Acoma Xray
Acoma Xray
Acoma Xray
Prdnstallation
Table 3-1
Minimum Wire Size from Distribution Transformer to ,Room Disconnect
WIRE sm AE
WE
GENERATOR 30m 45 rn 60m
VOLTAGE
om') m I#w)
A N 18 AWG YB AWG U
440VAC
AWG 16
AIllfQ #
AWG 16
AWG #6
AWG 14
AWG #4
U O VAC AllWj 18 AWO P8 AwG #4
380 VAC A m 14 AWG H A% 12
PI- 10 D02-0322-R2
-
-
HF Series C;lenemtars
Pm-lmblation
POWER OUTPUT
LlNE VOLTAGE
373 kW 40 kW 45 W 50 KW akW
260 VAC R
0.0~6 0.080 n 0.071 n NA KA
380 VAC ' 0.21 R NA NA 0.15 E1 0.12 Q
Line Phase:
~ i r dbreaker
t rating should be:
For 37 k y 40 kW and 4-5k W generatars: 100 k
For 50 kW and 60 k W generators: 75 A.
UWE CURRENT
LINE VOLTAGE
375kW-14 37.5kW-3+ 4OkW-19 45kW-30 5OkW-30 60W-39
Stand-by Amperes 3A 3A 5A
All ratings and du$y cycles apply to ambient temperature between 10'C
(5OaF1and 38'C (IOO'F), average relative humidity not exceeding 95% and
altitude not exceeding 2400 m (8000 ft) a b ~ v esea level. Environment must
be controlled
within these restrictions.
This generator contains advanced circuj try which will maintain the selecbd
X-ray techniques duringadverse line conditions. However, there is a limit to
the generators ability to correct for inadequak h e power.
The power requirements given here (wire sizes, ete.) are the recommended
spedficatian and conform t o the National Electric Code. h c a l Standards in
effect could be more stringent and, therefore, must be checked.
W
itb the exception of high current carrying conductors and grounds, low
voltage connections are made with preterminated cables.
HB Series Generators
Wnstatiation .-
ltluSmtioil2-2
Mountlng Holes and Center of Gravity
2.2 MOUNTlNG AND SERVICE AREA
SURFACE
COY PONENT
bft Side Right Skfa Front Rbrr TOP Botbom
I
POWER CABINET
a5m
(19-77
0 5 tn
(19-r)
1m
W.47
COmflMeb
free
-
Ml4TROL CONSOLE
0.1 m 0.1 m m p l
w 0.1 m mprew -
P-93 (3.9") tree (3.97 free
HS ROTOR C O m O U E R
02 m
(7.v
0 2 rn
v.m
1 rn
(3s.43
- 02
v.m
m 0.1
@.st)
m
This page i
n
- W
t blank
HF Sedas
Generators
Pre-Installation
2. t PHYSICAL CHARACTERISTICS
DIMENSIONS
COMPONEm VOLUME WEIGHT
FOOT PRlHC
Length Wdtil Helght
POWER CABINm
Power Module a d HV Twubmwr 896 rnm 457 mm 490m 44.95 dft? 200.64 &I? Wkg
side by side (fwwdm?ab/e-1
-- (352T) (1 87 (19.29") (634.6 I$)
--
($2246 br3 (253 ~ b )
&.as& 40kg
Pwrer W I e
(3956w (89 Ibs)
SECTION I INTRODUCTION
insbnation.
This d~cumentconsiders only the generator and its associated oomponents.
.., Product information, environmental and eletbical requirements, and
shippingdata i s M e d .
RESPONSIBILITY OF PURCHASER
the installationplan.
1
Ptovide current room dimensions, including hall way and enby door
siz~.
TABLE OF CONTENTS
Section Page
1 INTRODUCTION .........................................................
PI-I
...................
3 2 . 4 Interconnection and Grounding Requirements
3 2 5 Safety M e s ..............................................
4 SHIPPING DATA .........................................................
PAGE C-I
APPENDIX C
SF & F'L EXPOSURES FROM
CONSOLE
During NORMAL mode (out of CALIBRATION mode), Spot Film and Fluoro
exposures must be made fiom a Spot Film Device or Foot wvitch. However, some
single tube .Fluor0 systems may require that Spot Film and Fluoro exposures to be
made from the Console PREP and EXP switches in NORMAL mode.
To do this, the PREP and EXP switches for each type of Console must be rewired
as follows.
A small signal switching switch must be added, it must be wired in such a way that
it will allow both d'bration and normal Fluoro and Spot Film exposures to be made
from the Console. figure-1 is a schematic with the recommended wiring of a small
3PDT switch used to switch Console PREP and EXPOSE signals.
r-----*-*-**--
PREP 1 I
SWITCH : I C o n s o l e 58-7 (SF PREP3
I I
0 0 I
I
I oCfiL j WHT w i r e removed f r o m PREP suitch
1 I
I I
I I
EXP L I
: TPDT switch
----------*--+.
:
PAGE C-2
O n the APR Console, the modification is much simpler. You will need to add 2 wire
jumpers on the back side of the 25-pin D-connector of J2 INTERFACE cable P/N
3028 as follows:
APPENDIX B
ONE TUBE FLUORO SYSTEM
-
Single tube Fluoro system are supplied with a single tube HV Transformer. lFluoro
is normally on tube two, but when connected to a single tube Transformer, the
filaments of the X-ray tube are reversed. To correct this, the flament return lea&
connected to the terminal block on top ofthe HV Transformer must be reversed as
follows:
The RED wire that is normally connected to the FIL 1 RTN terminai
must now be connected to FIL 2 RTN terminal.
Q The WHT
wire that is normally connected to the FTL 2 RTN terminal
must now be connected to FIL 1 RTN
terminal.
During calibration, some values, such as E03, E05, E06 and E07 of the EtAD tube
extended memory (see Chapter 5 , Table 5-1 on page 5-2 for Standard system or
Table 5-5 on page 5-7 for APR system) may have to be changed. T%is requires
setting position 6 (Tube 1 R4D 1 enabled) of the dip switch SW4 (Standard system)
or SW3 (APR system) on the Operators Console PCB to the ON (dosed) position
to allow the RAD tube selection and access to its extended memory until &%ration
is complete. No exposures are required with the RAD t u k selected.
NOTE
G. P ,
< ,
O
to d i r a t e RAD rube extended memory, you have to temhradya'
To be able
reconnect the rTV INTLK s i s a l on top of the EW Transformer until you go
back to SFIFL tnbe, I
05-02-95
-
APPENDIX A 'XWO TUBE RAD SYSTEM PAGE A-2
1
I I
I I
I 1
#
115 WAC RTN TB4-11 ! I
: 4PDT R E M Y
: 115 VAC COIL:
I
- - - - - - - --*---. I
APPENDIX A
TWO TUBE RAD SYSTEM
All spdcations for the two tube Radiographic system (RIR) are the same as the
two tube Radiographi~uoroscopic system with the exception of the following:
1.00 GENERAL-.......................................................................................... 22
2.00 S Y W M !START-UP......................................................................... 22
1.00 GENERAL...................................................................................... 23
This seelion shows the wire and mblc mns, and the &ring Peguirementsin
ablock diagrm Formore infomadon about intmmm&bn andgrounding
mfer fo "System Intemonnection " document in ibis Service Manual.)
Illustration 3-1
lnterconneetion Block Diagram
TRANSFORMER RATED 3%
REGUMION
AT 95% POWER FACTOR
( o p t i d lrse)
tmvidedb~e n
Table 3-3
Wire and Cable runs
7 1
2
See role
-
14 :208 240 VAC
Pwrer Supply lo HS Rotor Controller.
1 Ground.
NOTE: - Wre rrrn Ienglhs Were calarlaled for type THW ar TWpower cable, stranded copper con&ctors. rated at 86PF ImT).
- For wire size refer to Sedbn 3.2.2.Consul1to L a a l Standards for ground wire size ~ ' r e m e n l s .
- me system power g w p o i n t is located in Ihe Power Cabinet-
Device6 such as Safety Switch I Emergency Switch, Warning Light, and Door
Interlock Switch should be supplied and installedby the customer. (Refer tu
IZ-n 3-2.)
The Safety Switch should be installed in the Room Eleetricd Cabinet &om
Disaonneetl (close tothe Generator Power Module), and pnwided with ligth
indicatorsfor "Power OnlO f f ".It shouldbe usedfor main dimmeetion,and
lmkd in an accessible place where it mn be seen and mnkoUed during
operatian and s m i a
The Door Interlock Switch inhibits X-ray generation when Doorways t o the
X-ray room are open.
This switch should be installed in the entrance dwr(s) and its meeting
cable should be muted to the Generator Power Madde.
WARNING LIGHT
The Waming
Light is a signal lamp installed outside of the X-ray m m (near
of the main entrance) that indicates an X-ray exposure is ON. The Warning
Light connection cable should be routed t o the Generator Power Module.
(For schemutic mfer to System Intmnnectian document.)
-
D02-0322-R2 PI- 73
lllugtration3-2
&
OFF
SSr Safefy Switch ussd for generator main &sconncdon. watl ONmFF positions.
EM: Emergency Switch near to cmtml cansde andor to the room main entrance.
W Warning Light (red tamp) louted outfide of the X-ray room (near of the main entrance)
PI- 14 R2
D02-0322-
HF Series Generatow
Pebtallatbn
This section provides the shipping sizes, weights and method of shipment of
the generator c o m w t s .
Table 4-1
Shipping Data
DIMEMSLONS
COMPOMEHT WE'GHT
(MASS) METHQDOF SHIPMEW
Length W r Height
Control Conwle.
Instal lation
HF Series Generators
[mlACOMA
4
OF PROTECTION ARE
S m
It is important that everyone worktng with X-r and take adequate steps to insure protectjon
agabt injury. lt Is also 'mperative that thes wilh the recommendations of the lnternafiona!
Commission on Radiion Protection con of h e ICW wittr the recammendations ol
the National Council on Radiation bblished in NCRP Reports (available from
NCRP Publications, 7910 Woodmont & hwith Dmer apprtble standards.
TABLE OF CONTENTS
Section Page
I INTRODUClION .........................................................
2.2
PowerCabinetInsWlation ...........................................
2.3' Control ConsoIe Installation ..........................................
SECTION 1 lNTRODUCTlON
~ d assorted bits.
Electric drill m o h m
W2-0323-RZ IN- 1
HF S e r b Generators
lnstallatlon
PRE-INSTALLATIONCHECK
Conduits.
HF Series Generators
installation
2.1 UNPACKING
Upon receipt of the X-ray unit and assodatedequipment, inspect all shipping
i
containersfor signs of damage. If damage is found, notify the h e r or his
agent immediately.
1. Open the shipping box (top side) and remove the Control Console,
Inhercannection Cables, and other fxmhhed park. Do not discard any
packing material such as envelopes, b m bags until an parts are
accounted for as listed-on the packinglist.
3. Remove the Power Cabinet down from the shipping pallet. Wefer to
Section 22.)
When the equipment is unpacked, check the part numbers and serial
numbers of each component with its identification lab&, and inspect
all
pieces for visl'ble damage. If any damaged parts axe found, repait or order
repkments to prevent unnecessary delay in installation.
When the room is ready for the installation, move and position the units as
close to their final locations as possible. It may be helpful t o leave the units
on shipping skids for movement t o the installationarea.
Leavea working area around the equipment until its final assembly is
compleb.
HF Series
Generators
Installation
IllustmtIon2-1
Power Cabinet Unpacldng
W Series Generators
1. After removing the pa* material, lift both generator cavers (back
andfront covers)from the top of the cabinet. (Refer t o I Z l u s W n 2-1.)
to its site in the room. At least two people are required for this
operation.
HFSeries -rs
InsWation
&&urn 9 md 4.31.
Illustration 2-2
Power Cabinet Installation
HF Series Generators a
3. In R&F Contml Consoles, the Fluoro CPU PCB is located next to the
Console CPU PCB.
4. If AEC is inskdld, the ABC Control PCB is located below the Console
CPU PCB. Access to the AEC antrol.PCB by removing the three (3)
screws that fxxed AEC cover to the bottom of the Control Cop60le.
Illustration2-3
R2
002-0323- IN- 7
-
- .. - . ,,
24 HIGH SPEED ROTOR CONTROLLER INSTALLATlON
Set acceleration and brake times per the instructians provided *ith the HS
Rotor Controller. Weferto "High Speed Rotor Conid1ed"'SenkeM d . )
1
Illustration 2-4
HS Rotor Controller Mounting Holes
HF Series Generators
lnstallation
3.1 INTRODUCTION
1. Verify that the power supply line is "OFF"in the Room Electrical
Cabinet.
4. Internally route internally power and ground cables near the two (2)
Fastening Cable Bars.
5. Connect the power wires and the ground wire t o the comqmndhg
lugs (L1, L2, l3,Ground) located on the Back Panel of the Power
Module as indhted below:
N
PHASE LlNE
6. Route the feeder wires and canned them to the respective terminals
in the Room Electrid Cabinet.
7. Verify that Fmergency Switch has been conmckd ta Room FJectrical
Cabinet so that it cuts the power to the merator when isswitch off.
Illustration 3-1
Power Line Connection
8. Measure and verify t h e power Line in the Raom Electrical Cabinet and
according to it, connect cables "I" and %kiE"from fuses F12 and F13 t o
the indicated Transformer T2-TBs:
POWER LINE
72
IIOVAC t30VAC 2WVAC 22OVAC 240VAC 260VAC 380VAC 415VAC 440VAC 4BDVAC
-
HF Series Generators
Installation
Note B T For generafors with a "Single X-ray Tube for Fhromscopy /Spot
film: connectionsof the t7fament leads FIL-1 RTNm (TB 1-6) and
"FIL-2 R W (TB1-8)must be m r s e d , andthe "KT INL" P I - 9 )
wire musl be disconnect& and insulated fmm the terminal strip or
ground.
2. Prepare the High Voltage terminals that will be installed in the X-ray
TubeIs) receptacles. Apply Silicone Paste over the entire surface of the
Plug including the Pins.
3.4.2 S T F R CABLE
1
HIGH SPEED
In this
case, routethe S t a b cable together
w i t h the HV cables to
the Power
Cabinet. Conned t h e Stator able terminals to the Terminal Block TB4 on
the Front Panel as indicated below
IN- 12 D02-0323-R2
HF Series Generators
Installation
THERMOSTAT SIGNAL
1fanx-ray~ u bis-not
e provided with 'Thermostat signal,jump both wireends
of the Interface cable,
v
3.5 ANODEROTATOR
It is recommended
h mpp1y the HS Rotor Controller power line through
Terminal Block TB7in the Power Module.
Check the line volbge in the Power Module (TB7-1 and TB7-3) ta determin
if it can be used as the AC Line for the HS Rotor Controller.'Or connect the
neutral line to TB7-5 to supply the HS Rotor Controller between one phase
and neutral (TB7-3 and TB7-5). mfer to "High Speed Rotor C o n f t o l l ~ "
Service Manual.)
IllustrationS 2
HS Rotor Controller Power Supply (Power Moduk connections)
LINE
VOLTAGE
HS ROTOR CONTROLLER
(betwen two phases)
I AC UNE FOR
HS ROTOR CONTROLLER
(between one phase and neuhl)
1 GND
3.52 LOWSPEED
Table 3-1
Low Speed Stator Voltage
1-Phase or $Phase Sump TB7-I with fB7-2. and TB7-3 with TB7-4
3-Phase with Neutral J w T37-3with TB74. and connect Neutralto TB7-2
+IFSeries Generators
Installation
Ifthe installationis not provided with a Compatiiility Box, route and connect
the interconnection cabIes from each component installed in the system to
the Power Module or Control Console. Be advised that without a
Compatibility Box or Wall Box these connections will be difficult to make.
T h e cables that connectthe Control Console to the Power Module have Molex
connectors on the Power Module end. If needed for routing these cables
through a conduit,remove the Molex connectors to facilitate pulling the cable
by using the appropriate "Inserter1Exttactor" tool (Molex FIT-2038or Molex
HT-2285).Once these cables have been routed re-install their connectors
with the same tool.
002-0323- R2 IN- 15
HF Serlea Generators
Installation
Ilustratton 3-3
Interconneetlon Cables
TOUMWXTAGE
BREAKER
Door signal from the Room Dow Interlock Switcb enters the Control Console
through Conneetors 52-19 (door
signal) and 52-18(ground).
Identify both wires of the Interface cable,and connect their-free ends t o t h e
Room Door Interlock S e k h .
If the X-ray Room is not provided with Door signal, jump both wire ends of
the Interface cable.
HF Series Genwators
Installation
Cables from Buckys are connected h the Interface Panel of the Power
Module.
Connect each Bucky as indicated in the "System Interconnectionn and
"Schematics" documents of this Service Manual Wso, refer fo HBucky"
Service M m d .
-
IN- 18 002-0323-U2
HF Series Generators
Installation
4.1 HV TRANSFORMER
Remove the Oil Plug from the top of the HV Tmndormerand venfy
that the
oil levelis within12 mm
(0.5") from the top.
Remove the Ventilation Screw from the top of the HV Transformer.
42 CABLE FASTENING
connections,have been made and routed, wmplete the
Once that all the cable
cable installation by -g the cables securely to the cabinet. Twa Fastening
Cable Brus are used t o secure ail the cables to the back side. Interconnection
cables must be also secured to the right side Xstrueture bar) and Interface
P d in the front side. (Refer to
lllusbution 4-1.)
Intmdyroute each d l e along of the back side toward t h e cable outlets and
secure the cables to the cabinet by means of cable clamps and strain reliefs.
lllwtration 4-1
Cable Fixation and Back Cover Cable Outlets
HV CABLES
m2-0323-R2
IN-19
TABLE OF CONTENTS
System Interconnection
Section Page
2 SYSTEM 3NTERCONNECTION........................................................................................
.4
3 INTERCONNECTION CABLES
(listed in Order)
Table Bucky Interface
Liebel, Semi-Automatic
Liebel, Automatic
Ultravit
Dong-A
Vertical Bucky Inttrface
Liebel, Semi-Automatic
Liebd, Automatic
uttfavit
Dong-A
H M S High S p d Starter, CB 5 15
HMS Hgh S p e d Starter, CB 527
Tomo 1 Interface
Tomo 2 Interface
AEC, AID
System Locks
GE AEC, Modification
X-Ray On Light
Installation
4.3 COVERS
Check that all electrical connections are fmand secure, and that all cable
h p s and strain reliefs are in place. Check that all cables are correctly
mted
Re-install the Cabinet Back Cover by using the sir(6) cover screws, and
connect its internal ground wire. Pass the Power Line, High Vo1-e and
htemonnection cables through t h e respective Back Cover mble outlets.
@$w to
Illustrution 6 1 .)
T h k h i g a ~ ~ i D d i c a t t r t h L ~ ~ ~ ~ T h i r ~ k n d 0 ~
l2-22 AU3E wmcSpDtFilmryrtemmdndto~tbeSpDt~~m~~positioa~
~ m m d t o a I k u m p i i h
T h i r b w g o i D g t i p l ~ t b t ~ ~ ~ ~ ~ ~ i s l u e d t o ~
J2-24 - U E ~ c r m c S p o t % ~ d k d t o ~ & S p o t F i h n d e v i c e t o t h c a c l r r ~ ~
4- mandeaphumc5lm
Bl - W E Lnw&mW~&HTMm.Zf-PREPishbrSpotFharBAD-
kmade,elstrmK*o~isrmdt
&2 GHTDATA S a i r l d a t a t o t h ~ ~ P C B ~ d a t t i r ~ w i m ~ G ~ C L X ~
~adogJgd~rbtwrtprtd~HvPorvcr~o~tbt~CclmdPCBfhis
0-7 FIVPTCRL ~ ~ ~ n t b c o p t i o a r I A E C ~ P C B . P h r S ~ ~ f b t ~ t o k O
m a O v D a t s ~ t k ~ *t* 0 - tcfy-1200a
13-8 -kVWWN A l o w ~ k a ~ f o r t b c ~ M ~ m d r i v t ~ t w k V p W W N w b c n ~ a
~ c r p o a m m t k A B C ~
n-1I -BUCKYZ ~ l o w r i ~ t o t b c ~ a a f r c r ~ ~ c ~ ~ . ~ t ~ ~ . ~ z ~ ~ f b t
DB MID -slmd)&-
h14 -1 A b d @ t o ~ ~ ~ o l P C B ~ a d t o ~ ~ W ( rMf&rT yr b- l le
DR CMD m) drive r i d
JS-3 - R D I DR Alowsignsltodedt&+fieldiat&bhk.
154 - m 3 DR Akws~topekah~ficldinthclon~-
~ h g o i n g ~ ~ I h ~ r n b o o r t t b . ~ l l & M ~ k r
J24 -SFPREP SdOdCd~nt~Crabol~dpccprrrrIh~haSpa~Thb~kreddy
~ l h t T b 2 ~ I + F i l m ) i c d d d
I24 EOWTOII 'Ihitbwrigaal - b t N O m ~ O L D - & . t t k C r " ' ' .Sirrpnir
d ~ w I = ~ T u b l I r w > ) k ~
-
~ i r t b e ~ C O ) A M A N D i r p r l b t b t W ~ ~ ~ ~ ) h S W
J2-I7 -FLEXf - S F P R E S ~ i x ~ b a ~ v k ~ dh X
e r~ ~ ~ ~ ~
Spot*- k d
n-19 - m R %iStbt*forhDo#dtbeX-~jman'Zhh~mkwbcaprr~cqxl~lrru
I b k n @ i r h d t b E d m h ~ ~ ~ b m m t R A D p a d r i m T h i r n r
l3-3-13 -IITINL ~h~whirh~mupormeifWbehigb~&CmtbaffVT~]kin
hmrmllpgitim
PP
Jbl IClIWUT % ~ i f t b c ~ d h B u c k y I I m ~ ( ~ h T T l e I c a ~ ) .
T h i c h i ~ g o i n g ~ ~ I h A c n n l ~ O f ~ l l & s i g n l k d t o ~ i o
J2-22 ALOE #~lacSpotEhryrtcmdkdbLdvmDttbeS@W*~Wd-&
~ * r t m & o o m t ~ m n
~ b w g o i n g ~ p l i D d i c u r t r b t ~ ~ O f ~ ~ ~ i n t u s d ~ ~
n-24 -ALOE sowsptmmrystcmdirurcdto~~be~~deuictmtbenmtpositioa~
Ls- rndm&runc*
13-1 - m E Low&~~mtbt~~lPCB.Zf-PREPbloahrSp~tFhaltAD~
k~tlscaFhxm . n d
rhis~sig.at~mtwaprtofrbtHvPmvctS~~rbt~cc*lbdFeR~
J3-7 FIVPTCRL ~ O r i ~ o n t b c + A E C M ~ . P h r r S ~ ~ t b t ~ ~ b t O ~
d O ~ ~ t h c ,-~ - ft d y -0l Z M ) % W k
J54 - M 3 DR ALows~gnaltodcftttKQntCTfieldmhlaa~.
GENERAL
3.01 STANDARD!N!XEMS
3m AFXSYSTEMS
omom
4.0 AUTOMATIC EXPOSURE a N l R O L (AEC)
MFER
MAXMUM PGRMIsrBLEDosi(MPD)
~ A c r u R E R R
SE s m M B I l l T Y
RADIATION PROTECIION
MONfTORTNG OF E
FtwmEL
DHHS rnMPLIANCE
X-RAY TLIBE OOMPATIB-
smzamcAnoNs
1201 OurPurkVp
1202 OUrPtPTmA
1
m 0UrPUT-
1
m MAXIMCmiomWrmkP
1- EXPOSURETIME
1 FXUORO kVp O m U T
12-09 FLUORO z d
1213 MAXIMUM 0
RATING
13.M) WWERREQ-
13131 INVERTER-SOURCE
UM ~ICmwERsoURW
14.W SPACgREQ-
14.02 HV-RMER
14m WWERMODULE
mr n r n G v R A n 0 r r (STANDARD B APR)
POWER SWPLY (srAPa)ARD & APR)
&
POWER-UP C O ~ C A T I O N w m (STANDARD & APR)
INVERTER S A n C (!XANDARD dt APIl
LM W kVp AND mA
CAI, PR-URE (STANDARD & APR) 5-24
219
B u m 1 (TABLE) AEC CAL PROCEDURE (APR)
220 FIu4~1AM)3CALPROCEDURB(APR)
Contents
nwms
200 o m ~
3m B B U C R Y ~ A C B
5.00 -0
1 AND PHOTO-MULmPLlER r n E I W A ( = E
Contents
CHAPTER 1
INTRODUCTION
1.00 GENERAL
This manual contains installation, calibration, acceptance and service information for
the Acoma Medical Imaging, Inc. FUTURUS 2001 x-ray generator. The generator
is a part of a system wbich contains other equipment which is not descriid in this
manual. To gain an understanding ofthe complete system, study the operatois and
service manuals for all associated equipment. Also, study the FWIWZUS 2001
Operatois Manual.
Throughout the manual there are statements in shaded boxes which are preceded by
alert words. These alert words and the following statements contain information to
assist the user of the manual. The information may direct the user in the
performance of a task or it may inform the user of potentidy hazardous situations.
Each alert word is always used with only one specific type of information. The alert
words and the information with which they are used are as follows:
NOTE
WARNING
PAGE 1-2
3.00 EQUIPMENT
DESCRPIION
The Futunrs
2001 Standard x-ray generator is a 20 kHz high frequency,
constant load system with the following features:
375 k W sgstem: 25 mA, 50 mA, 75 mA, 100 mA, 150 rnA, 200 mA,
250 mA and 300 mA.
10-04-94
CHAPTER 1
INTRODUCTION
1.00 GENERAL
I Independent Heat Unit storage for each x-ray tube. Heat Unit status
can be viewed by the operator by holding the ON switch depressed and
display it through KVP display. Note that the KVP display now
displays H##, where ## is the Heat Unit %, from 0% to 99%.
AJTURUS-2081 OPERATOR'S MANUAL.
1-94
-
Independent Heat Unit storage for each x-ray tube. Heat Unit %
dispIayed constantly.
All controls and information displays are easily accessible and clearly
FUTURUS-2W)l OPERATOR'S
MANUAL
104-94
T h e following options to the FUTURUS 2001 Standard and APR generators may be
selected by the user.
The spot
film/Fluoro (RF) option provides:
W The flexible
interface is adaptable to most spot film devices.
I Constant Contrast fluoro (mA increases with kVp increases and vice
versa).
40 to 125
Optional AEC.
It is yitally important that everyone associated with x-ray work is familiar with the
recommendations ofthe Dep-ent ofHealth, National Bureau of Standards, and
the National Council on Radiation Protection. me control of diagnostic medical x-
ray equipment varies m detail from state to state. However, in general, aU of the
states adhere strictly to the established recommendations of the NCRP. It is not
practical to list all the relevant mmmendations in this manual. llerefore, prior
to operation, be sure that all personnel who are authorized to operabe the x-ray
system are familiar with the established regulations ofthe authorities named above. %
.
Also, they should be monitored to assure that they conform to the recommendations.
Current sources of information include:
Although x-ray radiation is hazardous, x-ray equipment does not pose any
danger when it is properly used. Be certain that all service and operating
personnel be
properly informed on the hazards of radiation. A b , those
X
responsLble for the system must understand the safety requirements for x-ray
operation. Study this manual and the manuals for each component in the
system to become aware of all the safety land operational requirements.
Various studies of the effects of x-ray radiation have provided a foundation for
establishing of the maximum perrm'ssf'bledose W D ) of x-ray radiation, The results
of these studies have been used by the NCRP and the ICEP to develop
recommendations for MPD.
ICRP recommends that the MPD to the most critical organs (heart, lungs, liver,
kidney, brain, etc.) accumulated at any age shall not exceed five rems multiplied by
the number of years beyond 18:
For hands, forearms, feet and ankles, the reammended MPD is 75 xems in any one
year.
Although this equipment incorporates protection against x-ray radiation other than
the useful beam, pract cal design annot provide complete protection. Equipment
i
design d& not compel the operator or his assistants to take adequate precautions,
Nor d~ it prevent the possibility of improper use which m l t s in a d o r i d or
unauthorized persons from carelessly, unwisely or
Be certain that all personnel authorized to use the equipment are aware of the
danger of excessive expsure to x-ray radiation.
l l i s equipment is sold with the understanding that Acoma Medical Imaging, Inc., its
agents and representatives, do not accept any responsibility for werexposnre of
patients or personnel to x-ray radiation.
Furthermore, Acoma Medical Imaging Lnc. does not accept any mpnsiIbiIity h r
+
overexposure ofpatients or personnel to x-ray radiation generated by this equipment
which is a result of poor operating techniques or procedures.
Also, no responsibility will be assumed for any machine that has not been serviced
and maintained in a~cordancewith the system technical manual, or which has been
modified or tampered with in any way.
Because exposure to x-ray radiation may be damaging to health, use great care to
provide protection against exposure to the primary beam. Some of the effects of x-
ray radiation are cumulative and may extend over a period ofmonths or years. The
best safety rule for x-ray operators is, Avoid exposure to the primary beam at all
times.
Any object in the path of the primary beam produces secondary (scattered) radiation.
The intensity of the secondary radiation is dependent upon the energy and intensity
of the primary beam and on the atomic number for the objector material struck by
FWTURUS-2001 OPERATOR'S MANUAL
10-04-94
the primary beam. Secondary radiation may be of greater intensity than that of the
radiation reaching the h. Take protective measures to safeguard against it.
thicknessof lead or e . q W e n t . Use such protective devices for all personnel exposed
to radiation field of 5 millikRoentgens per hour or more. While servicing or
operating x-ray equipment, do not expose hands, wrists, arms or other parts of the
body to the primary beam. ..
The most e&ctive method of determining whether or not the existing protective
measures are adequate is the use of instruments to measure the exposure in RADs.
TXs measurementshould be taken at all lbcations where the operator, or any portion
of his body may be during exposure. Eqmure must never exceed the accepted
tolerable dose.
A frequently used, but less accurate, method of determining the amount of exposure
is the placement of hat strategic locations, After a specified period of time,
develop the film to detennine the amount of radiation. Fluorescent screens (used
in a darkened rwm) may also be nsed to detect excessive radiation. 3-
10-04-94
The Acoma
Medical Imaging, Inc, x-ray generator system (FUTURUS 2001)
complieswith the Department of Health and Human Sewices Radiationperformance
standards per Tiffe 21 CFFt, Chapter 1, Subchapter J, Section 1020.
CONTROL CONSOLE
CONTROL CONSOLE
C O r n O L CONSOLE
POWER MODULE
POWER MODULE
POWER MODULE
POWER MODULE
POWER MODULE
POWER MODULE
POWER MOD=
POWER MODULE
H.T. TRANSFORMER
H.T. TRANSFORMER
H.T. M S F O R M E R
H.T. TRANSFORMER
FLUORO CONTROL
FLUORO CONTROL
Visually inspect the inside of all the major components for dust or foreign
items. Search carefully to detect objects which might cause short circuits and
for loose connections.
10-04-94
CHAPTER 2
STANDARD CONTROLS AND INDICATORS
1.00 GENERAL
AlI controls and indicators, except the fluom controls, are located on the Operatois
Console.
AU cantrok and indicators are mounted in related groups. These controls and
indiators are illustrated in Figure 2-1- Their functions are Iisted below:
OVEKOAD
R O T O R m
-
r0--1
DF=-' FLmm =
POU ERROR -
Figure 2-1
1 O N switch: applies power to the system. Also is used to display mAs on the
time display, after the unit bas been turned ON.
10-04-94
BUCKY 2 switch: selects the radiographic tube and tbe wall bucky or chest
stand. The proper Ion Chamber (if AEC option is installed) is also selected.
NO BUCKY
switch: selects the radiographic tube and no bucly.
FIELD switches: select the fields of the I w Chamber. The indicators shows
the relatiy? physical location of the Ion Chambers selected. Flashing indicators
show that no field has not been selected. At least one field must be selected
before an e w e is allowed. -These wntrols are active only in the
radiographic made.
DENSITY switches: select the 161m density of AEC exposures. Each number
indicates approximately 25% change in dose (nub). Neutral (normal) film
density is selected by pressing either +1 or -1 switch when that densily is
seiected.
PREP Mtch: prepares the x-ray tube for a radiographic exposure. The
indicator show the x-ray tube is ready br an exposure and there i s no r.
interlock failure or system faults.
EXP switch: starts the exposure. The exposure is terminated if the EXP switch
is released before normal exposure termination. When the exposure is
terminated by releasing the EXP switch, the actual mAs of the exposure is
displayed on the TIME display. The indicator remains illuminated for then
length of exposure.
kVp switch: selects the radiographic and spot film x-ray tube voltage. The
rotary kVp selector switch changes the value by 1 kVp for each position
change, Normal kVp range is 40 kVp to 125 kVp is 1 kVp steps.
mA switch: selects the radiographic and spot film x-ray tube current. Normal
IiWTlJRUS-2001 OPERATOR'S MANUAL
10-04-94
II 'ITME switch: seIects the radiographic and spot film manual exposure time.
The normal range is .005 sec to 15 sec If
AEC is selected, time is
automatidly restricted such that backup mAs cannot exceed 500 mAs. Also
selects the back-up time for AEC exposures.
I kVp display: displays selected kVp. Tbe kVp display is used to display the
-
software version number at .power up. ?3e software version number is
preceded by the letter "P" (i.e. P12). The kVp
display is also used to display
system faults. Error messages are preceded by the letter "En(i.e. E01).
MOTE
rn SM SPOT indiator: indicates that the small focal spot of the x-ray tube has
FIITURUS-2001 OPERATOR'S MANUAL
10-04-94
I LG SPOT indicator: indicates that the large focal spot of the x-ray tube has
been selected. This selection is controlled by the mA station selection
(normally 200 mA and higher).
1 FIL ERROR iodicatoc indicates a fault condition with the x-ray tube f i l m ent
control circuit and exposure is inhibited.
I ]PGM ERROR
indicator: indicates an improper technique has been detected
(e.g., no field selected in AEC mode ...) and exposure is inhibited.
RITURUS-2002OPEBATOR'S MANUAL
10-04-94
CHAPTER 3
APR CONTROLS AND INDICATORS
1.00 GENERAL
All controls and indicators, except the fluom controls, are located on the Operator's
Console.
Each technique is called up for a medium size, additional techniques are stored for
small and large sizes. The operator may select any of these a1tematives after selecting
the anatomical region and view.
For each operation, the operator can modify (override) any factor in the
preprogrammed technique to meet specific requirements,
All controls and indicators are mounted in related groups. These controls and
hdicators are illustrated in. Figure 3-1. Their functions are listed below:
FWTURUS-2001OPERATOR'S
MANUAL
10-04-94
Figure 3-1
I
OFF switch: removes power horn the system. ..
I BUCKY 1 switch applies pwwer to the system. After power has been applied
will default to NO BUCKY.To select BUCKY 1 FABLE
to the system, it
BUCKY, RAD tube), this switch
must be prtssed again.
BUCKY 2 switch: applies power to the system. After pawer has been applied
to the system, it will default to NO BUCKY. To
select BUCKY 2 (WALL
BUCKY,RAD tnbe), this switch must be pressed again.
2
NO BUCKY switch: applies power to the system. After power has been
applied to the system, this switch selects the RAD tube and NO BUCKY.
SPOT LlLM switch: applies power to the system. After power has been
applied to the system, it will default to NO BUCKY.To select SPOT FILM
(FLUORO tube), tbis switch must be pressed again.
It PED PATIENT switch: selects routine for children (pediatric) when indicator
is ON or adult when the indicator is OFF.
10-04-94
I MEDIUM PATIENT switch: selects routine for average size objects (normal
program).
II LARGE PATIENT switch: selects routine for larger size objects.
FIELD switches: select the fields of the Ion Chamber. The indicators shows
the relative physid location of the Ion Chambersselected. Flashing indicators
show that no field has not been selected. At Ieast one field must be selected
before an exposure is allowed. These cantrols are active only in the
radiographic mode.
I FILM SCREEN switches: select the FILM-SCFEEN speed of the AEC mode
only. Only one FILMSCREEN cad be selected at a time. FILM-SCREEN 1
is for &stspeed (eg., 400speed), twice faster than FILM-SCREEN 2,FILM-
SCREEN 2 is for medium speed .(e.g., 200 speed), twice faster than FILM-
SCREEN 3, and FILMSCREEN 3 is for slaw speed (e.g., 100 speed).
I kVp switches: select the radiographic and spot H m x-ray tube voltage. The
kVp up and down switches change the value by 1 kVp. Normal kVp range is
40 kVp to 125 kVp is 1 kVp
steps.
II mAs switches: select the radiographic and spot film PIE-MAS. Normal range
is
-125 mAs to 500 mAs in AEC mode, and horn -125 mAs to 1500 mAs in
MANUAL mode. mA and TIME stations wiU change accordingly to produce
an appropriate mAs steps, which is approximately 25% in upward increments
and 20% in downward decrements.
I mA switches: select the radiographicand spot film x-ray tube current. Normal
range is 25 mA to 300 mA (37.5 kW),or 500 mA (40 kW,45 kW),or 600 mA
TIME switches: select the radiographic and spot film manual exposure time.
F"UTURUS-2001 OPERATOR'S MANUAL
1044-94
The normal
range is .005 sec to 15 sec, If AEC is selected, time is
automatically restricted such that backup mks cannot exceed 500 mAs. Also
selects the back-up time for AEC exposures.
II FILM DEN switches: select the film density of AEC exposures. Each number
indicates anmximately 25% ,change in dose ( d l . Neutral (normal) film
density is selected by selecting 0 FILM DEN.
LABELED AX* switches(between top and bottom displays): select the program
for the anatomid region named on the control.
9-
WMBELED switches (at top and bottom of bottom display): select the view
or value visible in the display directly below or above it.
I PREP swit*. prepares the x-ray tube for a radiographic exposure. The
indicator shaw the x-ray tube is ready for an expofllre and there is no y,
interlock failure or system Eaults.
1 EXP switch: starts the exposure.The exposure is terminated if the EXP witch
is released before normal exposure termination. The indicator remains
illuminated for then length of exposure.
kVpdispIaydispiaysselectedkVp.ThekVpdisplayisusedtodisp1aythe
software version number at power up. The kVp display is also used to display
system faults. Error messages are preceded by the letter "E" (i.e. E01).
II mAs display: displays selected mAs. After the exposure is complete, the
FUTUIBUS-2001 OPERATOR'S MANUAL
10-04-94
display indicates the actual mAs momentarily (whether the exposure was
normally terminated, or by releasing EXP button during exposure).
II HEAT UNITS display: displays heat which the tube has accumulated during
operation. DispIays as a percent of a preselected vdue.
II TOP LCD
display: displays messages, error codes, CAL data(in calibration
mode), and selected exposure parameters.
.
I BOTIOM LCD display: displays view options when selecting the labeled AP
switches (e.g., SKULL, FACIAL .,.) between top and bottom displays, or a
selected view when pressing one ofthe unlabeled switches at top and bottom
of bottom display, also displays function keys (UP, DOWN and STORE) in
calibration mode.
SMALL SPOT indicator: indicates that the small f d spot of the x-ray tube
has been selected. This selection is controlled by the mA station selection
(normally 150 mA and lower).
OVER LOAD indicator indimtes that selected exposure factors exceed the
power rating of the x-ray tube and errposure is inhibited.
ROTOR ERROR
indicator: indicates a fault condition with the x-ray tube
rotor circuit in PREP mode and exposure is inhibited.
H L ERROR indicator: indicates a fault condition with the x-ray tube filament
control circuit and exposure is inhiiited.
HEAT UNITS indicator: indicates that the accumufated heat during operation
has exceeded 99% of the heat unit rating of the tube and exposure is
hbiiited.
1044-94
CHAPTER 4
FLUORO
CONTROLS AND INDICATORS
1.00 GENERAL
All fluoro controls and indicators are located on the F'luoro Control Box wbich is
mounted near the spot Hm device and/or image system.
The fluoroscope
is selected at the fIuoro control box.
PPS switch (DIGITALFLUORO BOX only): selects fluuoro kVp pulse rate
- (Pulses Per Second).
I ICVlP DOWN switch - decreases fluoro kVp when in the manual mode.
I RADISF switch changes the x-ray control from SF to RAD or RAD to SF.
MAG 1 switch:
selects magnification level 1 (normally 6 in.) mode on the
image tube.
kVp display: displays selected fluoro kVp in MANUAL mode or actual kVp
in AlBS mode.
FUTURUS-2M)I OPERATOR'S MANUAL
10-04-94
10-04-94
CHAPTER 5
OPERATING PROCEDURES
1.00 GENERAL
The Fururus 2001 generator requires 115 VAC for the Control Logic and 240
VAC or 4-80 VAC for the Power Module to operate. Make sure that you have all
the required circuit breakers ON before turning on the system. For system with
High Speed Stater, make sure that the HSS circuit breaker is dso ON.
CHAPTER 6
TECHNIQUE CHART
1.00 GENERAL
The Furttrtls
2001 generator has the equivalent radiation output of a three phase
system. Three phase of mnstant potential technique charts should be used for all
exposures. AEC (if installed) is recommended h r dl appropriate exposures.
Many factors can influence the film density, including the x-ray tube, x-ray beam
filtration, film prowsing factors and etc. The following
technique chart is for a 7
typical 400 speed film-screen combination and a medium size patient. The listed
techniques are suggestions only.
liWTURUS-2001 OPERATOR'S MANUAL
10-04-94
ABDOMEN
ANKLE
C-SPINE
Position Field size film loc. SID kVp rnA sec mAs
CHEm
10-04-94
ELBOW
AP 8 X 10
NOBKY 102 62 100 .050 5
Lateral 8 X 10 NO BKY
102 62 100 .075 75
Oblique 8 X 10 NOBKY 102 62 100 -050 5
FEMUR
Y
Position Reldsize FiFjiImloc, SU) kVp mA sec mAs
FINGER
FQar
10-04-94
FOREARM
Iated 10 X 12
NO BKY
102 62 100 -075 7.5
HANX)
HIP
Position Field size E l m Ioc. SID kVp mA sec mAs
HUMERUS
IVP
Position Field size film l a SID kVp mA see mAs
RPo 14 X 17
BUCKY 102 78 300 -200 60
KNEE
lWTURUS-2001OPERATOR'S MANUAL
10-04-94
PELYIS
SHOULDER
SKULL
Rt Lateral 10 X 12
BUCKY 102 76 300 .a50 15
Townes 10 X 12 BUCKY 102 80 300 -100 30
T-SPINE
10-04-94
TrBIA-FIBITILA
AP 7 X 17 NO BKY
Lateral 7 X 17 NO BKY
TOES
AP 8 X 10 NO BKY
Oblique 8 X 10 NO BKY
WRIsr
10-04-94
CHAPTER 7
APR ANATOMICAL
P R O G W S
On the APR Console, when you first turn it on (by seIecting any one of the
following remptors, BUCKY 1, BUCKY 2, NO BUCKY or SPOT FILM).
The top display starts displaying "SOFTWAREVERSION #,#= first, then "E 1" -.
To use the anatomical programs, you must select a body region first (e.g.,
SKULL), and then- and then a view (e-g., APIPA).
After a body region has been selected, the top display starts displaying "SELEn
A VIEW", and the bottom display displays all 8 availlabe views for that body
region. Select a view from the bottom display (with SW1 through SWS, see figure
3-2).
After a view has been selected, the top dispIay displays all the technique
parameters for that view, such as KVP, mAs, mA, TIME, and FILM DEN.
2.01 Note that in RGD mode, tbere are 8 body regions, each body region has 8
views (see table 7-I), with the exception of EXTREM TBL TOP (see table
7-2) and SPECMUCONTRAST (see table 7-3)which has some sub-views
for each view as follows:
F'UTURUS-2001 OPERGTOR'S MANUAL
10-04-94
With 97 views and sub-vim for 3 sizes for ADULT, and 3 sizes for
FUiWRIJS-2OOl OPERATOR'S MANUAL
1044-94
1 Select ADULT
(FEDPATIENT switch OFF) or PEDIATRIC
(PED PATENT switch ON), the select a patient size S m
URGE
MEDIUM or
Select a mA value.
II Select a value.
When
hi&selecting technique parameters, press SW5 and SW8
(see frgure 3-1) simultaneously to store the AP technique
into the memorg.
PAGE
14
Independent Heat Unit storage for each x-ray tube. Heat Unit status
can be viewed by the operator by holding the ON switch depressed and
display it through KVP display. Note that the KVP display now
displays W##,
where ## is the Heat Unit %, h r n 0% to 99%.
375 k W system: 25 mA, 50 -75 m& 100 mA, 150 mA, 200 mA,
250 mA and 300 mk
I Independent Heat Unit storage for each x-ray tube. Heat Unit %
displayed constantly.
All controls and information displays are easily accessib1e and clearly
visibIe on the control panel.
This
-tern provides a cost effective two tube Radiographic installation.
Constant Contrast fluoro (mA increases with kVp increases and vice
vm).
X
i 40 to 125 kVp (maximum fluoro kVp programmable) in 1 kVp steps.
Optional AEC.
PAGE 1-7
However, in no case sball the exposure exceed three (3) rems in any period of 13
consecutive weeks.
For bands, forearms, feet and ankles, the recommended MPD is 75 rems in any one
Year*
A1though this equipment incorporates protection against x-ray radiation other than
the useful beam, practical design cannot provide complete protection. Equipment
design does not compel the operator or his assistants to take adequate precautions. 7
Nor does it prevent the possibility of improper use which results in authorized or
unauthorized persons from carelessly, unwisely or unknowingly exposing themselves
or others to direct or secondary radiation. Allow only authorized, properly trained
personnei to operate this equipment
Be certain that all personnel authorized to use the equipment are aware of the
danger of excessive exposure to x-ray radiation.
This equipment is sold with the understanding that Acoma Medical Imaging, Inc., its
agents and representatives, do not accept any responsiiility for overexposure of
patients or personnel to x-ray radiation.
Furthermore, Awma Medical Imaging, Inc. does not accept any responsibility for
overexpawe of patients or personnel to x-ray radiation generated by this equipment
which is a result of poor operating techniques or procedures.
-%
Also, no responsibility will be assumed for any machine that has not been serviced
and maintained in accordance with the system technical manual, or which has been
modified or tampered with in any way.
Any object in the path of the primary beam produces secondary (scattered) radiation-
The intensity of the secondary radiation is dependent upon the energy and intensity
of the primary beam and on the atomic number for the objector material struck by
PAGE
1-8
the p r i m q beam. Secondary radiation may be of greater intensity than that of the
radiation reaching the film. Take protective measures to safeguard against it.
9.00 MONITORING OF ] P ] E R S O ~
The most effective method of determining whether or not the existing protective
measures are adequate is the use ofinstruments to measure the exposure in M s .
This measurement should be taken at all 1ocations where the operator, or any portion
of his body may be during expoflue. Exposure must never exceed the accepted
tolerable dose.
A frequently used, but less accurate, method of determining the amount of exposure
is the placement of
flrn at strategic locations. After a s w e d p e r i d of time,
develop the film to determine the amount of radiation. Fluorescent screens (used
in a darkened room) may also be used to detect excessive radiation.
The Awma Medical Imaging, Inc., x-ray generator system (IWTURUS 2001)
complieswith the DepartmentofHealth and Human Services Radiation performance
standards per Title 21 CFR,Chapter 1, Subchapter J, Sgctiw 1020.
CONTROL CONSOLE
CONTROL CONSOLE
CONTROL CONSOLE
POWER
MODULE
POWER
MODULE
POWER
M O D U
POWER
M O D U
POWER
MODULE
POWER
MODULE
POWER
MODULE
POWER MODULE
H.T. TRANSFORMER
H.T. TRANSFORMER
KT.TRANSFORMER
N.T. TRANSFORMER
PLUORO CONTROL
FLUOR0 CONTROL
PAGE 1-10
TabJe 5-14 through 5-16 in Chapter 5 list all the x-ray t u b that are presently
cornpabile with the above listed certified components.
12.00 SPECIFICATIONS
The following specifications apply to all models of the FUTURUS 2001 x-ray
generator except where specific values to certain models are listed. All measurements
are made in compliance with the directions of the FUTURUS 2001 Service Manual
in the Installation, Calibration and Acceptance procedures.
NOTE
-
+5% of indicated kVp, &2 kVp.
1202 OuTFUTmA
-
+5% of indicated mA, f5 mk
+
-10% of indicated mAs, +2 mAs,
1204 MAxlmJM 0 m m A s
II In AEC:
300 mAS for 37.5 k W system, 500 mAs for 40 kW,45 k W and
60 k
W systems.
+5%
- of indiated value L 2 kVp.
12.08 FLUORO EXPOSURETIME
-
+5% of indicated time.
-
+25% of indicated value
+1 mk
1210 X-RAY
G-TOR DUTY CYUE
1211 MAXIMUMBTURATING
T h e maximum
momentary input current rating for the Futurus 2001 is listed
inTable 1-1 below:
PAGE 1-12
The maximum output rating for the Futurus 2001 is listed in Table 1-2 below:
The FUTURUS 2001 X-Ray generator requires 2 seperate input power sources with
low speed rotor system, and requires 3 seperate input power sources with high speed
rotor spscem as follows:
13.01
lNWRTER POWER SOURCE
, .
~ i b d k d
': *s h for
, SV nm
#00 # 00 #W # 00
Roawnmelldcd NOT
- wire s k for RECOMMENDED # 00 #OO
- - 1m run
Table 1-3: Maximum momentary input power and recommended wire size-
PAGE 1-14
NOTE
A seperate 115 VAC,15 AMP circuit breaker required for the Futurus 2001
Control circuit. It is strongly recommended that this power source should not
come fiom the same transformer that Is used for the
source
to prevent possible noise interference problems for the
FUTURUS 2001
High Speed Starter power source: A seperate 240 VAC,1 phase, 20 AMP
circuit breaker also required for a High Speed Starter if the system has one.
The physical dimensions of the Operatofs Console, the Power Module and the
Transformer are as follows.
See figures 1-1 and 1-2 (Note: APR Console not shown, but dimensions for
Standard and APR Consoles are the same)
Height =
3.00 inches
PAGE 1-15
1 An invalid RAD tube type has been detected. C b d tubs 1 tube type in E02. I
1) 375KW,40- 45gW Tbt I G n s are over the normal operating temperature. It
could also just need d i b r a t i o n , set IGBT THERMAL SENSOR CALTBRATION in this 1
chapter.
I Main
invertor power supply failure detected or missing incoming p w c r line (L1and L2 to
the Power M d u l t ) .
Tht x-ray tube anode a n e n t at the stari of an expormre was missing. Problem wuld be
filament or filament &it failure.
Power Module is not responding. PmIbIc defective serial curnmunication link or the CPU
HT Controller PCB is not nmniag properly.
on the
I
circuit on the HT Controller PCB.
mA current feedback
is not at zero volts in standby mode. Probable cause is a defective mA
II/l
1 current monitoring drcuit o n the HT Controller PCB or the shield wire of the Power 11
II Module to the ~rksformcrterminal s h i p interconnect cable is not grounded.
kVp feedback is not at zero volts in standby mode. Probable cause is a defective kVp
I
CEAFIER 6 -T R O U B ~ o o T e K ; PAGE 6-5
89-XCFI
WARNLNG
5.01 Turn system off, turn 240 or 480 VAC line circuit breaker OFF.
5.02 Make sure that the inverter power supply is compJetely dkharged.
NOTE
Verifythatinstandby,thegateisbiasedto-5VDC&lVDC.
Make x-ray exposure for 6 second long (note that no radiation
should be produced, because the 240 VAC or 480 VAC circuit
breaker is still OFF), verify that the gate drive signal will swing
between the - 5 V and the + 15 V as shown in figure 6-1
below:
PAGE
6 4
5.09 If gate standby voltage or gate drive signal is bad, replace both the
IGBT and the IGBT DRIVER or IPM DRNER PC13 together.
5.10 Repeat the same procedure for "G2" & "E2II,"G3"& "E3"and "G4"&
"E4"on A300341
IGBT DIVER PCB or J 4 4 (GND2) and J4-3 (W
DR2) on A3063-01 LPM DRIVER PCB to determine if other IGBT is
also defective.
5.1 1 When finished, return DIP SW2-2 on the HT Controller PCB to OFF,
.
+
-A
.C I
, 6 .;
, ,
k\V ,'$*,
," ,,*m ] [ N G
,, A
. , L.,-
;<A '$@*; -.,'i%
GATE (+). COLLECTOR (-1 OPEN (OVER RANGE) NOT APPLICABLE FOR 60 KW
GATE (-), COLLEiCTOR (+ ) OPEN (OVER RANGE) NOT APPUCABLE FOR 60 KW
GATE (+), EMITTER (-1 OPEN (OVER RANGE) NOT APPLICABLE FOR 60 KW
- GATE (-1, EMITTER (+) OPEN (OVER U N G E ) NOT APPUCABLE FOR 60 KW
COLLECTOR (+), EMITTER (-) OPEN (OVER RANGE)
COLL?XTOR (-), EMTlZR (+) SOME RESISTANCE
READING (12K TO 2%)
The RESET switch on the HT .Controller PCB is used for the KV and MA
MULTIPLYING DIGITALTO ANALOG CONVERTER P A C ) TEST. When the
RESET switch is pressed, the HT Controller MicroprocessorwilI stop communimtion
with the Operator's Console and start outputting the count from 0 to 255 to U17 (KV
MULTIPLYING DAC IC) and U22 (FIL MULTIPLYING IlAC IC).This counting
cycle will be repeated for as long as the system is on, the only way to reset the system
is to turn off and then turn on the system again. Each MULTIPLYING DAC output -
can be verified as follows:
7.01 On the HT Controller PCB, connect the osci1loscope ground lead to GND test
point (top right of PCB).
7.03
To check the KV MULTIPLYING DAC U17,connect the probe to U17 pin
2. Verify that a sawtooth waveform 5V high, about 325mS period is observed
as shown in figure 6-3.If the waveform does not look normal, replace U17.
7.04 To check the FIL MULTIPLYING DAC U22, connect the probe ro U22 pin
2. Verify that a sawtooth waveform SV high, about 325111speriod is observed
as shown in figure 6-3. If the waveform does not look normal, replace U22.
PAGE
6-9
OSCILLOSCOPE SITIlNG:
fV/oMSION *
1OOrnQDMSlON
Figure 6-3
8.02 Use a 1K, 10 turn potentiometer, connect its center wiper to PI-8 and one
end to "GND"test point on the HT Controller PCB (top right side of pcb).
8.03 Turn system on, set the potentiometer for 150 ohms +1 ohm, adjust R10 on
the HT Controller PCB so that error code E09 just barely comes on in the
kVp display window.
8.04 Verify that when the potentiometer resistance is set for 140 ohms +1 ohm,
error code E09 goes off and normal kVp display comes back on.
8.05 Fine tuning E09 by repeating 10.03 and 10.04 as needed until the threshold
is correctly set.
8.06 When finish, turn system off. Remove the potentiometer, reconnect wire to
PI-8.
PAGE 6-10
The HT ControIler PCB contains a 4 channel A D converter, U4. The four channels
are as follows:
Channel 2 - kVp i
Channel 3 mA
Each of the A/D channels can be dispIayed on the Operator Console through kVp
display window. The AfD channel is dispIayed by setting dip switch SWS(on the
Operator Console PCB) positions 3 and 4 to OFF, than press one of the DENSITY
buttons as foilows:
-2 Last actual mA
When the system is first turned ON, reading the Rotor Current, kVp and mA
channels display the value of the present input to these channels which should be
approximately zero (less than 10).
The Filament current channel reads the stand-by filament current and should read
a value approximately equal to the filament stand-by number that was programmed
into tube 1 extended memory EOI.
After PREP button is pressed, the Rotor Current channel will display the rotor
current value (approximately 100 to 130 for a 240 VAC line) for the last PREP cycle.
After an exposure, the kVp channel will display the average kVp of t h e exposure and
rhe m A channel will: display the average m A of the exposure. If the exposure is
PAGE 6-11
longer that 0 5 SEC, than the reading is only for the first 0 5 SEC of the exposure.
Note that the feedback must be active (positions 3 and 4 of SW2 on the HT
ControUer PCB must be OFF) for the kVp and mA to be displayed.
If these values are not read than there is possibly a problem on the HT Control PCB.
The high voltage inverter has a built-in current limit on the switching devices
(IGBTs). When this current limit is exceeded, the kVp drops sharply (by 10
to 30 kVp). Check for defective or poor connection of the MKROME wire
in series with the IGBT bridge
10.03 Line voltage too low, kV regulating circuit could not regulate output kVp, a
15 kVA BUCKBOOST transformer xequired to increase line voltage up to
about 256VAC .
10.04 Distribution transformer kVA rating too low (soft line), kV regulatingcircuit
could not regulate output kVp.Tube 1
mended memory E07 MAXIMUM
KW must be derated to match with line kVA capacity or a distribution
transformer with the kVA rating of 1.5 times the system KW rating is required
(e.g., a 60kVA transformer for a 40KW system).
11.02 Check for defective or poor connection of the NlKROME wire (37.SKW,
40KW & 45KW onIy).
11.04 112 of the Inverter bridge is defective/inoperative. Check that a11 four gate
drives are present at the IGBTs gate terminals as demibed in paragraph 5.00
in this Chapter.
If any gate drive does not look normal, a resistance check for a possibly
defective IGBT is required as desmied in paragraph 6.00 in this Chapter.
12.02 A n under rated x-ray tube has been mistakenly installed. Consult your x-ray
tube data sheets for verification of mA and kVp ratings of focal spots.
12.05 X-ray tube too old, filament(s) have been excessively evaporated
(filament too resistive). Tube must be replaced.
If the exposure time is much shorter than the time displayed, the probable cause is
that hard-charge K6 is not energized on PREP. In this case, the exposure is
terminated whenever the charge on the capacitor bank is depleted.
PAGE 6-13
13.02 Verify that the -CHRG DR output signal at PI-16 ofthe HT Controller PCB
- goes low to turn on K6 during PREP. Tf not, U9 and/or Q1 FEl' (Field effect
transistor) on the HT Controller PCB could be defective.
14.01 This can happen in the new installation, if Transformer ANODE is connected
to Tube CATHODE, and Transformer CATHODE is connected to Tube
ANODE. Check your HV cables for reversed connection.
15.02 If this occurs at all times, replace CR5 diode on the Controller PCB.
If they are not present, perform the MULTIPLYING DAC CHECK for U17
as described in paragraph 7.00 in this Chapter. If no sawtooth waveform is
observed, replace U17.
16.02 After step 16.01 is verified good, and there is still no -W DRl and -ICVDR2
present at P3 pin 1 and P3 pin 2 respectively.
Verify that KV DR1 and KV Dl22 are present at U19 pin 10 and U19 pin 9
respectively. If no KV DR waveforms are observed, replace U19.
-
CHAPiXR 6 TROUBLESHOOTING PAGE 6-14
-1-
Verify that KV DR1 and KV DR2 are present at U20 pin 18 and U20 pin 17
respectively. If no KV DR waveforms are observed, replace U2U.
16.03 Check C9, a 40 uF,450V capacitor in the bottom shelf for open circuited
Replace C9 if needed.
17.00 NO FIUCMENT
OUTPUT
-
17.01 Perform filament check as descn'bed in paragraph 2.00. If everything checked
out good, go to step 17-02.
17.02 On the HT Controller PCB,verify that -FlL DRI and -FIL DR2 are present
at P3 pin 4 and P3 pin 5 respectively.
If they are not present, perfom the MULTIPLYING DAC CHECK for U22
as described in paragraph 7.00 in this Chapter. If no sawtooth waveform is
observed, replace U22.
17.03 After step 17.02 is verified good, and there is still no -FIL DRI and -FILDR2
present at P3 pin 4 and P3 pin 5 respectively.
Verify that FIL DR1 and Fn.DR2 are present at U20 pin 16 and U20 pin 15
respectively. If no FfL DR waveforms are observed, replace Urn.
18,01 CPU PCB P1 connector needs to be reseated into J7 on the back side of
Console Control PCB.
circuit. Verify and correct so that all the ion-chamber p u n d ( s ) and photo-
muItiplier ground are connected ONLY to the AEC cable ground (J3
BROWN WIRE). See ION-CHAMBER AND PHOTO-MULTIPLIER
TUBE INTERFACE in Chapter 7.
~eraIftbe~are~ed,yaocancbeckby~ectingthe53
CABLE (P/N A3029-01) to the back of tbe Operato131-1e. Ail the ion-
chamber grounds and phot*multipher ground shanld l x floating f b m the
&a!Bisgmmd
When reconnecting the J3 CAB= to the back of the Opaator's -1e. All
the i o ~ h a m b e rgrounds and photo-multiplier grmmd &odd read O ohm to
the^^
19.02 AEC cable shield wire is grounded on both ends. Check your AEC wiring,
make sure that fiorn the Ion Chamber to the Operator's Console, the AEC
cable shieId is grounded only on one end (shield wire normally not grounded
- at Operator's GonsoIe end).
Connect one side of a set of normally open contacts to the ionchamber reset
signal, the other side to ground. A cIamping diode must also be connected
across the relay coil, with the cathode toward +12 V side and the anode
toward the START DR signal side.
PAGE 7-1
CHAPTER 7
SYSTEM INTERFACE
T h e Fuhuus
X-ray generator is designed to easily interface with most X-ray tables,
both RF and IUD. AU input sipah are active low. This means that the inputs
must be pulled to ground (chassis ground of the generator) thm mntacts on a relay,
by a transistor ox other suitable switching device. The nurent requirement of the
switch is less than 10 mk Table 7-1 lists all of the input signals and their functions.
200 OUTPUTS
The output signds from the generator to the table etc. are actr've low (switched to
chassis ground of the generator). One exception of this is the ALOE (actual length
of expose) which is present as both active low (-ALOE) and active high (ALOE).
The output are open collecror &amistor drivers with a maximum load current of0 5
ampere at 24 VDC. Table 7-1 lists all of the output signds and their functions.
PAGE 7-2
TABLE 7
-1
==OR SIGNAL NAME FUTURUS ODNSOIE VO SIGNAL D-ON
U In
XCADIsF mode, -PREP and -EXPOSE b
t h
to generate a Radiographic exposure.
must be Iow
-EXPOSE signal gots low for the amount of time
tbat is selected on tbt Console.
C-HT DATA Output, serial data to the H.T. CONTROL PCB CPU
in
the Paver Module. This data is
~ c h r o n o uwith
s th t C-HI
CLK signat
HT-C DATA Input, seriai data from the H.T. CONTROL PCB CPU in
the Power Module.This data is vcbronous with the HTC
CUC.signal.
Output, low active signal. This signal is normalfy high, at
the start of prep cycle when dl the interlocks are ok, it
goes low and generates X-ray preparation wmmand signal
to the H.T. CONTROL PCB in the Power Module. It is
used to boost X-ray tube filament to the Iwe1 that controls
the front-end of the rnA waveform of the mA station
selected and to start the X-ray tuk rotor in Radiographic
mode.
C-HT CLK Output, serial data clock lo the H.T. CONTROL PCB CPU
in the Power M d u l e . This dock synchronizes the C-HT
DATA signal.
KT-C CLK Input, serial data clock from the K.T. CONTROL PCB
CPU in the Power Module. This clock synchronizes the
HT-C DATA signal.
-PWR CONT Oulput, low a&e signal. This signal is normally +24VDC
high when the system is off, wbcn the system is tuned on,
it goes low to energize the main 1ine contactor, K5,in tbe
P m t r Module bottom shelf.
-Bum 2 DR CMD Output, low active signal. This signal is normally +24VDC
high, at the end of prep cycle when the X-RAY switch on
the Consolt is p~csstd,it goes law and generates the Bucky
2 start command signal to the INTERFACE CONTROL
PCB in the Pmer Module to start the Wall Bucky grid.
-3UCKYEXP Input, low aetive signal. This signal is normally high, and
originates from the INTERFACE CONTROL PCB in the
Power Modub. It is used to start a Bucky
exposure.
-BUCKY 1 DR CMD Output, low active signal. This signal is normally i-24VDC
high, a t the end of prep cycle when t h e X-RAY switch on
the Console is pressed, i f goes low and generates the Bucky
PAGE 7 4
-SF PREP Input, low active signal. This signal is normally high, and
originates from the Spot Film M e .At the start of SF
prep cycle when all the intrrlmh art ok, it low and
generates X-ray preparation cbmmind sigual to the
Console, which in turn gentrat- the -PREPsignal to the
H.T. CONTROL PC3 in the Pawtr Modutt. It k used to
boost X-ray tube filament to the level that controls the
hont-end of the mA waveform of the mA station selected
and to start the X-ray tube rotor in Radiographic mode.
-COLL;IMATOR Input, low active signal. This signal is normally high, and
originates from the overhead collimator system. When the
collimator inttrlmk is ok, it goes low and dm -PREP
and -EXPOSE signals.
-ROOMLIGHT ,
Output, low adivt signal. This signal is normally high,
when
a RAD/SF prep witch or
FL X-ray switch is activated, it
goes low until the switch is deactivated. It is normally used
to. drive the X-RAY warning ligbt at the ruom door.
-READY Output, low a&e signal. This signal is normally high, when
the RADEF prep qcle is completed, it goes low (at the
end of rotor
-FLEXP Input, low active signal. This signal is normally bigh, and
used with Standard FIuoro o p k wly. It originates fiom
the X-ray command of the Spot Film Device and Foot
switch. Whenever the Spot Film Dcvicc X-ray -itch or
Foot witch is
adhe, it goes low and generates FL X-ray
wmmand signal to the ConsoIe,which in turn generates the
-EXPOSE
sigual to the H.T. OONTROL PCB in the
Power Mddc to start a Fluorcxzcopic -we.
-EXPEND Output, low active signal. This signal is normally high, when
the RADlSF exposure cycle is completed, it goes low for
50 mS (fixed time). It is normally used to interface to some
film changers, etc.
PAGE 7
6
IC 3 INPUT Input, afialog signal. This signal originates from the Spot
Film Dcl ~ e cIonchamber output in the R/F v t e m (SF
Tube and AEC on Console must be selected) or from the
second RAD Tube Table Bucky Ion-chamber output in the
RIR system (TUBE2 or RAD 2 and BUCKY 1 on Console
must be seltaed), normally
used for camettcldirect
technique phototiming.
chamber(s).
GND Input and output, Console AEC return ground for AEC
and Phototube signals.
IC 2 INPUT Input, analog signal. This signal originates from tbe Wall
Budq Ion-chamber output (TUBE 1 or RAD 1 and
BUCKY 2 on Console must be selected), normally used for
ossetteldirect technique pbototiming.
C-FL DATA Output, trial data to thc Fluoro Box CPU. This data is
synchronous with the GFL CLK signd.
-CAM FL EXP
Input, low active signal. This signal is nomaUy high, and
usad with Digital FIuoro option onIy. It originat- from the
X-ray command of tbe Spot Film Device and Foot wit&
and then being processed by the Fluoro Box CPU (to
FL-C DATA Input, serial data &om the Fluoro Box CPU. This data is
syaebronous with the FL-C CLK signal,
FL-C CLK Input, serial data clwk from the Fluoro Box CPU. This
clock synchronizes the FL-C DATA signal.
+12V (UNREG)
Output, unregulated + 1ZV supply for Fluoro Bor
GND Input and output, ConsoIe-FluoroBox return ground.
C-FL CLK Output, serial data cfock to the FIuoro 3ox CPU. This
dock synchronk the GFL DATA signal,
CAM SYNC Input, 1-30 Hz camera sync signal originates h m tbe CCU
(Camera Control Unit) of the Digital Camera sfstern then
being processed by the FIuoro Box CPU. This signal is used
to trigger the -EXPOSE signal at the PPS rate (Pulse Per
Second) s e l t a d on the Digital Fluoro Box for Fluoro
exposure (Digital Fluoro option only). Fluom Box
selectable pulse rate are: 1,3, 6, 15 and 30 PPS.
GND Input, Console return ground for +5V, -+ 12V and -12V.
+5v Input, Console f 5V supply for Digital circuit.
Up to 3 Ionxhambers and I Phototube can be interfaced with the system through the
AEC able as
s b m in
figure 7-3.
Also note that the loncbamber and Phototube grounds must bc connected to Opemtofs Console
ground through the AEC a b l e (PN A3025-1). DO NOT WNNEff TFIESE GROUND TO 3lI6
POWER MODULE GROUND OR ANY CKASSIS GROUND. IF GROUND
a N N E l X l O N S ARECORRECTLY OD-, BYDISWNNECIINGTHBAECCABLE
TO THE OPERATORS WNSOIJ3 ALL IONXHAMBER ANZ) P H GROUNDS
~
S H O W BE FLOATING TO CHASSIS GROUND-
Figure 7-3
PAGE
8-1
CHMYI'ER 8
PARTS LIST
PAGE 8-3
PAGE 94
TRANS - GASKET
NICHROME WIRE (375,40,45
KW)
TWO TUBE SW. H.T. TRANS
52301001
SOLENOID H.T. TRANS
5191300 1
SCREW LUG
53802001
FUSE BLOCK
INSULATOR
PAGE 8-5
PAGE 9-1
CKAPTER 9
SCHEMATIC DRAWINGS
DBSCruanON
CHARGE MONITOR
AEC CONTROL
iPMDRlvER(60ICW)
1 TUBE H.T.
TRANSFORMER (6001 41=375,40,45 WI60%=
60ICW)
SCHEMATICS
r2
SELECCIONAR CNTFUOA DE T I
SEGUN LA E t t I R M A O e L I M X
S f l P C T f P INWT m O I N O
I lddnr-
TO THE 1HPUI UNE
Thls Module mmy upp ply 240 VA ( about 24 VDC, 2 Amp. lor loeb, and 24 VAC, 8 Amp, for collrmtor lamp)
Esta Mddulopunde aumlnlstrar 240 VA ( unos 24 VDC, 2 Amp. para Itenw y 24 VAC, 8 Amp. pare Idrnpara del collmador )
I L
REVW m w e r mw
BACOMA Lmus MooutE
MODULO FRENOS
NOTE l . - B . s u n ~ ~ ~ X - R 4 Y ~ ~
m'em-botherWhgo
The -RE
NOTE2-
ORDER
rimlfaneouPty~~.ndn=
Tam sw&e
s&ecteormt
-Inthaw
-toam
TM-12&115 VAC
fBCdlIk2LOVAC
Pressing UPOSURE ORDER. Ihe Tomo Device execuf6-sthstomographic sweep and mrvbds the w n 6me (start9and
terminates Iha expwue). Selects bw!aq) fime on the Operalw consde (the n e a nghersereftaMeIme) in Mder Po termimle
exposure time mrrealyin the evenl Ihe Tomo Device fails.
T O M 0 IWTERFACE
0 EGhAClA F. G+RCU -5 ACOMA INTERFAZ TOM0
REV D E - P ~ ~ ~SSUELIBV MT
X-RAY ROOM
POWER TB5 ( SAIA RAY-X )
MODULE
5
+24 VDC
w
OPEFLATOR
CONSOlE
32
1m73i?
-j+-r -
w
Raw
UGM
m
ll-v- j
a -ROOMLIGHT (WW
Avlso
+. -- ._ RAY- ]
,* - - .
.. " - ,
-- ,--
-
--
-- e ME SnEErJDF
IF408
1 -. DaAlvrNG F . m Wlm
llf
7
RMSED F.CJSIO*. WlOM -
ROOM WARNING L I G m INTERFACE
@ACOMA INTERFU LAMPARA R A Y O S X S A m
P N OESCRT~-' ,suCoav DAS --
-
208 240 VAC
-0 Hz
POWER J1
MODUte Jl
+24VDC ::
10 a,.
1
J3
4 12 --PREP 4 START
-PREP r--
Z
HTeONtROL JS
HS
,9 -4 - HS SIX 5 ..
4 -5 - m R W 1 - !
-.. +
X-RAY
I m
..I1 GND 2
I
---
-
DR*IMHG F . U M Ww ,,,
. YF-009 -
F . m DYI- l v 1 1 I I +RE
1 1 . -- C
I @IAcoMA I ..
HMs &nD ) INTERF~CE
~ # (sRAD ) INTERFAZ
-
-
Tube 2 seleded
D Preparahnorder
SPOT FILMER
PREP OAOER
J2
OPERATOR
CONSOLE 4 - SF PREP
17 -flM P
.5 GND
I,' --
I
----- NAVE ME -
I-
- - I F 4 10
Z w u w - F.--, w1-
111
nmsm F m Wfm
J I . I C C I I Z ~q u n.rF
@A C ~ M A HMS ( R L F J ~ ~ E R F A Z
V . vvvv
*.
0
*.
k dt-l * -"
*
..
P r .C.
I
2; !.gh::
2 * CJ ,(
U
4 tl
CI
- 4-
1
w
1 1 11 1
.- .* C. c r r +.
1
.a
1 1 1 1 1
p t Z Z % 2 % %
1 t 1 1
2
* r I I
~
I I
.,
I
8
I
u ; ~ ~ ~
v . V V
V V
n
-
v
VVVV
I7
-.
0 k r+..v
h.
***
P *a
r !.EN;?
L.
0 ; ,=-a
4 I\
u,
#-
-
.
I
0
L.1
h
p
---
. . . . .
, . . . . .
I
I
!
'1
@ : = B=
-.z-
-. g ,1:;
!:
P .
3; +.9 Q
n
e
n
z
1;' m
- --, T U
m
4
-*
Pn B l e . -#
-&
D 6.;0
: ,- -----.
3 ' .*--m
b .**. -y -0
- 5 li
Y
12
Y
. .
.-.*
= P P ~ A R Y
*t
~ O ~ n p
1 1 1
n
1 t
a m--+
1 1 1
*r
1 ' 1 1 1 1 1 1 1
n a m kesp
.-...-1..
n -..--m m
-v -m
$ . . .- -. - . -- - - -
2 :: :q n
, . - - ,- .. ..,
0, ...... 0 4.
.-.-. 1 1
;
-' "'--6-
n t----*a- u> ? f ,:
;< ...---...,,
\
--.*!.- .P
0
p .-...U)
.-.- * -
**..
5 :....-...,
p .-.. ....
-.-.*
*
.
1
0
1 rn I
0 I
n I
m r >
7,
... ,
-
A
I
n
m I 0 I n 1 m I 3. -
0
5
rn
z
d 4
hS
2
5
n P
m
4
UI
0)
3 w
:: :?I.
-J
2 -...4.J
. --.Vcg
u ......-Kj-
E4 .-. ----0.
.*.-!.-- " -
N
a ---:!:I.
4 L?.,
, 0 --*.*.!---
p ..-.---
L
Ill #
r ---"""
4 .-... .-*a.
p
I 1
m P 1
0 I
m I P
-
- iifi!iili
e *
L1
S ;
z
(3
3
6+
VI
2 ; + -
ll!:i!i!i Y
!9 sa-$ O q
d
ap
P
Id
5
==
E r
;g-
*----------X--'-----'---"-'--"---"'----'------*- - - ."
4
z
0
L;
0
I
1
i % i; l :I
I I
I
g i % 2; ; ;
t
H
Em
"-&E
I
I I I
:r
r
4
I
I
I
I 8: d!nri :1
I I 6 -PI
5 8: $611E: -+----.------
h
-
m
C
zz
elin Bin
%' EnsI s
m
.*
<: ,. .V.L'
2 C. .i ,
- .
ROC
- - .. .... .+
/
73m-t tdMW
-
I*-stm)-
9nrdO3S3,u +
rr-r .kc
il IIU
I-IU
-
.
LAY
cz7
GY.
sls
214 3 9 'r*
Ir
Y
bJ
TJ
La
IJ
.u
.. b*
'
J*
.
c*
T*
.r
b*
5:I*
s*
bC
II:
Le
fL
J*
k
LL
-2l
~r I*.
.I
rt
I L
Lt
9r
J1
bt
tr
zt
tr
ot
I1
Jl
LI
*I
!:
JI
,I
1 i;
I
4
J
+
L:
I
L
5,
CJ
t-r
. CJ
5*
13
!*
Y
..A
b*
EF
m
I '*I l
,6"
:z
IL
JE
H
CC
z*
I t
or
bt
/I
' ::
LC
*z
tt
'Tr
IT
111
CI
JI
&I
91
J I
It
rI
It
lf
PI
b
#
L
'1
I
E
2
I
aqrvl nd3 aawv 4 1
o a a -1-U - 11s 000-top* -tSS
---
I-,"
I . OIGITAL FLUWO BOX SnDLIH MOUNTED Dtd 1.1..
M2 JUMER CLDSEO F W I~IGITAL FLUOREL.
IIC..
-nw
1-m
ICT AALCOw
m.
-
m n l m w c-am €.(.I. wn vmr.
TITLL.
=mu -
ACOMA MEDICAL IMAGING XNC. A
-
JS PDCl APR CDNSOLE.
6 , I F STAWARD FCWRO. *DO A HlHTrR f R W -YO- F U T L W I A I D I G I T U FL/PO-IS TABLE 1 N f LWhCl?
3. P R 7 3 8 . P R T I O . PAT42 AND PRT43 LOCATED I N PRT42-27 TD PRTd2-45. wTIDIRYTIICI1IIIUr
TABLE E4sE. mnm-u I S3020-OFL-90,' 15
4. - SIGH IU FRONT OF SIGNAL I N O I C A T E S
.EDu mrn SIZP RLVISIDEI: 0 SHEET 1 DF 3
In=. II -m.
SIGNAL IS Law ACTIVE.
1 DRWH: MH W6: MN OAT€: 05- 04-94
6 I 7 I 6 1 5 1 4 ! 3 1 2
I 1
4. D l C I T h L FLUDW W I X SHDWN WUHTED OH 1.1..
w2 W E R mOSEO FUR D f G I f k L FLUORO.
2. J 3 F Q I STAIUCIARO CO*OCE.
J9 r W APR CONSOLE.
3 . PRTm. PRT4R PRf42 AHO PRT43 LPCATEO I N
5. ALL SHIELD HIES MVST EM h7 PILT~~-6.
A DRAIW HIRE MUST BE W N E C T E L I FAOH PRT
42-1 7 D THE CEHEPAYOR POWER HDWLE
CHhS919 WOUND.
6 . I F STAMIARD FLWlRO, A110 A JUMPER FROM
WT4Z-21 10 PRT4Z-45.
nus-ronrm
I-nm
Ip
41nw
mm u v w r r
m.
I --
ACOMA HEOICAL I M A G I N G INC. A
TAW€ M S E .
4. - S I W I W F A O M DF S I W A L S W f C A T E S
516tUL IS
LOW A C T I V E .
8
1 7 I 6 I 5 I
I D I C l T h L FLUDRO BOX SHOWN HOUNTEO OH 1.1.. . 5 . ALL SHIELD MIRES HVST EN0 A T PRTAP-6.
W 2 m C R CLOSED FOR D I G I T A L FLUDRD. A M U I N WIFE W S T BE COHNECTW P W ' P R T
43-6 TO T K GENERATOR POWER M W K E
2. COA SlANOARD CONSOLE. CHASSIS FIROUND.
45 FW aPR CGUSDLE.
' n. I F SlANDAUD FLUDRD. ADD A Awa
3 . PUT38. P ~ T ~ OPRT42
. AN0 PRTd3 LOCATED I N PRTU-27 T O P R T 4 Z - 4 5 .
4.
TABLE
-
BASE.
SIGH I N FAMjT OF SIGNAL INOICA'TES
SIGNAL IS COW ACTIVE.
I
- " - -
WE: HN DATE: 05-04- 94
FLUORO BOX REAR
CONNECTORS FLUORO CPU PCB (3016-01)
STANDARD FUAO-
azul 1
1
oan2-3-92
P~&~TAP
L U 6 E FLUOR0
I
w x
cum 1-2-92
r - - y * . , N - d
0 0 0 Q 0 0 Q L )
8 9
u
1
I<
w
:: ." .
.;
3
-
1.:-.i . .
1-
0
t
.i4.P *.x I",
LA
1;
."
-
rd
n
nnn A n
-- -- --
O r :
-- lVl3VH ( 1I
-
.- --- ~ I U 8 ? V ~ 0.)
l%
-.
<- --
wunavrd* f L )
,--.
1 S'
( l j -
~ I ( J J ~ ! ~ ~ / . I
- .- - -- I 1 l l ~ J V b l . t( 1 )
nl>7vlIk ( K t
dnrVI.1 (0 f!
f Lu-0~
(orzuJ - vtr~
-
1
CONTENTS
I
'ITL' MAREF COUNT VALUE
JUDGEMENT C I R C U I
"..-No......-
CONTENTS
-
ACOMA X-RAY INDUSTRY
1
-
CO-. L7"