Fan Filter Unit: Installation & Operation Manual
Fan Filter Unit: Installation & Operation Manual
Fan Filter Unit: Installation & Operation Manual
O PERATIO N MANUAL
Table of Contents
Critical Operations of the Fan Filter Unit .......................................................................... .......................................3
Warnings ................................................................................................................................. .................................3
Installation.................................................................................................................................................................4
ON/OFF Switch - Speed/Airflow Adjustment ..........................................................................................................5
Troubleshooting.........................................................................................................................................................7
Pre-filter Cleaning (foam) .........................................................................................................................................8
Service: Removal and Replacement of FFD Filters...................................................................................................9
Service: Removal and Replacement of Roomside Replaceable Filters .................................................................10
Service: FFD and FFDR Motor Removal and Installation .......................................................................................11
Service: FFDRA Motor Removal and Installation ...................................................................................................12
Unit Wiring Diagrams .............................................................................................................................................13
Unit Replacement Parts List ...................................................................................................................................14
Drawing - FFD Filter ................................................................................................................................................15
Drawing - FFDR & FFDRAFilter ...............................................................................................................................16
Testing......................................................................................................................................................................17
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
Installation
Note: Titus fan filter units are completely assembled at the factory with
EYEBOLT
the exception of the optional ¼”-20 eyebolts that are used when hanging
the unit from an engineered design support system and installation of the
HEPA/ULPA filters (eyebolts not included and can be ordered separately,
p/n 222449-001).
Step 1. Carefully remove the unit from the shipping carton and inspect for
any damage that may have occurred during transportation (See Figure 1).
Note: When ordering FFDR and FFDRA units, the HEPA filters may FAN FILTER
be shipped separately to be installed into units after the fan box has UNIT
been installed.
Step 3. Raise the unit and secure it into place using the chosen support
system method suspended from a structural support bracing.
Step 5. Turn on the power using the two position rocker switch (ON/OFF)
located on the electrical box. For FFDR and FFDRA units, let the unit run for
a few hours to purge off particulate (if filters are shipped loose) that may
Figure 1: Unboxing be adhered to the inside of the unit before installing the filters. Do not run
fan at full speed as this may cause overload condition.
Note: Your fan filter may have been shipped separate. Controls have been
Step 2. If using rigidly supported grid (usually 2” (50 mm) or wider), raise shipped separately.
unit through ceiling and lower onto the gasketed grid. If using a flexible
grid (typically supported with wires), the unit must be secured to an
engineered design support system with s-hooks and chain. Screw the
four eyebolts into the nutserts on the lid assembly before lifting into an
overhead position (see Figure 2)
Fully rotating the speed control knob to the left or counter-clockwise will turn the unit off.
Note: When turning the unit “ON” from the “OFF” position of the speed control, the fan is at the highest speed. Turning the speed control knob
clockwise will lower the airflow.
OPTIONAL SPEED CONTROL
For units equipped with a three-position rotary switch, it is located on the side of the electrical box (See figure below). Recommended fan speed
during initial start-up and operation is the “LOW” speed. As airflow eventually decreases due to filter loading, fan speed may be increased by moving
the rocker switch to the top or “MEDIUM” position, and finally to the “HIGH” position. Periodic airflow velocity readings (per IEST Reccommended
Practices) should be conducted to determine the filter condition and appropriate fan speed setting.
Step 3. Restrict discharge airflow incrementally to increase differential Step 6. Adjust fan speed to operational set point
pressure until measured value matches filter loading requirements for
the project
Step 3. Check air velocity and if low, conduct the “Low Air Velocity”
procedure outlined above.
Note: To keep the filter in top operating condition, washing the foam WARNING
prefilter is recommended every three to six months. DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
Step 1. To gain access to the prefilter, remove the ceiling panel next to the ANY SERVICE
unit, if applicable.
Step 3. Remove the 16”x23” prefilter from the snap-in frame. (See
figure below)
ON/OFF SWITCH
SUPPORT SCREEN ON BOTTOM SIDE
WARNING
WARNING THE STANDARD FILTER IS PROTECTED WITH AN
DISCONNECT THE UNIT FROM THE ELECTRICAL EXTENDED METAL FACE SCEEN. THIS IS NEVER TO
POWER SOURCE BEFORE ATTEMPTING BE USED TO HANDLE THE FILTER. IT IS ONLY FOR
ANY SERVICE PROTECTION AGAINST AN ACCIDENTAL TOUCH OF THE
FILTER. ONLY HANDLE THE FILTER BY THE FRAME
Note: All filters should be visually inspected for freight damage before filter deflectors using 5/32 drill bit. Keep filter deflectors to install in
installation. It is necessary to use two workers when removing the filter new filter. Discard the used filter as per requirements of the applicable
and for installation to avoid twisting or separation of the media seals. regulations. Carefully install the filter deflectors into the new filter using
Handle the filter only by the frame and never place anything on the the 5/32 rivets. Do not touch or place the filter deflectors on the HEPA/
upstream filter side of the filter. Additionally, it is important to keep the ULPA media pack. This could cause tears in the filter pack.
filter level to prevent any shearing force on the media itself.
Step 4. Before replacing with the new filter, carefully inspect the new
FOR STANDARD FILTERS: filter for any visible damage. Also inspect the gasket and the T-Bar to
Tools Required: Phillips Head Driver, Battery Operated Drill with 5/32 drill insure a tight seal. Replace if necessary.
bit, Rivet Hand Tool, Ø5/32 aluminum rivet grip range.126-.187
Step 5. To replace a filter, raise the filter and rotate into position in
Step 1. Remove unit from ceiling. the ceiling grid (with power off), then lower the plenum housing into
place. Reconnect wiring and hardware from previous steps that have
Step 2. Remove the 10 screws holding the HEPA/ULPA filter to the been removed.
lid assembly.
Step 6. Restore power and verify proper operation of FFU.
Step 3. Lift the lid assembly off the HEPA/ULPA filter (see figure). Remove
On/Off Switch
Lid Assembly
#8 Screws (10x)
HEPA/ULPA Filter
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL POWER SOURCE BEFORE ATTEMPTING ANY SERVICE
Note: All filters should be visually inspected for freight damage before
installation. It is necessary to use two workers when removing the filter WARNING
and for installation to avoid twisting or separation of the media seals. THE STANDARD FILTER IS PROTECTED WITH AN
Handle the filter only by the frame and never place anything on the EXTENDED METAL FACE SCEEN. THIS IS NEVER TO
upstream filter side of the filter. Additionally, it is important to keep the BE USED TO HANDLE THE FILTER. IT IS ONLY FOR
filter level to prevent any shearing force on the media itself. PROTECTION AGAINST AN ACCIDENTAL TOUCH OF THE
FILTER. ONLY HANDLE THE FILTER BY THE FRAME
FOR FFDR & FFDRA FILTERS:
Tools Required: Phillips Head Driver, Battery Operated Drill, 3/16” hex head
ball driver (2ea)
Fan Filter Unit
Step 1. With the power off, remove the diffuser screen by removing the 6 2-Piece Welded
each 10-32x1/2 screws, then carefully place in a safe location. Plenum Housing
Filter
Step 2. Loosen the six 1/4x12 socket head screws far enough to rotate
the eight filter clips 90°. The filter may be loose enough to drop during Filter Clip and
Screw (typ 6)
this operation. If not, slowly pull the filter away from the knife-edge seal,
taking care not to touch the filter face during this operation. It is important
Diffuser Screen
to pull the filter slowly away from the seal, so that the gel remains in the Screws (typ 6)
filter gel track.
Step 4. Inspect filter for visible damage, if damaged set aside for
replacement or repair. Filter
Step 5. Inspect the gel seal, if reinstalling the removed filter. Determine Knife- Edge
if the gel has lost its ability to seal (i.e. the gel should reform to cover the Seal
track without voids or openings), if so repair the gel material or consider
replacement of filter. Gel Track
Step 6. Place the filter evenly against the filter-sealing surface of the unit.
Reposition filter clips and screws. The clips should be rotated and angled ¼ -20
into place. It is recommended that four workers work on each corner of the Cap
Screw Filter Clip
filter simultaneously, holding the filter seated into the track. Hand tighten
clips from opposite corners evenly until all clamps are tightened. 10-32
Diffuser
PHP
Screws Screen
Step 7. Reinstall diffuser screen by hand-tightening the screws.
FFDR & FFDRA Filter Replacement
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL WARNING
POWER SOURCE BEFORE ATTEMPTING ELECTRICAL SERVICE SHOULD ONLY BE PERFORMED
ANY SERVICE BY A LICENSED OR QUALIFIED ELECTRICIAN
Tools Required: Phillips Head Driver, Battery Operated Drill, (2) 8” Prefilter
adjustable wrenches, 10 mm hex head wrench, #2 screwdriver, and slip
joint pliers.
Motor
Step 1. To gain access to the motor, remove the ceiling panel next to the
unit, if applicable. Venturi Ring
Blower Wheel
Step 2. Switch the ON-OFF switch to the off position.
Step 3. Loosen the electrical box cover screws (2), and slide/lift off cover.
ON/OFF Switch
Step 4. Make note of all wire routing and locations for later reinstallation.
Step 5. Disconnect the two brown wires from the capacitor, using a pair
of pliers. Disconnect the motor wiring from the rotary switch and rocker
switch or speed control and rocker switch and remove the grommet from
the motor leads. Save this grommet for reinstallation.
Step 6. Remove the eight mounting screws to free the motor/blower Power Entrance
assembly from the lid assembly. If using power drivers, set the unit to a
low torque setting to avoid stripping the sheet metal screws. Carefully Motor/Electrical Removal
remove housing assembly, paying attention to wire routing.
Step 7. Using an adjustable wrench loosen the two set screws that attach
the blower wheel to the motor shaft.
Step 8. Mark the location of the motor support bracket (belly band), then
loosen the bolt just enough to allow the motor support bracket to slid off
the motor.
Step 9. Using the removed motor, mark the new motor with the location
of the motor support bracket.
Step 10. Replace with the new motor and reassemble by reversing the
above steps 1-8. Set the spacing at 0.25” (6.35 mm)
WARNING
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
ELECTRICAL SERVICE SHOULD ONLY BE PERFORMED
POWER SOURCE BEFORE ATTEMPTING
BY A LICENSED OR QUALIFIED ELECTRICIAN
ANY SERVICE
Note: Minimum 2 person project. speed control and rocker switch and remove the grommet from the motor
leads. Save this grommet for reinstallation.
Tools Required: 3/16 Ball Driver, Phillips screw bit, Head Driver, Battery
Operated Drill, (2) 8” adjustable wrenches, 10 mm Step 3. While supporting the motor blower assembly from below, remove
hex head wrench, #2 standard screwdriver, and slip joint pliers. the six screws on the underside of the venturi ring and lower the assembly.
(See Figure 7). Note the baffle does not have to be removed to remove the
Step 1. To gain access to the motor, remove the gel seal filter. motor/blower assembly.
Step 2. Prior to removing motor/blower assembly, remove blower wheel Step 4. Before removal of the motor mount bracket, measure the precise
to expose motor connectors on motor. Using an adjustable wrench loosen location of the bracket on the motor. Remove the bracket.
the two set screws that attach the blower wheel to the motor shaft.
Disconnect the two brown wires from the capacitor, using a pair of pliers. Step 5. Replace with the new motor and reassemble by reversing the
Disconnect the motor wiring from the rotary switch and rocker switch or above steps. Set the location of the motor mount bracket as measured.
Set the spacing at 0.25” (6.35 mm) clearance between the blower and
the upper motor plate/prefilter frame creating a 0. 1” (2.80 mm) overlap
between the wheel and the venturi ring. When reinstalling the assembly,
align the plate to insure that the leads will reach the electrical box.
Electrical connectors
located in inner
prefilter wall
Grommet
Machine Screw
Plenum
and washer
Motor/Blower Motor
Assy
Venturi
Ring
Baffle Assembly
Wellnut
Screen
120V 24332-001
FFD, FFDR 208V-240V PSC Motor/Blower Assembly (FFD & FFDR) 24332-002
277V 24332-003
120V 24332-015
FFDRA 208V-240V PSC Motor/FFDRA Blower Assembly (FFDRA) 24332-016
277V 24332-017
Recommend
Recommended ed –
Testing Testing – 8 readi
8 readings ngs
with a with a Velgr
Velgrid id
Notes