Protective Devices MV Panels Upto415v
Protective Devices MV Panels Upto415v
Protective Devices MV Panels Upto415v
________________________________________________________________________
Page 1
1 PROTECTIVE DEVICES
1.1 GENERAL
1.1.1 Scope
1 This Part shall specifies the requirements for protective devices.
1.1.3 Ratings
1 The ratings of the various overcurrent protective devices shall be, in general, as
indicated on the Project Drawings. However, the protective device ratings shall be
confirmed based on the equipment and items being provided by the Contractor.
Contractor shall provide calculation and justification for proposing any change in the
rating.
1.1.4 Standards
The following standards shall be complied with:
3 All overcurrent protective devices on this Project and the first upstream device of the
existing electrical system shall be co-ordinated so that they will perform as follows.
When two or more overcurrent protective devices (including the first upstream protective
device of the existing system) in series with each other experience current flow greater
than their rated current, the device with the lowest rated current shall trip and/or open
the circuit first and thereby prevent the higher rated devices from operating.
4 The Supplier of the overcurrent protective devices shall prepare a co-ordination study to
verify the above stated performance requirements. The study shall be documented by
the Supplier and the documents shall include but not be limited to the following:
a. a composite drawing or drawings (on full size, reproducible, log-log
paper) showing the entire new electrical system (including the first
upstream protective device of the existing system) showing all protective
device curves (including motor overloads), short circuit duties, motor
starting curves and damage curves for motors, equipment and
conductors. This drawing or drawings shall show that all protective
devices are properly co-ordinated to perform as stated above
b. manufacturer’s overcurrent operating curves (on full size, reproducible,
log-log paper) for each overcurrent device. In the case of fuses, both
minimum melt and maximum clearing time curves shall be included
c. reproducible copies of all Project single line diagrams so marked to show
short circuit duties at all switchboards and motor control centres, and
which operating curve applies to each overcurrent device on the diagram
(the operating curves shall also be correspondingly marked)
d. a tabulation of the short circuit duties at all switchboards and motor
control centres, sizes and ratings of all overcurrent protective devices
and the required settings of all of the adjustable overcurrent protective
devices so that the performance requirements are met. Protective
devices which have earth fault protection features are specifically
required to meet this performance requirement.
e. Breaker selection will be done for service breaking capacity (Ics) for
values indicated in drawings / specification.
5 This documented co-ordination study shall be submitted for review before the
overcurrent devices are supplied for the Project.
Siemens
Schneider Electric
Cutler Hammer
All major components (namely ACBs, MCCBs, MCBs etc) will be from one of the approved
supplier only for co-ordination and discrimination between upstream and downstream
products.
1.2 PRODUCTS
________________________________________________________________________
________________________________________________________________________
Page 3
shall be 500 V, 50 Hz, triple pole with neutral link for incoming and outgoing ACB or four
poles for bus tie ACB only with ratings as shown on the Drawings. They shall be air
break, trip free, draw-out type with mechanical and electrical ON/OFF indicators.
3 Where air circuit breakers are to be electrically operated by automatic motor wound
spring mechanism, a standby manual operating handle shall be provided for operating
the circuit breaker in case of power or motor failure.
4 The air circuit breaker shall be provided with over current, short circuit and earth fault
protection having the following characteristics:
a. adjustable long time delay current setting (40 % - 100 %) with varied
tripping time
b. adjustable short time delay current setting (1.5 to 10 times) with variable
tripping time
c. instantaneous tripping for heavier over current adjustable from 2 to 15
times of base current
d. adjustable earth fault trip current setting (20 % - 60 %) with variable
tripping time, if shown in the drawing.
5 The circuit breaker shall have three position on the draw-out mechanism, namely
service position where all main and auxiliary contacts are made, test position where
main contacts are open but auxiliary contacts are closed and isolated position where all
contacts are open. An indicator shall clearly show these positions and provisions shall
be made for locking the breakers in any position. ON/OFF indicator shall be provided.
6 Mechanical Interlocks shall be provided to prevent withdrawing or inserting of the
breaker when it is ‘ON’. Any attempt to do so shall trip the breaker automatically.
7 The withdrawable part of the circuit breaker shall be effectively connected to earth
through scraping contacts that shall make before and break after the main and auxiliary
contacts.
8 The moving contacts comprising the main and arcing contacts shall be of the spring
loaded, self aligning type. The arc contacts shall be arranged to make before and break
after the main contacts.
9 Each ACB shall be included but not limited with following components and accessories:
a. auxiliary Contacts
b. arc Chutes
c. folding Extension Rail
d. charging Handle
e. open and Close Push-buttons
f. over Current Trip Indicator
g. key lock on Trip Button
h. Spring Charge Condition Indicator
i. breaker Position Indicator
j. making Current Release
k. automatic Shutters for the B/B Terminal
l. carriage for every size of ACB exceeding 25 KG in Weight
m. operation Counter
n. shunt trip mechanism.
10 ACB’s shall be provided with solid state type microprocessor based over current & earth
fault relays with integral LCD display, which shall use digital programming techniques
for highest protection accuracy and be integrated as part of the circuit breaker. The
current transformers / sensors and the wiring shall be integrated within the case and
shall be self powered. The current sensors shall be located within the case of the circuit
breaker. The over current relay shall have a wide adjustment range to allow flexibility of
setting on site. The trip unit shall measure the true RMS value of any wave form of
current. The control unit shall be equipped with a push to reset mechanical indicator, for
anti-pumping function.
________________________________________________________________________
________________________________________________________________________
Page 4
Where indicated in the drawings, the trip unit shall be equipped with an earth fault
option.
All trip units for ACBs will have integral LCD display which will measure current, voltage
parameters. As a minimum the following parameters will be displayed on the integral
display unit:
Energy, Real Power, Apparent Power, Demand Power
Current for all three phases
Voltage
Power Factor
The integral LCD display will also contain Maintenance Indicators (contact wear,
Operation cycles etc) including last ten trips and alarms.
As an option, communication option will be provided which will read and set protection
parameters remotely, transmit all calculated indicators and measurements remotely
through Modbus protocol.
11 The Main Incoming Circuit Breakers shall be provided with cable terminal boxes to suit
the incoming cables from the transformer/source supply.
12 Circuit breakers shall be tropicalised to operate continuously in an ambient temperature
of 55 °C and high relative humidity.
13 Type test certificate for each size of circuit breakers and MCCB from an internationally
recognised testing authority acceptable to the Engineer shall be provided.
________________________________________________________________________
________________________________________________________________________
Page 5
9 Breakers with earth leakage relay protection shall be provided with shunt trips.
10 Frame sizes shall be as per manufacturer’s standard size and as approved by the
Engineer, however minimum frame size will be 200A for standardisation.
11 For breakers up to and equal to 250 Amps equipped with thermal trip units
Adjustable (from 80% to 100% of the current rating) thermal protection.
Fixed magnetic protection for current ratings up to 200 A
Adjustable (from 5 to 10 times the current rating) for current ratings greater
than 200 A. It shall be possible to ensure neutral protection. The tripping
threshold shall be equal to that of the phases, or to a reduced value (generally
half of that of the phases).
For breakers above 250 Amps equipped with electronic trip unit.
long time protection (LT)
Selectable Ir threshold with fourty-eight settings from 40 to 100% of the trip
unit rating.
short time protection (ST)
– Im threshold shall be adjustable from 2 to 10 times the thermal setting Ir.
– the time delay shall be fixed at 40 ms.
instantaneous protection
the threshold shall be fixed (between 12 and 19 times In, depending on the
rating)
For MCCBs above 250A, a thermal memory (in the event of repeated overloads, the
electronic trip units shall optimize protection of cables and downstream devices by
memorizing temperature variations). A load monitoring function shall be an integral part
of the electronic trip units indicating four loads levels (60%, 75%, 90% and 105%) by
LED's (with flashing LED for 105%). It shall be possible to install with the electronic trip
unit, a high threshold earth fault protection, a load monitoring remote indication or a set
of four fault indicating LED's in front to indicate the cause of tripping.
1.2.4 MCB/ELCB
1 Combined MCB/ELCB units shall be provided for final circuits supplying socket outlets,
water heaters and water pumps.
2 The units shall have a trip sensitivity of 30 mA.
________________________________________________________________________
________________________________________________________________________
Page 6
generally comply with IEC 61008 and the recommended specification CEE 227 of the
IEC on Rules for the approval of electrical equipment.
3 The breaker shall consist of a core balance transformer, a tripping coil with contact
assembly, main supply contacts, ON/OFF switch, a test button and a trip free
mechanism all enclosed in a robust body of all insulated material.
4 Degree of Protection against earth leakage throughout the electrical installation shall be
as indicated on the Drawings. Unless otherwise indicated, ELCB shall have 30 mA trip
settings.
5 The breaker protecting lighting and or power circuits shall be mounted in the panel
board enclosure.
2 Solid-state electronic protection relays shall be used for motors rated above 11 kW,
having the following protection features:
a. overload
b. overcurrent
c. single phase
d. earth fault
e. under-voltage
f. over-voltage
i. digital indication for above values
3. Documentary evidence must be produced showing the current/time characteristic of each
overload at its setting (hot/cold for the thermal overload) overlaid on the motor
manufacturers thermal stability time/current characteristic for comparison.
Consideration must be given as to the requested method of starting (DOL, star delta,
etc.).
1.2.7 Fuses
1 Fuses shall be the High Breaking Capacity (HBC) type to BS 88.
2 The fuse shall either include a suitable fuse carrier or it shall be capable of isolation. If
the fuse carrier is included it shall be such that when it is being withdrawn normally or
when it is completely withdrawn the operator is completely protected from accidental
contact with any live metal of its fuse link fuse contacts and fixed contacts.
3 If the fuse is capable of isolation it shall be so interlocked with the switch that isolation is
complete before the fuse enclosure can be opened further. The switch shall be
prevented from closing while the fuse-cover is open.
________________________________________________________________________
________________________________________________________________________
Page 7
b. fuses: to BS 88 bolted type, class Q1, 415 V and switches certified for AC-23A
duty, unless specified otherwise in the Project Documentation, rating as
indicated in the Project Documentation,
c. fused switch carriages: withdrawable type
d. fuse switches: ASTA certified to 50 kA, or as otherwise indicated on the
drawings.
________________________________________________________________________
________________________________________________________________________
Page 8
END OF PART
________________________________________________________________________