Megger Multi-Tap Automatic Current Transformer Test Set: User's Guide
Megger Multi-Tap Automatic Current Transformer Test Set: User's Guide
User’s Guide
P/N 80513-Rev. 8
1
Table of Contents
List of Figures..................................................................................................................... 3
Safety Precautions.............................................................................................................. 4
Input Power precautions................................................................................................... 5
Warning and Caution Notices........................................................................................... 5
Introduction........................................................................................................................ 6
Preparation for use............................................................................................................ 8
Basic Theory........................................................................................................................ 9
General............................................................................................................................... 9
Ratio Test............................................................................................................................ 9
Polarity Test...................................................................................................................... 10
Excitation Test.................................................................................................................. 11
Insulation Resistance Test................................................................................................ 13
Winding Resistance Test.................................................................................................. 14
Burden Test....................................................................................................................... 14
Description of Controls and Indicators........................................................................... 16
Operation and Controls................................................................................................... 19
Main menu....................................................................................................................... 19
Nameplate Info................................................................................................................ 20
File Manager..................................................................................................................... 23
System Default................................................................................................................. 26
Manual.............................................................................................................................. 37
Test Configuration........................................................................................................... 39
Saturation Test................................................................................................................. 41
Ratio Test.......................................................................................................................... 43
Insulation Test.................................................................................................................. 45
Winding Resistance Test.................................................................................................. 46
Burden Test....................................................................................................................... 48
Operating Instructions..................................................................................................... 49
Ratio & Polarity Test......................................................................................................... 49
Saturation Test................................................................................................................. 53
How to run multiple saturation tests.............................................................................. 59
Method I........................................................................................................................... 59
METHOD II........................................................................................................................ 61
DC Insulation Resistance Test.......................................................................................... 62
Winding Resistance Test.................................................................................................. 68
Manual Test...................................................................................................................... 71
Burden Test....................................................................................................................... 74
Recalling and Saving of Results....................................................................................... 77
PowerDB Lite.................................................................................................................... 87
Software Installation........................................................................................................ 87
Viewing Test Results......................................................................................................... 89
Sample PowerDB test form with results......................................................................... 91
Specifications.................................................................................................................... 93
CT Demagnetization........................................................................................................ 95
Maintenance & Calibration............................................................................................. 95
Warranty & Repair........................................................................................................... 96
2
List of Figures
3
Safety Precautions
Please read this user’s guide before operating the instrument. Read and understand all safety precautions
and operation instructions before attempting to use this unit. The purpose of this equipment is limited to
use as described in this user’s guide. Do not use the equipment or it’s accessories with any device other
than specifically described. Should a situation arise that is not covered in the general or specific safety
precaution please contact Megger regional representative or Megger, Dallas Texas.
The equipment under test must be de-energized and totally isolated from the electrical system before
test connections are made. The test set and specimen to which it is connected are a possible source of
electric shock hazard. Persons actually engaged in the test must stand clear of all parts of the test circuit
and connections, unless the test set is de-energized. Persons not directly involved with the work must be
kept away from test activities by suitable barriers, barricades or warnings.
Every effort has been made to point out the proper procedures and precautions to be followed by the
user in operating this equipment. It is not possible to foresee every hazard which may occur in the
various applications of this equipment. It is therefore essential that the user, in addition to following the
safety rules, also carefully consider all safety aspects of the test before proceeding.
Note: Make sure all connections are made properly to avoid accidental opening of the current
transformer secondary which can lead to damage of the transformer under test.
4
Input Power precautions
The instrument operates from a single phase power source. It has a three wire power cord and requires a
two pole, three terminal (live, neutral and ground) type connector. The voltage to ground from live pole
of the power source must be within the following operating voltage.
95-265 V 50/60 Hz
Before making connection to the power source, determine that instrument rating matches the voltage of
the power source. The power input plug must be inserted only into a mating receptacle with a ground
contact. Do not bypass the grounding connection. Any interruption of the grounding connection can
create an electric shock hazard. Determine that the receptacle is properly wired before inserting the plug.
WARNING
Warning, as used in this manual, is defined as a condition or practice which could
result in personal injury or loss of life.
CAUTION
Caution, as used in this manual, is defined as a condition or practice which could
result in damage to or destruction of the equipment or apparatus under test.
5
Introduction
Megger MCT1605 test is a lightweight, portable unit for shop and field testing of current transformers
using IEEE C57.13.1 method. The unit performs excitation, ratio and polarity test by providing a variable
output voltage up to 1600 V AC. It will calculate the rated knee point in compliance with IEEE C57.13.1,
IEC 60044-1, and IEC 60044-6. MCT1605 test set provides the flexibility of both automatic as well as
manual testing. It utilizes the latest DSP technology for testing single and multi-ratio CT’s. The test set
can also perform DC insulation resistance test on CT’s to verify the condition of winding to winding and
winding to ground insulation.
All three, excitation, ratio and polarity tests can be performed with same connection settings without
changing any leads. Current Transformers can be tested in their equipment configuration, such as being
mounted in transformers, oil circuit breakers or switchgear. This eliminates the need to remove CT’s from
switchgear. It is necessary for the equipment to be denergized and totally isolated from the electrical
system prior to testing.
MCT1605 performs the tests on CT’s to assure that CT’s are of marked ratio and polarity and would
perform satisfactorily as designed once put in service. Excitation and burden test ensures that CT’s
are of correct accuracy rating and is capable of supplying the known current at stated accuracy. The
results obtained from ratio, polarity and excitation tests can be compared with name plate data and
manufacturer’s curve to verify the accuracy of the CT under test.
The results of the test are displayed on 6.5 inch daylight readable color LCD screen. Ratio and polarity
test results can be read right off the screen without any need for calculations. Multiple saturation curves
with knee points are shown on the same display for comparison and analysis purpose.
MCT1605 can be operated either stand alone or remotely through computer using PowerDB Lite
software. All the test results can either be stored to unit’s internal memory or can be transferred to
computer using a thumb drive, through one of the available USB port on the unit.
6
Megger MCT1605
7
Preparation for use
Receiving Instructions
Contents of MCT1605 kit
Item (Qty.) Cat No.
MCT1605 Current Transformer Saturation, Ratio and Polarity Test Set........... MCT1605
Line cord, North America (1ea.)............................................................................. 620000
Line cord, International color coded wire (1ea.).................................................... 15065
Test Lead, H1 and H2 40ft. (1ea.).......................................................................... 620148
Test Lead, X red, 20ft., (1ea.).............................................................................. 2000-753
Test Lead, X green, 20ft., (1ea)............................................................................ 2000-747
Test Lead, X yellow, 20ft., (1ea).......................................................................... 2000-748
Test Lead, X blue, 20ft., (1ea).............................................................................. 2000-749
Test Lead, X white, 20ft., (1ea)............................................................................ 2000-746
Gnd lead, green with yellow, with large ground clip, 20ft., (1ea)....................... 620151
Large Test clip, red, 40mm opening, (1ea.) ......................................................... 640266
Large Test clip, black, 40mm opening, (1ea.)........................................................ 640267
Alligator clip, red, 4.1 mm, (1ea.)........................................................................... 684006
Alligator clip, black, 4.1 mm, (1ea.)....................................................................... 684007
Alligator clip, white, 4.1 mm, (1ea.).................................................................. 90000-882
Alligator clip, green, 4.1 mm, (1ea.).................................................................. 90000-883
Alligator clip, yellow, 4.1 mm, (1ea.)................................................................ 90000-884
Alligator clip, blue, 4.1 mm, (1ea.).................................................................... 90000-885
Soft side lead case.............................................................................................. 90000-165
USB memory stick................................................................................................... 830029
Instruction book........................................................................................................ 80513
PowerDB Lite..........................................................................................................DB0001
Check the equipment received against the packing list to ensure that all the materials are present. Notify
Megger of any shortages. Telephone 1-800-723-2861 and ask for Dallas Customer Service Department.
Examine the instrument for damage received in transit. If damage is discovered, file a claim with the
carrier at once and notify Megger or it’s nearest authorized sales representative, giving a detailed
description of the damage.
Supply Voltage
Unit operates on a single phase AC power source .The input operating voltage should be between the
following limits: 95-265 V 50-60 Hz 15A max.
Please refer to Input power precautions in safety section for detailed description of input power
requirements.
Operating System
Unit works on VX Work’s operating system.
8
Basic Theory
General
The purpose of this section is to explain the basic theory of the following tests and to guide the operator
for making appropriate measurements with MCT1605. Following tests can be performed by MCT1605.
■■ Ratio test
■■ Polarity Test
■■ Excitation Test
■■ DC Insulation Resistance Test
■■ Winding Resistance Test
■■ Burden Test
Ratio Test
The ratio is defined as the number of turns in the secondary as compared to the number of turns in the
primary.
The purpose of ratio test is to prove the ratio of the CT, is as specified and also to verify the ratio at
different taps of a multi tap CT. The turns ratio is equivalent to the voltage ratio and can be expressed as:
N2/N1=V2/V1
Where,
N2 and N1 are no. of turns of secondary and primary windings respectively
V2 and V1 are the secondary and primary side voltage readings respectively.
A suitable voltage, below saturation is applied to the secondary of the CT under test and primary side
voltage is measured to calculate the turns ratio from above expression.
9
MCT1605 performs the ratio test automatically by either selecting Saturation test or Ratio and polarity test.
User can also select manual Ratio test by selecting manual option and controlling the secondary applied
voltage.
CAUTION
In the manual operation, do NOT apply the voltage high enough to the secondary
of CT that would cause the CT to saturate; otherwise the readings won’t be
accurate.
Polarity Test
The Polarity test proves that the predicted direction of secondary CT current (leaving) is correct for a
given direction of primary current (entering).
Polarity marks designate the relative instantaneous directions of the currents. At the same instant of
time that the primary current is entering the primary terminal the corresponding secondary current is
leaving the similarly marked secondary terminal. A CT under test is supposed to have correct polarity if
instantaneous current direction for primary and secondary current is opposite to each other.
10
Figure 2 Polarity test
Same connection settings as for Ratio test can be used for performing Polarity test. The two non polarity
marks are shorted together internally and potential is measured across the two polarity mark points. For
correct polarity, primary winding voltage will be in-phase with secondary winding voltage, with a phase
angle difference of zero or close to that. A CT with reverse polarity would read the sum of the two
primary and secondary voltages indicating a phase difference of approximately 180 degrees. MCT1605
performs this test in automated fashion and display the result as either Polarity correct or incorrect.
Excitation Test
IEEE defines the saturation as “the point where the tangent is at 45 degrees to the secondary exciting
amperes”. Also known as “knee” point. This test verifies that the CT is of correct accuracy rating, has no
shorted turns in the CT and no short circuits are present in the primary or secondary windings of the CT
under test.
A typical excitation curve for C class current transformer is shown in following figure.
11
Figure 3 Excitation Curve
An Ac voltage is applied to the secondary winding of the CT. The voltage applied to the secondary
winding of the CT is increased slowly automatically by the test set. Voltage and current readings for the
secondary winding of CT are stored in the internal memory. Test set automatically determines the “Knee”
point as per selected standard by observing a small voltage increase causing a large increase in current.
The excitation curve around the points where current jumps up for a small increase of voltage; is very
important for comparison of curves with published curves or similar CT curves.
MCT1605 plots the saturation curve on the LCD display screen. Once a knee point is determined by
the test set, it will also display the corresponding saturation voltage and saturation current on the
display screen. Multiple CT saturation curves can be plotted on the same screen either for multi taps
or for comparison of similar type CT’s. The excitation test results should be compared with published
manufacturer’s data or previous recordings to determine any deviations from previously obtained curves.
The unit automatically demagnetizes the CT after performing the saturation test by slowing ramping
down the secondary voltage all the way back to Zero. It is advisable to demagnetize the CT
before performing any test that requires accurate measurements. Please refer to the section of CT
Demagnetization for details.
12
Insulation Resistance Test
The insulation between the windings and winding to ground should be checked while performing a
comprehensive CT test. The test set has inbuilt 1kV DC insulation tester that is used for measurement of
insulation resistance. The following connection needs to be made before performing an Insulation test
on CT.
Short the primary winding of the CT under test by shorting H1 and H2.
Short the secondary winding of the CT under test by shorting X1 and X2-X5
Note: MCT1605 does the above two steps automatically. User doesn’t have to perform the shorts
externally as unit does that automatically internally.
Remove the neutral ground and isolate the CT from any associated burden. After the shorts, it will be a
three terminal specimen.
Three tests are performed to determine the condition of the insulation of the CT under test.
The DC test voltage is automatically ramped up slowly and the insulation reading in (M) ohms is
displayed on the LCD display screen in digital format. The measured values should be compared with
similar readings obtained previously and a large deviation should call for further investigation. Any
reading in M ohms is considered to be a good insulation. The minimum insulation resistance that is
accepted is 1 M ohms. More than a no., it’s the trending of insulation test results that gives the true
condition of CT insulation.
Insulation readings are greatly affected by the temperature. Should a reading be compared to previously
taken readings, proper correction factors need to be applied, if taken under different temperature
conditions before drawing any conclusion. Insulation resistance readings should remain fairly constant
over a period of time. A sharp dip in trending of insulation resistance values, point towards insulation
degradation and further investigation is warranted to diagnose the problem.
13
Winding Resistance Test
The DC winding resistance measurement is an important measurement in accessing the true condition,
state and accuracy of a CT. With age, use, external conditions and loading effect winding resistance will
change over a period of time. It is recommended to do DC winding resistance periodically on a single
tap or multi tap CT and trend the values.
A high precision low resistance measurement circuit is required to measure this small winding resistance.
The resistance is found by dividing the voltage (measured from dc milli voltmeter) with dc current. The
CT should be demagnetized after the completion of winding resistance test.
Note: A CT should be demagnetized after running the winding resistance test. Run a saturation
test to demagnetize the CT at the completion of all winding resistance tests.
Burden Test
Burden can be defined as the total impedance in ohms on the CT output terminals. Each CT has a
secondary burden when connected in a relay or metering circuit. The total burden is a combination of
impedance offered by watt-hour meter coils, relay current coils, contact resistance, terminal blocks, wire
resistance and test switches used in the secondary loop.
Burden test is performed to verify that CT under test is capable of supplying a known current into a
known burden while maintaining its stated accuracy. A burden test is typically performed at full rated
secondary current value. Burdens are typically expressed in VA.
14
CT’s can be classified into two groups.
1) Metering CT’s
2) Relaying CT’s
The last number specifies the Burden in ohms. For a CT with secondary current of 5 A the VA burden
rating can be calculated as
The last number specifies the max. Secondary voltage at 20 times the rated secondary current without
exceeding the 10% ratio error. For a CT with secondary current rated at 5 A, 20 times rated current
secondary current would give a burden of 4 ohms.
CT’s are expected to provide the secondary output current based upon their accuracy class. If a CT is not
properly sized based upon secondary loop burden, it may result in decrease in CT secondary current.
Burden test is important to verify that CT is supplying current to a circuit with burden that does not
exceed its burden rating.
A detailed description of how to perform a burden test with MCT1605 is given in the test procedure.
15
Description of Controls and Indicators
17
3
6
4 1
16
15
5
14
6
7 8 9 10 11 12 13
16
Connections:
1. Input power: Receptacle for connecting the test set to an AC power source. Rating for voltage input
is 95-265 V, 50/60 Hz.
2. ON/OFF: Two pole, magnetic main circuit breaker controls the power to the test set and provide
short circuit and overload protection.
CAUTION
Caution symbols are appropriately marked on the unit for input and output terminals.
Follow the symbols to prevent any accidental electric shock.
3. Insulation Tester: 1000V DC output for performing Insulation test. Outputs are marked as positive
(red) and negative (blue).
4. X winding connection: Dual point connection to X winding of the current transformer under test. A
maximum of 1600V AC is available from this output.
WARNING
Appropriate warning symbols are marked on the unit, indicative of possible
source of electric shock. Follow the symbols while operating the unit.
6. Ground Connection: This wing nut is used to connect the test set to station ground.
Indicators:
7. High Voltage indicators: Red color LED’s indicating the presence of high voltage at the outputs of
the unit.
WARNING
High voltage is present at the X1, X2 output terminals of the unit whenever the
two red color LED lights are flashing.
Controls:
8. Function controls: F1 to F6 function keys are used to select different options in menu screen.
F1- Back to test /Load test /Update software/Select voltage and current
F2- Delete file/Range selection/Tap ratio
F3- Rename the File
F4- Copy the File to USB/Print
F5- Save results
F6- Main menu
17
9. QWERTY Keypad: It is used to enter alpha numeric data for test report. Function buttons are used to
access different control options in various test screens.
10. Navigation Button: These arrow keys are used to scroll sideways and up/down for accessing
different menu options.
11. Enter: This is used to activate a particular selection in the menu options.
13. Manual voltage controls: The potentiometer knob is used for manual control of output voltage from
test set to the secondary of the CT. Press the knob for fast variation in voltage.
14. Emergency Stop Button: This red push button interrupts testing. When pressed, the switch is locked
in OFF position. To reset the switch, turn the button in the direction indicated by the arrows.
16. Ethernet port: Ethernet port is used for connection of unit to the computer for remote operation.
Display:
17. LCD display screen: The 6.5” large graphical display provides easy to read test results and CT
saturation curve plots.
18
Operation and Controls
The MCT1605 works on “VX Works” operating system. At the boot up of the test set, Main Menu screen
will show up.
Main menu:
Main menu is the home screen of the test set. All the tests and settings for the unit can be accessed
from this screen. With the help of navigation button and enter key one can select the desired operation.
Following are the nine user selectable operation.
19
Refer to each menu item below for detailed description.
Nameplate Info:
Nameplate Info screen is used to fill out the CT serial no., name plate data and test report information.
Two pages are used for complete CT information. Toggle between the two pages of ‘Nameplate Info’ by
the help of F2 function key.
CT_ID:
CT_ID page is used to fill out the optional testing information such as:
■■ Technician name,
■■ Company information,
■■ Substation location,
■■ Position and phase of CT
■■ Other relevant testing data.
Function keys:
F1 Function: Hitting F1 function button would take user back to the previously selected test screen.
F2 Function: F2 function key is used to flip between the two pages (CT_ID and Name Plate) of ‘User
Input’ menu.
20
F4 Function: This key is used to configure the saturation, ratio and insulation test on a CT.
F5 Function: This key would save the test results to internal memory of the test set with file name as
CT id.
Name Plate:
Nameplate page is used to fill out the Name plate data of CT under test.
■■ Manufacturer: By using the tab button, place the cursor in this column and enter the manufacturer
of the CT.
■■ Serial No: Fill CT serial no. from the nameplate of the CT under test.
■■ Type: Select the appropriate type of CT from available selection.
a) Bar Type
b) Window Solid Type
c) Window Split Core
■■ Style: The style of CT can be entered in this column.
■■ Voltage rating: Voltage rating can be obtained from CT nameplate.
21
Accuracy Class Select the CT accuracy class from available options
■■
aa) C10 h) T10
b) C20 i) T20
c) C50 j) T50
d) C100 k) T100
e) C200 l) T200
f) C400 m) T400
g) C800 n) T800
■■ Ratio: For a multi- tap CT, different tap ratios can be obtained from nameplate and can be entered in
nameplate screen.
■■ Temperature & Humidity: If known, environmental conditions such as temperature and humidity
can be entered.
Note: All the information in Nameplate screen is optional. It is not required to perform a test on
CT. Only CT ID is required for storage of results.
Function keys:
F1 Function: Hitting F1 function button would take user back to the previously selected test screen.
F2 Function: F2 function key is used to flip between the two pages (CT_ID and Name Plate) of ‘User
Input’ menu.
F4 Function: This key is used to configure the saturation, ratio and insulation test on
a CT.
F5 Function: This key would save the test results to internal memory of the test set with file name as CT
id.
22
File Manager
File manager screen is used to view and access the stored test results. All stored test results are displayed
in alphabetical order along with date and time stampings. Test results are stored with the file name as
CT ID and extension as “.tst”. MCT1605 test set can store up to 3000 or more test results in its internal
memory. Function buttons are used to recall, delete or transfer the test results.
Function keys
F1 function: This key is used to load the test results on the MCT display screen.
■■ Select the desired test results by highlighting it.
■■ Hit F1 function key.
■■ A message will pop up indicating that a particular test result has been loaded
23
F2 function: This key is used to delete the previously stored test results from internal memory of the unit.
■■ Select the desired test to be deleted.
■■ Hit F2 function key.
■■ A window will come up for confirmation to delete the test result.
■■ Hit ‘YES’.
■■ Test result is now deleted.
■■ Hit OK.
■■ File name is now changed.
24
F4 function: This key is to copy the stored test results from internal memory to external memory device
like USB stick.
■■ Select the file to be transferred.
■■ Hit F4 function key.
■■ The unit will try to detect the external memory device. If there is no memory stick, following
message will come up.
■■ If external memory device is present, following message will be displayed, indicating that data has
been copied to the external memory device.
■■ Hit Ok.
Note: Stored test results are copied NOT transferred to the external memory device. In order to
free up the internal memory of the test set, user have to delete the test results.
F5 function: This key is used to print out the list of all stored test files inside the unit.
F6 function: This key is used to return back to main menu or home screen.
25
System Default:
The default settings for MCT1605 can be changed by accessing system default menu screen. This screen
also provides the software and firmware version information along with serial no. of the unit.
26
Function keys System Defaults
F1 Function: Hit F1 key to update the software. Unit look for the latest software files in the external
memory device connected to the USB port.
F6 Function: This key is used to return back to main menu or home screen.
IP Address: This button will launch a window that will allow the user to set the IP Address.
The laptop can be either connected to the network or isolated from the network.
27
■■ Based upon server settings either of the following messages will appear.
Condition I
■■ After enabling the DHCP, open the PowerDB Lite and select MCT-16xx instrument.
28
■■ Check Use Ethernet box and leave the Ethernet field blank.
■■ Hit OK.
■■ Initialize the instrument by hitting the highlighted button below in PowerDB.
29
Condition II
■■ IF DHCP initialization fails after pressing F1 function key then following message will appear.
■■ After the error message, the IP address screen will look like
30
■■ In instrument configuration screen check the “Use Ethernet” box and enter the noted down IP
address. Screen will look like as shown below.
■■ Hit OK.
■■ Initialize the instrument by hitting the highlighted button below in PowerDB.
31
Laptop not connected to the network
■■ If laptop is not connected to the network, user can establish communication using any one method
shown below:
Method I:
■■ Hit F1 function key in IP address screen to initialize DHCP communications
■■ Since, computer is not connected to the network, it will fail DHCP initialization.
■■ After the error message, the IP address screen will look like this.
32
■■ Hit OK.
■■ Initialize the instrument by hitting the highlighted button below in PowerDB.
33
Method II:
■■ Click on IP address in system default screen . It will show the factory default IP address.
34
■■ Following window will open up. Scroll down and double click on Internet Protocol (TCP/IP)
■■ Hit OK.
35
■■ Open PowerDB Lite and select the instrument MCT -16xx
■■ In instrument configuration screen check the “Use Ethernet” box and enter the noted down IP
address. Screen will look like as shown below.
■■ Hit OK.
■■ Initialize the instrument by hitting the highlighted button below in PowerDB.
36
Manual
MCT1605 gives user the option of manual testing on current transformers. Manual screen is used for
performing a manual test. In manual mode, manual voltage controls knob is used for application of test
voltage to the secondary of CT under test.
Range Selection: Use F2 function key to select the desired secondary voltage range. User can select any
one out of the four (40,160,800 and 1600V) available voltage ranges by repeatedly hitting F2 key.
Capture Reading: Use F3 function key to freeze the current reading and calculate the turns ratio. All
control knobs and function keys will be frozen except the F3 or Release function key. The ratio and
respective voltages will be displayed on the screen as shown below.
Release: After a reading has been captured use F3 function key to release the control knobs and other
function keys.
37
Tap: Use F4 function key to select the tap on which you perform the test.
Clear Test Data: This will clear the test results from current test screen.
Clear All: In addition to the clear test data function it will clear all the nameplate screen information.
H Range: Use F5 function key to select the desired primary voltage range. User can select one out of the
two (2 and 600V) available voltage ranges by repeatedly hitting F2 key.
Manual voltage controls: The test voltage knob on the front panel of the unit is used to apply a
controlled secondary test voltage to the CT under test. The manual voltage controls is a free to rotate
knob with no start/stop point. The default speed of knob is set to slow. To increase the speed (medium/
fast) press the knob and a higher voltage variation can be achieved for same rotation of the knob. Three
steps (slow, medium and fast) are available for the voltage variations. To revert back to low speed press
the knob again. Screen will display the current knob speed.
38
Secondary (X) Voltage: The applied secondary test voltage is displayed on the screen in digital
readout form.
Primary (H) Voltage: The measured primary voltage is displayed on the screen in digital readout form.
Secondary (X) Current: The secondary current is displayed for user reference to monitor while
performing ratio and saturation tests.
Test Configuration
This screen is used to configure and select the tests to be performed on different taps of the CT.
Tap Selection: Select different taps of CT on which you want to perform the tests using the check boxes.
All Taps: Selecting all taps would check all the boxes in that column. For instance selecting all taps in
saturation test column would select all taps and test set will perform saturation test on all the checked
taps.
Saturation: Checking box in this column in front of any tap would enable the saturation test for that
particular tap.
39
Ratio: Checking box in this column in front of any tap would enable the ratio test for that particular tap.
Winding resistance: Checking box in this column in front of any tap would enable the winding
resistance test for that particular tap.
Voltage range: Voltage range enables you to select the desired voltage range at which you want to run
the test.
Insulation resistance: Three different tests can be selected for insulation resistance based upon
between which two points you want to check the insulation.
■■ Primary to Secondary
■■ Primary to Ground
■■ Secondary to Ground
Once all the desired tests are selected in the test configuration screen, all the tests would run in
sequential order automatically, when you hit ‘Run’ button (F1 key).
After all the selected tests are finished, user can save the results by entering in the CT ID.
Function keys
Function F1: Hit F1 to run the all the selected tests sequentially and automatically.
Function F5: Hit F5 to go to nameplate screen and enter the CT nameplate information.
40
Saturation Test
Saturation test menu screen is used to perform a saturation test on CT. At the end of test, saturation
curve, measured ratio and polarity test results are displayed for the CT under test.
X Voltage (V): It displays the real time voltage readings of the secondary X winding while the test is
in progress.
X Current (A): It displays the real time current readings for the secondary X winding while the test is
in progress.
H Voltage (V): It displays the real time voltage readings of the primary H winding while the test is
in progress.
Saturation Curve: The excitation curve is Log-Log curve with secondary current on X coordinate and
secondary voltage on Y coordinate.
Ratio: At the completion of test, the measured ratio is compared with expected ratio (obtained based
upon user input) and a percent error in Ratio is determined by following formula.
Test voltage: It displays the selected test voltage. User can select any one out of four available test
voltages (40,160,800 and 1600).
41
Polarity: Unit automatically determines the polarity connections and displays the result as either polarity
Correct or Incorrect. The phase angle deviation between the secondary and primary voltage is also
displayed along with polarity.
Saturation points: The unit automatically determines the knee point based upon the user selected
standard (ANSI 30, ANSI 45 or IEC 60044-1). Saturation voltage and saturation current corresponding to
that knee point are displayed along with other results at the completion of the test.
Max limit: Hit F1 function button to select the desired test voltage. Four test voltages available are 40V,
160V, 800V and 1600 V. For instance, on selecting a test voltage of 800V, the unit will automatically vary
the voltage from 0 to 800V to determine the saturation curve and knee point.
If the selected voltage is not sufficient enough to determine the required parameters, the unit will display
the following error message.
Select a higher test voltage range and perform the test again.
Note: Appropriate voltage range can be selected by knowing the accuracy class of CT under test.
Tap ratio: Hit F2 function to put the expected tap ratio of the CT under test. Following pop up will
come up on hitting the F2 button.
Select the desired Tap and a window will pop up to enter the tap ratio.
42
Use tab button and numeric keypad to enter the desired tap ratio. Hit the enter button to accept a value
or on the OK button to finish.
Note: To clear Nameplate data and all test data, use “clear all” option in Tap/Ratio screen. To
save the Nameplate data, clear the test screens and clear off previous test results, use “clear Test
Data” option in Tap/Ratio.
Print result: Hit F4 function button to print out the saturation test results. Results will be printed on
8” by 11” paper through an external printer.
Save result: Hit F5 function button to store the saturation test results in the internal memory of the unit.
Only CT id is required to store the test results.
Main menu: Hit F6 button to return to main menu or home screen of the unit.
Ratio Test
43
Ratio menu screen is used to perform the ratio and polarity test. Measured ratio, polarity, test voltage and
current are displayed at the end of the test. Unit automatically selects the voltage range for the ratio test.
X Voltage (V): It displays the real time applied voltage to the secondary X winding of the CT under test.
H Voltage (V): It displays the real time measured voltage of the primary H winding of the CT under test.
Ratio: At the completion of test, the measured ratio is compared with expected ratio (obtained based
upon user input) and a percent error in Ratio is determined by following formula.
Test voltage: Unit automatically applies the required voltage for the ratio test. It displays secondary test
voltage at the completion of test.
Test current: Unit continuously monitors the secondary excitation current and displays test current at the
end of the ratio test.
Polarity: Unit automatically determines the polarity connections and displays the result as either polarity
Correct or Incorrect. The phase angle deviation between the secondary and primary voltage is also
displayed along with polarity.
Tap ratio: Hit F2 function to put the expected tap ratio of the CT under test. Following pop up will come
up on hitting the F2 button.
Select the desired Tap and a window will pop up to enter the tap ratio.
44
Use tab button and numeric keypad to enter the desired tap ratio. Hit the enter button to accept a value
or on the OK button to finish.
Note: To clear Nameplate data and all test data, use “clear all” option in Tap/Ratio screen. To
save the Nameplate data, clear the test screens and clear off previous test results, use “clear Test
Data” option in Tap/Ratio.
Print result: Hit F4 function button to print out the ratio and polarity test results. Results will be printed
on 8” by 11” paper through an external printer.
Save result: Hit F5 function button to store the ratio and polarity test results in the internal memory of
the unit. Only CT ID is required to store the test results.
Main menu: Hit F6 button to return to main menu or home screen of the unit.
Insulation Test
Insulation test menu screen is used to perform an insulation test between the windings (or windings
to ground) of the CT, by applying a 1000 VDC. Insulation resistance can be displayed in (M) ohms,
(K) ohms, and ohms.
Digital analog indicator: Displays the insulation resistance with a digital pointer on a log scale from
0.01 M ohms to 1000 M ohms.
Insulation resistance: Displays the insulation resistance in M ohms on digital read out.
Test volt: Select either 500V or 1000V DC test voltage by using function key F1.
45
Test configuration: Select desired test by repeatedly hitting function F2 key. User can select one of the
three test mode.
a) Primary to Secondary b) Primary to Ground c) Secondary to Ground
Tap: Hit F3 function key to select the tap configuration of the CT. This would select if there are 2, 3, 4 or
5 taps on a CT.
Print result: Hit F4 function button to print out the insulation test results. Results will be printed on 8”
by 11” paper through an external printer.
Save result: Hit F5 function button to store the insulation test results in the internal memory of the unit.
Only CT ID is required to store the test results.
Main menu: Hit F6 button to return to main menu or home screen of the unit.
Set Up:
Prior to conducting any winding resistance testing, the test leads supplied with the instrument need to
be zeroed out. This function needs to be performed upon initial receipt of the instrument and thereafter
only when an unexpected result is obtained. The function ‘Zero Leads’ can be performed in the
following steps:
46
1) From the Main Menu, select the Winding Resistance Test
3) Plug all of the supplied X ( Secondary) test leads into the appropriate colored coded jacks on the
front of the MCT1605
4) Each associated ‘Test Lead’ needs to be zeroed for each correlating tap. Thus this function needs be
performed 10 times in order to zero both the external and internal taps
5) Using the supplied alligator clips, connect the X1 Lead to the X2 Lead
7) Select the Zero Leads Function by selecting the (F1) hotkey. This will perform a test and calculate the
amount of resistance supplied by the circuit comprised by the X1 & X2 leads being connected. This
value will be approximately 1.2 ohm. This value will be stored within the system defaults and will be
subtracted from any future Winding Resistance tests involving X1 & X2.
As stated earlier, zeroing out the test leads needs to be performed upon initial receipt of the instrument,
and only periodically thereafter. It is recommended that if an unexpected result is ever obtained, then re-
zero the lead and re-run the test.
Winding resistance menu screen is used to determine if the dc resistance of the CT secondary winding
is within specification or not. A DC current is applied and voltage is measured to determine the winding
resistance for the selected tap. After measurement winding resistance is displayed in digital and analog
format on the screen.
Digital analog indicator: Displays the winding resistance with a digital pointer on a log scale from
0.01 ohms to 100 ohms.
Winding resistance: Displays the winding resistance in ohms on digital read out.
Tap: Hit F2 function button repeatedly to select the desired tap. This will select the tap on which it will
perform the winding resistance measurement.
Print result: Hit F4 function button to print out the insulation test results. Results will be printed on
8” by 11” paper through an external printer.
Save result: Hit F5 function button to store the insulation test results in the internal memory of the unit.
Only CT ID is required to store the test results.
Main menu: Hit F6 button to return to main menu or home screen of the unit.
Note: A CT should be demagnetized after running the winding resistance test. Run a saturation
test to demagnetize the CT at the completion of all winding resistance tests.
47
Burden Test
Burden menu screen is used to perform a burden test on CT secondary burden. Results are displayed in
VA and phase angle.
X Voltage (V): It displays the real time measured voltage across the burden of the CT.
X Current (A): It displays the applied current (user selected 1A or 5A) to the burden of the CT.
Burden VA: Displays the burden on the CT in VA, after the completion of test.
Rating: Based upon the CT rating, hit Function F1 to select the current as 1A or 5A.
Print result: Hit F4 function button to print out the burden test results. Results will be printed on
8” by 11” paper through an external printer.
Save result: Hit F5 function button to store the burden test results in the internal memory of the unit.
Only CT id is required to store the test results.
Main menu: Hit F6 button to return to main menu or home screen of the unit.
48
Operating Instructions
Ratio & Polarity Test:
The ratio is defined as the number of turns in the secondary as compared to the number of turns in the
primary.
N2/N1=V2/V1
Where,
N2 and N1 are no. of turns of secondary and primary windings respectively
V2 and V1 are the secondary and primary side voltage readings respectively.
A suitable voltage, below saturation is applied to the secondary of the CT under test and primary side
voltage is measured to calculate the turns ratio from above expression.
WARNING
There is always a possibility of voltages being induced at the terminals of the test
specimen because of proximity to high voltage energized lines. A residual static voltage
charge may also be present at these terminals. Ground each terminal to be tested with a
safety ground stick, before making connections.
4. Connect the test set secondary output binding posts X1 X2, X3, X4 and X5 to secondary of the current
transformer X1, X2, X3, X4 and X5 (if all taps all are not available on the CT, then connect the ones
that are available to the corresponding tap no. on the test set).Observe the polarity marks on the CT
(X1 on test set is polarity terminal).
5. Connect the test set primary binding posts H1 and H2 to CT primary bushings H1 and H2. Observe
the polarity marks on the CT (H1 on the test set is polarity terminal).
49
6. Turn Power ON/OFF switch to ON.
7. After the boot up, select the “Ratio Test” menu from the main screen by using scroll button.
8. In the ratio screen, hit F2 function button to select the appropriate tap to be tested.
9. Enter the expected nameplate ratio for the desired tap. Toggle through different columns by using
scroll, “TAB” button, or “Enter” button.
50
10. Select the tap configuration before hitting the TEST button. If test button is pressed before selecting
the tap, following message will appear:
12. A dialog box appears for confirmation of the test. Hit TEST button again.
WARNING
High Voltage is now present at the terminals of the specimen
13. This will start the test and a warning high voltage symbol will appear on the “test in progress”
screen.
14. At any point of time Test can be terminated by hitting the Test button again. Following message
will appear.
51
15. Test can also be stopped under emergency condition by hitting the “Emergency Push to Stop” button
on the front panel of MCT1605. Unit will shut off the output voltage and following message will
appear.
16. After completion of test, ratio and polarity results will be displayed on the screen along with test
voltages and current.
52
19. Put in the CT ID information.
20. Hit F1 function button to save or the F2 function button to cancel.
21. If F1 is selected and the file does not already exist the following message will appear indicating that
test has been saved. If F2 function button is selected then the user will be returned to previous menu.
22. If the file already exists the test results will be added to the existing file.
Saturation Test
IEEE defines the saturation as “the point where the tangent is at 45 degrees to the secondary exciting
amperes”. It is also known as “knee” point.
This test verifies that the CT is of correct accuracy rating, has no shorted turns in the CT and no short
circuits are present in the primary or secondary windings of the CT under test.
53
2. Connect the ground wing nut to a suitable ground.
WARNING
There is always the possibility of voltages being induced at the terminals of a test
specimen because of proximity to high voltage energized lines. A residual static voltage
charge may also be present at these terminals. Ground each terminal to be tested with
a safety ground stick, before making connections.
3. Connect the test set secondary output binding posts X1 X2, X3, X4 and X5 to secondary of the current
transformer X1, X2, X3, X4 and X5 (if all taps all are not available on the CT, then connect the ones
that are available to the corresponding tap no. on the test set).Observe the polarity marks on the CT
(X1 on test set is polarity terminal).
4. Connect the test set primary binding posts H1 and H2 to CT primary bushings H1 and H2.Observe
the polarity marks on the CT (H1 on the test set is polarity terminal).
54
9. Enter the expected nameplate ratio for the desired tap. Toggle through different columns by using
scroll and “TAB” button.
Hit OK to finish.
10. Select the tap configuration before hitting the TEST button. If test button is pressed before selecting
the tap, following message will appear:
WARNING
High Voltage is now present at the terminals of the specimen.
55
14. This will start the test and a warning high voltage symbol will appear on the “test in progress”
screen.
15. Following test screen will appear with a red indicator showing that the test is in progress.
16. At any point of time Test can be terminated by hitting the Test button again. Following message
will appear.
17. Test can also be stopped under emergency condition by hitting the “Emergency Push to Stop” button
on the front panel of MCT1605. Unit will shut off the output voltage and following message will
appear.
56
18. After completion of test, saturation curve, ratio and polarity results will be displayed on the screen
along with test voltages and current.
19. If the selected Test voltage range is not enough to perform the saturation test, following message
will appear.
57
20. Select the higher voltage range and perform the Test again.
21. Save the results by hitting F5 function button.
22. If no value exists in the CT_ID Field then the CT_ID screen will open up and request a new ID.
26. If the file already exists the test results will be added to the existing file.
Multiple saturation curves for different taps can be plotted on same chart by re running the test. As many
as 10 curves can be displayed at one time. Please refer to “How to run multiple saturation tests” below.
58
How to run multiple saturation tests
Method I:
■■ After finishing first saturation test, hit F2 function to select the next tap settings.
■■ Hit OK.
■■ Select the appropriate voltage range by hitting F1 (Max Limit) function button.
■■ Select the tap configuration before hitting the TEST button. If test button is pressed before selecting
the tap, following message will appear:
59
■■ Hit TEST button again.
WARNING
High Voltage is now present at the terminals of the specimen.
■■ This will start the test and a warning high voltage symbol will appear on the “test in progress”
screen.
■■ If the selected Test voltage range is not enough to perform the saturation test, following message
will appear.
■■ Select the higher voltage range and perform the Test again.
■■ At the completion of test saturation curve will be displayed on the same graph along with
previous curve(s).
■■ All the results like ratio, polarity, saturation voltage and current will also be displayed for the current
saturation test.
■■ As many as 10 different curves can be plotted on the same graph by repeating the same steps and
selecting different CT taps.
■■ The ratios for different taps are displayed on right hand side of screen in different colors. Use Tab
button to scroll through different ratios and detailed results for that particular Tap.
60
METHOD II:
■■ Go to Main menu.
■■ Select Test configuration.
■■ Select the taps on which you want to run the saturation test by checking the boxes in front of it in
the saturation column.
■■ Select the desired voltage range at which you perform the test.
■■ Hit F1 function key to run all the selected saturation tests sequentially.
Note: Appropriate voltage range can be selected by knowing the accuracy class of CT under test.
61
DC Insulation Resistance Test:
The insulation between the windings and winding to ground should be checked while performing a
comprehensive CT test. The test set has inbuilt 1kV DC insulation tester that is used for measurement of
insulation resistance.
WARNING
There is always the possibility of voltages being induced at the terminals of a test
specimen because of proximity to high voltage energized lines. A residual static
voltage charge may also be present at these terminals. Ground each terminal to be
tested with a safety ground stick, before making connections.
4. Connect the test set secondary output binding posts X1 X2, X3, X4 and X5 to secondary of the current
transformer X1, X2, X3, X4 and X5 (if all taps all are not available on the CT, then connect the ones
that are available to the corresponding tap no. on the test set).Observe the polarity marks on the CT
(X1 on test set is polarity terminal).
5. Connect the test set primary binding posts H1 and H2 to CT primary bushings H1 and H2. Observe
the polarity marks on the CT (H1 on the test set is polarity terminal).
62
6. On any CT insulation tests are performed between three points.
a) Primary b) Secondary c) Ground
Note: User does not have to short the primary or secondary sides of CT; the MCT1605 does that
automatically internally.
Note: User does not have to make any other connections except as described in steps 3, 4 and 5.
7. Remove the neutral ground and isolate the CT from any associated burden.
8. Turn Power ON/OFF switch to ON.
9. After the boot up, select the “Insulation Test” menu from the main screen by using scroll button.
10. Hit F3 function key to select the tap configuration of CT out of the following:
a) X1-X2 b) X1-X3 c) X1-X4 d) X1-X5
For instance you would select X1-X3 for a CT that has X1, X2 and X3 terminals.
11. Three DIFFERENT tests are performed to determine the condition of the insulation of CT under test.
The three tests are:
63
In this test it will apply the voltage between primary and secondary.
In this test it will apply the voltage between primary and ground.
64
■■ Third- Secondary to Ground:
Select the secondary to ground test from the insulation test screen and also select the desired voltage.
Based upon test selection MCT1605 would automatically know between which two points the voltage
needs to be applied.
In this test it will apply the voltage between secondary and ground.
Note: Refer to the Insulation Test diagram (Figure 9, 10 & 11) in Appendix for more details.
65
14. Hit TEST button again.
WARNING
High Voltage is now present at the terminals of the specimen.
15. This will start the test and a warning high voltage symbol will appear on the “test in progress”
screen.
16. At any point of time Test can be terminated by hitting the Test button again. Following message
will appear.
17. Test can also be stopped under emergency condition by hitting the “Emergency Push to Stop” button
on the front panel of MCT1605. Unit will shut off the output voltage and following message will
appear.
66
18. After completion of test, Insulation resistance in (M) ohms will be displayed on the LCD screen
as a digital readout.
67
Winding Resistance Test:
The winding resistance on each tap of a multi-tap CT should be checked while performing a
comprehensive CT test. The test set has inbuilt DC winding resistance tester that is used for measurement
of winding resistance of a CT.
WARNING
There is always the possibility of voltages being induced at the terminals of a test
specimen because of proximity to high voltage energized lines. A residual static
voltage charge may also be present at these terminals. Ground each terminal to be
tested with a safety ground stick, before making connections.
4. Connect the test set secondary output binding posts X1 X2, X3, X4 and X5 to secondary of the current
transformer X1, X2, X3, X4 and X5 (if all taps all are not available on the CT, then connect the ones
that are available to the corresponding tap no. on the test set).Observe the polarity marks on the CT
(X1 on test set is polarity terminal).
5. Connect the test set primary binding posts H1 and H2 to CT primary bushings H1 and H2. Observe
the polarity marks on the CT (H1 on the test set is polarity terminal).
68
6. Turn Power ON/OFF switch to ON.
7. After the boot up, select the “Winding Resistance Test” menu from the main screen by using scroll
button.
8. On a multi tap CT, following taps winding resistance can be measured.
9. Select the desired tap that you want to test by hitting F2 function key.
10. Select the tap configuration before hitting the TEST button. If test button is pressed before selecting
the tap, following message will appear:
69
13. Hit TEST button again.
14. This will start the test and a warning high voltage symbol will appear on the “test in progress”
screen.
15. At any point of time Test can be terminated by hitting the Test button again. Following message
will appear.
16. Test can also be stopped under emergency condition by hitting the “Emergency Push to Stop”
button on the front panel of MCT1605. Unit will shut off the output voltage and following message
will appear.
17. After completion of test, winding resistance in ohms will be displayed on the LCD screen as a digital
readout.
70
18. Save the results by hitting F5 function button.
Note: A CT should be demagnetized after running the winding resistance test. Run a saturation
test to demagnetize the CT at the completion of all winding resistance tests.
Manual Test:
MCT1605 is an automatic AND manual CT test set. Manual mode of testing is available, for controlling the
secondary test voltage to the CT under test. This is done by using a manual voltage controls knob.
WARNING
There is always the possibility of voltages being induced at the terminals of a test
specimen because of proximity to high voltage energized lines. A residual static
voltage charge may also be present at these terminals. Ground each terminal to be
tested with a safety ground stick, before making connections.
4. Connect the test set secondary output binding posts X1 X2, X3, X4 and X5 to secondary of the current
transformer X1, X2, X3, X4 and X5 (if all taps all are not available on the CT, then connect the ones
that are available to the corresponding tap no. on the test set). Observe the polarity marks on the CT
(X1 on test set is polarity terminal).
5. Connect the test set primary binding posts H1 and H2 to CT primary bushings H1 and H2. Observe
the polarity marks on the CT (H1 on the test set is polarity terminal).
6. Turn Power ON/OFF switch to ON.
7. After the boot up, select the “Manual Test” menu from the main screen by using scroll button.
8. In the manual test screen, hit F2 function button for range selection. Multiple hit of the F2 function
key would select different voltage ranges (40, 160,800 and 1600).
9. Select the tap on which you want to run the test in manual mode.
71
10. Select the tap configuration before hitting the TEST button. If test button is pressed before selecting
the tap, following message will appear:
WARNING
High Voltage is now present at the terminals of the specimen.
14. This will start the test and a warning high voltage symbol will appear on the “test in progress”
screen.
15. At any point of time Test can be terminated by hitting the Test button again. Following message
will appear.
72
16. Test can also be stopped under emergency condition by hitting the “Emergency Push to Stop”
button on the front panel of MCT1605. Unit will shut off the output voltage and following message
will appear.
17. Use the manual voltage controls knob to apply a known voltage to the secondary of the CT under
test. Keep an eye on secondary amps reading to prevent CT saturation. Most of the CT would
saturate at 1 amp of secondary current.
18. For Ratio test, apply one volt per turn to the secondary of the CT. Raise voltage slowly while
observing the meters.
CAUTION
CT secondary current should not go above 1A, that will saturate the CT and
readings for Ratio test will be incorrect
19. Capture Reading: Use the F3 function key to freeze the current readings and calculate the ratio.
20. Release: Use the F3 function key to release the readings and control knobs
21. If CT saturates before one volt per turn is reached, apply a smaller voltage which is a fraction of one
volt per turn.
22. Once a known secondary voltage is reached, note down the primary and secondary voltage readings
to get the turn’s ratio.
23. Hit the “TEST” button again to stop the test.
73
Burden Test:
Burden test is performed to verify that CT under test is capable of supplying a known current into a
know burden while maintaining its stated accuracy. A burden test is typically performed at full rated
secondary current value. Burdens are typically expressed in VA.
WARNING
There is always the possibility of voltages being induced at the terminals of a test
specimen because of proximity to high voltage energized lines. A residual static
voltage charge may also be present at these terminals. Ground each terminal to be
tested with a safety ground stick, before making connections.
74
10. A dialog box appears for confirmation of the test. Hit TEST button again.
WARNING
High Voltage is now present at the terminals of the specimen.
11. This will start the test and a warning high voltage symbol will appear on the “test in progress”
screen.
12. At any point of time Test can be terminated by hitting the Test button again. Following message will
appear.
13. Test can also be stopped under emergency condition by hitting the “Emergency Push to Stop” button
on the front panel of MCT 1600. Unit will shut off the output voltage and following message will
appear.
75
14. After completion of test, Burden in VA and power factor results will be displayed on the screen along
with test voltages and current.
15. The measured burden should be less than or equal to the Burden (VA) rating of the CT under test.
16. Save the results by hitting F5 function button.
76
Recalling and Saving of Results:
Saving Results
1. After performing saturation, ratio, polarity, or insulation test hit F5 function key to store the test results.
2. Enter the CT id to store the results. Test results are saved with CT id name.
Recalling Results
3. To recall a previous test result, select the “File Manager” option from the main menu screen.
4. File manager screen will display all the test results stored into the internal memory of the unit.
5. Select the desired test and hit on F1 function key to load the test results. Following message will
appear.
6. Screen will go to main menu from where different test results can be viewed.
77
Deleting Results
7. Hit F2 function key to delete any previously stored test results.
A confirmation box will come up; hit YES to delete a selected test.
Renaming File
8. Hit F3 function key to rename already stored file. Enter the new name in the dialog box and hit
F1 function key to rename the file.
Transferring Results
9. Hit F4 function key to transfer the data from internal memory to USB stick. Either of the two
USB ports could be used for data transfer to USB stick.
Note: MCT1605 works on VX operating system. The recommended limit of USB drive capacity
is up to 1 GB.
Home Screen
10. Hit F6 function key to return to main menu screen.
78
Appendix
79
Figure 8 Multi Ratio Current Transformer Test- B
■■ CT’s with no access to the primary side can be tested with connections to the secondary winding as
shown above for multi-ratio CT’s.
■■ Voltage applied to the X1-X2 taps of the CT will induce a proportionate voltage on the remaining
taps. By measuring voltage at different taps of CT, CT ratio can be verified.
80
Bushing CT’s can be tested in a de-energized circuit
breaker which has been totally isolated from the
power system. The breaker must be closed to
perform ratio and polarity tests.
NOTE: The breaker does not have to be closed to perform the voltage test.
81
Bushing CT’s can be tested in a de-energized circuit
breaker which has been totally isolated from the
power system. CT secondary leads will normally
terminate in the control cabinet. Refer to the chart
on for connections.
82
Bushing CT’s can be tested in a de-energized circuit
breaker which has been totally isolated from the
power system. CT secondary leads will normally
terminate in the control cabinet. Refer to the chart
on for connections.
83
Insulation Testing
Figure 12 Three terminal insulation test specimen: Primary, Secondary and Ground
84
Figure 14 Primary to ground Insulation measurement
85
Burden Testing
86
PowerDB Lite
Introduction
PowerDB Lite provides you with professional looking data forms with minimal effort. Print your files to
paper or .PDF and reduce the time it takes to complete your report generation.
PowerDB Lite allows you to view the MCT test files and save the forms with test results onto your
computer.
Software Installation
Hit OK.
87
3. Accept the terms of the license agreement by clicking ‘YES’.
Click Next.
88
5. Select default settings.
6. Install Shield Wizard will complete the installation of PowerDB Lite software.
Click finish to close the installation program.
89
3. Click on File> Open to view the MCT test results.
6. Select the file and hit Open to view the test results. To open a blank CT Test Form, Hit ‘New’.
7. A Current transformer Test form will be opened displaying the test results.
90
Sample PowerDB test form with results
91
92
Specifications
Input
95 to 265 V, 1j, 50 or 60 Hz
Output
Continuously variable in six ranges:
0 to 40V at 5.0A max (15 minute on, 15 minute off)
0 to 160 V at 5.0 A max (15 minute on, 15 minute off)
0 to 800 V at 1.5 A max (5 min on, 15 min off)
0 to 1600 V at 1.0 A max (5 min on, 15 min off)
Instrumentation
Voltmeters
Output
41/2 digit, auto ranging
Resolution: 0.0000 to 1.9999/19.999/199.99/1999.9
Ranges: 0 to 40/160/800/1600
Accuracy: ±0.5 % of reading and ±0.5% of range typical
±1% of reading and ±1 V maximum
Input
41/2 digit, auto ranging
Resolution: 0.0000 to 1.9999/19.999/199.99/600 V
Ranges: 0 to 2/600V
Accuracy: 2 V Range: ±0.5 % of reading and ±0.5% of range
600 V Range: ±0.5% of reading and ±0.5% of range
Ammeter
41/2 digit
Range: 0.0000 to 1.0000A/10.000
Accuracy: ±0.85 % of reading and ± LSD
Phase Angle
3 digits
Range: 0 to 360 degrees
Accuracy: ±1 degree
Ratio
Range Accuracy
0.8 to 5000: ±0.4% typical
±0.8% maximum
93
Insulation Test
Test Voltage: 1000 VDC, 500 VDC
Measuring Range: 10 KΩ – 999 MΩ
Short circuit current: 1.5 mA nominal
Test current on load: 1 mA at min. pass values of insulation
(As specified in BS7671, HD 384 and IEC 364)
Accuracy: ±3%, ±2 digits up to 10M
±5%, up to 100 M
±30% up to full scale
Computer Interface
USB
Ethernet
Environment
Operating: -10º C to 50º C
Storage: -30º C to 70º C
Enclosure
The unit is housed in a rugged enclosure suitable for use in outdoor substations
Standards
IEC 61010
CSA 22.2
CE
Dimensions
7.5”H X 19.25”W X 15”D
(190H X 489W X 940D mm)
Weight
47.6 lb (21.6 kg)
94
CT Demagnetization
A magnetized CT with residual magnetism will give incorrect ratio and saturation results. It is very
important to demagnetize the CT before/after every saturation test. MCT1605 automatically demagnetize
the CT at the completion of the test.
CT can have some residual magnetism if a large DC current was passed through it’s winding or high over
currents were interrupted at it’s peak value. The effect of residual magnetism is when the CT is energized
next time; it would result in CT ratio error and unpredictable early saturation.
The MCT1605 demagnetizes the CT by applying a suitable AC voltage to CT secondary and taking it
above saturation point. The unit then slowly decreases the secondary voltage back to zero thereby
demagnetizing it and clearing any residual magnetism.
The demagnetizing function is inbuilt to the unit and operator doesn’t have to do anything for CT
demagnetization.
Routine maintenance is all that is required for these test sets. The cables and connectors should be
inspected frequently to be sure that all connections are tight and no damaged or loose connection has
developed.
The appearance of the test set can be maintained by occasional cleaning of the MCT case and assemblies.
The front panel can be cleaned with a dry cloth or a cloth dampened with detergent and water. Do not
allow water to penetrate through output terminals or any panel holes, because damage to components
on the underside may result.
Calibration
A self calibration check can be done to verify the calibration of the unit. If there is any deviation in
results from normal, please contact Megger for more information. A complete operation and calibration
check is recommended at least once a year.
Self Check:
1. Make sure test set is OFF
2. Connect the ground wing nut to a suitable ground.
3. Connect the H1 lead to X1 and H2 lead to X2.
4. Turn the test set ON.
5. From main screen, select the manual option.
6. Select the H Voltage range as 600V by using F5 function button.
7. Select the X Voltage range as 40V by using F2 function button.
6. Apply a certain test voltage, for example 10V to the secondary X1 and X2.
7. Read the primary and secondary voltage readings from the screen.
10. Observe that both the readings should be same, or very close to each other.
11. Now increase the voltage to 20 V gradually. The change in secondary voltage will reflect same and
proportionate change in primary voltage.
95
Warranty & Repair
Warranty
Megger warrants to the original purchaser that the product is free from defects in material and
workmanship for a period of one (1) year from the date of shipment.
This warranty is limited and shall not apply to equipment which has damage, or cause of defect, due
to accident, negligence, and improper operation, faulty installation by purchaser, or improper service
or repair by any person, company or corporation not authorized by Megger. If examination by Megger
discloses that the product is or has been defective, then our obligation is limited to repair or replacement
of the defective units or its components, at our option.
The foregoing warranty constitutes Megger’s sole liability and is in lieu of any other warranty of
merchantability or fitness. Megger shall not be responsible for any incidental or consequential damages
arising from any breach of warranty.
Repair
In the event that MCT1605 appears defective, call the Megger Dallas service department at
1-800-723-2861. The service and technical support department will determine the cause of apparent
malfunction and provide the necessary support to correct the problem. At times, problems can be
corrected by troubleshooting on phone. Therefore, before returning the equipment to the factory for
repair/service discuss all problems with Megger.
If factory service is required, request repair service department for return instructions. A Return
Authorization (RA) number will be assigned for proper handling of the unit when it arrives at the factory.
Provide relevant information like model number, serial number of the unit, nature of the problem, return
address, your name and where you can be reached should the factory need to contact you.
96