MET 465 - Building Systems Heat Load Calculations Example - Fall 2009

This document provides an example of heat load calculations for four zones in a building. It includes tables with information on the sensible and latent loads for each zone, broken down by components such as the roof, walls, windows, infiltration, and ventilation. The total sensible and latent loads are provided for each zone and the entire building. Heat transfer coefficients and other building parameters are also included to calculate the individual component loads.

Uploaded by

Aditya Suardi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views5 pages

MET 465 - Building Systems Heat Load Calculations Example - Fall 2009

This document provides an example of heat load calculations for four zones in a building. It includes tables with information on the sensible and latent loads for each zone, broken down by components such as the roof, walls, windows, infiltration, and ventilation. The total sensible and latent loads are provided for each zone and the entire building. Heat transfer coefficients and other building parameters are also included to calculate the individual component loads.

Uploaded by

Aditya Suardi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

MET 465 - Building Systems

Heat Load Calculations Example - Fall 2009

Room Sensible Load Latent Load Total Load


Zone (BTU/hr) (BTU/hr) (BTU/hr)

1 1 21213 1613 22826 Zone 1 Total

2 2 21993 1833 23826


3 21250 1833 23082
43243 3665 46908 Zone 2 Total

3 4 21993 1833 23826 Zone 3 Total

4 conf 58954 10662 69617


hall 12289 0 12289
71243 10662 81906 Zone 4 Total

157692 17773 175465 Building Total


MET 465 - Building Systems
Heat Load Calculations - Example - Fall 2009

Heating Load Calculations - Zone 1

U (BTU/hr sqft F) A (sqft) TD (F) Q (BTU/hr) Zone Totals Sensible Latent


Room 1 (BTU/hr) (BTU/hr)
Roof 0.112 484 82 4445 Roof 4445
Walls 3569
Walls N 0.128 170 82 1784 Doors 0
E 0.128 170 82 1784 Windows 4756
S 0.128 0 82 0 Floor 2846
W 0.128 0 82 0 Slab Edge 1082
3569 Infiltration 4515 1613
Doors N 0.47 0 82 0 Ventilation 2985 1066
E 0.47 0 82 0
S 0.47 0 82 0 Total for Zone = 21213 1613 22826 (BTU/hr)
W 0.47 0 82 0
0
Windows N 0.58 50 82 2378 Room ACH = 0.75
E 0.58 50 82 2378 Length Width Height
S 0.58 0 82 0 Room Dims. 22 22 10
W 0.58 0 82 0
4756 Infiltration cfm = 60.5
U (BTU/hr sqft F) Perim/Area TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 441 1764 Occupancy = 2
Slab 0.3 44 82 1082
2846

Cond. Loss 15616

Infiltration cfm Constant TD / GD Q (BTU/hr)


sensible 61 0.91 82 4515
latent 61 0.68 39.2 1613

Ventilation cfm Constant TD / GD Q (BTU/hr)


sensible 40 0.91 82 2985
latent 40 0.68 39.2 1066
MET 465 - Building Systems
Heat Load Calculations - Example - Fall 2009

Heating Load Calculations - Zone 2

U (BTU/hr sqft F) A (sqft) TD (F) Q (BTU/hr) Zone Totals Sensible Latent


Room 2 (BTU/hr) (BTU/hr)
Roof 0.112 550 82 5051 Roof 10102
Walls 5983
Walls N 0.128 0 82 0 Doors 0
E 0.128 170 82 1784 Windows 7134
S 0.128 200 82 2099 Floor 7992
W 0.128 0 82 0 Slab Edge 1771
3884 Infiltration 10260 3665
Doors N 0.47 0 82 0 Ventilation 5970 2132
E 0.47 0 82 0
S 0.47 0 82 0 Total for Zone = 43243 3665 46908 (BTU/hr)
W 0.47 0 82 0
0
Windows N 0.58 0 82 0 Room ACH = 0.75
E 0.58 50 82 2378 Length Width Height
S 0.58 50 82 2378 Room Dims. 25 22 10
W 0.58 0 82 0
4756 Infiltration cfm = 68.75
U (BTU/hr sqft F) Perim/Area TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 504 2016 Occupancy = 2
Slab 0.3 47 82 1156
3172

Cond. Loss 16863

Infiltration cfm Constant TD / GD Q (BTU/hr)


sensible 69 0.91 82 5130 Room Load 21993 Sensible
latent 69 0.68 39.2 1833 1833 Latent

Ventilation cfm Constant TD / GD Q (BTU/hr)


sensible 40 0.91 82 2985
latent 40 0.68 39.2 1066

U (BTU/hr sqft F) A (sqft) TD (F) Q (BTU/hr)


Room 3
Roof 0.112 550 82 5051

Walls N 0.128 0 82 0
E 0.128 0 82 0
S 0.128 200 82 2099
W 0.128 0 82 0
2099
Doors N 0.47 0 82 0
E 0.47 0 82 0
S 0.47 0 82 0
W 0.47 0 82 0
0
Windows N 0.58 0 82 0 Room ACH = 0.75
E 0.58 0 82 0 Length Width Height
S 0.58 50 82 2378 Room Dims. 25 22 10
W 0.58 0 82 0
2378 Infiltration cfm = 68.75
U (BTU/hr sqft F) Perim/Area TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 1494 5976 Occupancy = 2
Slab 0.3 25 82 615
6591

Cond. Loss 16119

Infiltration cfm Constant TD / GD Q (BTU/hr)


sensible 69 0.91 82 5130 Room Load 21250 Sensible
latent 69 0.68 39.2 1833 1833 Latent

Ventilation cfm Constant TD / GD Q (BTU/hr)


sensible 40 0.91 82 2985
latent 40 0.68 39.2 1066
MET 465 - Building Systems
Heat Load Calculations - Example - Fall 2009

Heating Load Calculations - Zone 3

U (BTU/hr sqft F)
A (sqft) TD (F) Q (BTU/hr) Zone Totals Sensible Latent
Room 4 (BTU/hr) (BTU/hr)
Roof 0.112 550 82 5051 Roof 5051
Walls 3884
Walls N 0.128 0 82 0 Doors 0
E 0.128 0 82 0 Windows 4756
S 0.128 200 82 2099 Floor 2016
W 0.128 170 82 1784 Slab Edge 1156
3884 Infiltration 5130 1833
Doors N 0.47 0 82 0 Ventilation 2985 1066
E 0.47 0 82 0
S 0.47 0 82 0 Total for Zone = 21993 1833 23826 (BTU/hr)
W 0.47 0 82 0
0
Windows N 0.58 0 82 0 Room ACH = 0.75
E 0.58 0 82 0 Length Width Height
S 0.58 50 82 2378 Room Dims. 25 22 10
W 0.58 50 82 2378
4756 Infiltration cfm = 68.75
U (BTU/hr sqftPerim/Area
F) TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 504 2016 Occupancy = 2
Slab 0.3 47 82 1156
3172

Cond. Los 16863

Infiltration cfm Constant TD / GD Q (BTU/hr)


sensible 69 0.91 82 5130
latent 69 0.68 39.2 1833

Ventilation cfm Constant TD / GD Q (BTU/hr)


sensible 40 0.91 82 2985
latent 40 0.68 39.2 1066
MET 465 - Building Systems
Heat Load Calculations - Example - Fall 2009

Heating Load Calculations - Zone 4

U (BTU/hr sqft F) A (sqft) TD (F) Q (BTU/hr) Zone Totals Sensible Latent


conference room (BTU/hr) (BTU/hr)
Roof 0.112 1100 82 10102 Roof 15447
Walls 6990
Walls N 0.128 400 82 4198 Doors 3237
E 0.128 0 82 0 Windows 7134
S 0.128 0 82 0 Floor 6372
W 0.128 170 82 1784 Slab Edge 2214
5983 Infiltration 13059 4665
Doors N 0.47 0 82 0 Ventilation 29848 10662
E 0.47 0 82 0
S 0.47 0 82 0 Total for Zone = 71243 10662 81906 (BTU/hr)
W 0.47 0 82 0
0
Windows N 0.58 100 82 4756 Room ACH = 0.75
E 0.58 0 82 0 Length Width Height
S 0.58 0 82 0 Room Dims. 50 22 10
W 0.58 50 82 2378
7134 Infiltration cfm = 137.5
U (BTU/hr sqft F) Perim/Area TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 1029 4116 Occupancy = 20
Slab 0.3 72 82 1771
5887

Cond. Loss 29106

Infiltration cfm Constant TD / GD Q (BTU/hr)


sensible 138 0.91 82 10260
latent 138 0.68 39.2 3665

Ventilation cfm Constant TD / GD Q (BTU/hr)


sensible 400 0.91 82 29848 Room Load 58954 Sensible
latent 400 0.68 39.2 10662 10662 Latent

U (BTU/hr sqft F) A (sqft) TD (F) Q (BTU/hr)


Hallway
Roof 0.112 582 82 5345

Walls N 0.128 18 82 189


E 0.128 18 82 189
S 0.128 0 82 0
W 0.128 60 82 630
1008
Doors N 0.47 42 82 1619
E 0.47 42 82 1619
S 0.47 0 82 0
W 0.47 0 82 0
3237
Windows N 0.58 0 82 0 Room ACH = 0.75
E 0.58 0 82 0 Length Width Height
S 0.58 0 82 0 Room Dims. 50 6 10
W 0.58 0 82 0
0 Infiltration cfm = 37.5
U (BTU/hr sqft F) Perim/Area TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 564 2256 Occupancy = 0
Slab 0.3 18 82 443
2699

Cond. Loss 12289

Infiltration cfm Constant TD / GD Q (BTU/hr)


sensible 38 0.91 82 2798 Room Load 12289 Sensible
latent 38 0.68 39.2 1000 0 Latent

Ventilation cfm Constant TD / GD Q (BTU/hr)


sensible 0 0.91 82 0
latent 0 0.68 39.2 0