Fan Filter Unit: Installation & Operation Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

I N STALL AT ION &

O PERATIO N MANUAL

Fan Filter Unit


FF D / FFDR / F F DRA

Redefine your comfort zone. ™ | www.titus-hvac.com


IOM
F F D / FFDR / F F D RA

Table of Contents
Critical Operations of the Fan Filter Unit .......................................................................... .......................................3
Warnings ................................................................................................................................. .................................3
Installation.................................................................................................................................................................4
ON/OFF Switch - Speed/Airflow Adjustment ..........................................................................................................5
Troubleshooting.........................................................................................................................................................7
Pre-filter Cleaning (foam) .........................................................................................................................................8
Service: Removal and Replacement of FFD Filters...................................................................................................9
Service: Removal and Replacement of Roomside Replaceable Filters .................................................................10
Service: FFD and FFDR Motor Removal and Installation .......................................................................................11
Service: FFDRA Motor Removal and Installation ...................................................................................................12
Unit Wiring Diagrams .............................................................................................................................................13
Unit Replacement Parts List ...................................................................................................................................14
Drawing - FFD Filter ................................................................................................................................................15
Drawing - FFDR & FFDRAFilter ...............................................................................................................................16
Testing......................................................................................................................................................................17

2 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Critical Operation Conditions of FFD, FFDR, & FFDRA models
1. Touching of the HEPA filter will damage it, voiding the warranty
on the filter. The screen is only to protect against an accidental
‘touch’ of the filter. Never place a hand or tool on the filter. Never
lie filter face flat down on a surface always have filter on its side
to protect from damage.
2. Prior to powering the unit, verify voltage on label and that the unit
has been wired into the correct voltage. The serial number label on
the top of the unit has the required voltage.
3. To insure you order the proper replacement parts or complete
unit, record the part number and serial number. This information
is located on the serial number label, located adjacent to the
electrical box. If you can’t locate the Sales Order Number, please
contact Titus for this information. Once obtained, record the
information for reference.

WARNING
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:

A. Installation work and electrical wiring must be done by qualified


person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
B. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
C. If this unit is to be installed over an area using liquid, such as water
or chemical cleaning solutions, it must be marked as appropriate
for the application.
D. Use this unit only in the manner intended by the manufacturer. If
you have any questions, contact the manufacturer.
E. Before servicing or cleaning the unit, switch power off at unit
service panel and lock service panel to prevent power from being
switched on accidentally.

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 3


IOM
F F D / FFDR / F F D RA

Installation
Note: Titus fan filter units are completely assembled at the factory with
EYEBOLT
the exception of the optional ¼”-20 eyebolts that are used when hanging
the unit from an engineered design support system and installation of the
HEPA/ULPA filters (eyebolts not included and can be ordered separately,
p/n 222449-001).

Step 1. Carefully remove the unit from the shipping carton and inspect for
any damage that may have occurred during transportation (See Figure 1).
Note: When ordering FFDR and FFDRA units, the HEPA filters may FAN FILTER
be shipped separately to be installed into units after the fan box has UNIT
been installed.

Figure 2: Hanger Supports

Step 3. Raise the unit and secure it into place using the chosen support
system method suspended from a structural support bracing.

Step 4. Have an electrician wire the unit to the appropriate voltage,


according to the wiring diagram (page 13), and all national and local
electrical codes. All units are equipped with a three position terminal block
for field onnection. Verify correct singlephase power, before energizing
units.

Step 5. Turn on the power using the two position rocker switch (ON/OFF)
located on the electrical box. For FFDR and FFDRA units, let the unit run for
a few hours to purge off particulate (if filters are shipped loose) that may
Figure 1: Unboxing be adhered to the inside of the unit before installing the filters. Do not run
fan at full speed as this may cause overload condition.

Note: Your fan filter may have been shipped separate. Controls have been
Step 2. If using rigidly supported grid (usually 2” (50 mm) or wider), raise shipped separately.
unit through ceiling and lower onto the gasketed grid. If using a flexible
grid (typically supported with wires), the unit must be secured to an
engineered design support system with s-hooks and chain. Screw the
four eyebolts into the nutserts on the lid assembly before lifting into an
overhead position (see Figure 2)

Note: Confirm fan dimensions to match T-grid dimensions.

4 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Unit Control Box
ON/OFF SWITCH - SPEED/AIRFLOW ADJUSTMENT
All units are equipped with a speed control enabling adjustment of airflow at any setting within the recommended performance range. The speed
control knob is located on the side of the electrical box, adjacent to the on/off switch.

Speed Control Electrical Entrance ON/OFF Switch

SPEED CONTROL ADJUSTMENT


Airflow/speed is adjusted by rotating the knob (See figure above):
•• Clockwise Lowers the speed
•• Counter-Clockwise  Increases the speed

Fully rotating the speed control knob to the left or counter-clockwise will turn the unit off.

Note: When turning the unit “ON” from the “OFF” position of the speed control, the fan is at the highest speed. Turning the speed control knob
clockwise will lower the airflow.

OPTIONAL SPEED CONTROL
For units equipped with a three-position rotary switch, it is located on the side of the electrical box (See figure below). Recommended fan speed
during initial start-up and operation is the “LOW” speed. As airflow eventually decreases due to filter loading, fan speed may be increased by moving
the rocker switch to the top or “MEDIUM” position, and finally to the “HIGH” position. Periodic airflow velocity readings (per IEST Reccommended
Practices) should be conducted to determine the filter condition and appropriate fan speed setting.

3-Speed Switch Electrical Entrance ON/OFF Switch

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 5


IOM
F F D / FFDR / F F D RA

Filter Indicator Light option


The pressure switch for the filter indicator light option is set at 0.60 in wc a. If no specific filter loading requirements are specified a general
from the factory. The set point for the pressure switch can be adjusted recommendation is to use twice the pressure differential
between 0.50 in wc and 3.00 in wc by turning the set screw, accessible for measured in step 2
the front of the control enclosure. Counterclockwise rotation will increase
the set point differential for switching; clockwise rotation will reduce the Step 4. With the unit discharge blocked, adjust the set point of the
set point. pressure switch
a. If the indicator light is illuminated, increase the set point of the
The process to adjust this for a specific application is detailed below: pressure switch (CCW rotation) until the is unilluminated
i. Slowly decrease set point until light illuminates
Step 1. Adjust fan speed to highest setting b. If the indicator light is unilluminated, slowly decrease the set point
of the pressure switch (CW rotation) until the light illuminates
Step 2. Measure and note initial pressure differential between ceiling
plenum and unit plenum (downstream of the fan & upstream of the filter) Step 5. Remove obstruction(s) from the unit discharge

Step 3. Restrict discharge airflow incrementally to increase differential Step 6. Adjust fan speed to operational set point
pressure until measured value matches filter loading requirements for
the project

Filter Indicator Light


Pressure Switch Adjuster

Speed Control Electrical Kockout ON/OFF Switch

6 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Troubleshooting
LOW AIR VELOCITY:

Step 1. Adjust variable speed control for higher blower output. For
units equiped with 3-speed, adjust switch setting from “LOW” to
“MEDIUM” to “HIGH”.

Step 2. Check prefilter media; replace or clean as necessary.

Step 3. Check incoming power supply for proper voltage (120,208-


240,277/24).

Step 4. Examine the HEPA/ULPA filter.



HIGH AIR VELOCITY:

Step 1. Adjust variable speed control for lower blower output. For units
eqquped with 3-speed, adjust switch setting from “HIGH” to “MEDIUM”
to “LOW”.

FILTER ISSUES:
Non-Laminar Flow and/or Excessive Contamination:

Step 1. Insure that no large obstructions are upstream of airflow pattern.

Step 2. Determine that no other air-moving devices are operating in or


around clean room which disrupt room’s airflow pattern.

Step 3. Check air velocity and if low, conduct the “Low Air Velocity”
procedure outlined above.

Step 4. Conduct smoke and photometer test on HEPA/ULPA filter. Seal or


replace HEPA filter as necessary.

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 7


IOM
F F D / FFDR / F F D RA

Cleaning the Pre-filter (foam)


Tools Required: None.

Note: To keep the filter in top operating condition, washing the foam WARNING
prefilter is recommended every three to six months. DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
Step 1. To gain access to the prefilter, remove the ceiling panel next to the ANY SERVICE
unit, if applicable.

Step 2. Switch the ON-OFF switch to the off position.

Step 3. Remove the 16”x23” prefilter from the snap-in frame. (See
figure below)

Step 4. Clean the prefilter by hand washing in water with a mild


detergent or by using a vacuum cleaner. Allow prefilter to dry completely
before replacing.

Step 5. Reassemble by reversing the above steps.

PREFILTER SURFACE ON TOP SIDE

ON/OFF SWITCH
SUPPORT SCREEN ON BOTTOM SIDE

8 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Service: Removal and Replacement of FFD HEPA/ULPA Filters

WARNING
WARNING THE STANDARD FILTER IS PROTECTED WITH AN
DISCONNECT THE UNIT FROM THE ELECTRICAL EXTENDED METAL FACE SCEEN. THIS IS NEVER TO
POWER SOURCE BEFORE ATTEMPTING BE USED TO HANDLE THE FILTER. IT IS ONLY FOR
ANY SERVICE PROTECTION AGAINST AN ACCIDENTAL TOUCH OF THE
FILTER. ONLY HANDLE THE FILTER BY THE FRAME

Note: All filters should be visually inspected for freight damage before filter deflectors using 5/32 drill bit. Keep filter deflectors to install in
installation. It is necessary to use two workers when removing the filter new filter. Discard the used filter as per requirements of the applicable
and for installation to avoid twisting or separation of the media seals. regulations. Carefully install the filter deflectors into the new filter using
Handle the filter only by the frame and never place anything on the the 5/32 rivets. Do not touch or place the filter deflectors on the HEPA/
upstream filter side of the filter. Additionally, it is important to keep the ULPA media pack. This could cause tears in the filter pack.
filter level to prevent any shearing force on the media itself.
Step 4. Before replacing with the new filter, carefully inspect the new
FOR STANDARD FILTERS: filter for any visible damage. Also inspect the gasket and the T-Bar to
Tools Required: Phillips Head Driver, Battery Operated Drill with 5/32 drill insure a tight seal. Replace if necessary.
bit, Rivet Hand Tool, Ø5/32 aluminum rivet grip range.126-.187
Step 5. To replace a filter, raise the filter and rotate into position in
Step 1. Remove unit from ceiling. the ceiling grid (with power off), then lower the plenum housing into
place. Reconnect wiring and hardware from previous steps that have
Step 2. Remove the 10 screws holding the HEPA/ULPA filter to the been removed.
lid assembly.
Step 6. Restore power and verify proper operation of FFU.
Step 3. Lift the lid assembly off the HEPA/ULPA filter (see figure). Remove

On/Off Switch

Lid Assembly

Electrical Knock Out

#8 Screws (10x)

Filter Deflector Ø5/32 Rivet (6x)

HEPA/ULPA Filter

Standard Filter Change

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 9


IOM
F F D / FFDR / F F D RA

Service: Removal and Replacement of FFDR & FFDRA Filters

WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL POWER SOURCE BEFORE ATTEMPTING ANY SERVICE

Note: All filters should be visually inspected for freight damage before
installation. It is necessary to use two workers when removing the filter WARNING
and for installation to avoid twisting or separation of the media seals. THE STANDARD FILTER IS PROTECTED WITH AN
Handle the filter only by the frame and never place anything on the EXTENDED METAL FACE SCEEN. THIS IS NEVER TO
upstream filter side of the filter. Additionally, it is important to keep the BE USED TO HANDLE THE FILTER. IT IS ONLY FOR
filter level to prevent any shearing force on the media itself. PROTECTION AGAINST AN ACCIDENTAL TOUCH OF THE
FILTER. ONLY HANDLE THE FILTER BY THE FRAME
FOR FFDR & FFDRA FILTERS:
Tools Required: Phillips Head Driver, Battery Operated Drill, 3/16” hex head
ball driver (2ea)
Fan Filter Unit

Step 1. With the power off, remove the diffuser screen by removing the 6 2-Piece Welded
each 10-32x1/2 screws, then carefully place in a safe location. Plenum Housing

Filter
Step 2. Loosen the six 1/4x12 socket head screws far enough to rotate
the eight filter clips 90°. The filter may be loose enough to drop during Filter Clip and
Screw (typ 6)
this operation. If not, slowly pull the filter away from the knife-edge seal,
taking care not to touch the filter face during this operation. It is important
Diffuser Screen
to pull the filter slowly away from the seal, so that the gel remains in the Screws (typ 6)
filter gel track.

Step 3. Carefully clean plenum assembly knife edge surface of residual


gel material. FFDR & FFDRA Filter Change

Step 4. Inspect filter for visible damage, if damaged set aside for
replacement or repair. Filter

Step 5. Inspect the gel seal, if reinstalling the removed filter. Determine Knife- Edge
if the gel has lost its ability to seal (i.e. the gel should reform to cover the Seal
track without voids or openings), if so repair the gel material or consider
replacement of filter. Gel Track

Step 6. Place the filter evenly against the filter-sealing surface of the unit.
Reposition filter clips and screws. The clips should be rotated and angled ¼ -20
into place. It is recommended that four workers work on each corner of the Cap
Screw Filter Clip
filter simultaneously, holding the filter seated into the track. Hand tighten
clips from opposite corners evenly until all clamps are tightened. 10-32
Diffuser
PHP
Screws Screen
Step 7. Reinstall diffuser screen by hand-tightening the screws.
FFDR & FFDRA Filter Replacement

10 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Service: FFD and FFDR Motor Removal and Installation

WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL WARNING
POWER SOURCE BEFORE ATTEMPTING ELECTRICAL SERVICE SHOULD ONLY BE PERFORMED
ANY SERVICE BY A LICENSED OR QUALIFIED ELECTRICIAN

Tools Required: Phillips Head Driver, Battery Operated Drill, (2) 8” Prefilter
adjustable wrenches, 10 mm hex head wrench, #2 screwdriver, and slip
joint pliers.
Motor
Step 1. To gain access to the motor, remove the ceiling panel next to the
unit, if applicable. Venturi Ring

Blower Wheel
Step 2. Switch the ON-OFF switch to the off position.

Step 3. Loosen the electrical box cover screws (2), and slide/lift off cover.
ON/OFF Switch

Step 4. Make note of all wire routing and locations for later reinstallation.

Step 5. Disconnect the two brown wires from the capacitor, using a pair
of pliers. Disconnect the motor wiring from the rotary switch and rocker
switch or speed control and rocker switch and remove the grommet from
the motor leads. Save this grommet for reinstallation.

Step 6. Remove the eight mounting screws to free the motor/blower Power Entrance
assembly from the lid assembly. If using power drivers, set the unit to a
low torque setting to avoid stripping the sheet metal screws. Carefully Motor/Electrical Removal
remove housing assembly, paying attention to wire routing.

Step 7. Using an adjustable wrench loosen the two set screws that attach
the blower wheel to the motor shaft.

Step 8. Mark the location of the motor support bracket (belly band), then
loosen the bolt just enough to allow the motor support bracket to slid off
the motor.

Step 9. Using the removed motor, mark the new motor with the location
of the motor support bracket.

Step 10. Replace with the new motor and reassemble by reversing the
above steps 1-8. Set the spacing at 0.25” (6.35 mm)

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 11


IOM
F F D / FFDR / F F D RA

Service: Removal and Replacement of FFDR & FFDRA Filters

WARNING
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
ELECTRICAL SERVICE SHOULD ONLY BE PERFORMED
POWER SOURCE BEFORE ATTEMPTING
BY A LICENSED OR QUALIFIED ELECTRICIAN
ANY SERVICE

Note: Minimum 2 person project. speed control and rocker switch and remove the grommet from the motor
leads. Save this grommet for reinstallation.
Tools Required: 3/16 Ball Driver, Phillips screw bit, Head Driver, Battery
Operated Drill, (2) 8” adjustable wrenches, 10 mm Step 3. While supporting the motor blower assembly from below, remove
hex head wrench, #2 standard screwdriver, and slip joint pliers. the six screws on the underside of the venturi ring and lower the assembly.
(See Figure 7). Note the baffle does not have to be removed to remove the
Step 1. To gain access to the motor, remove the gel seal filter. motor/blower assembly.

Step 2. Prior to removing motor/blower assembly, remove blower wheel Step 4. Before removal of the motor mount bracket, measure the precise
to expose motor connectors on motor. Using an adjustable wrench loosen location of the bracket on the motor. Remove the bracket.
the two set screws that attach the blower wheel to the motor shaft.
Disconnect the two brown wires from the capacitor, using a pair of pliers. Step 5. Replace with the new motor and reassemble by reversing the
Disconnect the motor wiring from the rotary switch and rocker switch or above steps. Set the location of the motor mount bracket as measured.
Set the spacing at 0.25” (6.35 mm) clearance between the blower and
the upper motor plate/prefilter frame creating a 0. 1” (2.80 mm) overlap
between the wheel and the venturi ring. When reinstalling the assembly,
align the plate to insure that the leads will reach the electrical box.
Electrical connectors
located in inner
prefilter wall

Grommet

Machine Screw
Plenum
and washer

Motor/Blower Motor
Assy
Venturi
Ring
Baffle Assembly
Wellnut

Gel Seal Filter


Blower
Wheel

Screen

Motor/Electrical Removal Motor Assembly

12 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Wiring Diagrams

Three Speed Wiring Diagram

Speed Control Wiring Diagram

Pressure Monitor Switch)

Network Control Card Wiring Diagram

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 13


IOM
F F D / FFDR / F F D RA

Replacement Parts List

Model Size/Voltage Description Part Number


N/A Disconnect Switch 63739-002
N/A Pre-Filter (foam) 62981-001
N/A Deflector-Filter 38532-001
N/A Gasket, Neop. 125x5 62968
N/A Grommet 5/8 Id 1 1/8 Od 63388
120V 63677
208V-240V Transformer 24V 63666
277V 63665
FFD, FFDR
120V 63011
FFDRA
208V-240V Speed Controller 63015
277V 63016
230V Speed Controller (CE Marked) 63742
N/A Blower Wheel 63270
N/A Ventiri Ring 62964
120V 64083-001
208V-240V Network Control Card (FFD, FFDR, & FFDRA) 64083-002
277V 64083-003

120V 24332-001
FFD, FFDR 208V-240V PSC Motor/Blower Assembly (FFD & FFDR) 24332-002
277V 24332-003

120V 24332-015
FFDRA 208V-240V PSC Motor/FFDRA Blower Assembly (FFDRA) 24332-016
277V 24332-017

14 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


FFD Filter Drawing

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 15


IOM
F F D / FFDR / F F D RA

FFDR and FFDRA Filter Drawing

16 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Testing
Each fan filter unit is thoroughly tested at the factory before shipment. reading is to place one corner of the Velgrid head 1-1/4” from the corner of
However, because of the “rigors” of shipping, Titus encourages units are the filter face and then take four reading evenly spaced along the four foot
re-tested after installation. side, then repeat these reads three additional times. This gives a total of 8
reading to test the unit. All advertised data is based on using the Velgrid
Titus recommends that the customer contact an independent organization, with 8 readings (128 velocity points). Titus recognized the using 8 reading
with technicians trained and experienced in performance evaluation and during a cleanroom start-up may be time consuming and recommends
maintenance of clean air equipment. using 4 Velgrid readings taken on each 2x2 filter section will approximate
the same as 8 readings.
HEPA filters (Type J) are tested to IEST-RP-00034. ULPA filters are tested to
(Type F) IEST-RP-00034. All filters are UL 900 recognized. Your filters may Recommended Testing – 8 readings with a Velgrid
have special requirements, please see original engineering specifications
for you specific project. Additional independent testing on the Titus fan filter units show that using
one-2x4 or two-2x2 hoods simultaneously give airflow data (cfm) with 5
percent of a duct traverse using 10 diameters of straight duct upstream of
All units that are airflow tested at Titus are tested using a Shortridge
the fan intake.
Airdata Multimeter 870 with a Velgrid head. The recommended method of

Recommend
Recommended ed –
Testing Testing – 8 readi
8 readings ngs
with a with a Velgr
Velgrid id

Redefine your comfort zone. ™ | www.titus-hvac.com IOM - FFD 17


IOM
F F D / FFDR / F F D RA

Notes

18 IOM - FFD Redefine your comfort zone. ™ | www.titus-hvac.com


Notes