Remote FCU Manual
Remote FCU Manual
Features
Memorized time off
Cycle Per Hour (CPH)
Random startup
LCD display with simple user interface
Room temperature or setpoint temperature display
selectable
Manual or automatic fan speed selectable
Temperature units in either °C or °F
User setting can be stored with power loss
Freeze protection available
Four keypad lock options
Heating and cooling setpoint limitation
Flush mount on standard 86 wall mounting box
General Specifications
Power supply 220(+10%,-15%)VAC, 50Hz
The TF228WN digital thermostat is designed for 3-speed fan
and valve control in a fan coil system, including: Control PI, On/off output
2-pipe cool only/heat only/manual changeover
Ventilation mode Accuracy ±1°C at 21°C
Manual or automatic 3-speed fan control Rating capacity 3A for fan load,
Water valve control
2A for zone valve
Besides the basic controls, TF228WN featuring CPH (Cycle Protection class IP20
Per Hour) better maintains the room temperature to the set-
point and memorized time off function can automatically Set point range 10 ~ 32°C
turn off the thermostat to save energy. Display range 0 ~ 37°C
In addition, Honeywell Random start-up function would help Ambient operating limits 0~ +49°C
to maintain power grid stability. Ambient storage limits -30 ~ +49°C
Humidity limits 5~90% RH, non-condensing
1 ECC-CDS-CT01-14A-E01-EN
Table 1. Model Selection
COOL
2℃
Fan Speed is medium or off
1℃
LCD Display Fan Speed is low or off
Setpoint
Fan Speed is low or off
-1℃
HEAT
Fan Speed is medium or off
-2℃
Fan Speed is high or off
Temperature Display
The displayed temperature can be set to room temperature or
setpoint. The setting can be changed during ISU (Installation
Set Up) process.
ECC-CDS-CT01-14A-E01-EN 2
Memorized Time 0ff
The time off feature will automatically turn off the thermostat Operating Mode
after a selectable amount of time. To change the time setting,
press and hold the power button for more than 3 seconds and Comfort Mode
press “up” and “down” button to change the value when the In comfort mode, the setpoint can be changed by pressing up
thermostat is working . and down button. Applications include cool only, heat only and
NOTE: The setting range is from 0 to 12 hours. The step is manual heat/cool changeover.
1 hour and the default value is 0.
Ventilation Mode
Press mode button to enter “ventilation” mode. In “ventilation”
mode, no output for valve while the fan will operate at selected
Backlight fan speed.
To turn on the backlight, press any key. The backlight will
timeout 8 seconds after the last key is pressed. When in ISU
and Installation test mode, the backlight will timeout 60 sec-
onds after the last key is pressed.
Keypad Lockout
Keypad lockout can be set in ISU and the default status is “all
keys available”. Keypad lock can be optioned to “mode button
locked”, “Fan and mode buttons locked”, “all buttons (except
power button) locked” and “all buttons locked”.
Dimensions (mm)
Freeze Protection Mode
Freeze protection can be selected as disabled (default) or
enabled in the ISU. In freeze protection mode (only in heating
applications), when thermostat is off and the temperature is
below 6 ℃, the thermostat will activate heating mode until the
temperature rises to 8℃.
3 ECC-CDS-CT01-14A-E01-EN
Wiring Trouble Shooting Tips
If Then...
Item Terminal Description The system turns Make sure the memorized time off
off automatically value isn’t set to “0”.
1 L 220VAC live wire
ECC-CDS-CT01-14A-E01-EN 4
TF228WNM/U
Communicating Fan Coil Thermostat
SPECIFICATION DATA
Specifications
Physical Layer EIA485
Protocol Modbus RTU
Baud rate 4800/9600(Default)/19200
Parity None
Error Checking Mechanism CRC
Rated Power &Frequency 220/230VAC, 50/60Hz
Power consumption <2W
Control PI, On/off output
Accuracy ±1°C at 21°C
Auto Cycle times 100,000 times
Manual Cycle times 10,000 times
Protection class IP20
Set point range 10 ~ 32°C
Monitor range 0 ~ 37°C
Ambient operating limits 0~ +49°C
Ambient storage limits -30 ~ +60°C
Humidity limits 5~90% RH, non-condensing
Action Type: 1
Pollution Degree 2
Protection against electric
shock class Class II
Electronic control software
General class Class A
The TF228WNM/U communicating thermostat is de- Rated Impulse Voltage: 2500V
signed for a 3-speed fan and a motorized valve control Maximum Temperature
in fan coil system. The typical application including: for relay wiring 155°C
2-pipe cool only/heat only/manual changeover Wire sectional area
Ventilation mode (Recommendation) 1.0-1.5mm 2
Manual or automatic 3-speed fan control Applied altitude up to 2000m above sea level
Water valve on/off control Working current for the whole product : 4(3)A
4A: When the load of the thermostat is resistance
TheTF228WNM/U is available in Modbus RTU protocol
and can be easily integrated into building automation 3A: When the load of the thermostat is inductance.
system. For Fan Load
3A:when the load is resistance;
2A: when the load is inductance
Features For Valve load
RS485 interface in Modbus RTU slave mode 2A:when the load is resistance;
Memorized time off 1A:when the load is inductance
The valve need have over travel-limit organ to turn off
Cycle Per Hour (CPH)
Random startup
Room temperature or setpoint temperature
display selectable
Manual or automatic fan speed selectable
Temperature units in either °C or °F
User setting can be stored with power loss
Freeze protection available
Keypad lock options
Heating and cooling setpoint limitation
1
ECC-CDS-CT04-15B-E01-EN
Model Selection
Model Number Backlight Application Power Supply Ventilation Automatic
Mode Fan
220/230 VAC;
TF228WNM/U White 2 pipes FCU Y Y
50/60Hz
Function
Product Design
Valve Control
Thermostat appearance Thermostat measures the room temperature via inte-
grated sensor and maintains the setpoint by delivering
on/off valve control command outputs.
The fan setting can be selected as manual or automatic
3-speed operation. When in “manual” mode, the fan is
switched to the selected speed via control output FH
(High), FM (Medium) , FL (Low).
While in “automatic“ mode, fan speed depends on the
difference between room temperature and setpoint.
When room temperature reaches the setpoint, the valve
will be closed, and the fan will be closed in the mean-
while.
COOL
2℃
Fan Speed is medium or off
1℃
Fan Speed is low or off
Setpoint
LCD Display Fan Speed is low or off
-1℃
HEAT
Fan Speed is medium or off
-2℃
Fan Speed is high or off
Temperature Display
The displayed temperature can be set to room tempera-
ture or setpoint. The setting can be changed during ISU
(Installation Set Up) process.
ECC-CDS-CT04-15B-E01-EN 2
Memorized Time Off Operating Mode
The time off feature will automatically turn off the ther- Comfort Mode
mostat after a selectable amount of time. To change
the time setting, press and hold the power button for In comfort mode, the setpoint can be changed by press-
more than 3 seconds and press “up” and “down” button ing up and down button. Applications include cool only,
to change the value when the thermostat is working . heat only and manual heat/cool changeover.
NOTE: The setting range is from 0 to 12 hours. The
step is 1 hour and the default value is 0.
Ventilation Mode
Press mode button to enter ventilation mode. In ventila-
tion mode, no output for valve while the fan will operate
at selected fan speed.
Backlight
To turn on the backlight, press any key. The backlight
will timeout 8 seconds after the last key is pressed.
When in ISU and Installation test mode, the backlight
will timeout 60 seconds after the last key is pressed.
Keypad Lockout
Keypad lockout can be set in ISU and the default status
is “all keys available”. Keypad lock can be optioned to
“mode button locked”, “Fan and mode buttons locked”,
“all buttons (except power button) locked” and “all but-
tons locked”.
Dimensions (mm)
Freeze Protection Mode
Freeze protection can be selected as enabled (default)
or disabled in the ISU. In freeze protection mode (only
in heating applications), when thermostat is off and the
temperature is below 6°C , the thermostat will activate
heating mode until the temperature rises to 8°C .
3 ECC-CDS-CT04-15B-E01-EN
ISU (Installation Setup) Communicating Parameter Setting
Press and hold the “mode” and the “up” buttons together When the thermostat is integrated into building
for more than 3 seconds to enter or exit ISU. Change automation system, you can make configuration refer
the ISU code by pressing the “mode” button and then below list.
change the option setting by pressing the “up” and Addr Configura-
“down” button refer to the following introduction. Significance and Prop-
Reg- tion
adjustment erties
ISU isters parameters
Description Options
Code 01 Power 0-OFF;1-ON R/W
Switch
0 Address 1~64 1(Default)
02 Room Temp Room temperature R
0 Cool only
1 Heat only 03 Temp. 0-°F;1-°C R/W
1 System Type Scale*
2 Two pipes heating/cooling
manual (Default) 04 Setpoint* Set temperature value R/W
0 °F 05 Fan Status* 0-Low speed ;1-Med R/W
2 Temp. Scale
1 °C (Default) speed;2-High speed;3-
0 Auto only Auto
ECC-CDS-CT04-15B-E01-EN 4
19 Cooling 100~320 (10~32⁰C) R/W
Range step5(0.5⁰C)100 Wiring
stops* (Default
500~900 (50~90⁰F)
step10(1⁰F ) 500
(Default
20 Keypad lock- 0- All keys are available R/W
out * (Default);1- system but-
ton locked out;2- Fan
and system button
locked out;3- All button
locked out except power
button;4- All button are
locked
21 Freeze Pro- 0- Disabled ; 1- Enable R/W
tection* Default
Terminal Designations
No Terminal Description
1 N 220/230Vac Neutral
8 D+ RS 485+
9 D- RS 485-
5 ECC-CDS-CT04-15B-E01-EN
Trouble shooting Tips
If Then...
Heating system does not respond Set the mode to heating by pressing the mode button
Make sure the temperature is set above the room temperature.
Make sure “heat on” icon shows on the display
Wait 5 minutes for the system to respond
Cooling system does not respond Set the mode to cooling by pressing the mode button
Make sure the temperature is set below the room temperature
Make sure “cool on” icon shows on the display
Wait 5 minutes for the system to respond
The fan doesn’t work Make sure fan mode isn’t set to auto
Check heating or cooling system works well.
The mode button doesn’t work Make sure keypad is unlocked.
Check that thermostat is on.
The up or down button doesn’t work Make sure keypad is unlocked.
Make sure the system doesn’t work in ventilation mode
Check that thermostat is on.
The system turns off automatically Make sure the memorized time off value isn’t set to “0”.
Display Check the Modbus address and Baud rate. Use Master to read registers
Check the wiring.
ECC-CDS-CT04-15B-E01-EN 6