring does not respond ing the mode button.
 Make sure the temperature is set
below the room temperature.
 Make sure “cool on” icon shows on
the display.
 Wait 5 minutes for the system to
respond.

The fan doesn’t  Make sure fan mode isn’t set to


work auto.
 Check heating or cooling system
works well.

The mode or fan  Make sure keypad is unlocked.


button doesn’t  Check that thermostat is on.
work
Fig. 3. Honeywell VC6013/VN6013 Wiring
The up or down  Make sure keypad is unlocked.
button doesn’t  Make sure the system doesn’t
Terminal Designations
work work in ventilation mode.
 Check that thermostat is on.

Item Terminal Description The system turns  Make sure the memorized time off
off automatically value isn’t set to “0”.
1 L 220VAC live wire

2 N 220VAC neutral wire

3 vC Heating / Cooling valve close


4 vO Heating / Cooling valve open

5 FH High speed fan

6 FM Medium speed fan


7 FL Low speed fan

Automation and Control Solutions


Honeywell Environmental and Combustion Controls (Tian Jin) Co., Ltd
No. 158, NanHai Road
Tianjin Economic-Technological Development Area
Tianjin, 300457, P.R.C.

Subject to change without notice.

ECC-CDS-CT01-14A-E01-EN 4
TF228WNM/U
Communicating Fan Coil Thermostat
SPECIFICATION DATA

Specifications
Physical Layer EIA485
Protocol Modbus RTU
Baud rate 4800/9600(Default)/19200
Parity None
Error Checking Mechanism CRC
Rated Power &Frequency 220/230VAC, 50/60Hz
Power consumption <2W
Control PI, On/off output
Accuracy ±1°C at 21°C
Auto Cycle times 100,000 times
Manual Cycle times 10,000 times
Protection class IP20
Set point range 10 ~ 32°C
Monitor range 0 ~ 37°C
Ambient operating limits 0~ +49°C
Ambient storage limits -30 ~ +60°C
Humidity limits 5~90% RH, non-condensing
Action Type: 1
Pollution Degree 2
Protection against electric
shock class Class II
Electronic control software
General class Class A
The TF228WNM/U communicating thermostat is de- Rated Impulse Voltage: 2500V
signed for a 3-speed fan and a motorized valve control Maximum Temperature
in fan coil system. The typical application including: for relay wiring 155°C
 2-pipe cool only/heat only/manual changeover Wire sectional area
 Ventilation mode (Recommendation) 1.0-1.5mm 2
 Manual or automatic 3-speed fan control Applied altitude up to 2000m above sea level
 Water valve on/off control Working current for the whole product : 4(3)A
4A: When the load of the thermostat is resistance
TheTF228WNM/U is available in Modbus RTU protocol
and can be easily integrated into building automation 3A: When the load of the thermostat is inductance.
system. For Fan Load
3A:when the load is resistance;
2A: when the load is inductance
Features For Valve load
 RS485 interface in Modbus RTU slave mode 2A:when the load is resistance;
 Memorized time off 1A:when the load is inductance
The valve need have over travel-limit organ to turn off
 Cycle Per Hour (CPH)
 Random startup
 Room temperature or setpoint temperature
display selectable
 Manual or automatic fan speed selectable
 Temperature units in either °C or °F
 User setting can be stored with power loss
 Freeze protection available
 Keypad lock options
 Heating and cooling setpoint limitation
1

ECC-CDS-CT04-15B-E01-EN
Model Selection
Model Number Backlight Application Power Supply Ventilation Automatic
Mode Fan
220/230 VAC;
TF228WNM/U White 2 pipes FCU Y Y
50/60Hz

Function
Product Design
Valve Control
Thermostat appearance Thermostat measures the room temperature via inte-
grated sensor and maintains the setpoint by delivering
on/off valve control command outputs.
The fan setting can be selected as manual or automatic
3-speed operation. When in “manual” mode, the fan is
switched to the selected speed via control output FH
(High), FM (Medium) , FL (Low).
While in “automatic“ mode, fan speed depends on the
difference between room temperature and setpoint.
When room temperature reaches the setpoint, the valve
will be closed, and the fan will be closed in the mean-
while.

Fan Speed is high or off


Difference between RT and SP

COOL
2℃
Fan Speed is medium or off
1℃
Fan Speed is low or off
Setpoint
LCD Display Fan Speed is low or off
-1℃

HEAT
Fan Speed is medium or off
-2℃
Fan Speed is high or off

Fig. 1. Fan Speed Ramping Control Algorithm

Temperature Display
The displayed temperature can be set to room tempera-
ture or setpoint. The setting can be changed during ISU
(Installation Set Up) process.

Cycle Per Hour (CPH)


In order to achieve more accurate temperature control,
the CPH function enables the thermostat to open the
valve several times per hour as the room temperature
gets close to the setpoint.
The value can be changed in the ISU. The default value
is 4 for heating and 3 for cooling.

ECC-CDS-CT04-15B-E01-EN 2
Memorized Time Off Operating Mode
The time off feature will automatically turn off the ther- Comfort Mode
mostat after a selectable amount of time. To change
the time setting, press and hold the power button for In comfort mode, the setpoint can be changed by press-
more than 3 seconds and press “up” and “down” button ing up and down button. Applications include cool only,
to change the value when the thermostat is working . heat only and manual heat/cool changeover.
NOTE: The setting range is from 0 to 12 hours. The
step is 1 hour and the default value is 0.

Ventilation Mode
Press mode button to enter ventilation mode. In ventila-
tion mode, no output for valve while the fan will operate
at selected fan speed.
Backlight
To turn on the backlight, press any key. The backlight
will timeout 8 seconds after the last key is pressed.
When in ISU and Installation test mode, the backlight
will timeout 60 seconds after the last key is pressed.

Keypad Lockout
Keypad lockout can be set in ISU and the default status
is “all keys available”. Keypad lock can be optioned to
“mode button locked”, “Fan and mode buttons locked”,
“all buttons (except power button) locked” and “all but-
tons locked”.

Dimensions (mm)
Freeze Protection Mode
Freeze protection can be selected as enabled (default)
or disabled in the ISU. In freeze protection mode (only
in heating applications), when thermostat is off and the
temperature is below 6°C , the thermostat will activate
heating mode until the temperature rises to 8°C .

3 ECC-CDS-CT04-15B-E01-EN
ISU (Installation Setup) Communicating Parameter Setting
Press and hold the “mode” and the “up” buttons together When the thermostat is integrated into building
for more than 3 seconds to enter or exit ISU. Change automation system, you can make configuration refer
the ISU code by pressing the “mode” button and then below list.
change the option setting by pressing the “up” and Addr Configura-
“down” button refer to the following introduction. Significance and Prop-
Reg- tion
adjustment erties
ISU isters parameters
Description Options
Code 01 Power 0-OFF;1-ON R/W
Switch
0 Address 1~64 1(Default)
02 Room Temp Room temperature R
0 Cool only
1 Heat only 03 Temp. 0-°F;1-°C R/W
1 System Type Scale*
2 Two pipes heating/cooling
manual (Default) 04 Setpoint* Set temperature value R/W
0 °F 05 Fan Status* 0-Low speed ;1-Med R/W
2 Temp. Scale
1 °C (Default) speed;2-High speed;3-
0 Auto only Auto

1 manual only (3 speed: 06 System 0-Ventilation;1-Heat;2- R/W


3 Fan control Type Low→Med→High→Low) Mode* Cool
2 users can choose auto or
manual (Default) 07 Valve status 0-closed;1-open R
4 CPH value (heat) 1-12 4 (Default) 08 Error Code 0-None;1-Sensor 2- R
5 CPH value (cool) 1-6 3 (Default) EEprom;3-Sensor+
Display Temp. -2~2°C, 0.5°C. Default 0°C EEprom
6
adjustment (-4~4°F, 1°F. Default 0°F) 09 Baud rate R/W
0-9600 Default ;1-
0 room temp. (Default)
7 Temp. Display 4800;2-19200
1 set point
11 Address* 1~64 1( Default ) R/W
Heating Range 10~32°C. Default 32°C
8
Stops (50~90°F. Default 90°F) 12 System 0-Heat only;1-cool only;2- R/W
Cooling Range 10~32°C Default 10°C Type* Two pipes heating/cooling
9 manual (Default)
stops (50~90°F. Default 50°F)
0 All keys are available
(Default) 13 Fan Control 0-Auto;1-Manual ;2- R/W
1 system button locked out Type* Auto+Manual (Default)
2 Fan and system button 14 CPH (Heat)* 1-12 4(Default) R/W
10 Keypad lockout locked out
3 All button locked out except 15 CPH (Cool)* 1-6 3(Default) R/W
power button 16 Display 0~8(-2~2⁰C) step 1(0.5⁰C) R/W
4 All button are locked Temp. 4(Default
adjustment
0~8(-4~4⁰F) step 1(1⁰F)4
0 Disabled
11 Freeze Protection Default
1 Enable Default
17 Temp. Dis- 0- room temp. (Default);1- R/W
Power Recovery 0 OFF play* set point
12
status 1 Previous status (Default) 18 Heating 100~320 (10~32⁰C) step5 R/W
Range (0.5⁰C) 320(Default
Stops*
500~900 (50~90⁰F)step10
(1⁰F ) 900(Default

ECC-CDS-CT04-15B-E01-EN 4
19 Cooling 100~320 (10~32⁰C) R/W
Range step5(0.5⁰C)100 Wiring
stops* (Default
500~900 (50~90⁰F)
step10(1⁰F ) 500
(Default
20 Keypad lock- 0- All keys are available R/W
out * (Default);1- system but-
ton locked out;2- Fan
and system button
locked out;3- All button
locked out except power
button;4- All button are
locked
21 Freeze Pro- 0- Disabled ; 1- Enable R/W
tection* Default

22 Power Re- 0- OFF ; 1 Previous R/W


covery status (Default)
status*
Fig. 2. Honeywell VC4013/VN4013/VS4016 Wiring
29 Turn off 0~12; step 1 Unit: hour R/W
time*

30 Remain time 0~12; step 1 Unit : hour R


to turn off

Note: The parameters marked with”*” can be changed


either in ISU on site or modbus.

Terminal Designations

No Terminal Description
1 N 220/230Vac Neutral

2 L 220/230Vac Line Fig. 3. Honeywell VC6013/VN6013 Wiring


Heating / Cooling valve
3 vO
open
Heating / Cooling valve
4 vC
close
5 FH High speed fan

6 FM Medium speed fan

7 FL Low speed fan

8 D+ RS 485+

9 D- RS 485-

5 ECC-CDS-CT04-15B-E01-EN
Trouble shooting Tips
If Then...
Heating system does not respond  Set the mode to heating by pressing the mode button
 Make sure the temperature is set above the room temperature.
 Make sure “heat on” icon shows on the display
 Wait 5 minutes for the system to respond
Cooling system does not respond  Set the mode to cooling by pressing the mode button
 Make sure the temperature is set below the room temperature
 Make sure “cool on” icon shows on the display
 Wait 5 minutes for the system to respond
The fan doesn’t work  Make sure fan mode isn’t set to auto
 Check heating or cooling system works well.
The mode button doesn’t work  Make sure keypad is unlocked.
 Check that thermostat is on.
The up or down button doesn’t work  Make sure keypad is unlocked.
 Make sure the system doesn’t work in ventilation mode
 Check that thermostat is on.

The system turns off automatically  Make sure the memorized time off value isn’t set to “0”.
Display  Check the Modbus address and Baud rate. Use Master to read registers
 Check the wiring.