Liquid Overfeed Systems: Terminology
Liquid Overfeed Systems: Terminology
Liquid Overfeed Systems: Terminology
Fig. 1 Liquid Overfeed with Mechanical Pump Fig. 3 Double Pumper Drum System
It is time-consuming to adjust hand expansion valves to achieve Solution: Orifice diameter may be calculated as follows:
ideal flow conditions. However, they have been used with some suc-
Q 0.5 ρ 0.25
cess in many installations prior to the availability of more sophisti- d = ------ --- (1)
cated controls. One factor to consider is that standard hand Cd p
expansion valves are designed to regulate flows caused by the rela-
tively high pressure differences between condensing and evaporat- where
ing pressure. In overfeed systems, large differences do not exist, so d = orifice diameter, mm
valves with larger orifices may be needed to cope with the combi- Q = discharge through orifice, mL/s
nation of the increased quantity of refrigerant and the relatively small p = pressure drop through orifice, Pa
pressure differences. Caution must be exercised when using larger ρ = density of fluid at −35°C
orifices because controllability decreases as orifice size increases. = 683.7 kg/m3
Calibrated, manually operated regulating valves reduce some of Cd = coefficient of discharge for orifice
the uncertainties involved in using conventional hand expansion
0.5 683.7 0.25
d = ---------- -----------------------
valves. To be effective, the valves should be adjusted to the manu- 33.3
- = 2.47 mm
facturer’s recommendations. Because the refrigerant in the liquid 0.61 55 × 1000
feed lines is above saturation pressure, the lines should not contain
flash gas. However, liquid flashing can occur if excessive heat gains Note: As noted in the text, use a 2.5 mm diameter orifice to avoid
by the refrigerant and/or high pressure drops build up in the feed clogging.
lines.
Orifices should be carefully designed and selected; once OIL IN SYSTEM
installed they cannot be adjusted. They are generally used only for In spite of reasonably efficient compressor discharge oil separa-
top- and horizontal-feed multicircuit evaporators. Foreign matter tors, oil finds its way into the system low-pressure sides. In the case
and congealed oil globules can cause flow restriction; a minimum of ammonia overfeed systems, the bulk of this oil can be drained
orifice of 2.5 mm is recommended. With ammonia, the rate of cir- from the low-pressure receivers with suitable oil drainage facilities.
culation may have to be increased beyond that needed for the min- In low-temperature systems, a separate valved and pressure-pro-
imum orifice size because of the small liquid volume normally tected, noninsulated oil drain pot can be placed in a warm space at
circulated. Pumps and feed and return lines larger than minimum the accumulator. The oil/ammonia mixture flows into the pot, and
may be needed. This does not apply to halocarbons because of the the refrigerant evaporates. This arrangement is shown in Figure 6.
greater liquid volume circulated as a result of fluid characteristics. At pressures lower than atmospheric, high-pressure vapor must be
Conventional multiple outlet distributors with capillary tubes of piped into the oil pot to force oil out. Because of the low solubility
the type usually paired with thermostatic expansion valves have of oil in liquid ammonia, thick oil globules circulate with the liquid
been used successfully in liquid overfeed systems. Capillary tubes and can restrict flow through strainers, orifices, and regulators. To
may be installed downstream of a distributor with oversized orifices maintain high efficiency, oil should be removed from the system by
to achieve the required pressure reduction and efficient distribution. regular draining.
Existing gravity-flooded evaporators with accumulators can be Except at low temperatures, halocarbons are miscible with oil.
connected to liquid overfeed systems. Changes may be needed only Therefore, positive oil return to the compressor must be ensured.
for the feed to the accumulator, with suction lines from the accumu- There are many methods, including oil stills using both electric heat
lator connected to the system wet return lines. An acceptable and heat exchange from high-pressure liquid or vapor. Some
arrangement is shown in Figure 5. Generally, gravity-flooded evap- arrangements are discussed in Chapter 2. At low temperatures, oil
orators have different circuiting arrangements from overfeed evap- skimmers must be used because oil migrates to the top of the low-
orators. In many cases, the circulating rates developed by pressure receiver.
thermosiphon action are greater than the circulating rates used in Buildup of excessive oil in evaporators must not be allowed
conventional overfeed systems. because it causes efficiency to decrease rapidly. This is particularly
Example 1. Find the orifice diameter of an ammonia overfeed system with
critical in evaporators with high heat transfer rates associated with
a refrigeration load per circuit of 4.47 kW and a circulating rate of 7. low volumes, such as flake-type ice makers, ice cream freezers, and
The evaporating temperature is –35°C, the pressure drop across the ori- scraped-surface heat exchangers. Because the refrigerant flow rate
fice is 55 kPa, and the coefficient of discharge for the orifice is 0.61. through such evaporators is high, excessive oil can accumulate and
The circulation per circuit is 33.3 mL/s. rapidly reduce efficiency.
Fig. 7 Charts for Determining Rate of Refrigerant Feed (No Flash Gas)
valves with horizontal valve spindles eliminates possible traps. Gas liquid lines (minimum sized) feeding low-pressure receivers so
binding is more likely with high evaporating pressures. that positive shutoff is automatically achieved with system shut-
Installing discharge check valves prevents backflow. Relief down. This prevents excessive refrigerant from collecting in low-
valves should be used, particularly for positive displacement pressure receivers, which can cause carryover at start-up.
pumps. Strainers are not usually installed in ammonia pump suction To prevent pumps from operating without liquid, low-level float
lines because they plug with oil. Strainers, although a poor substi- switches can be fitted on liquid legs. An alternative device, a differ-
tute for a clean installation, protect halocarbon pumps from damage ential pressure switch connected across pump discharge and suction
by dirt or pipe scale. connections, causes the pump to stop without interrupting liquid
Pump suction connections to liquid legs (vertical drop legs from flow. Cavitation can also cause this control to operate. When hand
low-pressure receivers) should be made above the bottom of the expansion valves are used to control the circulation rate to evapora-
legs to allow collection space for solids and sludge. Vortex elimina- tors, the orifice should be sized for operation between system high
tors should be considered, particularly when submersion of the suc- and low pressures. Occasionally, with reduced inlet pressure condi-
tion inlet is insufficient to prevent the intake of gas bubbles. tions, these valves can starve the circuit. Calibrated, manually
Lorentzen (1963, 1965) gives more complete information. adjusted regulators are available to meter the flow according to the
Sizing the pump suction line is important. The general velocity design conditions. An automatic flow-regulating valve specifically
should be about 0.9 m/s. Small lines cause restrictions; oversized for overfeed systems is available.
lines can cause bubble formation during evaporator temperature Liquid and suction solenoid valves must be selected for refriger-
decrease because of the heat capacity of the liquid and piping. Over- ant flow rates by mass or volume, not by refrigeration ratings from
sized lines also impose increased heat gain from the ambient spaces. capacity tables. Evaporator pressure regulators should be sized
Oil heaters for the seal lubrication system keep the oil fluid, partic- according to the manufacturer’s ratings for overfeed systems. The
ularly during operation below −20°C. Thermally insulating all cold manufacturer should be notified that valves being ordered are for
surfaces of pumps, lines, and receivers increases efficiency. overfeed application because slight modifications may be required.
When evaporator pressure regulators are used on overfeed systems
CONTROLS for controlling air defrosting of cooling units (particularly when fed
The liquid level in the low-pressure receiver can be controlled with very low temperature liquid), the refrigerant heat gain may be
by conventional devices such as low-pressure float valves, achieved by sensible effect, not by latent effect. In such cases, other
combinations of float switch and solenoid valve with manual reg- defrosting methods should be investigated. The possibility of con-
ulator, thermostatic level controls, electronic level sensors, or necting the units directly to high-pressure liquid should be consid-
other proven automatic devices. High-level float switches are ered, especially if the loads are minor.
useful in stopping compressors and/or operating alarms; they are When a check valve and a solenoid valve are paired on an over-
mandatory in some areas. Solenoid valves should be installed on feed system liquid line, the check valve should be downstream from
1.6 1998 ASHRAE Refrigeration Handbook (SI)
the solenoid valve. When the solenoid valve is closed, dangerous evaporators, dual suction risers eliminate static pressure penalties
hydraulic pressure can build up from the expansion of the trapped (Miller 1974, 1979).
liquid as it is heated. When evaporator pressure regulators are used, Distribution must be considered when a vertical refrigerant feed
the pressure of the entering liquid should be high enough to cause is used because of the static pressure variations in the feed and
flow into the evaporator. return header circuits. For example, for equal circuit loadings in a
Multicircuit systems must have a bypass relief valve in the horizontal airflow unit cooler, use of gradually smaller orifices for
pump discharge. The relief valve’s pressure should be set consider- the bottom feed circuits than for the upper circuits can compensate
ing the back pressure on the valve from the low-pressure receiver. for pressure differences.
For example, if the low-pressure receiver is set at 300 kPa and the When the top feed free-draining arrangement is used for air-cool-
maximum discharge pressure from the pump is 900 kPa, the relief ing units, liquid solenoid control valves can be used during the
valve should be set at 600 kPa. When some of the circuits are defrost cycle. This applies in particular to air, water, or electric
closed, the excess liquid is bypassed into the low-pressure receiver defrost units. Any liquid remaining in the coils rapidly evaporates or
rather than forced through the evaporators still in operation. This drains to the low-pressure receiver. Defrost is faster than in bottom
prevents higher evaporating temperatures from pressurizing evap- feed evaporators.
orators and reducing capacities of operating units. Where low-tem-
perature liquid feeds can be isolated manually or automatically, REFRIGERANT CHARGE
relief valves can be installed to prevent damage from excessive
hydraulic pressure. Overfeed systems need more refrigerant than dry expansion sys-
tems. Top feed arrangements have smaller charges than bottom feed
systems. The amount of charge depends on the evaporator volume,
EVAPORATOR DESIGN the circulating rate, the sizes of flow and return lines, the operating
Considerations temperature differences, and the heat transfer coefficients. Gener-
ally, top feed evaporators operate with the refrigerant charge occu-
There is an ideal refrigerant feed and flow system for each evap- pying about 25 to 40% of the evaporator volume. The refrigerant
orator design and arrangement. An evaporator designed for gravity- charge for the bottom feed arrangement occupies about 60 to 75% of
flooded operation cannot always be converted to an overfeed the evaporator volume with corresponding variations in the wet
arrangement, and vice versa, nor can systems always be designed to returns. Under certain no-load conditions in up-feed evaporators,
circulate the optimum flow rate. When top feed is used to ensure the charge may occupy 100% of the evaporator volume. In this case,
good distribution, a minimum quantity per circuit must be circu- the liquid surge volume from full-load to no-load condition must be
lated, generally about 30 mL/s. Distribution in bottom feed evapo- considered in sizing the low-pressure receiver (Miller 1971, 1974).
rators is less critical than in top or horizontal feed because each Evaporators with high heat transfer rates, such as flake ice mak-
circuit fills with liquid to equal the pressure loss in other parallel ers and scraped-surface heat exchangers, have small charges
circuits. because of small evaporator volumes. The amount of refrigerant in
Circuit length in evaporators is determined by allowable pres- the low side has a major effect on the size of the low-pressure
sure drop, load per circuit, tubing diameter, overfeed rate, type of receiver, especially in horizontal vessels. The cross-sectional area
refrigerant, and heat transfer coefficients. The most efficient circuit- for vapor flow in horizontal vessels is reduced with increasing liq-
ing is determined in most cases through laboratory tests conducted uid level. It is important to ascertain the evaporator refrigerant
by the evaporator manufacturers. Their recommendations should be charge with fluctuating loads for correct vessel design, particularly
followed when designing systems. for a low-pressure receiver that does not have a constant level con-
trol but is fed through a high-pressure control.
Top Feed Versus Bottom Feed
System design must determine whether evaporators are to be top START-UP AND OPERATION
fed or bottom fed, although both feed types can be installed in a sin-
All control devices should be checked prior to start-up. If
gle system. Each feed type has advantages; no best arrangement is
mechanical pumps are used, the direction of operation must be cor-
common to all systems.
rect. System evacuation and charging procedures are similar to
Advantages of top feed include those for other systems. The system must be operating under normal
• Smaller refrigerant charge conditions to determine the total required refrigerant charge. Liquid
• Possibly smaller low-pressure receiver height is established by liquid level indicators in the low-pressure
• Possible absence of static pressure penalty receivers.
• Better oil return Calibrated, manually operated regulators should be set for the
• Quicker, simpler defrost arrangements design conditions and adjusted for better performance when neces-
sary. When hand expansion valves are used, the system should be
For halocarbon systems with greater fluid densities, the refrigerant started by opening the valves about one-quarter to one-half turn.
charge, oil return, and static pressure are very important. When balancing is necessary, the regulators should be cut back on
Bottom feed is advantageous in that those circuits not starved of liquid to force the liquid through the
• Distribution considerations are less critical underfed circuits. The outlet temperature of the return line from
• Relative locations of evaporators and low-pressure receivers are each evaporator should be the same as the saturation temperature of
less important the main return line, allowing for pressure drops. Starved circuits
are indicated by temperatures higher than those for adequately fed
• System design and layout are simpler
circuits. Excessive feed to a circuit increases the evaporator temper-
The top feed system is limited by the relative location of com- ature because of excessive pressure drop.
ponents. Because this system sometimes requires more refrigerant The relief bypass from the liquid line to the low-pressure
circulation than bottom feed systems, it has greater pumping load, receiver should be adjusted and checked to ensure that it is function-
possibly larger feed and return lines, and increased line pressure ing. During operation, the pump manufacturer’s recommendations
drop penalties. In bottom feed evaporators, multiple headers with regarding lubrication and maintenance should be followed. Regular
individual inlets and outlets can be installed to reduce static pres- oil draining procedures should be established for ammonia systems;
sure penalties. For high lift of return overfeed lines from the a comparison should be made between the quantities of oil added to
Liquid Overfeed Systems 1.7
and drained from each system. This comparison determines whether LOW-PRESSURE RECEIVER SIZING
oil is accumulating in systems. Oil should not be drained in halocar-
Low-pressure receivers are also called liquid separators, suction
bon systems. Due to the miscibility of oil with halocarbons at high
traps, accumulators, liquid-vapor separators, flash-type coolers, gas
temperatures, it may be necessary to add oil to the system until an
and liquid coolers, surge drums, knock-out drums, slop tanks, or
operating balance is achieved (Stoecker 1960, Soling 1971).
low-side pressure vessels, depending on their function and the pref-
Operating Costs and Efficiency erence of the user.
The sizing of low-pressure receivers is determined by the
Operating costs for overfeed systems are generally lower than required liquid holdup volume and the allowable gas velocity. The
for other systems. Operating costs may not be lower in all cases due volume must accommodate the fluctuations of liquid in the evapo-
to the variety of inefficiencies that exist from system to system and rators and overfeed return lines as a result of load changes and
from plant to plant. However, in cases where existing dry expansion defrost periods. It must also handle the swelling and foaming of the
plants were converted to liquid overfeed, the operating hours, liquid charge in the receiver, which is caused by boiling during tem-
power, and maintenance costs were reduced. The efficiency of the perature increase or pressure reduction. At the same time, a liquid
early gas pump systems has been improved by using high-side pres- seal must be maintained on the supply line for continuous circula-
sure to circulate the overfeed liquid. This type of system is indicated tion devices. A separating space must be provided for gas velocity
in the controlled pressure system shown in Figure 4. Refinements of low enough to cause a minimum entrainment of liquid drops into the
the double pumper drum arrangement (shown in Figure 3) have also suction outlet. Space limitations and design requirements result in a
been developed. wide variety of configurations (Miller 1971; Stoecker 1960;
Gas-pumped systems, which use refrigerant gas to pump liquid Lorentzen 1966; Niemeyer 1961; Scheiman 1963, 1964; Sonders
to the evaporators or to the controlled-pressure receiver, require and Brown 1934; Younger 1955).
additional compressor volume, from which no useful refrigeration In selecting a gas-and-liquid separator, adequate volume for the
is obtained. These systems consume 4 to 10% or more of the com- liquid supply and a vapor space above the minimum liquid height
pressor power to maintain the refrigerant flow. for liquid surge must be provided. This requires an analysis of oper-
If the condensing pressure is reduced as much as 70 kPa, the ating load variations. This, in turn, determines the maximum oper-
compressor power per unit of refrigeration drops by about 7%. ating liquid level. Figures 8 and 9 identify these levels and the
Where outdoor dry- and wet-bulb conditions allow, a mechanical important parameters of vertical and horizontal gravity separators.
pump can be used to pump the gas with no effect on evaporator per- Vertical separators maintain the same separating area with
formance. Gas-operated systems must, however, maintain the con- level variations, while separating areas in horizontal separators
densing pressure within a much smaller range to pump the liquid change with level variations. Horizontal separators should have
and maintain the required overfeed rate. inlets and outlets separated horizontally by at least the vertical sep-
arating distance. A useful arrangement in horizontal separators dis-
LINE SIZING tributes the inlet flow into two or more connections to reduce
The liquid feed line to the evaporator and the wet return line to turbulence and horizontal velocity without reducing the residence
the low-pressure receiver cannot be sized by the method described time of the gas flow within the shell (Miller 1971).
in Chapter 33 of the 1997 ASHRAE Handbook—Fundamentals. In horizontal separators, as the horizontal separating distance is
Figure 7 can be used to size liquid feed lines. The circulating rate increased beyond the vertical separating distance, the residence
from Table 1 is multiplied by the evaporating rate. For example, an time of the vapor passing through is increased so that higher veloc-
evaporator with a circulating rate of 4 that forms vapor at a rate of ities than allowed in vertical separators can be tolerated. As the sep-
50 g/s needs a feed line sized for 4 × 50 = 200 g/s. arating distance is reduced, the amount of liquid entrainment from
Alternative methods that may be used to design wet returns gravity separators increases. Table 2 shows the gravity separation
include the following: velocities. For surging loads or pulsating flow associated with large
step changes in capacity, the maximum steady flow velocity should
1. Use one pipe size larger than calculated for vapor flow alone. be reduced to a value achieved by a suitable multiplier such as 0.75.
2. Use a velocity selected for dry expansion reduced by the factor The gas-and-liquid separator may be designed with baffles or
1 ⁄ Circulating Rate . This method suggests that the wet return eliminators to separate liquid from the suction gas returning from
velocity for a circulating rate of 4 is 1 ⁄ 4 = 0.5 or half that of the top of the shell to the compressor. More often, sufficient sepa-
the acceptable dry vapor velocity. ration space is allowed above the liquid level for this purpose. Such
3. Use the design method described by Chaddock et al. (1972). The a design is usually of the vertical type, with a separation height
report includes tables of flow capacities at 0.036 K drop per above the liquid level of from 600 to 900 mm. The shell diameter is
metre of horizontal lines for R-717 (ammonia), R-12, R-22, and sized to keep the suction gas velocity at a value low enough to allow
R-502. the liquid droplets to separate and not be entrained with the return-
When sizing refrigerant lines, the following design precautions ing suction gas off the top of the shell.
should be taken:
1. Carefully size overfeed return lines with vertical risers because
more liquid is held in risers than in horizontal pipe. This holdup
increases with reduced vapor flow and increases pressure loss
because of gravity and two-phase pressure drop.
2. Use double risers with halocarbons to maintain velocity at partial
loads and to reduce liquid static pressure loss (Miller 1979).
3. Add the equivalent of a 100% liquid static height penalty to the
pressure drop allowance to compensate for liquid holdup in
ammonia systems that have unavoidable vertical risers.
4. As alternatives in severe cases, provide traps and a means of
pumping liquids, or use dual-pipe risers.
5. Install low pressure drop valves so the stems are horizontal or
nearly so (Chisolm 1971). Fig. 8 Basic Horizontal Gas-and-Liquid Separator
1.8 1998 ASHRAE Refrigeration Handbook (SI)
Vertical
Maximum Steady Flow Velocity, m/s
Temp., Separation
°C Distance, mm R-717 R-22 R-12 R-502
+10 250 0.15 0.07 0.08 0.06
610 0.64 0.31 0.36 0.25
910 0.71 0.39 0.43 0.32
-7 250 0.21 0.10 0.11 0.08
610 0.87 0.44 0.49 0.35
910 0.99 0.52 0.58 0.42
-23 250 0.31 0.14 0.16 0.11
610 1.29 0.61 0.69 0.49
910 1.43 0.72 0.81 0.59
-40 250 0.48 0.21 0.24 0.17
610 1.99 0.88 1.01 0.71
910 2.17 1.04 1.17 0.84
-57 250 0.80 0.33 0.37 0.25
610 3.30 1.36 1.54 1.08
910 3.54 1.57 1.78 1.25
Source: Adapted from Miller (1971).
For the alternate location of C2, determine IDS from the follow-
ing equation:
1270Q 2
---------------- + C 2
C1 = inlet pipe diameter, OD, mm IDS = (2)
C2 = outlet pipe diameter, OD, mm V
SH = slot height = C1/4, mm The maximum liquid height in the separator is a function of the
SL = slot length = 3C1, mm type of system in which the separator is being used. In some systems
H1 = height of C1 above maximum liquid level, mm;
for pseudo D = 600 mm
this can be estimated, but in others, previous experience is the only
guide for selecting the proper liquid height. The accumulated liquid
H1 = 51 Q ⁄ V , mm (at D = 600 mm)
must be returned to the system by a suitable means at a rate compa-
Q = maximum gas flow in the shell at maximum sustained
operating conditions, L/s
rable to the rate at which it is being collected.
V = separation velocity, m/s With a horizontal separator, the vertical separation distance used
H2 = location of C1 from inside top of shell, mm is an average value. The top part of the horizontal shell restricts the
H2 = D + 0.5 × depth of curved portion of head or 50 mm gas flow so that the maximum vertical separation distance cannot be
D = vertical separation distance, mm actual used. If Ht represents the maximum vertical distance from the liquid
H3 = location of gas exit point for alternate location of C2 level to the inside top of the shell, the average separation distance as
measured from inside top of shell, mm a fraction of IDS is as follows:
H3 = 0.5 × depth of curved portion of shell or 50 mm,
whichever is greater
Ht /IDS D/IDS Ht /IDS D/IDS
IDS = internal diameter of shell = 1270 Q ⁄ V , mm
0.1 0.068 0.6 0.492
0.2 0.140 0.7 0.592
Fig. 9 Basic Vertical Gravity Gas-and-Liquid Separator 0.3 0.215 0.8 0.693
0.4 0.298 0.9 0.793
0.5 0.392 1.0 0.893
Although separators are made with length-to-diameter (L/D)
ratios of 1/1 increasing to 10/1, the least expensive separators usu- The suction connection(s) for refrigerant gas leaving the hori-
ally have L/D ratios between 3/1 and 5/1. Vertical separators are zontal shell must be located at or above the location established by
normally used for systems with reciprocating compressors. Hori- the average distance for separation. The maximum cross-flow
zontal separators may be preferable where vertical height is critical velocity of gas establishes the residence time for the gas and any
and/or where large volume space for liquid is required. The proce- entrained liquid droplets in the shell. The most effective removal of
dures for designing vertical and horizontal separators are different. entrainment occurs when the residence time is at a maximum prac-
A vertical gas-and-liquid separator is shown in Figure 9. The end tical value. Regardless of the number of gas outlet connections for
of the inlet pipe C1 is capped so that flow dispersion is directed uniform distribution of gas flow, the cross-sectional area of the gas
downward toward the liquid level. The suggested opening is four space is
times the transverse internal area of the pipe. The height H1 with a
120° dispersion of the flow reaches to approximately 70% of the 2000DQ
Ax = --------------------- (3)
internal diameter of the shell. VL
An alternate inlet pipe with a downturned elbow or mitered bend where
can be used. However, the jet effect of entering fluid must be con- Ax = minimum transverse net cross-sectional area or gas space, mm 2
sidered to avoid undue splashing. The outlet of the pipe must be a D = average vertical separation distance, mm
minimum distance of IDS/5 above the maximum liquid level in the Q = total quantity of gas leaving vessel, L/s
shell. H2 is measured from the outlet to the inside top of the shell. It L = inside length of shell, mm
equals D + 0.5 times the depth of the curved portion of the head. V = separation velocity for separation distance used, m/s
Liquid Overfeed Systems 1.9
For nonuniform distribution of gas flow in the horizontal shell, Lorentzen, G. and R. Gronnerud. 1967. On the design of recirculation type
determine the minimum horizontal distance for gas flow from point evaporators. Kulde 21(4):55.
of entry to point of exit as follows: Miller, D.K. 1971. Recent methods for sizing liquid overfeed piping and
suction accumulator-receivers. Proceedings I.I.R., Washington, D.C.
1000QD Miller D.K. 1974. Refrigeration problems of a VCM carrying tanker. ASH-
RTL = --------------------- (4) RAE Journal 11.
VA x
Miller, D.K. 1979. Sizing dual suction risers in liquid overfeed refrigeration
where systems. Chemical Engineering 9.
Niederer, D.H. 1964. Liquid recirculation systems—What rate of feed is rec-
RTL = residence time length, mm ommended. The Air Conditioning & Refrigeration Business (December).
Q = maximum flow for that portion of the shell, L/s Niemeyer, E.R. 1961. Check these points when designing knockout drums.
All connections must be sized for the flow rates and pressure drops Hydrocarbon Processing and Petroleum Refiner (June).
permissible and must be positioned to minimize liquid splashing. Scheiman, A.D. 1964. Horizontal vapor-liquid separators. Hydrocarbon
Processing and Petroleum Refiner (May).
Internal baffles or mist eliminators can reduce the diameter of ves-
Scheiman, A.D. 1963. Size vapor-liquid separators quicker by nomograph.
sels; however, test correlations are necessary for a given configura- Hydrocarbon Processing and Petroleum Refiner (October).
tion and placement of these devices. Scotland, W.B. 1963. Discharge temperature considerations with multicyl-
An alternate formula for determining separation velocities that inder ammonia compressors. Modern Refrigeration (February).
can be applied to separators is Scotland, W.B. 1970. Advantages, disadvantages and economics of liquid
overfeed systems. ASHRAE Symposium Bulletin KC-70-3, Liquid over-
ρl – ρv feed systems.
v = k ---------------- (5)
ρv Soling, S.P. 1971. Oil recovery from low temperature pump recirculating
hydrocarbon systems. ASHRAE Symposium Bulletin PH-71-2, Effect of
where oil on the refrigeration system.
Sonders, M. and G.G. Brown. 1934. Design of fractionating columns, en-
v = velocity of vapor, m/s trainment and capacity. Industrial & Engineering Chemistry (January).
ρl = density of liquid, kg/m3
Stoecker, W.F. 1960. How to design and operate flooded evaporators for
ρv = density of vapor, kg/m3
cooling air and liquids. Heating, Piping & Air Conditioning (December).
k = factor based on experience without regard to vertical separation
Younger, A.H. 1955. How to size future process vessels. Chemical Engi-
distance and surface tension for gravity separators
neering (May).
In gravity liquid/vapor separators that must separate heavy
entrainment from vapors, use a k of 0.03. This gives velocities BIBLIOGRAPHY
equivalent to those used for 300 to 350 mm vertical separation dis- Chaddock, J.B. 1976. Two-phase pressure drop in refrigerant liquid over-
tance for R-717 and 350 to 400 mm vertical separation distance for feed systems—Design tables. ASHRAE Transactions 82(2):107-33.
halocarbons. In knockout drums that separate light entrainment, use Chaddock, J.B., H. Lau, and E. Skuchas. 1976. Two-phase pressure drop in
a k of 0.06. This gives velocities equivalent to those used for 900 refrigerant liquid overfeed systems—Experimental measurements. ASH-
mm vertical separation distance for R-717 and for halocarbons. RAE Transactions 82(2):134-50.
Geltz, R.W. 1967. Pump overfeed evaporator refrigeration systems. Air
Conditioning, Heating & Refrigeration News (January 30, February 6,
REFERENCES March 6, March 13, March 20, March 27).
Chaddock, J.B., D.P. Werner, and C.G. Papachristou. 1972. Pressure drop in Lorentzen, G. and A.O. Baglo. 1969. An investigation of a gas pump recir-
the suction lines of refrigerant circulation systems. ASHRAE Transac- culation system. Proceedings of the Xth International Congress of
tions 78(2):114-23. Refrigeration, p. 215. International Institute of Refrigeration, Paris.
Chisholm, D. 1971. Prediction of pressure drop at pipe fittings during two- Richards, W.V. 1959. Liquid ammonia recirculation systems. Industrial
phase flow. Proceedings I.I.R., Washington, D.C. Refrigeration (June):139.
Lorentzen, G. 1963. Conditions of cavitation in liquid pumps for refrigerant Richards, W.V. 1970. Pumps and piping in liquid overfeed systems. ASH-
circulation. Progress Refrigeration Science Technology I:497. RAE Symposium Bulletin KC-70-3, Liquid overfeed systems.
Lorentzen, G. 1965. How to design piping for liquid recirculation. Heating, Slipcevic, B. 1964. The calculation of the refrigerant charge in refrigerating
Piping & Air Conditioning (June):139. systems with circulation pumps. Kältetechnik 4:111.
Lorentzen, G. 1966. On the dimensioning of liquid separators for refrigera- Thompson, R.B. 1970. Control of evaporators in liquid overfeed systems.
tion systems. Kältetechnik 18:89. ASHRAE Symposium Bulletin KC-70-3, Liquid overfeed systems.
Lorentzen, G. 1968. Evaporator design and liquid feed regulation. Journal Watkins, J.E. 1956. Improving refrigeration systems by applying established
of Refrigeration (November-December):160. principles. Industrial Refrigeration (June).