NTPC DRG. No.

: 0260-101-01-TR-PVM-U-027
JOB NO:
STATUS: CONTRACT
DISTRIBUTION NTPC TAMILNADU ENERGY COMPANY LTD
VALLUR THERMAL POWER PROJECT
2 x 500 MW
STEAM GENERATOR WITH ESP PACKGE
TO Dept Name Sign Date
No. BHARAT HEAVY ELECTRICALS LTD. Code
DRN
of UNIT : HIGH PRESSURE BOILER
Rev Date ALTD CHD APPD PLANT DESN JLJ/AVR 25.02.11
TIRUCHIRAPPALLI – 620 014 CHD MA 25.02.11
APPD MA/SCS 25.02.11
TITLE
SCAPH SELECTION & SIZING CALCULATION / DATA
DEPT. SCALE DRAWING NO.
SIGN.
DATE. SHEET 1 OF 2 REV 00 Signature
CAUTION: THIS DRAWING IS THE PROPERTY OF BHARAT HEAVY ELECTRICALS LTD., AND IS NOT TO BE REPRODUCED OR USED TO FURNISH ANY Not Verified
INFORMATION FOR MAKING OF DRAWINGS OR APPARATUS EXCEPT WHERE PROVIDE FOR AGREEMENT WITH SAID COMPANY.

Digitally signed by G
K Halder
Date: 2011.03.10
14:51:09 IST
Reason: CAT IVR
Location: NTPCEOC
SCAPH SELECTION DATA

Steam parameter at Auxiliary steam header:

a) Steam pressure kg /cm2(a) : 16

b) Steam temperature °C : 210

Secondary SCAPH Primary SCAPH


DESCPITION Unit Best Coal Oil Firing Worst Coal
30% 30% 30%
BMCR BMCR
BMCR BMCR BMCR
Total air flow t/h 1324 368 660 945 425

Air flow / SCAPH t/h 662 184 330 473 213

Air temperature entering °C 6 6 6 6 6

Air temperature leaving °C 27 100 86 27 100

Draft loss mmwc 50 - - 50 -

Location Bypass Duct Bypass Duct

No. of SCAPH /boiler. TWO (2) TWO (2)

PROJECT : NTECL / VALLUR TPP – 2 x 500 MW


Engineer JLJ/AVR TITLE: SCAPH SIZING DATA
Rev. with MA/SCS NTPC DWG : 0260-101-01-TR-PVM-U-027
Approved by MA/SCS Sheet : 2 of 2 Rev.00