RPC Manual (English)
RPC Manual (English)
RPC Manual (English)
MODEL : RPC-07-A
(2011. JULY)
Table of Contents
1. CHECKPOINTS PRIOR TO USE & NOTICE FOR WIRING
2. SYNOPSIS
3. STANDARD SPECIFICATIONS
4. MAIN FUNCTIONS & HOW TO USE
1) INPUT SIGNAL SELECTION
2) INPUT SIGNAL SET-UP & CHANGE (CH1)
3) SIGNAL FAIL SAFE POSITION
4) DELAY TIME (Motor Recess Time Set-Up when running in reverse direction)
5) DEAD BAND (Tolerance Set-Up)
6) HOW TO MANUALLY OPERATE WITH BUTTONS
7) A-FULL (Functions) SET-UP
8) AUTO SETTING (A-SCAN)
9) MANUAL SET-UP (CH2)
10) ADJUSTMENT OF OUTPUT
11) REV: How-To-Use when Actuator and Valve/Damper are in opposite direction
12) HOW TO CHECK LED STATUS
5. TOOLS REQUIRED
6. POTENTIOMETER SET-UP
7. LIMIT SWITCH SET-UP
8. HOW TO CHECK RPC OPERATION
9. RPC LAY-OUT
10. LCD LAY-OUT (Optional)
11. HOW TO REPLACE RPC
12. ELECTRICITY WIRING DIAGRAM
1) ITQ0080-70500-F (1PH)
2) ITQ0100-70500-F (1PH)
3) ITQ0160-70500-F (1PH)
4) ITQ0160-80500-F (3PH)
5) ITQ0160-84500-F (1PH / MCC : Built-In)
6) ITQ0160-90500-F (24V DC)
7) ITQ0160-96500-F (DC 24V/MCC built in)
8) ICMQ0160-81500-F (3PH / INTEGRAL / DISPLAY : LED / MCC built in)
9) ICMQ0160-82500-F (3PH / INTEGRAL / DISPLAY : LCD / MCC built in)
2. SYNOPSIS
As RPC (Remote Position Controller) is a controller dedicated for ratio-control system, it is
possible to provide Open/Close contact for forward/backward rotation comparing current
position value of the equipment and input signal since 12-bit A/D converter and 8-bit
microprocessor are used. Also, it shows/outputs current position value with the current values
3. STANDARD SPECIFICATIONS
1) Model : RPC-07-A
2) Power : 1Ph, 85~265VAC, 50/60Hz, Free Voltage (Option : AC/DC 24V)
3) Input Signal : 4-20mA DC / 1-5V DC / 2-10V DC / 0-5V DC / 0-10V DC
4) Input Resistance : 250Ω
5) Feed Back Potentiometer : 1KΩ
6) Output Signal : 4-20mA DC (SOURCE TYPE)
7) Load Resistance : Max. 750 Ω
8) Number of Output Contact : 2EA (Open Relay & Close Relay)
9) Motor Recess Time when running reverse direction (Delay Time)
1.0~8.5sec (0.5sec/1step, 0~15 Step)
10) Tolerance (Dead Band) : 0.1~4.5% (0.3%/1step, 0~15 Step)
11) Position Conversion Accuracy : ±0.5% ~ ±1.5% (might depend on circumstance)
12) Signal Fail Safe : Close / Open / Stop
13) Resolution : Min 1/1000
14) Ambient Temperature : -10℃~60℃ (Surface of RPC board)
15) Ambient Humidity : 90% RH Max (Non-Condensing)
16) Dielectric Strength Test : 1800VAC, 1Second (Input to Output, Power to GND)
17) Insulation Resistance : 500VDC more than 100MΩ
18) Vibration & Shock Test : (Axis: X, Y, Z) 10g (6g based on RMF), Frequencies: 0.2~34Hz,
less than 180min.
1 2 3
0~10V DC OFF ON ON
ZERO SPAN
those LED FAULT, CLOSE, and OPEN blink twice, then please put the hand off the
“SPAN” button.
f. Once input signal setup completed, please confirm if POWER (White) LED light is
„ON‟ after getting the „CH1 Dip Switch‟ off for sure.
g. Please enter input signal and check out if it is normally operated.
C. Change input signal into different kind (e.g. From 4~20mA DC to 0~10V DC)
a. Input Signal Selection is OFF-ON-ON (0~10V DC)
b. After put the CH1 Dip Switch “ON”, please check if the POWER LED (White) light
goes in and out.
c. Input „Close‟ value (0V DC), and please press “ZERO (Blank)” button until those
LED such as FAULT (Yellow), CLOSE (green), and OPEN (Red) blink twice, then
please put the hand off the “ZERO” button.
d. Input „Open‟ value (10V DC), and press “SPAN (Gray)” button until those LED
FAULT, CLOSE, and OPEN blink twice, then please put the hand off the “SPAN”
button.
e. Once input signal setup completed, please confirm if POWER (White) LED light is
„ON‟ after getting the „CH1 Dip Switch‟ off for sure.
f. Please enter input signal and check out if it is normally operated.
g. When you want to change Input signals (e.g. 2~10VDC, 1~5VDC, 0~5VDC),
please select “Input Signal Selection” switch for right signal, and do “b.”~”f.”
h. When Input signal select is 0~5V DC or 0 ~ 10V DC, RPC card doesn't supply A-
Full Function.
3) SIGNAL FAIL SAFE POSITION
A. Fail Close : Full Close to be operated when Signal
Fail / F-C On & F-O OFF
B. Fail Open : Full Open to be operated when Signal
Fail / F-C OFF & F-O On
C. Fail Stop : Stop when Signal Fail / both of F-C & F-
O should be all OFF or all ON
D. Factory set-up is „Fail Stop‟ (all OFF)
E. Exception : when input signal select is 0~5V or 0 ~10V, RPC card does not supply
Signal Fail Safe Position.
4) DELAY TIME (Motor Recess Time Set-Up when running in reverse
direction)
A. It is possible to set up the recess time of the motor when the
actuator is to move „forward to backward‟ (and vice versa) for
intended position since input signal is changed.
B. The range is „from 0 to F‟ which means 1.0sec to 8.5sec as 1
CLOSE
OPEN
A. It is possible to set up tolerance range for the actuator position according to input
signal.
B. The range is „from 0 to F‟ which means 0.1% to 4.5%: set-up levels are 15 levels in
total.
C. The lower level (closer to 0) means that there will be more possibilities for the
actuator not to be stopped for the intended position and „Hunting‟ may occur.
D. If „Hunting‟ continuously occurs, it may cause malfunction of Motor, RPC Card,
Potentiometer, Valve/Damper, and so on.
E. Factory set-up is “4 (1.3%)”.
6) HOW TO MANUALLY OPERATE WITH BUTTONS
A. Please simultaneously press the buttons „ZERO
ZERO SPAN
(Black)‟ and „SPAN (Gray)‟ at the same time.
B. If FAULT (Yellow) LED light is ON after those
LED lights such as FAULT (Yellow), CLOSE
(Green), and OPEN (Red) blink twice, please
put the hand off the buttons.
C. If ZERO (Black) button is pressed, those LED lights such as FAULT (Yellow), CLOSE
(Green), and OPEN (Red) blink twice and then it is operated for CLOSE direction with
CLOSE (Green) LED light ON. However, it is operated only for the time while the
button „ZERO (Black)‟ is pressed.
D. If SPAN (Gray) button is pressed, those LED lights such as FAULT (Yellow), CLOSE
(Green), and OPEN (Red) blink twice and then it is operated for OPEN direction with
OPEN (Red) LED light ON. However, it is operated only for the time while the button
„SPAN (Gray)‟ is pressed.
E. If those buttons “ZERO (Black)” and “SPAN (Gray)” are pressed again at the same
time, , those LED lights such as FAULT (Yellow), CLOSE (Green), and OPEN (Red) blink
twice and then it is set back to „stand-by‟ for further operation.
F. Or it just passes about 15 seconds without pressing those buttons “ZERO (Black)”
and “SPAN (Gray)”, then it is set back to „stand-by‟ for further operation.
7) A-FULL (Functions) SET-UP
A. If the signal of 4.3mA(2%) or lower is given, it is
“Full Close”. If the signal of 19.7mA(98%) or higher
is given, it is “Full Open”.
B. When Input signal select is 0~5V DC or 0 ~ 10V DC,
RPC card doesn't supply A-Full Function.
C. Factory set-up is “On”.
8) AUTO SETTING (A-SCAN)
A. Please press the button “A-SCAN (Red)”. A-SCAN
B. If FAULT (Yellow) LED light is ON after those LED lights such as
FAULT (Yellow), CLOSE (Green), and OPEN (Red) blink twice,
please put the hand off the button “A-SCAN”.
C. The actuator is automatically operated for Full Close and Full
Open and measures the range.
D. Please check out if “OPEN (Red)” LED blinks when OPEN is operated and/or “CLOSE
(Green)” LED blinks when CLOSE is operated.
E. Once Auto-Setting completed, it returns to „stand-by‟ after those LED lights such as
FAULT (Yellow), CLOSE (Green), and OPEN (Red) blink twice.
F. Please give input signal and check out if it is normally operated.
G. If running Auto Setting, it will delete those values currently saved and it will save
new values, so please be noticed.
H. Please run only once for initial installation, Limit Switch CAM adjustment,
Potentiometer replacement, and/or RPC replacement.
LED SIGNAL
White On Power On
5. TOOLS REQUIRED
1) Wrench (mm) : 1set
2) Screw Driver (-) : 1ea
3) Monkey Spanner 200mm : 1set
4) Signal Generator (0~20mA DC or 0~10V DC) : 1set
5) Multi-Tester : 1set
6) Measuring Instrument for output signal confirmation (0~25mA) : 1set
6. POTENTIOMETER SET-UP
1) ITQ0080~ITQ3000
A. Please get the actuator „Full Close‟.
B. Using measuring instrument such as DMM (Digital Multi Meter), please confirm if the
resistance value between P1 (Orange) and P2 (Purple) is 80 to 120Ω.
C. If the value measured is not in the range, please adjust with tools so that the
Potentiometer value measured can be in the range.
D. Please get the actuator „Full Open‟.
E. Please confirm if the resistance of both ends P1 (Orange) and P2 (Purple) at the
Potentiometer is 980Ω or lower.
F. When Full Open, if the resistance of both ends P1 (Orange) and P2 (Purple) is higher
than 980Ω as measured, the equipment may occur malfunction so Open CAM should
be adjusted.
2) IQL04~IQL25 & ITQ6000~ITQ9000 (Gearbox Type)
1) Please pull the HAND/AUTO Lever of the actuator to HNAD and then turn the handle CW
(Clockwise) so that the Valve/Damper will be Full Close.
2) Using wrench, please release the bolts for Close Limit CAM and then turn the „CLS CAM‟
clockwise or counterclockwise so that it is matched with the Limit Switch contact. And
then, exactly fix the bolts.
3) Please pull the HAND/AUTO Lever of the actuator to HNAD and then turn the handle
CCW (Counterclockwise) so that the Valve/Damper will be Full Open.
4) Using wrench, please release the bolts for Open Limit CAM and then turn the „OLS CAM‟
clockwise or counterclockwise so that it is matched with the Limit Switch contact. And
then, exactly fix the bolts.
2V ~ 10V 2V 10V
0V ~ 5V 0V 5V
1V ~ 5V 1V 5V
9. RPC LAYOUT
1) Model Selection
A. “Q” : Model “ITQ” (Quarter turn actuator)
B. “L” : Model “IQL” (Linear actuator)
2) Potentiometer Position Selection
A. QS or DA : Model “ITQ” (Quarter turn actuator)
However, except for ITQ6000~ITQ9000 Gear box
B. GL or RA : Model IQL (Linear actuator) & Gear box (ITQ6000~ITQ9000)
2) ITQ0100-70500-F (1PH)
A. Model : ITQ-0100 (100NM)
B. Incoming & Control Power :1PH, AC 110V / AC 220V, 50/60Hz
3) ITQ0160-70500-F (1PH)
A. Model : ITQ-0160 ~ ITQ-9000 (160NM ~ 9000NM)
B. Incoming & Control Power : 1PH, AC 110V / AC 220V, 50/60Hz
4) ITQ0160-80500-F (3PH)
A. Model : ITQ-0160 ~ ITQ-9000 (160NM ~ 9000NM)
B. Incoming Power : 3PH, AC 380~460V
C. Control Power : 1PH, AC 110V / AC 220V, 50/60Hz (Option : DC 24V)