This document contains lecture notes on power system analysis II. It covers the following topics: 1. Symmetrical components and how to resolve unbalanced three-phase systems into balanced positive-sequence, negative-sequence, and zero-sequence components. 2. Sequence impedances and how balanced impedances will produce voltage drops for each sequence when their corresponding sequence currents are flowing. 3. Examples of applying symmetrical components analysis to unloaded generators and transmission lines to analyze unsymmetrical faults. 4. Additional sections cover unsymmetrical faults on power systems, load flow analysis, and power flow in short transmission lines using the Newton-Raphson method.

Uploaded by

Abcd
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views

Zero Sequence of Transformerspdf

This document contains lecture notes on power system analysis II. It covers the following topics: 1. Symmetrical components and how to resolve unbalanced three-phase systems into balanced positive-sequence, negative-sequence, and zero-sequence components. 2. Sequence impedances and how balanced impedances will produce voltage drops for each sequence when their corresponding sequence currents are flowing. 3. Examples of applying symmetrical components analysis to unloaded generators and transmission lines to analyze unsymmetrical faults. 4. Additional sections cover unsymmetrical faults on power systems, load flow analysis, and power flow in short transmission lines using the Newton-Raphson method.

Uploaded by

Abcd
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45

EE 472 POWER SYSTEM ANAYSIS II

LECTURE NOTES
PROF.DR. M. “EZAİ DİNÇER

Near East University Department of Electrical and Electronics Engineerig


Page

EE472 Power System Analysis II


CONTENTS
1. SYMMETRICAL COMPONENTS............................................................................................................. 2

2. SEQUENCE IMPEDANCES AND SEQUENCE NETWORKS ...................................................................... 7

2.1. Sequence Networks of an Unloaded Generator ........................................................................... 8

2.2. Zero-Sequence Networks of Transformers ................................................................................. 10

2.3. Single line-to-ground Fault on an Unloaded Generator ............................................................. 14

2.4. Double line-to-ground Fault on an Unloaded Generator ........................................................... 23

3. UNSYMMETRICAL FAULTS ON POWER SYSTEMS .............................................................................. 26

4. LOAD FLOW ANAYSIS......................................................................................................................... 32

5. POWER FLOW IN A SHORT TRANSMISSION LINE .............................................................................. 36

5.1. Load Flow with The Newton-Raphson Method .......................................................................... 40

1
Page

EE472 Power System Analysis II


1. SYMMETRICAL COMPONENTS

Three unbalanced phasors of a three-phase system can be resolved into three balanced systems of
phasors. The balanced sets of components are:

1. Positive-sequence components consisting of three phasors equal in magnitude, displaced


from each other by 120 degrees in phase, and having the same phase sequence as the
original phasors.
2. Negative-sequence components consisting of three phasors equal in magnitude, displaced
from each other by 120 degrees in phase, and having the phase sequence opposite to that
of the original phasors.
3. Zero-sequence components consisting of three phasors equal in magnitude and with zero
phase displacement from each other.

Fig. 1.1. Three sets of balanced phasors which are the symmetrical components of three unbalanced
phasors.

The three sets of symmetrical components are designated by the additional subscript 1 for the
positive-sequence components, 2 for the negative-sequence components, and 0 for the zero-
sequence components. The positive-sequence components of , , and are , , and .

Similarly, the negative-sequence components are , , and , and the zero-sequence

components are , , and . Phasors representing currents will be designated by with

subscripts as for voltages.

Since each of the original unbalanced phasors is the sum of its components, the original phasors
expressed in terms of their components are:
2
Page

(1.1)

EE472 Power System Analysis II


(1.2)

(1.3)

The phase displacement of the symmetrical components of the voltages and currents in a three-
phase system by , it is convenient to have a shorthand method of indicating the rotation of a
phasor through . The result of the multiplication of two complex numbers is the product of their
magnitudes and the sum of their angles.

The letter a is commonly used to designate the operator which causes a rotation of in the
counterclockwise direction. Such an operator is a complex number of unit magnitude with an angle
of and is defined by the following expressions:

If the operator a is applied to a phasor twice in succession, is rotated through . Three successive
a applications of a rotate the phasor through . Thus, the phasor

and

Fig. 1.2. Phasor diagram of the various powers of the operator a.

We note that the number of unknown quantities can be reduced by expressing each component of
Va and Vb as the product of some function of the operator a and a component of Va. Reference to
Fig. 1.1 verifies the following relations:

(1.4)
3
Page

EE472 Power System Analysis II


Upon substitution of Eqs. (4) in Eqs. (1) to (3), we obtain

(1.5)

(1.6)

(1.7)

Adding Eqs. (1.5), (1.6), and (1.7) gives

(1.8)

and, since ,

(1.9)

Equation (1.9) enables us to find the zero-sequence components of three unsymmetrical phasors.
We see that no zero-sequence components exist if the sum of the phasors is zero. Since the sum of
the line-to-line voltage phasors in a three-phase system is always zero, zero-sequence components
are never present in the line voltages, regardless of the amount of unbalance. The sum of the three
line-to-neutral voltage phasors is not necessarily zero, and voltages to neutral may contain zero-
sequence components.

The equations could have been written for any set of related phasors, and we might have written
them for currents instead of for voltages. They may be solved either analytically or graphically.
Because some of the preceding equations are so fundamental, they are summarized below for
currents.

(1.10)

(1.11)
4
Page

(1.12)

EE472 Power System Analysis II


(1.13)

(1.14)

(1.15)

In a three-phase system the sum of the line currents is equal to the current in the return path

through the neutral. Thus,

(1.16)

Comparing Eqs. (1.15) and (1.16) gives

(1.17)

In the absence of a path through the neutral of a three-phase system, is zero, and the line currents

contain no zero-sequence components.

Example:

Find the symmetrical components of the current.

Answer:
5
Page

EE472 Power System Analysis II


6
Page

EE472 Power System Analysis II


2. SEQUENCE IMPEDANCES AND SEQUENCE NETWORKS

The symmetrical components of unbalanced currents flowing in balanced impedances will produce
voltage drops like sequence only.

The impedance of a circuit when positive-sequence currents alone are flowing is called the
impedance to positive-sequence current. Similarly, when only negative-sequence currents are
present, the impedance is called the impedance to negative-sequence current. When only zero-
sequence currents are present, the impedance is called the impedance to zero-sequence current.
These names of the impedances of a circuit to currents of the different sequences are usually
shortened to the less descriptive terms, positive-sequence impedance, negative-sequence
impedance, and zero-sequence impedance.

The analysis of an unsymmetrical fault on a symmetrical system consists of finding the symmetrical
components of the unbalanced currents which are flowing. Since the component currents of one
phase sequence cause voltage drops of like sequence only and are independent of currents of other
sequences, in a balanced system, currents of any one sequence may be considered to flow in an
independent network composed of the impedances to the current of that sequence only. The single-
phase equivalent circuit composed of the impedances to current of anyone sequence only is called
the sequence network for that particular sequence. The sequence network includes any generated
emfs of like sequence. Sequence networks carrying the currents , , and are interconnected

to represent various unbalanced fault conditions. Therefore, to calculate the effect of a fault by the
method of symmetrical components, it is essential to determine the sequence impedances and to
combine them to form the sequence networks.

The positive-sequence and negative-sequence impedances of linear, symmetrical, static circuits are
identical, because the impedance of such circuits is independent of phase order provided the applied
voltages are balanced. The impedance of such circuits to zero-sequence currents may differ from the
impedance to positive- and negative-sequence currents. The impedances of rotating machines to
currents of the three sequences will generally be different for each sequence.

In deriving the equations for inductance and capacitance of transposed transmission lines, we
assumed balanced three-phase currents and did not specify phase order. Therefore, the resulting
equations are valid for both positive- and negative-sequence impedances. The inductance and
capacitance of transmission lines for zero-sequence currents will be discussed later.
7
Page

EE472 Power System Analysis II


For symmetrical three-phase static loads consisting of lumped constants or loads which can be
analyzed as having lumped constants, the impedances to current of positive, negative, and zero
sequences are the same because each phase is isolated from, and independent of, the other phases.

2.1. Sequence Networks of an Unloaded Generator

FIG. 2.1 Circuit diagram of an unloaded generator grounded through a reactance. The emfs of each
phase are , , and .

In this section our task is simple because one generator and perhaps an impedance in the neutral
comprise the entire circuit. The generated voltages are of positive sequence only, since the generator
is designed to supply balanced three-phase voltages. Therefore the positive-sequence network is
composed of an emf in series with the positive-sequence impedance of the generator. The negative-
and zero-sequence networks contain no emfs but include the impedances of the generator to
negative- and zero-sequence currents, respectively. The sequence components of current are shown
in Fig. 2.2. rrhey are flowing through impedances of their own sequence only, as indicated by the
appropriate subscripts on the impedances shown in the figure. The sequence networks shown in Fig.
2.2 are the single-phase equivalent circuits of the balanced three-phase circuits through which the
symmetrical components of the unbalanced currents are considered to flow. The generated emf in
the positive-sequence network is the no-load terminal voltage to neutral, which is also equal to the
voltages behind transient and subtransient reactances and to the voltage behind synchronous
8

reactance since the generator is not loaded. The reactance in the positive-sequence network is the
Page

EE472 Power System Analysis II


sub-transient, transient, or synchronous reactance, depending on whether subtransient, transient, or
steady-state conditions are being studied.

Fig. 2.2 Paths for current of each sequence in a generator, and the corresponding sequence
networks.

The reference bus for the positive- and negative-sequence networks is the neutral of the generator.
So far as positive- and negative-sequence components are concerned the neutral of the generator is
at ground potential since only zero-sequence current flows in the impedance between neutral and
ground. The reference bus for the zero-sequence network is the ground at the generator.
9
Page

EE472 Power System Analysis II


The current flowing in the impedance between neutral and ground is . By referring to Fig.

2.2e, we see that the voltage drop of zero sequence from point a to ground is ,

where is the zero-sequence impedance per phase of the generator. The zero-sequence network,

which is a single-phase circuit assumed to carry only the zero-sequence current of one phase, must,
therefore, have an impedance of , as shown in Fig. 2.2f. The total zero-sequence

impedance through which flows is

(2.1)

Usually the components of current and voltage for phase a are found from equations determined by
the sequence networks. The equations for the components of voltage drop from point a of phase a to
the reference bus (or ground) are, as may be deduced from Fig. 2.2,

(2.2)

(2.3)

(2.4)

Where is the positive-sequence no-load voltage to neutral, and are the positive- and

negative-sequence impedances of the generator, and is defined by Eq. (2.1). The above equations,

which apply to any generator carrying unbalanced currents, are the starting points for the derivation
of equations for the components of current for different types of faults. They apply to the case of a
loaded generator if is given the value computed for the voltage behind subtransient, transient, or

synchronous reactance for the load existing before the fault.

2.2. Zero-Sequence Networks of Transformers

The zero-sequence equivalent circuits of three-phase transformers deserve special attention. The
various possible combinations of the primary and secondary windings in and Δ alter the zero-
sequence network. Transformer theory enables us to construct the equivalent circuit for the zero-
sequence net,vork. We remember that no current flows in the primary of a transformer unless
current flows in the secondary, if we neglect the relatively small magnetizing current. We know, also,
that the primary current is determined by the secondary current and the turns ratio of the windings,
again with magnetizing current neglected. These principles guide us in the analysis of individual
10

cases. Five possible connections of two-winding transformers will be discussed. These connections
Page

are shown in Fig. 2.3. The arrows on the connection diagrams show the possible paths for the flow of

EE472 Power System Analysis II


zero-sequence current. Absence of an arrow indicates that the transformer connection is such that
zero-sequence current cannot flow. The zero-sequence approximately equivalent circuit, with
resistance and a path for magnetizing current omitted, is shown in Fig. 2.3 for each connection. The
letters P and Q identify corresponding points on the connection diagram and equivalent circuit. The
reasoning to justify the equivalent circuit for each connection follows.

FIG. 2.3. Zero-sequence equivalent circuits of three-phase transformer banks, together with diagrams
of connections and the symbols for one-line diagrams.
11
Page

EE472 Power System Analysis II


Example:

TR1 TR2
G M

Y Δ-Y Y-Δ Y

Solve the (+), (-) and (0) sequence networks of the above power system.

(+)

G M

TR1 Line TR2

(-)

TR1 Line TR2


12
Page

EE472 Power System Analysis II


(0)

TR1 Line TR2

Example:

TR1 TR2
G M

Y Y-Y Y
Y-Y

Zero sequence network,

(0)

TR1 Line TR2


13
Page

EE472 Power System Analysis II


2.3. Single line-to-ground Fault on an Unloaded Generator

The circuit diagram for a single line-to-ground fault on an unloaded -connected generator with its
neutral grounded through a reactance is shown in Fig. 2.4 where phase is the one on which the
fault occurs. The relations to be developed for this type of fault will apply only when the fault is on
phase , but this should cause no difficulty since the phases are labeled arbitrarily and any phase
may be designated as phase . The conditions at the fault are expressed by the following equations:

FIG. 2.4. Circuit diagram for a single line-to-ground fault on phase a at the terminals of an unloaded
generator whose neutral is grounded through a reactance.

When and are substituted in Eqs. (1.13) to (1.15), we obtain

and
14
Page

Therefore,
EE472 Power System Analysis II
(2.5)

By Eq. (1.5), since ,

and

Then, by Eq. (2.2),

and from Eqs. (2.3) and (2.4)

but, since ,

and, solving for , we obtain

(2.6)

Equations (2.5) and (2.6) are the special equations for a single line-to-ground fault. They are used
with Eqs. (2.2) to (2.4), together with the symmetrical-component relations to determine all the
voltages and currents at the fault. If the three sequence networks of Fig. 2.2 are connected in series
as shown in Fig. 2.5, we see that the currents and voltages resulting therefrom satisfy the equations
above, for the three sequence impedances are then in series with the voltage . With the sequence

networks so connected, the voltage across each sequence network is the symmetrical component of
of that sequence. The connection of the sequence networks as shown in Fig. 2.5 is a convenient

means of remembering the equations for the solution of the single line-to-ground fault, for all the
necessary equations can be determined from the sequence network connection.
15
Page

EE472 Power System Analysis II


FIG. 2.5 Connection of the sequence networks of an unloaded generator for a single line-to-ground
fault on phase at the terminals of the generator

If the neutral of the generator is not grounded, the zero-sequence network is open-circuited, and

is infinite. Since Eq. 2.6 shows that is zero when is infinite, and must be zero. Thus no

current flows in line since is the sum of its components, all of which are zero. The same result

can be seen without the use of symmetrical components since inspection of the circuit shows that no
path exists for the flow of current in the fault unless there is a ground at the generator neutral.

Example: A -kva, kv generator has a direct-axis sub transient reactance of per unit.
The negative- and zero-sequence reactances are, respectively, and per unit. The neutral of
the generator is solidly grounded. Determine the subtransient current in the generator and the line-
16

to-line voltages for subtransient conditions when a single line-to-ground fault occurs at the generator
Page

terminals with the generator operating unloaded at rated voltage. Neglect resistance.

EE472 Power System Analysis II


Solution

On a base of kva, kv, per unit, since the internal voltage is equal to the

terminal voltage at no load.

Then, in per unit,

Subtransient current in line is,

The symmetrical components of the voltage from point to ground are:

Line-to-ground voltages are:

17

Line-to-line voltages are:


Page

EE472 Power System Analysis II


Since the generated voltage-to-neutral was taken as per unit, the above line-to-line voltages

are expressed in per unit of the base voltage-to-neutral. When expressed in volts the postfault line
voltages are:

If ,

(due to the reactance of )


18
Page

EE472 Power System Analysis II


Tutorial 1.

TR1 TR2
G M

Y Y
Δ-Y Y-Δ

: , , ,

: , , ,

: , ,

: , ,

: ,

Select system common base values as 100 MVA and 11 kV at the generator side and marking each
respective value in p.u. draw
Positive sequence network, negative sequence network and zero sequence network of the given
power system.

Answer:

:
19
Page

: ,

EE472 Power System Analysis II


- Positive Sequence Network,

(+)

G M

j0.8 p.u. j1.0 p.u.

j0.33 p.u. j0.92 p.u. j0.4 p.u.

TR1 Line TR2

- Negative Sequence Network,

(-)

j0.8 p.u. j1.2 p.u.

j0.33 p.u. j0.92 p.u. j0.4 p.u.

TR1 Line TR2

20
Page

EE472 Power System Analysis II


- Zero sequence network,

(0)

j0.24 p.u. j0. 25 p.u.

j0.33 p.u. j2.3 p.u. j0.4 p.u.

TR1 Line TR2


:

Tutorial 2.Single line to ground fault at terminal a. Find the fault current value at point a?

A B

and transformers: , , ,

Answer:
21
Page

EE472 Power System Analysis II


Positive Sequence Network Negative Sequence Network Zero Sequence Network

G M j1.5 p.u.

j0.2 p.u. j0.2 p.u. j0.2 p.u. j0.2 p.u. j0.05p.u j0.05p.u

+
22
Page

EE472 Power System Analysis II


2.4. Double line-to-ground Fault on an Unloaded Generator

The circuit diagram for a double line-to-ground fault on an unloaded, -connected generator having
a grounded neutral is shown in Fig. 2.7. The faulted phases are and . The conditions at the fault
are expressed by the following equations:

Substituting and in Eqs. (1.9), , and

gives
23
Page

EE472 Power System Analysis II


FIG. 2.7 Circuit for a double line-to-ground fault on phases and at the terminals of an unloaded
generator whose neutral is grounded through a reactance.

Therefore,

(2.7)

Solving Eqs. (2.3) and (2.4) for and and substituting for and , we obtain

Replacing by gives

and
24

Since ,
Page

EE472 Power System Analysis II


and

(2.8)

Equations (2.7) and (2.8) are the special equations for a double line-to-ground fault. They are used
with Eqs. (2.2) to (2.4) and the symmetrical component relations to determine all the voltages and
currents at the fault. Equation (2.7) indicates that the sequence networks should be connected in
parallel, as shown in Fig. 2.8, since the positive-, negative-, and zero-sequence voltages are equal at
the fault. Examination of Fig. 2.8 shows that all the conditions derived above for the double line-to-
ground fault are satisfied by this connection.

FIG. 2.8 Connection of the sequence networks of an unloaded genera tor for a double line-to-ground
fault on phases and at the terminals of the generator

The diagram of network connections shows that the positive-sequence current is determined by

the voltage impressed on in series with the parallel combination of and . The same

relation is given by Eq. (2.8).

In the absence of a ground connection at the generator no current can flow into the ground at the
fault. In this case would be infinite and would be zero. In so far as current is concerned the

result would be the same as in a line-to-line fault. Equation (2.8) for a double line-to-ground fault
approaches for a line-to-line fault as approaches infinity, as may be seen by
25

dividing the numerator and denominator of the second term in the denominator of Eq. (2.8) by
Page

and letting be infinitely large.

EE472 Power System Analysis II


26
Page

EE472 Power System Analysis II


3. UNSYMMETRICAL FAULTS ON POWER SYSTEMS

In the derivation of equations for the symmetrical components of currents and voltages in a general
network during a fault, we will designate as , , and the currents flowing out of the original

balanced system at the fault from phases , , and , respectively. We can visualize the currents ,

, and by referring to Fig. 3.1, which shows the three lines of the three-phase system at the part

of the network where the fault occurs. The flow of current from each line into the fault is indicated
by arrows shown on the diagram beside hypothetical stubs connected to each line at the fault
location. Appropriate connections of the stubs represent various types of faults. For instance,
connecting stubs and produces a line-to-line fault through zero impedance. The current in stub
is then zero, and is equal to .

FIG. 3.1 Three conductors of a three-phase system. The stubs carrying currents , , and may be

interconnected to represent different types of faults

The line-to-ground voltages at the fault will be designated , , and . Before the fault occurs, the

line-to-neutral voltage of phase at the fault will be called , which is a positive-sequence voltage

since the system is assumed to be balanced. We met the prefault voltage previously in

Symmetrical Three-Phase Faults on Synchronous Machines in calculations to determine the


currents in a power system when a symmetrical three-phase fault occurred.

A single-line diagram of a power system containing three synchronous machines is shown in Fig. 3.2.
Such a system is sufficiently general that equations derived therefrom are applicable to any balanced
system regardless of the complexity. Figure 3.2 also shows the sequence networks of the system. The
point where a fault is assumed to occur is marked on the single-line diagram and on the sequence
27

networks. As we saw in Symmetrical Three-Phase Faults on Synchronous Machines , the load


Page

current flowing in the positive-sequence network is the same, and the voltages to ground external to
the machines are the same, regardless of whether the machines are represented by their voltages
EE472 Power System Analysis II
behind subtransient reactance and their subtransient reactances, or by their voltages behind
transient reactance and their transient reactances, or by their voltages behind synchronous
reactance and their synchronous reactances.

FIG. 3.2 One-line diagram of a three-phase system, the three sequence networks of the system, and
the Helmholtz-Thevenin equivalent of each network for a fault at

Since linearity is assumed in drawing the sequence networks, each of the networks can be replaced
by its Helmholtz-Thevenin equivalent between the two terminals composed of its reference bus and
the point of application of the fault. The Helmholtz-Thevenin equivalent circuit of each sequence
28

network is shown adjacent to the diagram of the corresponding network in Fig. 3.2. The internal
Page

voltage of the single generator of the equivalent circuit for the positive-sequence network is , the

EE472 Power System Analysis II


prefault voltage to neutral at the point of application of the fault. The impedance of the
equivalent circuit is the impedance measured between point and the reference bus of the positive-
sequence network with all the internal emfs short-circuited. The value of is dependent on
whether subtransient, transient, or synchronous reactance is used in the sequence network, which is,
in turn, dependent on whether subtransient, transient, or steady-state currents are being computed.

Since no negative- or zero-sequence currents are flowing before the fault occurs, the prefault voltage
between point and the reference bus is zero in the negative- and zero-sequence networks.
Therefore, no emfs appear in the equivalent circuits of the negative- and zero-sequence networks.
The impedances and are measured between point and the reference bus in their respective

networks and depend on the location of the fault.

Since is the current flowing from the system into the fault, its components , and flow

out of their respective sequence networks and the equivalent circuits of the networks at , as shown
in Fig. 3.2. Examination of the equivalent circuits of the sequence networks shows that the voltages
, , and at point are expressed by the following equations:

(3.1)

(3.2)

(3.3)

The only differences between Eqs. (3.1) to (3.3) and Eqs. (2.2) to (2.4) are the substitution of for

and the interpretation of , , and . For a fault at the terminals of an isolated generator at no

load, and are equal, and Eqs. (3.1) to (3.3) reduce to Eqs. (2.2) to (2.4).

Solution Algorithm for Unbalanced Faults:

Step 1. Draw the positive-, negative- and zero-sequence networks of the overall system.

Step 2. Calculate and replace the sequence networks by Thevenin equivalence as seen from the fault
points.

Step 3. For the given fault type find out the relationships amoung (+), (-) and (0) sequence are
voltages and currents.
29

Step 4. Interconnect sequence network such that the relations in step 3 are satisfied.
Page

EE472 Power System Analysis II


Step 5. So that resulting network for the designed variables.

Example:

TR1 Line 1 TR2


A B
F

Y Line 2
Y-Y Y
Y-Y

Unit and generate voltage,

: , ,

: , ,

: :

All data given in with respect to select all common bases of the power system. :

Voltage before the fault.

Double lin-to-ground fault occurs at , find the

(+)

A B

j0.3 p.u. j0.25 p.u.


j0.3 p.u.

j0.12 p.u. F Line 1 j0.1 p.u.

TR1 j0.3 p.u. TR2

Line 2
30
Page

EE472 Power System Analysis II


(-)

j0.2 p.u. j0.15 p.u.


j0.3 p.u.

j0.12 p.u. F Line 1 j0.1 p.u.

TR1 j0.3 p.u. TR2

Line 2

(0)

j0.05 p.u. j0.05 p.u.


j0.7 p.u.

j0.12 p.u. F Line 1 j0.1 p.u.

TR1 j0.7 p.u. TR2

Line 2

31
Page

EE472 Power System Analysis II


(+) sequence (-) sequence zero sequence

. .

Let’s sol e the same problem ith the same fault point location for a single line to ground fault.

+
32
Page

EE472 Power System Analysis II


If fault through an impedance,

33
Page

EE472 Power System Analysis II


4. LOAD FLOW ANAYSIS

A load flow study is the determination of voltage, current and p.f. at the given nodes of the power
system network under normal operating conditions. Load flow studies are essential in planning and
future development of the system.

: Active power

: Reactive power

: Voltage magnitude

: Active power

Imaginary
Axis

Real Axis

Hence we have to consider the conjugate vector.


34
Page

EE472 Power System Analysis II


Positive Network

1 2 3 4

Generator Load Connection

Assume for a 4 bus system,

: Bus Admittance Matrix

a
1

4
b
3

2
35
Page

EE472 Power System Analysis II


j0.2 p.u.
a j1.15 p.u. j0.1 p.u. 1

j0.25 p.u.
b j1.15 p.u. j0.1 p.u. j0.125 p.u. 4
3
j0.4 p.u.
c j1.15 p.u. j0.1 p.u.
j0.2 p.u.
2

Corresponding reactance diagram all data given in p.u. With current sources replacing the equivalent
voltage sources (values shown are admittance in p.u.).

4
3

36
Page

EE472 Power System Analysis II


Properties of the Bus Admittance Matrix

- It is a source matrix of order


- It is symmetrical
- It is complex

Each off diagonal element is the negative of the branch admittance between busses and .

Each diagonal element is the sum of admittances the branches terminating on the bus , including
the branches to ground

37
Page

EE472 Power System Analysis II


5. POWER FLOW IN A SHORT TRANSMISSION LINE

At the secondary end, on per phase basis

Hence,

Now suppose that,

38
Page

EE472 Power System Analysis II


(Power Angle
Curve)

For a 4 bus system

Gauss-Seidell Method

Bus system for bus 2,

39
Page

EE472 Power System Analysis II


Example:

5
2
We use that

3 4

BUS Remarks
1 Swing (Slack) Bus

2 Load Bus
Initial
Voltage Magnitude
3
Initial Constant

4 Load Bus
Initial

5 Load Bus
initial

G B
LINE

1-2
1-4
1-5
2-3
40

2-4
3-5
Page

EE472 Power System Analysis II


Find using Gauss-Seidell?

Answer:

(no connection between bus)

(conjugate of )

41
Page

EE472 Power System Analysis II


5.1. Load Flow with The Newton-Raphson Method

For bus system at bus ,

Let,

Then,

Reminder

Consider two functions of two variables and such that,

where and are constants.

Let and be the initial estimates,


42

Let and be the values by which,


Page

EE472 Power System Analysis II


We initial estimates differ from the correct solutions,

Expanding the left hand side in a Taylor series,

Matrix Form,

The solution of gives and ,

Then a better estimate at the solution,

The iterations are continued until and become smaller than a predetermined value.

Finishing Reminder

Corresponding to the Matrix Equation for a three bus system (with bus as the slack (swing) bus)
43
Page

EE472 Power System Analysis II


44
Page

EE472 Power System Analysis II