MET 465 - Building Systems Heat Load Calculations Example - Fall 2009
MET 465 - Building Systems Heat Load Calculations Example - Fall 2009
Walls N 0.128 0 82 0
E 0.128 0 82 0
S 0.128 200 82 2099
W 0.128 0 82 0
2099
Doors N 0.47 0 82 0
E 0.47 0 82 0
S 0.47 0 82 0
W 0.47 0 82 0
0
Windows N 0.58 0 82 0 Room ACH = 0.75
E 0.58 0 82 0 Length Width Height
S 0.58 50 82 2378 Room Dims. 25 22 10
W 0.58 0 82 0
2378 Infiltration cfm = 68.75
U (BTU/hr sqft F) Perim/Area TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 1494 5976 Occupancy = 2
Slab 0.3 25 82 615
6591
U (BTU/hr sqft F)
A (sqft) TD (F) Q (BTU/hr) Zone Totals Sensible Latent
Room 4 (BTU/hr) (BTU/hr)
Roof 0.112 550 82 5051 Roof 5051
Walls 3884
Walls N 0.128 0 82 0 Doors 0
E 0.128 0 82 0 Windows 4756
S 0.128 200 82 2099 Floor 2016
W 0.128 170 82 1784 Slab Edge 1156
3884 Infiltration 5130 1833
Doors N 0.47 0 82 0 Ventilation 2985 1066
E 0.47 0 82 0
S 0.47 0 82 0 Total for Zone = 21993 1833 23826 (BTU/hr)
W 0.47 0 82 0
0
Windows N 0.58 0 82 0 Room ACH = 0.75
E 0.58 0 82 0 Length Width Height
S 0.58 50 82 2378 Room Dims. 25 22 10
W 0.58 50 82 2378
4756 Infiltration cfm = 68.75
U (BTU/hr sqftPerim/Area
F) TD (F) Q (BTU/hr)
Office cfm rate = 20 cfm / person
Floor 4 504 2016 Occupancy = 2
Slab 0.3 47 82 1156
3172