Selection Guide
Catalog
2510CT9701R01/16
2016
Class 2510, 2511, 2512, 2601
CONTENTS
Fractional Horsepower Manual Starters—Type F . . . . . . . . . . . . . . . Page 3
Manual Switches—Type K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
Integral Horsepower Starters—Types M and T . . . . . . . . . . . . . . . . Page 13
Accessories, Modifications, and Renewal Parts. . . . . . . . . . . . . . . . Page 17
Reversing Drum Switches—Class 2601 . . . . . . . . . . . . . . . . . . . . . Page 18
Manual Starters and Switches
Fractional Horsepower Manual Starters with Melting Alloy Thermal Overload Relay—Type F
Application Data
Type F fractional horsepower starters provide overload protection as well as manual On-Off control for
small motors in a variety of industrial and commercial installations. Typical applications include fans,
conveyors, pumps, and small machine tools.
Both one-pole and two-pole versions are suitable for use with AC single-phase motors rated up to
1 hp. Two-pole starters can also be used with DC motors rated up to 0.75 hp.
Type FG2P Table 1: Electrical Ratings
277 Vac maximum (1 or 2 pole)
Voltage Rating 230 Vdc maximum (2 pole only)
Continuous Current Rating 16 A
Enclosures: NEMA 1 surface mounting enclosures are sheet steel with a thermoplastic wrap-around
cover for convenience in wiring. The NEMA 1 enclosure is also available in an oversized version that
allows more space for wiring. A zinc alloy die casting is used for NEMA 4 enclosures, and a cast
aluminum enclosure is offered for NEMA 3R, 7 & 9 applications.
Pilot Light: Red or green pilot light units are available factory installed in NEMA 1 surface- and flush-
mounting enclosures and in NEMA 4 enclosures. They are also available as a field modification kit for
NEMA 1 enclosures and gray flush plates.
Type FO2 For a red pilot light, use the order number as is. For a green pilot light, add a G to the number.
Handle Guard/Lock-Off: An optional handle guard on NEMA 1 enclosed starters prevents accidental
operation of the toggle operator and allows the toggle operator to be padlocked in either the On or Off
position.
The handle guard can be factory installed on NEMA 1 enclosed starters. It is also available in kit form
for field installation on NEMA 1 surface- and flush-mounting enclosures. Standard NEMA 4 and
NEMA 3R, 7 & 9 enclosures include provision for locking in the Off position.
Terminals: Binder head screw-type terminals are suitable for 10 AWG or smaller copper wire, and are
accessible from the front. All terminals are clearly marked.
Mounting: Open types without a pilot light fit standard single-gang switch boxes, and can be used with
any cover plate having a standard toggle cutout. Single-unit flush mounting types, including those with
a pilot light, are suitable for wall mounting in a standard switch box or for machine cavity mounting
without a box.
Operator: Available with toggle handle or with removable key-type operator to discourage
unauthorized operation.
Thermal Units: Starters will not operate without a properly installed thermal unit. Install the thermal
unit so that the markings face the front of the starter.
Emergency Off Actuator: A toggle operator extender is available for NEMA 1 surface-mounted units.
The extender has a red vinyl button that provides a fast and easy method for locating and switching the
device’s toggle operator into the Off position. The Emergency Off Actuator is available in kit form only
for field installation.
3
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Fractional Horsepower Manual Starters with Melting Alloy Thermal Overload Relay—Type F
Table 3: Approvals
Enclosed Unit Open Unit Explosion-Proof Unit
File E42243
— —
CCN NLRV2
2 1
L1 L1 A L1
O
Pilot light Pilot light H Pilot light
+ (if used) + (if used) 4 3 + (if used)
R R R
T1 T1 T1
– – –
T1 T2 T1 T2 2 4 4 T2
4
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Fractional Horsepower Manual Starters with Melting Alloy Thermal Overload Relay—Type F
1 Mechanical interlock and two red pilot lights [1] FG11P FF11P — FO1PT 2
High-Off-Low selector switch and two red pilot lights [1] — — FS101P FO1PT 2
Toggle
Mechanical interlock FG22 FF22 — FO2T 2
2 Mechanical interlock and two red pilot lights [1] FG22P FF22P — FO2PT 2
High-Off-Low selector switch and two red pilot lights [1] — — FS202P FO2PT 2
[1] For a green pilot light, add the letter G to the catalog number (for example, 2510FG02PG).
5
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Manual Starters and Switches
Manual Switches—Type K Reversing, Non-Reversing, Two Speed
Manual Switches—Type K
Reversing, Non-Reversing, Two Speed
Application Data
Type K motor starting switches provide manual On-Off control of single- or three-phase AC motors,
where overload protection is not required or is provided separately. These devices are suitable for use
with three-phase AC motors rated up to 20 hp. Compact construction and a 600 V rating make these
switches suitable for a wide range of industrial and commercial uses. Typical applications include small
machine tools, pumps, fans, conveyors, and many other types of electrical machinery. They can also
Type KG1A be used on non-motor loads such as resistance heaters.
Enclosures: NEMA 1 surface-mounting enclosures are sheet steel with a thermoplastic wrap-around
cover for convenience in wiring. The NEMA 1 enclosure is also available in jumbo and oversized
versions that allow more space for wiring. A zinc alloy die casting is used for NEMA 4 enclosures, and
Type KO2 a cast aluminum enclosure is offered for NEMA 3R and 7 & 9 applications.
Mounting: Open types without a pilot light fit standard single-gang switch boxes, and can be used with
any cover plate having a standard toggle cutout. Single-unit flush-mounting types, including those with
pilot light, are suitable for wall mounting in a standard switch box or for machine cavity mounting
without a box. For difficult wall surfaces, such as concrete block or tile, a jumbo size flush plate is
recommended. See the dimensional drawings for additional details and mounting provisions of
enclosed types.
Pilot Light: Red or green pilot light units are available factory installed in NEMA 1 surface- and flush-
mounting enclosures and in NEMA 4 enclosures. They are also available as a field modification kit for
NEMA 1 enclosures and gray flush plates.
For a red pilot light, use the order number as is. For a green pilot light, add a G to the number.
Operator: Available with a toggle handle or with a removable key-type operator to discourage
unauthorized operation.
Emergency Off Actuator: A toggle operator extender is available for NEMA 1 surface-mounting units.
The extender has a red vinyl button that provides a fast and easy method for locating and switching the
device’s toggle operator into the Off position. The Emergency Off actuator is available in kit form only
for field installation.
6
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Manual Switches—Type K Reversing, Non-Reversing, Two Speed
Table 9: Approvals
Enclosed Unit Open Unit Explosion-Proof Unit
File E42243
— —
CCN NLRV2
T2
T1 T3 T1 T3
MOTOR MOTOR
7
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Manual Starters and Switches
Manual Switches—Type K Reversing, Non-Reversing, Two Speed
8
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Approximate Dimensions, Types F and K
Type FO2 Types FO1, 1P, 2 Mounting Holes for #6-32 Screws (2)
Fractional Hp Starter Pilot Light
1.69
OFF
43
.84
21
2.38
60
3.28
83
4.13
105
2.22
56
1.59
40
1.69
OFF
43
.84
21
2.38
3.28 60
4.13 83
105
2.34
60
1.70
43
2.75 1.63
70 41 Pilot
2.44 Light
2.88
73 62
0.56
14
0.41
10
1.06
27
Type FG2P
0.5–0.75 in. Conduit Knockout, Both Ends
9
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Manual Starters and Switches
Approximate Dimensions, Types F and K
2.75 1.63
70 41 Pilot
2.88 Light
2.88
73 73
0.56
14
0.69
17
1.06
27
3.28
4.86 83
123 0.71
18
3.09
Pilot Light
78
10
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Approximate Dimensions, Types F and K
Figure 8: Dimensions for NEMA 3R, 7, and 9 Cast Aluminum Enclosure for
Hazardous Locations
3.95 4.35
100 2x 0.30
1.37 8 110
35
6.36
161
One Starter and One Toggle 2510 FG71, FG71P, FG72, FG72P
Selector Switch [1] Key 2510 FG74P
Reversing Switch [2] Toggle 2511 KG11, KG11A, KG11B, KG22A, KG22B, KG22C
Two-Speed Starter Toggle 2512 FG11, FG11P, FG22, FG22P
Two-Speed Switch Toggle 2512 KG11, KG11A, KG11B, KG22, KG22B, KG22C
[1] The selector switch is on the left. It increases the overall depth to 3.5 in.
[2] Only one pilot light (located on the right) is used on Class 2511 switches.
11
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Manual Starters and Switches
Approximate Dimensions, Types F and K
Figure 10: Dimension Drawing for Two-Unit NEMA 1 General Purpose Enclosure
.25
(4) Dia. Mtg. Holes
6
Pilot
Light
3.00
OFF OFF 76
4.25
108
Operator Dimensions
Device Class Type
Style A B C D
FF22, FF22P 5.25 3.75 5.25 1.44
Toggle 2510
FS22P 4.56 3.5 4.5 1.44
Two Starters
FF44P 5.25 3.75 5.25 1.44
Key 2510
FS44P 4.56 3.5 4.5 1.44
FF71, FF71P, FF72, FF72P 5.25 3.75 5.25 2.0
Toggle 2510
One Starter and One FS71P, FS72P 4.56 3.5 4.5 2.0
Selector Switch [1] FF74P 5.25 3.75 5.25 2.0
Key 2510
FS74P 4.56 3.5 4.5 2.0
KF11, KF11A, KF11B
Reversing Switch [2] Toggle 2511 5.25 3.75 5.25 1.75
KF22, KF22A, KF22B, KF22C
Two-Speed Starter Toggle 2512 FF11, FF11P, FF22, FF22P 5.25 3.75 5.25 1.44
KF11, KF11A, KF11B
Two-Speed Switch Toggle 2512 5.25 3.75 5.25 1.75
KF22, KF22B, KF22C
Class 2512 Type KF22
[1] The selector switch is on the left and extends 1.63 in. from the mounting surface.
[2] Dimensions include factory-wired power connections.
Figure 11: Dimension Drawing for Two-Unit General Purpose Flush Mounting Plate
OFF OFF C
2.56
65
A Pilot
Light
.75
D
19
.91
23 B
12
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Class 2510, 2511, 2512 Integral Horsepower Starters—Types M and T
Application Data
Types M and T integral horsepower manual starters provide convenient On-Off operation of small
single-phase, polyphase, or DC motors. Typical applications include small machine tools, pumps, fans,
and conveyors. They feature push button or toggle operators and reliable overload protection. Pilot
lights and auxiliary contacts are available. For modifications, see page 17.
Class 2510 Size: Available in NEMA Sizes M-0, M-1, and M-1P
Type M and T
in General Purpose Poles:
Enclosure
AC: Two poles single-phase; three poles polyphase
DC: 2 poles (3 poles in series)
Voltage Rating: 600 Vac maximum, 250 Vdc maximum
Overload Relays: Melting alloy thermal overload relays have provisions for one Type B thermal unit
for single-phase starters, or three Type B thermal units for three-phase starters. All thermal units must
be installed, and the device reset, before the starter contacts will operate. After an overload relay trips,
wait one or two minutes before resetting to allow the alloy to solidify.
Operator: Open and NEMA 1 versions are available with a push button or toggle operator. NEMA 4
and 12 are available with a direct-acting push button only. NEMA 4X and 7 & 9 use an external toggle
to actuate a push button device inside.
Mechanism Lock Off: Open devices and starters in the following enclosures can be locked in the Off
or Stop position: NEMA 1 surface and flush mounting; and NEMA 4, 4X, 7 & 9, and 12 .
Devices in the following enclosures can also be locked closed to prevent unauthorized entry: NEMA 1
surface mounting; and NEMA 4, 4X, and 12 . NEMA 7 & 9 enclosures are bolted closed.
Size M-1, 3-Pole Table 16: Terminals
Push Button Operated
Power Terminals Auxiliary Interlock Terminals
NEMA Size Wire Range Wire Range
Type of Lug Type of Lug
Solid or stranded copper wire Solid or stranded copper wire
13
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Manual Starters and Switches
Class 2510, 2511, 2512 Integral Horsepower Starters—Types M and T
Accessories and Modification Kits: One auxiliary contact, either N.O. or N.C., can be easily added
internally to any open or enclosed Type M or T manual starter. It occupies the space provided in either
the upper right or left corners of the device. These contacts are for AC loads only.
A unique red pilot light assembly that clips into place is available factory-installed on NEMA 1, 4, 4X,
12, and flush enclosures. The assembly is also available as a field modification kit for NEMA 1 surface
or flush mounting enclosures. The color cap assembly snaps into a knockout in the enclosure cover on
the NEMA 1 enclosures. Pilot light kits are available for use on various voltages, 110–600 V. (Pilot light
assemblies are not available for NEMA 7 & 9 enclosures.)
Class 2511 reversing manual starters consist of two mechanically interlocked Class 2510 Type M or
T manual starters. They are available in NEMA 1 surface-mounting enclosures or as open type.
Class 2512 two-speed manual starters are for wye-connected separate winding motors only. They
consist of two mechanically interlocked Class 2510 Type M or T manual starters.
NEMA 4/4X Starters will not operate unless the thermal units have been properly installed (with the markings
Watertight and Dusttight facing the front of the starter) and the device has been reset.
Stainless Steel
Table 18: Class 2510 Device Type Numbers—Non-Reversing,
Integral Horsepower Manual Starters, 600 Vac Maximum
Ratings NEMA Enclosure Open Style
NEMA 1 NEMA 4/4X Watertight, Dusttight, NEMA 7 & 9 [1] for NEMA 12 [2] Square
No. of NEMA Max. HP
Motor Surface Mounting and Corrosion-Resistant Hazardous Locations Dusttight Push Toggle
Poles Size
Voltage Poly- Single Square Push Button Toggle Brushed Class I : Grps C, D and Driptight Button Operator
Glass Polyester Class II : Grps E, F, G Industrial Use Operator
Phase Phase Operator Operator Stainless Steel
115 — 1
M-0 MBG1 TBG1 MBW11 [3] MBW1 [3] MBR1 [3] MBA1 [3] MBO1 TBO1
230 — 2
2 115 — 2
M-1 MCG1 TCG1 MCW11 MCW1 MCR1 MCA1 MCO1 TCO1
Pole 230 — 3
115 — 3
M-1P MCG2 TCG2 MCW12 MCW2 MCR2 MCA2 MCO2 TCO2
230 — 5
115 — —
M-0 200–230 3 — MBG2 TBG2 MBW12 [3] MBW2 [3] MBR2 [3] MBA2 [3] MBO2 TBO2
3 380–575 5 —
Pole 115 — —
M-1 200–230 7.5 — MCG3 TCG3 MCW13 MCW3 MCR3 MCA3 MCO3 TCO3
380–575 10 —
115 1 hp, DC
DC M-0 MBG4 TBG4 MBW14 MBW4 — MBA4 MBO4 TBO4
230 1.5 hp, DC
2
Pole 115 1.5 hp, DC
M-1 MCG5 TCG5 MCW15 MCW5 MCR5 MCA5 MCO5 TCO5
230 2 hp, DC
[1] For NEMA 7 & 9, these Type numbers are for cast-iron enclosures. For outdoor use, NEMA 4X and 7 & 9 cast-aluminum enclosures are available; to order these enclosures, replace the R in the
Type number with a T. For additional information, contact your local Square D™ field sales office.
[2] NEMA 12 enclosures can be field modified for outdoor applications.
[3] Approved for group motor installations in accordance with NEC 430-53(c).
14
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Class 2510, 2511, 2512 Integral Horsepower Starters—Types M and T
1.44
37
.69 Prov. for 0.44 Travel to
18 (3) #10 11 Reset 1.00 3.00 (2) .50–.75 K.O. 1.02
1.13 Mounting
25 76
Top and Bottom 26
29 3.97 5.00
Screws 101 127
NEMA 4/4X Class 2510 Type M, Open Style Class 2510 Types M and T, Sizes M-0 and M-1
Watertight, Dusttight, and Sizes M-0, M-1, M-1P NEMA 1 General Purpose Enclosure
Corrosion-Resistant Approximate Shipping Weight: 3 lb Approximate Shipping Weight: 5 lb
Glass Polyester
3.38 .22 5.00
86 .88 6 127
.94 1.69 22 1.06 5.78 .75 Conduit Hub 1.31
24 43 27 147 Top and Bottom 33
1.27 3.25 .38 NEMA 4/4X
1.00 32 83 10
25
.50 - .75 K.O. 10.00 .50 - .75 K.O. .31 Dia. .47
(2) Top Back START
254 (2) Each Side (2) Mounting 12
Holes 10.75
STOP
RESET 8.13 START 273
207 10.92
STOP
RESET 10.00 277
.22 Dia. 254
(3) Mounting
Holes
1.00 1.00
25 25
.94 4.13
24 105 (1) .50 - .75 K.O.
6.00 (2) .75 - 1.00 K.O. 1.06 2.89 5.76
152 Top and Bottom (2) .31 Wide Slots
27 73 146
Class 2510 Types M and T, Size M-1P Class 2510 Type M Sizes M-0, M-1, and M-1P
NEMA 1 General Purpose Enclosure NEMA 4/4X Watertight Stainless Steel Enclosure
Approximate Shipping Weight: 5 lb NEMA 12 Dusttight Industrial Use Enclosure
NEMA 7 & 9 Approximate Shipping Weight: 9 lb
Hazardous Location
Cast Iron
5.78 6.50 .75 6.41
147 165 19 163
.75 5.00
19 127 1.28
33
1.69
R
43
E ON
S
8.75
E 222
T R ON
E
S
OFF 7.31 10.34 E
T
186 263 OFF
8.75
(2) .31 Dia. 222
Mtg. Holes 12.13
308
(2) .31 Dia.
Mtg. Holes
1.69
.72 3.69 .75 Conduit Hub 43
18 94 .72 Top and Bottom
5.13 18 .81 1.41 .75 Conduit Hub
21 36 2.19 In Top and Bottom
130 56
Class 2510 Type M, Size M-0 (AC or DC) and M-1 (DC) Class 2510 Type M Sizes M-1 and M-1P (AC)
NEMA 4/4X Watertight, Corrosion-Resistant NEMA 4/4X Watertight, Corrosion-Resistant
Glass Polyester Enclosure Glass Polyester Enclosure
Approximate Shipping Weight: 6 lb Approximate Shipping Weight: 6 lb
15
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Manual Starters and Switches
Class 2510, 2511, 2512 Integral Horsepower Starters—Types M and T
Figure 13: Dimensions for Class 2510, 2511, and 2512 Starters
6.00
152
.66 4.69 .34 6.13
17 119 9 156
R ON
E
S
E
10.50
T
267
OFF 9.94
252
.28 Dia.
(3) .5 -.75 K.O. .22
Top and Bottom 6
Mtg. Holes
START START
1.69
.75 43 1.28
7.25 19
3.38 33
184 86
8.94 .84
227 21
16
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Accessories, Modifications, and Renewal Parts
Table 21: Accessories for Table 23: Replacement Nameplates for Class 2510 Types F and K
Class 2510 Types F and K
Nameplate Type Number—Class 2510
Description Class and Type For Type F Starter
Nameplate For Type K Switch (Includes Reset
Handle Guard Kit with Padlock Provision [1] 2510 FL1 Description Application
Marking Indication)
Emergency Off Actuator 2510 PB1 Pilot Light
Additional Key for Key Operated Devices 2510 FK1 Without With Without With
[1] Standard on Type K devices. 1-3/4" x 2-13/16" Standard commercial Blank FN1 — FN2 —
Nameplate with switch box cover or
Embossed Mounting flush plate, including Special marking
Table 22: Replacement Parts Holes for #6 Oval Square D™ stainless (specify the FN5 — FN6 —
Head Screws steel plates marking)
Description Class and Type
Blank FN10 FN20 FN30 FN40
Replacement Toggle Kits:
Type FW and KW (NEMA 4) 9998 HW1 High FN11 FN21 FN31 FN41
Type FR and KR (NEMA 7 & 9) 9998 HR2 1-29/32" x 3-27/32"
Square D NEMA 1 Low FN12 FN22 FN32 FN42
Replacement Handle Kits: Flat Nameplate with
surface mounted Forward FN13 — — —
Type MBA, MCA, MBW, MCW (NEMA 4 and12) 9998 HWA1 Mounting Holes for
enclosure or gray
Type MBR, MCR, MBW, MCW (NEMA 4X, 7 & 9) 9998 HR3 #6 Pan Head Reverse FN14 FN24 — —
flush plate
Screws
Internal Lever 9998 IL1 Special marking
(specify the FN15 FN25 FN35 FN45
marking)
Table 26: P11 Pilot Light Voltage Codes Table 27: Modifications (Types M and T Only)
for Class 2510, 2511, and 2512, Type M and T
Factory Modifications: Field Modifications:
Description
Form Number Kit Class and Type
Voltage Code
9999MP1 (110–120 V )
120 V V02 Red Pilot Light [1] P11 [2] 9999MP2 (208–240 V )
200/208 V V08 9999MP3 (440–600 V )
17
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Manual Starters and Switches
Class 2601 Reversing Drum Switches
Reversing drum switches are designed to start and reverse motors by connecting them directly across-
the-line. The devices can be used with squirrel cage motors; single-phase motors designed for
reversing service; and series, shunt, and compound DC motors. The applications should be such that
across-the-line starting of the motors is not objectionable, unless other means is provided for limiting
starting current and torque. Class 2601 drum switches are field convertible from maintained to
momentary operation.
Application Data
Type AG2
The reversing drum switches are particularly suited for use in manual reversing control applications
such as machine tools, woodworking machines, and similar types of equipment. Examples include
lathes, milling machines, planers, grinders, shapers, and boring mills. Other possible applications
include door operators, small hoists, and conveyor belts.
Overload and low-voltage protection are not incorporated into these reversing drum switches. Should
the power fail, the contacts will remain closed unless assembled for momentary operation, and the
handle will stay in the selected position. The motor will restart when the power returns.
.
18
12/2016 © 1997–2016 Schneider Electric
All Rights Reserved
Manual Starters and Switches
Class 2601 Reversing Drum Switches
Table 28: Class 2601 Device Types—NEMA 1, 4, and 13—without Overload Protection
Internal Switching
Ratings Device Type, 600 Vac Maximum Device Type, 360 Vdc Maximum
1 2 1 2 1 2
Maximum Horsepower Enclosure Enclosure
3 4 3 4 3 4
Volts NEMA 1 NEMA 4 NEMA 1 NEMA 13
AC AC
5 6 5 6 5 6 DC General Watertight and Maintained and Oiltight
1-Phase Polyphase
Purpose Dusttight Momentary [1] Flush Mounting
Reverse Off Forward
115 1.5 — 0.25
200/230 — 2 —
AG2 AW2 AG2S2 AF2
230 2 — 0.25
460/575 — 2 —
Three-Phase Wiring Diagram
115 1.5 — 2
T1 L1 200/230 — 5 —
L2 BG1 BW1 — —
230 3 — 2
T2 460/575 5 7.5 —
T3 L3
[1] Maintained–Forward; Momentary–Reverse. Not field convertible.
5.38
4.00 6.62
5.18
2.68 2.91
3.26 3.53
4.61
4.86
19
© 1997–2016 Schneider Electric 12/2016
All Rights Reserved
Schneider Electric USA, Inc. Schneider Electric and Square D are trademarks and the property of Schneider Electric SE, its
subsidiaries, and affiliated companies. All other trademarks are the property of their respective
800 Federal Street owners.
Andover, MA 01810 USA
888-778-2733 2510CT9701R01/16 Replaces 2510CT9701, 12/1997
www.schneider-electric.us © 1997–2016 Schneider Electric All Rights Reserved
12/2016